1 CPA Residential Re-roof Inspection Page 1 of 9 ROOFING New and Re-roofs City of Palo Alto (CPA) Building Inspection Division 285 Hamilton Ave. Inspection Request: Building Division IVR# s: Tear-off 802, Revision Date: 02/07/11 General Requirements/Checklist for: Residential Codes Enforced: 2010 CRC, CBC, CPC, CMC, CEC Palo Alto Municipal Code (PAMC) In-Progress 805, Final 808 The information provided in this document is general and intended as a guide only. Each project is unique and additional requirements may be enforced as deemed appropriate. WARNING Failure to complete items below prior to inspection may result in a re-inspection fee. GREEN BUILDING TIPS Link to all of the energy efficiency tax credits: Installing radiant barrier sheathing reduces summer heat gain and winter heat loss, reflects 97% of heat back towards its source and can cut your annual energy cost by approximately 20% to 30%. Solar reflective asphalt shingles. Solar powered roof fan. Energy star skylights or light tubes. Attic/roof insulation rebate. Dispose of old roof at a local recycling center. See list of Recycling Centers APPLICATION Accessory structures: Structures 120 s.f. or less in area do not require reroofing permits. Structures greater than 120 s.f. will require submittal of documentation verifying status as a legal permitted structure including a dimensioned site plan prior to inspection. A permit is required for repairs that exceed 100 sq. ft./1 square. Approved roof assemblies covered under CBC chapter15: Asphalt shingles, Clay and concrete tile, Metal roof panels, Metal roof shingles, Mineral-surfaced roll roofing, Wood shingles, Wood shakes, Built-up roofs, Modified bitumen roofing. All other roof assemblies are considered an alternative methods and shall be pre-approved prior to installation. All approved roofing systems shall be installed per manufacturer s instructions. Proposed skylights and/or structural changes require appropriate permits; including all building, electrical, plumbing and mechanical, as required. Structural plans shall be included as required. Overlay installations must have prior approval. A pre -roof inspection is required.

2 CPA Residential Re-roof Inspection Page 2 of 9 DOCUMENTATION Permit card shall be at all scheduled inspections. Provide inspector with manufacturer s installation instructions OR provide ICC/ES report (ICC/ES evaluation service at DUST CONTROL PAMC (A) (21) Dry cutting of tile/stone/concrete is not allowed, must use wet saw. ALTERNATIVE METHODS Roofing systems not covered in the CBC chapter 15, such as fluid applied or applied nonasphaltic sheets, shall be pre-approved and installed with materials and procedures approved by the building official including ICC/ES report submittals. CBC NOT ALLOWED Copper rain gutters/downspouts are not allowed per PAMC sec (b) 2 Buildings with eave overhangs cannot collect or direct water over adjacent properties (must install gutters). ACCESS TO ROOF (LADDER) Provide extended ladder secured to building, extended minimum of 30 above roof level. provide ladder(s) at all roof levels. Ladders to be minimum rated at 350 lbs load capacity. Ladders shall be placed so as not to damage roof and gutters. CBC FIREPLACE CHIMNEY Damage: When inspection reveals that an existing fireplace chimney is not safe for the intended application, it shall be repaired, rebuilt, or replaced with a approved factory built chimney. CBC 115.1, CMC See fireplace transition frame checklist. Spark Arrester Replacement alteration or repair to roof requires a spark arrester to be installed. All chimneys attached to any appliance or fireplace that burns solid fuel/wood burning shall be equipped with an approved spark arrester. Spark arrester shall be properly sized, screened, accessible and removable for cleaning per CBC 2113a.9.1 architectural shroud(s) are not allowed unless listed as part of the fireplace. CRC R , CBC 2113a.9.1, , CBC 2113a.9.1, PAMC Penetration in roof 30 or more requires a cricket. (Skylight and chimney) SKYLIGHTS Skylights require separate permit and inspections. Skylight curbs required at 3:12 slope, min. 4 for less than 3:12 roof. FIRE CLASSIFICATION Roof assemblies shall be divided into classes defined below. The minimum roof coverings installed on buildings shall comply with table based on the type of construction of the building.

