1 Ruling No Application No BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, AND IN THE MATTER OF Articles , and of Regulation 403, as amended by O. Reg. 22/98, 102/98, 122/98, 152/99, 278/99, 593/99, 597/99 and 205/00 (the Ontario Building Code ). AND IN THE MATTER OF an application by Mr. Bruno G. Schickedanz, B.G. Schickedanz Homes Inc., Woodbridge, Ontario, for the resolution of a dispute with Mr. Yaman Uzumeri, Chief Building Official, City of Toronto, Ontario, to determine whether the as-built exterior concrete stairs and landings, having widths ranging from 814 mm to 850 mm, provide sufficiency of compliance with Articles , and of the Ontario Building Code at Units 9 and 10 Charlton Settlement Avenue, and Units 13, 15 and 17 Rivers Edge Drive the Riverboat Landing development, 1400 Weston Road, Toronto, Ontario. APPLICANT RESPONDENT PANEL PLACE Mr. Bruno G. Schickedanz B.G. Schickedanz Homes Inc. Woodbridge, Ontario Mr. Yaman Uzumeri Chief Building Official City of Toronto Dr. Kenneth Peaker, Chair Mr. Fred Barkhouse Mr. Donald Pratt Toronto, Ontario DATE OF HEARING November 30 th, 2000 DATE OF RULING November 30 th, 2000 APPEARANCES Mr. Alex Talwood Toronto, Ontario Agent for the Applicant Mr. Jim Laughlin Manager, Field Office City of Toronto, Ontario Designate for the Respondent

2 -2- RULING 1. The Applicant Mr. Bruno G. Schickedanz, B.G. Schickedanz Homes Inc., Woodbridge, Ontario, has received an order to comply under the Building Code Act, 1992 to rectify certain alleged deficiencies in respect to the construction of a townhouse complex known as Riverboat Landing, Charlton Settlement Avenue and Rivers Edge Drive, 1400 Weston Road, Toronto, Ontario. 2. Description of Construction The Applicant has constructed a townhouse complex consisting of 43 townhomes arranged in 7 blocks. The buildings have a Group C occupancy classification, a building area of less than 600 m 2 and are three storey in building height. Throughout the townhouse blocks are five units subject to this dispute. These are identified as Units 9 and 10, fronting onto Charlton Settlement Avenue and Units 13, 15 and 17, fronting onto Rivers Edge Drive. The units are called the Simcoe and York models and have floorareas of m 2 (1,200 ft 2 ) and m 2 (1,120 ft 2 ) respectively. All of the buildings are comprised of combustible construction. The construction in dispute involves the width of the exterior covered concrete stairs and landings which form part of the required exit from each of the subject units. The front entrance to each unit is located approximately 1,371 mm (4 ft 6 in) to 1,524 mm (5 ft) above grade and is recessed behind the front wall face of the subject dwelling. The widths of the front stairs and landings range from 814 mm (Unit 15) to 850 mm (Units 10 and 13) when measured between the adjacent wall faces. The front door to each of the units measures 790 mm (31 in) in width. 3. Dispute The issue at dispute between the Applicant and Respondent is whether the as-built concrete stairs and landings at the front of the subject units provide sufficiency of compliance with Articles , and of the Ontario Building Code. Sentence (1) of Article requires a minimum width for exit stairs, when measured between wall faces or guards, of 900 mm (2 ft 11 in). In the case at hand, the as-built stairs form part of a required exit from the dwelling units in question and as a result, the 900 mm minimum width requirement applies. The stair widths, however, measure between 814 mm (32 in) and 850 mm (33 ½ in) rather than the required 900 mm. Further, Article requires that landings shall be at least as wide and as long as the width of the stairs in which they occur. This article continues by providing certain exemptions for that length of some landings, however, it offers no relief for the width requirement (i.e., must be the same as stairs) of landings. In this instance, while the landings are generally the same width as the stairs in which they occur, like the stairs, they do not meet the minimum 900 mm width requirement. Article further prescribes the widths of required exits, mandating that (except for doors and corridors) the width of every exit facility shall be not less than 900 mm. As already noted, the as-built stairs and landings, with measurements between 814 mm and 850 mm, do not meet this minimum standard.

