CROSS CONNECTIONS & BACKFLOW PREVENTION DEPARTMENT OF PUBLIC WORKS AND PARKS ENVIRONMENTAL SERVICES DIVISION

Similar documents
FAQ and Device/Usage Chart. What Is a Cross-Connection? What Is Backflow Prevention? What Is Backflow?

Cross-Connection Control. Protecting the potable water supply from contamination.

ARTICLE 1141 Cross Connection Control Program

WESTFIELD WATER RESOURCES DEPARTMENT

A Cross-Connection is a. water system and a nonpotable CROSS-CONNECTION CONTROL BACKFLOW PREVENTION CROSS-CONNECTION CROSS-CONNECTION

(a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems.

Cross Connection Control and Backflow Prevention Program Guidelines

CHAPTER 26 PLUMBING CODE

CROSS-CONNECTIONS AND BACKFLOW PREVENTION MANUAL

ORDINANCE NO THE CITY COUNCIL OF THE CITY OF NORTH LAS VEGAS, NEVADA, DOES HEREBY ORDAIN AS FOLLOWS:

Revised April (May) 2015

Sample Exam Questions and Recommended References for ABC s Backflow Prevention Assembly Tester Exam

Metropolitan Domestic Water Improvement District. Backflow Prevention Control Ordinance. Ordinance No

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

CITY OF BAY CITY ORDINANCE NO. 628

Rule No. 16. b. The service connection will determine the point of delivery of water service to the customer.

15. Design of plumbing systems for industrial and temporary applications

77 ILLINOIS ADMINISTRATIVE CODE, PART 890 (NEW) ILLINOIS PLUMBING CODE (02/04) SUBPART I: WATER SUPPLY AND DISTRIBUTION

MassDEP Cross Connection Control Program Regulations CMR 22.22

Cross Connection Control Policy

ALBUQUERQUE BERNALILLO COUNTY WATER UTILITY AUTHORITY CROSS CONNECTION PREVENTION AND CONTROL ORDINANCE

Backflow Bulletin #1

Backflow Prevention & Cross-Connection Control Manual For the Education of Ohio Certified Backflow Prevention Technicians.

CIPHI s 75 th Annual conference Safe Drinking Water Course Cross Connection Control and Backflow Prevention

CROSS-CONNECTION CONTROL PROGRAM MANUAL

Plumbing Code in Commercial Kitchens

TUCSON BACKFLOW ORDINANCE ARTICLE V. BACKFLOW PREVENTION AND CROSS-CONNECTION CONTROL*

PLUMBING & CROSS-CONNECTION CONTROL

How To Protect Water Supply From Cross Connections

STATE OF CONNECTICUT CROSS CONNECTION CONTROL MANUAL

Cross-Connection Control Manual

Element D Services Plumbing

Inexpensive Leak Detection for Small Waterworks. Virginia Department of Heath Office of Drinking Water Catalog Number: HTO/005/2015

SECTION 11 PLUMBING AND CROSS CONNECTION CONTROL DRAINS INDEX. I. Plumbing Systems II. Cross-Connections: Direct & Indirect 11-1

PUBLIC WORKS TECHNICAL BULLETIN July 2001 CROSS-CONNECTION CONTROL AT ARMY INSTALLATIONS

Minimum Standards for a Cross-Connection Control Program

City of West Chicago Community Development Department 475 Main Street, West Chicago, IL Phone: (630) x 131 / Fax: (630)

MAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT

Plumbing Code Sections For Commercial Food Facilities

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter Adopt Entire Chapter as amended (amended sections listed below)

Winterizing Backflow Prevention Assemblies

TCEQ Requirements. Effective Cross-Connection: Why & How. Plumbing Ordinance. Plumbing Ordinance. Plumbing Ordinance. Plumbing Ordinance

The Plumbing Pipeline

Chapter 8 Water and Sewage Systems

CROSS-CONNECTION CONTROL MANUAL

The Plumbing Pipeline

WATER & WASTEWATER SYSTEM DESIGN. Technical Design Manuals 1 & 2

FILLING AND PURGING THE SYSTEM

CITY OF FRISCO Irrigation Rules & Requirements. Ordinance No

PLBG/GAS SAFETY Information Bulletin

TORONTO MUNICIPAL CODE CHAPTER 851, WATER SUPPLY. Chapter 851 WATER SUPPLY

Proposed standard significant deficiency language is provided in italics. Notes to staff are provided in blue and are [bracketed].

