Integrated Cabinets and Thermal Systems May 15, 2014 Panduit Korea Technical System Engineer Chester Ki
|
|
- Sybil Wilkins
- 7 years ago
- Views:
Transcription
1 1 Integrated Cabinets and Thermal Systems May 15, 2014 Panduit Korea Technical System Engineer Chester Ki 4/10/2014
2 2 Agenda Market Trends Thermal Architectures Data Centre Cabinet Systems Net-Access Cabinet Net-SERV Server Cabinet Vertical Exhaust System Net-Contain Roadmap
3 3 Integrated Cabinet Overview The Integrated Cabinets Offering: Provides high level value to Panduit s integrated data centre strategy Facilitates the progression of offering passive components to fully integrated data centres Provides solutions and consultative services that support consolidation, virtualization, and environmental stewardship initiatives in the data centre. Reduces OpEx and risks to physical infrastructure availability while enabling agility today and in the future.
4 4 Top of Mind Issues Customers face challenges to: Effectively providing thermal management to ensure proper equipment operation and uptime Enabling scalability for data centre expansions and network upgrades Manage, protect and showcase cabling and equipment Allowing open-rack accessibility with the aesthetics and security of a cabinet Ensure correct cable bend radius resulting in greater network availability
5 5 Relevant Customer Business Trends Business Trends Include: Increasing power costs Government regulated power usage Increased pressure to reduce OPEX & CAPEX Speed to market Trends Within the Data Centre Include: Rise in the energy consumption curve Collapsing layers and network aggregation switches Rise in data centre construction cost Condensed implementation timelines Virtualization/consolidation Denser environments Higher bandwidth requirements
6 6 Equipment Heat Density Trends - ASHRAE Chart 2005 ASHRAE, Datacom Equipment Power Trends and Cooling Applications, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.,
7 Thermal Architectures
8 8 Types of Thermal Architecture Data Centre Thermal Architectures Include: Cooling Conservation Room, Row, and Rack Based Cooling (Hot Aisle/Cold Aisle) Over Row/Cabinet Cooling Hot Air Containment/Vertical Exhaust System (VES) Cold Aisle / Hot Aisle Containment
9 Cooling Conservation 9
10 Room, Row, and Rack Based Cooling Architectures 10
11 Room Cooling Architecture Hot Aisle/Cold Aisle 11
12 Thermal Analysis Results Standard Cabinets Without VED 12 Without exhaust duct, hot air re-circulates to the front of the cabinet heating the top 12 RU Above Ceiling Hot Air Return Plenum Cold Aisle Hot Aisle Under Floor Plenum Cold Aisle Hot Aisle Cold Aisle
13 Row Cooling Architecture Over-Row/Cabinet Cooling System 13
14 14 Room Cooling Architecture Hot Air Containment (Vertical Exhaust System) Based on ASHRAE Thermal Guidelines for Data Centre Processing Environments
15 15 Thermal Analysis Results Vertical Exhaust Duct Exhaust duct sends hot air to return plenum Uniform cold air available to server inlets Above Ceiling Hot Air Return Plenum Highest possible return air temperature to CRAC units for maximum cooling efficiency Cold Aisle Traditional Hot Aisle Under Floor Plenum Cold Aisle Traditional Hot Aisle Cold Aisle
16 Cold Aisle/Hot Aisle Containment 16
17 17 Summary and Analysis of Thermal Management Strategies A review and analysis suggests the following conclusions: Rack-oriented architecture is the: Most flexible Fastest to implement Achieves extreme density (additional expense) Room-oriented architecture is: Less flexible Time consuming to implement Less versatile at higher density, but has cost and simplicity advantages at lower density Row-oriented architecture provides: Flexibility, speed, and density advantages of the rack-oriented approach Cost similar to the room-oriented architecture
18 Data Centre Cabinet Systems
19 19 Net-Access Switch/Server Cabinet Overview Net-Access Switch /Server Cabinet features include: In-cabinet ducting solutions to enable optimized airflow of switches Large vertical pathways for high cable count applications Cable and thermal management are scalable to address future higher density applications Dual hinge door for maximum accessibility between adjacent cabinets StructuredGround Grounding System
20 20 Thermal Management Switch Cabinet The Switch Cabinet Thermal Management System: Uses ducting to adapt side-to-side airflow switches to hot aisle /cold aisle data centre layout Tested compatible with Cisco series switches Directs exhaust air to hot aisle Matches thermal performance of network switches in cabinets with ducting equal to open frame Utilizes front and rear perforated doors designed to maximize airflow Incorporates ventilation designs optimized with input from Cisco thermal engineers
21 21 Front View - Cut Through Centre of 6509 Switches No Ducts Alternate Racks Ducted