3 -3-4. Provisions of the Ontario Building Code Article Stair Width (1) Exit stairs and stairs used by the public shall have a width, measured between wall faces or guards, of not less than 900 mm (2 ft 11 in). (2) At least 1 stairway between each floor level in a dwelling unit shall have a width between wall faces of not less than 860 mm (2 ft 10 in). Article Dimensions of Landings (1) Landings shall be at least as wide and as long as the width of stairs in which they occur, except that (a) the length of landing for exterior stairs serving not more than 1 dwelling unit need not exceed 900 mm (2 ft 11 in), and (b) the length of landing for all other stairs in a straight run need not exceed mm (3 ft 7 in). (See also Articles and for landings in exits.) Article Exit Width (1) Except for doors and corridors, the width of every exit facility shall be not less than 900 mm (2 ft 11 in). (See Article for doors and Subsection for stairs.) 5. Applicant s Position The Agent for the Applicant began by providing the Commission with some background information, explaining that construction of the townhomes commenced in the fall of The issue of noncompliance was discovered in late winter or early spring of 2000, when an order to comply was issued by the City. At this point, he argued, it was too late to halt construction and alter the design to comply with the OBC. He advised that the townhomes are now built and occupied. In his opinion, safety is not reduced because of the differential in stair and landing widths. He noted that the as-built condition is only slightly less than the minimum requirement. The Agent stated that his client did not intentionally construct the stairs and landings to be noncompliant with the OBC requirements. He indicated that, the problem occurred as a result of a construction error. Specifically, it appeared that the landings were built without taking into consideration the thickness of the masonry veneer used on the lower portion of the townhouses. In effect, the masonry veneer thereby narrowed the landing areas and the stairs were subsequently built to the same narrowed width as the landings. The Agent then argued that the stair and landing widths are greater than the width of the associated doors and, as such, it is his opinion that if a person can pass through the wooden door frame, they are also able to pass through the landing area. In addition, he submitted that more than the required number of exits have been provided within each unit. An occupant, he argued, has the option of exiting from the front door, the rear door or any one of the operable casement windows on the second and third floors. In addition, many of the units have access to the garage from the interior of the dwelling.

4 -4- In summation, the Agent submitted that the Code violation in this instance was a genuine mistake. The stairs and landings were constructed unintentionally narrow and given the extenuating circumstances involved, rectifying the situation would have been difficult at the time the order to comply was issued. The Agent again emphasized that additional means of egress from the buildings had been provided, stating that safety would not be compromised in this instance. 6. Respondent s Position The Designate for the Respondent submitted that a permit had not been issued for this development at the time construction commenced. The permit plans, however, indicated landings and stairs which would have been wide enough to satisfy the OBC requirements. In his opinion, it was not too late to remedy the situation at the time the order was issued. There were alternatives available to the Applicant that were not pursued. In fact, stucco was used on the wall face of one of the units that was identified prior to finished construction. Using a similar material here may have resolved the dispute involving the units in question. The Designate argued, because this is a means of egress, the narrow landings and stairways pose a real problem and may jeopardize the safety of the occupants of the subject units. This access point, being the front door to the dwelling, he submitted, is the most frequently used entrance/exit and is logically the route for safety first thought of in an emergency situation. In addition he disputed the Applicant s claim with respect to the number of available egress routes. He argued that one may not reasonably be expected to jump out of a second or third storey window and, in any event, it should not be considered as a route that would contribute to the safe evacuation of the dwelling. In summation, the Designate argued that the stairs and landings in question are considered to be part of the required exit. In addition, the front door of the dwellings would likely be selected as the main exit by the occupants of the units in an emergency. It is important that the minimum provisions of the Building Code be complied with in this respect. 7. Commission Ruling It is the decision of the Building Code Commission that the as-built exterior concrete exit stairs and landings, having widths ranging from 814 mm to 850 mm, do not provide sufficiency of compliance with Articles , , and of the Ontario Building Code at Units 9 and 10 Charleton Settlement Avenue and Units 13, 15 and 17 Rivers Edge Drive, 1400 Weston Road, Toronto, Ontario. 8. Reasons i) The as-built stairs and landings do not meet the minimum standards set out in the Building Code, nor have any acceptable compensating measures been offered in lieu of compliance. ii) There were, and continue to be, viable options available to the Applicant enabling him to comply with the minimum standard outlined in the OBC.

