1 HP Power Distribution Unit with Power Monitoring Installation Instructions HP Power Distribution Unit with Power Monitoring Overview The HP Power Distribution Unit with Power Monitoring is a PDU optimized for vertical mounting in HP Series racks (36U or larger). This product provides: Vertical mounting in the rear of the rack, maximizing rack space (no additional parts are required for mounting) Power cord retention bands A front panel display that indicates operating parameters A color-coded branch circuit HP Power Distribution Unit with Power Monitoring Components Read Instructions Completely Before Beginning Installation Procedures Copyright 2004 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. December 2004 (First Edition) Part Number Audience Assumptions This document is for the person who installs power products. No installation or service procedure should be carried out by someone other than a technician with specific experience with high-voltage equipment. HP assumes you are qualified in the servicing of high-voltage equipment and trained in recognizing hazards in products with hazardous energy levels. Callout Description 1 C19 outlet 2 C13 outlet 3 Load segment 4 Front panel display 5 Breakers 6 Power cords 7 Mounting brackets* 8 Serial number 9 Model number *Single PDUs have only one mounting bracket.
2 Installation Overview The PDU can be mounted in the rack so that the breakers are at the top of the unit or on the bottom of the unit to accommodate multiple configuration options. The PDU can be mounted in the rack the following ways: Standard mount ("Installing the HP Power Distribution Unit with Power Monitoring in the Standard Mount Position" on page 3) NOTE: This product arrives with the mounting brackets already installed for a standard right side, breakers at the bottom mount. Right side, breakers at the bottom Left side, breakers at the top Alternative mount ("Installing the HP Power Distribution Unit with Power Monitoring in an Alternative Mount Position" on page 5) Right side, breakers at the top Left side, breakers at the bottom Important Safety Information Before installing this product, read the Important Safety Information guide provided. WARNING: To reduce the risk of personal injury from electric shock, do not remove the cover. There are no field-serviceable or user-serviceable components inside. WARNING: A risk of personal injury from electric shock and hazardous energy levels exists. The installation of options and routine maintenance and service of this product must be performed by individuals who are knowledgeable about the procedures, precautions, and hazards associated with AC power products. Follow these safety precautions when connecting multiple pieces of information technology equipment to power products. The input power cord must be securely attached and it should be connected to the AC mains by hardwiring or through the use of a nonresidential, industrial-style plug that maintains positive earth connection. If the total system leakage current through the ground conductor exceeds five percent of the input current per line under normal operating conditions, the system loads should be divided among multiple power connections. Kit Contents The following hardware pieces are included: One single PDU North America and Japan Model S1140 S1324 -or- One single PDU International Model S1132 S1316 -or- One dual PDU North America and Japan Model S2140 S2324 -or- One dual PDU International Model S2132 S2316 Power cord retention bands 5.5 mm x 12 mm self-tapping screws Extra hardware might be included for your convenience. Required Tool You will need a Phillips screwdriver. WARNING: To reduce the risk of personal injury from high-leakage current, verify earth connection before connecting the power supply. The summation of input power for multiple pieces of information technology equipment through the use of power products can result in high-leakage currents. If the total system leakage current for a system of components exceeds 3.5 ma: The use of a detachable input power cord is prohibited.
3 Installing the HP Power Distribution Unit with Power Monitoring in the Standard Mount Position 1. Slide the tabs on the PDU mounting bracket into the rack frame. 2. Insert three screws, securing the PDU to the rack frame. 3. Attach the device power cords to the PDU.
4 4. (Optional) Wrap a power cord retention band around each power cord, and insert the end of the power cord retention band into the appropriate slot on the PDU mounting bracket. NOTE: Firmly pull the power cord retention bands tight, paying special attention not to sever them. 5. Plug the PDU power cords into the appropriate power outlets. NOTE: Be sure that the circuit breakers are in the off position before attaching the power cords to the power outlets.
