Applicability of Decorative Concrete Overlays as a Context Sensitive Solution for Vertical Infrastructure



Similar documents
ARDEX GUIDE SPECIFICATION ARDEX Exterior Concrete Repair & Resurfacing Polymer-Modified, Cement-Based, Patch & Horizontal Overlay Materials

Resurfacing Concrete. Page 1 of 5

Minor Cracks in Horizontal Surfaces

Concrete Repair. Applications and Procedures

Chapter 2 Basis of design and materials

Photo courtesy of Delta Stone, Heber City, UT. Installation Solutions for: Manufactured Stone, Natural Thin Veneer, and Thin Brick

Guidelines for Durable Driveways, Carports Patios, Walks, Garage Floors

INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles

Example Specification for Concrete using Current Building Code Requirements

Installation Solutions for: Manufactured Stone, Natural Thin Veneer, and Thin Brick ARCHITECTURAL SPECIFICATIONS / CAD MODELS TVISTM WARRANTIES

CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS

SECTION XXXXXX TECHNICAL SPECIFICATIONS FOR INSTALLATION OF PROTECTIVE COATINGS FOR MANHOLES, WETWELLS, AND OTHER SANITARY SEWER STRUCTURES

LAYING BLOCK AND BRICK

MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS

SECTION RESURFACING CAST IN PLACE CONCRETE

cement Masonry Cement Engineered for quality and reliability, Lafarge cements for masonry deliver consistent performance. page 2 Lafarge Cement

These recommendations generally follow the Construction Specifications Institute (CSI) Master Format.

Lesson 3. Portland Cement and Concrete

Concrete Resurfacing. System Guide. by Parchem Construction Supplies

Free-Form Concrete Pool

Moisture and Resilient Floor Covering

Manufactured Stone Veneer Installation Instructions

SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION CONCRETE BONDING COMPOUND.

Construction. 3-part thixotropic epoxy patching mortar. Product Description. Tests

Metropolitan Builders Association Masonry & Concrete Standard

Proper use of the Rebound Hammer Updated to reflect the changes to ASTM C805

RHOPLEX MC-1834P Cement Mortar Modifier

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS

Vanishing Lid Trays Construction Methods with Tile or Masonry

MARTIN TESTING LABORATORIES (MTL) PAINTS AND COATINGS TESTING CAPABILITIES

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

Wecryl Waterproofing System under surfacing supplied by others

738-B-297 POLYMERIC CONCRETE BRIDGE DECK OVERLAY. (Adopted )

Scotch-Weld TM. Acrylic Adhesives. DP8405NS Green. Product Data Sheet. Date: March 2014 Supersedes: August 2013

SECTION POLISHED CONCRETE FINISHING

K2 STONE NATURAL VENEER

BENTLEY ELEMENTS COLLECTION LVT

FIXIT.CH. Aerogel Insulating Plaster System. Handling Guidelines. Easy to use. Mineral based W/mK BAUSTOFFE MIT SYSTEM

TECHNICAL REQUIREMENTS AND SPECIFICATIONS

Lab 1 Concrete Proportioning, Mixing, and Testing

The Strength of Concrete

GUIDE SPECIFICATION COMBINATION SURFACE SYSTEM FOR NEW HOT MIX ASPHALT TENNIS COURTS I. PART 1 - GENERAL

OLD BRICK ORIGINALS KILN-FIRED THIN BRICK VENEER Installation Guide. GeneralShale.com

Natural Thin Stone Veneer

CHAPTER 3 MOISTURE TESTING

VC 104+ Rigid Grade / Rigid Grade Imagine VC 104 Rigid Grade Commercial Customised

Epoxy Crack Injection (the basics)

Hardened Concrete. Lecture No. 14

PROPERTIES AND MIX DESIGNATIONS

The AQUAFIN Approach to Concrete Repair

Strength of Concrete

GUIDELINES FOR POLISHED CONCRETE FLOORS A Guide for Integrally Colored, Dyed and Stained Polished Floors

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

Technical Data Sheet February 2014

Manufacturing Quality Concrete Products

International Greenhouse Company

Adhesive Recommendation for Altro Flooring. Porous (absorbent) subfloors (most wood subfloors and some concrete)

Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI

Thin Veneer Stone Installation Guide

Life-365 Service Life Prediction Model Version 2.0

WATERPROOFING OF WET ROOMS

Chapter 5 Bridge Deck Slabs. Bridge Engineering 1

High Performance PSA in Sheet Membrane in Water Protection

MASONRY INFORMATION. Selecting and Specifying Mortar and Grout for Unit Masonry. Introduction. Desirable Mortar Properties. Selection of Mortar

