BD150 INDUSTRIAL DEHUMIDIFIER USER MANUAL



Similar documents
USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

Meaco 30L and Meaco 40L dehumidifier instruction manual

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

PORTABLE AIR CONDITIONER

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Dehumidifier D 850E. - Instruction manual version 02

GenStore Archive Cabinet

Operating Instructions Split System Air Conditioner

LOBOY 16 AIR CONDITIONERS

Portable Evaporative Air Cooler. OWNER S MANUAL Read and save these instructions before use. Model: CL30XC

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Dehumidifier Users manual. For Models: DH45S DH65S

Meaco 10L Basic Small Home Dehumidifier

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

ECOCIAT. Domestic hot water heat recovery unit

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

Vertical Display and Storage B SKOPE Gen2: Three Door Chiller

Use and Care Manual. Model CPA12KH AIR CONDITIONER

USER S MANUAL HSC-24A

ThermoStar Refrigeration Air Dryers

Failure code manual. content

Series IDU/IDF. Refrigerated Air Dryer

CRAC Precision climate control units for data centres

Bauknecht AG, Industriestrasse 36, 5600 Lenzburg,

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

Troubleshooting Your Refrigerator

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

SAFEGUARDING THE ENVIRONMENT

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

INFRARED QUARTZ WALL HEATER

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

WINDOW ROOM AIR CONDITIONER

Portable Air Conditioner INSTRUCTION MANUAL

hore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &

Operating Instructions Air Conditioner

Instruction manual for Firstline FCS12000CH

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

PORTABLE AIR CONDITIONER

Undercounter & Slimline Cabinet Range HR/LR 120 HRB/LRB120 HR/LR 140 HR/LR 150 HR/LR 200 HR/LR 240 HR/LR 360 HR/LR 410

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

Built in Fridge Freezer LAM6800. Installation & Operating Instructions

Refrigerated Air Dryers. Catalogue

GENANO 4500 MEDICAL AIR PURIFICATION DEVICE

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

V94 BULK TAPE DEGAUSSER

HP switch LP switch Discharge thermo Comp. Surface thermo

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM EXPLOSION VIEW 12 6.

CW-5000/ 5200,1'8675,$/ &+,//(5 86(5 0$18$/

INSTRUCTION MANUAL CIRRO MK 3/TYPE 2 MIST GENERATOR

Meaco DD8L desiccant dehumidifier Instruction Manual

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

CR Band Auto Set Dual Alarm Clock Radio ROBERTS. Sound for Generations. Please read this manual before use

SIBIR MANUAL V110 KE. English page 5 RKE - 1D

Refrigeration Air Dryers. Catalogue

SILENT10 PORTABLE AIR CONDITIONER USER MANUAL

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex

Rittal White Paper 305: Selecting Air Conditioners for Industrial Enclosures By: Judith Koetzsch Mark Corcoran, Editor

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

technical data air conditioning systems RXS E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

Room Air Conditioners

Portable Evaporative Air Cooler for Outdoor, Indoor & Commercial Use. OWNER S MANUAL Read and save these instructions before use.


SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL

SHHH AIR COMPRESSOR Model Nos. SHHH2 - SHHH2/9 - SHHH3/9 - SHH3/24

CORNER FRIDGE THERMOLUX TL6 - TL10 - TL16 INSTALLATION AND OPERATION INSTRUCTIONS

Technical data. Danfoss DHP-A

Transformer oil cooler ALFA A02

OR S HANDBOOK Kenco S i n g l e s B r e w e r OPERA

COMPRESSED AIR DRYER

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps)

AFE424 SERVICE PARTS

INDUSTRIAL DIRECT DRIVEN PISTON COMPRESSORS CL - CH - CK

Important Safeguards

MFU200 Integrated Under Counter Larder Fridge

Split Type Room Air Conditioner. KSWM units

Geyser-R Heat pump water heater Installation manual

EVAPORATIVE AIR COOLER INSTRUCTION MANUAL

AIR-CONDITIONER SPLIT TYPE

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

RE-3 : SOLID TOP RANGE RANGE TOP ONLY

Operating Instructions Air Conditioner

Gree Solar Hybrid Hi Wall Inverter Air Conditioner

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

AIR DEHUMIDIFYING Condensation drying for industry and trade

Table Z. Troubleshooting Chart for Air Conditioners. Cause

ON-VEHICLE INSPECTION

IMMERSION MANAGEMENT SERVICE KG

SMD Rework Station TABLE OF CONTENTS

SAFETY PRECAUTIONS Read all of the instructions before using this appliance. When using this appliance, always exercise basic safely precautions,

T-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N

Transcription:

BD150 INDUSTRIAL DEHUMIDIFIER USER MANUAL Drawing : - TPC337 Issue : - 2 Date : - 24/01/12

