NELES ND800 VALVE CONTROLLER Neles valve controller, as part of a total final control element, provides a means of improving process control accuracy. The ND800 can be used with either cylinder or diaphragm-type pneumatic actuators for rotary or linear valves. The ND800's unique ability to obtain better process accuracy lies in its use of a special control algorithm, derived from a mathematical simulation model developed by Metso Automation. This control algorithm is the basis for achieving dramatic improvements in control valve performance without concurrent changes in the control system. The ND800 monitors valve performance while on line, thus allowing for faster and more accurate valve response. The ND800 has no internal Iinks between modules. As a result, it is highly resistant to wear and to the effects of vibration. All moduls are easily replaceable in the field. The rugged cover protects the unit from environmental hazards and external abuse. The ND800 valve controller uses a standard twowire 4-20 ma current loop and is HART-compatible or Fieldbus powered digital signal 0-100 %, providing for low-cost installation. No external power supply is needed. ADVANCED CONTROL PERFORMANCE Microprocessor-controlled operation provides better accuracy and speed of response when compared with traditional positioners, resulting in reduced process variability. ECONOMICAL AND EASY TO USE Low air consumption reduces operational costs. Easy adjustment and parameter settings with local keypad and display, or by using auto tunnig HART connection or by Profibus PA. DIAGNOSTICS Built-in diagnostic capabilities accessed via the HART communication or Profibus PA connection allow more precise control and predictive maintenance. The ND800 allows predictive maintenance planning for the entire control valve by permitting valve performance on-line monitoring, trend analysis and deviation tracking. Graphic user interface, Windows-based Valve Manager software or PDM-configurator for Profibus PA can be linked into General Plant Management Systems. CE-MARK The ND800 carries the CE-mark concerning the countries which belong to the European Economic Area. FEATURES Fast and accurate response Operating algorithm developed from a control valve mathematical simulation model guarantees faster and more accurate response to control valve signal change. Faster response reduces process variability. Spool-type air valve provides very high air capacity leading to fast response times. Stable operation, control algorithms and optimization of parameters result in optimal performance of the control valve. Excellent vibration resistance Contact-free position feedback and spool valve drive do not depend on mechanical links which can be affected by vibration. The position sensor is immune to wear and unaffected by dirt. Feed back signal is free from electrical disturbances. Rugged construction, small moving masses and modular design with few parts. 7 ND 20EN Issue 9/2001
METSO AUTOMATION 4 3 98 54 51 40 PROFIBUS PA The ND84_ is a fieldbus powered. The configuration can be done either using local push buttons, PDM or some other suitable Profibus PA configurator. Local keypad and LCD display Easy to use auto calibration without external devices. Time-saving self-calibration. No need for hand-held terminal during installation. Valve Manager An embedded HART modem on the circuit board and a PDM or other suitable Profibus PA configurator allows remote parameter settings and access to predictive maintenance system. Connection; Device description. Change of an address in connection with Profibus PA Configuration; Parameter settings. Characterization; Via Nelprof valve sizing program. On-Line Monitoring; input current, valve position, actuator differential pressure and board temperature. EXPLODED VIEW 6 65 7 5 46 2 1 5 Diagnostics; Control error trend, travel duration histogram and load factor