TECHNICAL DATA. important to control accidental water discharge due to inadvertent damage to the sprinkler

Size: px
Start display at page:

Download "TECHNICAL DATA. important to control accidental water discharge due to inadvertent damage to the sprinkler"

Transcription

1 Preaction 329a 1. Description The System with Electric Release can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction System with Electric/Pneu-Lectric Release. These preaction reaction systems are commonly used where it is important to control accidental water discharge due to inadvertent damage to the sprinkler piping. small p p ig ig lig ig pilot pi op p Viking i ing comp p as shown in Figure 8. This pilot operated externally reset valve also includes an internal check diaphragm, which eliminates the need for a separate check valve being installed in the system riser. A. Viking Supervised Single-Interlocked Electric Release Preaction Systems Utilizing the Viking G-3000P Valve The system piping is pressurized with air or nitrogen as required by NFPA 13 for sup isory purp only. Viking n a minimum of 15 to 20 SI (1.0 to 1.4 bar) for sup isory air p u for sing in sy ( f to Tab 2 for ub interlock systems). This feature serves to prevent undetected leaks on the system piping network. If the system piping or a sprinkler is damaged, the supervisory pressure is reduced and a low air supervisory alarm is activated. E ically p ion sy qui a 24 VDC normally ic solenoid valve controlled by an approved release control panel with compatible detection sy. In con ition n ion sy op sy control panel energizes the solenoid valve open. When the solenoid opens, the priming water is relieved from the internal prime chamber bly. pri chamb bly collap an p through an in nal iaphragm to sy piping n. nti sprin sy fills with. sprin piping will in with until a sprinkler operates. B. Viking Supervised Double-Interlocked Electric/Pneu-Lectric Release Preaction Systems Utilizing the Viking G-3000P Valve The system piping is pressurized with air or nitrogen to serve both as a means of supervising the integrity of the piping network and as one portion of the system release operation. This feature serves to prevent undetected leaks on the system piping network. If the system piping or a sprinkler is damaged, the supervisory pressure is reduced and a low air supervisory alarm is activated. 24 DC VDC n y normally i electric i n i solenoid n i n and n n an n additional i i n i i n low air i i alarm switch i i are connected nn nn to a compatible p ib p ib release control panel and compatible detection devices. The release control panel is programmed so that a signal from both a release device and the low air alarm switch must be received before the solenoid is allowed to open. The air pressure switch has two independently operating connections. The high side is wired as a low air supervisory switch, and the low side is wired as low air alarm. In con ition a ion i and the low air alarm switch must operate in order to open the solenoid valve. When noi op n priming is i from s in nal pri chamb bly. pri chamb bly is f op n by sy supply an p through an in nal iaphragm to sy piping n. nti sprin sy fills with. 2. Listing and Approvals culus Listed: VLFT FM Approved: Preaction Sprinkler Systems 3. Technical data Viking nical Data may b foun on Viking Corporation s W b si at The Web site may include a more recent edition of this Technical Data Page. Specifications: u Rating: 250 SI (17.2 Bar) W Working u Factory Hy ically to: 500 SI (34.5 bar) Friction Loss (Gi n in f of S u 40 pip b on Haz n & Williams formula: C = 120): M : 17.3 Q= C v P S 12 S ion of ip : 1 Q= Flow W Supply Control : 10 C M C v Factor: 225 v = Flow Factor ( M/1 SI ) Color: Black = u Loss through Material Specifications: Refer to Figure 11. S= Sp ific Gravity of Flui Form No. F_ R p pag 329 July (R i the replacement parts list and Figure 11.)