UNPACKING Thank you for deciding to purchase an EIPL Industrial dehumidifier. Like the many tens of thousands of people who have already bought an EIPL dehumidifier we are confident you will find it is the most effective answer to the problem of condensation and dampness related problems. room, or other enclosed space where the dehumidifier is used. IMPORTANT Your industrial dehumidifier is packed in a plastic wrapping please ensure that it is disposed of safely where it will not be a danger to children. INTRODUCTION Carefully remove the BD150 dehumidifier unit from it s transit box and visually check for any signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Retain the packaging for further use, or dispose of it considerably. This user manual tells you how to use the BD150 dehumidifier. Please read it thoroughly before operating the dehumidifier. If you have any questions about the unit please contact our Customer Service Department at the address shown at the back manual. Dehumidifiers remove moisture from the air circulating through it. Continuous operation reduces the relative humidity of the air and this helps prevent rust, rot, mould, mildew and condensation within the A dehumidifier consists of a motor, compressor unit, a refrigerant condenser, an air circulating fan, a refrigerated surface, a means of collecting and disposing of the condensed moisture and a cabinet to house these components. GENERAL EIPL Industrial dehumidifiers can be stored and transported in the horizontal or vertical position. To operate, stand the unit upright, connect power and it is ready for operation. When a generator is used to supply the power, it is essential to check the minimum kva required in the technical section within this manual. The generator must be started before connection is made to the dehumidifier.

OPERATION The fan draws moist air through the refrigerated surface which cools it below it s dew point, removing moisture which is collected and lead away. The cool air then passes over the hot condenser, where it is reheated. With the addition of other radiated heat the air is discharged into the room at a higher temperature but a lower relative humidity than when the air entered the unit. Continuous circulation of the room air through the dehumidifier unit gradually reduces the relative humidity in the room. The BD150 Industrial Dehumidifier is a robust, compact unit designed to control the humidity in the enclosed space in which it is placed. The unit is thermally protected and will switch off for a period if the maximum operating temperature of 35 C is exceeded. MAINS PLUG WIRING INFORMATION FOR EBAC INDUSTRIAL DEHUMIDIFERS IMPORTANT The wires in the mains lead are coloured and must be connected as shown in the diagrams above by a qualified electrician. ELECTRICAL CONNECTIONS The wire which is coloured Green and Yellow must be connected to the terminal marked E or by the Earth symbol. The wire which is coloured Blue must be connected to the terminal in the plug which is marked with the letter N or coloured Black. The wire which is coloured Brown must be connected to the terminal which is marked with the letter L or coloured Red. CHANGING THE FUSE 13 amp fuses that are ASTA approved to BS1362 should only be used.

BASIC STEPS FOR DRYING Ensure that all EXTERNAL doors and windows are CLOSED. Where no doors or windows are fitted, temporarily screen off the openings. POSITIONING For small areas position centrally in the area to be dried. For larger areas such as open plan buildings, offices, factories, a number of dryers may be required, in such cases they should be spread evenly around the area. Ensure that no unit is positioned in such a way that it blows directly into another. For private house or flats, position the dryer on one floor at a time, starting at the lowest floor, closing all internal doors on the floor previously dried. Continue until all floor levels have been dried. Note when a particular damp patch is to be dried out that the air outlet grille should be directed towards that area but should NEVER be closer than 1m to the surface. At no time should the inlet grilles be covered or obstructed. DRAINAGE Under most operating conditions water will be produced continuously and it is important that it is drained away correctly and not allowed to spill. Any spillage will evaporate and will, therefore, have to be recycled through the dryer again, which in effect, only prolongs the drying period. PORTABLE CONTAINERS Position a closed top container underneath the water discharge pipe (approximately 25 litre capacity). Place a short length of pipe one end over the discharge pipe and the other end in the container. Use a transparent container, this will enable you to check the level of the water and so prevent overflowing. As the unit will be running for long periods of time, e regular check should be made on the container water level. PERMANENT DRAINAGE Connect a flexible hose to the water discharge pipe of sufficient length so that it will reach a permanent drain. The gravity head created will allow for a gradual fall from the unit to the drain. Ensure that the hose is free of kinks and is not allowed to rise at any point above the level of the discharge point from the dehumidifier. Any air locks which may be created, should the level be raised by the hose passing over obstructions, could cause the water to back up the hose and spill form the dryer. SWITCHING ON Plug the unit into the power supply and switch on. Turn the rotary switch to the ON position. (On dual voltage units turn the rotary switch to the correct power supply voltage). Where applicable press and hold the push button for 1 second. The unit should now start. SWITCHING OFF Turn the rotary switch to the OFF position. Turn off the power supply and disconnect.

