BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION'^^ j E DIRECT TESTIMONY RAJESH GUPTA PROJECT MANAGER, ENTERGY SERVICES, INC.

Size: px
Start display at page:

Download "BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION'^^ j E DIRECT TESTIMONY RAJESH GUPTA PROJECT MANAGER, ENTERGY SERVICES, INC."

Transcription

1 BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION'^^ j E s : D IN THE MATTER OF THE APPLICATION OF ENTERGY ARKANSAS, INC. FOR A CERTIFICATE OF ENVIRONMENTAL COMPATIBILITY AND PUBLIC NEED TO CONSTRUCT AND OPERATE THE ETTA 00 KV SUBSTATION AND RELATED 00 KV TRANSMISSION LINE SEGMENTS AND ASSOCIATED TRANSMISSION FACILITIES, IN HOT SPRING COUNTY, ARKANSAS DIRECT TESTIMONY OF RAJESH GUPTA PROJECT MANAGER, ENTERGY SERVICES, INC. ON BEHALF OF ENTERGY ARKANSAS, INC. MAY,00

2 . INTRODUCTION AND BACKGROUND Q. PLEASE STATE YOUR NAME, BUSINESS AFFILIATION AND ADDRESS? 6 0 A. Q. A. Q. I am Rajesh Gupta. I am employed by Entergy Services, Inc. ( EW), an affiliate of Entergy Arkansas, Inc. ( EAI or the Company ). My business address is Entergy Corporation Building, 6 Loyola Avenue, New Orleans, LA 0. ON WHOSE BEHALF ARE YOU TESTIFYING? I am testifying on behalf of EAI. WHAT POSITION DO YOU HOLD WITH ESI? A. I am a Project Manager in the Transmission Project Management Organization with ESI. 6 Q. PLEASE DESCRIBE YOUR PROFESSIONAL EDUCATION, QUALIFICATIONS AND EXPERIENCE. 0 A I graduated from the University of Indore, India, in with a Bachelor of Science degree in Civil Engineering and was awarded a Master of Business Administration degree by Tulane University in. I worked as a Consulting Engineer in Power Plant Design for Sargent and Lundy Engineers and Stone and Webster Engineering Corporation until. I was subsequently employed by Entergy Operations, Inc., as a Senior --

3 Engineer and later as an Engineering Supervisor in Power Plant Design Engineering from until 000. In August 000, I was named a Project Manager within the Engineering Management and Capital Construction Department ( EMCCI ), Transmission, ESI. 6 Q. WHAT ARE YOUR DUTIES IN ARKANSAS? I am responsible for managing all EA capital transmission projects in the Arkansas jurisdiction. 0 6 Q. PLEASE SUMMARIZE THE FUNCTION OF ESI AS IT RELATES TO THIS FILING. A. ESI is responsible for providing engineering, procurement, project management and construction support to design and construct the facilities required to allow Duke Energy Hot Spring, LLC ( DEHS ), an Independent Power Producer ( IPP ), to connect a new generating plant (the Duke Energy Facility ) to the Company s transmission facilities. 0 Q. PLEASE EXPLAIN WHY THE COMPANY HAS FILED AN APPLICATION TO CONSTRUCTl OPERATE AND MAINTAIN THE PROPOSED ELECTRICAL FACITILIES? A. DEHS plans to construct and operate the,0 MW, natural gas-fired power plant near Etta, Arkansas, on property currently owned by it and --

4 adjacent to the right-of-way boundary of the Company s 00 kv transmission line running from the Hot Springs 00 kv Substation to the McNeil 00 kv Substation. The Duke Energy Facility will have the capability initially to produce,0 MW of electricity. 6 Q. A WHAT IS THE PURPOSE OF YOUR TESTIMONY IN THIS PROCEEDING? My testimony will support the Company s Application for a Certificate of Environmental Compatibility and Public Need ( CECPN ) to allow the Company to construct and operate two new 00 kv line segments and related expansions that will terminate in the new 00 kv Etta Substation (the Proposed Electrical Facilities ) to interconnect the Duke Energy Facility with the electrical grid. I will describe the equipment and design of the Proposed Electrical Facilities, other equipment alternatives that were considered, and the economics of construction design types and installation cost, as well as the timeframe for construction completion. The Company will present additional witnesses to support its Application. Mr. Murry Witcher, ESI Transmission Specialist, will testify to the process used by the Company to acquire land and rights-of-way and describe the general use of the properties in the area of the Proposed Electrical Facilities. Mr. G. Robert Burner, representing DEHS, will describe the Duke Energy Facility and its operation. In addition, Mr. John Zimmerman, ESI Manager of Transmission Policy, will discuss the --

5 Company s Interconnection Agreement with DEHS, and Mr. Greg Zakrzeski, ESI Senior Staff Accountant, will address the rate treatment and accounting of funds used in the construction and operation of the project. 6. Q, 0 ELECTRICAL DESIGN AND EQUIPMENT OF THE PROPOSED ELECTRICAL FACILITIES PLEASE DESCRIBE THE DESIGN OF THE PROPOSED ELECTRICAL FACILITIES. The Proposed Electrical Facilities will include a new 00 kv substation that will contain four 00 kv breakers and two new 00 kv line terminations and associated equipment. Two segments of 00 kv 6 transmission line, each approximately,000 feet in length, will be constructed to connect the proposed Etta 00 kv Substation to the existing Hot Springs 00 kv Substation to McNeil 00 kv Substation Transmission Line. A more detailed description of the Proposed Electrical Facilities to be constructed and EAl s proposed transmission line route, along with the electrical design criteria, is contained in EA Application Exhibit D filed in this Docket. 0 Q. A. WHY WAS THIS PARTICULAR CONFIGURATION SELECTED? This configuration allows DEHS to connect to the electric grid and produce electricity in a manner that provides for the best system stability and --