22 22 Net-Access Server Cabinet Overview Net-Access Server Cabinet features and options include: Same platform as switch cabinet to enable maximum flexibility and deployment options Vertical exhaust duct for optimal thermal performance Maximum cable management area and thermal performance Vertical patch panel configuration provides up to eight additional rack units in the same footprint
23 23 Thermal and Superior Cable Management Server Cabinet Server Cabinet Thermal Management System Key Features Include: Superior management of cables allows server fans to more efficiently exhaust air from cabinet Vertical and horizontal blanking panels direct intake air to servers and prevent cold air bypass
24 Net-SERV Server Cabinet
25 25 Net-SERV Server Cabinet Overview Net-SERV Server Cabinet features and options include: High density data and power cables are organized in segregated channels away from server exhaust for unobstructed air flow POU mounting brackets accommodate a wide range of server applications Variety of cabinet widths Multiple openings in top with fittings and sealing system Electrically bonded for single point ground Vertical patch panels maximize rack space utilization for additional servers and other devices
26 Net-Access and Net-SERV Vertical Exhaust System
27 27 Vertical Exhaust System For Maximum Energy Efficiency The Vertical Exhaust System: Removes heated air without additional moving parts through a passive system Channels heat from cabinet directly to the above ceiling return plenum increasing cooling efficiency Enables increased server densities by preventing hot and cold air mixing and eliminating hot spots Dampens noise in data centre Can be applied as modular system at initial installation or added when required as heat densities increase
28 28 Primary Application Deployed On All Heat Generating Cabinets Above Ceiling Hot Air Return Plenum Vertical Exhaust Duct Vertical Exhaust Duct Cooling Air Directed to Entire Room Cooling Air Directed to Entire Room Slab Floor * Vertical Exhaust System is also compatible with raised floor cooling systems
29 Alternate Implementation Deployed Only On Highest Heat Generating Cabinets 29 Above Ceiling Hot Air Return Plenum Vertical Exhaust Duct Raised Floor
30 30 Net-Contain Cold Aisle Containment (CAC) System The CAC System: Isolates the cold supply air from the hot equipment exhaust Prevents hot air recirculation Reduces cooling system operational costs Modular Containment System Allows: Mixing of Net-Access and Net-SERV 45RU cabinets A mix of cabinet sizes 32 (800mm) Allows End of Row switch and storage architectures Net-Access Net-SERV
31 Net-Contain Cold Aisle Containment System 31 Vertical panel mounted to the cabinet Cross aisle tee beam Clear polycarbonate ceiling panels Fire suppression/detection cross bracket Cabinet Cabinet End of row doors
32 32 Net-Contain Cold Aisle Containment System Airflow Comparison : Cold Aisle Containment versus Hot Aisle/Cold Aisle Cold Aisle Containment Hot Aisle/Cold Aisle Deployment Drop ceiling return plenum CRA C Unit CRA C Unit Raised floor air delivery
33 33 Net-Contain Cold Aisle Containment System Computational Fluid Dynamics Analysis: Hot Aisle/Cold Aisle Hot air re-circulates over top of cabinets and at the end of rows to IT equipment inlets Under Floor Plenum Cold Aisle Hot Aisle Cold Aisle
34 Net-Contain Cold Aisle Containment System Airflow Comparison: Cold Aisle Containment versus Hot Aisle/Cold Aisle 34 Cold Aisle Containment Drop ceiling Hot Air Return Plenum CRA C Unit CRA C Unit Raised floor air delivery
35 35 Net-Contain Cold Aisle Containment System Computational Fluid Dynamics Analysis: Cold Aisle Containment Complete separation of hot and cold air to provide uniform temperature for IT equipment inlets Under Floor Plenum Cold Aisle Traditional Hot Aisle Cold Aisle
36 36 Net-Contain Cold Aisle Containment System Benefits Net-Contain Optimizes Airflow Distribution by: Preventing the mixing of cold and hot air streams Eliminating recirculation of hot air to cabinet inlets Providing uniform temperature at the inlets of IT equipment Preventing cold air bypass Net-Contain Improves Cooling System Thermal Performance by: Raising the supply air set point temperature Providing higher return air temperature increases to utilize the thermal capacity of cooling units Closely matching supply cooling airflow to IT equipment airflow 25% or more Cooling Energy Savings comes from: Fan Power Savings by reducing CRAH/CRAC fan speeds Chiller energy savings by raising the chiller water set point temperature Pump energy savings by reducing its throughput Increased hours of economizer usage Use of less number of cooling units
37 Increasing Heat Densities Cabinet System Overview Thermal Capacity Roadmap 37 0 kw Medium to High-Density Server Applications Low to Medium- Density Server Applications Switch Applications 10 kw PANDUIT Net-Access Switch Cabinets High-Density Server Applications 15 kw+ PANDUIT Net-Access Server Cabinets PANDUIT Scalable Cabinet Solution 30 kw+ PANDUIT Server Cabinet Vertical Exhaust System PANDUIT Net-Contain Cold Aisle Containment System