3 CPA Residential Re-roof Inspection Page 3 of 9 Table * MINIMUM ROOF COVERING CLASSIFICATION FOR TYPES OF CONSTRUCTION IA IB IIA IIB IIIA IIIB IV VA VB B B B C B C B B C * Unless otherwise required in accordance with chapter 7A.(Exterior Wildland Exposure) REQUIRED INSPECTIONS Tear-off: REPLACE DAMAGED WOOD PRIOR TO INSPECTION. Verify structure is adequate for roofing system load. Verify fireplace chimney is structurally safe. Sheathing: If applicable, sheathing must be completed prior to inspection. Tear-off and roof nailing may be combined except in repaired areas must leave accessible for inspection. In-progress: Complete a representative sample of roof underlayment, starter coarse, nailing, flashing, attachments, clearances, and drainage provisions. Final: All work complete, spark arrester installed, roof and job site clean of debris. If gutters and rain leaders existed prior to the installation of the roofing, they must be installed at the time of the inspection. CPA INSPECTION General Requirements Structural loads Verify roofing materials have not changed creating added load. Structural roof components shall be capable of supporting the roof-covering system and the material and equipment loads that will be encountered during installation of the system. If necessary, an engineer s assessment will be required. CBC Roof covering Roof coverings shall be installed per approved manufacturer s installation instructions and applicable provisions of CBC Identification: Roof-covering material packages shall bear manufacture s identification marks and approved testing agency labels. CBC Roof-coverings shall be compatible with each other and with the building to which the materials are applied. CBC Fire classification Min. Class C. CBC WildLand Urban Interface fire area shall have min. Class A. CBC , Sheathing Sheathing cut into widths less than 24 require solid blocking at all panel edges. CBC Plywood and OSB roof sheathing shall be exterior grade (Exposure 1) including the under side of eaves. CBC Minimum sheathing thickness shall not be less than 7/16 for plywood and 11/32 for OSB. CBC TABLE

4 CPA Residential Re-roof Inspection Page 4 of 9 Sheathing shall be gapped 1/8 at edges. Fasteners: Min. 6 edge and 12 field nailing with min. 8d commons nails. Flashing (Coastal Zone Requirements) Material: Metal flashing shall be min. corrosion resistant 26 gage galvanized sheet AND shall be primed and painted. CBC Location: Flashing shall be installed at wall and roof intersections, at gutters, change in roof slope or direction, around openings, and drip edge flashing at eaves and gable edges. CBC , Counter flashing is required at all vertical surfaces (walls and chimneys). Sidewall flashing shall be by the step-flashing method. The flashing shall be a minimum of 4 high and 4 wide. CRC R Frequently missed/inspection failure: Missing, rusted or damaged flashing and counter flashing vent caps and metal edging shall be replaced with new materials. All metal allowed to be reinstalled shall be primed prior to re-roofing and painted prior to final installation CBC Valley flashing shall extend a min. 8 from centerline each way, total 16, and shall have a min. 4 end lap. CBC Valley flashing for wood shakes and shingles shall extend a minimum 11 from centerline each way, total of 22, and shall have a min. 4 end lap. CBC , All flashing shall be sloped ¼ per foot. Frequently missed/inspection failure Provide drip edge at eaves and gables of asphalt and wood shingles Drip edge shall extend a min. ¼ below sheathing and extend back on roof a min. 2 and mechanically fastened a maximum of 12 on center. CBC Note: Rain gutters shall not be used in place of drip edge unless the flange is a min. 2. See detail below

5 CPA Residential Re-roof Inspection Page 5 of 9 Vent flashing and vent caps Roof top vent flashing minimum requirements: See Table A-1 below Vent caps shall be primed and painted prior to final inspection. Table A-1 Rooftop Vent Flashing Minimum Size Requirements Regular Wood Shingle Wood Shake Vent pipe Base size Vent pipe Base size Vent pipe Base size size size size x x x x x x26 Cricket or saddle *New CBC Code requirement as of January 1, 2008 *Cricket or saddle shall be installed at the ridge side of chimney or penetration greater than 30 wide CBC SEE FIGURE A-2