6 reliability. This configuration directly strengthens the Company s 00 kv transmission system. Q. 6 A. PLEASE DESCRIBE THE COMPANY S EXPERIENCE WITH THESE TWNSMISSION FACILITIES AT SIMILAR VOLTAGE LEVELS. EA has more than,600 miles of 6/ kv transmission lines in service. EA has extensive experience in designing, constructing, 0 6 operating and maintaining this type of line and associated facilities. The most recent construction projects are the Pleasant Hill to Quitman 6 kv Transmission Line that was recently completed and included a 00 kv substation facility similar to the one proposed in this Docket. Other recent, similar projects include the. mile Fordyce Switching Station to Georgia- Pacific Corporation s OSB Plant kv Transmission Line, which was completed in 000, and the. mile Pine Bluff East Substation to Pine Bluff International Paper Company kv Transmission Line, completed in. Q. 0 A. WHAT ALTERNATIVE TYPES OF TRANSMISSION LINE STRUCTURES WERE CONSIDERED FOR THIS PROJECT? Steel lattice towers, guyed Y structures, and steel pole structures were considered. In addition to lattice structures, which are used on the existing 00 kv main line, two and three steel pole structures were selected for the new tangent pole towers, primarily for economic and -6-

7 environmental reasons as well as the efficient utilization of available space in the new right-of-way for the Proposed Electrical Facilities. Underground construction at the 00 kv voltage level is possible, but is not economically viable. 6 Q A. 0 HOW DO YOU PLAN TO CONSTRUCT THESE FACILITIES? Our intentions are for the transmission line construction and substation construction to be accomplished by contract personnel. EA will maintain supervisory and inspection personnel at the project site to monitor and oversee the project during construction. Q. A. 6 WHAT INDUSTRY STANDARDS WILL THE DESIGN AND CONSTRUCTION OF THESE PROPOSED ELECTRICAL FACILITIES FOLLOW? The requirements set forth in the National Electrical Safety Code, as currently adopted by this Commission, will be met or exceeded. Q. 0 A. WHEN AND HOW WILL EA TAKE TITLE TO THE PROPOSED E LECTRl CAL FAC I LIT ES? EA will receive ownership of the Proposed Electrical Facilities from DEHS upon completion of the project. --

8 Q. PLEASE EXPLAIN THE TIMEFRAME WHEN THE COMPANY IS PROPOSING TO ADD THE PROPOSED ELECTRICAL FACILITIES TO THE ENTERGY TRANSMISSION GRID. A. EA is proposing to construct and complete these facilities in order to meet the customer's in-service date of June Q. PLEASE DESCRIBE WHAT FACILITIES EA WILL OWN AFTER THE DUKE ENERGY FACILITY IS COMPLETED. A. All of the electrical service facilities constructed by, or on behalf of EA for this project, will be owned by EA upon project completion. This includes the Etta 00 kv Substation, and the proposed 00 kv transmission line segments and all associated equipment. 6. Q. COSTS AND FINANCING OF THE PROPOSED ELECTRIC FACILITIES WHAT IS THE ESTIMATED COST OF THE PROPOSED ELECTRICAL FACl LITIES? A. Total project costs including overheads are estimated as follows: $(million) 00 kv Transmission $.0 00 kv Substation. Metering 0. Relay and Communications. Corporate Loading. Total $.0 --

9 6 0 The 00 kv transmission line estimates are based on approximately,000 feet of two and three pole steel construction with approximately structures per mile. Based on our experience in this type of terrain, it was assumed, for estimating purposes, that the line would require the installation of caisson type foundations of varying depths depending on soil conditions. This estimate also includes the required Etta 00 kv Substation, customer metering equipment, and relay and communications equipment needed to operate the two proposed line segments. Q. A. 6 0 WHAT IS THE SALVAGE VALUE OF THE PROPOSED ELECTRICAL FACILITIES AFTER THEIR LIFE EXPECTANCY? Life expectancy of the transmission line is based on periodic depreciation studies that estimate remaining life of a line depending on the maintenance and improvements performed on the line - generally 0 years. If the line is abandoned at the end of its useful life, EA will remove the conductors and structures from the right-of-way. Salvaged material will be sold as scrap and the right-of-way will revert back to the owners. The estimated cost in present dollars to remove the proposed transmission facilities is approximately $00,000, with salvage values less than $00,000. Reuse of material is very unlikely due to possible contamination or possible damage to material during removal. --

10 Q. A. HOW WILL EA FINANCE THE PROPOSED CONSTRUCTION? DEHS will pay all of the cost of the facilities as a Contribution in Aid of Construction. EA has developed a payment schedule based on the 6 project cash flow for engineering, procurement and construction, and DEHS will make payments each month to cover expected expenses according to the cash flow projections. More detail on this topic is included in the Direct Testimony of Mr. John Zimmerman. IO Q. A. 6 0 PLEASE SUMMARIZE YOUR TESTIMONY. In my opinion, based upon my professional experience and the information available to me, I believe that the construction of the Proposed Electrical Facilities for which EA is seeking a CECPN is in the public interest. The project described herein is considered to be the most reasonable, complete, environmentally responsible, and cost effective means to provide the necessary electrical connections for the electricity produced by the Duke Energy Facility to access the electrical grid. Existing, as well as future residential, commercial, and industrial customers in Arkansas and the region would benefit from this project and the increased quality, availability and reliability of electric service from the Proposed Electrical Facilities. -0-

11 I Q. DOES THIS CONCLUDE YOUR TESTIMONY? A. Yes. - -

12 CERTIFICATE OF SERVICE I, Steven K. Strickland, do hereby certify that a copy of the foregoing has been served upon all parties of record this th day of May, 00. Steven K. Strickland

345 kv Brazos Valley Connection Project FAQs

345 kv Brazos Valley Connection Project FAQs 345 kv Brazos Valley Connection Project FAQs Overview 1. Who is CenterPoint Energy Houston Electric, LLC? CenterPoint Energy Houston Electric, LLC (CenterPoint Energy) is an electric utility that maintains

More information

Morris S. Stover, P.E. Sponsor, Transmission Area

Morris S. Stover, P.E. Sponsor, Transmission Area Page 1 of 5 Job Function Morris has nearly 28 years in the power industry including design and construction of transmission line and substation facilities, He has extensive experience in contract development

More information

STATE OF VERMONT PUBLIC SERVICE BOARD ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) PREFILED TESTIMONY OF SCOTT S. MALLORY ON BEHALF OF PETITIONERS