trend. Testing; Hysteresis & dead band; step response see separate instructions. HART Multiplexer Network makes predictive maintenance even easier. Low air consumption Air consumption a fraction of that of today s positioners. Installation Suitable for rotary or linear, double-acting or spring-return pneumatic actuators in different sizes. Enclosure Beacon position indicator on top. Metal case provides Faraday cage effect to protect electronics from EMC interference. Protects against mechanical damage. Protection class according to IEC IP65 or Nema 4 and 4x. OPTIONS Intrinsically safe construction for hazardous areas according to CENELEC EEx ia IIC T6/T5, BS 6941, ZONE 2 CSA Class I, Division 1 and 2, Groups A, B, C and D. FM Class I, Division 2, Groups A, B, C and D. For Profibus PA approvals are pending Combination of limit switches; electro-mechanical or inductive proximities. Low Temperature option -40 C/-40 F. DIN 43650 A/ISO 4400 connection plugs. Valve Manager software for point to point communication = HART 11. PDM/GSD-drivers in connection with Profibus PA Valve Manager software for Hart Multiplexer Networks = HART 12. Position transmitter, output 4-20 ma. EExi -approval also available. Pressure gauge kit. Air set. Conduit entries 1/2 NPT, M20 x 1.5 and R 1/2. Conduit male connector for Profibus PA Gold plated micro switches Profibus PA powered and configurated CONSTRUCTION MODULES Item Part Name Material 1 Housing Aluminium 2 Cover Aluminium *3 Prestage Stainless steel/aluminium *4 Spool valve Stainless steel/aluminium *5 Circuit board Std or Profibus PA (3 cards) *6 Position sensor *7 Differential pressure sensor 40 Shaft Stainless steel 46 Protective cover Aluminium 51 Ear Stainless steel 54 Coupling s jacket Plastic *65 Pointer Plastic 98 Gasket Rubber * Note: All these modules are replaceable. Part 4 and 98 are only recommended spare parts. - 2 -
NELES ND800 VALVE CONTROLLER PRINCIPLE OF OPERATION C2 C1 S SV PR 5 6 7 8 1 3 4 P µ C 1 2 3 4 HART α 4-20mA +HART Profibus PA 2+ The ND82_ is a 4-20 ma loop-powered microprocessorbased valve controller. A 3.8 ma minimum required input signal allows sufficient energy to begin communication via push buttons on the circuit board or via HART. A 275 HART handheld terminal or a PC with HART modem (Valve Manager ) can be connected to the terminal strip located in the ND800 itself or in the DCS. Maximum load voltage is 13.5 Vdc with 20 ma input signal. Using push buttons or HART the control parameters can be adjusted according to the actuator and valve in question. Then auto-calibration can be started via push buttons or HART. Display with three digits and text items shows the operation. The ND84_ is a fieldbus powered 9 to 32 Vdc microcontroller-based valve controller. The configuration can be done either using local push buttons, simatic PDM (Process Device Manager) or some other suitable Profibus PA configurator. In control service the microcontroller µc reads input signal (ma), position sensor (α) and differential pressure sensor (p). A change in input signal is detected by control algorithm inside µc. The microcontroller changes the pilot current to one of the prestage (PR) coils. The PR valve lowers the pilot pressure at the end of the spool valve (SV). The spool moves in the direction of low pressure to open the flow to the top of the actuator cylinder and to open the flow out from the other side of the piston. Differential pressure sensor (p) measures the cylinder pressure difference for µc. Increasing pressure difference over the piston moves the piston and rotates the feedback shaft. The position sensor measures the rotation for µc. The microcontroller calculates with the control algorithm a new pilot current until a new position of the actuator proportional to the input signal (ma) is reached. In the steadystate position the spool valve (SV) and prestage valve (PR) are closed. General