NEMA Standards Publication

Similar documents
ANSI/IEC Degrees of Protection Provided by Enclosures (IP Code) (identical national adoption)

American National Standard for Electric Lamps Specifications for Performance of Self-ballasted Compact Fluorescent Lamps

NEMA XR Standard Attributes on CT Equipment Related to Dose Optimization and Management

NEMA ICS (R2013) Programmable Controllers Part 1: General Information

NEMA Enclosure Types

American National Standard For Electrical Rigid Steel Conduit (ERSC)

American National Standard For Electric Power Systems and Equipment Voltage Ratings (60 Hertz)

NEMA SB Guide for Proper Use of System Smoke Detectors

American National Standard. For Insulators. Wet Process Porcelain and Toughened Glass Suspension Type ANSI/NEMA C

American National Standard. Physical Aspects of Watthour Meters Safety Standard. ANSI C Revision of ANSI C

Technical application guide IP codes in accordance with IEC 60529

For Instrument Transformers for Revenue Metering 10kV BIL through 350 kv BIL (0.6 kv NSV through 69 kv NSV)

NEMA Standards Publication No. WC EEMAC Standards Publication Binational Wire and Cable Packaging Standard

Degrees of protection. IP codes. W.M.M. Menheere Holec Holland N.V. The Netherlands

GUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT

NEMA ICS (R2013) Programmable Controllers Part 4: User Guidelines

Evaluating Water-Damaged Electrical Equipment

NTCIP 2301 v02. Simple Transportation Management Framework (STMF) Application Profile (AP) (AP-STMF)

Solving the Problem of Motor Protection from Moisture, Water and Dust in Commercial Refrigerators.

White Paper IK code: Impact protection in line with the IEC standard. By Sven Schnautz

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment

INTERNATIONAL STANDARD

Evaluating Fire- and Heat-Damaged Electrical Equipment

Solid State Lighting Definitions for Functional and Decorative Applications

Andre Gretler, LPLS BU Function Operation and Sales Low Voltage Systems ANSI vs IEC. BU 3101 Low Voltage Systems June 27, 2013 Slide 1

American National Standard for Electric Meters

IR WINDOW CERTIFICATION GUIDEBOOK. Copyright CorDEX Instruments Ltd. ex.com. ID 4016 Rev A

Understanding LED Drivers

SAFETY ALERT SWITCHBOARD INTERNAL SEGREGATION AND IP RATING. May 2014 BACKGROUND

IP Rating Chart. 910 East Orangefair Lane Anaheim, CA USA , Fax

Digital Imaging and Communications in Medicine (DICOM) Part 1: Introduction and Overview

INTERNATIONAL STANDARD

SSA-312. ISA Security Compliance Institute System Security Assurance Security development artifacts for systems

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

Securing your electrical installations Prisma,

CONSOLIDATED VERSION IEC Medical device software Software life cycle processes. colour inside. Edition

Explosion proof enclosures

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

IAAS Product Terms PRODUCT TERMS

prevailing of JAMS/Endispute. The arbitrator's award shall be binding and may be entered as a judgment in any court of competent jurisdiction.

INTERNATIONAL STANDARD

HAZARDOUS AREA TECHNICAL GUIDE

Revenue/Expenses Balance by Fund

62 Max/62 Max + Infrared Thermometer

Basics of Explosion Protection

FAQs-Main switchboard design criteria

American National Standard. Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable

Infrastructure-as-a-Service (IaaS) Product Terms

General Terms and Conditions for Online Sales of TomTom Inc ( TomTom )

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

This document has been provided by the International Center for Not-for-Profit Law (ICNL).

Single Phase Soft Starter

Title 24-A: MAINE INSURANCE CODE

Intel Server System S7000FC4UR

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual

Technology Solution Guide. Deploying Omnitron PoE Media Converters with Aruba Access Points and AirMesh Routers

Unified requirements for systems with voltages above 1 kv up to 15 kv

ELECTRONIC TRADING FACILITIES SUPPLEMENTAL TERMS AND CONDITIONS OF TRADING

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

Ex q Powder Filling. This is a technique primarily used for oil filled switch-gear. The spark is formed under oil and venting is controlled.