STATE OF VERMONT PUBLIC SERVICE BOARD ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) ) PREFILED TESTIMONY OF SCOTT S. MALLORY ON BEHALF OF PETITIONERS STATE OF VERMONT PUBLIC SERVICE BOARD Joint Petition of Vermont Transco, LLC, Vermont Electric Company, Inc. ( VELCO, City of Burlington Electric Department ( BED and Green Mountain Power Corporation for

More information

1. Who is CenterPoint Energy Houston Electric, LLC?

1. Who is CenterPoint Energy Houston Electric, LLC? 1. Who is CenterPoint Energy Houston Electric, LLC? CenterPoint Energy Houston Electric, LLC (CenterPoint Energy or the Company) is an electric utility that maintains the wires, towers, poles, and electric

More information

SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD

SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD HOLLAND CLIFF HEWITT ROAD 230 KV TRANSMISSION LINE PROJECT ELECTRIC ALTERNATIVE EVALUATION STUDY BLACK & VEATCH CORPORATION B&V Project 146026(G)

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

COMMONWEALTH OF VIRGINIA LRK,'S UNCE AT RICHMOND, SEPTEMBER 7,2012 TRUL CE.. P 112 : 51 APPLICATION OF FINAL ORDER

COMMONWEALTH OF VIRGINIA LRK,'S UNCE AT RICHMOND, SEPTEMBER 7,2012 TRUL CE.. P 112 : 51 APPLICATION OF FINAL ORDER COMMONWEALTH OF VIRGINIA STATE CORPORATION COMMISSION LRK,'S UNCE AT RICHMOND, SEPTEMBER 7,2012 TRUL CE.. P 112 : 51 APPLICATION OF VIRGINIA ELECTRIC AND POWER COMPANY For approval and certification of

More information

COMMONWEALTH OF KENTUCKY BEFORE THE KENTUCKY STATE BOARD ON ELECTRIC GENERATION AND TRANSMISSION SITING

COMMONWEALTH OF KENTUCKY BEFORE THE KENTUCKY STATE BOARD ON ELECTRIC GENERATION AND TRANSMISSION SITING COMMONWEALTH OF KENTUCKY BEFORE THE KENTUCKY STATE BOARD ON ELECTRIC GENERATION AND TRANSMISSION SITING In the Matter of the Application of The ) Cincinnati Gas & Electric Company for a ) Construction

More information

Virginia State Corporation Commission efiling CASE Document Cover Sheet

Virginia State Corporation Commission efiling CASE Document Cover Sheet Virginia State Corporation Commission efiling CASE Document Cover Sheet Case Number (if already assigned) pue-201 1-00011 Case Name (if known) Application of Virginia Electric and Power Company for approval

More information

FILED IN THE MATTER OF THE P TITION OF ) ENTERGY ARKANSAS, INC. FOR AN ) ACCOUNTING ORDER AUTHORIZING ) ESTABLISHMENT OF A REGULATORY )

FILED IN THE MATTER OF THE P TITION OF ) ENTERGY ARKANSAS, INC. FOR AN ) ACCOUNTING ORDER AUTHORIZING ) ESTABLISHMENT OF A REGULATORY ) BEFORE THE r r r ARKANSAS PUBLIC SERVICE COMMI&@ FILED IN THE MATTER OF THE P TITION OF ) ENTERGY ARKANSAS, INC. FOR AN ) ACCOUNTING ORDER AUTHORIZING ) ESTABLISHMENT OF A REGULATORY ) DOCKET NO. 08 -

More information

TERMS AND CONDITIONS

TERMS AND CONDITIONS Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator

More information

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering Title 20 PUBLIC SERVICE COMMISSION Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES Chapter 02 Engineering Authority: Public Utility Companies Article, 2-121, 5-101 and 5-303, Annotated Code of Maryland.

More information

Q: PLEASE STATE YOUR NAME AND BUSINESS ADDRESS. A: Gerry Sheerin. Sheerin Technical, 25 Eastville Avenue, Toronto, Ontario Canada

Q: PLEASE STATE YOUR NAME AND BUSINESS ADDRESS. A: Gerry Sheerin. Sheerin Technical, 25 Eastville Avenue, Toronto, Ontario Canada DIRECT TESTIMONY OF GERRY SHEERIN, P. ENG ON BEHALF OF PIEDMONT ENVIRONMENTAL COUNCIL BEFORE THE STATE CORPORATION COMMISSION OF VIRGINIA CASE NOS. PUE-00-0001 AND PUE-00-000 1 1 1 1 1 1 1 1 1 Q: PLEASE

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

Tucson Electric Power Company Rules and Regulations

Tucson Electric Power Company Rules and Regulations Original Sheet No.: 907 Introduction The Company will construct, own, operate and maintain lines along public streets, roads and highways which the Company has the legal right to occupy, and on public

More information

UNITED STATES OF AMERICA 151 FERC 62,147 FEDERAL ENERGY REGULATORY COMMISSION ORDER AUTHORIZING DISPOSITION OF JURISDICTIONAL FACILITIES

UNITED STATES OF AMERICA 151 FERC 62,147 FEDERAL ENERGY REGULATORY COMMISSION ORDER AUTHORIZING DISPOSITION OF JURISDICTIONAL FACILITIES UNITED STATES OF AMERICA 151 FERC 62,147 FEDERAL ENERGY REGULATORY COMMISSION Georgia Power Company Docket No. EC15-132-000 ORDER AUTHORIZING DISPOSITION OF JURISDICTIONAL FACILITIES (Issued June 1, 2015)

More information

Last revised: September 1, 2014 TRANSMISSION FUNCTION TITLES AND JOB DESCRIPTIONS

Last revised: September 1, 2014 TRANSMISSION FUNCTION TITLES AND JOB DESCRIPTIONS Last revised: September 1, 2014 TRANSMISSION FUNCTION TITLES AND JOB DESCRIPTIONS EVP, Chief Operations Officer, has primary responsibility for the overall planning, operations and control of the transmission

More information

Portland General Electric Company P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES

Portland General Electric Company P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES 1. Acceptance of Electricity Service By establishing or requesting a POD or by continuing an

More information

Certificate of Registration

Certificate of Registration Certificate of Registration This is to certify that Clancy Docwra Limited Supplier Number: 061973 are now fully registered as a supplier on UVDB for the following products/services 1.4.25 Communication

More information

An Economic Impact Analysis of Entergy Operations in Mississippi

An Economic Impact Analysis of Entergy Operations in Mississippi An Economic Impact Analysis of Entergy Operations in Mississippi 2012 Prepared by Table of Contents Introduction......3 Scope of Study....3 Method of Estimation.. 4 Company Overview..... 5 Economic Impact

More information

6. The estimated costs here do not include any applicable ITCC tax

6. The estimated costs here do not include any applicable ITCC tax General Notes and Clarifications: 1. The following estimated costs are based on past experiences and are intended to provide an order of magnitude of the total project cost given the major system components.

