TABLE OF CONTENTS PART III MINIMUM DESIGN STANDARDS Section 120 WATER TRANSMISSION LINES (LARGER THAN 24 DIAMETER)

Similar documents
SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

Wastewater Capital Projects Management Standard Construction Specification

SECTION POLYVINYL CHLORIDE (PVC) PIPE

Suggested Specifications: Steel Pipe for Water Transmission

2013 Edition. Flanged fittings 30"-64" NSF. industrial Applications, water & Wastewater. Certified to ANSI/NSF 61

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

SECTION DUCTILE-IRON PIPE AND FITTINGS

SECTION DUCTILE IRON PIPE AND FITTINGS

SECTION ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL

DIVISION 4300 STORM DRAINAGE

INDEX. Sec. No. Items Page Nos.

SECTION STORM DRAINAGE SYSTEM

SECTION DUCTILE IRON PIPE AND FITTINGS

SECTION HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION

Section SEWER PIPE INSTALLATION AND TESTING

Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING

SECTION 6 SANITARY SEWER MAIN 6.01 SCOPE

SECTION PRESTRESSED CONCRETE CYLINDER PIPE

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

SECTION SANITARY SEWER PIPE

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.

SECTION NONREINFORCED CONCRETE SEWER PIPE

STANDARD SPECIFICATIONS SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE. 1. Trenching, Backfilling, and Compacting: 02223

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

SECTION PRECAST CONCRETE UTILITY STRUCTURES

SECTION HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS

San Antonio Water System Standard Specifications for Construction ITEM NO SLIP-LINING SANITARY SEWERS

SECTION STEEL PIPE, MORTAR LINED AND COATED

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

SANITARY SEWER SPECIFICATIONS

SECTION STORM DRAIN SYSTEM

COATING & WRAPPING OF UNDERGROUND PIPING

SECTION GROUND WATER STORAGE TANKS

Section 2100-Trenching and Tunneling

SECTION PVC PRESSURE PIPE AWWA C900

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta

STANDARD SPECIFICATION SECTION POLYVINYL CHLORIDE (PVC) PRESSURE PIPE (AWWA C900)

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

Specification for Pipe Bursting Gravity Sewer Mains with HDPE Pipe

Caps STANDARD WEIGHT Inches / Pounds

CHAPTER 6 - SANITARY SEWER

Sewer Water Pipeline Replacement with CERTA LOK RESTRAINED JOINT PVC PIPE

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

DUCTILE IRON PIPE JOINTS AND THEIR USES

Model Specification 509 DRISCOPLEX 4200 and DRISCOPLEX 4300 Gravity Flow Sanitary Sewer

SECTION 603 SANITARY SEWER FORCE MAINS

AMERICAN Mechanical Joint Pipe For Water, Sewage or Other Liquids

SECTION 1 GENERAL REQUIREMENTS

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES SITE UTILITIES

BLADDER SURGE CONTROL SYSTEM

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS

TECHNICAL NOTE Lining of Casings with SaniTite HP Pipe

SECTION STORM DRAINAGE TABLE OF CONTENTS

CITY OF BEVERLY RULES AND REGULATIONS - SEWER SYSTEM TESTING. General

September 2012 Brunswick County Engineering Department Revision 1.0. Technical Specification GRAVITY SANITARY SEWER SYSTEM

TABLE OF CONTENTS SECTION 500 SANITARY SEWER AND FORCE MAIN

SECTION 3 SANITARY SEWER DESIGN

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

Section C-1 Pipes and Fittings

SECTION FIRE HYDRANTS

PRE INSTALLATION MANUAL

Price List January 1, 2015

STANDARD SPECIFICATIONS SECTION INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223

Meeting the Challenge of Pipeline Emergency Repair

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

NAPCA BULLETIN APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE

ASME/ANSI B Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B Malleable Iron Threaded Fittings ASME/ANSI B16.