Integration of a 400W ac dc power supply into a closed system relying only on natural convection cooling

American National Standard. Magnet Wire ANSI/NEMA MW Secretariat:

MCC Ratings. Voltage Rating

Pesticide Spills. Chapter 26. In This Chapter. Keywords. Accidents. Pesticides Act and Environmental Protection Act

GENOA, a QOL HEALTHCARE COMPANY WEBSITE TERMS OF USE

ECLIPSE FOUNDATION, INC. MEMBERSHIP AGREEMENT

SELLING TERMS AND CONDITIONS

BUSINESS ONLINE BANKING AGREEMENT

GENOA, a QoL HEALTHCARE COMPANY GENOA ONLINE SYSTEM TERMS OF USE

Terms and Conditions for Purchase Orders for Recycling Materials

How To Get A Water Line Repair Program To Pay For A House To Be Fixed

Australian/New Zealand Standard

PeopleSoft Enterprise Human Resources 9.1 PeopleBook: Track Faculty Events

INVESTMENT ADVISORY AGREEMENT

OVERVIEW EMERGENCY CALL & INFORMATION PILLARS

Telemetry system for cathodic protection equipment of underground metal pipelines

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

NFC Communication Tray Model: HHX-IT3-Z

Digital Imaging and Communications in Medicine (DICOM) Part 1: Introduction and Overview

Terms and Conditions

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

User Agreement. Quality. Value. Efficiency.

Web Site Hosting Service Agreement

SolarEdge Technologies Ltd.

This is a preview - click here to buy the full publication

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

Part I - Installation

Screen Enclosure Protect your Screen against: rain, temperature, vandalism damage and theft

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Terms of Service. Your Information and Privacy

Transcription:

NEMA Standards Publication A Brief Comparison of NEMA 250 Enclosures for Electrical Equipment (1000 Volts Maximum) and IEC 60529 Degrees of Protection Provided by Enclosures (IP Code) Published by National Electrical Manufacturers Association 1300 North 17th Street Rosslyn, Virginia 22209 www.nema.org All rights including translation into other languages, reserved under the Universal Copyright Convention, the Berne Convention for the Protection of Literary and Artistic Works, and the International and Pan American Copyright Conventions.

NOTICE AND DISCLAIMER The information in this publication was considered technically sound by the consensus of persons engaged in the development and approval of the document at the time it was developed. Consensus does not necessarily mean that there is unanimous agreement among every person participating in the development of this document. The National Electrical Manufacturers Association (NEMA) standards and guideline publications, of which the document contained herein is one, are developed through a voluntary consensus standards development process. This process brings together volunteers and/or seeks out the views of persons who have an interest in the topic covered by this publication. While NEMA administers the process and establishes rules to promote fairness in the development of consensus, it does not write the document and it does not independently test, evaluate, or verify the accuracy or completeness of any information or the soundness of any judgments contained in its standards and guideline publications. NEMA disclaims liability for any personal injury, property, or other damages of any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the publication, use of, application, or reliance on this document. NEMA disclaims and makes no guaranty or warranty, expressed or implied, as to the accuracy or completeness of any information published herein, and disclaims and makes no warranty that the information in this document will fulfill any of your particular purposes or needs. NEMA does not undertake to guarantee the performance of any individual manufacturer or seller s products or services by virtue of this standard or guide. In publishing and making this document available, NEMA is not undertaking to render professional or other services for or on behalf of any person or entity, nor is NEMA undertaking to perform any duty owed by any person or entity to someone else. Anyone using this document should rely on his or her own independent judgment or, as appropriate, seek the advice of a competent professional in determining the exercise of reasonable care in any given circumstances. Information and other standards on the topic covered by this publication may be available from other sources, which the user may wish to consult for additional views or information not covered by this publication. NEMA has no power, nor does it undertake to police or enforce compliance with the contents of this document. NEMA does not certify, test, or inspect products, designs, or installations for safety or health purposes. Any certification or other statement of compliance with any health or safety related information in this document shall not be attributable to NEMA and is solely the responsibility of the certifier or maker of the statement.

Page 1 Section 1 GENERAL 1.1 WHAT IS IEC 60529 AND WHAT DOES IT COVER? IEC 60529 is a standard developed through the International Electrotechnical Commission (IEC) that describes a system for classifying the degrees of protection provided by an enclosure. An enclosure as used in 60529 is a part providing protection of equipment against certain external influences and in any direction protection against direct contact. As such, 60529 may be applied to products other than just metal or polymeric enclosures for electrical equipment for particular environmental conditions as covered by NEMA 250. (For example: An individual circuit breaker, switch, contactor, etc. may have an IEC 60529 IP rating. Until it is enclosed in a metal or polymeric enclosure, NEMA 250 would not apply.) 1.2 WHAT IS NOT COVERED BY IEC 60529? IEC 60529 is NOT a product standard and does not cover enclosure requirements other than the degree of protection provided. For instance IEC 60529 does not specify the corrosion protection and other environmental operating requirements and tests defined in NEMA 250. 1.3 WHAT DOES DEGREE OF PROTECTION MEAN IN IEC 60529? Degree of protection is a term used in the standard to describe the following: the protection of persons against access to hazardous parts inside the enclosure; the protection of the equipment inside the enclosure against ingress of solid foreign objects; the protection of the equipment inside the enclosure against harmful effects due to the ingress of water.