2 Preaction 329b December 2, 2011 Table 1 - Pipe Capacity for Sizing Air Compressors Pipe Diameter Capacity Schedule 40 (1 to 6 ) US International Schedule 30 (8 ) Schedule 10 Gal / Ft L / m Gal / Ft L / m 1 DN /4 DN /2 DN DN /2 DN DN /2 DN DN DN DN DN For M ic Units 1 Ft. = M 1 Gal. = 3.785L Ordering Information: Available since 2010 Part Number: Electric Release Preaction System Riser Assembly (R f to Figu 8.) Accessories: (S Figu 9.) Drain Manifold: M E-1 A : M LD-1 Anti-Column D i : Installation: A. General Installation Instructions 1. For proper operation and approval, the valve must be installed in the vertical position as trimmed from the factory. DO NOT modify the factory assembled trim except as described in this technical data sheet. 2. A 12 section of pipe is provided with the G-3000P Electric Release Preaction System Riser Assembly. Prior to valve maintenance, this section of pipe may be removed to provide clearance for lifting the cover from the body. 3. must b in in an not subj to f zing p u or physical g. If qui provi a hou ( nclosu ) with qu aroun an trim. F zing p u will g. W n corrosi atmosp an /or contamin suppli p n it is own s ponsibility to ify compatibility with M an associ quip nt. 4. Viking M E-1 A shou b in at location in i in Figu 1 n qui. N : would only be used for double interlock systems. B. Air Supply Design 1. Air Comp Siz Viking n a minimum of 15 to 20 SI (1.0 to 1.4 bar) of sup isory p u b bli within piping n for sing in sy ( f to Tab 2 for ub in sy ). Whi p u by NF A 13 for sing in p ion sy maintaining hig air p u within sy will assist main nan p nn in fin ing and isolating inadvertent or accidental leaks within the system quickly. NF A 13 qui that air supply b capab of filling nti sprin sy to its qui air p u within 30 minu. A common method of sizing an air compressor is to use the following formula: Comp Siz (cfm) = V x 7.48 x 14.7 x T Where: V = Volu = R qui Air u T = Fill ti (typically 30 min.) 7.48 = gal. / ft = atmosp ic p u f comp shall b capab of provi ing 5 cfm. Table 2 - Air Pressure Settings For Systems with Tank Mounted Compressors: Air Maintenance Device Air Pressure Supervisory Switch Low Air Alarm Switch Table 3 - Quick Reference Compressor Size Compressor Size (HP) Single Interlock Free 40 PSI (2.8 bar) (cfm) Max System Size to Pump to 40 PSI (2.8 bar) in 30 Minutes (Gal) 1/ / / Double Interlock 20 SI (1.4 bar) 30 SI (2.1 bar) 15 SI (1.0 bar) 25 SI (1.7 bar) SI (1.4 bar) For Systems with Riser Mounted Compressors: Comp On/Off Switch Air Pressure Supervisory Switch Low Air Alarm Switch 15 SI (1.0 bar) / 25 SI (1.7 bar) 30 SI (2.1 bar) / 40 SI (2.8 bar) 10 SI (0.7 bar) 25 SI (1.7 bar) SI (1.4 bar) Example: Sy volu as in by tab 1 = 750 gallons R qui Air p u = 20 SI (1.4 bar) (Sing In System) (750 x 20) Comp Siz (cfm) = = 4.5 cfm 7.48 x 14.7 x 30

3 Preaction 329c Figure 1 - Air Supply Options

4 Preaction 329d December 2, 2011 Figure 2 - Alarm Pressure Switch Wiring (Alarm u Switch shou b to 5 SI (0.34 bar) Single Interlock Double Interlock Figure 3 - Air Supervisory Switch Wiring FIELD ADJUSTMENTS: Alarm Pressure Switch: The operating point of the switch can be ju to any point b n 4 SI (0.27 bar) an 8 SI (0.55 bar) by turning ju nt knob(s) clockwi to rai actuation point or counter-clockwise to lower the actuation point. Air Supervisory Switch: The operating point of the switches can b ju to any point b n 10 SI (0.7 bar) an 60 SI (4.1 bar) by turning ju nt knob(s) clockwi to rai actuation point or counter-clockwise to lower the actuation point. high an low swi ju in p n ntly. Figure 4 - Pressure Adjustment NOTE: Viking n tank-moun air comp for Doub In E ic/ n u-l ic R ion Sy. 2. Nitrog n Cylin Gas Supply (S Figu 1) Nitrogen may be used in place of air compressors. Nitrogen is supplied in pressurized cylinders in various sizes and pressures. S of most common 122 Cu. Ft. at SI ( 455 L at 131 bar) 225 Cu. Ft. at SI (6 72 L at 145 bar) an 280 Cu. Ft. at 2 SI (7 930 L at 159 bar). When nitrogen cylinders are used as a primary air supply, spare cylinders should be furnished and located at the valve location. To determine the approximate amount of nitrogen to be furnished, the following formula may be used: Vc = Vs x 100 English Units Where: Vc = Volu of Cylin (ft 3 ) = R qui Nitrog n u ( SI) V = Volu of Sy (gal) Vc = Vs x 108 Metric Units Where: Vc = Volu of Cylin (L) = R qui Nitrog n u (bar) V = Volu of Sy (L) Sp ial ntion must b gi n to sy ploying a b gas supply. B u only a limi amount of gas is availab small (which normally wou go unnoti in sy b ing suppli by nical comp ) can b critical to sy s p forman. If sy is to function at p u as low as -40 F (-40 C) an if b nitrog n is the gas supply, the system is particularly susceptible to leakage, and special care should be taken to ensure against leaks throughout the entire system. C. Air Supply Installation 1. Install qui air supply as ib in ion 4.B. siz of comp an amount of air qui shou b termined in accordance with Tables 1-3. The air or nitrogen supply to the preaction system must be clean, dry, and oil free. 2. Automatic air suppli must b gu i an from a continuous sou. A Viking air main nan i shou be installed on each system equipped with a tank-mounted compressor, plant air, or nitrogen. For compressors with a capacity than 5.5 ft 3 /min at 10 SI (0.154 (.154 m 3 /min at 0.69 bar), NFPA 13 does not require an air maintenance device. In addition, an air maintenance device should not be used with riser-mounted compressors as this can lead to compressor short cycling. Viking n that a tank-moun comp with air main nan i b u. i This can n become b critical i i when n accelerators are installed on the system. D. Pressure Switch Wiring; Wi Alarm u Switch ( S10) an Air Sup isory Switch ( S40) an just p u ings as shown in Figu 2-4.

