SECTION STEAM AND STEAM CONDENSATE SPECIALTIES
|
|
- Britton Harvey Johns
- 7 years ago
- Views:
Transcription
1 SECTION STEAM AND STEAM CONDENSATE SPECIALTIES PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Steam traps. B. Steam air vents. C. Vacuum breakers. D. Drip pan elbows. E. Overflow drainer. 1.2 REFERENCES A. ANSI/ASTM - Boiler and Pressure Vessel Code. B. ASTM A105 - Forgings, Carbon Steel, for Piping Components. C. ASTM A126 - Gray Iron Castings for Valves, Flanges, and Pipe Fittings. D. ASTM A216 - Steel Casings, Carbon, Suitable for Fusion Welding, for High Temperature Service. E. ASME B Building Services Piping. 1.3 REGULATORY REQUIREMENTS A. Conform to ASME B Building Services Piping. 1.4 QUALITY ASSURANCE A. Manufacturer: For each product specified, provide components by same manufacturer throughout. 1.5 SUBMITTALS A. Submit shop drawings and product data for manufactured products and assemblies required for this project. B. Include product description, model, dimensions, component sizes, rough-in requirements, service sizes, and finishes. C. Submit schedule indicating manufacturer, model number, size, location, rated capacity, and features for each specialty with cross reference to supporting product data. GMP-R1 Addendum # Randall Stout Architects, Inc.
2 1.6 EXTRA STOCK A. Provide two service kits for each size and type of steam trap. PART 2 - PRODUCTS 2.1 FLOAT AND THERMOSTATIC TRAPS A. ASTM A126, cast iron or semi-steel body and bolted cover rated for maximum system pressure or 125 psig, whichever is greater; provide access to internal parts without disturbing piping; with bottom drain plug, stainless steel balanced pressure type air vent rated for 45 F of superheat, stainless steel float, stainless steel lever and valve assembly. B. Manufacturer 2. Armstrong. 2.2 STEAM AIR VENTS A. Balanced pressure type with ASTM A126 cast iron body and cover for maximum system pressure or 125 psig WSP whichever is greater; provide access to internal parts without disturbing piping; stainless steel bellows, stainless steel valve and seat. B. Manufacturer 2. Armstrong. 2.3 VACUUM BREAKERS A. Vacuum breakers shall be used on all modulating or on/off exchangers and coils. They shall be installed in the supply side between the control valve and equipment and be of hardened ball check valve design with all working parts manufactured from stainless steel. Bodies shall be made from stainless steel and shall be suitable for operating conditions of 304 psig saturated steam. 1. Body: Cast iron, bronze, or stainless steel. 2. End Connections: Threaded. 3. Sealing Ball, Retainer, Spring, and Screen: Stainless steel. 4. O-ring Seal: EPR. B. Vacuum Breakers shall require a vacuum of no greater than 2 inches of H2O to open. GMP-R1 Addendum # Randall Stout Architects, Inc.
3 C. Manufacturers 2. Armstrong. 2.4 DRIP PAN ELBOWS A. Drip pan elbows for use with safety valves shall be cast iron rated in accordance with ASTM A126 Class B, and be of the same size as the safety relief outlet or larger. B. All risers shall have drip pan elbows and the riser pipe after the drip pan elbow shall be unrestricted and larger than the drip pan inlet size. C. Manufacturers 2. Armstrong. 2.5 STEAM SAFETY VALVES A. Size and Capacity: As required for equipment according to ASME Boiler and Pressure Vessel Code. Furnish complete with cast-iron drip pan elbow having threaded or flanged inlet, and threaded drain connection. B. Bronze Safety Valves 1. Disc Material: Forged copper alloy. 2. End Connections: Threaded inlet and outlet. 3. Spring: Fully enclosed steel spring with adjustable pressure range and positive shutoff, factory set and sealed. 4. Pressure Class: Drip-Pan Elbow: Cast iron and having threaded inlet and outlet with threads complying with ASME B Size and Capacity: As required for equipment according to ASME Boiler and Pressure Vessel Code. C. Cast Iron Safety Valves 1. Disc Material: Forged copper alloy with bronze nozzle. 2. End Connections: Raised-face flanged inlet and threaded or flanged outlet connections. 3. Spring: Fully enclosed cadmium-plated steel spring with adjustable pressure range and positive shutoff, factory set and sealed. GMP-R1 Addendum # Randall Stout Architects, Inc.