Table of Contents. Definitions of Cross Connection Control... 4

CITY OF SURREY BY-LAW NO. 6569

HARRIS COUNTY MUNICIPAL UTILITY DISTRICT NO SH 249, Suite 210, Houston, Texas Phone Number (281)

WELCOME INTERNATIONAL RESIDENTIAL CODE 2009 EDITION PLUMBING SECTION

TITLE 4 PUBLIC WORKS

Fire Pump Plan Review March 2010

6. Principles of effective plumbing systems

Installation, Maintenance, & Repair Series 4000B/LF4000B

Lebanon Utilities GENERAL TERMS AND CONDITIONS FOR WATER SERVICE LEBANON, INDIANA

Presented by: Jeremy Harris, E.I. Department of Health & Hospitals/ Office of Public Health Engineering Services

UTILITIES DEPARTMENT

SECTION 5 - COMMERCIAL CONSTRUCTION MECHANICAL, ELECTRICAL, PLUMBING AND SOLAR OTHER TECHNICAL CODES

Page 1 of 51 Exterior Plumbing Quiz Part 1

WATER SUPPLY AND DISTRIBUTION

DIVISION 1 - PLUMBING INSPECTOR SEC POSITION OF PLUMBING INSPECTOR

WHITE PLAINS PLUMBING CODE PART 1. GENERAL REQUIREMENTS

WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!

Definitions; contractors licensed by Board; examination; posting license, etc.

What to Expect From the Examination. How to Study the Plumbing Codes

Title 15 - Mississippi Department of Health Part 20: Bureau of Public Water Supply Subpart 72: Public Water Supply

Proposed New City of Toronto Water Supply By-law CONTENTS. Water Supply By-law. Index of Fee Schedules A, B, C. Orders Fines Tickets (reference list)

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Undersizing Backflow Preventers

31. ECO-INFO -- SEPTIC SAFE PROTECT YOUR HEALTH AND ENVIRONMENT YOUR SEPTIC PUMP-OUT SYSTEM with SELF ASSESSMENT TROUBLE SHOOTING GUIDE

Heating Water by Direct Steam Injection

FERTIGATION. Lawrence J. Schwankl

BULK WATER HAULING GUIDELINES

2014 Oregon Plumbing Specialty Code New Oregon Amendments

REGISTRATION EXAMINATION, JUNE 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Amendments to the 2012 International Plumbing Code

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

Watts Regulator Examines Product Applications for. The 2000 National Standard Plumbing Code

Plumbing for retail food businesses

Septic Tank Use & Maintenance Tips

FIRE SUPPRESSION INSTALLATION CITY OF HARRISONBURG, VIRGINIA

NOTE: Unless otherwise specified, unit prices for the demolition of structures shall be for wet demolitions.

Chapter 5 Water, Plumbing, and Waste

Additional Services Agreement. Part 3: Schedule of our requirements

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs

INSTALLATION INSTRUCTIONS GEO-BOOSTER TM

SECTION THREE CONSTRUCTION CODES

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS

PLUMBING CODE REGULATION

Risk Assessment Based Environmental Management Systems for Petroleum Retail Stores

Transcription:

CROSS CONNECTIONS & BACKFLOW PREVENTION 1

Overview Theory Documented Examples Types of Devices Selection of Devices City of St. John's Program 2

Cross - Connection What is a cross connection? This can be defined as actual or potential connections between a potable and nonpotable water supply. Example Hose Bib 3

Cross - Connection Why do cross-connections exist? Lack of Knowledge - Plumbing connections are frequently installed by individuals who are unaware the inherent dangers of cross connections. The cross connections are made as a matter of convenience without regard to the dangerous situation that might be created. The connections are made with reliance on inadequate protection (such as a single valve or another mechanical device) 4

Backflow What is Backflow? This can be defined as fluid flow in an undesirable or reverse direction. 5

Back Siphonage Types of Backflow Caused by atmospheric pressure exerted on a pollutant liquid forcing it toward a potable water supply system that is under a vacuum. Causes of Vacuum in Potable Water System Water Main Break Constricted Flow Venturi Dynamically Reduced Pipe Pressures - Pump 6

Back Siphonage 7

Real Examples of Backflow - Insecticide in Water System - Contractor applying insecticide treatment, mixing water to dilute chemical from hose bib. City workers were completing maintenance on a section of water main. What occurred: Combination of low water pressure and simultaneous use of hose submerged in tank. Back Siphonage!!! Instead of water entering the tank, the entire contents of the tank (insecticides) were drawn in the opposite direction, into the potable water supply. 8