General Guidelines for Repairing Buried PE Potable Water Pressure Pipes

1.3.2 Method of construction and restoration of existing water service connections. This shall include:

TECHNICAL SPECIFICATION

Mechanical Joint Restraints

STANDARD SPECIFICATIONS SECTION CLEANING AND LINING WATER MAINS

SECTION 15 AIR RELEASE VALVE ASSEMBLIES General

SECTION STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

53.03 MATERIALS FOR SEWER LINER PIPE AND FITTINGS: The following materials are approved for installation in sanitary sewer lines:

San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS

SECTION UNDERGROUND ELECTRIC SERVICE

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

WATER SERVICE 2

A. The CONTRACTOR shall provide pipe coating, complete and in place, in accordance with the Contract Documents.

SECTION REINFORCED CONCRETE PIPE. A. The following is a list of SPECIFICATIONS, which may be related to this section:

SUBMITTAL 10 FEET. Cast Iron Soil Pipe Products Hubless Pipe & Fittings HUBLESS PIPE 10 FEET*

Engineering Specifications

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

POLYURETHANE LINING AND COATING ON PIPE RAW WATER

SECTION 724 PIPE CULVERTS

LS 2540 SEWER LATERALS AND INSPECTION TEES

TECHNICAL SPECIFICATIONS GRAVITY AND PRESSURE SEWER LINE AND MATERIALS

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

Section Four: Linings and Coatings

Vogt Valves The Connection Bulletin for Extended Body Forged Steel Valves Welded Bonnet, Bolted Bonnet, Class 800 & Class 1500 CB 22

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe

ARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH Purpose and Application.

SECTION BUILDING SEWERS. B. Connection of building sanitary drainage system to municipal sewers.

Transcription:

TABLE OF CONTENTS PART III MINIMUM DESIGN STANDARDS Section 120 WATER TRANSMISSION LINES (LARGER THAN 24 DIAMETER) 120.1 GENERAL... 120.1 120.2 PRE-MANUFACTURE OF PIPE REQUIREMENTS... 120.1 120.2.1 Design Calculations... 120.1 120.2.2 Shop Drawings... 120.1 120.2.3 Pipe Laying Schedule and Marking Diagram... 120.1 120.2.4 Submittal Reviews and Revisions... 120.2 120.3 MATERIAL FABRICATION, TESTING AND CERTIFICATION... 120.2 120.3.1 Certification... 120.2 120.3.2 Marking Pipe and Specials... 120.2 120.3.3 Lining and Coating Protection... 120.3 120.3.4 Standard Joints... 120.3 120.3.5 Harnessed Joints... 120.3 120.3.6 Flanges and Nozzles... 120.4 120.3.7 Mechanical Couplings... 120.4 120.3.8 Closures and Correction Pieces... 120.5 120.3.9 Specials and Fittings... 120.5

PART III MINIMUM DESIGN STANDARDS SECTION 120. WATER TRANSMISSION LINES (LARGER THAN 24 DIAMETER) ADDITIONAL DESIGN REQUIREMENTS 120.1 GENERAL Transmission lines larger than twenty-four (24") inch diameter may be Steel (S), or Ductile Iron (DI). Steel and ductile iron pipe shall be cement mortar lined. Steel pipe shall be coated at the factory with an exterior tape coating system in accordance with AWWA Standard C214. Ductile iron pipe shall be coated with an asphaltic shop coating and encased with polyethylene in accordance with ANSI/AWWA C105/A21.5 Except as herein modified, the pipe shall conform to the applicable AWWA specification set forth in Section 30, Table 30.1. Metallic type pipe shall be designed, manufactured, tested, inspected and cathodically protected in accordance with Section 30 and this section of these standard specifications. Minimum wall thickness of steel pipe shall be approved by the City Engineer. 120.2 PRE-MANUFACTURE OF PIPE REQUIREMENTS Within twenty (20) calendar days following the "Notice of Award", the Contractor shall obtain from the supplier and submit to the Engineer for review four (4) complete sets of the following: 120.2.1 Design Calculations 120.2.2 Shop Drawings Design calculations (steel pipe only) shall comprise concise, yet complete, stress analysis of each critical section of pipe wall, girth joints, harness system, specials, outlets and appurtenances, sufficient to ascertain conformance of the pipe and fittings with these specifications. All steel pipe shall be designed in accordance with AWWA Manual M11. Shop drawings shall accurately indicate the precise geometry; type, gauge, diameter, strength, manufacturing tolerance and thickness of the elements to be incorporated in manufacture of the pipe, joints, fittings and appurtenances. 120.2.3 Pipe Laying Schedule and Marking Diagram Laying schedule shall indicate by consecutive number the order and direction of installation of each pipe section, special fitting, valves, access manholes, nozzles, outlets, and other appurtenances. In addition, the laying schedule shall include: A. The station and elevation to which the bell end of each pipe shall be laid and all changes in gradient or horizontal alignment. B. All elements of curves and bends, both in horizontal and vertical alignment. City of Arvada 120.1 07/11