4 4. Pressure Class: Drip-Pan Elbow: Cast iron and having threaded inlet, outlet, and drain, with threads complying with ASME B Exhaust Head: Cast iron and having threaded inlet and drain, with threads complying with ASME B Size and Capacity: As required for equipment according to ASME Boiler and Pressure Vessel Code. D. Manufacturer 2. Fisher. 2.6 AUTOMATIC STEAM CONTROL VALVES A. Furnish and install as specified on plans for the control of steam entering heating hot water heat exchanger. B. Valves shall be two-port single seated ductile iron globe type conforming to ANSI/ASME standards. Valve shall provide characterized modulating flow control. Valve plug, stem, and seat shall be of stainless steel. Shut-off tightness shall be ANSI class IV or better. Valve rangeability shall be 50:1 or better. Stem seal shall be PTFE chevron type. C. Actuators shall be electric, reversible, and have linear output. Supply voltage to be 110 VAC. Shall be supplied with a positioner card capable of accepting both a 4-20mA and 2-10VDC control signal. D. Control signal shall come from BAS or single loop electronic controller, as specified on plans. Single loop controller shall be powered from a 110 VAC source. Accuracy to be ±0.25% of span, and output signal to be 4-20mA. Controller to incorporate autotune and fuzzy logic features. Pt100 temperature sensors/transmitters shall be used for temperature control. E. Manufacturer 2. Fisher. 1.6 FLASH TANKS A. Shop or factory fabricated of welded steel according to ASME Boiler and Pressure Vessel Code, for 150-psig rating; and bearing ASME label. Fabricate with tappings for low-pressure steam and condensate outlets, high-pressure condensate inlet, air vent, safety valve, and legs. 1.7 PRESSURE-REDUCING VALVES A. Manufacturers GMP-R1 Addendum # Randall Stout Architects, Inc.
5 1. Armstrong International, Inc. 2. Hoffman Specialty; Division of ITT Industries. 3. Leslie Controls, Inc. 4. Spence Engineering Company, Inc. 5. Spirax Sarco, Inc. B. Size, Capacity, and Pressure Rating: Factory set for inlet and outlet pressures indicated. C. Description: Pilot-actuated, diaphragm type, with adjustable pressure range and positive shutoff. D. Select pressure-reducing valves to develop no more than 85 dba at an elevation of 3 feet above adjacent floor and at 3 feet in any direction. E. Body: Cast iron. F. End Connections: Threaded connections for valves NPS 2 (DN 50) and smaller and flanged connections for valves NPS 2-1/2 (DN 65) and larger. G. Trim: Hardened stainless steel. H. Head and Seat: Replaceable, main head stem guide fitted with flushing and pressure-arresting device cover over pilot diaphragm. I. Gaskets: Non-asbestos materials. 1.8 STEAM METERS A. Manufacturers 1. EMCO Flow Systems; Division of Advanced Energy Company. 2. ISTEC Corp. 3. Preso Meters; a division of Racine Federated Inc. 4. Spirax Sarco, Inc. B. Meters shall have a microprocessor to display totalizer flow, flow rate, temperature, pressure, time, and date; alarms for high and low flow rate and temperature. 1. Computer shall have 4 to 20-mA or 2 to 10 volt output for temperature, pressure, and contact closure for flow increments. 2. Independent timers to store four peak flow rates and total flow. 3. Interface compatible with central workstation described in Division 15 Section "HVAC Instrumentation and Controls." 4. Microprocessor Enclosure: NEMA 250, Type 4. GMP-R1 Addendum # Randall Stout Architects, Inc.