6 CPA Residential Re-roof Inspection Page 6 of 9 Ventilation Roof/Attic ventilation: Min. net free ventilation 1/150 sq. ft. of area with 50% at upper portion a min. of 3 above eave or cornices vents and the balance ventilation provided by eave or cornice vents. Openings to attics shall be covered with corrosion-resistant wire mesh. Mesh openings: Min. of 1/8 not to exceed ¼. CBC , Fasteners All roofing systems shall use corrosion resistant, 12 gage fasteners/nails, clay or tile min. 11 gage. Fasteners shall have a sufficient length to penetrate into deck a min. of ¾. CBC , Rain Gutters/Downspouts Frequently Missed/Inspection Failure: Contractor shall provide SPLASH BLOCKS (min. 2 long) under downspouts diverting water from foundation. CBC Roof gutters shall be of non-combustible materials or min. schedule 40 plastic pipe.

7 CPA Residential Re-roof Inspection Page 7 of 9 Vent and chimney termination Paint all ABS/Plastic vent pipes. IAPMO Installation standards section Heat producing double wall type B vents shall maintain a min. 1 clearance to combustibles and terminate with a listed vent cap. CPC 510.6, Chimney(s) terminations must be 2 above any roof/structure within 10 and not less than 3 above the highest point were the chimney passes through the roof. See figure CMC Dryer back-draft damper shall be approved/listed for horizontal/rooftop termination (no screens). CMC Gas appliance vents 12 or smaller shall terminate a min. of 12 above any portion of a building within 10 horizontally when 6:12 or flatter, see CMC Figure 8-2 for vents larger than 12. Vents within 8 of a wall shall terminate a min. of 2 above the wall s roof edge. Exception: Direct-Vent CMC , Waste vents shall terminate vertically not less than 6 above roof, nor less than 1 from any vertical surface and 10 from or 3 above any opening such as windows, doors, air intake, nor less than 3 from any lot line. Side wall vent may not terminate under vented soffit. CPC 906.1, 2 Roof top equipment See Roof Top Equipment guidelines on checklist Remove abandoned equipment above rooftops. Existing mechanical equipment at roof shall be seismically secured per CMC See HVAC checklist for all requirements. All existing piping systems disturbed by re-roofing shall be reinstalled to comply with applicable codes. SEE [FIGURE A-1] Frequently Missed/Inspection Failure Equipment deck and cap flashing drainage: All equipment sheet metal deck/caps/lids and cap flashing shall have a min. ¼ per foot slope. FIX: Apply a two part epoxy system roof coating or snow roof system. CMC , Electrical Electrical wiring systems under roofing materials shall have physical protection from nails such as angle iron or rigid metal conduit. MC, AC, romex cable or flex are not suitable unless protected. Gas piping CPC Gas test: Provide gas test as applicable when gas pipe is altered/changed. See Whole House Gas Test checklist for test requirements. When gas piping is required to be concealed/encapsulated in roof assembly (not recommended) provide base vent flashing at all gas connections i.e. elbows, tees etc. Roof drains Existing flat roof decks shall have positive slope to move surface water to roof drains (preventing water ponding). CBC exception

