SPLIT PASSIVE ENERGY RECOVERY HEAT PIPES
|
|
- Prosper Augustine Black
- 7 years ago
- Views:
Transcription
1 PRODUCTS SPLIT PASSIVE ENERGY RECOVERY HEAT PIPES HRM-V Series 6904 Parke East Blvd, Tampa, FL Tel: (813) Fax: (813)
2 Split Passive HRM-V Energy Recovery Heat Pipes Passive, No Moving Parts Bi-Directional or Single Season Heat Transfer Made with High Quality Copper Tubes for Reliability and Longevity Multiple Circuits for Enhanced Performance Optional Control Valves for Capacity, Defrosting, or Economizer Control Separate Liquid and Vapor Lines for Maximum Performance Flexibility in Dimensions and Configurations No Cross Contamination Between Air Streams Applicable to Retrofits and New Construction Site Completion by Factory Technicians HRMV-1
3 Split Passive HRM-V Energy Recovery Heat Pipes SYSTEM DESCRIPTION Heat Pipe Technology split passive (HRM-V) energy recovery heat pipes are an air to air heat exchange system designed to move heat from one air stream to another. Split passive HRM-V heat pipes provide economical and reliable recovery for summer only, winter only, or all season applications where supply and exhaust air streams are remotely located. These systems are designed for both process and comfort applications to pre-cool or preheat outside air using otherwise wasted heat from exhaust air. Natural thermosiphon is used to circulate refrigerant, from the supply air coil to the exhaust air coil where it changes phase from a liquid to a gas and back to a liquid. Because of this natural phase change unique to heat pipes, the HRM-V system can produce significantly higher heat transfer capabilities than a comparable water glycol system often yielding 40% or more. Best of all, because they have no moving parts HPT heat pipes require minimal maintenance and provide passive, reliable energy recovery. Construction Coil construction consists of tube and fin design with copper tubes and aluminum or copper fins. The coils are encased on top, bottom and sides with either galvanized or stainless steel casing for easy installation into air handling units or duct work. Headers are type L copper. Header size will vary based on the capacity of the coil. Each coil is divided into multiple circuits, to be piped in a counter flow arrangement, and individually charged for maximum heat transfer effectiveness. The tubes of the coil are configured vertically with fins oriented horizontally. The rows of tubes for each circuit are manifolded to a vapor header at the top of each circuit and a liquid header at the bottom of each circuit. Systems can be designed with two rows per header or one row per header depending on the performance requirements of the application. The HRM-V system can be configured with any amount of rows. However, a typical HRM-V heat pipe system will use 6-rows. Air pressure drop and fan power increase with each row. Coil depth is based on the number of rows. Figure 1 - Typical dimensions HRMV-2
4 Tubes ½-inch OD copper Fins aluminum or copper, sine wave pattern Casing galvanized, 304 stainless, or stainless steel Headers Type L, ACR copper, pipe sizes based on capacity Coil Sizing o Face Height maximum face height is 48 inches per coil for reasonable handling max performance and condensate management o Face Length maximum face length is 220 inches per coil Coatings For contaminated air streams or applications close to salt water protective coatings are strongly recommended. Figure 2 - Typical Dimensions Installation Configurations When installed on the same elevation, the HRM-V system can transfer heat in both directions making it ideal for summer and winter recovery. For installations where air stream is elevated, the HRM-V system can only transfer heat from the lower air stream to the higher air stream, therefore, limiting heat transfer to one season. HPT offers the following arrangements; A. Winter Only Recovery B. Summer Only Recovery C. Winter/Summer Recovery A. Winter Only Recovery When cooler outside air is above warmer exhaust air Maximum 100* ft equivalent horizontal separation Maximum 50 ft* equivalent vertical separation *Valves and elbows shorten this distance Figure 3 HRMV-3
5 B. Summer Only Recovery When warmer outside air is below cooler exhaust air Maximum 100 ft* equivalent horizontal separation Maximum 50 ft* equivalent vertical separation Figure 4 *Valves and elbows shorten this distance C. Winter/Summer Recovery When outside air is on the same elevation as exhaust air Maximum 40 ft equivalent horizontal separation *Valves and elbows shorten this distance Figure 5 HRMV-4
6 Comfort Energy Recovery HPT split passive energy recovery heat pipes can be used for comfort-to-comfort applications or for process applications. Comfort-to-comfort applications include heating only recovery for cooler climates, cooling only recovery for warm climates, or more often, both heating and cooling recovery. Split passive energy recovery heat pipe systems are being used for heating/cooling recovery from cold northern zones with harsh winters to the heat of more southern climates. Process Energy Recovery For process applications, heating/cooling recovery can also take place in either direction. Process applications frequently involve air temperatures elevated above normal room conditions. The heat pipes can be made to withstand temperatures up to 200 F. For air streams with corrosive components, the heat pipes can be provided with a protective coating. Heat pipes can also be fabricated with both fins and tubes made of copper. Design Considerations The HRM-V system allows for multiple coil sections to be utilized for applications with larger airflows. The HRM-V system design permits one supply coil to be used for each exhaust coil. Furthermore, supply and exhaust coils can be sized differently to handle unequal supply and exhaust airflows. Above in Figures 3-5 the different split passive energy recovery heat pipe orientations are shown. For maximum heat transfer, air streams must be piped in counter flow. Counter flow operation is where two air streams are arranged such that they flow in opposite directions through the heat pipe coils. If necessary, due to design considerations, the air streams may need to flow in the same direction through the heat pipe. In this case counter flow can still be achieved through connecting the liquid and vapor headers in a counter flow fashion. See Figure 6. Figure 6 - Counter flow piping Operation For an HRM-V system where coils are located on the same level, the system will transfer heat from whichever end is warmest in either direction. For a HRM-V system where the warmer airstream is lower, the system will transfer heat in one direction. Heat transfer is due to the entering air temperature difference and the latent heat of evaporization and condensation capabilities of the working fluid within the system. With a small difference in temperatures from one side to the other, a percentage of that difference is transferred to the other end. As the temperature difference increases, the difference in temperature across each end increases. Operation of heat pipes is automatic by refrigerant circulation and needs no further attention. The coils are fully pressure tested and will give many years of trouble-free operation. HRMV-5