GigaCrete Specification PlasterMax

Tex-421-A, Splitting Tensile Strength of Cylindrical Concrete Specimens

Analysis of M35 and M40 grades of concrete by ACI and USBR methods of mix design on replacing fine aggregates with stone dust

Division 4 Section Concrete Masonry Specifications

FACT SHEET: HYDRATED LIME FOR MASONRY PURPOSES

Standard Method for Sampling and Analysis of. of Chlorine Containing Bleaches. Soap Products

Dryvit Finish System For Exterior Soffits

Bonding Agents: The Good, the Bad, and What Works. Bond with Your Concrete

TECHNICAL SPECIFICATIONS CONCRETE SIDEWALKS, DRIVEWAYS AND CURB AND GUTTER

CA-48 TECHNICAL SPECIFICATION

1.02 DESCRIPTION A. This Section specifies furnishing and installing Cast in Place Detectable/Tactile Warning Surface tiles where indicated.

SEE HOW TO MAKE LIME PLASTER WHY USE LIME? PATTI STOUTER, BUILD SIMPLE INC. FEBRUARY 2013

CRACK and JOINT REPAIRS on INDUSTRIAL CONCRETE FLOORS, PAVEMENTS and SECONDARY CONTAINMENT AREAS

VIRGINIA DEPARTMENT OF TRANSPORTATION MATERIALS DIVISION MEMORANDUM

Dubai Municipality Standard DMS 1: Part 5: 2004

MINIMUM QUALITY CONTROL PLAN FOR FIELD PLACEMENT OF LATEX MODIFIED MORTAR OR CONCRETE WEARING SURFACE

T R A N S F E R A B L E F U L LY

Demonstration of an Innovative Large-Diameter Sewer Rehabilitation Technology in Houston, Texas

A NEW APPROACH FOR MEASUREMENT OF TENSILE STRENGTH OF CONCRETE

Scotch-Weld. Low-Odor Acrylic Adhesives DP810 DP810 NS. Technical Data June, 2004

SECTION FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)

Guide Specifications for Maple Flooring Systems

SOLAR SOLUTIONS BONDED MOUNTING TECHNOLOGY. DURABLE BONDING OF PV MODULES TO MOUNTING SYSTEMS WITH Sikasil

Scotch-Weld TM. Epoxy Adhesive 1838 B/A Green 1838 B/A Tan 1838-L B/A Translucent. Technical Data February, Product Description

Mortars for Brickwork - Selection and Quality Assurance

LEGACY REPORT. (800) (562) A Subsidiary of the International Code Council. *Corrected March 2014

ELASTOCEM. Technical features. Applications. Two-component flexible, waterproofing and protective cementitious grout.

Installation PowerPoint for Grasscrete Formers

Ron Miedema Cement Contractor 1865 Pine Ridge ~ Jenison, MI 49428

Shower Walls and Tub Surrounds

Acceptance Criteria for Durability Tests

G VYCOR DECK PROTECTOR. For longer lasting decks, install Grace Vycor Deck Protector. It s an easy add-on to your deck projects.

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

Fire and Concrete Structures

Transcription:

Applicability of Decorative Concrete Overlays as a Context Sensitive Solution for Vertical Infrastructure Jason Riegler 1, Ryan DaPonte 2, Aleksandra Radlinska 3,and Leslie McCarthy 4 1 Graduate Researcher, Civil and Environmental Engineering, Villanova University, 800 Lancaster Avenue, Villanova PA 19085 USA. Email: jason.riegler@villanova.edu 2 Undergraduate Research Assistant, Civil and Environmental Engineering, Villanova University, 800 Lancaster Avenue, Villanova PA 19085 USA. Email: ryan.daponte@villanova.edu 3 Assistant Professor, Civil and Environmental Engineering, Villanova University, 800 Lancaster Avenue, Villanova PA 19085 USA. Email: aleksandra.radlinska@villanova.edu 4 Assistant Professor, Civil and Environmental Engineering, Villanova University, 800 Lancaster Avenue, Villanova PA 19085 USA. Email: leslie.mccarthy@villanova.edu ABSTRACT: The concept of applying Decorative Concrete Overlays (DCO) in infrastructure is an innovative solution that supports the widespread implementation of green engineering through Context Sensitive Solutions (CSS). The purpose of this research was to determine the limits of durability on decorative concrete overlay in terms of bond strength. Although DCO has been used extensively in horizontal applications such as sidewalks and driveways, the parameters of feasibility and durability must be tested for its use on vertical infrastructure surfaces (bridge piers, traffic barriers, noise walls, etc.). This study looks at initial evaluation of these parameters by conducting laboratory testing to measure flexural fatigue and adhesion strength of DCO on two sets of specimens varying in age; 28 days old vs. 125 days old. The flexural fatigue results proved that the bond between concrete and DCO was very effective. Even though the concrete finally failed under the increasing load, the DCO product remained completely bonded as evidenced by the cracked chips of specimen surface. The adhesion strength of the DCO bond to beam specimens varied and results indicated that this difference in strength is due to the thickness of the DCO coating rather than the age of the concrete. INTRODUCTION Page 1