8 CPA Residential Re-roof Inspection Page 8 of 9 Min. ¼ per foot slope to drain. CBC Roof drains that run through the interior of the building shall be in plumbing pipe. Primary drain(s) shall be sized per CPC Table 11-1 at the 2 inch per hour rate. Secondary drain(s) shall be the same size as the primary drain with the inlet flow line 2 above the low point of the roof and shall be an independent system OR overflow scupper(s) shall be installed with the inlet flow line located 2 above the low point of the roof and the scupper opening a min. of 4 high and have a width equal to the circumference of the primary drain. Overflow drains shall not be connected to the primary drain. CPC ,2 Strainer(s) for flat deck primary drain(s) shall be level with the deck with the inlet area not less than 2 times the area of the drain pipe. CPC Strainer(s) for all flat roof secondary drain(s) shall be a min. of 4 above with the inlet area not less than 1-1/2 times the size of the inlet pipe. CPC FIGURE A-1 WILDLAND URBAN INTERFACE WEST OF 280 Roof covering for all new buildings shall be fire-retardant minimum class A. Re-Roofing of existing structure where more than 50% of the total roof area is replaced, the entire roof covering shall be a fire-retardant roof covering that is at least Class A PMCA Valley flashing: Minimum 26 gage galvanized sheet metal installed over a min. 36 wide No. 72 cap sheet running full length of valley. CBC 704.A.1.3 Fire-stopped/birdstop with approved materials, where roof profile allows a space between roof covering and deck to prevent the intrusion of flames and embers. OR have one layer of No. 72 ASTM cap sheet installed over the combustible decking. CBC 704A.1.2 Attic ventilation: Roof surface vents shall resist the intrusion of flame and embers into attic, or shall be protected with corrosion resistant, non combustible wire mesh with ¼ openings. CBC 704A.2.1 Gutters and Downspouts shall be constructed with non-combustible materials and shall be installed with means to prevent debris from accumulating such as screens. CBC 704A.1

9 CPA Residential Re-roof Inspection Page 9 of 9 Information on specific roofing types are available in the CPA Roofing Guidelines Manual at Development Center counter and Building Division web page. Roof overlay Metal roof Single ply membranes roof (TPO) Spray applied roof Tar and gravel roof Clay and concrete tile roof

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Detached accessory structures that contain no conditioned floor area are exempt.

Detached accessory structures that contain no conditioned floor area are exempt. RESIDENTIAL ROOFING PERMITS: A roofing permit is required for roofing of residential dwellings and garages in accordance with Section R105 of the International Residential Code. Updated 11/2013 City of

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

Dollars & Sense of Compliance!

Dollars & Sense of Compliance! CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors

More information

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing

More information

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

If you are a web registered user of ArlingontPermits.com you may also request an inspection at:

If you are a web registered user of ArlingontPermits.com you may also request an inspection at: TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors

More information

HCD DSA OSHPD 1 2 1/AC AC SS 1 2 3 4

HCD DSA OSHPD 1 2 1/AC AC SS 1 2 3 4 CALIFORNIA RESIDENTIAL CODE MATRIX ADOPTION TABLE CHAPTER 9 ROOF ASSEMBLIES (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and

More information

ROOF ASSEMBLIES CHAPTER 9

ROOF ASSEMBLIES CHAPTER 9 CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION

More information

RB271 06/07 R807.1 RB272 06/07 R807.1. Public Hearing: Committee: AS AM D Assembly: ASF AMF DF. Proponent: Rick Davidson, City of Hopkins, MN

RB271 06/07 R807.1 RB272 06/07 R807.1. Public Hearing: Committee: AS AM D Assembly: ASF AMF DF. Proponent: Rick Davidson, City of Hopkins, MN 3. The use of asphalt shingles and other roof coverings has been successful over these composite insulation panels, so the extra details about vapor retarders, etc. can be eliminated. RB271 06/07 R807.1

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and

More information

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and

More information

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes

More information

ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof

ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof ROOF CONSTRUCTION The overall appearance of a building is greatly affected by the roof lines and the roofing materials. The designer has many standard designs to choose from and should be able to find

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING

More information

ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof

ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof ROOF CONSTRUCTION The overall appearance of a building is greatly affected by the roof lines and the roofing materials. The designer has many standard designs to choose from and should be able to find

More information

Shingle Installation Guide

Shingle Installation Guide Shingle Installation Guide Getting Started Dedicated to improving the environment, NewTech manufactures roofing tiles that are composed of up to 90% recycled post-industrial plastic. The manufacture of

More information

NRCA s steep-slope manual is thoroughly revised for 2013

NRCA s steep-slope manual is thoroughly revised for 2013 Photo courtesy of Boone Brothers Roofing, Omaha, Neb. NRCA s steep-slope manual is thoroughly revised for 2013 by Maciek Rupar 38 www.professionalroofing.net MARCH 2013 P ublished in January, The NRCA

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and

More information

Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..

Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers.. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and

More information

Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010

Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Custom bid generated for: Job site address: Lake Villas Condominium Attention:

More information

Solar Panel Installations

Solar Panel Installations Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and

More information

C. Remove all existing asphalt shingles, underlayment and any loose debris into contractor provided dumpsters.

C. Remove all existing asphalt shingles, underlayment and any loose debris into contractor provided dumpsters. SCOPE OF WORK Project Title: Replace Deteriorated Roof Singles at Cape Lookout National Seashore Maintenance Shop PMIS # 159350 Prepared By: Mike Baker Cape Lookout National Seashore 131Charles St Harkers

More information

Pre-Drywall Inspection Report

Pre-Drywall Inspection Report SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion

More information

CPA Steel Stud Framing Page 1 of 11

CPA Steel Stud Framing Page 1 of 11 CPA Steel Stud Framing Page 1 of 11 STEEL STUD FRAMING General Requirements City of Palo Alto (CPA) Building Inspection Division 285 Hamilton Ave. Inspection Request: 650 329-2496 Building Division IVR#

More information

Mark Cramer Inspection Services, Inc.

Mark Cramer Inspection Services, Inc. Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction

More information

ROOF INSPECTION REPORT

ROOF INSPECTION REPORT ROOF INSPECTION REPORT Date: October 9, 2012 Requesting Firm: FIRST CHOICE INSPECTIONS Santiago Salazar Address: 447 Chilberg Court, San Jose, CA 95133 Phone #: 408-771-7563 Roof Inspected At: 1465 Gerlach

More information

How To Plan Out An Array Of Solar Panels

How To Plan Out An Array Of Solar Panels CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013

More information

CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION

CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION IF SUBSIDIARY, PROVIDE MASTER PERMIT NUMBER HERE: CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION Location of Improvements

More information

Preventing Ice Dams on Roofs

Preventing Ice Dams on Roofs Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the

More information

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in one year.

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in one year. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-900* Reissued March, 20 This report is subject to renewal in one year. A Subsidiary of the International Code Council DIVISION:

More information

Chapter 9: INSTALLING ROOFING

Chapter 9: INSTALLING ROOFING 9.1 LEAK BARRIER (ICE AND WATER SHIELD) 9.2 SHINGLE UNDERLAYMENT 9.3 INSTALLING GUTTER APRON AND GABLE D-EDGE 9.4 INSTALLING SHINGLES 9.5 RIDGE VENT AND CAP Tools needed by each volunteer: Hammer (16 oz.

More information

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It

More information

Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions

Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions Discount Direct Metal Roofing Plus Rib Roofing Panels Installation Instructions All questions and concerns please call 904-696-9700 Discount Direct Metal Roofing Plus Rib metal roofing panels are a strong,

More information

HERITAGE WOODGATE LAMINATED ASPHALT SHINGLES Dallas, TX

HERITAGE WOODGATE LAMINATED ASPHALT SHINGLES Dallas, TX Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING

More information

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36.

Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36. Demolition/Removal of Work 4-ply built up roofing to the insulation (smooth cap sheet) Smooth cap sheet - 0-10 SQ $ 63.00 Smooth cap sheet - 11-50 SQ $ 63.00 Smooth cap sheet - 51-100 SQ $ 35.00 Smooth

More information

780 CMR 15.00 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

780 CMR 15.00 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 780 CMR 15.00 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 780 CMR 1501.0 GENERAL 1501.1 Scope. The provisions of 780 CMR 15.00 shall govern the design, materials, construction and quality of roof assemblies,

More information

16 2 10.3 Materials and Colors

16 2 10.3 Materials and Colors 16 2 10.3 Materials and Colors To create a harmonious and coherent image for each development, building designs shall pay close attention to choice of materials and colors. Building construction shall

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER:

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER: 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1900 Reissued 03/2016 This report is subject to renewal 03/2017. DIVISION: 07 00 00 THERMAL

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck. SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied

More information

Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS

Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings

More information

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,

More information

The Florida Building Code

The Florida Building Code The Florida Building Code Florida s Response to Hurricane Risk Rick Dixon Florida Building Commission Florida Building Commission Architect Structural Engineer Mechanical Engineer Fire Protection Engineer

