Model: RDT. Automatic Transfer Switch 100-400 Amps. 200 amp load center models use up to 24 circuit breakers



Similar documents
RXT. Model: Model RXT Automatic Transfer Switch

Controller Features. Modbus link to define inputs and outputs. Programmable Outputs Auxiliary switch fault Common fault.

Model: RXT. Model RXT Automatic Transfer Switch. Standard Features. Standard Interface Board. Available Models

Model KSS. Transfer Switch Standard Features. Available Controllers. Ratings. Automatic Transfer Switches Standard Specific-Breaker Rated

MPAC 1500 Controller

Model KGS/KGP. Automatic Transfer Switches Bypass/Isolation. Transfer Switch Standard Features. Controller. Standard Transition Models (KGS) Ratings

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

ASCO SERIES 185 Power Transfer Switches

TS 910 AUTOMATIC TRANSFER SWITCHES OWNERS MANUAL

GTEC transfer switch open transition

Decision-Maker Paralleling System. Power Distribution Switchboards and Circuit Breakers. Standard Features

How To Operate A Gec Transfer Switch Open Transition Amp Power Supply

Automatic Transfer Switch Controller

Continuous Power... Continuous Protection

Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance/Non-Service Entrance

O & M Manual for the A EGSX Transfer Switch

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Applications. Remote Display Mounting Kits

Sentron Series Circuit Breakers

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

CPS Y S K CPS Y S C

Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, (210) 16 (407) 5.5 (140) (283) 16 (407) 5.5 (140)

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

Transfer switch BTPC open, closed or delayed transition

SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

ATC-300 Automatic Transfer Switch Controller

SmartOnline V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial

EVlink Electric Car Charging Stations Powering the Future of Sustainable Mobility

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

Electronic overload relay EF19 and EF45

FIREDEX Conventional Fire Panels

Electronic overload relay EF65, EF96 and EF146

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

80 Series - Modular timers 16 A. Features

Fire Pump Controllers Remote Alarm Panels

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Three-phase monitoring relay CM-PFE

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting

WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

Thyristor-controlled power supplies and battery chargers

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Power Supplies 3. SDN-P DIN Rail Series

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

CTS SERIES AUTOMATIC TRANSFER SWITCH

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

SECTION DETECTION AND ALARM

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

SECTION VARIABLE FREQUENCY DRIVES

80 Series - Modular timers 16 A. Features

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

City of Leesburg, Florida I.T. Data Center APPENDIX A TOSHIBA UPS INFORMATION

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

T5000 T000 LCD Digital Fan Coil Thermostat

Catalog January. Heavy industrial power applications Motor contactors and starters

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Diesel Engine Driven Generators Page 1 of 6

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Tmax MCCBs. Molded case circuit breakers. Tmax

The standards mentioned in this document

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Transfer Equipment Controls

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Distribution Dry Type Transformers

O & M Manual for the 200A EGSU Automatic Transfer Switch with RTC-100 Control

Series TS Amp. Automatic Transfer Switches

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

SmartOnline V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)

32VFD Variable Frequency Drives for Centrifugal Chillers

HM-W536 Install Guide

How To Test A Power Switch On A Power Supply

Electronic, Digital and Mechanical Vibration Switches

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Centro-Matic Automatic Lubrication Systems System Controls

SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Transcription:

Model: RDT Automatic Transfer Switch 100-400 Amps MPAC 500 Controller Features User-friendly interface with easy-to-read international symbols Source available and contactor position indicators LED indication of system faults Failure to acquire standby source Failure to transfer Auxiliary switch fault Common fault contact: latches closed on system faults shown above Engine start contact: provides contact closure to start the generator set Load control contact: allows 5-minute delay in startup of selected loads Test button (with or without load) Exercise set button Weekly 20-minute generator set exercise With or without load Single-phase voltage sensing on both sources, ±5% Line-to-line frequency sensing, ±2% Fixed time delays Standard Features UL listed Models with load centers, UL 67 listed, file #E251086 Models without load centers, UL 1008 listed, file #E58962 CSA certified, file #LR58301 (not applicable to service entrance models) 220/240 VAC, 50/60 Hz (selectable) 100, 200, and 400 amp models available Two-pole, single-phase open-transition transfer switch Contactor electrically and mechanically interlocked Double throw inherently interlocked design Solid neutral Contactor manually operable for maintenance purposes Silver alloy main contacts All models are 100% equipment rated and can be applied at the rated current without derating 100 and 200 amp models available with or without prewired Square D type QO load center 100 amp load center models use up to 16 circuit breakers (up to 8 tandem breakers can be used for a maximum of 24 circuits) 200 amp load center models use up to 24 circuit breakers Two enclosures available NEMA Type 1 steel ANSI 49 gray enclosure for indoor installation. 100 amp and 200 amp models without load centers can be recess-mounted between wall studs (not service entrance model) NEMA Type 3R corrosion-resistant aluminum ANSI 49 gray padlockable enclosure. Approved for indoor or outdoor installation Auxiliary position-indicating contacts (one set standard on 400 amp models only) Five-year limited warranty See page 5 for available accessories Service Entrance Model Features 200 and 400 amp service entrance rated automatic transfer switches available Service disconnect circuit breaker on the normal (utility) source (80% rated) NEMA 3R aluminum ANSI 49 gray enclosure (without load center) Circuit breaker for generator set battery charger Circuit breaker for engine heater (optional on 200 amp models, standard on 400 amp models) Auxiliary position-indicating contacts (one set standard on 400 amp models only) See page 5 for available SE model accessories G11-98 (Model RDT Automatic Transfer Switch) 12/11k Page 1

Operating temperature: Storage temperature: Humidity: Engine start Common fault Load control Environmental Specifications 20 C to70 C ( 4 F to 158 F) 40 C to85 C ( 40 F to 185 F) Contact Ratings Auxiliary contacts (optional; one set standard on 400 amp models) 5 to 95% noncondensing 0.5 A @ 125 VAC; 2A@30VDC SPST normally closed (NC) 0.5 A @ 125 VAC; 2A@30VDC SPST normally open (NO) 10 A @ 120 VAC SPST normally open (NO) 15 A @ 277 VAC Form C Source Sensing Undervoltage dropout 80% Undervoltage pickup 85% Underfrequency dropout 90% Underfrequency pickup 96% Time Delays Adjustment with Factory Accessory Board* Time Delay Setting Range Increment Engine start 3 seconds 1--10 seconds 1 second Transfer from Normal to Emergency 3 seconds 1--10 seconds 1 second Retransfer from Emergency to Normal 6 minutes 3--30 minutes 3 minutes Engine cooldown 5 minutes 1--10 minutes 1 minute Exercise run time 20 minutes 5--50 minutes 5 minutes Exercise interval 1 week 1 week/2 week (DIP switch) Load control connection delay Failure to acquire Emergency source 5 minutes 5 or 10 minutes (DIP switch) 78 seconds NA Undervoltage dropout 0.5 second NA Underfrequency dropout 3 seconds NA * Optional accessory board required for time delay adjustments NA = not adjustable Switch Size, Amps Cable Sizes AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections Range of Wire Sizes, Cu/Al Normal and Emergency (per phase) Load (per phase) Neutral Ground 100 (1) #14 to 1/0 AWG (1) #14 to 1/0 AWG (3) #12 to 1/0 AWG (9) #14 to #4 AWG 100 B (1) #14 to 1/0 AWG (1) #14 to 1/0 AWG (1)#6to2/0AWG (9) #14 to #4 AWG 200 (1) #6 AWG to 250 KCMIL (1) #6 AWG to 250 KCMIL (3) #6 AWG to 250 KCMIL (9) #14 to #4 AWG 200 B (1) #6 AWG to 250 KCMIL (1) #6 AWG to 250 KCMIL (1) #4 AWG to 250 KCMIL (9) #14 to #4 AWG 200 SE (1) #4 AWG to 300 KCMIL (1) #6 AWG to 250 KCMIL (1) #6 AWG to 250 KCMIL (3) #14 to #1/0 AWG 400 (2) #1/0 AWG to 250 KCMIL or (1) #4 AWG to 600 KCMIL (2) #1/0 AWG to 250 KCMIL or (1) #4 AWG to 600 KCMIL (6) #1/0 AWG to 250 KCMIL or (3) #4 AWG to 600 KCMIL (3) #14 to 1/0 AWG 400 SE (2) #1/0 AWG to 250 KCMIL (2) #1/0 AWG to 250 KCMIL (6) #1/0 AWG to 250 KCMIL (3) #14 to 1/0 AWG B = Load center model SE = Service entrance model G11-98 (Model RDT Automatic Transfer Switch) 12/11k Page 2

