I-7C7. Series 7C7 Air Maintenance/Compressor Assembly WARNING NOTICE INSTALLATION INSTRUCTIONS

Similar documents
I-768 FireLock NXT Dry Valve

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

Compressor Service & Maintenance Manual

BERMAD Fire Protection

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

PC1130 Electric Air Compressor

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

PC1131 Electric Air Compressor

ROUGHNECK II Pumpless Drain

Float and Thermostatic Traps Series H, C and X

! WARNING. Before using product, read and understand instructions.

Number Wheeler P/N Description Set Rex P/N Notes Base 1 J Support, Right 1 J Support, Left 1 J Nut (M8)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual

Utility Distribution Systems

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

How To Replace A Reverse Osmosis Water Tank

TECHNICAL DATA. Dry 122a. November 12, 2013

OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION

accidents which arise due to nonobservance and the safety information herein.

DV-5 Deluge Valve with Remote-Resetting, Pressure-Reducing Trim 4 Inch and 6 Inch (DN100 and DN150) General Description.

LIEBERT VNSA Installation Sheet

SunMaxx Solar Filling Station Operating Instructions

Number Wheeler P/N Description Set Rex P/N Notes

Volkswagen Jetta, Golf, GTI 1999, 2000 Brake System 47 Brakes - Hydraulic Components (Page GR-47)

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

AMERBRITE UNDERWATER WHITE LED POOL LAMP

123 Industrial Loop Road Paynesville, MN Phone:

Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation

Buy Karcher Parts Online: Need Technical Help? Call: Requests to:

Product Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description

7.1. Part Lists. Hardware Insertion Machine. Instructions. Instructions

SELECTION, APPLICATION AND MAINTENANCE

Series Hose Reels

VOYAGER 570G. 744A Sprayer Control

Your safety and the safety of others are very important.

Technical Data. Installation

123 Industrial Loop Road Paynesville, MN Phone: MASTER MANUFACTURING MASTER GARDNER

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

BERMAD Fire Protection

Model 43AP Pneumatic Controller, Style B

Pallet Jack. OWNER S MANUAL Model MH1230. Important Safety Instructions Assembly Instructions Parts and Hardware Identification

Please also see 10 golden rules for correct Saniflo installation on

Not required for most applications Not required for most applications High pressure ( provided) High pressure ( provided)

Oil and Coolant Circulating Heating System. Model - OCSM

Self Purging Liquid Trap (SPLT ) User s Manual

ETZGAR CONVEYOR COMPANY Controls Section v12.05

Line to Refrigerator Ice/Water Dispenser

Unit 24: Applications of Pneumatics and Hydraulics

MODEL G300 BRAKE BLEEDER

TD01211 PIN: NX nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

FANG 24T, 26T and 28T -EU

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page Phase Simplex Page 8-13

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

OPL BASIC. Dosing System for Professional Laundry machines. Contents

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

DANGER DANGER. General Information. Safety Is Your Responsibility. Ordering Parts. Contact Information

MACBlower Model Number: MAC40R MAC60R MAC80R MAC100R. MAC120R MAC150R MAC 200R Serial #

300 SERIES 331, 332, 333, 344, 356 AND 367 MODELS

Lawn Sprinkler Systems Reserve Irrigation Inc. O & M. Version Roseland Drive Macedonia, Ohio

Operating Instructions

MCR1900 Media Converter 19-Slot Chassis

CTV-1500 Cooling Tower Vacuum Operating & Maintenance Manual

INSTALLATION & OPERATING INSTRUCTIONS

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

Power Cube Open Source Ecology Page 1. Power Cube. Version 4

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

15GAL STEEL OIL DRAIN WITH 110V PUMP

PRODUCT RELEASE CKMTA12 / 24. Copyright 2011 by ARB Corporation Limited

Preaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description

2 HP / 4 GALLON AIR COMPRESSOR OWNER'S MANUAL

INSTRUCTION MANUAL A REVISION A. Series E1 and E3 Instant Hot Water Recirculating Systems