More information

KITCHEN HOODS GUIDELINES

KITCHEN HOODS GUIDELINES KITCHEN HOODS GUIDELINES City of Palo Alto Building Inspection Division 285 Hamilton Ave. Inspection Request: 650 329-2496 Revision Date:6/27/12 General Requirements/Checklist for: Commercial Codes Enforced:

More information

TARRANT COUNTY DETAIL STANDARDS

TARRANT COUNTY DETAIL STANDARDS TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout

More information

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,

More information

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional

More information

EcoTouch Insulation with PureFiber Technology

EcoTouch Insulation with PureFiber Technology PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016 Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.

More information

SHINGLE APPLICATION GUIDE

SHINGLE APPLICATION GUIDE SHINGLE APPLICATION GUIDE CONTENTS 01. General conditions 01. Material requirements 02. Terms 07. Estimating shingle requirements 08. Roof preparation 10.Shingle application E version 2006 GENERAL CONDITIONS

More information

Multi-Width Shake. Widths: 9", 8", 7", 6", 4" Length: 22" Thickness at butt: 5/8" Single-Width Shake. Widths: 9" Length: 22" Thickness at butt: 5/8"

Multi-Width Shake. Widths: 9, 8, 7, 6, 4 Length: 22 Thickness at butt: 5/8 Single-Width Shake. Widths: 9 Length: 22 Thickness at butt: 5/8 N DaVinci Shake Multi-Width Shake Single-Width Shake INSTALLATION GUIDE DaVinci polymer shakes are carefully engineered to provide the authentic look of hand-split shakes with dramatically increased durability

More information

CertainTeed. Protecting Your Home From Ice Dams Homeowner s Guide

CertainTeed. Protecting Your Home From Ice Dams Homeowner s Guide CertainTeed Protecting Your Home From Ice Dams Homeowner s Guide What Are Ice Dams? Ice dams are formed when heat from the inside of a home escapes into the attic and warms the roof decking during the

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the

More information

Directions For Applying Malarkey Laminate Shingles

Directions For Applying Malarkey Laminate Shingles S Laminate Shingle Instructions 1 Directions For Applying Malarkey Laminate Shingles GENERAL INSTRUCTIONS Install Malarkey laminate shingles according to building code and local amendments. To qualify

More information

Classic Products, Inc. ClickLock Standing Seam Installation Manual

Classic Products, Inc. ClickLock Standing Seam Installation Manual Classic Products, Inc. ClickLock Standing Seam Installation Manual Classic Products, Inc. 8510 Industry Park Drive Piqua, OH 45356 800.543.8938 Table of Contents page Introduction 1. 1 Starter. 2. 1 Panels.

More information

INSTALLATION MANUAL For Grand Rib-3 / Multi Purpose / & Classic Rib Roofing Panels

INSTALLATION MANUAL For Grand Rib-3 / Multi Purpose / & Classic Rib Roofing Panels INSTALLATION MANUAL For Grand Rib-3 / Multi Purpose / & Classic Rib Roofing Panels Grand Rib-3 / Multi-Purpose / Classic Rib Grand Rib-3 / Multi-Purpose / & Classic Rib Grand Rib 3 panels are a strong,

More information

Low-slope reroofing guidelines

Low-slope reroofing guidelines Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof! Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing

More information

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER

Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Department of Advanced Education and Skills Apprenticeship and Trades Certification Division Record of Work Experiences Trade Qualifier or Pre-Apprenticeship Credits ROOFER Note to Apprenticeship Applicants

More information

Total Home Inspection Checklist

Total Home Inspection Checklist Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work.

Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work. Installation Guide Before you begin, take the time to read this entire guide to clearly understand the requirements and steps to follow for proper installation. Warning Do not install defective material.