5 Preaction 329e Figure 5 - Trim Components E. Hydrostatic Test: ion Sy inclu ing Sprin iping an Sprin shall b hy ically at 200 SI (13.8 bar) an maintain for 2 hou in n with NF A 13. Sy normally subj to working sy p u in x of 150 SI (10.3 bar) shall b at a p u of 50 SI (3.4 bar) in x of sy working p u. F. Placing the Valve in Service: (R f to Figu 5.) When the Preaction System is ready to be placed in service, verify that the electric release system has been reset and is in a normal condition. 1. ify that supply main control supplying is. 2. C pri. 3. Open the main drain valve. 4. Op n flow. 5. Drain all from p ion sy. If sy has op or if has n sy allow nough ti to completely drain the system. 6. C main in. 7. Op n priming. i p u will n an xpan s in nal iaphragm bly onto ff i y closing. ify pri p u has b n bli on pri p u gaug. 8. Establish air pressure on the system. 9. When the priming pressure has been verified as being established, slowly open the water supply control valve. 10. W n flow is p from flow CLOSE flow. 11. Fully open the water supply main control valve. 12. ify that no flows from ip n plung is pu. 13. Secure all valves in their normal operating position. 14. R control pan to any sup isory alarms. 15. Notify Authoriti Having Juri iction an in aff that sy is in i. 16. The system is now fully operational. G. Operational Test: An operational test shall be performed on the system in accordance with NFPA 13. Refer to Section 6 for Inspection and Operation Test Procedures.

6 Preaction 329f December 2, Operation A. In the Set Position: Air pressure is introduced into the sprinkler piping for supervisory purposes only for single interlock systems. For double interlock systems, air pressure ressure is used for supervisory su ervisory purposes ur oses and as one of the two initiation actions of the cross-zoned solenoid. Prime water is routed to the normally closed solenoid valve, and to the prime chamber. When prime water enters the prime chamber, the prime chamber assembly is pressurized, causing it to expand downward onto the water seat. Figure 6 - Set Position

7 Preaction 329g B. Activation of Release System (Single Interlock System): When the detection system operates, the normally closed solenoid valve is powered open. Prime water is drained from the prime chamb causing to op n filling sprin piping with. W from in i chamb of p uriz nsing n of OR causing ORV to op n. op n ORV p nts p u from building in the prime chamber should the solenoid close. Figure 7a - Activation of Release System - Single Interlock System

8 Preaction 329h December 2, 2011 C. Fire Condition (Double Interlock System): In a con ition op ion of ion sy acti first initiating circuit in control pan causing an alarm to activate. When a sprinkler operates, air pressure escapes from the sprinkler piping. The air supervisory switch activates n initiating circuit in control pan. W n BOTH initiating circuits b n acti control pan energizes the solenoid valve open. With the solenoid valve open, prime water is drained from the prime chamber, causing the G- to op n filling sprin piping with. W from in i chamb of p uriz nsing n of ORV causing ORV to op n. op n ORV p nts p u from bui ing in pri chamber should the solenoid close. Figure 7b - Fire Condition - Double Interlock System