Overview PARTS LIST. B. Lever mounting base C. Flush handle assembly D. Grey/Blue float stop E. Grey float (Full Flush) F. Flush valve washer

PRESSURE REDUCING CONTROL VALVE

Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:

Installation Instructions

Number Wheeler P/N Description Set Rex P/N Notes

VE17 DSP. Model: VE-17DS. Lista Części Polish

Mono-Block II Installation & Operation Manual

Model 5600SE Downflow

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS

MBSAW. Meat Cutting Band Saw With Meat Grinder Assembly & Operating Instructions

POSEIDON 2-29, 2-25 & 2-22 POSEIDON 2-29, 2-25 & 2-22 XT

INSTALLATION INSTRUCTIONS

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

FILLING AND PURGING THE SYSTEM

Fleck Service Manual INSTALLATION AND START-UP PROCEDURE TABLE OF CONTENTS JOB SPECIFICATION SHEET

JOB or CUSTOMER: ENGINEER: CONTRACTOR: SUBMITTED BY: SPECIFICATION REF: QUANTITY TAG NO. MODEL NO. GPM FEET LEAD LENGTH COMMENTS.

System Accessories Pricing. Page 0 Effective 7/02

Morrison Bros. Co. General Product Specifications

Industrial Hydraulic Remote Controlled Monitor

Parts. Ultra 395/495/595t Ultra Max II 490/495/595t V 120 VAC psi (228 bar, 22.8 MPa) Maximum Working Pressure.

9013 PUMPTROL Commercial Pressure Switches Type F and 9013 Commercial Pressure Switches Type G. January. Catalog

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

Transcription:

INSTALLATION INSTRUCTIONS I-7C7 Series 7C7 Air Maintenance/Compressor Assembly WARNING Read and understand all instructions before attempting to install any Victaulic piping products. Depressurize and drain the piping system before attempting to install, remove, adjust, or perform maintenance on any Victaulic products. Wear safety glasses, hardhat, and foot protection when working with Victaulic piping products. Any activities that require taking the valve out of service may eliminate the fire protection provided by the system. Before removing the valve from service, notify the authority having jurisdiction. Consideration of a fire patrol should be given for the affected areas. Failure to follow these instructions could result in serious personal injury and/or property damage. EXPLODED VIEW DRAWING AND DESCRIPTION AIR MAINTENANCE TRIM OF THE SERIES 7C7 The Series 7C7 Air Maintenance/Compressor Assembly is comprised of air maintenance trim and a 1/6-Hp, 1/3-Hp, 1/2-Hp, or 3/4-Hp (for international use only) air compressor. This assembly is designed to control system air pressure for Series 768 FireLock NXT Dry Valves, Series 764 FireLock NXT Alternate Wet/Dry Valves, and Series 769 FireLock NXT Deluge and Preaction Valves (pneumatic systems). A decrease in air pressure will close the pressure switch. When the pressure switch closes, the air compressor turns on to restore air pressure. When air pressure is restored, the air compressor turns off, and pressure in the compressor automatically bleeds off through the release valve of the pressure switch. The release valve protects the air compressor from startup overload.. Bill of Materials Item Qty. Description 1 1 Restrictor (½-inch NPT) 2 1 Strainer (½-inch NPT) 3 1 Swing Check (½-inch NPT) 4 1 Slow-Fill Ball Valve (Normally Open) 1 Spring-Loaded, Soft-Seated Ball Check Valve 6 1 Pressure Switch 7 1 Compression Fitting, Straight (¼-inch NPT x ¼-inch Tube) 8 1 Compression Fitting, 9 Elbow (¼-inch NPT x ¼-inch Tube) 9 1 Copper Tubing (¼-inch OD) 1 Fast-Fill Ball Valve (Normally Closed) 11 1 Pressure Switch Isolation Ball Valve (Normally Open - Lockable) 9 Exaggerated for Clarity 7 2 8 NOTICE 6 11 1 3 4 To ½-inch NPT Nipple of Series 7C7 Assembly ONLY ONE SYSTEM IS ALLOWED PER SERIES 7C7 AIR MAINTENANCE/COMPRESSOR ASSEMBLY. AIR SUPPLY REQUIREMENTS The required air pressure for Series 768 FireLock NXT Dry Valves, Series 764 FireLock NXT Alternate Wet/Dry Valves, and Series 769 FireLock NXT Deluge and Preaction Valves is 13 psi/.9 Bar minimum, regardless of the system supply water pressure. Normal air pressure should not exceed psi/1.2 Bar. Victaulic presets the Series 7C7 Air Maintenance/Compressor Assembly to the recommended air pressure of 13 psi/.9 Bar as the on or low pressure setting for the compressor and psi/1.2 Bar as the off or high pressure setting. Failure to maintain air pressure within the 13-psi/.9-Bar to -psi/ 1.2-Bar range could delay system operation response time. The Series 7C7 Air Maintenance/Compressor Assembly MUST NOT be used on a Series 768 or Series 769 FireLock NXT Valve installed with a Series 746 or Series 746-LPA Dry Accelerator, unless a tank and air regulator are added. ELECTRICAL REQUIREMENTS 1/6-Hp compressor is available for 1-volt AC/6 Hz operation The 1/3-Hp compressor is available standard for low-voltage, 1-volt AC/6 Hz operation. In addition, high-voltage, 22-volt, single-phase AC/ - 6 Hz operation for international use is available. 1/2-Hp compressor is available for 1-volt AC/ - 6 Hz operation The 3/4-Hp compressor is available for international use only. A 22-volt, single-phase AC/ Hz option or a 22-volt, single-phase AC/6 Hz option is available. COMPRESSOR CAPACITIES The engineer/system designer is responsible for sizing the compressor so that the entire system is charged to the required air pressure within NFPA guidelines ( minutes). DO NOT oversize the compressor to provide more airflow. An oversized compressor will slow down or possibly prevent valve operation. Nominal AC Voltage/ Capacity WITH Capacity WITHOUT Hz Pressure Time Auto Vent Auto Vent Amp Hp (+/- %) psi/bar Minutes gallons/m 3 gallons/m 3 Draw 1/6 1/6 17 27 1.2.7 1.1 2.1 Amps 1/3 1/6 37 2 1.2 1.4 2. 3.6 Amps 1/3 22/ 16 23 1.2.6.9 1/3 22/ 4 66 6 1.2 1.7 2. 1.8 Amps 1/3 22/6 37 4 1.2 1.4 1. 1/2 1/ 66 67 1.2 2. 2. 1/2 1/6 78 8 1.2 3. 3.1 6.6 Amps 3/4 22/ 6 67 1.2 2.3 2. 3/4 22/6 7 77 1.2 2.7 2.9 3/4 22/ 12 13 6 1.2 4.. 3.8 Amps 3/4 22/6 137 12 6 1.2.2.8 NOTE: Refer to the charts on the following pages for minimum required fill capacities to 13 psi/.9 Bar. Low air alarms will clear at 13 psi/.9 Bar. In addition, these charts contain higher capacities to psi/1.2 Bar that are not shown in the table above. I-7C7_1