The Federal Highway Administration (FHWA) strongly encourages state transportation agencies to more extensively implement context-sensitive solutions (CSS) into new and existing transportation facilities. Context-sensitive solutions are defined as: A collaborative, interdisciplinary approach that involves all stakeholders to develop a transportation facility that fits its physical setting and preserve scenic, aesthetic, historic and environmental resources, while maintaining safety and mobility [1]. A tool which has hitherto been used in landscape architecture but not in transportation is decorative concrete overlay (DCO), a microtopping of a polymeracrylic cementitious product. Decorative concrete overlay is one potential tool for CSS and can be applied directly on top of new or existing concrete. A great benefit of using DCO as a CSS is its versatility to be color-admixed, patterned, textured and stained to resemble stone, brick, wood, tile or many other materials. Unlike other CSS tools like cast-in-place panels or stamped concrete, DCO can be quickly applied to existing concrete structures or new construction after the process of surface preparation, thus making the structure more aesthetically pleasing. Preparation of Test Samples The first step in determining the durability of DCO was to identify a series of appropriate laboratory tests. It was determined that flexural fatigue tests and adhesion tests would be conducted as initial experiments. During sample specimen preparation, the beams were cast using wooden forms as shown in Figure 1. A total of 12 beams were constructed using ½-inch (1.27-cm) plywood as the base of the formwork, adding 2x6 pieces of wood as the walls. Each beam was measured precisely at 3 ft x 5.5 in. x 5.5 in. (91.44 cm x 13.97 cm x 13.97 cm) in dimension. FIG. 1. Beam formwork Since the primary purpose of the experimentation was specifically to test the durability of DCO on vertical components of infrastructure, the concrete mixture was designed in accordance with Pennsylvania Department of Transportation (PennDOT) specifications for vertical structures [2]. In order to be consistent with PennDOT Section 714 (standards for concrete barriers, median barriers, and sound barrier panels), the design used No. 57 coarse aggregate, standard Type A fine aggregate, and ordinary portland cement. The concrete was designed to have a water to cement Page 2

ratio of 0.45 and an air content of 6%. The specimens were mixed using a 7-cubic foot concrete mixer and poured into the formwork following ASTM C192 procedure [3]. Additionally, each beam was reinforced with one #5 bar placed directly in the center of the sample shown in Figure 2a. After 24 hours, the samples were removed from the forms, and moved to the moist room at a constant temperature of 22.8 C (73 F) with a relative humidity of 100% maintained for 7 days. Figure 2b presents an example of the cured concrete beams. (a) (b) (c) FIG. 2. (a) Beam specimens, (b) Cured concrete beam, and (c) Grinding surface DCO Application Process A complete surface preparation of the specimens is essential to ensure optimum bond strength between the structural concrete and the decorative overlay [4]. Therefore sufficient cleaning and profiling of the concrete was necessary to prevent any bonding failures. There are two conditions that must be met before the coating can achieve a strong bond with the concrete. The first condition is that the surface must be clean of dirt, chemicals, and other contaminants. The second condition is that the surface must be given a mechanical etch or profile. Scarifying or grinding down the surface (as shown in Figure 2c) removes any dirt, coatings, grease, or sealers. Denatured alcohol was then rubbed onto the surface of the concrete for etching. The final step of preparation was high pressure water jetting to finalize the cleaning process before any decorative concrete overlay was applied. This preparation was done prior to DCO application on both series of sample to be tested at 28-days and 125-days. The mixture components of the decorative concrete overlay include cement (series 105 polymerized dry component), a liquid modifier (modified acrylic resin), and any desired colorant [5, 6]. The proportion of a complete mixture used was 8 ounces colorant to 4.25 gallons modifier to 50 pounds of cement. The mixing process occurs immediately prior to application of DCO to the test specimens. After the mixture is complete, DCO can be applied using a trowel, sponge, and/or spray gun. While each technique can be used either separately or concurrently, the test beams were only treated using a trowel and spray gun. The first coat was applied using a trowel while the second coat was sprayed on. Before the first mixture of DCO is mixed and applied, a primer coat containing 3 parts water and 1 part liquid modifier was sprayed onto the concrete surface to ensure enhanced adhesion of the Page 3