Page 2 Section 2 IP CODE 2.1 WHAT IS AN IP CODE? The IP Code is a designation that indicates the level, or amount, of the protection. The IP Code designation consists of the letters IP (International Protection) followed by two numerals. 2.2 WHAT DOES THE FIRST NUMERAL OF AN IP CODE INDICATE? The first characteristic numeral indicates the degree of protection provided by the enclosure with respect to persons having access to hazardous parts and with respect to solid foreign objects entering the enclosure. The first number specifies the following as described in Table 2 1: Table 2 1 IEC 60529 DEGREES OF ACCESS TO HAZARDOUS PARTS, FIRST CHARACTERISTIC NUMERAL First Characteristic Numeral With Respect to Persons With Respect to Solid Foreign Objects 0 Non-protected. Non-protected. 1 Protected against access to hazardous parts with the back of a hand. Protected against solid foreign objects > 50 mm diameter. 2 Protected against access finger. 3 Protected against access tool. 4 Protected against access wire. 5 Protected against access wire. 6 Protected against access wire. Protected against solid foreign objects > 12.5 mm diameter. Protected against solid foreign objects > 2.5 mm diameter. Protected against solid foreign objects > 1.0 mm diameter. Dust-protected (Dust shall not penetrate in quantity to interfere with satisfactory operation of the apparatus or to impair safety). Dust-tight (No ingress of dust).

Page 3 2.3 WHAT DOES THE SECOND NUMERAL OF AN IP CODE INDICATE? The second characteristic numeral indicates the degree of protection provided by the enclosure with respect to the harmful ingress of water. The second number specifies the following as described in Table 2 2: Table 2 2 IEC 60529 DEGREES OF PROTECTION AGAINST WATER INGRESS, SECOND CHARACTERISTIC NUMERAL Second Characteristic Numeral With Respect to the Harmful Ingress of Water 0 Non-protected. 1 Protected against vertically falling water drops. 2 Protected against vertically falling water drops when enclosure tilted up to 15 0. 3 Protected against spraying water. 4 Protected against splashing water. 5 Protected against water jets. 6 Protected against powerful water jets. 7 Protected against the effects of temporary immersion in water. 8 Protected against the effects of continuous immersion in water.

Page 4 Section 3 NEMA ENCLOSURE TYPE RATINGS/ IEC ENCLOSURE CLASSIFICATION DESIGNATIONS 3.1 IF A REQUIREMENT FOR AN ENCLOSURE TYPE IS SPECIFIED, CAN AN EQUIVALENT IP RATED ENCLOSURE BE SUBSTITUTED? NO! The IP Code only addresses requirements for protection of people, ingress of solid objects, and ingress of water. There are numerous other requirements covered by the Type designations that are not addressed by the IEC 60529/IP Codes. IEC 60529 does not specify the following: Construction requirements Door and cover securement Corrosion resistance Effects of icing Gasket aging and oil resistance Coolant effects The Type designation specifies requirements for these additional performance protections. For this reason, the IEC enclosure IP Code designations cannot be converted to enclosure Type numbers. 3.2 CAN A SPECIFICATION FOR AN IP CODE BE MET BY USING A TYPE ENCLOSURE? Possibly! Table 3 1 shows a matrix of the NEMA Type and IP Code designations for enclosures. This table provides a summary of the NEMA Type Enclosure Ratings that exceed the specification requirements for the respective IEC IP Code designations. This Table was created after a detailed review of each test requirement specified for a particular NEMA Type number, versus the test requirements specified for each IP Code. As previously stated, Table 3 1 cannot be used to convert from IEC IP Codes to enclosure Type numbers. 3.3 WHAT VALID USAGE EXISTS FOR IP CODES IN NORTH AMERICA? NEMA 250 is a product standard that addresses many aspects of enclosure design and performance requirements; IEC 60529 addresses only the degree of enclosure protection provided. As such an IP Code can only be used to supplement the NEMA Type designation; it cannot necessarily be used instead of a required NEMA Type designation. Two examples illustrate this point: Example #1: An enclosure meets all the requirements for a NEMA Type 4X rating and can be marked by an appropriate label. If the enclosure additionally meets the requirements for IP 56, it is appropriate to claim IP 56 compliance for the enclosure. Example #2: If a compartment within a NEMA Type 1 rating has been evaluated for compliance with the finger protection requirements of IEC 60529, it would be appropriate to claim IP 20 compliance for that compartment in addition to the NEMA Type 1 designation for the overall enclosure.