7 System Control If it is desired to control the heat pipes off or throttle back the heat transfer, this can be achieved through optional control valves or bypass dampers for the HRM-V system. Modulating Control Valves - A control system with proportional valves for each circuit is available to control capacity. Advanced stepper modulating valves that manage the internal refrigerant flow and draw no power except when adjusting are available for frost protection and economizer operation. For heat recovery during the heating season, the leaving temperature of the exhaust air stream may be lowered to near freezing or below freezing. Such conditions normally result in the formation of frost on the exhaust side of the heat pipe with partial or complete blockage of the air stream. To remedy this situation, control valves can be installed in the liquid lines of each circuit. With all control valves open, the heat pipe system will operate at full capacity. With all valves closed no heat transfer takes place. The valves are equipped with over 3,000 steps each to modulate performance anywhere in between fully opened and fully closed positions. Closing valves in freeze protection mode ensures that the leaving temperature of the exhaust air stream is kept warm enough to prevent frost formation. As the leaving air (exhaust) temperature drops below 36 F, the valves should begin to modulate closed. The control valves must be controlled by the Building Automation System. The BAS can monitor the temperatures in and out of the coil and determine when to start modulating the valves. Control valves can also be used for capacity control, when outside air is suitable for direct cooling and will not need to be heated by the heat pipes. Figure 7 Example of 3 circuit, 3 valve, wiring diagram Face and Bypass Dampers Face and bypass dampers (provided and installed by others) can also be used for capacity, economizer or frost control. Bypassing the air around one end of the coil reduces the amount of air flow through that end of the coil, thereby reducing the heat that will be absorbed and transferred to the opposite side. In frost protection mode opening the bypass damper will reduce the heat transfer to a rate that will not cause frost to form while still transferring as much heat as possible. By monitoring the leaving air temperature from the exhaust heat recovery coil, frost can be prevented. Again, as the leaving air temperature drops below 36 F, the damper should modulate open and be fully open at 35 F. The damper actuator must be controlled by the Building Automation System in the building. The BAS can monitor the temperatures in and out of the coil and determine when to start opening the bypass. Heat transfer can be variably controlled with this method, thus modulating performance under economizer conditions or completely bypassing supply air to prevent frosting in extreme cold conditions. If space is available, dampers are recommended for economizer operation because bypassing air can provide hours of free conditioning in moderate weather and helps save on air pressure drop. Economizer operation is optional. HRMV-6
8 Control Strategy by Season Control of the split passive heat pipe heat recovery system shall be as dictated by needs such as frost control, and to perform energy transfer to fit the requirements of the specifications. The design engineer is responsible for providing the set points for operation. Controls are designed to allow the Building Automation System to interface and control the heat pipe circuits as required Summer Control During summer operation, all of the control valves can be opened whenever the outdoor air temperature or mixed air temperature, depending on design, rises above the temperature of the exhaust air stream. Typically, maximum heat pipe pre-cooling will be needed for summer recovery. Winter Control There are two common control strategies for winter operation with HRM-V split passive heat pipe systems. A simple approach is to control the stages of the system with outdoor air temperature, having a set point for each circuit. The second approach is to use the leaving air temperature of the air handler. This approach is more complex, but provides more precise control. For outdoor air temperature control, it will be necessary to estimate the outdoor air temperature at which the first call for heating in the building will occur. This temperature is typically around 50 F, but could be higher or lower depending on the construction of the building and the heat load. For example, with a 2 row circuit design using 50 F as a starting point, and 70 F exhaust, each stage on the heat recovery system will produce about 3-4 F of pre-heat. With a three circuit system, 3 set points will be needed. The first stage would need to come on at 50 F, the second at 47 F, and the third at 44 F. These set points can be adjusted during the first winter of operation to provide better accuracy. Another method of control is to use the leaving air temperature set point. As the temperature reaches and goes below set point, the three stages of heat recovery can be used as the first stages of heat. Again, each stage will add 3-4 F to the leaving air temperature, so a dead band and/or time delay, will have to be entered appropriately for each stage to prevent short cycling. Frost Control When outdoor temperatures approach 0 F, enough heat will be transferred from the exhaust coil to the supply coil so that frost formation may occur on the exhaust coil. The point at which this begins depends on the system, location, and the air flow through each coil. To control frost, the downstream temperature on the exhaust coil must be monitored. As the temperature of the exhaust coil approaches freezing the temperature of the air leaving the exhaust coil will follow by about 4 F. Valves should begin to close one circuit at a time. For example, with a three circuit system, at 36 F leaving the exhaust coil, the valve on circuit 1 should begin to modulate closed. If the leaving temperature again reaches 35 F, the valve on circuit 2 should begin to modulate closed and so on, until all valves are closed. Scope of Work Due to the split nature of the HRM-V system, a complete factory installation into an air handling unit is not always practical or feasible. More often the heat pipe coils are installed into air handling units, at HPT or at a manufacturer s facility, and then shipped to the project location where the remaining work is completed on site. Therefore, provisions should be made for field work by Heat Pipe Technology technicians and by a local mechanical contractor. Heat pipe coil installation is usually by the equipment vendor at the manufacturer s facility when systems are installed in air handling units. If practical, the air handling units can ship to HPT for factory coil installation at HPT s facility. Installation in duct work is typically by a local mechanical contractor. Below are guidelines for a standard scope of work involved for an HRM-V split passive heat pipe system installation. HRMV-7