5 6. Power on the PDU breakers. Installing the HP Power Distribution Unit with Power Monitoring in an Alternative Mount Position 1. Remove the five screws securing each mounting bracket to the PDU. NOTE: For single PDUs, be sure that the five screws, on the side of the unit without a mounting bracket, are also removed.
6 2. Rotate the PDU 180 degrees, so that the power cords are now at the top of the rack. 3. Reattach each mounting bracket to the PDU using the same five screws from step 1. NOTE: For single PDUs, be sure that the five screws from step 1, are inserted into the side of the unit without a mounting bracket. 4. Continue to "Installing the HP Power Distribution Unit with Power Monitoring in the Standard Mount Position (on page 3)." Checking the Circuit Breakers If power to a device is interrupted, check the circuit breakers and reset them if necessary. If power is still not restored, contact your HP authorized service representative.
7 Front Panel Display Overview The PDU front panel has a two-digit, LED display that shows the current in each circuit breaker, a scroll button to scroll through values, and six LEDs, which indicate current overloads and voltage out of range conditions. During the power-on process or after a power restart, all of the indicators on the front panel display are illuminated for a minimum of two seconds to verify operation (the bicolor LEDs are switched every second during this verification process). NOTE: Each load segment is associated with one circuit breaker. For NA/JPN three-phase models, each load segment is fed by one pair of phase conductors. For International three-phase models; each load segment is fed by one phase conductor and the neutral conductor. Front Panel Display Components Callout Description 10 Scroll button 11 Seven segment LED numeric display Inverting the Numerical Display If you are mounting the PDU in the rack with the breakers at the top, press and hold the scroll button for over three seconds to invert the seven-segment display 180 degrees. HP Power Distribution Unit with Power Monitoring Normal Operating Conditions The dual seven-segment display shows the current in the load segment selected. For current values above one Amp, the value is displayed without a decimal point. For example, one Amp is displayed using only the right-most digit. During normal conditions, all load segment LEDs are illuminated green. The illuminated green LED corresponding to the load segment currently being displayed flashes. If an alarm condition exists, the load LED for that load segment is not illuminated green, but rather amber or red. After five minutes of inactivity, if no alarms are present, the front panel display begins to automatically scroll through the load segments. Inactivity is defined as no user inputs for example, not pushing the scroll button, for five minutes. When the unit is automatically scrolling through each load segment the current displays for three seconds before switching to the next segment. When the scroll button is pushed during the automatic function, the automatic function is terminated until the five-minute criteria for automatic scrolling is met again. HP Power Distribution Unit with Power Monitoring Alarm Operating Conditions The following alarm conditions are indicated by flashing alarm LEDs on the front panel display: Callout Description 1 Reset button 2 Local configuration port ( O O 1) 3 Green load segment LED (L3) 4 Green load segment LED (L2) 5 Green load segment LED (L1) 6 Amber/red alarm load segment LED (L3) 7 Amber/red alarm load segment LED (L2) 8 Amber/red alarm load segment LED (L1) Current Overload Overload Current greater than 102% of allowed maximum per load segment (red alarm LED) If an overload condition exists, the corresponding load segment LED with the alarm condition is illuminated red, while the green load segment LED for that particular load segment is not illuminated. Load Warning Current greater than 80%, but less than 102%, of allowed maximum per load segment (amber alarm LED) If a load warning condition exists, the corresponding load segment LED with the alarm condition is illuminated amber, while the green load segment LED for that particular load segment is not illuminated. 9 Remote communication port ( O O 2)
8 Voltage Out of Range Overvoltage of 10% to 20% (amber alarm LED), overvoltage of greater than 20% (red alarm LED) Undervoltage of 10% to 20% (amber alarm LED), undervoltage of more than 20% (red alarm LED) When an alarm condition occurs, the front panel display automatically changes to show the circuit with the alarm condition regardless of the present display setting. The automatic scrolling function is disabled when an alarm condition exists. If an alarm condition displays and you scroll to display another circuit that does not have an alarm condition present, the circuit without an alarm is displayed for 10 seconds and then switches back to the alarmed circuit. If an alarm condition displays and you scroll to another circuit with an alarm condition, the display remains on the last circuit selected with an alarm until the alarm condition clears or you scroll to a different circuit. If multiple circuits have alarm conditions at the same time, the last circuit to activate an alarm is displayed. Current Alarms Load Segment Conditions 80% 102% Greater then 102% of Max Rated Alarm LED Colors Load Warning Amber Overload Red Models S S S S S S S S *Values expressed in Amps. Front panel display does not show tenths.