5 -5- Dated at Toronto this 30 th, day in the month of November in the year 2000 for application number Dr. Kenneth Peaker, Chair Mr. Fred Barkhouse Mr. Donald Pratt

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-25-880 Application No. 2002-21 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 9.30.1.2 of

More information

New Ontario Building Code Highlights

New Ontario Building Code Highlights New Ontario Building Code Highlights Part 9 This summary highlights items that are believed to be significant changes to the 2012 OBC and is not intended to include all changes made within this or other

More information

Number of Sides Required to Have a Handrail

Number of Sides Required to Have a Handrail Excerpt from 2012 B.C. Building Code HANDRAILS & GUARDS 9.8.7. Handrails 9.8.7.1. Required Handrails 1) Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and ramps in accordance

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 05-03-1017 Application No. 2004-73 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 3.1.10.5. of

More information

9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards.

9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards. Section 9.8. Stairs, Ramps, Handrails and Guards 9.8.1. Application 9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and

More information

http://www.iccsafe.org/

http://www.iccsafe.org/ Sections R311 and R312 from the 2006 International Residential Code These sections of Chapter 3 of the 2006 International Residential Code for One and Two Family Dwellings (R311 and R312) including the

More information

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS

Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44

More information

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 **Disclaimer: This document is to serve as informational purposes only. This is not a code book or a final interpretation of the

More information

Certification: Building Plans Examiner. Exam ID: B3

Certification: Building Plans Examiner. Exam ID: B3 Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 STAIRWAYS 46. LANDINGS. Section R311 IRC 2009 R311.7.5 Landings for stairways. There shall be a floor or

More information

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012 2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,

More information

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

Area of Rescue Assistance Communication System ADA Code Applicable excerpts: Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

WINDOW AND DOOR REPLACEMENT REQUIREMENTS

WINDOW AND DOOR REPLACEMENT REQUIREMENTS WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.

More information

BUILDING PERMIT SPECIFICATIONS

BUILDING PERMIT SPECIFICATIONS BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide

More information

APPLICATION NO. 15/P/00168 RECEIVED: 27-Mar-2015. Change of use of shop to residential flat (first floor) and shop alterations

APPLICATION NO. 15/P/00168 RECEIVED: 27-Mar-2015. Change of use of shop to residential flat (first floor) and shop alterations DATE OF COMMITTEE: 12-May-2015 APPLICATION NO. 15/P/00168 RECEIVED: 27-Mar-2015 PROPOSAL: Change of use of shop to residential flat (first floor) and shop alterations LOCATION: APPLICATION TYPE: APPLICANT:

More information

H:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh

H:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh Accessory Apartment Construction Guide For Single Detached Dwelling and Semi-Detached Dwellings that have been in existence for at least five (5) years Notes: Buildings that are less than five (5) years

More information

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this

More information

ORDINANCE NO. 2013 -

ORDINANCE NO. 2013 - ORDINANCE NO. 2013 - AN ORDINANCE OF BREVARD COUNTY, FLORIDA AMENDING CHAPTER 62, LAND DEVELOPMENT REGULATIONS SECTION 62-2891, LOT DRAINAGE, AND CHAPTER 22 BUILDINGS AND BUILDING REGULATIONS, SECTION

More information

CITY OF TORONTO. BY-LAW No. 349-2008

CITY OF TORONTO. BY-LAW No. 349-2008 Authority: Licensing and Standards Committee Item 12.3, adopted as amended, by City of Toronto Council on April 28 and 29, 2008 Enacted by Council: April 29, 2008 CITY OF TORONTO BY-LAW No. 349-2008 To

More information

17,280 square feet Overview:

17,280 square feet Overview: CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The

More information

Enrolled Copy S.B. 117

Enrolled Copy S.B. 117 1 COMMERCIAL INTERIOR DESIGN CERTIFICATION 2 MODIFICATIONS 3 2016 GENERAL SESSION 4 STATE OF UTAH 5 Chief Sponsor: Luz Escamilla 6 House Sponsor: Mike Schultz 7 8 LONG TITLE 9 General Description: 10 This

More information

City of Peterborough

City of Peterborough City of Peterborough Building Division Basement Finishing Guide Residential Information Guides This information is intended to be used as an guide that outlines minimum requirements when finishing a basement,

More information

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.

OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes. 1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310

More information

MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal

MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY Policy #: Subject of Policy: INS-04 (2007) Escape Windows Revised and Approved By: Title: Jerry Rosendahl State Fire

More information

BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010

BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance

More information

PUBLIC MINUTES PROPERTY MAINTENANCE APPEALS BOARD. Wednesday, November 25, 2015, 3:46 p.m. Committee Room B, City Hall

PUBLIC MINUTES PROPERTY MAINTENANCE APPEALS BOARD. Wednesday, November 25, 2015, 3:46 p.m. Committee Room B, City Hall PUBLIC MINUTES PROPERTY MAINTENANCE APPEALS BOARD Wednesday,, 3:46 p.m. Committee Room B, City Hall PRESENT: Mr. Ian Oliver, Chair Mr. Michael Brockbank, Vice-Chair Mr. Roy Fleming, Member Mr. Donald Stiller,

More information

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) Chapter 1 : Definitions clause 1.2.10 : circulation space OLD CLAUSE A space mainly used as means of access between a room or protected shaft

More information

Residential Adjustments. Overview 4.1

Residential Adjustments. Overview 4.1 Overview 4.1 Summary This chapter contains an overview of residential structural components, quality of construction, main dwellings, and construction types. It also provides adjustments such as wall height,

More information

The replacement or modification of existing windows shall comply with the following requirements:

The replacement or modification of existing windows shall comply with the following requirements: City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)

More information

NRC Canadian Codes Centre. Codes Update. Nedjma Belrechid October 2012

NRC Canadian Codes Centre. Codes Update. Nedjma Belrechid October 2012 NRC Canadian Codes Centre Codes Update Nedjma Belrechid October 2012 Codes Update Outline Activities of CCBFC, PTPACC, NRC-IRC Code Development Public Reviews Active/Inactive SC Tasks Detailed: Step Dimensions

More information

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM

More information

Code Requirements for Existing Buildings

Code Requirements for Existing Buildings Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)

More information

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013 Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have

More information

The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE

The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE BUILDING SERVICES DEPARTMENT 789 Broadway Street, Box 3000 Wyoming, ON N0N 1T0 Telephone: 519 845-0801 Toll-free: 1-866-324-6912 Fax: 519

More information

NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02

NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 PART A: Project Data and Classification 1. Project name & location Renovation of the Cheerwine Building, 322 East Council St.,

More information

Exterior Elevated Elements Inspection Guidelines

Exterior Elevated Elements Inspection Guidelines Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code

More information

Guidance on loft conversions in two-storey houses

Guidance on loft conversions in two-storey houses Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations

More information

RESIDENTIAL WOOD DECKS

RESIDENTIAL WOOD DECKS RESIDENTIAL WOOD DECKS 1 A Building Permit is required for the construction of a wood deck where the deck is more than 600 mm above grade at any point. Definition: For the purposes of this pamphlet, a

More information

SECTION XI OPINION OF PROBABLE COST

SECTION XI OPINION OF PROBABLE COST SECTION XI OPINION OF PROBABLE COST OPINION OF PROPABLE COSTS HARBOR ISLAND THE PAVILION 1) Provide a sprinkler system for the entire building. 8000 SF X $15/SF $120,000 2) Remove and replace existing

More information

MULTI-FAMILY, COMMERCIAL, INDUSTRIAL, AS GOVERNED BY THE BC BUILDING CODE PART 3

MULTI-FAMILY, COMMERCIAL, INDUSTRIAL, AS GOVERNED BY THE BC BUILDING CODE PART 3 TOWN OF SIDNEY Multi-Family, Commercial, Industrial and Institutional Building Permit Guide The information provided is intended as a guide only and does not replace current bylaws and regulations. Complete

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,

More information

Edward R. Sajecki Commissioner of Planning and Building

Edward R. Sajecki Commissioner of Planning and Building Corporate Report Clerk s Files Originator s Files FA.31 06/001 W1 DATE: June 6, 2006 TO: FROM: SUBJECT: Chair and Members of Planning and Development Committee Meeting Date: June 26, 2006 Edward R. Sajecki

More information

Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:

Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION

More information

Fixed Access Ladders. Table of Contents. 1. Legislative Requirements

Fixed Access Ladders. Table of Contents. 1. Legislative Requirements Fixed Access Ladders Engineering Data Sheet 2-04 Revised: January 1997 Table of Contents 1. Legislative Requirements 2. General 3. Rungs 4. Side Rails 5. Safety Cages 6. Attachment & Anchoring 7. Platforms

More information

CHAPTER 6 CONSTRUCTION TYPES

CHAPTER 6 CONSTRUCTION TYPES CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use

More information

Lindsay Thurber Comprehensive High School Red Deer School District No. 104 School Facilities Evaluation Project Page 1

Lindsay Thurber Comprehensive High School Red Deer School District No. 104 School Facilities Evaluation Project Page 1 School Facilities Evaluation Project Page 1 Executive Summary In November 1999, Alberta Infrastructure, School Facilities Branch engaged Stephens Kozak Carr and Brown Architects to conduct evaluations

More information

Section 801 Driveway Access Onto Public Right-of-Ways

Section 801 Driveway Access Onto Public Right-of-Ways Section 801:00 Section 801 Driveway Access Onto Public Right-of-Ways Section 801:00. Definitions. The following words and terms, when used in this Article, shall have the following meanings, unless the

More information

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,

More information

I N T E R N A T I O N A L R E S I D E N T I A L CO D E

I N T E R N A T I O N A L R E S I D E N T I A L CO D E Visual Interpretation Of The I N T E R N A T I O N A L R E S I D E N T I A L CO D E 2006 STAIR BUILDING CODE Portions of this document reproduce sections from the 2006 International Residential Code, International

More information

Classroom Door Security & Locking Hardware

Classroom Door Security & Locking Hardware Classroom Door Security & Locking Hardware The ability to protect students and teachers while in the classroom is a high priority in all educational institutions. Many schools and school districts have

More information

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the

More information

REQUIREMENT 3. Usable Doors

REQUIREMENT 3. Usable Doors Chapter Three: REQUIREMENT 3 Usable Doors 3...covered multifamily dwellings with a building entrance on an accessible route shall be designed in such a manner that all the doors designed to allow passage

More information

Prior to submission of drawings for building permit, the architectural control process will be undertaken for the developer and/or builders.

Prior to submission of drawings for building permit, the architectural control process will be undertaken for the developer and/or builders. 6.0 Design Review process 6.0 Design Review Process The design review process will coordinate the public and private realm architecture for the community, i.e., the site planning, streetscape, and architecture

More information

The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri

The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri Determination 2009/103 The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri 1. The matters to be determined 1.1 This is a determination under Part 3 Subpart 1 of the

More information

SECTION 5 RESIDENTIAL R1 ZONE

SECTION 5 RESIDENTIAL R1 ZONE SECTION 5 RESIDENTIAL R1 ZONE 5.1 GENERAL PURPOSE OF THE R1 ZONE The R1 Zone is the most restrictive residential zone, and provides for and regulates single detached dwellings. The zone variations are

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT SINCERE KNIT GARMENTS LTD UNIT-1 EAST ISDAIR, CHANDMARI, FATULLAH OTHER FACTORIES: FAKIR KNIT LTD. July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by

More information

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE

More information

Glass and Building Regulations Impact Safety

Glass and Building Regulations Impact Safety Glass and Building Regulations Impact Safety England and Wales Approved Document N Scotland Part P Northern Ireland Part V Foreword For new buildings, and for buildings subject to major refurbishment,

More information

Ontario s 2012 Building Code Division B, Part 9 (Ontario Regulation 332/12)

Ontario s 2012 Building Code Division B, Part 9 (Ontario Regulation 332/12) Ontario s 2012 Building Code Division B, Part 9 (Ontario Regulation 332/12) Notice: This e-learning module is intended for general information purposes only. It only highlights certain provisions of the

More information

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT Page 1 CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT CIVIC CENTRE 2141 MAJOR MACKENZIE DRIVE MAPLE ONTARIO L6A 1T1 905-832-2281 Page 2 SECTION 1 - GENERAL OBJECTIVES To provide

More information

Chapter 3: Use and Occupancy Classification

Chapter 3: Use and Occupancy Classification Chapter 3: Use and Occupancy Classification General Comments Chapter 3 provides for the classification of buildings, structures and parts thereof based on the purpose or purposes for which they are used.