EXPLODED VIEW DRAWING - SERIES 7C7 AIR MAINTENANCE COMPRESSOR ASSEMBLY WITH 1/6-HP COMPRESSOR 14 1 3 9 11 12 2 8 13 7 6 1 To Actuator Trim 4 Bill of Materials Item Qty. Description 1 1 Compressor 2 1 Mounting Bracket 3 1 Series 77P Air Maintenance Trim Assembly with Pressure Switch 4 1 Stainless Steel Braided Flex Hose 2 Hose Clamp 6 3 Hex-Head Bolt 7 3 Lock Washer 8 1 Identification Tag 9 1 Straight Connector, Flexible Cord 1 Connector, Flexible Cord 11 1 Liquid-Tight Conduit 12 3 #8 U-Style Wire Connector 13 1 Identification Label* 14 1 Strain Relief Connector* 1 1 14 AWG Grounded Cord with Plug* * NOTE: Items 13-1 apply only to the CSA version Exaggerated for Clarity Series 7C7 with 1/6-hp (1 VAC) Compressor and Auto Vent Series 7C7 with 1/6-hp (1 VAC) Compressor and No AutoVent 7 psi psi 13 psi 6 13 psi 2 Time (Minutes) 4 2 1 2 2 3 4 1 2 2 3 4 System Size (gallons) System Size (Gallons) I-7C7_2

EXPLODED VIEW DRAWING - SERIES 7C7 AIR MAINTENANCE COMPRESSOR ASSEMBLY WITH 1/3-HP COMPRESSOR 16 1 11 3 12 9 13 14 2 6 1 To Actuator Trim 7 8 4 Bill of Materials Item Qty. Description 1 1 Compressor 2 1 Mounting Bracket 3 1 Series 77P Air Maintenance Trim Assembly with Pressure Switch 4 1 Stainless Steel Braided Flex Hose 2 Hose Clamp 6 4 Hex-Head Bolt 7 4 Lock Washer 8 4 Hex Nut 9 2 Straight Conduit Connector 1 Liquid-Tight Conduit 11 2 14 AWG, 3-Strand Cable 12 3 #8 U-Style Wire Connector 13 1 Identification Tag 14 1 Identification Label* 1 1 Strain Relief Connector* 16 1 14 AWG Grounded Cord with Plug* * NOTE: Items 14-16 apply only to the CSA version Exaggerated for Clarity Series 7C7 with 1/3-hp (1 VAC) Compressor and Auto Vent Series 7C7 with 1/3-hp (1 VAC) Compressor and No Auto Vent 6 psi 13 psi psi Time (Minutes) 4 13 psi 2 2 1 2 2 3 4 4 6 6 7 7 System Size (Gallons) 1 2 2 3 4 4 6 6 7 7 System Size (gallons) NOTE: Refer to the following page for charts reflecting the 22-volt 1/3-hp option. I-7C7_3

CHARTS FOR THE 1/3-HP COMPRESSOR, 22-VOLT OPTION 22-volt Option Series 7C7 with 1/3-hp (22-24 VAC, -Hz) Compressor and Auto Vent 22-volt Option Series 7C7 with 1/3-hp (22-24 VAC, 6-Hz) Compressor and Auto Vent 6 1.2 Bar.9 Bar 6 1.2 Bar 4 4.9 Bar 2 2.2.6 1. 1.4 1.8 2.2 2.6 3. System Size (cubic meters).2.4.6.8 1. 1.2 1.4 1.6 1.8 2. 2.2 2.4 2.6 2.8 System Size (cubic meters) 22-volt Option Series 7C7 with 1/3-hp (22-24 VAC, Hz) Compressor and No AutoVent 7 6 1.2 Bar 4.9 Bar 2. 1. 1. 2. 2. 3. System Size/Volume (cubic meters) 22-volt Option Series 7C7 with 1/3-hp (22-24 VAC, 6 Hz) Compressor and No Auto Vent 6 1.2 Bar 4 2.9 Bar. 1. 1. 2. 2. 3. System Size/Volume (cubic meters) I-7C7_4