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
More informationHP 36-Port InfiniBand Switch Cable Management Kit Installation Guide
HP 36-Port InfiniBand Switch Cable Management Kit Installation Guide HP Part Number: 574412-doc Published: May 2009 Copyright 2009 Hewlett-Packard Development Company, L.P. The information contained herein
More informationHP R12000 and R18000 DirectFlow UPS User Guide
HP R12000 and R18000 DirectFlow UPS User Guide Abstract This document includes installation, configuration, and operation information for the HP R12000 and R18000 DirectFlow UPS. This document is for the
More informationHP 16/18-Port Cable Management Kit Installation Guide
HP 16/18-Port Cable Management Kit Installation Guide Abstract This document describes how to attach the HP 16 Port or 18 Port Cable Management Kit to an HP rack. The cable management bracket is designed
More informationWall-Mounting your HP computer. User Guide
Wall-Mounting your HP computer User Guide The only warranties for Hewlett-Packard products and services are set forth in the express statements accompanying such products and services. Nothing herein should
More informationMemory Modules User Guide
Memory Modules User Guide Copyright 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products and services
More informationHP ProLiant DL380 G6 Carrier-Grade Server Read Before Install
HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install Carrier-Grade Instructions HP Part Number: AM275-9001A Published: July 2012 Edition: 3 Copyright 2009, 2012 Hewlett-Packard Development Company,
More informationMemory Modules. Document Part Number: 407947-001. This guide explains how to replace and upgrade memory in the computer. May 2006
Memory Modules Document Part Number: 407947-001 May 2006 This guide explains how to replace and upgrade memory in the computer. Contents 1 Adding or replacing memory modules Adding or replacing a memory
More informationHP Advanced Wireless Docking Station. User Guide
HP Advanced Wireless Docking Station User Guide Copyright 2014, 2015 Hewlett-Packard Development Company, L.P. Intel is a trademark of Intel Corporation in the U.S. and other countries. Windows and Windows
More informationHP ProDisplay P19A LED Backlit Monitor. User Guide
HP ProDisplay P19A LED Backlit Monitor User Guide 2013 Hewlett-Packard Development Company, L.P. The only warranties for HP products and services are set forth in the express warranty statements accompanying
More informationHP Roar Plus Speaker. Other Features
HP Roar Plus Speaker Other Features Copyright 2014 Hewlett-Packard Development Company, L.P. Microsoft, Windows, and Windows Vista are U.S. registered trademarks of the Microsoft group of companies. Bluetooth
More informationMemory Modules. Document Part Number: 396849-001. This guide explains how to replace and upgrade memory in the computer.
Memory Modules Document Part Number: 396849-001 March 2006 This guide explains how to replace and upgrade memory in the computer. Contents 1 Adding or replacing memory modules Adding a memory module to
More informationUpgrading and Servicing Guide
Upgrading and Servicing Guide The only warranties for Hewlett-Packard products and services are set forth in the express statements accompanying such products and services. Nothing herein should be construed
More informationHP Designjet L65500 printer series Site preparation checklist (second edition)
HP Designjet L65500 printer series Site preparation checklist (second edition) Legal notices 2009 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
More informationQuickSpecs. HP Fixed Cord PDUs & Extension Bars (Zero-U/1U Modular PDUs) Overview
Overview Fixed Cord PDUs and Extension Bars have a unique architecture designed specifically for 1U fixed rail servers (HP ProLiant DL360, HP ProLiant DL320, HP ProLiant DL140). This new design consists
More informationCompaq Presario Desktop Products. Upgrading and Servicing Guide
Compaq Presario Desktop Products Upgrading and Servicing Guide The information in this document is subject to change without notice. Hewlett-Packard Company makes no warranty of any kind with regard to
More informationAXIS 291 1U Video Server Rack Installation Guide
AXIS 291 1U Video Server Rack Installation Guide About This Document This document describes how to install Axis blade video servers in the AXIS 291 1U Video Server Rack. Updated versions of this document
More informationRefer installation of power supplies to qualified service personnel.