9 Heat Pipe Technology - HPT will custom manufacture coils according to the design engineer s plans and specifications. Parts included shall be the exhaust and supply heat pipe coils, modulating stepper valves, and control box. Once the system has been installed and the air handlers are operational, a Heat Pipe Technology technician will travel to the project location and perform the following; verification of pressure test, evacuation of circuits, and charging. The HPT technician will inspect the system and installation to ensure there are no problems with the installation. HPT technicians will verify the pressure test that shall be left on the system by the mechanical contractor. Once verified to be leak free, each circuit will be evacuated and charged by the Heat Pipe Technology technicians with an amount of refrigerant to be calculated based on actual pipe lengths measured by Heat Pipe Technology technician. Due to variance from the estimated length the mechanical contractor may be required to supply additional refrigerant over the amount estimated. Equipment Vendor - The equipment vendor may be required to provide space and/or install the heat pipe coils within their air handling units. The equipment vendor shall be responsible for providing mounting hardware as well as drain pans and drain connections for removing condensate. Equipment Vendor or Mechanical Contractor - The equipment vendor or mechanical contractor shall be responsible for the installation of the heat pipe coils in the supply and exhaust air streams and/or the placement of air handling equipment containing heat pipe coils in a mechanical room according to the engineer s plan. The equipment vendor or mechanical contractor shall provide and install type L, ACR copper piping, fittings and valves between the coils, insulation for all exposed piping, condensate drains including appropriate traps for both coils, brazing equipment, and nitrogen for purge and pressure test per Heat Pipe Technology s specified pipe sizes and guidelines. The equipment vendor or mechanical contractor shall also provide the refrigerant to charge the system per Heat Pipe Technology s estimate amount plus any extra that may be needed due to changes in estimated piping lengths. Piping between the coils shall be run overhead and properly supported without creating traps as per Heat Pipe Technology drawings and guidelines. Brazing of the joints shall be with suitable silver brazing rod while purging the pipe with nitrogen. When the assembly of the piping is complete, the equipment vendor or mechanical contractor shall provide a pressure test with nitrogen of each circuit to 200 PSI. The pressure shall hold on the system for a period of at least 48 continuous hours before being read again. Pressure readings shall be made at a time of day and recorded to provide the same temperature on the system. After pressure testing, the access valves shall be shut and capped and the system left under pressure until verified by Heat Pipe Technology. The equipment vendor or mechanical contractor shall be responsible for repair of any leaks found by Heat Pipe Technology. The connecting piping shall not be insulated until the leak test is complete and approved by HPT. The equipment vendor or mechanical contractor shall have the refrigerant for charging available during the scheduled field work for use by Heat Pipe Technology. Drain Pans A drain pan is required to retrieve moisture from both supply and exhaust sides of the heat pipe coils. Intermediate drain pans are also required when heat pipes are installed in stackable sections. Due to the vertical orientation of the tubes, the fins are horizontal. Condensate does not drain to the bottom of the coil as it does with a conventional coil. The condensate can build on each fin until it is pushed away at the leaving face by airflow. Therefore, condensate management must be taken into account during the initial layout of the system. An extended drain pan that continues at least 3 feet past the leaving face of the coil is suitable for capturing condensate. For some applications where significant condensate is present, the coils may be tilted at an angle from the horizontal plane to help with condensate management. Filters To ensure a clean fin surface and optimal performance, suitable filters should be installed. Filter racks should be placed upstream of the supply and exhaust coils even if the exhaust is from clean indoor air. The types of filters should be compatible with the specific environmental conditions for a given application. It is recommended that inspection doors be installed adjacent to the heat pipe on both supply and exhaust sections. HRMV-8
10 Selection Criteria The effectiveness of the heat pipe system expressed in a percent is the ratio of the amount of heat transferred to the amount of heat available. This percent effectiveness will remain close to constant, unless there is condensation on the coil, regardless of indoor or outdoor conditions. The predicted effectiveness is calculated for a system based on the above design parameters. Several factors go into the effectiveness calculation and if these factors change the expected effectiveness can change. Construction variables such as difference in coil dimensions between supply and exhaust will affect the calculated effectiveness. Unequal airflows between the supply and the exhaust will also change the effectiveness. If there is more air through the supply end than the exhaust end, which is common with fresh air systems, then the temperature across the supply end, and the related effectiveness, will be lower than that across the exhaust end. More air flow on one side will reduce the effectiveness on that side by the ratio of the air flows. If BTUH for one side: 1.05 equals BTUH for the other side and no condensation is taking place, then the measurement variables can be considered accurate. Face velocity Air pressure drop Tube size Number of Rows Fin Type and Density Working Fluid Ratio of supply and exhaust airflows HRMV-9