decorative concrete overlay to the surface for the purpose of increasing the durability of the overlay. Once the concrete surface is slightly moist with the primer coat, the first coat of sandstone-colored DCO was applied using a trowel and allowed to dry for approximately two hours (Figure 3a). Afterward, a second coat with gray colorant was applied using a spray gun as pictured in Figure 3b. This procedure was also applied on slab specimens to resemble a monochromatic brick pattern as pictured in Figure 3c. Grout lines were made by laying tape lines as desired prior to spraying the second coating of red colorant on the slabs. (a) (b) (c) FIG.3. (a) First coat (sandstone), (b) Second coat (gray), (c) Slab brick pattern The last and final step to the decorative overlay process was to apply two series 150 clear coats. A double-layered clear coat is designed to enhance the DCO s durability by providing additional protection against various environmental conditions including temperature, sunlight, and humidity, as well as preventing the penetration of dirt and chemicals. The series 150 clear coat also enhances the color of the DCO by making it more vibrant. Manufacturers recommend that the clear coat be reapplied every three years to the overlay for the purpose of preventative maintenance [7]. Flexural Fatigue Testing This test method covers the determination of the flexural strength of concrete by the use of a simple beam with third-point loading [8]. In relation to decorative overlay durability, the flexural fatigue test was used to investigate the effect of cyclical loading on the bond of the DCO to concrete. The simply-supported reinforced decorative concrete beam specimens were subjected to loads applied in 200-lb increments, and then qualitatively examined for cracks and other failures in the overlay. The apparatus, as pictured in Figure 4a and 4b, included a load cell, hydraulic piston, and a deflection gauge located at the center span of the beam. As the amount of force at center-span increased, the decorative concrete beam was monitored for cracking, particularly in the overlay. All 12 beams were loaded until failure. Page 4

(a) (b) FIG. 4. (a) Flexural fatigue test system, (b) Piston applying force to load cell In all twelve tests that were conducted, the concrete failed close to the center (Figure 4b), causing the decorative concrete overlay to bubble and chip off. However, an inspection of the chips that had peeled off revealed that the overlay had remained attached to the top layer of the broken concrete pieces. This implies that the force applied to the beam caused spalling to the concrete and not the decorative overlay (concrete fractured rather than the overlay) as seen in Figures 5a and 5b. Under cyclical loading, the reinforced concrete beam failed as expected with cracking and spalling primarily at center span. Directly underneath the hydraulic piston, no cracks were found in the overlay. Ultimately for both the 28 and 125 day specimens, the bond between the decorative overlay and the concrete endured the force applied from the piston. The load-deflection plots in Figures 6a and 6b demonstrate that all twelve beams behaved as typical reinforced concrete beams. (a) (b) FIG. 5. (a) Spalling on beam 2, (b) Spalling on beams 1-4 (a) (b) FIG. 6. (a) Beam 2 (28-days), (b) Beam 11 (125-days) Page 5

Pull-off Adhesion Strength Testing In order to further investigate the potential of DCO as a viable CSS tool, another bond durability test was conducted. The strength of the overlay to the decorative concrete beam before and after failure was evaluated as per ASTM Standard D-7234-05. This test determines the greatest perpendicular force (in tension) that a surface area can bear before a plug of material is detached [9]. While attached to the decorative concrete overlay, the portable pull-off adhesion tester (Figure 7a) applied a uniformly-increased concentric tensile load until the localized layer of overlay (Figure 7b) was separated from the concrete piece (Figure 7c). (a) (b) (c) FIG. 7. (a) Apparatus, (b) Before DCO removal, (C) After DCO removal As reported in Table 1, the force required to remove the DCO from the concrete was much greater with the 28-day old beam specimens than it was for the 125-day old beam specimens. The average adhesion strength for the 28-day old beams and the 125-day old beams was 286 psi and 131 psi, respectively. However, data implies that the difference in strength was not dependent on age of the test beams, but rather on thickness of the DCO coating on the 125-day specimens (applied twice as thick as on 28-day beams). As a result, the increase in thickness produced a weaker bond to the concrete. Table 1. Adhesion Strength, 28 days vs. 125 days Age (days) Strength (psi) Specimen 1 28 109 Beam 2 28 312 Beam 3 28 439 Beam 4 28 285 Beam 5 125 64 Beam 6 125 45 Beam 7 125 97 Beam 8 125 310 Beam 9 125 101 Beam 10 125 166 Beam 11 120 104 Outdoor Slab 12 120 122 Outdoor Slab Page 6