AC Power Supply For 5-Slot Housing and 9000 Series Access Carrier Installation Instructions Document Number 9000-A2-GN17-50 August 2000 Before You Begin Both the 5-slot housing and the 9000 Series Access
More informationHP Bluetooth Pendant Headphones User Guide
HP Bluetooth Pendant Headphones User Guide Copyright 2008 Hewlett-Packard Development Company, L.P. Windows and Windows Vista are either trademarks or registered trademarks of Microsoft Corporation in
More informationThe power module is Feature Number 8800-F2-901.
Hotwire 8820 GranDSLAM AC to DC Power Supply Installation Instructions Document Number 8800-A2-GZ41-00 AC to DC Power Supply The AC to DC Power Supply consists of a power supply chassis and one or two
More informationHP 2400/2500 Ultra Light Docking Station User Guide
HP 2400/2500 Ultra Light Docking Station User Guide Copyright 2007 Hewlett-Packard Development Company, L.P. Microsoft is a U.S. registered trademark of Microsoft Corporation. The information contained
More informationQuickSpecs. HP Managed Power Distribution Units (mapdu) Overview
Overview Looking for a power distribution unit that meets the demands of high temperature operating environments and provides monitoring and switching capabilities? The HP Managed Power Distribution Unit
More informationQuickSpecs. HP 480/277 Volt Solutions. Overview
Overview As the quest for efficiency continues it becomes apparent that what worked in the past needs improvement. More and more data center managers are looking at alternate power plans to distribute
More informationUPGRADING AND SERVICING GUIDE
UPGRADING AND SERVICING GUIDE HPTouchSmart 610 PC Computer features may vary by model. Removing and Replacing a CD/DVD Drive...2 Removing the CD/DVD Drive... 2 Installing a New CD/DVD Drive... 5 Removing
More informationHP PDU Management Module Overview
Overview The enables you to monitor and manage power environments through comprehensive control of individual HP PDUs. Access the management module: Remotely through a Web browser. Remotely through a Telnet
More informationStorTrends 3400 Hardware Guide for Onsite Support
StorTrends 3400 Hardware Guide for Onsite Support MAN-3400-SS 11/21/2012 Copyright 1985-2012 American Megatrends, Inc. All rights reserved. American Megatrends, Inc. 5555 Oakbrook Parkway, Building 200
More informationExpress5800/120Ed. Rack Mount Kit Installation Procedures PN: 455-01607-001
Express5800/120Ed Rack Mount Kit Installation Procedures PN: 455-01607-001 Proprietary Notice and Liability Disclaimer The information disclosed in this document, including all designs and related materials,
More informationIP DSLAM IDL-2402. Quick Installation Guide
IP DSLAM IDL-2402 Quick Installation Guide Table of Contents Package Contents... 3 Overview... 4 Setup the IDL series IP DSLAM... 5 Safety Instruction... 5 Hardware Installation... 6 WEB Configuration...