6 C. Sensor: Vortex type with stainless-steel wetted parts and flange connections; and with a piezoelectric sensor removable and serviceable without shutting down the process. At least 10:1 turndown with plus or minus 1 percent accuracy over full-flow range. 1.9 OVERFLOW DRAINER A. Furnish and install an overflow drainer for the deaerator and humidifier condensate drain lines. Unit shall be cast iron with 150 lb. flanged connections. B. Manufacturer: Warren. PART 2 - EXECUTION 2.1 INSTALLATION AND APPLICATION A. Install drip legs at low points and natural drainage points such as ends of mains, bottoms of risers, and ahead of pressure regulators, and control valves. 1. On straight runs with no natural drainage points, install drip legs at intervals not exceeding 300 feet. 2. Size drip legs same size as main. In steam mains NPS 6 and larger, drip leg size can be reduced, but to no less than NPS 4. B. Install specialties in accordance with manufacturer's instructions. C. Install float and thermostatic traps to drain condensate where shown. D. Size steam traps to handle minimum of two times maximum condensate load of apparatus served. E. Traps used on steam mains and branches shall be minimum 3/4 inch size. F. Install steam traps with union or flanged connections at both ends. G. Provide globe valve and strainer at inlet, and globe valve and check valve at discharge of steam traps. H. Provide minimum 10 inch long dirt pocket of same pipe sizes as apparatus return connection between apparatus and steam trap. I. Remove thermostatic elements from steam traps during temporary and trial usage, and until system has been operated and dirt pockets cleaned of sediment and scale. J. Terminate equipment relief valves to roofs. Provide drip pan elbow with drain connection to nearest floor drain. K. Each relief valve vent shall run to the roof separately except where otherwise noted on the drawings. L. Flash Tank 1. Pitch condensate piping down toward flash tank. GMP-R1 Addendum # Randall Stout Architects, Inc.
7 2. If more than one condensate pipe discharges into flash tank, install a check valve in each line. 3. Install thermostatic air vent at tank top. 4. Install safety valve at tank top. 5. Install full-port ball valve, and swing check valve on condensate outlet. 6. Install inverted bucket or float and thermostatic trap at low-pressure condensate outlet, sized for three times the calculated heat load. M. Air vent discharge piping shall run to a floor sink or otherwise safe location so as not to endanger personnel or equipment. 2.2 PRESSURE-REDUCING VALVE INSTALLATION A. Install pressure-reducing valves in accessible location for maintenance and inspection. B. Install bypass piping around pressure-reducing valves, with globe valve equal in size to area of pressure-reducing valve seat ring, unless otherwise indicated. C. Install gate valves on both sides of pressure-reducing valves. D. Install unions or flanges on both sides of pressure-reducing valves having threaded- or flangedend connections respectively. E. Install pressure gages on low-pressure side of pressure-reducing valves after the bypass connection according to Division 15 Section "Meters and Gages." F. Install strainers upstream for pressure-reducing valve. G. Install safety valve downstream from pressure-reducing valve station. 2.3 STEAM OR CONDENSATE METER INSTALLATION A. Install meters with lengths of straight pipe upstream and downstream according to steam meter manufacturer's instructions. B. Provide data acquisition wiring. Refer to Division 15 Section "HVAC Instrumentation and Controls." 2.4 SAFETY VALVE INSTALLATION A. Install safety valves according to ASME B31.1, "Power Piping" and ASME B31.9, "Building Services Piping." B. Pipe safety-valve discharge without valves to atmosphere outside the building. C. Install drip-pan elbow fitting adjacent to safety valve and pipe drain connection to nearest floor drain. GMP-R1 Addendum # Randall Stout Architects, Inc.
8 D. Install exhaust head with drain to waste, on vents equal to or larger than NPS 2-1/2. END OF SECTION GMP-R1 Addendum # Randall Stout Architects, Inc.
DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES
SECTION 15062 STEAM AND CONDENSATE PIPING PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Comply with the provisions of the following: 1.2 DESIGN CRITERIA 1. ASME B 31.9 Building Services Piping : for
More information5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationVAD. Variable Area Desuperheaters
Desuperheater overview Steam used in process plants can be superheated, that is, heated to a temperature above saturation. The excess of temperature above its saturation is called 'superheat'. Desuperheated
More informationVAD Variable Area Desuperheaters
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationTYPE E Main Valve Sizes 3 /8 through 12
SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,
More informationFloat and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
More informationREGULATORS D& HD Series
Watson McDaniel reserves the right to change the designs and/or materials of its products out notice. 2002 Watson McDaniel Company Ductile Iron body - HD Series Full port strainer & blowdown valve on pilot
More informationBlowdown vessels Meeting the requirements of HSE PM60
Blowdown vessels Meeting the requirements of HSE PM60 BDV60 blowdown vessels complete range of equipment for the safe disposal of boiler blowdown Boiler blowdown Steam boilers must be blown down to remove
More informationDESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
More informationPRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
More informationHS-901(A) BASIC STEAM HEATING SYSTEMS
HS-901(A) BASIC HEATING SYSTEMS One-Pipe Two-Pipe Basic Steam Heating Systems One-pipe steam heating system EQUALIZER SAFETY FACTOR STATIC HEAD PRESSURE DROP 2" HEATING UNIT 15" DRIP CONNECTION In a one-pipe,
More informationRMF Engineering 23 05 23
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
More informationFIRING RANGE PHASE 1 DESIGN 224500-1
FIRING RANGE PHASE 1 DESIGN 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationD Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00
SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air
More informationType 92S Pilot-Operated Steam Regulator
Type 92S Pilot-Operated Steam Regulator Introduction The Type 92S steam regulator is piston actuated for high cycle steam service which includes a Type 6492L, 6492H or pilot (see Figure 1). These pilots
More informationASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.
ASME/ANSI B16.1-1998 - Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B16.3-1998 - Malleable Iron Threaded Fittings ASME/ANSI B16.4-1998 - Cast Iron Threaded Fittings ASME/ANSI B16.5-1996 - Pipe
More informationA. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationMustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
More informationWD600 STEAM TRAPS. Thermodynamic Steam Trap
WD600 Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2010 Watson McDaniel Company WD600, WD600L Sizes 3/8, 1/2, 3/4, 1 NPT Material Stainless
More informationFLASH TANK ECONOMIZER PRODUCT GUIDE
FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.
More informationSpira-trol TM Two-port Control Valves EN Standard KE, KF and KL DN15 to DN300 and ASME Standard KEA, KFA and KLA ½" to 12"
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationLAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
More informationConstantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW
Installation, Operating and Maintenance Instructions 90/4.5.5 Rev. 0 Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Table of Contents SECTION I... 2 INSTALLATION...
More informationREGULATING VALVE APPLICATIONS
REGULATING APPLICATIONS GENERAL REGULAR APPLICATION & INSTALLATION NOTES Regulator Application & Installation Notes The following are considerations for all steam regulator installations, as system operation
More informationTypes 66R and 66RR Low-Pressure Relief Valves
November 2009 Types 66R and 66RR Low-Pressure Relief Valves W1953 W1908 TYPE 66R RELIEF VALVE TYPE 66RR RELIEF VALVE Figure 1. Typical Constructions Introduction Types 66R and 66RR low-pressure throttling
More informationSECTION 221413 FACILITY STORM DRAINAGE PIPING
SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationIndirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
More informationA. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 22 45 00 - (ADD#2) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More information3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
More informationJay R. Smith Mfg. Co.