DEFROST OPERATION If the ambient temperature of the room in which the dehumidifier is conditioning, falls below 15 C ice will form on the evaporator coil as air passes over it. Over a period of time this build up of ice will effect the efficiency of the dehumidifier on it s ability to maintain the required set conditions within the room. The BD150 is therefore fitted with a defrost control device. This defrost control device is timed to operate every 42 minutes for a period of 4 minutes. SPECIAL FEATURES During the defrost cycle the high pressure hot gas from the compressor is diverted into the evaporator coil where it melts the ice which has formed on the evaporator coil. DUAL VOLTAGE MODELS The BD150 dehumidifier unit is fitted with a transformer which will allow the unit to operate on either 110volts or 230volts 1ph 50Hz power supply. All electrical components within the dehumidifier are rated for 110volts, for safety reasons. The rotary switch allows for the selection of the required voltage prior to starting the unit. VOLTAGE PROTECTION DEVICE The dual voltagebd150 dehumidifier unit is fitted as standard with a unique voltage selection protection device. Should the unit be connected to 110volts supply and the rotary selector switch set inadvertently to 230volts, the unit will not start. This unit is fitted with a screw type in line fuse holder with a 10 amp anti fuse holder.

SAFETY DO NOT USE THE UNIT IF THE CABINET OR POWER CORD IS DAMAGED. DO NOT INSERT OBJECTS INTO ANY OF THE GRILLES ON THE MACHINE. DO NOT COVER OR OBSTRUCT AIRFLOW FROM THE GRILLES DO NOT OPERATE THE UNIT WITH THE COVERS REMOVED. DO NOT ATTEMPT ANY REPAIRS SHOULD THE UNIT FAIL TO OPERATE. DO NOT STAND ON THE UNIT. DO NOT ATTEMPT TO LIFT HEAVY UNITS UN ASSISTED. DO CHECK THE PLUG ON THE EQUIPMENT MATCHES THE SUPPLY DO USE THIS UNIT ONLY FOR THE PURPOSE FOR WHICH IT WAS DESIGNED. DO ENSURE THE POWER CORD AND SUPPLY IS EARTHED CORRECTLY. DO CHECK THE VOLTAGE SELECTION BEFORE ATTAMPTING TO POWER UP THE UNIT (DUAL VOLTAGE UNITS ONLY). DO USE A RESIDUAL CURRENT DEVICE RCD WHERE POSSIBLE. SERVICE This machine should be serviced by qualified Ebac personnel or others having technical competence in servicing refrigeration equipment following the instructions in the Ebac Service Manual. SPARES Full spare parts listings and Ebac Service Manuals are available upon request by contacting Ebac Industrial Products Ltd as listed on the back of this manual. OZONE FRIENDLY The gas which is used inside the hermitically sealed refrigeration circuit is R407c, which is an HFC. Under NO circumstances should this gas be released into the atmosphere. The unit should be serviced by trained personnel who will re-claim the removed gas. DISPOSAL OF THE UNIT At the end of the machines working life the refrigerant must be disposed of in the correct manner. CONTACTING EIPL CUSTOMER SERVICES If you have any further queries please contact the EIPL customer Services Department on 01388 664400 and have the following information to hand: Part Number and Serial Number of the machine(located on the rating plate at the front of the machine) Full name and address Where your machine was purchased

TECHNICAL SPECIFICATION 1021800 UK 1021900 UK Units of Measure Height: 915 915 mm Width: 610 610 mm Depth: 692 692 mm Weight: 80 75 Kg Airflow: 510 510 m3/min Voltage: 230/110 230 V Phase: 1 1 Frequency: 50 50 Hz Maximum Power: 1.5 1.5 kw Maximum Current: 8/16 8 A Generator Size: 1.5 1.5 kva Fuse Rating: 13 13 A Effective Volume: 300 300 m3 Refrigerant Type: R407c R407c Refrigerant Quantity: 0.54 0.54 Kg Normal Extraction: 18 18 L/24hrs Maximum Extraction: 82 82 L/24hrs Noise Level: Less than 70dba when running Finish: Epoxy Coated Zintec Steel Mobility: Light in construction and easily positioned Normal: Rated Extraction at 15 C 65% RH Conditions Maximum: Rated Extraction at 45 C 99% RH Conditions This machine has been manufactured in the United Kingdom "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed. The Global Warming Potential (GWP) of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit, please refer to the product data label"

UK Head Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Tel: +44 (0) 1388 664400 Fax: +44 (0) 1388 662590 www.eipl.co.uk sales@eipl.co.uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Tel: +01 757 873 6800 Fax: +01 757 873 3632 www.ebacusa.com sales@ebacusa.com German Sales Office Ebac Industrial Products Ltd Miraustra 64 66 13509 Berlin Germany Tel: +49 3043 557241 Fax: +49 3043 557240 www.eip-ltd.de sales@eip-ltd.de