More informationHP SATA/SAS hard drive and Solid State Drive installation
HP SATA/SAS hard drive and Solid State Drive installation This document describes how to install Serial ATA (SATA) and Serial Attached SCSI (SAS) hard drives or Solid State Drives (SSD) in an internal
More informationHP LASER GAMING MOUSE USER MANUAL
HP LASER GAMING MOUSE USER MANUAL v1.0.en Part number: 513192-001 Contents Selecting a User Profile... 1 Customizing a User Profile... 2 Customizing DPI Profiles... 3 Selecting a DPI Profile... 3 Changing
More informationQuick Start Guide. RV0xx Series Routers
Quick Start Guide RV0xx Series Routers RV042 Dual WAN VPN Router RV042G Gigabit Dual WAN VPN Router RV082 Dual WAN VPN Router RV016 Multi-WAN VPN Router Package Contents VPN Router Power Adapter (Cisco
More information5-Slot Housing and FrameSaver 9000 Series Access Carrier AC Power Supply Installation Instructions
TM 5-Slot Housing and FrameSaver 9000 Series Access Carrier AC Power Supply Installation Instructions Document Number 9000-A2-GN17-30 August 1998 Before You Begin Both the 5-slot housing and the FrameSaver
More informationUser Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed
More informationDesignjet T2500 emultifunction Series
Designjet T2500 emultifunction Series What is it? Your printer is a color inkjet multifunction printer designed for printing, scanning, and copying large, high-quality images. This introductory document
More informationHP ProDisplay P17A LED Backlit Monitor. User Guide
HP ProDisplay P17A LED Backlit Monitor User Guide 2013 Hewlett-Packard Development Company, L.P. Microsoft, Windows, and Windows Vista are either trademarks or registered trademarks of Microsoft Corporation
More informationMCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
More informationMounting HP Desktop Mini Rack Mount Tray Kit HP Desktop Mini Security/Dual VESA Sleeve
Mounting HP Desktop Mini Rack Mount Tray Kit HP Desktop Mini Security/Dual VESA Sleeve Optical Drive HP Desktop Mini DVD Super Multi-Writer ODD Expansion Module Input / Output / HDD HP Desktop Mini 500GB
More informationHP 2530 8-Port Switches Quick Setup Guide
HP 2530 8-Port Switches Quick Setup Guide The switch drawings in this document are for illustration only and may not match your particular switch model. For more detailed instructions and information to
More informationHP ProLiant DL165 G7 Server. Installation Instructions
HP ProLiant DL165 G7 Server Installation Instructions Identifying server components Front panel components Figure 1 Front Panel Components / 4 3.5 HDD Item 1 Thumbscrews for rack mounting 2 Drive status
More informationHP LeftHand SAN Solutions
HP LeftHand SAN Solutions Support Document Best Practices Best Practice for Active Monitoring of LeftHand SANs Legal Notices Warranty The only warranties for HP products and services are set forth in the
More informationQuickSpecs. HP Modular Power Distribution Units (Zero-U/1U Modular PDUs) Overview
Overview HP Modular PDUs have a unique modular architecture designed specifically for data center customers who want to maximize power distribution and space efficiencies in the rack. Modular PDUs consist
More informationNotebook Tour User Guide
Notebook Tour User Guide Copyright 2007 Hewlett-Packard Development Company, L.P. Microsoft and Windows are U.S. registered trademarks of Microsoft Corporation. Bluetooth is a trademark owned by its proprietor
More information42U/45U 28" Wide Rack Installation & Service Guide
42U/45U 28" Wide Rack Installation & Service Guide 96-00171-005 Rev B Important Information Information in this document is subject to change without notice and does not represent a commitment on the part
More informationHP Point of Sale (POS) Peripherals Configuration Guide ap5000 VFD Windows (non-opos)
HP Point of Sale (POS) Peripherals Configuration Guide ap5000 VFD Windows (non-opos) Document Version 3.23 November 2010 1 Copyright 2007-2010 Hewlett-Packard Development Company, L.P. The information
More informationQuickSpecs. Models HP T1500 UPS JPN/TWN. HP UPS T1000 G2, T1500 G2 Models Overview
Overview The Tower UPS "G2" models are the next generation HP tower UPSs with USB support. These new UPSs are designed to provide advanced power protection (or increased uptime and data corruption avoidance)
More informationKeysight N4877A Clock Data Recovery and Demultiplexer 1:2
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 Getting Started Getting Started with the Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 You only need a few minutes to get started
More informationQuickSpecs. HP Managed and Unmanaged Notebook Charging Carts. Models HP 30-Notebook Charging Cart
Overview HP Managed and Unmanaged Notebook Charging Carts Models HP 20-Notebook Charging Cart HP 30-Notebook Charging Cart HP 20-Notebook Managed Charging Cart HP 30-Notebook Managed Charging Cart QL488AA#ABA