More information

Control Number : 14637. Item Number : 5. Addendum StartPage : 0

Control Number : 14637. Item Number : 5. Addendum StartPage : 0 Control Number : 14637 Item Number : 5 Addendum StartPage : 0 Pubtic Utility Commission of Tex s 7800 Shoal Creek Boulevard Austin, Texas 78757-1098 512/458-0100. (Fax) 458-8340 Pat Wood, III Chairman

More information

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER GRANTING PETITION FOR DECLARATORY ORDER. (Issued March 15, 2007)

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER GRANTING PETITION FOR DECLARATORY ORDER. (Issued March 15, 2007) UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: Joseph T. Kelliher, Chairman; Suedeen G. Kelly, Marc Spitzer, Philip D. Moeller, and Jon Wellinghoff. Cottonwood Energy

More information

MEMORANDUM. March 9, 2007

MEMORANDUM. March 9, 2007 MEMORANDUM March 9, 2007 TO: FROM: SUBJECT: MEMBERS, PORT COMMISSION Hon. Anne Lazarus, President Hon. Kimberly Brandon, Vice President Hon. Rodney Fong Hon. Michael Hardeman Monique Moyer Executive Director

More information

License Agreement for Screening Wall at 31786 Woodward Ave. October 1, 2015. The Honorable Mayor Ellison and Members of the City Commission:

License Agreement for Screening Wall at 31786 Woodward Ave. October 1, 2015. The Honorable Mayor Ellison and Members of the City Commission: Community Development Department Planning Division 211 South Williams Street Royal Oak, MI 48067 License Agreement for Screening Wall at 31786 Woodward Ave. October 1, 2015 The Honorable Mayor Ellison

More information

Seattle City Light s Asset Management Program

Seattle City Light s Asset Management Program Seattle City Light s Asset Management Program September 25-26, 2012 Agenda Asset Management vs. WAMS Definitions and Distinctions AM Program Budget Status AM Program Major Accomplishments WAMS Budget Status

More information

ELECTRIC RULE NO. 15 Sheet 1 DISTRIBUTION LINE EXTENSIONS

ELECTRIC RULE NO. 15 Sheet 1 DISTRIBUTION LINE EXTENSIONS Revised Cal. P.U.C. Sheet No. 20093-E Cancelling Revised Cal. P.U.C. Sheet No. 15575-E ELECTRIC RULE NO. 15 Sheet 1 APPLICABILITY: This rule is applicable to extension of electric Distribution Lines* of

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. PJM Interconnection, L.L.C. ) Docket No. ER14-

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. PJM Interconnection, L.L.C. ) Docket No. ER14- UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION PJM Interconnection, L.L.C. ) Docket No. ER14- AFFIDAVIT OF DR. SAMUEL A. NEWELL AND MR. CHRISTOPHER D. UNGATE ON BEHALF OF PJM

More information

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003 F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify

More information

PUBLIC UTILITIES COMMISSIO~t~ Docket No. DE 15-

PUBLIC UTILITIES COMMISSIO~t~ Docket No. DE 15- Th~NALZZ~ Exhibit STATE OF NEW HAMPSHIRE t~~eeee BEFORE THE FROM FILE PUBLIC UTILITIES COMMISSIO~t~ Liberty Utilities (Granite State Electric) Corp. dibla Liberty Utilities Calendar Year 2014 Reliability

More information

Syed Ahmed Richard Krause Southern California Edison

Syed Ahmed Richard Krause Southern California Edison An Electric Utility s Power Transmission Modernization Needs Syed Ahmed Richard Krause Southern California Edison 2 Presentation Outline Existing System Electric System Components, Basic Power System,

More information

APPENDIX D DISTRIBUTION WIRES ONLY RATE BASE

APPENDIX D DISTRIBUTION WIRES ONLY RATE BASE APPENDIX D PAGE 1 APPENDIX D DISTRIBUTION WIRES ONLY RATE BASE This appendix is composed of the following three parts: 1. Part I - Guidelines for determining the distribution or wires only assets and activities;

More information

Please Refer to Attached Sample Form

Please Refer to Attached Sample Form Pacific Gas and Electric Company San Francisco, California U 39 Revised Cal. P.U.C. Sheet No. 29987-G Cancelling Revised Cal. P.U.C. Sheet No. 22381-G Gas Sample Form No. 62-0982 Distribution and Service

More information

Overhead lines in Ireland

Overhead lines in Ireland Overhead lines in Ireland The value in Cigré Jarlath Doyle Abstract The main theme of my presentation is to give a brief overview of the valuable information and influence Cigré has and is having on the

More information

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055 Generation Interconnection Feasibility Study Report-Web Version For PJM Generation Interconnection Request Queue Position Z1-055 South Bend Generation Project March 2014 PJM Interconnection 2014. All rights

More information

Electric Operations Manager

Electric Operations Manager CITY OF ANAHEIM invites applications for the position of: Electric Operations Manager SALARY: $10,602.75 - $14,578.75 Monthly $127,233.00 - $174,945.00 Annually OPENING DATE: 04/07/16 CLOSING DATE: Continuous

More information

REQUEST FOR PROPOSALS For Natural Gas Pipeline Infrastructure and Transportation Services

REQUEST FOR PROPOSALS For Natural Gas Pipeline Infrastructure and Transportation Services REQUEST FOR PROPOSALS For Natural Gas Pipeline Infrastructure and Transportation Services Stillwater Electric Utilities A Division of Stillwater Utilities Authority City of Stillwater, Oklahoma Dated:

More information

Electricity from the Power Plant To the Consumer

Electricity from the Power Plant To the Consumer Electric Transmission Lines Electricity from the Power Plant To the Consumer The Nature of Electricity Electricity must be used as it is generated. Unlike other commodities, there is very little ability