A Brief Comparison of NEMA 250 and IEC 60529 Page 5 Table 3 1 CONVERSION OF NEMA ENCLOSURE TYPE RATINGS TO IEC 60529 ENCLOSURE CLASSIFICATION DESIGNATIONS (IP) (CANNOT BE USED TO CONVERT IEC CLASSIFICATION DESIGNATIONS TO NEMA TYPE RATINGS) IP First Character 1 2 3 3R 3S NEMA Enclosure Type 4 4X 5 6 6P 12 12K 13 IP Second Character IP0_ IP_0 IP1_ IP_1 IP2_ IP_2 IP3_ IP_3 IP4_ IP_4 IP5_ IP_5 IP6_ IP_6 IP_7 IP_8 A B A B A B A B A B A B A B A B A B A B A B A B A B A = A shaded block in the A column indicates that the NEMA Enclosure Type exceeds the requirements for the respective IEC 60529 IP First Character Designation. The IP First Character Designation is the protection against access to hazardous parts and solid foreign objects. B = A shaded block in the B column indicates that the NEMA Enclosure Type exceeds the requirements for the respective IEC 60529 IP Second Character Designation. The IP Second Character Designation is the protection against the ingress of water. EXAMPLE OF TABLE USE An IEC IP 45 Enclosure Rating is specified. What NEMA Type Enclosures meet and exceed the IP 45 rating? Referencing the first character, 4, in the IP rating and the row designated IP4_ in the leftmost column in the table; the blocks in Column A for NEMA Types 3, 3S, 4, 4X, 5, 6, 6P, 12, 12K and 13 are shaded. These NEMA ratings meet and exceed the IEC protection requirements against access to hazardous parts and solid foreign objects. Referencing the second character, 5, in the IP rating and the row designated IP_5 in the rightmost column in the table; the blocks in Column B for NEMA Types 3, 3S, 4, 4X, 6 and 6P are shaded. These NEMA ratings meet and exceed the IEC requirements for protection against the ingress of water. The absence of shading in Column B beneath the NEMA Enclosure Type 5 indicates that Type 5 does not meet the IP 45 protection requirements against the ingress of water. Likewise the absence of shading in Column B for NEMA Type 12, 12K and 13 enclosures indicates that these enclosures do not meet the IP 45 requirements for protection against the ingress of water. Only Types 3, 3S, 4, 4X, 6 and 6P have both Column A in the IP4_ row and Column B in the IP_5 row shaded and could be used in an IP45 application. The NEMA Enclosure Type 3 not only meets the IP 45 Enclosure Rating, but also exceeds the IEC requirements because the NEMA Type requires an outdoor corrosion test; a gasket aging test; a dust test; an external icing test; and no water penetration in the rain test. Slight differences exist between the IEC and NEMA test methods, but the IEC rating permits the penetration of water if it does not deposit on insulation parts, or reach live parts. The IEC rating does not require a corrosion test; gasket aging test; dust test or external icing test. Because the NEMA ratings include additional test requirements, this table cannot be used to select IP Designations for NEMA rated enclosure specifications. IEC 60529 specifies that an enclosure shall only be designated with a stated degree of protection indicated by the first characteristic numeral if it also complies with all lower degrees of protection. Furthermore IEC 60529 states that an enclosure shall only be designated with a degree of protection indicated by the second characteristic numeral if it also complies with all lower degrees of protection up to and including the second characteristic numeral 6. An enclosure designated with a second characteristic numeral 7 or 8 only is considered unsuitable for exposure to water jets (designated by second characteristic numeral 5 or 6) and need not comply with requirements for numeral 5 or 6 unless it is dual coded. Since the IEC protection requirements become more stringent with increasing IP character value up through 6, once a NEMA Type rating meets the requirements for an IP designation up through 6, it will also meet the requirements for all lower IP designations. This is apparent from the shaded areas shown in the table. A Brief Comparison of NEMA 250 and IEC 60529 Page 5