More informationUPDATEUPDATEUPDATE. Converting the tower chassis to a rack-mount chassis. A - M5 13 8 To mount outer member to rack
UPDATEUPDATEUPDATE Converting the tower chassis to a rack-mount chassis Rail overview Converting your Server to Rack-Mount The rail kit includes the following: Two rail units Five packages of screws (labeled
More informationHP Managed and Unmanaged Notebook Charging Carts Overview. Models HP 30-Notebook Charging Cart. HP 30-Notebook Managed Charging Cart
Overview Models HP 20-Notebook Charging Cart HP 30-Notebook Charging Cart HP 20-Notebook Managed Charging Cart HP 30-Notebook Managed Charging Cart QL488AA#ABA H4F31AA#ABA QL489AA#ABA QL490AA#ABA Introduction
More informationTable of Contents. 1. Introduction...1. 2. PDU Package...2. 3. Function...3. 4. Installation...5. 5. Web Interface...7
PDU User Manual Table of Contents 1. Introduction...1 2. PDU Package...2 3. Function...3 4. Installation...5 5. Web Interface...7 1. Introduction The PDU is an Internet ready device designed and is equipped
More informationModem and Local Area Network
Modem and Local Area Network User Guide Copyright 2007 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products
More informationModem and Local Area Networks. Document Part Number: 383057-002
and Local Area Networks Document Part Number: 383057-002 October 2005 Contents 1 Modem Using the modem cable............................ 2 Using a country-specific modem cable adapter.......... 3 Modem
More information=============================== WARNING
=============================== WARNING EXPLANATION OF GRAPHICAL SYMBOLS This symbol is intended to alert the user to the presence of unprotected dangerous voltage" within the product's enclosure that
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationHP Mobile Remote Control (Select Models Only) User Guide
HP Mobile Remote Control (Select Models Only) User Guide Copyright 2008 Hewlett-Packard Development Company, L.P. Windows and Windows Vista are either trademarks or registered trademarks of Microsoft Corporation
More informationINSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
More informationAutomatic Phone-Out Home Monitoring Systems
Automatic Phone-Out Home Monitoring Systems Power Outage and Freeze Alarm Model Number: THP202 Power Outage, Freeze and Flood Alarm Product Description Model Number: THP201 These monitoring systems are
More informationEKOS Cart. Instructions for Use
EKOS Cart Instructions for Use EKOS Corporation 11911 North Creek Parkway South Bothell, WA 98011 USA (425) 415-3100 (tel) (425) 415-3102 (fax) info@ekoscorp.com (e-mail) - 1-4913-002 REV E Intended Use
More informationBluetooth Pairing. User Guide
Bluetooth Pairing User Guide Copyright 2012 Hewlett-Packard Development Company, L.P. Microsoft, Windows, and Windows Vista are U.S. registered trademarks of Microsoft Corporation. Bluetooth is a trademark
More informationMultimedia. User Guide
Multimedia User Guide Copyright 2006 Hewlett-Packard Development Company, L.P. Microsoft and Windows are U.S. registered trademarks of Microsoft Corporation. The information contained herein is subject
More informationBODi rs BD004 Series Bandwidth-on-Demand Internet with Reliability and Survivability. Quick Start Guide NOTES
NOTES BODi rs BD004 Series Bandwidth-on-Demand Internet with Reliability and Survivability Quick Start Guide This is a Class A device and is not intended for use in a residential environment. Important
More informationHow to Set Up Your NSM4000 Appliance
How to Set Up Your NSM4000 Appliance Juniper Networks NSM4000 is an appliance version of Network and Security Manager (NSM), a software application that centralizes control and management of your Juniper
More informationIP PHONE SYSTEM. CooVox Series-U60 For Small and Medium Business. Quick Installation Guide. www.zycoo.com
SYS WAN LAN IP PHONE SYSTEM Series-U60 For Small and Medium Business Quick Installation Guide www.zycoo.com Table of Contents 1 Package Contents 2 Hardware Installation 2.1 Safety Precautions 2.2 Installation
More informationSet Up Your MXI -Express x4 System
Set Up Your MXI -Express x4 System Terminology This document explains what you will need to set up various MXI-Express x4 hardware configurations. The products covered by this guide are the NI PCIe-8371/8372
More informationRI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
More informationHP Pavilion All-in-One MS200 series PC. Upgrading and Servicing Guide. Printed in
HP Pavilion All-in-One MS200 series PC *579907-001* *579907-001* Printed in Upgrading and Servicing Guide Replacing a Wireless Keyboard or Mouse...2 Before You Begin... 2 Replacing the Keyboard or Mouse...