Jay R. Smith Mfg. Co. Automatic Backwater Valve SMITH CUSTOMER DRIVEN FLOOD-GATE FEATURES Index Page Flood-Gate Features and Applications 2 How Flood-Gate Works 3 Flood-Gate Operation & Approvals 4 Valve
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationPilot Operated Pressure Reducing Valve PRV 47 (Steel) PRV47I (St.Steel)
OPTIONS: USE: AVAILABLE MODELS: Pilot Operated Pressure Reducing Valve PRV 47 (Steel) PRV47I (St.Steel) DESCRIPTION The ADCA PRV47 pilot operated pressure reducing valves are designed for use on steam,
More informationEquivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409
Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam
More informationV47 Series Temperature Actuated Modulating Water Valves
V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate
More informationCommercial Semi-Instantaneous Water Heaters
FEATURES HWI Models A. O. Smith s HWI models are available for operation with steam or boiler water as the energy source. They are factory assembled with components sized, piped and checked at the factory
More informationIn-Line Air Separators
Air Elimination & Control In-Line Air Separators The AC models of air separators deliver all the quality and performance you expect from Taco products. They are built to last with shell, heads and ANSI
More informationMorrison Bros. Co. General Product Specifications
Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationBERMAD Waterworks. Quick Active Check Valve. 700 Series. Model 740Q. Features and Benefits. Major Additional Features
Booster Pump Control Valve Quick Active Check Valve Isolates system from the effects of pump starts and stops for: Solitary single speed pumps Battery of single speed pumps (add & switch) Battery of variable
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationSECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES
SECTION 22 42 00 COMMERCIAL PLUMBING FIXTURES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationElement D Services Plumbing
PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL
More informationPRESSURE REDUCER AND RELIEF VALVES WITH METALLIC BELLOW FOR WATER STEAM
PRESSURE REDUCER AND RELIEF VALVES WITH METALLIC BELLOW FOR WATER STEAM PRESSURE REDUCER AND RELIEF VALVES These devices are used to reduce and control a gaseous flow pressure (air, steam, gas ). The PRESSURE
More informationMFP14, MFP14S and MFP14SS Automatic Pumps
Page 1 of 6 TI-P136-02 ST Issue 12 Cert. No. LRQ 0963008 ISO 9001, S and SS utomatic Pumps Description The Spirax Sarco automatic pump is a displacement receiver operated by steam or compressed air. It
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationBERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features
Pressure Relief/Sustaining Valve Prioritizing pressure zones Ensuring controlled pipeline fill-up Preventing pipeline emptying Pump overload & cavitation protection Safeguarding pump minimum flow Excessive
More information112039.00 224500 EMERGENCY PLUMBING FIXTURES
PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following emergency plumbing fixtures: 1. Emergency showers. 2. Eyewash equipment. 3. Eye/face wash equipment. 4. Hand-held drench hoses. 5. Combination
More informationA. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.
SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationOne Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty
One Year Warranty ELECTRIC Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches Fused Ceramic Shield tank lining is corrosion-resistant for years of dependability. Adjustable
More informationSteam System Design and Best Practices Related to Kiln Drying
Steam System Design and Best Practices Related to Kiln Drying New England Kiln Drying Association Steam Design and Best Practices HerLine Technologies What is Steam? Like other substances water can exist
More informationSteam System Efficiency. Bill Lumsden Leidos Engineering
Steam System Efficiency Bill Lumsden Leidos Engineering Steam System Efficiency Steam System Efficiency Key Take-aways: Review of the properties of ice, water, and steam Learn the basics of steam trap
More information2-Port Self-acting Temperature Control Valve Selection for Heating and Cooling Applications
Page 1 of 12 TI-S21-07 CH Issue 1 Cert. No. LRQ 0963008 ISO 9001 2-Port Self-acting Temperature Control Valve Selection How to select a system Valve selection: 1. Is the application for heating or cooling?
More informationPBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationREGULATORS 175/153 Series
175/153 Series 175 HEATING 153 COOLING Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2002 Watson McDaniel Company Revised 7/2002 175 / 153 Screwed
More informationSECTION 226113 MEDICAL COMPRESSED-AIR PIPING FOR HEALTHCARE FACILITIES PART 1 - GENERAL
SECTION 226113 MEDICAL COMPRESSED-AIR PIPING FOR HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Medical air piping and specialties, designated "medical air,"
More informationQLM and QLD Series Three-port Control Valves
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationCopper and Copper Alloy Tube, Pipe and Fittings
Copper and Copper Alloy Tube, Pipe and Fittings COPPER and COPPER ALLOY TUBE and PIPE Seamless Copper Pipe: Copper pipe is almost pure copper manufactured to the requirements of ASTM B 42 - Standard Specification
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationDesuperheater Online Program Sizing Guidance
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationAPCO SLOW CLOSING AIR/VACUUM VALVES
BULLETIN 1 JULY 01 APCO SLOW CLOSING AIR/VACUUM VALVES Series 1900 APCO Slow Closing Air/Vacuum s Maximum Air Flow Velocity in Good Pipeline Design The Air/Vacuum operates in the normal fashion allowing
More informationNAVIEN AMERICA INC. 17855 FITCH AVENUE
Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:
More informationDirect steam injection humidifiers
Direct steam injection humidifiers Direct steam injection gives quality control of air humidity. Research and development in separation, the use of lightweight stainless steel combined a constant temperature
More informationAIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
More informationSECTION 23 64 10 AIR COOLED WATER CHILLERS
PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2
More informationOPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE
OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203)
More informationINSTRUMENTATION & CONTROLS VALVE & AUTOMATION EXPERTS VALVE REPAIR TUBE SERVICES
INSTRUMENTATION & CONTROLS VALVE & AUTOMATION EXPERTS VALVE REPAIR TUBE SERVICES GREAT PRODUCTS ARE ONLY PART OF OUR SUCCESS. YOU SHOULD MEET OUR PEOPLE. From the machinist with over 20 years experience
More informationMTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter
Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases
More informationSteam Coil Installation, Operation and Maintenance
Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils manufactured by Luvata in Grenada, MS have been
More informationPLUMBING RE-SUBMITTAL 22 11 17
PLUMBING RE-SUBMITTAL 22 11 17 ACADEMIC BUILDING & PATRIOT S CASA TEXAS A&M UNIVERSITY - SAN ANTONIO, TX NO. 25-3122, VAC NO. 39019 OWNER: ARCHITECT: MEP ENGINEER: GENERAL CONTRACTOR: PLUMBING CONTRACTOR:
More informationvalve solutions Chemical Cosmetic Cryogenic Food & Beverage Marine Mining Nuclear Oil & Gas Paint Pharmaceutical Pulp & Paper www.quilinox.
valve solutions www.quilinox.com Chemical Cosmetic Cryogenic Food & Beverage Marine Mining Nuclear Oil & Gas Paint Pharmaceutical Pulp & Paper valvulas esfera PBM.pdf (1753) 2015/01 1/10 D E SIGN F E A
More informationAPI Flanged Safety Relief Valves Series 526 CATALOG
API Flanged Safety Relief Valves Series 26 CATALOG The-Safety-Valve.com 1 Valve finder How to find the right product group High operating to set pressure ratio, high backpressure or low total height? Yes
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 15430 PLUMBING SPECIALTIES
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Roof drains 1. Coordinate location and depth of drains to assure adequate pitch of the drainage area to drain. 2. Overflow system shall be piped
More informationAll work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
More informationNICHOLSON STEAM TRAP. 845.778.5566 Fax: 845.778.7123 www.nicholsonsteamtrap.com STEAM TRAP
1 NICHOLSON STEAM TRAP Nicholson Steam Trap was founded in 1883 by W. H. Nicholson, Sr. He, along with his sons William, George and Samuel produced a variety of steam specialty products at their facility
More informationModulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, 1060. Instruction No.
Instruction No. AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA PIPING GUIDE GF-115-P Modulex Gas Fired Boiler Systems Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909,
More informationStyle 07 Zero Flex Rigid Coupling. Style 75 Flexible Coupling. Style 77 Flexible Coupling 11. Description
Style 07 Zero Flex Rigid Coupling The unique angled pad design adjusts to standard pipe tolerances to positively clamp the pipe to resist flexural and torsional loads. Working pressures are based on standard
More informationWhen Should Examination Preparation Begin?
Texas State Board of Plumbing Examiners Tradesman Plumber-Limited Licensee Examination Review Course The following Examination Review Course is designed to assist a registered Plumber s Apprentice in preparing
More informationBaumann 24000 Little Scotty Bronze Control Valve
24000 Valve Product Bulletin Baumann 24000 Little Scotty Bronze Control Valve Baumann Little Scotty industrial control valves are intended for general utility service in pressure, flow, and temperature
More informationFig B36 Stainless Steel 'T' Type or Basket Type Strainers
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
More informationMedical Air Systems: Scroll
GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing
More informationSAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE
1 Which tool is used to correct internal hi-low when preparing a 4-in. steel pipe for welding? A. 4-in. grinder with cutting disc. B. Mini-grinder with flapper disc. C. Pencil grinder with cone stone.