9 Preaction 329i 6. Inspection and operational test NOTICE: The owner is responsible for maintaining the fire protection system and devices in proper operating condition. It is imp i that sy is insp an on a gular basis in n with NF A 25. The frequency of the inspections may vary due to contaminated water supplies, corrosive water supplies, corrosive atmospheres, as as con ition of air supply to sy. For minimum main nan an insp ion qui n f to NF A 25. In dition, the Authority Having Jurisdiction may have additional maintenance, testing, and inspection requirements that must be followed. Viking not qui in nal insp ion of as part of routin insp ion an ing. In nal main nan is g n y only required for valve repairs and internal component replacement. WARNING: Any sy main nan that in placing a control or ion sy out of i may imin p ion capabiliti of that sy. ior to p ing notify all Authoriti Having Juri iction. Consi ion shou b gi n to ploy nt of a patrol in aff. A. Low Air Pressure Alarm Test: (R f to Figu 5.) Quarterly testing of low air alarms is recommended. To Test Sprinkler System Low Air Supervisory Alarm: 1. To p nt op ion of an filling sy with uring DO NOT op ic ion sy uring. Consi closing main supply control. 2. Partially open the sprinkler system main drain or test connection. 3. ify that low air alarms op within an ptab ti p i an continu without in uption. 4. C main in or conn ion. 5. Establish sup isory air p u to n p u. 6. Reset the system release control panel. The supervisory alarms should stop. When testing is complete, return the system to service following steps 1 through 8 below. B. Full Flow Trip Test: (R f to Figu 5) forman of a trip is n annually uring warm. Consi inating this with op ion ing of the detectors. Caution! Performance of this test will cause the G-3000P Valve to open and the sprinkler system to fill with water. To Trip E ically Con ion Sy : 1. Notify the Authority Having Jurisdiction and those in the area affected by the test. 2. Trip by p forming option or b b. a. Op ic control sy ing to manufactu s instructions (for sing in or ub in sy ) an n op n p n sprin p in sy y conn ion nn i n (for (f ub ub in in sy ). y ). b. Operate the emergency release valve. 3. shou op n filling sprin sy with. W flow alarms shou op. 4. Op n sprin sy main in or sprin sy to ify qu flow. When Trip Testing is complete: 5. form ps 1 through 16 of ion 4.F - LACING THE SYSTEM IN SERVICE to urn sy to i. 6. Notify the Authority Having Jurisdiction and those in the affected area that testing is complete. 7. Maintenance Viking not qui an in nal insp ion of un is an in ication of g to in nal compon nts. A. Taking the system out of service: (R f to Figu 5.) 1. C supply main control placing sy out of i. 2. Op n flow in b of. 3. C air (or nitrog n) supply to p ion sy piping. 4. C priming 5. R i all air p u from p ion sy piping. If sy has op op n main in to allow system to drain completely. B. Removing the Cover from the Body: (R f to Figu 1 & 11.) 1. R g coupling from top of. 2. R 12 ion of pip i y ab Remove the air supply line from the air supervisory switch. 4. R 1-1/4 g coupling b main in.

10 ion 329j December 2, R 10 (8). 6. an trim that is still conn may now b from b y. (It may b n y to pry open as the diaphragm may bond itself to the cover and body over time.) C. Removing / Replacing the Check Diaphragm: (R f to Figu 11.) 1. iaphragm (7) may b lif from b y (1). 2. If n y p iaphragm (7). D. Inspecting the Prime Chamber and Coupling for Leaks: (R f to Figu 5.) If i it is possib to an insp for with. 1. Slowly open the prime valve. 2. With prime water established, partially open the main water supply control valve. 3. Visually insp insi of for. 4. C supply control. E. Removing / Replacing the Prime Coupling: (R f to Figu 11.) 1. Open the 1/2 union on the prime line. 2. Using a nch on flats of coupling (6) coupling (6) from b y (1). 3. Insp coupling (6) an O-rings (5). R p if n y, using instructions in O-Ring R p nt Bu in F_ F. Removing / Replacing the Prime Chamber Assembly: (R f to Figu 11.) 1. pri chamb bly (4) is now in p by two flang on outsi i of bly. Sli pri chamb bly (4) pri lin an from b y (1). 2. Inspect and replace if necessary. 3. Insp. shou b n an f of f ign ial. If is g must b replaced. G. Re-Assembling the Valve: (R f to Figu 11) 1. pri chamb bly (4) in b y (1). M su two flang position in g. 2. pri coupling (6) into b y (1). M su n of pri coupling (6) is in into pri chamb bly (4). 3. Lay iaphragm (7) into b y (1). 4. ition onto b y (1) an install an tig n (8). 5. R install any trim that was. 6. in i by following ps in S ion 4.F. 8. AVAILABILITY Viking M is availab through a n of ic an in national istributors. S Viking Corp. W b si for istributor or contact Viking Corporation.