Contactor Ratings with Coordinated Circuit Breakers The transfer switches are UL listed at 240 VAC maximum. The following table lists contactor withstand current ratings (WCR) for 100--400 ampere non-service entrance rated switches with specific manufacturer s circuit breakers per UL and Canadian safety standards. Suitable for control of motors, electric discharge lamps, tungsten filament lamps and electric heating equipment where the sum of motor full-load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of switch rating. Switch Rating, Amps 100 10,000 200 10,000 400 65,000 WCR Ratings with Specific Manufacturer s Molded-Case Circuit Breakers WCR, RMS Symmetrical Amps Manufacturer Type or Class Maximum Size, Amps FCL, FB, QCHW, GB, GHB, GC, GHC, GD, EHD 100 Eaton/Cutler-Hammer FDB, FD, HFD, FDC, CA, CAH 150 FI,FC,FA,FH 100 QOM1, QOM1--VH 125 Square D Q2, Q2--H. Q2H 175 QOM2, QOM2--VH 225 QB, QD, QG, GJ 250 CED6, ED2, ED4, ED6, HED4, HED6, QP(Q2125), QPH(Q2125H) 125 Siemens QJ2, QJH2 150 THQB, THQC, THHQB, THHQC 100 GE THHQL, TQDL, THQDL 125 SE, TQD, THQD, THED 150 CSR/BHW, FD, HFD 225 JD, JDB, HJD 225--250 Eaton/Cutler-Hammer JDC 250 DK, KD, KDB, HKD, KDC, LCL, LA 400 Q2. QOM2, QOM2--VH, Q2--H, Q2H 225 Square D KI, KA, KH, KC, QB, QD, QG, QJ 250 LE, LX, LXI, LC, LI, LA, LH 400 Siemens FD6-A, FXD6-A, HFD6, CFD6 250 TQDL, THQDL 125 GE THLC2 225 SF 250 FCL, FB TRI-PAC 100 FD, FDC, HFD 150 HJD, JD, JDB, JDC 250 Cutler-Hammer HKD, KD, KDB, KDC, LA TRIPAC, LCL, DK, CHKD 400 HLD, CHLD, LDC, CLDC 300--600 NB TRI--PAC 300--800 FC, FH, FI 100 KA, KC, KH, KI 250 Square D LA, LC, LE, LH, LI, LX, LXI 400 LI, LXI, LX, LE, LC 600 MX, ME, MH 800 CED6, ED6, HED4, HED6, ED4 125 CFD6, HFD6, FD6, FXD6 250 Siemens CJD6, SCJD6, HHJD6, HHJXD6, SHJD6, HJD6, SJD6 400 CLD6, SCLD6, HHLD6, HHLXD6, SHLD6, HLD6 600 CMD6, SCMD6, HMD6, SHMD6, HMXD6, MD6, MXD6, SMD6 800 CF250L, CF250H 250 CJ400L, CK400H, CJ400H, CK400N 400 Merlin Gerin CJ600H 600 CK800H, CK800N 800 JHB 400 ABB S6 800 G11-98 (Model RDT Automatic Transfer Switch) 12/11k Page 3