More informationChange your perspective of work
Change your perspective of work with the addition of multiple monitors Multiple monitors in the workplace In many professions, using more than one monitor from a single machine is not a new thing. Many
More informationAPC Step-Down Transformer. User s Manual
APC Step-Down Transformer Models: AP9621, SURT005, SURT006, SUTF3, SYTF2, SYTF2J, SYTF3 and SYTF3J User s Manual English 990-7820D, July 2003 TABLE OF CONTENTS APC Contact Numbers and Support Visit the
More informationCascade Profiler Fibre Channel SAN Attached Storage Installation Guide. Version 8.2 March 2009
Cascade Profiler Fibre Channel SAN Attached Storage Installation Guide Version 8.2 March 2009 Trademarks Riverbed, the Riverbed logo, Riverbed Cascade, and Cascade are trademarks of Riverbed Technology,
More informationRack Installation Instructions
Rack Installation Instructions Guidelines This publication provides information about how to install your server into a standard rack cabinet using the rail kit shipped with your server. If you no longer
More informationRain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English. 1-800- RAIN BIRD (800-724-6247) or visit www.rainbird.
Rain+Birdt Simple To Set r (SST) Setup & Operation Instructions English Installation...2 Tools and Supplies Needed...2 Step 1. Mount r...2 Step 2. Connect Power...2 Indoor r...2 Outdoor r...2 Step 3. Connect
More informationMedium voltage VCP-W MR2 (integral racking)
Supersedes March 2013 Contents Description Page Notices and warnings...................... 2 Introduction.............................. 3 Breaker pan configurations.................. 3 Inspection/maintenance.....................
More informationNEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL info@tuncmatik.com / www.tuncmatik.com Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3.
More informationHP Thin Client Imaging Tool
HP Thin Client Imaging Tool Table of Contents: Abstract... 1 Introduction... 1 System Requirements... 1 Software... 1 Hardware... 1 Getting Started... 2 Formatting a USB Flash Device... 3 Unpacking the
More informationInstallation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
More informationHP UPS Management Module Overview
Overview The enables you to monitor and manage power environments through comprehensive control of HP UPSs. The can support either a single UPS configuration or provides additional power protection with
More informationSunny Boy Accessories SMA POWER BALANCER
Sunny Boy Accessories SMA POWER BALANCER Installation Guide SBUS-PowBal-IUS102810 IMUS-SBUS-PBL Version 1.0 US SMA America, LLC Legal Restrictions Copyright 2010 SMA America, LLC. All rights reserved.