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level

More information

Approved Document Q: Security

Approved Document Q: Security Approved Document Q: Security Requirement Q1 Unauthorised access Consultation draft September 2014 1 The approved documents What is an approved document? The Secretary of State has approved a series of

More information

EXAM GUIDE. Schematic Design. Overview 2. Interior Layout Vignette 3 Sample Passing Solution 5 Sample Failing Solution 6

EXAM GUIDE. Schematic Design. Overview 2. Interior Layout Vignette 3 Sample Passing Solution 5 Sample Failing Solution 6 RE EXAM GUIDE Schematic 2 3 Sample Passing Solution 5 Sample Failing Solution 6 7 Sample Passing Solution 10 Sample Failing Solution 12 14 Copyright 2015 This document, effective August 2015, supersedes

More information

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration

More information

Measuring Single Family Dwellings Town homes Condominium Units. www.thompsonappraisals.com P)843-626-7625 ~ F)843-626-7627

Measuring Single Family Dwellings Town homes Condominium Units. www.thompsonappraisals.com P)843-626-7625 ~ F)843-626-7627 Measuring Single Family Dwellings Town homes Condominium Units www.thompsonappraisals.com P)843-626-7625 ~ F)843-626-7627 You have been taught your whole career that the three most important factors concerning

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management

More information

WARRANTIES AND PERFORMANCE STANDARDS T A B L E O F C O N T E N T S General Provisions Introduction Warranties Effective Date of Warranties Exclusive

WARRANTIES AND PERFORMANCE STANDARDS T A B L E O F C O N T E N T S General Provisions Introduction Warranties Effective Date of Warranties Exclusive WARRANTIES AND PERFORMANCE STANDARDS T A B L E O F C O N T E N T S General Provisions Introduction Warranties Effective Date of Warranties Exclusive Warranties Time Limits for Reporting Manufacturer s

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

It is against this refusal that the appellant appealed to the Secretary of State.

It is against this refusal that the appellant appealed to the Secretary of State. Our Ref: APP/007002/014 Your Ref:... 7 October 2014 BUILDING ACT 1984 - SECTION 39 APPEAL AGAINST REFUSAL TO DISPENSE REQUIREMENT B1 (MEANS AND WARNING OF ESCAPE) IN PART B (FIRE SAFETY) OF SCHEDULE 1

More information

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING BUILDING CODEACT, 1992 RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING Pursuant to clause 29(l)(b) of the Building Code Act, 1992. as amended, the Director of the Building and Development Branch

More information

Building Permit Application

Building Permit Application Building Permit Application Front of Yonge Township Office 1514 County Road 2, P.O. Box 130 Mallorytown ON, K0E 1R0 Tel: 613-923-2251 Fax: 613-923-2421 admin@frontofyonge.com www.mallorytown.ca Last Updated

More information

Small Business Permit Service

Small Business Permit Service Small Business Permit Service Building Permit Requirements For a Unit Finish or Interior Alteration Industrial, Commercial or Institutional Occupancies Building Permit Application The following documents

More information

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Facility Assessment for. 11801 East Main Street, Huntley, IL

Facility Assessment for. 11801 East Main Street, Huntley, IL Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested

More information

Residential Decks. Planning and Development Services Department

Residential Decks. Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks

More information

A Homeowner s Guide to Building Permits

A Homeowner s Guide to Building Permits A Homeowner s Guide to Building Permits Building Division City of London 300 Dufferin Ave. P.O. Box 5035 London, ON N6A 4L9 Table of Contents What is a Building?... 3 Planning Your Project... 3 When is

More information

Ministry of the Environment Decree on accessible building

Ministry of the Environment Decree on accessible building F1 THE FINNISH BUILDING REGULATIONS 1 Barrier-free Building Regulations and 2005 Ministry of the Environment Decree on accessible building adopted in Helsinki on the 1 st of October 2004 In accordance

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County Building Permit Application Packet The purpose of Building Codes is to establish the minimum requirements to safe guard the public health, safety and general welfare through structural strength, means