11 Preaction 329k Part Number : 1 M 1 Model G-3000P Electric Release Trim (Inclu NC S noi ) 1 12 Section of Schedule 10 Pipe and Coupling 1 Air u Sup isory Switch ( S40-2A) 1 Alarm u Switch ( S10-2A) 1 W Supply Control Figure Assembly Accessories: Model E-1 Accelerator M LD-1 Anti-Column D i Drain Manifold Figure 9 - Optional Accessories

12 Preaction 329l December 2, 2011 Figure 10 - Installation Dimensions

13 Preaction 329m Figure 11 - Model G-3000P Valve Components List/Replacement Parts Item Number Part Number Description Material 1 -- B y Ducti Iron Seat UNS-C11000 Copp or UNS-S30400 Stain S Anaerobic Adhesive i Chamb A bly B E DM Nitri 304 Stain S Bronz Alloy 1 Number Required 5 * O-Rings EPDM and Nitrile 2 or 3** Coupling UNS-S17400 Stain S C Diaphragm EPDM /2-13 x 1-1/4 HHS UNS-S30400 Stain S C Ducti Iron Data Plate Aluminum Tack Alloy Carbon S 4 -- Replacement part is not available. * Indicates part available only in a Sub-Assembly, as indicated below. Sub-Assembly O-Ring Replacement Kit (**Refer to O-Ring Replacement Bulletin Form No. F_ for instructions.) Form No. F_ R p pag 329 July (R i the replacement parts list and Figure 11.)

TECHNICAL DATA. Dry 122a. November 12, 2013

TECHNICAL DATA. Dry 122a. November 12, 2013 Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around

More information

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety

More information

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 thru inch (DN40 thru DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical

More information

Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)

Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200) Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0.6 bar -to- 1.9 bar) Max 3. Reset externally. Cover removal is not

More information

I-768 FireLock NXT Dry Valve

I-768 FireLock NXT Dry Valve HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR EASY FUTURE REFERENCE WARNING WARNING Failure to follow instructions and warnings can cause product failure, resulting in serious personal injury and

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

3, 4, 6 & 8 Model H Series Alarm Check Valve Installation and Maintenance Guide ", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,

More information

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 gpm@gpmhydraulic.com www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS

More information

TECHNICAL DATA. 30a. September 18, 2009 1-1/4-8 (DN32 - DN200)

TECHNICAL DATA. 30a. September 18, 2009 1-1/4-8 (DN32 - DN200) September 18, 2009 30a 1. DESCRIPTION Viking EasyPac Commercial Riser Manifold Assemblies are available in sizes 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 6 and 8 for commercial systems. They are available with an

More information

Technical Data. Installation

Technical Data. Installation Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems General Description The Figure 51 (1) Riser Manifolds

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Design & Construction Standards, Revised January 2013 5.21.30-1

Design & Construction Standards, Revised January 2013 5.21.30-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator

Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator Andy L. Kaempfer Business Development Manager Potter Electric Signal Company, LLC 1609 Park 370 Place St. Louis,

More information

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed

More information

4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX

4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX Butterfly Valves 4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com MAY 2013 L-1 BULLETIN BUTTERFLY REV. #5 GLOBE BUTTERFLY VALVE INSTALLATION

More information

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

Oildyne. 165 Series Hydraulic Power Units. Pressures to 241 bar (3500 psi) Flows to 5.4 lpm (1.4 gpm)

Oildyne. 165 Series Hydraulic Power Units. Pressures to 241 bar (3500 psi) Flows to 5.4 lpm (1.4 gpm) Oildyne Hydraulic Power Units Pressures to 241 bar (3500 psi) Flows to 5.4 lpm (1.4 gpm) 11 Power Unit Features We are pleased to introduce our new power units. The power units let you put more power where

More information

Preaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description

Preaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation /2 thru 8 Inch (DN thru DN200) General Description The DV5 Supervised Single

More information

DV-5 Deluge Valve with Remote-Resetting, Pressure-Reducing Trim 4 Inch and 6 Inch (DN100 and DN150) General Description.

DV-5 Deluge Valve with Remote-Resetting, Pressure-Reducing Trim 4 Inch and 6 Inch (DN100 and DN150) General Description. Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim 4 Inch and 6 Inch (DN and DN5) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water

More information

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2. May 3, 2013 Foam 138a 1. DESCRIPTION Chemguard Water Powered Oscillating Monitors are designed to automatically discharge over a specific design area upon system activation. These are suitable for use

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information

TD01211 PIN: NX010 201007.2 nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA

TD01211 PIN: NX010 201007.2 nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA Water Motor Alarm MODEL: NX010 GENERAL DESCRIPTION TECHNICAL SPECIFICATIONS Model NX010 Working Water Pressure Range 5 to 175 psig 0.035 to 1.2 MPa (0.35 to 12 bar) Shipping Weight 11 lbs 5 kg Alarm Line

More information

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,

More information

Transformer Deluge Systems

Transformer Deluge Systems Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange Description VF 2 VF 3 VF 2 and VF 3 valves provide a quality, cost effective solution for most water and chilled applications. The