C. The limits of each reach of any welded joints, closures or concrete encasements. 120.2.4 Submittal Reviews and Revisions The Engineer will inspect and return two (2) copies of design calculations, working drawings and other submittals to the Contractor properly executed and marked either "Reviewed", "Revise and Resubmit", "Furnish as Noted" or "Rejected" within twenty (20) calendar days after receipt thereof. The Contractor shall review and back check indicated revisions deemed necessary by the Engineer to correct defects. He shall revise submittals returned to him that have been marked "Revise and Resubmit" or marked "Rejected", and shall resubmit in quadruplicate said revisions to the Engineer within fifteen (15) calendar days after the Contractor's receipt thereof. Further revisions, if and when required, will be handled in accordance with the above procedure. Only upon the Contractor's receipt of submittals marked or designated "Reviewed" or "Furnish as Noted" shall the manufacturer of pipe commence: Provided that said drawings designated "Furnish as Noted" are corrected and resubmitted to the Engineer immediately. Upon receipt of duly executed "Reviewed" design calculations, laying diagrams and shop drawings, the Contractor shall immediately forward to the Engineer eight (8) prints of each such approved submittals for use during construction. Neither the inspection nor lack of inspection of any drawings, design calculation, material list, laying schedule, sample or piece of data (furnished to the Engineer for his review) shall waive any of the requirements of these Specifications, Drawings and Contract Documents or relieve the Contractor of any obligations thereunder; and defective workmanship, work, materials and finished product may be rejected notwithstanding conformance with Drawings and other submittals reviewed by the Engineer. 120.3 MATERIAL FABRICATION, TESTING AND CERTIFICATION 120.3.1 Certification The Engineer or his designated representative shall be permitted to make inspections necessary during the manufacture of the pipe and appurtenances to determine compliance with the specifications. The manufacturer, via the Contractor, shall furnish the Engineer four (4) copies of the following certifications as to compliance with the specifications: Mill analysis and test of steel. Hydrostatic test reports. Compliance of materials and application of linings and coating. Usage of Type V or modified Type II cement as required in mortar coatings on pipe, specials and fittings. 120.3.2 Marking Pipe and Specials The manufacturer shall legibly mark and number in sequence all steel pipe sections and specials in accordance with the laying schedule and pipe installation survey laying stations. All pipe specials shall be marked at each end with the top field centerline stations. City of Arvada 120.2 07/11