More informationHP 22-in-1 Media Card Reader
HP 22-in-1 Media Card Reader Introduction This document describes how to install the HP 22-in-1 Media Card Reader into an HP Workstations adapter bracket, and then install the media card reader and bracket
More informationHP Compaq LE1902x, LE2002x, LE2002xm, and LE2202x LED Backlit LCD Monitors. User Guide
HP Compaq LE1902x, LE2002x, LE2002xm, and LE2202x LED Backlit LCD Monitors User Guide 2011 Hewlett-Packard Development Company, L.P. Microsoft, Windows, and Windows Vista are either trademarks or registered
More informationQuickSpecs. HP Remote Monitored Power Distribution Units (mpdu) Overview
Overview HP Remote Monitored Power Distribution Units (PDU) provide rack level power monitoring over the network. With billing grade accuracy these PDUs are excellent choices for data centers wanting to
More informationPower Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation
One Dell Way Round Rock, Texas 78682 www.dell.com Dell Enterprise White Paper Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation January, 2008
More informationHard Disk Drive (HDD)
Installation Instructions Hard Disk Drive (HDD) Catalog Number 6189V-35HDDST80, 6189V-35HDDST160 Topic Page About This Publication 1 Important User Information 2 Electrostatic Discharge (ESD) Precautions
More informationRack Power Distribution. Worldwide
Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data
More informationSmall form factor bay converter and hard drive installation
Small form factor bay converter and hard drive installation HP xw6600 and HP xw8600 Workstations This document describes how to convert HP xw6600 and HP xw8600 Workstation 3.5-inch hard drive bays to hold
More informationInstruction / Installation Sheet DataComm Electronics 50-6623-WH-KIT Flat Panel TV Cable Organizer Kit with Duplex Power Solution
Instruction / Installation Sheet DataComm Electronics 50-6623-WH-KIT Flat Panel TV Cable Organizer Kit with Duplex Power Solution DataComm Electronics, Inc. 6349 Peachtree Street Norcross, GA 30071-1725
More informationQuick Start Guide. Cisco Small Business. 300 Series Managed Switches
Quick Start Guide Cisco Small Business 300 Series Managed Switches Welcome Thank you for choosing the Cisco 300 Series Managed Switch, a Cisco Small Business network communications device. This device
More informationInstallation Instructions
READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:
More informationINSTALLATION & SERVICE MANUAL. Display Panel
INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed
More informationSizing up screen differences
Sizing up screen differences What is the difference between square and widescreen monitors? Aspect ratios 101 Before we discuss the differences between square and widescreen monitors, it is important to
More informationMODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
More informationLT Charging Cart for Laptops
Built with Anthro-DNA LT Charging Cart for Laptops Owners Manual This unit has been tested to Underwriters Laboratories U.S. and Canadian (Bi-National) Standard for Safety of Informational Technology Equipment,
More informationSNQ-60x0-320 Series Data Center Switch. Quick Installation Guide
Introduction This guide is to assist the reader with the most basic form of installation and connection to switches in this series. As there is more than one switch in this series, the diagrams might slightly
More informationSense Components. Sense monitor. Antenna assembly. External mounting kit Current sensors. Download the Sense app. Go to sense.com/app.
Sense Components Sense monitor Antenna assembly External mounting kit Current sensors Download the Sense app. Go to sense.com/app Power cable Technical Specifications Sense is a home energy monitoring
More informationPower Commander Power Distribution Units from Wiremold/Legrand offer
Power Commander Power Distribution Units Rack Power Distribution Solutions for IT/Network Environments Power Commander Power Distribution Units from Wiremold/Legrand offer comprehensive power distribution
More informationRack Installation. Unpacking the System. Choosing a Setup Location. General Server Precautions. Barracuda Appliances
This set of instructions applies to racking and rail kit installation for 6XX and above. The Rack Mounting Instructions section below provides information on installing the SC825 chassis into a rack unit
More informationSATA and SAS Hard Drive Backplane
SATSASBAY3BK Instruction Manual SATA and SAS Hard Drive Backplane 3 Drive 3.5 Removable SATA/SAS Mobile Rack Backplane FCC Compliance Statement This equipment has been tested and found to comply with the
More informationUser Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply
User Manual English APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC Tower Uninterruptible Power Supply 990-1587A 12/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent
More informationOPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
More informationCalculating power requirements for HP ProLiant rack-mounted systems
Calculating power requirements for HP ProLiant rack-mounted systems technology brief Abstract... 2 Introduction... 2 Key parameters... 2 Input line voltage... 2 Device VA rating... 3 Device input power...
More information