Real Examples of Backflow - Human Blood in Water System - Funeral home using a hydraulic aspirator directly connected to potable water supply. Water flow through the aspirator creates suction, utilized to draw body fluids through a hose and needle attached to the suction side of the aspirator. What occurred: Combination of low water pressure and simultaneous use of the aspirator. Back Siphonage!!! Instead of body fluids flowing into the sanitary drain, they were drawn in the opposite direction, into the potable water supply of the funeral home. 9

Back Pressure Types of Backflow Any interconnected fluid system in which the pressure of the one exceeds that of the other, may have flow from one to the other as the result of pressure differential. Causes of Back Pressure in Water System High Rise Building booster pump Fire Protection Line booster pump Heating System recirculation or chemical feed pump 10

Back Siphonage Any pumped system within a building, could be a possible source of a backflow event. 11

Real Examples of Backflow - Shipyard Backflow Contamination - Shipyard was aware of the need for backflow protection at the dockside tie up area. Waiting on device to be delivered and installed. What occurred: Shipyard potable water supply was connected to a ship at the dock, accidentally creating a direct crossconnection with the on-board salt water fire protection water system. Back Pressure!! Fire protection system, being at a greater pressure than the potable supply, forced raw sea water into the shipyard potable supply lines. 12

Real Examples of Backflow - Car Wash Water in Water Main - High pressure pump used to pump recycled reclaimed wash and rinse water from the reclaim tanks back to the initial scrubbers. No potable plumbing connection is normally made to the car wash's scrubbers. What occured: Pump failed removed for repair. "Temporarily" connected a 2-inch hose between the potable water piping and the scrubber cycle piping. Pump reinstalled. Hose not removed. Back Pressure! Large quantity of reclaimed wash/rinse water pumped into 12-inch water main in street. 13

Types of Backflow Preventers Air Gap Vacuum Breaker Dual Check Valve Double Check Valve Reduced Pressure Principle 14

Types of Backflow Preventers Air Gap Non mechanical backflow preventers Extremely effective device Can only be used to prevent backsiphonage Requires break in piping layout Current standard outlet must be 2 diameters water surface 15

Air Gap 16

Types of Backflow Preventers Vacuum Breaker - Atmospheric Simplest and least expensive device Can only be used to prevent backsiphonage Water lifts float, loss of water causes float to drop and the unit to vent to atmosphere Minor or Moderate Hazard 17

Vacuum Breaker - Atmospheric 18

Types of Backflow Preventers Vacuum Breaker Hose Bib Consists of a spring loaded check valve which seals against the atmospheric outlet when the water is turned on. When the water is shut off the device vents to atmosphere. Minor Hazard 19

Vacuum Breaker Hose Bib 20

Types of Backflow Preventers Vacuum Breaker Pressure This type of vacuum breaker could be used under constant pressure and has test cocks. This device will not protect against backpressure conditions Device must be installed 150mm to 300mm above outlet. Minor, Moderate or Severe Hazard against back siphonage ONLY 21

Vacuum Breaker Pressure 22

Types of Backflow Preventers Dual Check Valve Consist of two independently acting internally loaded check valves with or without an atmospheric vent. Are not equipped with test cocks. Primarily Residential Applications. Minor Hazard Only 23

Dual Check Valve 24

Types of Backflow Preventers Double Check Valve Consist of two independently acting internally loaded check valves either force or internally loaded. Will prevent backflow if either check valve fails to close Equipped with Test Cocks for regular testing. Minor or Moderate Hazard 25

Double Check Valve 26

Types of Backflow Preventers Reduced Pressure Zone Assembly Consist of two independently acting internally loaded check valves separated by a reduced pressure zone. During normal operation the pressure between the two check valves is maintained at a pressure lower the supply pressure (reduced pressure zone). If a backflow occurs the second check valve closes and if the pressure increases in the reduced pressure zone as it approaches the supply pressure the relief valve will open. Can be used for Severe Hazard 27

Reduced Pressure Zone Assembly 28

Selection of BFP Device Need to Determine the following: The probability of back siphonage will cause backflow; The probability of back pressure will cause backflow; The severity of the hazard; The type of building. 29