Service Entrance Transfer Switch Ratings The service entrance transfer switch is factory-equipped with a normal source disconnect circuit breaker. Switch Rating, Amps WCR, RMS Symmetrical Amps at 240 VAC 200 22,000 400 35,000 The ATS meets or exceeds the requirements of the following specifications: Underwriters Laboratories UL 67, Enclosed Panel Boards (load center models) file # E251086 Underwriters Laboratories UL 1008, Standard for Automatic Transfer Switches for Use in Emergency Systems, file # E58962 Underwriters Laboratories UL 508, Standard for Industrial Control Equipment CSA certified, file #LR58301 (not applicable to service entrance models) NFPA 70, National Electrical Code NFPA 110, Emergency and Standby Power Systems IEEE Standard 446, IEEE Recommended Practice for Emergency and Standby Power Systems for Commercial and Industrial Applications Codes and Standards NEMA Standard IC10--1993 (formerly ICS2--447), AC Automatic Transfer Switches ANSI C37.90.1 (IEEE472), 2000, EFT/Surge Relay Systems EN61000-4-5 Surge Immunity Class 4 (voltage sensing and programmable inputs only) EN61000-4-4 Fast Transient Immunity Severity Level 4 IEC Specifications for EMI/EMC Immunity CISPR 11, Radiated and Conducted Emissions, Class B IEC 61000-4-2, 2001, Electrostatic Discharge IEC 61000-4-3, 2002, Radiated Immunity IEC 61000-4-4, 2001, Electrical Fast Transients (Bursts) IEC 61000-4-5, 2001, Surge Voltage Immunity IEC 61000-4-6, 2003, Conducted RF Immunity IEC 61000-4-8, Magnetic Field Immunity IEC 61000-4-11, Voltage Dips and Interruptions Weights and Dimensions Shipping Weight Enclosure Type Amps Load Center kg (lb.) Dimensions, H x W x D, mm (in.) 100 None 10 (22) 610 x 330 x 154 * (24.0 x 13.0 x 6.0) * 100 16 circuits 19.5 (43) 914 x 406 x 154 (36.0 x 16.0 x 6.0) NEMA 1 (steel) 200 None 11 (24) 610 x 330 x 154 * (24.0 x 13.0 x 6.0) * 200 24 circuits 20.4 (45) 914 x 406 x 154 (36.0 x 16.0 x 6.0) 400 None 68 (150) 1223 x 560 x 362 (48.1 x 22.0 x 14.3) 100 None 8.2 (18) 613 x 340 x 177 (24.1 x 13.4 x 7.0) 100 16 circuits 15 (32) 917 x 416 x 177 (36.1 x 16.4 x 7.0) 200 None 9.1 (20) 613 x 340 x 177 (24.1 x 13.4 x 7.0) NEMA 3R (aluminum) 200 24 circuits 16 (35) 917 x 416 x 177 (36.1 x 16.4 x 7.0) 200 SE None 17 (37) 858 x 473 x 163 (33.8 x 18.6 x 6.4) 400 None 54 (120) 1067 x 560 x 269 (42.0 x 22.0 x 10.6) 400 SE None 59 (130) 1067 x 560 x 269 (42.0 x 22.0 x 10.6) * Can be recess-mounted between 16 in. O.C. wall studs. Service entrance model G11-98 (Model RDT Automatic Transfer Switch) 12/11k Page 4