More informationAURORA. 1030 AND 1040 Series SUCTION DIFFUSERS, COMBINATION AND TRIPLE DUTY VALVES WWW.AURORAPUMP.COM
UROR 1030 ND 1040 Series SUCTION DIFFUSERS, COMINTION ND TRIPLE DUTY VLVES WWW.URORPUMP.COM UROR 1030 ND 1040 Series Suction Diffusers, Combination and Triple Duty Valves Designed for Direct Mounting on
More information1. Conductivity < 15 micro ohms/cm 2. ph of 6.0 to 9.0 3. Nonvolatile TOC content < 1.0 ppm
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More information1805 Series Relief Valves
October 2011 1805 Series Relief Valves P1026 1805G Type 1805-2 Type 1805-4 Figure 1. Typical 1805 Relief Valves Introduction The 1805 Series relief valves are designed for use in farm tap applications
More informationSECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
More informationKUNKLE SAFETY AND RELIEF VALVE PRODUCTS OVERVIEW
KUNKLE SAFETY AND RELIEF VALVE PRODUCTS OVERVIEW ISSUED FEBRUARY 2014 KUNKLE SAFETY AND RELIEF VALVE PRODUCTS OVERVIEW Contents Models 1 and 2 Brass Safety Valves... 4 Models 19, 19M, 20, 20M, 20P, 20MP,
More informationD. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities:
SECTION 232500 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following HVAC water-treatment systems: 1. Open Loop Chemical Treatment Systems. 2. Closed Loop Chemical Treatment Systems. 3.
More informationC. Burner management system to follow requirements of Industrial Risk Insurers (IRI).
SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE
More informationPLUMBING ROUGH IN INSPECTION
This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.
More information2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
More informationSERVICE GUIDE Armstrong Inverted Bucket Steam Traps
Bulletin 301-M SERVICE GUIDE Armstrong Inverted Bucket Steam Traps A B T T D C Font C A21755 Table of Contents Trap Priming 2 Installation 3-8 Testing 9-10 Inspection & Repair 10-14 Trouble Shooting 14-18
More informationSECTION 220523 VALVES. A. Product Data: Manufacturer s catalog sheets and specifications for each valve type.
SECTION 220523 VALVES PART 1 GENERAL 1.01 ABBREVIATIONS A. IBBM: Iron body, bronze mounted. B. OS&Y: Outside screw and yoke. C. WOG: Water, oil, gas. D. WSP: Working steam pressure. 1.02 SUBMITTALS A.
More informationFT43, FT44, FT46 and FT47 Ball Float Steam Traps
0667050/9 IM-S02-30 ST Issue 9 FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationNFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
More informationDOUBLE SEAT BRONZE BODY HIGH CAPACITY
PS593DB HEAVY DUTY BRONZE GLOBE CONTROL VALVES DB DOUBLE SEAT BRONZE BODY HIGH CAPACITY 1, 1-1/4, 1-1/2, and 2 Union Ends ANSI Class 250 Body Rating ANSI Class II Close off Bronze or Stainless Steel Trim
More informationCHAPTER 11 STORM DRAINAGE
CHAPTER STORM DRAINAGE SECTION PC 0 GENERAL 0. Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be
More informationVG7000 Series Bronze Control Valves
VG7000 Series Bronze Control Valves Product Bulletin VG7000 Series Code No. LIT-977140 Issued November 15, 2013 Supersedes March 29, 2013 VG7000 Series Bronze Control Valves are designed primarily to regulate
More informationDV-5 Deluge Valve with Remote-Resetting, Pressure-Reducing Trim 4 Inch and 6 Inch (DN100 and DN150) General Description.
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim 4 Inch and 6 Inch (DN and DN5) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water
More informationSubpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
More information