More information

BEFORE THE MICHIGAN PUBLIC SERVICE COMMISSION

BEFORE THE MICHIGAN PUBLIC SERVICE COMMISSION BEFORE THE MICHIGAN PUBLIC SERVICE COMMISSION Electric Generation Alternatives Analysis for Proposed ) Permit, to Install No. 341-07, for an Advanced Supercritical ) Case No. U-15996 Pulverized Coal Boiler

More information

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114. Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position X1-114 Sandyston January 2012 Preface The intent of the System Impact Study is to determine

More information

Please state your name and position, business address and position with Virginia

Please state your name and position, business address and position with Virginia DIRECT TESTIMONY OF STEVEN A. EISENRAUCH ON BEHALF OF VIRGINIA ELECTRIC AND POWER COMPANY BEFORE THE STATE CORPORATION COMMISSION OF VIRGINIA CASE NO. PUE-2013-00020 1 2 Q. Please state your name and position,

More information

PREPARED DIRECT TESTIMONY OF MICHAEL R. WOODRUFF ON BEHALF OF SAN DIEGO GAS & ELECTRIC COMPANY AND SOUTHERN CALIFORNIA GAS COMPANY

PREPARED DIRECT TESTIMONY OF MICHAEL R. WOODRUFF ON BEHALF OF SAN DIEGO GAS & ELECTRIC COMPANY AND SOUTHERN CALIFORNIA GAS COMPANY Application No: A.1-0-01 Exhibit No.: Witness: M. Woodruff In The Matter of the Application of San Diego Gas & Electric Company (U 0 G) and Southern California Gas Company (U 0 G) for a Certificate of

More information

BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION

BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION BEFORE THE ARKANSAS PUBLIC SERVICE COMMISSION IN THE MATTER OF THE APPLICATION ) OF SOUTHWESTERN ELECTRIC POWER ) COMPANY FOR APPROVAL OF PROPOSED ) REVISIONS TO THE ENERGY COST ) RECOVERY RIDER TO RECOVER

More information

Regulation of Natural Gas Pipelines. June 23, 2008

Regulation of Natural Gas Pipelines. June 23, 2008 Regulation of Natural Gas Pipelines June 23, 2008 Federal and State Regulations Federal: 49 United States Code 60101. et. seq. Title 49 Code of Federal Regulations The Office of Pipeline Safety (OPS),

More information

FACT SHEET. BSES, Delhi - Distribution Network. Power Systems Consultancy from ABB

FACT SHEET. BSES, Delhi - Distribution Network. Power Systems Consultancy from ABB BSES, Delhi - Distribution Network improve power quality System design for optimal techno-economic distribution network based on current and future load forecast Analysis of existing sub-transmission and

More information

Report on Orange and Rockland Utilities, Inc. s Implementation of the Electric Safety Standards For the 12-Month Period Ending on November 30, 2005

Report on Orange and Rockland Utilities, Inc. s Implementation of the Electric Safety Standards For the 12-Month Period Ending on November 30, 2005 Report on Orange and Rockland Utilities, Inc. s Implementation of the Electric Safety Standards For the 12-Month Period Ending on November 30, 2005 Case 04-M-0159 Pearl River, NY January 15, 2006 Table

More information

Re: Preliminary Permit Application for the Rose Creek Pumped Storage Project

Re: Preliminary Permit Application for the Rose Creek Pumped Storage Project September 12, 2013 Kimberly D. Bose, Secretary Federal Energy Regulatory Commission 888 First Street, N.E. Washington, D.C. 20426 Re: Preliminary Permit Application for the Dear Ms. Bose, Please find attached

More information

S T A T E O F M I C H I G A N BEFORE THE MICHIGAN PUBLIC SERVICE COMMISSION * * * * *

S T A T E O F M I C H I G A N BEFORE THE MICHIGAN PUBLIC SERVICE COMMISSION * * * * * S T A T E O F M I C H I G A N BEFORE THE MICHIGAN PUBLIC SERVICE COMMISSION * * * * * In the matter of the application of ) CONSUMERS ENERGY COMPANY ) for certain relief in connection with the ) Case No.

More information

FINAL. Alternative Evaluation. for the. Proposed Burlington-Wray 230-kilovolt Transmission Project

FINAL. Alternative Evaluation. for the. Proposed Burlington-Wray 230-kilovolt Transmission Project FINAL Alternative Evaluation for the Proposed Burlington-Wray 230-kilovolt Transmission Project Prepared by Tri-State Generation and Transmission Association, Inc. 1100 W. 116th Avenue Westminster, Colorado

More information

GEORGIA TECH FOUNDATION, INC. COMMITTEE OPERATING PROCEDURES REAL ESTATE COMMITTEE

GEORGIA TECH FOUNDATION, INC. COMMITTEE OPERATING PROCEDURES REAL ESTATE COMMITTEE GEORGIA TECH FOUNDATION, INC. COMMITTEE OPERATING PROCEDURES REAL ESTATE COMMITTEE The Real Estate Committee is charged with overseeing all matters concerning real estate owned or operated by, or being

More information

APSC FILED Time: 9/26/2014 11:13:03 AM: Recvd 9/26/2014 11:01:49 AM: Docket 14-099-U-Doc. 1

APSC FILED Time: 9/26/2014 11:13:03 AM: Recvd 9/26/2014 11:01:49 AM: Docket 14-099-U-Doc. 1 Arkansas Public Service Commission Docket Summary Cover Sheet (For all dockets other than Rate Cases, "TD", "C" and "TF" Dockets Must be filed with each new docket filed at the Commission STYLE OF DOCKET:

More information

CITY OF GLENDALE CALIFORNIA REPORT TO CITY COUNCIL

CITY OF GLENDALE CALIFORNIA REPORT TO CITY COUNCIL FORM CM-36 CITY OF GLENDALE CALIFORNIA REPORT TO CITY COUNCIL February 7,2012 AGENDA ITEM Request for Approval to Issue a Request for Qualification (RFQ) of Firms, and Request for Proposal (RFP) to Engineer,

More information

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING Revised October, 2013 TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 REQUIRED DRAWINGS... 3 2.1 Site Plan... 3