11 Split Passive HRM-V Energy Recovery Heat Pipes Features Passive Operation No energy input is required to operate the heat pipes. When two air streams pass through the heat pipe, with one air stream through one coil and the other air stream through the other coil, the temperature difference between the two air streams activates the heat pipes and causes them to exchange heat. Heat pipe operation utilizes the heat capacity available when the working fluid changes phase, from a liquid to a vapor and back again. Because heat pipes use a phase change fluid, more heat transfer is achievable than with convection flow. Long Life There is nothing in the heat pipes to break or fail! They provide passive heat recovery where the only moving parts are the working fluid inside the tubes and the air to be treated. To guard against corrosion, the heat pipes can be ordered with a protective coating. No Cross Contamination Spilt passive energy recovery heat pipes are suitable for all applications, especially those where cross contamination is not acceptable. Airstreams can be located remotely with a horizontal and/or vertical separation to completely isolate hazardous exhaust from fresh intake air. Heat Pipe Technology also offers coatings and special materials of construction to protect coils from contaminated exhaust airstreams. Minimal Maintenance Since the heat pipes have no moving parts (except for optional dampers or control valves) no complex maintenance is needed. A periodic cleaning is the only required maintenance. A coil cleaner may be applied for this purpose just as for any cooling coil. Design Flexibility Split passive energy recovery heat pipes are custom designed for your particular application. Heat Pipe Technology s manufacturing processes offer variations in materials of construction, fin density, circuiting, working fluids, and configurations. And since split passive heat pipe systems are suitable for remote supply and exhaust airstreams, they provide more design flexibility for applications where large ductwork cannot be positioned side-by-side. HRMV-10
12 Split Passive HRM-V Energy Recovery Heat Pipes ENGINEERING SPECIFICATIONS Site or Factory Installed Energy Recovery Heat Pipes HRM-V Model with Modulating Control Valves 1.0 GENERAL Air Handler(s) Packaged Air Conditioning Equipment shall be equipped with Energy Recovery Heat Pipes supplied by Heat Pipe Technology, Inc. to transfer heat from the exhaust air to the incoming supply air. Supply and Exhaust heat pipe sections are separated horizontally a few feet on the same level or separated horizontally and vertically as specified. 1.1 CONSTRUCTION Coil tubes shall be oriented vertical and the fins run horizontal. One or two rows shall be manifolded together into one liquid line at bottom and one gas line at top and constitute one circuit. Lines shall be sized according to the performance requirements of the circuit. Each heat pipe section shall be installed level and connected to the other section by two horizontal copper lines, for each circuit, one for liquid and one for vapor. 1.2 OPTIONAL MODULATING CONTROL VALVE FEATURE All or a portion [SPECIFY] of the Heat Pipe circuits shall be equipped with modulating control valves to control the operation of the Heat Pipe circuits. Each circuit shall have one modulating step motor valve in the lower liquid line in an accessible location, between the two coils. Each valve will connect to a control printed circuit board in a NEMA box which also houses a 24 VAC transformer. Multiple circuit installations will have the several control boards in one NEMA box. The customer supplied electrical power to the control panel power supply transformer shall be: 120 VAC 208 VAC 230 VAC 1 phase 60 Hz. The NEMA box shall be located on the exterior or interior surface of the equipment cabinet as indicated or on a nearby surface. The Building Automation System shall provide the sensors necessary for determination of heat pipe modulation operation and the BAS computer shall be programmed to send the operating control signals to the modulating valves control boards as required for correct system operation. The control signal shall go through a BAS interface installed near the heat pipe NEMA box. The BAS control signal provided shall be 0 to 10 volt DC signal. HRMV-11
13 All additional wiring shall be provided and installed by others. With all control valves open, the energy recovery heat pipe assembly will operate at full capacity. Modulating one valve closed restricts the liquid return flow and reduces the heat transferred by the heat pipe until closing the valve shuts off that circuit. Frost control, if needed, is accomplished by closing or shutting off one or more circuits. Economizer operation is also accomplished by shutting off circuits to achieve desired heat transfer. 2.0 The Heat Pipe supplier shall have a minimum of 5 years of experience designing, manufacturing, and installing Heat Pipes specifically for split energy recovery applications. Heat pipes must be manufactured and assembled at the heat pipe supplier s own facility by supplier s own staff. 2.1 The tubes shall be copper only, of specific design for Heat Pipe application, permanently expanded onto the fin collar to form a firm, rigid, and complete pressure contact at all operating conditions. Aluminum tubes will not be allowed. 2.2 The fin surface shall be continuous plate type aluminum or copper fins of specific design to produce maximum heat transfer efficiency for Heat Pipe applications. Airside pressure loss shall be as given on the schedule, or otherwise specified. Fin density and the number of rows of tubes shall be as specified. 2.3 The Heat Pipe modules are available with an optional protective coating. 2.4 Heat transfer fluid shall be classified as Safety Group A1 in ASHRAE Standard Heat Pipe capacities, entering and leaving dry and wet bulb temperatures, and face velocity shall be as specified. 2.6 The Heat Pipes shall be installed as specified. 2.7 Frames and mounting structure shall be minimum 20 gauge galvanized steel or stainless steel. 2.8 Heat Pipe interconnecting piping and circuitry shall be as specified by Heat Pipe Technology design. Each circuit shall be individually processed, charged, hermetically sealed, and tested. 2.9 The heat pipe system shall be pressure tested on site under the supervision of the manufacturer s crew. Manufacturer s crew shall vacuum and charge the system. Vacuuming and charging by parties other than the manufacturer s own crew shall not be acceptable. HRMV-12