Selection of BFP Device Severity of the Hazard CSA definition Minor Hazard any type of crossconnection or potential cross-connection that involves a substance that constitutes only a nuisance that results in a reduction in only the aesthetic qualities of water Cannot create a danger to health. 30

Selection of BFP Device Severity of the Hazard CSA definition Moderate Hazard any minor hazard that has a low probability of becoming a severe hazard. Connections involving water where the aesthetic qualities of water have been reduced and under certain conditions can create a danger to health. 31

Selection of BFP Device Severity of the Hazard CSA definition Severe Hazard any type of crossconnection or potential cross-connection involving water that has additives or substances that under any concentration can create a danger to health. 32

Selection of BFP Device 33

Selection of BFP Device 34

Selection of BFP Device 35

Cross Connection Control Program The AWWA recognizes water purveyors have the responsibility to supply potable water to their customers. In the exercise of this responsibility, water purveyors must implement, administer and maintain ongoing backflow prevention and cross-connection control programs to protect public water systems from the hazards originating on the premises of their customers and from temporary connections that may impair or alter the water in the public water systems. The return of any water to the public water system after the water has been used for any purpose on the customer s premises or within the customer s piping system is unacceptable. 36

Cross Connection Control Program Development of a Program CSA B64 states that to protect the municipal or private potable water supply systems from contamination the authority administering the local cross connection control program has several options available when determining the location of backflow preventers within industrial, commercial and residential properties. 37

Cross Connection Control Program Development of a Program - Option 1 Containment Theory Backflow prevention is installed on the incoming service, providing premise isolation that utilizes a minimum number of backflow preventers to isolate the municipal potable water system from the private system. But this does not protect the consumer from the source of internal contamination within the building. 38

Cross Connection Control Program Development of a Program - Option 2 Internal Protection Backflow preventers are either installed on individual usages or zones of usage. This approach protects the private potable water system from internal contamination but does not adequately protect the municipal potable water system because of the complexity of the internal plumbing system. 39

Cross Connection Control Program Development of a Program - Option 3 Containment & Internal Protection Combines both Options 1 & 2 to ensure that both the public and private potable water supply systems are protected. The City of St. John s has selected Option #1 40

CSJ Premise Isolation Program CSJ's Water Distribution System Permit to Operate "The owner should recognize the importance of putting in place a cross connection control program with ongoing testing and maintenance of cross connection control equipment within its facilities and also to address existing and potential cross connections in the water distribution system such as bleed lines into manholes, unprotected watering stations, commercial and industrial establishments, private water supplies, etc." 41

CSJ Premise Isolation Program Development of a Program 2007 researched existing programs & developed draft document. Feb. 26, 2008 presented Premise Isolation Policy to Public Works Committee March 3, 2008 Council passed Premise Isolation Policy for new developments Currently developing By-Law 42

CSJ Premise Isolation Program Details of Program Applies to all properties with the exception of residential with two dwelling units and residential properties with home office. Premise Isolation BFP device to be installed on water service line prior to any branch. Includes domestic, sprinkler and hydrant lines. BFP device selected by Hazard Classification. Annual Testing of BFP Device. 43

CSJ Premise Isolation Program 44

CSJ Premise Isolation Program 45

CSJ Premise Isolation Program Other Details Properties with Fire Hydrants: BFP device to installed at property line inside heated enclosure; or BFP device located inside a building with the hydrant line supplied from the building. Acceptable BFP devices are Double Check or Reduced Principle types Only. These are testable devices. 46

CSJ Premise Isolation Program Future Plans Hire a Cross Connection Control Officer Review plans; Conduct inspections; Conduct spot testing of BFP devices; Ensure annual testing of BFP devices; Educate designers and contractors. Continue to develop City By-Law. 47

CSJ Premise Isolation Program Noted Problems Understanding Premise Isolation Theory; BFP installed on service line to provide isolation from the Municipal Water Distribution system. Uses the least number of devices. Example Restaurant Table B.2 defined as Moderate hazard Table B.1 Ice Machine for Commercial restaurant can moderate or severe. 48

CSJ Premise Isolation Program Noted Problems Inspection process between divisions and groups; Plumbing inspected by Building Dept. BFP and Meter inspected by Env. Services Division Wrong type of device selected / installed; Installation not constructed according to approved plans; Protecting fire hydrants. 49

Selection of BFP Device 50

Selection of BFP Device 51

Thank You DEPARTMENT OF PUBLIC PARKS AND PARKS 52