EXPLODED VIEW DRAWING - SERIES 7C7 AIR MAINTENANCE COMPRESSOR ASSEMBLY WITH 1/2-HP COMPRESSOR 16 9 14 3 1 8 11 14 2 12 6 7 1 13 To Actuator Trim 4 Bill of Materials Item Qty. Description 1 1 Compressor 2 1 Mounting Bracket 3 1 Series 77P Air Maintenance Trim Assembly with Pressure Switch 4 1 Stainless Steel Braided Flex Hose 2 Hose Clamp 6 4 Lock Washer 7 4 Hex Nut 8 2 Straight Conduit Connector 9 1 Liquid-Tight Conduit 1 14 AWG, 3-Strand Cable 11 3 #8 U-Style Wire Connector 12 1 Identification Tag 13 1 Compressor Air Intake Filter 14 1 Identification Label* 1 1 Strain Relief Connector* 16 1 14 AWG Grounded Cord with Plug* * NOTE: Items 14-16 apply only to the CSA version Exaggerated for Clarity Series 7C7 with 1/2-hp (1 VAC, Hz) Compressor and Auto Vent Series 7C7 with 1/2-hp (1 VAC, Hz) Compressor and No Auto Vent psi 4 psi 4 4 3 2 2 13 psi 2 13 psi 1 1 2 2 3 4 4 6 6 7 7 8 8 9 9 System Size (gallons) 1 2 2 3 4 4 6 6 7 7 8 8 9 9 1 System Size (gallons) 4 Series 7C7 with 1/2-hp (1 VAC, 6-Hz) Compressor and Auto Vent psi Series 7C7 with 1/2-hp (1 VAC, 6 Hz) Compressor and No Auto Vent 3 13 psi 4 psi 2 2 1 2 13 psi 1 2 2 3 4 4 6 6 7 7 8 8 9 9 1 11 12 System Size (gallons) 2 7 12 17 22 27 32 37 42 47 2 7 62 67 72 77 82 87 92 97 2 7 112 117 122 System Size (gallons) I-7C7_

EXPLODED VIEW DRAWING - SERIES 7C7 AIR MAINTENANCE COMPRESSOR ASSEMBLY WITH 3/4-HP COMPRESSOR 1 9 14 3 2 12 7 13 To Actuator Trim Bill of Materials Item Qty. Description 1 1 Compressor 2 1 Mounting Bracket 3 1 Adapter Plate 4 1 Series 77P Air Maintenance Trim Assembly with Pressure Switch 1 Liquid-Tight Connector, Conduit 6 1 Stainless Steel Braided Flexible Hose 7 4 Helical Spring-Lock Washer 8 4 Hex Nut 9 4 Hex Bolt 4 Helical Spring-Lock Washer 11 4 Hex Nut 12 1 Identification Label 13 2 Hose Clamp 14 1 Liquid-Tight Flexible Conduit 4 8 11 6 Exaggerated for Clarity I-7C7_6

CHARTS FOR THE 3/4-HP COMPRESSOR, 22-VOLT OPTION 6 22-volt Option Series 7C7 with 3/4-hp (22-24 VAC, -Hz) Compressor and Auto Vent 1.2 Bar 4.9 Bar 2.4.6.8 1. 1.2 1.4 1.6 1.8 2. 2.2 2.4 2.6 2.8 3. 3.2 3.4 3.6 3.8 4. 4.2 4.4 4.6 6 System Size (cubic meters) 22-volt Option Series 7C7 with 3/4-hp (22-24 VAC, 6-Hz) Compressor and Auto Vent 1.2 Bar 4.9 Bar 2.4.6.8 1. 1.2 1.4 1.6 1.8 2. 2.2 2.4 2.6 2.8 3. 3.2 3.4 3.6 3.8 4. 4.2 4.4 4.6 4.8..2 6 System Size (cubic meters) 22-volt Option Series 7C7 with 3/4-hp (22-24 VAC, -Hz) Compressor and No Auto Vent 1.2 Bar 4.9 Bar 2.8 1. 1.2 1.4 1.6 1.8 2. 2.2 2.4 2.6 2.8 3. 3.2 3.4 3.6 3.8 4. System Size (cubic meters) 4.2 4.4 4.6 4.8..2 6 22-volt Option Series 7C7 with 3/4-hp (22-24 VAC, 6-Hz) Compressor and No Auto Vent 1.2 Bar 4 2.9 Bar.8 1. 1.2 1.4 1.6 1.8 2. 2.2 2.4 2.6 2.8 3. 3.2 3.4 3.6 3.8 4. System Size (cubic meters) 4.2 4.4 4.6 4.8..2.4.6.8 I-7C7_7