14 Split Passive HRM-V Energy Recovery Heat Pipes INSTALLATION LIST Recent Installations State City Location Alberta Edmonton Edmonton Clinic St. Albert Fountain Park Recreation Centre Colorado Colorado Springs Valor Gym Denver Data Center Florida Orlando VA Affairs Gainesville UF Pathogen Idaho Idaho Falls Idaho National Laboratory Illinois Waukegan Lake City Permit University Park Governors State University Indiana South Bend Notre Dame Innovation Park Maryland Germantown Montgomery College Fairfax Fairfax City Hall Towson Towson University Massachusetts Chatham Chatham WWTP Minnesota Hinckley Hinckley Elementary School Nebraska Lincoln McPhee Elementary School Lincoln Whittier Building New York New York City PS 276 North Carolina Kings Mountain Infocrossing Data Center Chapel Hill University of North Carolina Locker Room Greenville Vector Mau North Dakota Grand Forks University of North Dakota Dorms Ohio Columbus Franklin County Courthouse Ontario Scarborough St. Sylvester School Pennsylvania Mansfield Mansfield University Tennessee Franklin Franklin Police Department Texas Houston Lone Star College Virginia Charlottesville University of Virginia IRDF Washington Lynnwood Edmonds Community College Seattle Madrona Pathfinder Elementary School Seattle James Monroe Elementary School Seattle Hawthorne Elementary School Wisconsin Wausau Wausau School District Wyoming Laramie University of Wyoming Berry Center HRMV-13
15 Split Passive HRM-V Energy Recovery Heat Pipes QUICK SELECT Manual selection procedure below is meant to be a guideline for the design engineer. Selections for this product are to be completed by an HPT applications engineer. The following procedure is an abbreviated method for roughly selecting a split passive energy recovery heat pipe. All determinations are for supply CFM equal to exhaust CFM with 450 FPM face velocity, and 12 fins per inch. Working fluid is R-410a. Exhaust entering air temperatures are indoor dry bulb temperatures of 78 F summer and 70 F winter. Air pressure drop is 0.53 in. WG or less for each side. Split passive energy recovery heat pipe standard sizes are given in Table HR01. For summer performance quick select, turn to Table HR02A. Find the outdoor dry bulb/wet bulb temperatures in the left column. Choose a number of rows of the Heat Pipe between 4 and 8 (most frequently used is 6). Read the performance under the column with the number of rows of Heat Pipe. The performance data given are leaving air temperatures of supply and exhaust, and Btuh per 1000 CFM. Select a heat pipe size from Table HR01. If a satisfactory standard size cannot be found in Table HR01, you may devise a custom size. The face length should be a multiple of 1.25 inches. If the CFM's of the air flows are within 25% of each other, sizing coils so that face velocities are equal will have little effect on the thermal performance of the heat pipe, but will equalize the air pressure drops on each side of the system. The fan power required can be calculated as.. If Motor Eff. = 0.9 and Fan Eff. = 0.75, then For winter performance quick select, use Table HR02B. Table HR01 - ENERGY RECOVERY HEAT PIPE SIZES Number of Rows Supply Face Height (in.) Exhaust Face Height (in) Supply Face Length (in.) Exhaust Face Length (in.) 300 FPM 350 FPM CFM per Side 400 FPM 450 FPM 500 FPM 550 FPM HRMV-14
16 Table HR02A - QUICK SELECT - SUMMER COOLING RECOVERY* Condition: Face Velocity: Exhaust EAT: Pressure Drop: 450 FPM 78 F DB/65 F WB (50% RH) 0.53 in. WG (each side for standard fins) Read the table as follows: F DB/ F WB - Supply LAT. F DB/ F WB - Exhaust LAT. Btuh per 1000 CFM. For example, Outside Supply EAT 95 F DB/76 F WB) with 4 rows: 89.6 F DB/74.6 F WB Supply LAT 83.5 F DB/66.8 F WB Exhaust LAT 6,027 Btuh per 1000 CFM Outside Supply EAT ( F DB/ F WB) Number of Rows Cooling 105/ / /67.8 9, / / , / / , / / /67.3 7, / / , / / ,809 95/ / /66.8 6, / /67.3 7, / /67.7 9,127 90/ / /66.3 4, / /66.6 5, / /66.9 6,443 85/ / /65.7 2, / /66.0 3, / /66.1 3,757 80/ / / * Two rows per circuit configuration 79.2/ / / /65.3 1,073 HRMV-15
17 Table HR02B - QUICK SELECT - WINTER HEATING RECOVERY Condition: Face Velocity: Exhaust EAT: Pressure Drop: Outside Supply EAT ( F DB/ F WB) 65/61 60/56 55/51 50/46 45/42 40/38 35/33 30/29 25/24 20/19 15/14 10/9 5/4 0/0 450 FPM 70 F DB/55 F WB (32% RH) 0.53 in. WG (each side for standard fins) Number of Rows / /54.4 1, / /53.7 3, / /53.0 5, / /52.3 7, / /51.7 8, / / , / / , / / , / / , / / , / / , / / , / / , / / ,542 Heating 67.1/ /54.2 2, / /53.3 4, / /52.4 6, / /51.5 9, / / , / / , / / , / / , / / , / / ,657 38/ / , / / , / / , / / , / /54.0 2, / /53.0 5, / /52.0 7, / / , / / , / / , / / , / / , / / , / / , / / , / / , / / , /25.8* 38.9/ ,820 Tow rows per circuit configuration. *Theoretical exhaust LAT only. Provision must be made for frost control such that leaving dry bulb temperature 36 F. Frost control can be accomplished with HPT optional control valves or site installed bypass dampers. HRMV-16
18 Split Passive HRM-V Energy Recovery Heat Pipes Selection Procedure for Non-Condensing Air Flows Manual selection procedure below is meant to be a guideline for the design engineer. Selections for this product are to be completed by an HPT applications engineer. Shown below is a split passive energy recovery heat pipe with counter flow air streams. The symbols T1, T2, T3, and T4, when used in the equations below, are the dry bulb temperatures, in F, at the various points, 1, 2, 3, or 4 as shown in Figure 8. When not used in an equation, the symbols may refer to both the dry bulb and wet bulb temperatures, FDB/ FWB. Airflow No. 1 refers to the supply airflow entering dry bulb temperature. Airflow No. 3 refers to the exhaust airflow entering dry bulb temperature. Airflow No. 1 has an entering dry bulb temperature of T1. Airflow No. 3 has an entering dry bulb temperature of T3. Airflow No. 1 has a flow rate of SCFM1 standard cubic feet per minute. Airflow No. 3 has a flow rate of SCFM3 standard cubic feet per minute. If the flow rates are initially given as actual cubic feet per minute (ACFM), then convert them to SCFM (standard cubic feet per minute) using the following formula: 530/ where T refers to the entering dry bulb temperature in F or, more accurately, to the average temperature of the air flows, for the warmer air stream or for the cooler air stream, if T2 and T4 are known. Calculate the air flow ratio. State the required value of T2 and/or T4. where SCFMmin is the smaller of SCFM1 and SCFM3. Calculate the required temperature effectiveness. 1 Figure x 1 HRMV-17
19 Go to Table HR03. Select a combination of Face Velocity and No. of Rows at the calculated value of M that gives the desired Recovery Factor, R. When a face velocity has been selected, the heat pipe face height, FH, and face length, FL, may be selected. The face height and length for each coil are the dimensions for the face (finned) area not including casing and header dimensions. Face height is the finned dimension is the vertical direction and face length is the finned dimension is the horizontal direction. Supply and exhaust coils can have different face dimensions. For selection convenience, Table HR01 gives a number of sample sizes from which to choose. If a satisfactory size cannot be found in Table HR01, you may devise a custom size. The face length should be a multiple of 1.25 inches. If the supply and exhaust air flows are within 25% of each other, sizing coils to make the face velocities equal will have little effect on the thermal performance of the heat pipe system, but will cause a higher maximum pressure drop on the side with the larger airflow. Determine the pressure drop, P, from Table HR04. The fan power required can be calculated as If Motor Eff. = 0.9 and Fan Eff. = 0.75, then. / / 5752 Now check to see if there is condensation in the warmer air flow. If there is condensation, the performance will be different. To check if there is condensation, use the psychrometric chart on page 19. First plot FDB/ FWB for T1. Then draw a horizontal line to the left of T1 to the saturation line. The temperature at the saturation line is T1DP, the dew point temperature for the warmer airflow. If the calculated value of T2 (dry bulb) is less than T1DP, then there is condensation. If there is condensation, the HPT HRM-V energy recovery selection software should be used. Please contact factory for help with selection. HRMV-18