Available Accessories Accessory board Alarm horn indicates system faults Adjustable time delays: Engine start Engine cooldown Preferred to standby Standby to preferred Exercise duration Inputs and Outputs: Remote start/stop input (loaded) Programmable exerciser input Generator set supplying load output: 10 A @ 120 V SPST normally open (NO) contact External alarm module connection Dip switches: 1 week/2 week exerciser Load/no load exercise mode (for optional programmable exerciser) Momentary/maintained external start/stop input: Selects momentary (1 second) push button or maintained contact closure for remote start/stop signal Load control, 5 minutes/10 minutes: Allows adjustment of the startup delay after transfer to generator set for selected loads (e.g. air conditioners or other large motor starting loads) Audible alarm disable Auxiliary position-indicating contacts One closed on normal position and one closed on emergency position Form C contacts rated 15 A @ 277 VAC One set standard on 400 amp models External alarm module Alarm horn Alarm silence/lamp test button Remote start/stop button Generator supplying load indicator Fault indicator Fits into standard outlet box Multiple alarm modules can be connected Accessory board required Additional Accessories for Service Entrance Model Utility-side surge suppressor Highly reliable surge protection Fully automatic operation with automatic reset LED status indication Thermal fusing and short circuit protection UL 1449 (second edition) listed at 330 V Working voltage: 120/240 VAC split phase Maximum continuous operating voltage: 140 VAC Lines protected, AC: L--N, L--G, L--L, N--G Maximum surge current: 80kA per phase (8/20µs) Duty cycle performance (8/20µs): 80,000 A, 1 impulse 10,000 A, >4,000 impulses 100 A, infinite Long duration current pulse (10/10,000µs) capability: 3600 A (tested) Response time: <5ns Remote indication contacts: Normally open (NO) and normally closed (NC) contacts rated 2 A @ 250 VAC AIC short circuit rating: 100,000 RMS symmetrical amps, 240 V max. Operating temperature range: 40 C to85 C ( 40 F to 185 F) Humidity: 95% (non-condensing) Let-through voltage: 430 V @ 3 ka 690 V @ 10 ka 8/20µs waveform. Tested as per ANSI/IEEE C62.45 and ANSI/ IEEE C62.41 Enclosure space heater 150 Watts Hygrostat (humidity control) Built-in temperature limiter for overheat protection 15 A single-pole Square D type QO circuit breaker Accessory circuit breaker For generator set engine heater 15 A single-pole Square D type QO circuit breaker Standard on 400 amp SE models Programmable exerciser Seven-day programmable timer allows scheduling up to 56 on/off events LCD display indicates day, time, program/run modes, and on/off/skip status Skip next cycle button 5-year lithium backup battery Accessory board required Wall-mount bezel (for Type 1 enclosures) For 100 and 200 amp recess-mounted switches For NEMA type 1 enclosures only (not for NEMA 3R or service entrance switches) G11-98 (Model RDT Automatic Transfer Switch) 12/11k Page 5

KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455 Model Mechanism Transition Controls Voltage Poles Enclosure Current Rating Load Center Service Entrance Kohler Model Designation Key This chart explains the Kohler transfer switch model designation system. The sample model designation shown is for a Model R service entrance rated automatic transfer switch that uses a standard-transition contactor with MPAC 500 electrical controls rated at 240 volts/60 Hz, 2 poles, 3 wires, and solid neutral in a NEMA 3R enclosure with a current rating of 200 amperes and no load center. SAMPLE MODEL DESIGNATION RDT-CFNC-0200ASE Model R: Model R automatic transfer switch Mechanism D: Specific-breaker rated Transition T: Standard transition Electrical Controls C: MPAC 500 (Microprocessor ATS Control) Voltage/Frequency D: 220 Volts/50 Hz F: 240 Volts/60 Hz Number of Poles/Wires N: 2-pole, 3-wire, solid neutral Enclosure A: NEMA 1 (steel) * C: NEMA 3R (aluminum) Current Rating: Numbers indicate the current rating of the switch in amperes: 0100: 100 amps 0200: 200 amps 0400: 400 amps Load Center A: Without load center B: With load center (N/A for service entrance models) Service Entrance: SE: Service entrance model Blank: Not rated for service entrance * NEMA 1 only: 100 and 200 amp models without load centers can be recess-mounted between wall studs. Optional wall-mount bezel available. Service entrance transfer switches are available with 200 or 400 amp ratings with NEMA 3R enclosures and no load center. DISTRIBUTED BY: Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohler generator distributor for availability. 2004, 2005, 2007, 2008, 2009, 2010, 2011 by Kohler Co. All rights reserved. G11-98 (Model RDT Automatic Transfer Switch) 12/11k Page 6