TECHNICAL SPECIFICATIONS Enclosure Suitable for rotary and sliding-stem valves. Actuator connection in accordance with VDI/VDE 3845 standard. Action: Double- or single-acting. Turning angle: min. 45 - max. 95. Characteristic: Linear, equal percentage or freely defined with 11-point characterization exactly to application requirements through Valve Manager. Environmental influence Operational temp: -20 - +85 C / -4 - +185 F. Standard -40 - +85 C / -40 - +185 F. Optional Influence of temperature on valve position: Influence of vibration on valve position: < 0.05%/ C. < 1% under 2g 5-150 Hz and 1g 150-300 Hz 0.5g 300-2000 Hz. Material: Anodized aluminium alloy. Protection class: IP65, Nema 4 and 4x. Mechanical position indicator: on cover. Pneumatic ports: 1/4 NPT. Electrical connection: Screw terminals internal for 2.5 mm 2. Conduit entry: PG13.5 (1/2 NPT, M20 x 1.5 and R 1/2 as options). Weight: 2.1 kg / 4.6 lbs. Pneumatics Supply pressure: 2.5-8 bar / 36-115 psi. Effect of supply pressure : < 0.2 %/10kPa / 0.14%/psi. Air quality: as defined by ISA S7.3 standard. Capacity 4 bar / 60 psi supply: max. 30 Nm 3 /h / 18 scfm with 6 mm spool valve max. 12 Nm 3 /h / 7 scfm with 2 mm spool valve Consumption 4 bar / 60 psi supply: 0.4 Nm 3 /h / 0.24 scfm in steady state position. - 3 -
METSO AUTOMATION Electronics Supply power: Loop powered, 4-20 ma. No external power needed. Minimum signal: 3.8 ma. Current max : 100 ma. Load voltage: up to 13.5 Vdc/20 ma (corresponding 675 Ω.) (Maximum Voltage drop) Supply voltage: max. 30 Vdc Intrisically safe: Terminals 1 & 3 EEx ia IIC T6 U i = 28 Vdc I i = 120 ma P i = 1 W C i = 16 nf L i = 0 H Polarity protection: -30 Vdc. Over current protection: active over 25 ma. Supply power Profibus PA: 9-32 Vdc Power consumption: 23 ma Electronic current limitation: I max 24 ma in case of fault Performance with moderate constant-load actuators Intrinsically safe, code XU CSA Class I, Division 1 and 2, Groups A, B, C and D. Non-incendive code NU FM Class I, Division 2, Groups A, B, C and D certification. Position transmitter (optional) Output signal: 4-20 ma (galvanic isolation; 2500 Vdc). 0-100 % via Profibus PA -bus powered Supply voltage: 12-36 Vdc, 2-wire. 12-24 Vdc, for intrinsically safe. Power from external supply. Intrisically safe: Terminals 2 & 4 EEx ia IIC T6 U i = 24 Vdc I i = 120 ma P i = 1 W C i = 75 nf L i = 0 H Accuracy: < 2% Load resistance: max. 0-1200 Ω. max. 0-600 Ω, for intrinsically safe. Approvals: Intrinsically safe as option. CENELEC EEx ia IIC T5/T6. Limit switches (optional) Dynamic hysteresis and dead band < 0.8 %. Static hysteresis and dead band < 0.3 %. Local keypad functions Code K06: Ambient temperature: Micro switches OMRON D2VW-01, gold plated contacts -40...+85 C/+40...+185F * Calibration: Automatic / Manual * Control feedback: 0-3 (d and b) * Gain configuration: 0.1-3 (gain) * Mode selection: Auto/Man/Off. * Signal: Dir: Direct/reverse acting * Rotation: Rot: clockwise or counterclockwise to close * AO: Dead Angle * SAF: Cut-off safety range (default 2%) * Stroke limitation Input signal: Electrical connections 4-20 ma, 2-wire according to ANSI/ISA S50.1. Approvals Intrinsically safe; CENELEC EEx ia IIC T5/T6, code X CENELEC pr EN50021:1996 Ex nl IIC T6/T5, Zone 2 IEC79-15, First Edition 1987 Ex nc IIC T6/T5, Zone 2 British Standard: BS6941; 1988 Ex N IIC T6/T5, Zone 2 User interfaces Local: 3 keys + LCD display. HART: PC with Valve Manager software. Device Connection Type: Current Input Terminal impedance (Rtt): min. 310 ohms Terminal capacitance (Ctt): max. 5000 pf Profibus PA: Simatic PDM Configurator Electromagnetic protection Protection standards: EN50081-1 and EN50082-2. IEC 801-2 ESD, level 4. IEC 801-3 electromagnetic field, level 3. IEC 801-4 Fast Transients, level 4. Electromagnetic compatibility: CE marking 89/336/EEC. - 4 -