20 HRMV-19 HRMV-19 Figure 9 - Psychrometric chart
21 Table HR03 - ENERGY RECOVERY HEAT PIPE EFFECTIVENESS* Copper 1/2 in. O.D. tubes, Aluminum standard fins, 12 fins/in. SCFM1 / SCFM3 M = 0.75 M = 1.00 M = 1.25 M = 1.50 Face Velocity Number of Rows (ft./min.) * Two rows per circuit configuration Table HR04 - ENERGY RECOVERY HEAT PIPE AIR STATIC PRESSURE DROP For each side of dry Heat Pipe (in WG) Copper 1/2 in. O.D. tubes, Aluminum standard fins, 12 fpi Face Velocity Number of Rows (ft./min.) HRMV-20
22 Split Passive HRM-V Energy Recovery Heat Pipes Data Gathering Worksheet Company: Phone: Fax: Job Name: Model #: Serial #: Test performed by: Date: Heat Pipe Orientation Exhaust below supply (winter only) Supply below exhaust (summer only) Winter and summer recovery Test Data Summer / Cooling Winter / Heating Temperature* Temperature* APD* Airflow* (F DB) (F WB)* (in of H 2 O) (CFM) Temperature* (F DB) Temperature* (F WB) APD* (in of H 2 O) Airflow* (CFM) 1 Air Side Description Number of Rows Supply Dimensions Exhaust Dimensions Describe Frost Control Scheme: in. Face Height in. Face Length Misc. Air filters clean? Yes No Yes No Condensate drain installed? HRMV-21
23 * Multiple readings up and down & side to side should be taken and then averaged out. Split Passive HRM-V Energy Recovery Heat Pipes (Heat Exchangers Only) Five-Year Limited Warranty Subject to the following conditions, Heat Pipe Technology, Inc. (HPT), warrants this product to be free from defects in material and workmanship for a period of FIVE YEARS from the date of installation but not to exceed 90 days from date of shipment for the heat exchangers only and 12 months for HPT supplied control valves and control box. This warranty is in lieu of all other warrants not expressly set forth herein, whether expressed or implied by operation of law or otherwise. In the event this product fails under normal use and service within the applicable period, HPT will correct, repair or, at its sole discretion, replace the defective product or refund the purchase price of products which are returned freight prepaid to HPT for inspection, when accompanied by proof of purchase and written claims of defect, and which upon inspection by HPT, do comply with the terms of this warranty. This warranty applies to the first retail buyer and extends to any subsequent owners of the systems. The cost of replacement parts or components shall be determined by the price schedule in effect at the time of submission of warranty claim. Repair or replacement parts will be furnished F.O.B. factory in all cases. If HPT elects to replace or provide a refund, the defective product must be returned to HPT free and clear of liens or other encumbrances. This warranty does not cover and no warranty is made with respect to: Limitations on Liability A. Failures not reported to HPT within the period specified above; B. Failures or damage due to misapplication, misuse, abuse, improper storage or handling, abnormal conditions of temperature, water, dirt, corrosive substances or other contaminants; C. Products which have been repaired with parts or materials not furnished or approved by HPT or by its authorized dealers or representatives, or products which have been in any way tampered with or altered; D. Products damaged in shipment or storage or otherwise without fault of HPT; E. Normal maintenance as outlined in the installation and servicing instructions or owners manual including coil cleaning, filter cleaning and periodic flushing of systems; F. Damage or repairs required as a consequence of faulty installation or application by others; G. Damage or repairs required as a consequence of any misapplication, abuse, improper servicing, unauthorized alteration or improper operation; H. Damage as a result of floods, winds, fires, lightning, accidents, corrosive atmosphere or other conditions beyond the control of HPT; I. Damage resulting from freezing of domestic water or condensate, inadequate or interrupted water supply, use of corrosive water, fouling or restriction of the water circuit by foreign material or like causes; J. Damage resulting from operation with an inadequate supply of air or water; K. Dampers or other mechanical options. HPT total responsibility for any claims, damages, losses or liabilities related to the product covered hereunder shall not exceed the purchase price of such product. In no event shall HPT be liable for any special, indirect, incidental or consequential damages of any character, including but not limited to loss of use of productive facilities or equipment, lost profits, property damage, transportation, installation or removal, lost production, or personal injury whether suffered by Purchaser or any third party. HPT disclaims all liability for any and all costs, claims, demands, charges, expenses or other damages, either direct or indirect, incident to personal injury or property damage arising out of any cause of action based on strict liability. Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the exclusion or limitation above of consequential damages or the limitation of time above on implied warranties may not apply to you. This warranty gives you specific legal rights and you may have other rights which may vary from state to state. HRMV-22
24 Split Passive HRM-V Energy Recovery Heat Pipes (Coils Only) Warranty Registration To insure your warranty protection, please fill in the Warranty Registration Form and mail or fax it to: Heat Pipe Technology, Inc Parke East Blvd, Tampa, FL Fax: (813) Customer Name: Customer Address: WARRANY REGISTRATION FORM Phone: ( ) - Fax: ( ) - Please check one: Homeowner Serial No: Model No: Dealer Type of Product: Date of Installation: Dealer/Installer: Name & Address of Dealer/Company You Purchased from Name: Address: Customer Signature: HRMV-23
COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here.
COIL INPUT SCREENS Example of a Water Coil Input Screen: (*please see the appendix for an example of an Evaporator, Steam or Condenser Coil input screen) PHYSICAL DATA ITEM NUMBER: Always use a 1 through?
More informationCeiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationInnovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
More informationSECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
More informationDr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
More informationUSER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
More informationM SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
More informationCE6500 Energy Recovery Ventilator
ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge
More informationBring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
More informationDC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL Service Information If service or parts are required, contact the nearest Norcold Service Center. To find an authorized Norcold Service Center
More informationSteam Coil Installation, Operation and Maintenance
Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils manufactured by Luvata in Grenada, MS have been
More informationContents and Nomenclature
DX Coils Contents and Nomenclature Nomenclature... 1 Evaporator Coil Types EN... 2 EF... 2 ER... 2 EJ... 3 EK... 3 Evaporator Construction Connections... 4 Tubing... 4 Headers... 5 Tube Supports... 5 Coil
More informationName of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationDehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
More informationSun Vinyl New Construction Windows Homeowner's Warranty
Sun Windows Sun Vinyl New Construction Windows Homeowner's Warranty Vinyl Sun Windows, Inc. warrants for a period of 2 years that the quality of workmanship and materials of vinyl items shall be free from
More informationHome Owners Guide HR SERIES HEAT RECOVERY VENTILATOR (HRV) Models HR100V, HR160H & HR220H RESIDENTIAL USE ONLY HR160H & HR220H
HR SERIES HEAT RECOVERY VENTILATOR (HRV) Home Owners Guide Models HR100V, HR160H & HR220H RESIDENTIAL USE ONLY HR100V HR160H & HR220H READ AND SAVE THIS GUIDE PP0924 09/2013 ABOUT S&P S&P is the world's
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationAIR CONDITIONING TECHNOLOGY
AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air
More informationDefining Quality. Building Comfort. Heating and Cooling Coils
Defining Quality. Building Comfort. Heating and Cooling Coils Heating and Cooling Coils Heating and Cooling Coils For over 20 years, AAON has supplied the coil needs of industrial and commercial HVAC customers.
More information543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
More informationWARRANTY CERTIFICATE Please complete the following details and retain with the original purchase docket
WARRANTY CERTIFICATE Please complete the following details and retain with the original purchase docket TERMS OF WARRANTY AIR CONDITIONERS Australia & New Zealand AHI-Carrier (Australia) Pty Ltd 34-40
More informationService & Parts Manual
Service & Parts Manual Portable Air Conditioner Models P09B and P2B ( Serial Number Beginning with an "A") Models P09B-A and P2B-A Portable Air conditioner-200 Svc Parts (4-200) Service Points and Flow
More informationSolar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...
Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system
More informationMold Alert... Operation Manual P0270
Mold Alert... Operation Manual P0270 introduction Congratulations on your purchase of the P0270 Mold Alert! Mold is as old as the Earth and it s everywhere. Under the right set of conditions, it can actually
More informationTODAY S PARADIGM FOR AIR TO AIR HEAT RECOVERY
Tom Brooke, April 11, 2012 TODAY S PARADIGM FOR AIR TO AIR HEAT RECOVERY INTRODUCTION Technology advances! Just as commercial and industrial HVAC controls, chillers, and unitary equipment are constantly
More informationChilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
More informationOWNER S Manual PRINTED IN CANADA 10/2009
OWNER S Manual PRINTED IN CANADA 10/2009 Table of contents Introduction 2 General Safety Instructions 4 Installation Instructions Location 6 Water piping 7 Electrical 7 Bonding 8 Bonding and plumbing
More informationInstallation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK Safety Instructions Installation Warranty IN-LINE SERIES: 2-5 & 7 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON VERTICAL SERIES: 14-20-32-36-52-86-96-119 GALLON KEEP
More informationSECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
More informationSECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
More informationInstallation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationWhat you can expect from your Solar Hot Water System
Owner s Manual Your Solar Hot Water System Thank you for your investment in the FAFCO Solar Hot Water System. Since 1969 our goal has been to design, test, and produce solar heating systems that save you
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationAPC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
More informationWMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler
WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility
More informationGlossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
More informationPool Dehumidification Basics
Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing
More informationLesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
More informationINSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
More informationComparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
More informationOverview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
More informationAluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03
Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cooling Coil Nomenclature 4 C X C B 0 3 6 C C 3 C U A A Refrigerant Type 4 - R410A Product Family T-Premium (Heat Pump or Convertible
More informationAir Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationAABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
More informationMechanical Rooftop Custom Capabilities
Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition
More informationENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
More informationHow To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
More informationAnswers to Your Questions from the Webinar
2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in
More informationControlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015
Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed
More informationINSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER Dehumidification The highly efficient Ultra-Aire 100V dehumidifier utilizes refrigeration to cool the incoming air stream
More informationAir Conditioning Systems Warranty Manual. Version 1.8
Air Conditioning Systems Warranty Manual Version 1.8 1/2015 Air Conditioning System Warranty Contents Purpose 4 External Distribution... 4 Policies 5 Warranty Policy Overview... 5 Warranty Period... 5
More informationCharacteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
More information1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
More informationINSTALLATION, OPERATING AND SERVICE INSTRUCTIONS
INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS HEAT-FLO HOT WATER STORAGE / BOOSTER TANKS MODELS 30-ST, 40-ST, 40L-ST, 60-ST, 60L-ST, 80-ST, 115-ST, 80-ST-C, 115-ST-C FOR SINGLE TANK INSTALLATIONS For
More informationLH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_001_071015. Products that provide lasting solutions.