38 Questions
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationSupporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products
More informationUnified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
More informationManaging Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationData center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
More informationData Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
More informationUnified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
More informationEducation Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
More informationGUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
More informationAPC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
More informationOptimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
More informationADC-APC Integrated Cisco Data Center Solutions
Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the
More informationBenefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
More informationAPC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationEnergy-efficient & scalable data center infrastructure design
Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable
More informationData Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
More informationData Center Equipment Power Trends
Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data
More informationHot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
More information2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms
Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms Agenda Review of cooling challenge and strategies Solutions to deal with wiring closet cooling Opportunity and value Power
More informationThe New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
More informationOCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers
Layer Zero, the Infrastructure Layer, and The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds
More informationGreat Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
More informationSealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential
TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com
More informationCreating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that
More informationAirflow Management Solutions
Data Center Products Airflow Management Solutions Switch N to Eaton. Computational Fluid Dynamics (CFD) model of an optimized data center illustrating cold-aisle isolation and Eaton s Heat Containment
More informationGREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
More informationIMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
More informationColocation and Cloud Hosting Solutions. Build a strong and efficient physical infrastructure that delivers service reliability and profitability
Colocation and Cloud Hosting Solutions Build a strong and efficient physical infrastructure that delivers service reliability and profitability 2 Dependability and Deployment Speed that Improves Your Bottom
More informationLiquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
More informationLayer Zero. for the data center
Layer Zero for the data center Preparefor the Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,
More informationBRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
More informationSelecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers
C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published
More informationIntelligent Data Centers: Delivering Business Value. May 15, 2014 Panduit Korea Technical System Engineer Chester Ki
Intelligent Data Centers: Delivering Business Value May 15, 2014 Panduit Korea Technical System Engineer Chester Ki 4/10/2014 Core Business Panduit is a world-class developer and provider of leading-edge
More informationHow To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
More informationRack Hygiene. Data Center White Paper. Executive Summary
Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
More informationChoosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
More informationHow Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that
More informationData Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
More informationElements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
More informationHow To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
More informationCenter Thermal Management Can Live Together
Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots
More informationSMARTPLAY7. Increase your Deal Size and Profitability with SmartPlays
SMARTPLAY7 Increase your Deal Size and Profitability with SmartPlays - Comstor and Panduit have joined forces to promote the power and flexibility of UCS combined with market leading energy efficient enclosures.