More information

G VYCOR DECK PROTECTOR

G VYCOR DECK PROTECTOR G VYCOR DECK PROTECTOR Self-Adhered Flashing Contractor s Guide DECKS AND DETAIL AREAS For longer lasting decks, install Grace Vycor Deck Protector. FROM THE MAKERS OF G Ice & Water Shield What Self-Adhered

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC 0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND

More information

application instructions

application instructions application instructions ARCHITECTURAL COLLECTION PRIMED BOLD PROFILE 120 SERIES LAP SIDING (D5, T4, D8, T5, Q4) General At the time of manufacture, siding meets or exceeds the performance standards set

More information

Proper roof slope and drainage are important to prevent excessive water accumulation

Proper roof slope and drainage are important to prevent excessive water accumulation Proper roof slope and drainage are important to prevent excessive water accumulation by Jason P. Wilen, AIA, CDT, RRO P onding water sometimes occurs on membrane roof systems as a result of snow, rainfall

More information

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL Boiler Manual A. INSTALLING EXHAUST VENT AND INTAKE AIR VENT B. GENERAL n DANGER The Elite Heating Boiler must be vented as detailed in this section.

More information

Home Inspection Report

Home Inspection Report 4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:

More information

University of California - Santa Barbara West Campus Point Faculty Housing

University of California - Santa Barbara West Campus Point Faculty Housing University of California - Santa Barbara West Campus Point Faculty Housing Reconstruction Guidelines and Considerations to Correct Exterior Building Envelope Weatherproofing Defects and Recommended Upgrades

More information

GUIDE SPECIFICATION. Manufacturer: DECRA Roofing Systems, Inc.

GUIDE SPECIFICATION. Manufacturer: DECRA Roofing Systems, Inc. GUIDE SPECIFICATION Manufacturer: DECRA Roofing Systems A Fletcher Building Company 1230 Railroad Street Corona, CA 92882 951-272-8180 phone 951-272-4476 facsimile www.decra.com SECTION 07314 [07 31 14]

More information

BUSI 441 Project 1: Reserve Fund Study

BUSI 441 Project 1: Reserve Fund Study BUSI 441 Project 1: Reserve Fund Study Estimating Roofing Replacement Cost In Project 1, Part One, section (b) you are instructed to identify the roofing type and area for your subject building. The section

More information

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs. Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12

More information

Shingle Roofing: What s below the surface is important

Shingle Roofing: What s below the surface is important What s below the surface is important The roof is leaking, the shingles look old, and the downspouts are dripping. It must be time to replace the roof or is it? Shingle roofs may seem simple, but a roof

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

CHIMNEYS AND FIREPLACES

CHIMNEYS AND FIREPLACES CHAPTER 10 CHIMNEYS AND FIREPLACES > > Pursuant to ORS 215.730, if a single-family dwelling located on forest-zoned lands has a chimney or chimneys, each chimney shall have a spark arrester. SECTION R1001

More information

Delaney-Vogel School

Delaney-Vogel School Wrentham Public Schools Delaney-Vogel School Schematic Design 1. INTRODUCTION Wrentham Public Schools contracted with Turowski2 Architecture, Inc. on November 11, 2015 to assess necessary roof repairs

More information

Commercial Roof Inspection Form

Commercial Roof Inspection Form Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building

More information

GreenGuard Housewrap Installation Guide

GreenGuard Housewrap Installation Guide 000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be

More information

IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT

IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT WHAT IS THE RATIONALE BEHIND THE REQUIREMENTS FOR IGNITION RESISTANT CONSTRUCTION? The wildfires of 2003 and 2007 were the largest in California

More information

SECTION 07 61 13 STANDING SEAM METAL ROOFING

SECTION 07 61 13 STANDING SEAM METAL ROOFING SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced

More information

CONTENTS. General conditions 2. Material requirements 3. Terms 4. Estimating shingle requirements 4. Roof preparation 6. Shingle application 9 - 1 -

CONTENTS. General conditions 2. Material requirements 3. Terms 4. Estimating shingle requirements 4. Roof preparation 6. Shingle application 9 - 1 - CONTENTS General conditions Material requirements 3 Terms 4 Estimating shingle requirements 4 Roof preparation 6 Shingle application 9 Shingle Shingle application application guide guide - - b a 3a 3b

More information

Rehab Inspection Report Page 1

Rehab Inspection Report Page 1 Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation

More information

Additions and Alterations

Additions and Alterations Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal

More information

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC

More information