More information

PRESSURE REDUCING CONTROL VALVE

PRESSURE REDUCING CONTROL VALVE Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line

More information

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual Manual No. 5EP-OM1-1 Electric Panel Pump Control System Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION... 2 SEQUENCE

More information

Wet alarm valves. Wet alarm valves. FM trim

Wet alarm valves. Wet alarm valves. FM trim Description Usually, a wet alarm valve station comprise: - a Rolland wet alarm valve linked to the water motor gong. - a set of valves and by pass used to test the system. - a drain valve. - a test valve

More information

Pressure Testing Procedures for Building Services Piping

Pressure Testing Procedures for Building Services Piping Pressure Testing Procedures for Building Services Piping Document Number Revision 0 Approved By Ric Morris McMurdo, Palmer, and South Pole February 25, 2005 Active Divisions/Departments FEMC Raytheon Polar

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

ACCUMULATOR INSTALLATION

ACCUMULATOR INSTALLATION 7001-7 ACCUMULATOR INSTALLATION BRAKE ACCUMULATORS I 308L93 Rae 7-59710 Issued 6-93 Printed in U.S.A 7001-8 Removal ACCUMULATOR VALVE 1. Park the machine on a level surface and lower the. loader bucket

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into

More information

Pr o d u c t In f o r m at i o n V008.0

Pr o d u c t In f o r m at i o n V008.0 AGF Manufacturing Inc. Pr o d u c t In f o r m at i o n V008.0 Reliability, Versatility, Code Compatibility BK002 COLLECTa ndrain The COLLECTa ndrain family of products are anti-trip drum drips that prevent

More information

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This

More information

BERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features

BERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features Pressure Relief/Sustaining Valve Prioritizing pressure zones Ensuring controlled pipeline fill-up Preventing pipeline emptying Pump overload & cavitation protection Safeguarding pump minimum flow Excessive

More information

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority

More information

FILLING AND PURGING THE SYSTEM

FILLING AND PURGING THE SYSTEM FILLING INSTRUCTIONS FOR WATER HEATER OR CONDENSING BOILER (City Water) Safety tip: Before beginning, turn off power to boiler and circulator. FILLING AND PURGING Step 1: Close Return Manifold Isolation

More information

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS GAP.14.1.2.2 A Publication of Global Asset Protection Services LLC WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS INTRODUCTION A hydrant or other large-volume flow test is necessary for proper water

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

Installation Manual DIAPHRAGM WELL TANK

Installation Manual DIAPHRAGM WELL TANK Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of

More information

Compressed Air Systems

Compressed Air Systems Efficiency Vermont Guide to Savings Helping Vermont businesses save energy and money Compressed Air Systems 888-921-5990 www.efficiencyvermont.com 1 Save money and optimize system performance Air compressors

More information

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013 Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge

More information

CPL SYSTEMS / GROENEVELD AUTOMATIC GREASING SYSTEM COMPLETE SYSTEM CHECK PNEUMATIC PUMP

CPL SYSTEMS / GROENEVELD AUTOMATIC GREASING SYSTEM COMPLETE SYSTEM CHECK PNEUMATIC PUMP CPL SYSTEMS / GROENEVELD AUTOMATIC GREASING SYSTEM COMPLETE SYSTEM CHECK PNEUMATIC PUMP Feb 5, 2003 1 CPL SYSTEMS / GROENEVELD AUTOMATIC GREASING COMPLETE SYSTEM CHECK - PNEUMATIC PUMP THE SYSTEM DOES

More information

Diameter 3" 4" 6" 8" Flange type PN 16 PN 16 PN 16 PN 16. Orange-red ( RAL 2002) Height (cm) 27,70 26,30 28,70 29.70

Diameter 3 4 6 8 Flange type PN 16 PN 16 PN 16 PN 16. Orange-red ( RAL 2002) Height (cm) 27,70 26,30 28,70 29.70 Description Usually, a wet alarm valve station comprise: a Rolland wet alarm valve linked to the water motor gong. a set of valves and by pass used to test the system. a drain valve. a test valve gauges

More information

BERMAD Waterworks. Quick Active Check Valve. 700 Series. Model 740Q. Features and Benefits. Major Additional Features

BERMAD Waterworks. Quick Active Check Valve. 700 Series. Model 740Q. Features and Benefits. Major Additional Features Booster Pump Control Valve Quick Active Check Valve Isolates system from the effects of pump starts and stops for: Solitary single speed pumps Battery of single speed pumps (add & switch) Battery of variable

More information

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days

More information

TECHNICAL DATA. NOTES: For use with Trim Chart on page 27 b. (open fold-out)