INSTALLATION OF THE SERIES 7C7 AIR MAINTENANCE/COMPRESSOR ASSEMBLY NOTICE Two people are required to install the Series 7C7 properly and safely. Make sure the Series 7C7 is mounted in the correct orientation. Due to the swing check valve in the air maintenance trim, the compressor can be mounted vertically or horizontally. 1. Mount the Series 7C7 Air Maintenance/Compressor Assembly on the riser with the hose clamps provided. When mounting the assembly on the riser, take into account the 26-inch/66-mm length of stainless steel braided flex hose that will be installed from the elbow in the air maintenance trim into the air manifold in the actuator trim. Make sure the hardware is tightened completely. 3. Connect the 1/2-inch/13-mm stainless steel braided flex hose to the fitting in the air manifold, as indicated in the trim drawings. NOTE: Ensure the rubber washer is captured in the hose nut to prevent air leakage. 2. Install the fitting from the 1/2-inch/13-mm stainless steel braided flex hose into the air manifold in the actuator trim, as shown above. I-7C7_8

I-7C7 / Series 7C7 Air Maintenance/Compressor Assembly / Installation Instructions ELECTRICAL CONNECTIONS DANGER Only qualified electricians should connect incoming power to the Series 7C7 Air Maintenance/Compressor Assembly. To reduce the risk of electric shock, check the electrical source for proper grounding. Failure to follow these instructions could result in death or serious personal injury. Only qualified electricians should connect incoming power to the Series 7C7 Air Maintenance/Compressor Assembly. All wiring shall be completed in accordance with requirements of the local authority having jurisdiction and any applicable electrical codes. CABLE PRESSURE SWITCH VERSION A L1 T1 T2 L2 L1 T1 T2 L2 HOT - Black Wire NEUTRAL - White Wire GREEN To Ground Connection MOTOR Ground Connection ELECTRICAL CONNECTION NEMA 1 Enclosure - Intended Only for Indoor Use CABLE PRESSURE SWITCH VERSION B LINE MOTOR LINE LINE MOTOR LINE HOT - Black Wire NEUTRAL - White Wire GREEN To Ground Connection MOTOR Ground Connection ELECTRICAL CONNECTION NEMA 1 Enclosure - Intended Only for Indoor Use I-7C7_9

ADJUSTMENT OF PRESSURE SWITCH VERSION A DIFFERENTIAL ADJUSTMENT B Follow the instructions in this section if the internal components of the pressure switch match the above photo. DANGER Disconnect and lock-out the electrical supply before attempting to remove the pressure switch cover. Failure to follow this instruction could result in serious personal injury. The pressure switch is factory set for typical system air pressures (13 - psi/.9-1.2 Bar). NOTE: Any adjustment made may affect correct operation and increase the cut-off time. Higher air pressure may slow down the system response time. Refer to the system air pressure gauge when making any adjustments. PRESSURE RANGE Set the operating point on the rising pressure by adjusting the differential spring nut (B). NOTE: Turning the differential spring nut clockwise will increase the pressure difference between the cut-in and cut-out operating points by increasing the cut-out point only. RELEASE VALVE C A The release valve is factory installed. If the release valve is replaced or the release valve screw (C) requires adjustment, complete the following steps: 1. Loosen the lock nut. 2. With air pressure applied to the valve and the switch contacts open, turn the release valve screw (C) clockwise until the release valve just begins to release air. 3. Turn the release valve screw (C) clockwise an additional 11/2 turns. Adjust the range spring nut (A) first, until the desired operating point on the falling pressure is obtained. NOTE: Turning the range spring nut clockwise will increase the setting. This adjustment changes both the cut-in and cut-out operating points but should be adjusted only for the cut-in point. E D 4. Lock the jam nut (D) against the bearing-plate lever (E). I-7C7_