More informationDriving Data Center Efficiency Through the Adoption of Best Practices
Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary
More informationImproving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures
More informationAir, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360
Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy
More informationAirflow Management Solutions
Data Center Products Airflow Management Solutions Switch N to Eaton. Computational Fluid Dynamics (CFD) model of an optimized data center illustrating cold-aisle isolation and Eaton s Heat Containment
More informationThermal Optimisation in the Data Centre
Thermal Optimisation in the Data Centre Best Practices for achieving optimal cooling performance and significant energy savings in your data centre 1. Thermal analysis 2. Cold-Aisle-Containment 3. Seal
More informationEnclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
More informationIn Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
More informationProduct Brochure. Airflow Management Solutions
Product Brochure Airflow Management Solutions Computational Fluid Dynamics (CFD) model of an optimized data center illustrating cold-aisle isolation and Eaton s Heat Containment System (HCS). See CFD Services
More informationData Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
More informationData Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
More informationCANNON T4 MINI / MICRO DATA CENTRE SYSTEMS
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly
More informationSmall Data / Telecommunications Room on Slab Floor
Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationHigh Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
More informationHow To Power And Cool A Data Center
Architecting the Green Data Center Viktor Hagen Field Business Development Data Center & High Performance Computing 1 Where we are Today Environmental sustainability is a major global trend for the 21st
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More informationAirflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
More informationContainment Solutions
Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationEnergy Efficient Data Center Cabinet Systems
Net-Access Cabinet has tested compatible with Cisco Nexus 708, MDS 95, and Catalyst 6509. Go to www.panduit.com/cisco for disclaimer. Energy Efficient Data Center Cabinet Systems Enhance Reliability. Overcome
More informationImproving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures
More informationCooling Audit for Identifying Potential Cooling Problems in Data Centers
Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationLayer Zero. for the data center
Layer Zero for the data center PREPAREFOR THE Data centers are the foundations of enterprises, vital to the daily operation of the entire organization - they no longer simply store data. Virtualization,
More informationEnergy Performance Optimization of Server Room HVAC System
International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department
More informationTen Steps to Solving Cooling Problems Caused by High- Density Server Deployment
Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.
More informationSpecialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationWHITE PAPER. Creating the Green Data Center. Simple Measures to Reduce Energy Consumption
WHITE PAPER Creating the Green Data Center Simple Measures to Reduce Energy Consumption Introduction Energy Awareness Driving Decisions in the DataCenter The continued thirst for energy is a recurring
More informationOptimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
More informationData Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015
Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and
More informationPower and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
More informationEnvironmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
More informationSERVER ROOM CABINET INSTALLATION CONCEPTS
SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS ZPAS 169 EXAMPLES OF SERVER ROOMS PROJECTS WITH ZPAS CABINETS Data Box in the
More informationGreen Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs Topics The Why? The How? Conclusion The Why? Drivers for Green IT According to Forrester Research, IT accounts
More informationEuropean Code of Conduct for Data Centre. Presentation of the Awards 2013
European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started
More informationQUALITATIVE ANALYSIS OF COOLING ARCHITECTURES FOR DATA CENTERS
WHITE PAPER #30 QUALITATIVE ANALYSIS OF COOLING ARCHITECTURES FOR DATA CENTERS EDITOR: Bob Blough, Emerson Network Power CONTRIBUTORS: John Bean, APC by Schneider Electric Robb Jones, Chatsworth Products
More informationReducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs
WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level
More informationIntroducing Computational Fluid Dynamics Virtual Facility 6SigmaDC
IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: info@itisltd.co.uk www.itisltd.com Introducing Computational
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationEnergy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
More informationData Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
More informationBlade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity
Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face
More informationHow To Cool A Data Center
Overview and Design of Data Center Cabinets In today s technology-dependent world, a reliably operating data center is a core necessity for small and large businesses alike. Without properly running network
More informationHIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE
HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365
More informationDataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
More informationAnixter ipassured SM for Data Centres. Products. Technology. Services. Delivered Globally.
Anixter ipassured SM for Data Centres Products. Technology. Services. Delivered Globally. Anixter is a leading global supplier of communications and security products, electrical and electronic wire and
More informationData Center Racks. Vantage S2. Enclosure System. Switch N to Eaton.
Data Center Racks Vantage S2 Enclosure System Switch N to Eaton. The Lean Data Center Data center managers are constantly moving, adding and changing IT equipment and electrical circuits all while trying
More informationOverview & Design of Data Center Cabinets
Overview & Design of Data Center Cabinets Power & Cooling Overview pg. 3 Enclosure Overview & Discussion pg. 9 Cabinet Configurations pg. 14 Best Practices pg. 28 2 2 2 2 OVERVIEW & DESIGN OF In today
More informationCOMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION
COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION 1/16 Contents: 1. Introduction: the increasing importance of energy efficiency 1.1 Power consumers in the data
More informationServer Room Thermal Assessment
PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...
More informationReducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
More information