More information

Article 5: Building Regulations

Article 5: Building Regulations Article 5: Building Regulations Division 37: Additional Building Regulations for Archaic Materials and Methods of Construction (Added Additional Building Regulations for Archaic Materials and Methods of

More information

Beth Israel Deaconess Medical Center Environment of Care Manual

Beth Israel Deaconess Medical Center Environment of Care Manual Beth Israel Deaconess Medical Center Environment of Care Manual Title: Interim Life Safety Measures (ILSM) Plan Policy #: EC39 Purpose: ILSM are fully adhered to in areas where the hospital/site occupants

More information

780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL EXISTING BUILDING CODE 2009

780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL EXISTING BUILDING CODE 2009 780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL EXISTING BUILDING CODE 2009 CHAPTER 34: EXISTING STRUCTURES 3401.1 Replace as follows: 3401.1 Scope. Chapter 34 of the International Building Code

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com

PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com June 17, 2015 Ms. Kimberley Heaton McCarthy Supervising Planner Building and Safety

More information

BUILDING REGULATIONS GUIDANCE NOTE NHBC BUILDING CONTROL

BUILDING REGULATIONS GUIDANCE NOTE NHBC BUILDING CONTROL BUILDING REGULATIONS GUIDANCE NOTE NHBC BUILDING CONTROL ACCESS TO AND USE OF BUILDINGS Parts M and K* to the Building Regulations require that people, regardless of disability, age or gender are able

More information

RESIDENTIAL WINDOW REPLACEMENT

RESIDENTIAL WINDOW REPLACEMENT 3S258 MANNING AVENUE WARRENVILLE, IL 60555 PH: 630.393.9050 FAX 630.393.1531 RESIDENTIAL WINDOW REPLACEMENT A building permit is required for the installation or replacement of windows in a residence.

More information

The Homeowner s Building Application Checklist for Constructing a Residential Sundeck

The Homeowner s Building Application Checklist for Constructing a Residential Sundeck This checklist provides homeowners a summary of the Building Permit submission requirements for constructing a residential sundeck. Regardless of the deck s walking surface area, if the deck is adjacent

More information

BROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208

BROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 BROWNSVILLE STRUCTURES STUDY July 2012 Prepared by LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 TABLE OF CONTENTS I. SUMMARY OF BUILDING ANALYSIS.. 1 II. INDIVIDUAL BUILDING

More information

ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY

ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY CHAPTER 32 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY SECTION BC 3201 GENERAL 3201.1 Scope. The provisions of this chapter shall govern the encroachment of structures into the public right-of-way. 3201.1.1

More information

By-law to Regulate Vacant Buildings

By-law to Regulate Vacant Buildings By-law to Regulate Vacant Buildings A-35 Enacted November 23, 2009 This by-law is printed under and by authority of the Council of the City of London, Ontario, Canada Disclaimer: The following consolidation

More information

STICKLEY AUDITORIUM RENOVATION Community and Stakeholder Presentation

STICKLEY AUDITORIUM RENOVATION Community and Stakeholder Presentation STICKLEY AUDITORIUM RENOVATION Community and Stakeholder Presentation APRIL 30, 2014 SCHEMATIC DESIGN PROGRESS Code Study Analysis: key issues and resolutions Seating Analysis of sightlines, seating and

More information

STATE OF FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF FLORIDA CONDOMINIUMS, TIMESHARES AND MOBILE HOMES

STATE OF FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF FLORIDA CONDOMINIUMS, TIMESHARES AND MOBILE HOMES STATE OF FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DIVISION OF FLORIDA CONDOMINIUMS, TIMESHARES AND MOBILE HOMES IN RE: PETITION FOR ARBITRATION 2701 Riverside Drive 107-B, LLC, Petitioners,

More information

THE CORPORATION OF THE TOWNSHIP OF SEVERN BY-LAW NO. 2014-01

THE CORPORATION OF THE TOWNSHIP OF SEVERN BY-LAW NO. 2014-01 THE CORPORATION OF THE TOWNSHIP OF SEVERN BY-LAW NO. 2014-01 BEING A BY-LAW TO PROVIDE FOR THE ADMINISTRATION OF THE BUILDING CODE ACT WITHIN THE CORPORATE LIMITS OF THE TOWNSHIP OF SEVERN WHEREAS the

More information