LH and GH/GL Series UNIT COOLERS Technical Bulletin: LHGH_001_07101 Products that provide lasting solutions. LH Series Unit Coolers Dual Discharge Low Hite Series At 9 1/ maximum height, the LH Series
More informationTECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES
TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S NATURAL GAS 40-130 MBH INPUT Due to continuous product improvement, specifications are subject to change
More informationCOMMERCIAL WARRANTY. www.daikincomfort.com
COMMERCIAL WARRANTY Who Is Providing The Warranty? This warranty is provided to you by Daikin North America LLC ( Daikin ), which warrants all parts of this heating or air conditioning unit, as described
More informationCased/Uncased Coils For Gas And Oil Furnaces
Indoor Coils Cased/Uncased Coils For Gas And Oil Furnaces RCFL- Series featuring Industry Standard R-410A Refrigerant Airflow Capacity 600-1,900 CFM [283-897 L/s] Rheem Indoor Coils are designed for use
More informationService Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007
Service Guide Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines ORDER No: UN-SVG001A-EN DATE: October 9, 2007 Introduction This document defines American Standard and Trane s recommendations
More informationTotal Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
More information10 YEAR WARRANTY REGISTRATION PROCEDURES. Please see product warranty section in back of book for registration procedures
10 YEAR WARRANTY REGISTRATION PROCEDURES Please see product warranty section in back of book for registration procedures Carrier Systems are eligible for 10 YEAR Warranty Coverage when registered! Important
More informationNSN 4120-01-21 4-3692
*TM 9-4120-388-14 TECHNICAL MANUAL Operator s, Unit, Direct Support, And General Support Maintenance Manual AIR CONDITIONER, VERTICAL, COMPACT, 18,000 BTU/HR 208 VOLT, 3 PHASE, 50/60 HERTZ NSN 4120-01-21
More information12V Portable Diaphragm Compressor Operating and Maintenance Instructions
12V Portable Diaphragm Compressor Operating and Maintenance Instructions (Part No. DC2) Part No. Serial Number Date Purchased Table of Contents Page Safety Messages...2 Guidelines for Product Use...2 Operation
More informationMUELLER FALLING FILM CHILLERS
MUELLER FALLING FILM CHILLERS MUELLER FALLING FILM CHILLERS ARE DESIGNED TO COOL ANY FLUID TO WITHIN 2 F OF ITS FREEZE POINT. The primary application for Mueller s falling film chiller is to cool food-grade
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationSelect Radiators Installation Guide
Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall
More informationSWIMMING POOL AIR-HANDLING UNITS KU-DB Series
SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =
More informationDESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
More informationEnergy Recovery Ventilation Equipment
AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not
More informationOperation and Installation Manual. Max Series
Operation and Installation Manual Max Series Models 95MAX 155MAX 155ECM 155MAXRX 200MAX 200MAXRX MAXTOP 195DCS 300DCS 200ERV 200ERVD New Auto Dehumidistat Function prevents unwanted use of the dehumidistat
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
More informationPropane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
More informationAmerican Fireglass Outdoor Fire pit kit information. General instructions/warnings for outdoor gas pan and burner systems
American Fireglass Outdoor Fire pit kit information General instructions/warnings for outdoor gas pan and burner systems We strongly recommend that our burner products be installed by a licensed and certified
More informationMassachusetts COOL SMART. RESIDENTIAL CENTRAL AC/DUCTED AIR SOURCE HEAT PUMP Rebate Application
Massachusetts COOL SMART 2015 RESIDENTIAL CENTRAL AC/DUCTED AIR SOURCE HEAT PUMP Rebate Application COOL SMART CENTRAL AC/HP PROGRAM COOL SMART is a residential central air conditioning rebate program
More informationNewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE
More informationDTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual
DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR Installation and Operation Manual 1 ENGLISH Safety Instructions 2 Features 2-3 Specifications 3 Installation 4-5 Wiring Diagrams 6-7 Warranty 8
More informationNewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationPlease read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3
More informationTimer Fan Speed. Mode. Power 93061000_0
Mode 93061000_0 Timer Fan Speed Power For inner cleaning, contact an Authorized Service Center or a dealer. Do not use harsh detergent that causes corrosion or damage on the unit. Harsh detergent may
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
More informationMULTIZONE APPLICATION OF SOLUTION UNITS
MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages
More informationTom Brooke, PE, MBA, CEM tabrooke@embarqmail.com
Tom Brooke, PE, MBA, CEM tabrooke@embarqmail.com Framework, perspective or example in a particular discipline at a given time These four new models are: New and additional, or Updated Today's Paradigm
More informationUsing Portable Spot Air Conditioners in Industrial Applications
Using Portable Spot Air Conditioners in Industrial Applications Cooling People, Processes and Equipment In today s highly competitive manufacturing sector, companies are constantly looking for new ways
More informationInstaller s Guide 18-AH39D1-13
18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,
More informationFrequently Asked Questions Generators
Frequently Asked Questions Generators Fuel Related How much fuel do the generators use during normal operation? At exercise? The generator fuel consumption is given in each of the product knowledge books
More informationBottom Loading Water Dispenser
Bottom Loading Water Dispenser Model # 601000 TO REDUCE THE RISK OF INJURY AND PROPERTY DAMAGE, USER MUST READ THIS MANUAL BEFORE ASSEMBLING, INSTALLING & OPERATING DISPENSER. SAVE THIS MANUAL FOR FUTURE
More informationSWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
More informationHow To Warranty A Car From Nordyne
Warranty Program NORDYNE offers an Expressed (Limited) Warranty on all products that it manufacturers and/or sells. This warranty is extended to the end user (Consumer) of the product. The warranty is
More informationLOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
More informationCooling/Heat Pump Convertible Air Handlers
Cooling/Heat Pump Convertible Air Handlers 2/4TEC3F18-60A1000A 1½ 5 Ton PUB. NO. 22-1774-01-0905 (EN) Features and Benefits 13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way
More informationUltraviolet Germicidal Lamps Owner s Manual MODELS 1910 & 1930
Ultraviolet Germicidal Lamps Owner s Manual MODELS 1910 & 1930 WARNING Ultraviolet light is harmful to eyes and skin. Never look at light produced by this lamp. Unplug lamp before servicing. Electrical
More informationSPACE COOLERS. P.O. Box 956 Paoli, PA 19301 (800) 523-7590 FAX (610) 251-0805 www.coilcompany.com. The leader in packaged Space Cooling.
SPACE COOLERS P.O. Box 956 Paoli, PA 19301 (800) 523-7590 FAX (610) 251-0805 www.coilcompany.com The leader in packaged Space Cooling. 2 Table of Contents Description Space Cooler from Coil Company. A
More informationRGC-IR Remote Gas Calibrator for IR400
Remote Gas Calibrator for IR400 The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized in writing by
More informationDBF 4XL Dryer Booster Fans
Installation and Operation Manual Item #: 401315 Rev Date: 121514 DBF 4XL Dryer Booster Fans DBF4XL Kit Includes: Dryer Booster Fan, 1 pc Fan Mounting Bracket and Hardware, 1 pc Wall Label (Mount on wasll
More information