TECHNICAL DATA. NOTES: For use with Trim Chart on page 27 b. (open fold-out) De cem ber 6, 1999 Trim 27 a MODEL J-1 ALARM CHECK VALVE VERTICAL TRIM Maximum 250 PSI WWP This Trim Chart is for use with the following Viking Trim Sets Valve Size Standard* Trim P/N Foam System** Trim

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

Cooling system components, removing and installing

Cooling system components, removing and installing Page 1 of 34 19-1 Cooling system components, removing and installing WARNING! The cooling system is pressurized when the engine is warm. When opening the expansion tank, wear gloves and other appropriate

More information

Wet System. Technical Manual for Operation, Maintenance, and Troubleshooting

Wet System. Technical Manual for Operation, Maintenance, and Troubleshooting Wet System Technical Manual for Operation, Maintenance, and Troubleshooting October, 2008 Form No. F_010508 Page II October 15, 2008 Table of Contents Page I. DESCRIPTION 3 II. APPLICATIONS 4 III. REQUIREMENTS

More information

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions

ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions 4057250/8 IM-P405-16 AB Issue 8 ABV20 Air Actuated Boiler Blowdown Valve Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Operation

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female

More information

HYDROSTATIC TEST PUMPS

HYDROSTATIC TEST PUMPS HYDROSTATIC TEST PUMPS MANUAL HYDROSTATIC TEST PUMPS Ideal for testing residential water lines. Also for pressure testing small pressure tanks, sprinkler, boiler and solar systems. Lightweight and easy

More information

Fisher 377 Trip Valve

Fisher 377 Trip Valve Instruction Manual Fisher 377 Trip Valve Contents Introduction... 1 Scope of Manual... 1 Description... 1 Specifications... 2 Educational Services... 2 Installation... 4 Supply Pressure Requirements...

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

HENRY TECHNOLOGIES - OIL LEVEL REGULATORS (CONVENTIONAL)

HENRY TECHNOLOGIES - OIL LEVEL REGULATORS (CONVENTIONAL) HENRY TECHNOLOGIES - OIL LEVEL REGULATORS (CONVENTIONAL) The oil level regulator controls the oil level in the compressor crankcase with a float operated valve. Oil level regulators are designed to attach

More information

PBX Series Quick Fit Connector Bimetallic Steam Traps

PBX Series Quick Fit Connector Bimetallic Steam Traps 6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

PREPIPED LIQUID FUEL MANIFOLDS PLPM

PREPIPED LIQUID FUEL MANIFOLDS PLPM PREPIPED LIQUID FUEL MANIFOLDS PLPM INSTRUCTIONS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components,

More information

To: All Shipowners, Ship Managers, Ship Masters and Classification Societies

To: All Shipowners, Ship Managers, Ship Masters and Classification Societies 海 事 處 船 舶 事 務 科 香 港 中 環 統 一 碼 頭 道 38 號 海 港 政 府 大 樓 ---------- 香 港 郵 箱 4155 號 MARINE DEPARTMENT Shipping Division Harbour Building 38 Pier Road, Central, Hong Kong ----------- G.P.O.Box 4155 網 站 Website

More information

Model RV-1 Pressure Relief Valve 2 to 8 Inch (DN50 to DN200), 250 psi (17,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description

Model RV-1 Pressure Relief Valve 2 to 8 Inch (DN50 to DN200), 250 psi (17,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description Technical Services 00-3-932 +-0-7-220 www.tyco-fire.com Model RV- Pressure Relief Valve 2 to Inch (DN50 to DN200), 250 psi (7,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description The

More information

Model F1FR Series Quick Response Glass Bulb Sprinklers

Model F1FR Series Quick Response Glass Bulb Sprinklers Model F1FR56 Sprinkler Types Standard Spray Standard Spray Conventional / Vertical Sidewall Model F1FR56 Recessed Sprinkler Types Standard Spray Model F1FR56 Concealed Sprinkler Types Standard Spray Model

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

Industrial Hydraulic Remote Controlled Monitor

Industrial Hydraulic Remote Controlled Monitor Industrial Hydraulic Remote Controlled Monitor Models: 294-11XBHC-N4X, 294-11XBHC-N7/4, 299-20XHC-N4X, & 299-20XHC-N7/4 Installation, Operating, & Maintenance Instructions 1302 WEST BEARDSLEY AVENUE P.O.