More information

Tehachapi Renewable Transmission Project (TRTP)

Tehachapi Renewable Transmission Project (TRTP) SM Tehachapi Renewable Transmission Project (TRTP) February 2009 Why We Are Here Today Provide background on SCE s commitment to renewable energy Discuss the operational and economic importance of the

More information

Cellular Antenna Towers for Cellular Telecommunications Service or Personal Communications Services

Cellular Antenna Towers for Cellular Telecommunications Service or Personal Communications Services ARTICLE XV CELL TOWER REGULATIONS Cellular Antenna Towers for Cellular Telecommunications Service or Personal Communications Services Sect. 1500 Purpose The purposes of these regulations are: to provide

More information

Treasure Valley Electrical Plan

Treasure Valley Electrical Plan Treasure Valley Electrical Plan Community Advisory Committee January 25, 2006 Agenda 10 a.m. Welcome 10:10 a.m. Follow up DSM discussion 10:30 a.m. TVEP CAC process update 10:40 a.m. Transmission Presentation

More information

Manufacturing. Detailing. Transmission Structures. Quality. Reliability. Timely Delivery. Design. Prototyping. Testing. Supply. Towers.

Manufacturing. Detailing. Transmission Structures. Quality. Reliability. Timely Delivery. Design. Prototyping. Testing. Supply. Towers. Transmission Structures Design Detailing Prototyping Testing Manufacturing Supply Towers Poles Substation Structures Hardware Engineering Tower Testing Quality. Reliability. Timely Delivery. SAE Towers

More information

NTUA GUIDELINES FOR DESIGNING AN ELECTRICAL POWER DISTRIBUTION SYSTEM FOR NEW DEVELOPMENTS

NTUA GUIDELINES FOR DESIGNING AN ELECTRICAL POWER DISTRIBUTION SYSTEM FOR NEW DEVELOPMENTS NTUA GUIDELINES FOR DESIGNING AN ELECTRICAL POWER DISTRIBUTION SYSTEM FOR NEW DEVELOPMENTS These guidelines are intended to familiarize Developers regarding some issues that are important to get electric

More information

ARKANSAS DEPARTMENT OF EDUCATION RULES GOVERNING THE ISSUANCE OF SUBPOENAS BY THE ARKANSAS STATE BOARD OF EDUCATION

ARKANSAS DEPARTMENT OF EDUCATION RULES GOVERNING THE ISSUANCE OF SUBPOENAS BY THE ARKANSAS STATE BOARD OF EDUCATION ARKANSAS DEPARTMENT OF EDUCATION RULES GOVERNING THE ISSUANCE OF SUBPOENAS BY THE ARKANSAS STATE BOARD OF EDUCATION 1.00 REGULATORY AUTHORITY 1.01 These rules shall be known as the Arkansas Department

More information

VILLAGE OF PLEASANT PRAIRIE COMMERCIAL COMMUNICATION PERMIT

VILLAGE OF PLEASANT PRAIRIE COMMERCIAL COMMUNICATION PERMIT VILLAGE OF PLEASANT PRAIRIE COMMERCIAL COMMUNICATION PERMIT CLASS 1 COLLOCATION New Commercial Communication Structure Substantial Modification Please check one of the following: CLASS 2 COLLOCATION OTHER

More information

On behalf of Ozarks Electric Cooperative Corporation, I respectfully submit the following documents for electronic filing in this matter:

On behalf of Ozarks Electric Cooperative Corporation, I respectfully submit the following documents for electronic filing in this matter: APSC FILED Time: 2/19/2015 10:00:04 AM: Recvd 2/19/2015 9:51:40 AM: Docket 15-012-tf-Doc. 1 February 19, 2015 Mr. Dallas Heltz Secretary of the Commission Arkansas Public Service Commission 1000 Center

More information

THE STATE OF NEW HAMPSHIRE BEFORE THE NEW HAMPSHIRE PUBLIC UTILITIES COMMISSION. Docket No. VIVINT SOLAR, INC. PETITION FOR DECLARATORY RULING

THE STATE OF NEW HAMPSHIRE BEFORE THE NEW HAMPSHIRE PUBLIC UTILITIES COMMISSION. Docket No. VIVINT SOLAR, INC. PETITION FOR DECLARATORY RULING THE STATE OF NEW HAMPSHIRE BEFORE THE NEW HAMPSHIRE PUBLIC UTILITIES COMMISSION Docket No. VIVINT SOLAR, INC. PETITION FOR DECLARATORY RULING I. Introduction Pursuant to N.H. Code Admin. R. Ann. PUC 203

More information

Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva

Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva Issued: August 2009 SIZED UP TO 100 KVA TABLE OF CONTENTS 1.0 Introduction... 1 1.1 Applicability... 1 1.2 Definitions...

More information

CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska. February 10, 2014

CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska. February 10, 2014 CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska February 10, 2014 QUESTIONS AND ANSWERS TO: Prospective Proposers FROM: Chugach Electric Association, Inc. 5601 Electron Drive Anchorage, Alaska SUBJECT:

More information

Exhibit C SCE Depreciation Testimony in 2015 CPUC General Rate Case

Exhibit C SCE Depreciation Testimony in 2015 CPUC General Rate Case Exhibit C SCE Depreciation Testimony in 2015 CPUC General Rate Case DOCKET DIRECT TESTIMONY of DANE A. WATSON on behalf of SOUTHERN CALIFORNIAL EDISON COMPANY (Revenue Requirement) (Filename: DWatsonRRDirect.doc)

More information

Attachment 2-1 Distribution System Plan Attachment 2-2 OEB Appendix 2-FA and 2-FC REG Expansion Investment

Attachment 2-1 Distribution System Plan Attachment 2-2 OEB Appendix 2-FA and 2-FC REG Expansion Investment Waterloo North Hydro Inc. EB-2015-0108 Exhibit 2 Page 1 of 95 Filed: May 1, 2015 TABLE OF CONTENTS 2.5 EXHIBIT 2 - RATE BASE.... 2 2.5.1 Rate Base...2 2.5.1.1 Overview... 2 2.5.1.2 Gross Assets Property