In order to capture real-time weathering and temperature effects, DCO was applied to an outdoor field slab (Figure 8) in November 2009. Pull-off adhesion strength testing was conducted when the outdoor slab had already experienced four months of exposure to multiple freeze-thaw cycles, and multiple snowstorms, throughout the winter and spring seasons. The results from the portable pull-off testing on the outdoor field section are well within the range shown for other beams of the same age (Table 1). CONCLUSIONS FIG. 8 DCO on outdoor field slab The intent of the research was to provide initial steps in evaluating a new potential context sensitive solution for state transportation agencies to utilize on new or existing infrastructure. Thus far, the research has shown that decorative concrete overlay (DCO) appears to be a viable and easily accessible tool for today s infrastructure. In comparison to other CSS tools such as stamped concrete and castin-place panels, DCO demonstrated advantages such as ease and speed of application by three simplistic approaches (trowel, sponge, and/or spray). Flexural fatigue and adhesion test results, which were conducted on both 28-day and 125-day old specimens, confirmed that the bond of DCO to structural concrete can withstand extreme load conditions as well as substantial tensile forces. In all twelve flexural fatigue tests, the bond of DCO to concrete was only broken along fracture lines, implying that it was the concrete that had cracked rather than the overlay under increased loading. Average adhesion strength values indicated that the thickness of DCO can significantly influence the bond to structural concrete. The thinner DCO surfacing showed a double increase in bond strength. Extreme weathering and realtime temperature cycling of a concrete field slab treated with DCO did not appear to degrade the bond strength when compared to laboratory-controlled samples. Initial research has indicated that the durability of DCO make it an effective option for the aesthetic treatment of vertical infrastructure surfaces. RECOMMENDATIONS Initial results from testing DCO indicate a deal of promise as a CSS tool; however, further research is required to test its durability in full-scale environmental conditions. For example, an investigation into sodium chloride ponding and sodium chloride tank submersion is necessary to determine the effect of salt solutions on the structure and Page 7

appearance of the overlay. This is particularly important to ascertain the use of DCO on infrastructure components that would be subjected to deicing salts (walkways) or aqueous conditions (bridge piers). Also, an extensive look into the behavior of DCO subjected to ultra-violet light testing and freeze-thaw cycling would give important insight on its ability to withstand fundamental weathering conditions. Additionally, results from the adhesion testing stressed the importance of maintaining as thin a layer of DCO as possible. This could be most reasonably achieved by the use of professional contractors who are trained in the successful application of DCO. ACKNOWLEDGMENTS The authors appreciate the generous support of Villanova University, AiRestoration, Dauphin Masonry, Inc., CTI, and Rowan University. REFERENCES [1] Deatrick, John, and Shari Schaftlein. Results of Joint AASHTO/FHWA Context Sensitive Solutions Strategic Planning Process. Rep. Raleigh: Center for Transportation and the Environment, 2007. Print. [2] United States of America. Commonwealth of Pennsylvania. Department of Transportation. Section 714 - Precast Concrete Products. Print. [3] ASTM (2007), C192/C192M-07, Standard Practice for Making and Curing Concrete Test Specimens in the Laboratory, West Conshohocken, Pa. [4] Wheelabrator, William F. "Surface Prepararion for Concrete Flooring." Journal of Protective Coatings and Linings (1989). Web. [5] Concrete Technology Inc. (2009), CTI System Series 110/111 Modifier, Concrete Technology Inc., Largo, FL. [6] Concrete Technology Inc. (2009), CTI System Series 105 Grout, Concrete Technology Inc., Largo, FL. [7] Concrete Technology Inc. (2009), CTI-200 Series Pro Seal Sealer, Concrete Technology Inc., Largo, FL. [8] ASTM (2008), C 78-08, Standard Test Method for Flexural Strength of Concrete (Using Simple Beam with Third-Point Loading), American Society for Testing and Materials, West Conshohocken, PA. [9] ASTM (2005), D 7234-05, Standard Test Method for Pull-Off Adhesion Strength of Coatings Using Portable Pull-Off Adhesion Testers, American Society for Testing and Materials, West Conshohocken, PA. Page 8