120.3.3 Lining and Coating Protection It shall be the responsibility of the manufacturer to provide adequate strutting to prevent damage to the coating and lining caused by deflections beyond the specified allowable limits for the type of pipe supplied during handling, loading, transporting, unloading and storing. Any additional strutting or stulling required during installation to prevent damage to the coating and/or lining caused by deflections beyond the allowable limits shall be the responsibility of the Contractor. The Contractor shall be responsible to be sure that all strutting remains in place until after the pipe section, special or fitting has been properly backfilled. The manufacturer shall provide a polyethylene or other suitable bulkhead on the ends of the pipe section and on all special openings to prevent drying out of the linings. The Contractor shall be responsible to assure that the polyethylene or bulkheads remain intact on the pipe ends until the section or fitting is being installed in the trench. 120.3.4 Standard Joints Standard joints for transmission line pipe shall be either an expanded bell and rolled spigot or the Carnegie bell and spigot end ring (steel pipe only), each with rubber gasket. Mechanically coupled, flanged, mechanical, restrained or welded joints may be required where called for on the drawings. The joint construction shall be suitable for at least 250 psi water service and regardless of type shall be designed to be self-centering. The bells and spigots shall have a smooth close sliding fit at the self-centering surface, and the joint shall be capable of either symmetrical or asymmetrical joint closure and shall remain water-tight under all conditions of water service. The joint assemblies shall be so formed and accurately manufactured that when the pipes are drawn together in the trench, they shall form a continuous watertight conduit with smooth and uniform interior surface and shall provide for a slight movement of any pipe in the pipeline due to contraction, settlement or lateral displacement. The maximum tolerances permitted in the construction of the joint shall be that stated in the pipe manufacturer's design as approved. Any fabrication performed prior to approval of details shall be at the Contractor's risk. Approval by the engineer shall not be held to relieve the Contractor of any part of the Contractor's responsibility to meet all of the requirements of these specifications or of the responsibility for the correctness of the joint details. 120.3.5 Harnessed Joints Harness joint designs for steel pipe shall be submitted to the Engineer for approval. On steel transmission lines twenty seven (27) inches diameter and larger, the joint harness designs shall include considerations of stresses induced not only in the attachments, but also in joint rings and steel cylinder by thrust at bulkheads, bends, reducers, and valves resulting from the internal working pressure including the transient pressures. Design stresses shall not exceed fifty (50) percent of the specified minimum yield strength of the grade of steel utilized when longitudinal thrust is uniformly distributed around the circumference of the joint. The manufacturer shall supply a mechanical method of joint restraint suitable to the engineer that will allow for expansion, contraction and deflection after assembly. Proof-of-design tests need not be conducted specifically for a project. Certified reports covering tests of harnessed joints constructed in the identical fashion as that proposed may be found acceptable. City of Arvada 120.3 07/11

120.3.6 Flanges and Nozzles Flanges in the line and for outlets of the size and at locations shown on the drawings shall meet the requirements of AWWA Standard C-207, Class "D", minimum 150 psi working pressure. Flanges may be either ring type flanges or hub type flanges, but all flanges supplied must be of the same type and class. Blind flanges shall be designed in accordance with ASME Unfied Pressure Vessel Code, Section VIII. The design pressure for blind flanges shall be minimum 150 psi. Bolt holes in all flanges shall straddle field vertical centerline. Bolt holes for insulating flanges shall be 3/16" larger than the bolt diameter. Gaskets for standard flanged outlets shall be 1/8" ring type compressed cloth inserted rubber Garlock 3000 or approved equal. Insulating flange gaskets shall be PSI - Pacific Seal gaskets with sleeves and double insulating washers or approved equal. Nozzles shall have 1/4" minimum wall thickness. The machined faces of all flanges shall be shop coated with rust preventative compound, Dearborn Chemical "No-Ox-Ld", Houghton "Rust-Veto 344" or Rust-Oleum "R-9" or approved equal. Edges and back faces of attached flanges shall be shop coated with Koppers "Bitumastic Mill Undercoat" or approved equal. All surfaces of blind flanges, except the machines surfaces, shall be shop coated with Koppers "Bitumastic Mill Undercoat" or approved equal. 120.3.7 Mechanical Couplings Where mechanical couplings are required, the ends of the pipe shall be prepared for flexible steel couplings, Dresser, Baker or approved equal. Plain ends for use with couplings shall be smooth and round for a distance of twelve (12) inches from the ends of the pipe, with pipe diameter not more than 1/64" smaller than the nominal O.D. of the pipe. The middle ring of the coupling shall be truly round. After welding, all middle rings shall be tested by coldexpanding a minimum of one (1) percent beyond the yield point to proof-test the weld to the strength of the parent metal. The weld of the middle ring shall be subjected to air test for porosity. The followers shall be single-piece contoured mill section welded and cold-expanded as required for the middle rings. They shall be of sufficient strength, in the opinion of the engineer, to accommodate the number of bolts necessary to obtain adequate gasket pressures without excessive rolling. The shape of the follower shall be of such design as to provide positive confinement of the gasket. Gaskets shall be rubber-compounded material that will not deteriorate from age or exposure to air under normal storage or use conditions. The rubber in the gasket shall meet the following specifications: Color - Jet Black Surface - Non-blooming Durometer Hardness - 74 + 5 Tensile Strength - 1000 psi Minimum Elongation - 175% Minimum The gaskets shall be immune to attack by impurities normally found in water. All gaskets shall meet the requirements of ASTM designation D2000 AA 709Z meeting Suffix B13 except as noted above. City of Arvada 120.4 07/11