ADJUSTMENT OF PRESSURE SWITCH VERSION B DIFFERENTIAL ADJUSTMENT B Follow the instructions in this section if the internal components of the pressure switch match the above photo. DANGER Disconnect and lock-out the electrical supply before attempting to remove the pressure switch cover. Failure to follow this instruction could result in serious personal injury. Set the operating point on the rising pressure by using the differential adjustment screw (B). NOTE: Turning the differential adjustment screw clockwise will increase the pressure difference between the cut-in and cut-out operating points by increasing the cut-out point only. The pressure switch is factory set for typical system air pressures (13 - psi/.9-1.2 Bar). NOTE: Any adjustment made may affect correct operation and increase the cut-off time. Higher air pressure may slow down the system response time. Refer to the system air pressure gauge when making any adjustments. PRESSURE RANGE A Adjust the pressure range screw (A) first, until the desired operating point on the falling pressure is obtained. NOTE: Turning the pressure range screw clockwise will increase the setting. This adjustment changes both the cut-in and cut-out operating points but should be adjusted only for the cut-in point. I-7C7_11

INSTALLATION INSTRUCTIONS I-7C7 Series 7C7 Air Maintenance/Compressor Assembly FAST-FILL BALL VALVE, SLOW-FILL BALL VALVE, AND PRESSURE SWITCH ISOLATION BALL VALVE INFORMATION The following information describes the function of the fast-fill ball valve, the slow-fill ball valve, and the pressure switch isolation ball valve of the air maintenance trim. Always refer to the installation, maintenance, and testing manual for the FireLock NXT valve for complete setup information. Pressure Switch Isolation Ball Valve Shown in Initial System Piping Integrity Test Position (Closed) Pressure Switch Isolation Ball Valve (Lockable - Normally Open) SYSTEM PIPING INTEGRITY TEST 1. To perform the one-time initial system piping integrity test (per NFPA requirements), close the pressure switch isolation ball valve to allow the compressor to charge the system pressure above the cut-out pressure. Upon completion of the test, open the pressure switch isolation ball valve. Manually bleed the system pressure down to psi/1.2 Bar by opening the system main drain valve. Lock the pressure switch isolation ball valve in the open position. Slow-Fill Ball Valve (Normally Open) Fast-Fill Ball Valve (Normally Closed) 1. Open the slow-fill ball valve and fast-fill ball valve to charge the system. NOTE: The slow-fill ball valve s normal operating position is open. Failure to leave the slow-fill ball valve open may allow system pressure to drop, resulting in valve operation in the event of a system leak. 2. Ensure the pressure switch isolation ball valve is open. 3. When system air pressure is established, close the fast-fill ball valve. The fast-fill ball valve s normal operating position is closed. TROUBLESHOOTING PROBLEM POSSIBLE CAUSE SOLUTION Valve operates without sprinkler activation Loss of air pressure in the system or trim Check for any leaks in the system and trim. Confirm that the air maintenance trim is operating properly. Consider installing a low-air supervisory switch. Pressure switch is set too low, or the compressor is not operating properly Increase the ON setting of the pressure switch, and check the air compressor for proper operation. Compressor short cycles/chatters Manual pull station has operated Close the manual pull station, then reset the fire protection system by referencing the applicable installation, maintenance, and testing manual for the specific valve. Pressure switch is out of adjustment Refer to the Pressure Switch Adjustment section to readjust pressure and differential. Slow-fill and fast-fill ball valves were closed at the same time, creating back pressure at the compressor Relieve pressure at the motor by opening the slow-fill ball valve and pushing the relief valve at the pressure switch. For complete contact information, visit victaulic.com I-7C7 483 REV F UPDATED 7/214 Z7C7 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY AND/OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND/OR OTHER COUNTRIES. 214 VICTAULIC COMPANY. ALL RIGHTS RESERVED.