More information

15/40/80CN Series Medium Pressure Filters

15/40/80CN Series Medium Pressure Filters 1/4/8CN Series Medium Pressure Filters Max 32 l/min - 7 bar Global Filtration Technology 1/4/8CN Series TYPICAL APPLICATIONS Compressor Lube Oil Off-line Filter Loops Machine Tools (Automotive Standard)

More information

Index 11.1. Page. Pumping Systems...11.2-11.4 Intensifiers...11.5 Gas Boosters...11.6-11.7 High Pressure Generators...11.8-11.9

Index 11.1. Page. Pumping Systems...11.2-11.4 Intensifiers...11.5 Gas Boosters...11.6-11.7 High Pressure Generators...11.8-11.9 Pumping Systems, Intensifiers, Gas Boosters and High Pressure Generators High Pressure Equipment Company produces a number of components and systems for general industrial, elevated pressure applications.

More information

Sprinkler Guards Model C Model D

Sprinkler Guards Model C Model D Bulletin 208 Rev. M Sprinkler Guards Model C Model D Bulletin 208 Rev. M Model C Sprinkler Guards Model C Series sprinkler guards are designed to be assembled onto installed sprinklers. They are constructed

More information

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL

ESFR PRE-PRIMED SINGLE INTERLOCKED PREACTION COLD STORAGE SYSTEM MANUAL ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL The Viking Corporation 210 N Industrial Park Road Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:

More information

Rental Services Temporary Cooling - Flexible Water Hose

Rental Services Temporary Cooling - Flexible Water Hose Engineering Bulletin Rental Services Temporary Cooling - Flexible Water Hose September 2006 CHS-PRB007-EN Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate

More information

Electro-Pneumatic Bus Door Control Mechanism

Electro-Pneumatic Bus Door Control Mechanism Electro-Pneumatic Bus Door Control Mechanism Application and Feature 1. Pneumatic Door Mechanism actuates the open/close movements of bus door through two double acting cylinders and two linkages with

More information

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap 1263050/6 IM-P126-07 ST Issue 6 BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation

More information

Model KFR56 Series Quick Response Standard Spray

Model KFR56 Series Quick Response Standard Spray Bulletin 036 Model KFR56 Series Quick Response Standard Spray Bulletin 036 Model KFR56 Sprinkler Types Standard Upright Standard Pendent Horizontal Sidewall Model KFR56 Sprinkler Types Pendent F1/F2/FP

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

BERMAD Waterworks. High Pressure, Surge Anticipating Control Valve. 800 Series. Model 835-M. Features and Benefits. Major Additional Features

BERMAD Waterworks. High Pressure, Surge Anticipating Control Valve. 800 Series. Model 835-M. Features and Benefits. Major Additional Features High Pressure, Surge Anticipating Control Valve Eliminates surge in all pumping systems: Booster & deep well, single & variable speed Eliminates surge in all distribution networks: Municipal, high-rise

More information

15/40/80CN Series Coreless Medium Pressure Filters

15/40/80CN Series Coreless Medium Pressure Filters //8CN Series Coreless Medium Pressure Filters //8CN Series Applications Compressor Lube Oil Off-line Filter Loops Machine Tools (Automotive Standard) Hydrostatic Drive Charge Pumps Mobile Equipment Pilot

More information

Fighting Fire in Sprinklered Buildings. Student Guide

Fighting Fire in Sprinklered Buildings. Student Guide Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction

More information

Midwest Industrial Tanks

Midwest Industrial Tanks FOR AGRICULTURE AND INDUSTRY Midwest Industrial Tanks Fuel & Oil Storage Solutions Midwest Industrial Tanks Is Your Source For All Of Your Fuel Storage And Fuel Transportation Needs. Our Satisfied Customers

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

Air Eliminators and Combination Air Eliminators Strainers

Air Eliminators and Combination Air Eliminators Strainers Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.

More information

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES SECTION 15062 STEAM AND CONDENSATE PIPING PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Comply with the provisions of the following: 1.2 DESIGN CRITERIA 1. ASME B 31.9 Building Services Piping : for

More information

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100

FOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100 MODEL - FCA & FCA-S HD FIRE PROTECT TECHNICAL DATA MODELS FCA-65, FCA-80 & FCA-100 Carbon Steel Construction FCA-S 65, FCA-S 80 & FCA-S 100 Stainless Steel Construction INLET SIZE 65, 80, 100 NB WORKING

More information

OHIO MEDICAL CORPORATION. Medical Gas Panel. Installation and Maintenance Manual

OHIO MEDICAL CORPORATION. Medical Gas Panel. Installation and Maintenance Manual OHIO MEDICAL CORPORATION Medical Gas Panel Installation and Maintenance Manual P/N 255105 (Rev.5) 08/2005 P/N 255105 (Rev.5) 08/2005 PAGE 2 OHIO MEDICAL CORPORATION PAGE 3 1.0 User Responsibilities The

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information