In addition, where insulating couplings are required, both ends of the coupling shall have a wedge-shaped gasket which assembles over a rubber sleeve of an insulating compound in order to obtain insulation of all coupling metal parts from the pipe. Each coupling shall pass a resistance test of 10,000 ohms after being assembled on the pipe for 72 hours. 120.3.8 Closures and Correction Pieces Closures and correction pieces for steel pipe shall be provided as required so that closures may be made due to different headings in the pipe laying operation and that correction may be made to get the pipe laying on station. Closures and correction pieces shall be provided as required by the Contractor and shall be approved by the Engineer. Closures shall be so constructed as to have not less than a minimum of eighteen (18) inches and maximum of two (2) times the pipe I.D. adjustment, which may be made in the field. The correction piece shall be a nominal length of pipe with a length of bare pipe on the spigot end for a field trim. Linings shall be held back six (6) inches from the required length on the spigot end. 120.3.9 Specials and Fittings Unless otherwise specified herein or on the plans, all specials and fittings for steel transmission lines shall conform to the dimensions of the applicable AWWA or ASTM Standards. Specials and fittings shall be designed and constructed to be of equal or greater strength than the transmission line and shall have the same type of lining and coating as the abutting pipe. Specials and fittings shall be made of segmentally welded sections from hydrostatically tested Pipe cylinders, with ends to mate the type of joint or coupling specified. The deflection angle between adjacent segmented bands shall not be greater than 22 1/2 degrees. Specials and fittings for steel pipe that cannot be mechanically lined and coated shall be lined and coated by hand, using the same materials as are used for the pipe and in accordance with the applicable AWWA Standards. Coatings and linings applied in this manner shall provide protection equal to that specified for the pipe. Fittings may be fabricated from pipe that has been mechanically lined and/or coated. Areas of lining and coating that have been damaged by such fabrication shall be repaired by hand applications in accordance with applicable AWWA Standards. Areas of cement-mortar linings repaired in this manner need not be reinforced with wire mesh. Reinforcement for wyes, tees, and nozzles shall be designed in accordance with AWWA M- 11 "Steel Pipe Manual". Reinforcement shall be designed for the working pressures indicated. Access manholes with covers shall be 20" in diameter (O.D.) as detailed on the drawings. All threaded outlets shall be forged steel suitable for 3000 pound service. Moderate deflections and long radius curves may be made by means of beveled joint rings, by deflecting a straight pipe, by using short lengths of pipe, or by a combination of any of these methods. City of Arvada 120.5 07/11

Unless specifically approved by the Engineer, all curves for steel pipe must begin with a pipe joint or fabricated angle at the P.C. and end with a pipe joint or fabricated angle at the P.T. within station locations shown on the Drawings. All deflection angles shall fall on the curve. The laying schedule P.I.'s must meet the P.I.'s as shown on the Drawings in the horizontal direction. The laying schedule for vertical P.I.'s must meet the P.I.'s as shown on the Drawings where interference is critical. City of Arvada 120.6 07/11