More information

IESO Supply Deliverability Guidelines

IESO Supply Deliverability Guidelines PUBLIC IMO_GDL_0021 IESO Supply Deliverability Guidelines Issue 3.0 This document is to be used to evaluate long-term system adequacy and connection assessments Public Disclaimer The posting of documents

More information

#1258. WHEREAS, the Board of Commissioners of the Township of Haddon has determined the following:

#1258. WHEREAS, the Board of Commissioners of the Township of Haddon has determined the following: #1258 ORDINANCE OF THE TOWNSHIP OF HADDON, COUNTY OF CAMDEN AND STATE OF NEW JERSEY SUPPLEMENTING, AMENDING AND REVISING CHAPTER 142-38 OF THE TOWNSHIP OF HADDON ENTITLED, CONDITIONAL USES WHEREAS, The

More information

APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT

APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT APPLICATION FOR DEMOLITION & RIGHT-OF OF-WAY PERMIT City of Swartz Creek 8083 Civic Drive Swartz Creek, MI 48473 810-635-4464 Fee Received: $ Date: / / Receipt No: Demolition Permit (including Right of

More information

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF COLORADO

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF COLORADO BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF COLORADO IN THE MATTER OF THE APPLICATION OF ) PUBLIC SERVICE COMPANY OF ) COLORADO FOR A CERTIFICATE OF PUBLIC CONVENIENCE AND NECESSITY DOCKET NO.

More information

The Impact of Transmission Cable System Construction and Design on Commissioning Test Options & Results

The Impact of Transmission Cable System Construction and Design on Commissioning Test Options & Results The Impact of Transmission Cable System Construction and Design on Commissioning Test Options & Results Steve Campbell General Cable Benjamin Lanz IMCORP Subcommittee A ICC Meeting in Fountain Hills, AZ

More information

SWITCH BUSINESS SOLUTIONS, LLC FIRST AMENDMENT TO REVOCABLE RIGHTS-OF-WAY LICENSE AGREEMENT

SWITCH BUSINESS SOLUTIONS, LLC FIRST AMENDMENT TO REVOCABLE RIGHTS-OF-WAY LICENSE AGREEMENT SWITCH BUSINESS SOLUTIONS, LLC FIRST AMENDMENT TO REVOCABLE RIGHTS-OF-WAY LICENSE AGREEMENT This First Amendment to Revocable Rights-of-Way License Agreement (this "Amendment") is made as of January 5,2009

More information

Section 1: Executive Summary

Section 1: Executive Summary Section 1: Executive Summary SECTION 1: EXECUTIVE SUMMARY 1.1 SECTION PURPOSE This report has been prepared for the Nevada Energy Assistance Corporation (NEAC), a 501(c)(3) non-profit agency; in support

More information

Funding the Vision: Investing in Safe, Reliable Service

Funding the Vision: Investing in Safe, Reliable Service Funding the Vision: Investing in Safe, Reliable Service KUB Financial Plan Executive Summary Fiscal Year 2015 Table of Contents Funding The Vision: Investing in Safe, Reliable Service 1 KUB Proposed Fiscal

More information

PSYCHIATRIC RESIDENTIAL TREATMENT FACILITY APPLICATION FORM ARKANSAS HEALTH SERVICES PERMIT COMMISSION

PSYCHIATRIC RESIDENTIAL TREATMENT FACILITY APPLICATION FORM ARKANSAS HEALTH SERVICES PERMIT COMMISSION PSYCHIATRIC RESIDENTIAL TREATMENT FACILITY APPLICATION FORM ARKANSAS HEALTH SERVICES PERMIT COMMISSION ARKANSAS HEALTH SERVICES PERMIT AGENCY 5800 WEST 10TH STREET, SUITE 805 LITTLE ROCK, ARKANSAS 72204

More information

RECORD OF PLAN CONFORMANCE AND CATEGORICAL EXCLUSION (CX) DETERMINATION

RECORD OF PLAN CONFORMANCE AND CATEGORICAL EXCLUSION (CX) DETERMINATION RECORD OF PLAN CONFORMANCE AND CATEGORICAL EXCLUSION (CX) DETERMINATION CX Log #: DOI-BLM-OR-V060-2015-032-CX CE Exemption category: 516 DM 11.9, E.12: Grants of right-of-way wholly within the boundaries

More information

All routes and route segments included in this notice are available for selection and approval by the Public Utility Commission of Texas.

All routes and route segments included in this notice are available for selection and approval by the Public Utility Commission of Texas. Application of Brazos Electric Power Cooperative, Inc. to Obtain a Certificate of Convenience and Necessity for a Proposed Transmission Line in Denton County, Texas PUBLIC UTILITY COMMISSION OF TEXAS (PUC)

More information

RR1-455 of 566 00584

RR1-455 of 566 00584 DOCKET NO. 00 APPLICATION OF SOUTHWESTERN PUBLIC SERVICE COMPANY FOR AUTHORITY TO CHANGE RATES AND TO RECONCILE FUEL AND PURCHASED POWER COSTS FOR THE PERIOD JULY 1, 01 THROUGH JUNE 0, 01 PUBLIC UTILITY

More information

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems This Agreement is made and entered into this day of, 20, ( Effective Date ) by and between the Orlando Utilities Commission

More information

By Manitoba Hydro, March 4 th 2013

By Manitoba Hydro, March 4 th 2013 Rebuttal to Bipole III Coalition underground cable report Potential Use of Underground Cables for Sections of the Planned 500 kvdc Bipole III Overhead Line in Manitoba By Manitoba Hydro, March 4 th 2013

More information

CHECKLIST FOR TELECOMMUNICATION TOWER CO-LOCATION APPLICATIONS. Conditional Use Permit Approved by Board of Supervisors Date of approval:

CHECKLIST FOR TELECOMMUNICATION TOWER CO-LOCATION APPLICATIONS. Conditional Use Permit Approved by Board of Supervisors Date of approval: CHECKLIST FOR TELECOMMUNICATION TOWER CO-LOCATION APPLICATIONS Conditional Use Permit Approved by Board of Supervisors Date of approval: Site Plan Approval: Date of approval: Fees: $4,000 Licensed Co-location