NELES ND800 VALVE CONTROLLER DIMENSIONS, mm / inch ND800/S1 21 0.83 1/4NPT M6x12 4 0.16 137 5.39 23 0.90 47.5 1.87 (3) 23.5 PG13.5 (0.12) 25 0.93 117 0.98 4.60 33 33 23 1.30 1.30 0.90 (35.4) (1.39) C2 S C1 F05-Ø50(VDI/VDE3845) ND800/S1/K00 and ND800/S1/I00 PG13.5 70 2.76 46 1.81 23.5 PG13.5 0.93 38 55 1.49 2.16 172 6.77 ND800/S1 (rotary) ø6 ø0.24 26.8 1.05 13.9 0.55 21 0.83 C2 S C1 33 33 23 1.30 1.30 0.90 (35.4) (1.39) (35.4) (1.39) M6 / 10 (VDI/VDE 3845) 23 0.90 137 5.39 47.5 1.87 39.5 5 0.20 29 1.14 137 5.39 ø15 1/4 NPT F05-ø50 2 0.08 44 1.73 1.55 ND800A (linear) C2 ø0.59 137 5.39 M6/10 39.5 1.55 (35.4) (1.39) - L = 1/2 NPT - I = M20x1.5 - NJ = R1/2 (26) (1.02) S C1 4 0.16 M5 / 18 - L = 1/2 NPT - I = M20x1.5 - NJ = R1/2 (26) (1.02) - 5 -
METSO AUTOMATION HOW TO ORDER 1. 2. 3. 4. 5. *) *) *) 6. *) ND 8 2 2 - / S1 / K 05 - ND 8 2 2 - / S1 / K 05 - *) Slash shall always be marked in places shown above. *) Slash shall always be marked in places shown above. 1. sign PRODUCT GROUP ND Valve controller 2. sign SERIES CODE 3. sign INPUT SIGNAL RANGE 2 4-20 ma 3 Foundation Fieldbus, Bus Voltage 9-32 Vdc ( pending ) 4 Profibus PA Bus Voltage 9-32 Vdc Transmission system to IEC 1158-2, Normative parts acc. to EN 50170 volume 2 Not applicable with 6. sign F, X, XU, ZU, NU, T, T1, T2, T3, P. 4. sign SPOOL VALVE 1 Ø 1 mm, double acting, available only with EC-actuators CONNECTIONS (S, C1, C2) 1/4 NPT, G 1/4 (S4) 2 Ø 2 mm, double action. 1/4 NPT, G 1/4 (S4) 6 Ø 6 mm, double action. 1/4 NPT, G 1/4 (S4) 11 21 61 Ø 1 mm, 3-way spool valve, single action, available only with EJ-actuators Ø 2 mm, 3-way spool valve, single action. Ø 6 mm, 3-way spool valve, single action. 1/4 NPT, G 1/4 (S4) 1/4 NPT, G 1/4 (S4) 1/4 NPT, G 1/4 (S4) 5. sign ACTION Double action, without sign. Specify 4. sign 1, 2 or 6. In connection with B_CU6,B_CU9, B_CU11, EC10 and EC12 actuators 4. sign must be 2. In connection with EC05 and EC07 4.sign must be 1. Single action, without sign. Specify 4. sign 11, 21 or 61. In connection with B_JU8, QP1, QP2, EJ07 and EJ10 actuators 4. sign must be 21.In connection with EJ05 4.sign must be 11. Not applicable with double acting actuators. A Linear motion, applicable to Metso Automation D/R-series diaphragm actuator. Not applicable to attachment face according to standard VDI/ VDE 3845 (6. sign S1). 21A is for RA and DA. 61A is for RB, RC, RD, RE and DB, DC, DE. Also applicable to linear actuators according to IEC 60534-6-1 with own linkage set. Specify 4. sign 2, 6, 21 or 61 according to stroke volume, specify the stroke (20-60 mm or 60-100 mm). 6. sign OPTIONS Standard, IP 65 enclosure, NEMA 4 and 4X. Built-in display and local keypad. PG 13.5 conduit entry. Temperature range -20 C... +85 C / -4 F... +185 F. Load voltage: up to 13.5 Vdc at 20 ma corresponding 675 Ω since Rev. 5.0 (maximum voltage drop). Supply voltage 30 Vdc. C F X XU ZU NU T T1 T2 T3 S1 S4 A Low temperature construction -40 C/-40 F. High limit for temperature according to option in question. Valve controller without HART. Available with standard, X, XU, ZU and NU constructions. Intrinsically safe construction. CENELEC EEx ia IIC T5/T6 certification (EN 50014, EN 50020). CENELEC draft pren 50021, Ex nl IIC T5/T6, Zone 2; IEC79-15, Ex nc IIC T5/T6, Zone 2; British Standard: BS 6941, Ex N IIC T5/T6, Zone 2. Temperature range -20 C... +75 C/-4 F... +167 F. T5, when temp. + 75 C/+167 F; T6, when temp. +50 C/+122 F. Load voltage up to 13.5 Vdc / 675 Ω / 20 ma. (Maximum voltage drop/supply voltage 30 Vdc.) CSA Class I, Divisions 1 and 2, Groups A, B, C and D certification. 1/2 NPT conduit entry. Temperature range 20 C... +70 C/-4 F... +158 F. Load voltage max. 13.5 Vdc / 675 Ω / 20 ma. CSA Class I. Division 2, Groups A, B, C and D certification. 1/2 NPT conduit entry. Temperature range 20 C... +70 C/-4 F...+158 F. Load voltage max. 13.5 Vdc / 675 Ω / 20 ma. No Zener Barriers needed. FM Class I. Division 2, Groups A, B, C and D certification. 