More information

TEMPORARY CONSTRUCTION AND PERMANENT UTILITY EASEMENT AGREEMENT RECITALS

TEMPORARY CONSTRUCTION AND PERMANENT UTILITY EASEMENT AGREEMENT RECITALS TEMPORARY CONSTRUCTION AND PERMANENT UTILITY EASEMENT AGREEMENT This temporary Construction and Permanent Utility Easement Agreement (the Agreement ) is entered into by and between, ( Grantor ); and, (

More information

Commercial Electricity and Natural Gas Supply Services Cooperative Program Application

Commercial Electricity and Natural Gas Supply Services Cooperative Program Application Commercial Electricity and Natural Gas Supply Services Cooperative Program Application Customer Location: AUTHORIZATION TO OBTAIN BILLING, PAYMENT HISTORY, ACCOUNT SERVICE DATA, AND CREDIT DATA Legal Customer

More information

National Science Foundation Funds Request

National Science Foundation Funds Request University Corporation for Atmospheric Research National Science Foundation Funds Request 1. (NSF USE ONLY) 2. FACILITY NAME & LOCATION 3. PROJECT NAME 4. UCAR TRACKING NUM. NCAR Mesa Lab 15KV FEEDER REPLACEMENT

More information

Colorado PUC E-Filings System

Colorado PUC E-Filings System BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF COLORADO DOCKET NO. 1A E IN THE MATTER OF THE APPLICATION OF BLACK HILLS/COLORADO ELECTRIC UTILITY COMPANY, LP, FOR A CERTIFICATE OF PUBLIC CONVENIENCE

More information

Scope of Restoration Plan

Scope of Restoration Plan RWG Area Restoration Review Worksheet (10/28/09) EOP-006-02 Directory 8 EOP-005 NYSRG Rule G Text Restoration Plan Requirement R1.Each Reliability Coordinator shall have a Reliability Coordinator Area

More information

Lifecycle Strategy DISPOSAL AND DIVESTMENT

Lifecycle Strategy DISPOSAL AND DIVESTMENT Lifecycle Strategy DISPOSAL AND DIVESTMENT Document 07/10/2013 Page 1 of 19 C O P Y R I G H T 2013 T R A N S P O W E R N E W Z E A L A N D L I M I T E D. A L L R I G H T S R E S E R V E D This document

More information

How To Build A 230 Kv Transmission Line In Orange County

How To Build A 230 Kv Transmission Line In Orange County STANDARD APPLICATION FOR A CERTIFICATE OF CONVENIENCE AND NECESSITY FOR A PROPOSED TRANSMISSION LINE AND APPLICATION FOR A CERTIFICATE OF CONVENIENCE AND NECESSITY FOR A PROPOSED TRANSMISSION LINE PURSUANT

More information

Before the New Hampshire Public Utilities Commission DE 15-464. Public Service Company of New Hampshire d/b/a Eversource Energy. Motion to Intervene

Before the New Hampshire Public Utilities Commission DE 15-464. Public Service Company of New Hampshire d/b/a Eversource Energy. Motion to Intervene Before the New Hampshire Public Utilities Commission DE 15-464 Public Service Company of New Hampshire d/b/a Eversource Energy Petition for Approval of Lease Agreement between PSNH dba Eversource Energy

More information

Wind Turbine Technology Overview

Wind Turbine Technology Overview Wind Turbine Technology Overview Course No: M01-009 Credit: 1 PDH Brian McCaffrey, P.E. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)

More information

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE This section provides substation design information for Load Entities interconnected at transmission voltage

More information

Electric system improvements near you South and West of Edmonton Area Transmission Development

Electric system improvements near you South and West of Edmonton Area Transmission Development Electric system improvements near you South and West of Edmonton Area Transmission Development SAUNDERS LAKE SUBSTATION AND TRANSMISSION LINES January 2014 Volume 2 PLEASE NOTE: We want to inform you that

More information

PUBLIC UTILITY COMMISSION OF TEXAS (PUC) DOCKET NO. 37529

PUBLIC UTILITY COMMISSION OF TEXAS (PUC) DOCKET NO. 37529 Application of Oncor lectric Delivery Company LLC to Obtain or Amend a Certificate of Convenience and Necessity for a Proposed CRZ 345 kv Transmission Line in Nolan, Taylor and Runnels Counties, Texas

More information

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas ENERGY NETWORKS ASSOCIATION Electricity Industry EMF Measurement Protocol for High Field Areas Contents 1 Introduction 1.1 Background 1.2 High Field Areas 2 High Field Area - Generation Businesses 2.1

More information

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE Toll Free Telephone Numbers Residential Services 800.454.3853 Commercial Services 800.653.5307 Utility Locating Company N.C. 800.632.4949 S.C. 888.721.7877

More information

Square D Company P. O. Box 729 Houston, Texas 77001 Business Phone: 713-222-9195

Square D Company P. O. Box 729 Houston, Texas 77001 Business Phone: 713-222-9195 JOHN A. GRISWOLD Square D Company P. O. Box 729 Houston, Texas 77001 Business Phone: 713-222-9195 Education Deer Park High School - Deer Park, Texas 1989 Graduate Professional Certifications AVO Training

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

University of Denver, MBA, Business Administration, 1973 Regis University, BS, Business Administration, 1972

University of Denver, MBA, Business Administration, 1973 Regis University, BS, Business Administration, 1972 Resume of Michael J. McFadden MICHAEL J. MCFADDEN AREAS OF QUALIFICATION Rates, regulatory affairs, strategic planning, electric and gas utility operations, corporate finance, financial analysis, asset

More information

FIXED CHARGE: This is a cost that goes towards making the service available, including

FIXED CHARGE: This is a cost that goes towards making the service available, including ELECTRICITY BILL COMPONENTS FIXED CHARGE: This is a cost that goes towards making the service available, including installation and maintenance of poles, power lines and equipment, and 24-hour customer

More information

Chesapeake Regulatory Consultants, Inc 1698 Saefern Way Annapolis, MD 21401-6529

Chesapeake Regulatory Consultants, Inc 1698 Saefern Way Annapolis, MD 21401-6529 Chesapeake Regulatory Consultants, Inc 1698 Saefern Way Annapolis, MD 21401-6529 Phone: 410.849.3210 email: rgtsbs@comcast.net Robert G. Towers Basil L. Copeland, Jr. David E. Peterson December 17, 2009

More information