1/2 NPT conduit entry. Temperature range -20 C...+70 C/-4 F...+158 F. Load voltage max. 13.5 Vdc / 675 Ω / 20 ma. No Zener Barriers needed. Position transmitter. Analog position feedback signal, output 4-20 ma. Load voltage up to 13.5 Vdc / 675 Ω / 20 ma. (Maximum voltage drop/supply voltage 30 Vdc.) Position transmitter. Analog position feedback signal, output 4-20 ma. Intrinsically safe construction CENELEC EEx ia IIC T5/T6. (passive). Available only with option X. Position transmitter. Analog position feedback signal, output 4-20 ma. Intrinsically safe construction. CSA Class I, Groups A, B, C and D. (passive). Available only with options XU or ZU. Position transmitter. Analog position feedback signal, output 4-20 ma. Intrinsically safe construction. FM Class I, Division 2, Groups A, B, C and D. (passive). Available only with option NU. Valve controller attachment face according to standard VDI/VDE 3845, equipped with an H-clip. When valve controllers are separate deliveries, VDI/VDE 3845 ear is supplied. Not applicable to globe valve diaphragm actuators (5. sign A). Valve Controller attachement face only for EC/EJ-actuators without air tubings. Pressure gauges, scale bar/psi/kpa, basic material brass, nickel plated housing stainless steel, glycerine filled. Temperature range -40 C... +70 C / -40 F... +158 F. - 6 -
NELES ND800 VALVE CONTROLLER *) 6. *) 7. 8. ND 8 2 2 - / S1 / K 05 - *) Slash shall always be marked in places shown above. *) *) 9. ND 8 2 2 - / S1 / K 05-6. sign OPTIONS P P1 P2 Y Connection plug according to DIN 43650A / ISO 4400 (PG11). Not available with options X, XU, ZU, NU, XT1, XUT2, ZUT2, NUT3 and accessories L, I, NJ. Connnection plug male eurofast, Weidmuller 945565, PG13,5 / M12 Available only with sign 3. and 4. Connection plug male minifast,turck RSFV48 / 13,5 Available only with sign 3. and 4. Special construction, to be specified. 9. sign OPTION OF LIMIT SWITCH - X P Y Standard IP 65 enclosure. NEMA 4 and 4X. PG 13.5 conduit entry (4 pcs). Temperature range according to switch type. Intrinsically safe construction. DEMKO EEx ia IIC T6 certification (EN 50014, EN 50020). Temperature range -20 C... +65 C / -4 F... +149 F. Connection plug according to DIN 43650A/ISO 4400 (PG11). Not available with options X, XU, ZU, NU and accessories L, I, NJ. Special construction, to be specified. 7. sign LIMIT SWITCH CODE I Inductive proximity switches, defined with 8. sign. K Micro switches, defined with 8. sign. 8. sign LIMIT SWITCH TYPE Inductive proximity switches (I), 2 pcs. P+F; NJ2-12GK-N. DC > 3 ma; < 1 ma. Intrinsically safe according to EEx ia IIC T6 (CENELEC EN 50014, 01 EN 50020), 2-wire type. Option of valve controller shall always be X (6. sign). 9. sign always X. Temperature range -20 C... +65 C / -4 F... +149 F. 56 05 06 06B ifm IFC 2002-ARKG/UP. DC; 150 ma, quiescent current < 0.6 ma, 2-wire. Not applicable to option X, XU, ZU, NU, P Temperature range -20 C... +80 C / -4 F... +176 F. Micro switches (K), 2 pcs OMRON D2VW-5, standard. Not applicable to option X, XU, ZU, NU, OMRON D2VW-01, gold plated contacts, 30 V DC/125 V AC, 100 ma Not applicable to options X, XU, ZU, NU, P. OMRON D2VW-01, gold plated contacts 30 Vdc, I < 100 ma Bus Powered, no external power needed Available only with sign 3. and 4. - 7 -
METSO AUTOMATION Subject to change without prior notice. Metso Automation, Field Systems Division Europe, Levytie 6, P.O.Box 310, 00811 Helsinki, Finland. Tel.int +358 20 483 150. Fax int. +358 20 483 151 North America, 42 Bowditch Drive, P.O. Box 8004, 01545 Shrewsbury, USA. Tel. int +1-508-852-3567. Fax int. +1-508-852-3562 Latin America, Av. Central, 181- Chácaras Reunidas, 12238-430, São José dos Campos, SP BRAZIL. Tel. int. +55 12 3935-3500. Fax int. +55 12 3935-3535 Asia Pacific, 501 Orchard Road, #05-09 Wheelock Place, 238880 Singapore. Tel. int. +65 735 5200. Fax int. +65 735 4566 www.metsoautomation.com