1 TeSys Vacuum Contactors June 2002 Building a New Electric World

2 Selection guide, characteristics Contactors 5 Selection guide Contactor size LC1-V160 LC1-V320 LC1-V610 For utilisation category AC-3 Maximum operational current in AC-3 A V kw V kw (standard power ratings 525 V kw of motors) 690 V kw V kw V kw For 3-phase motors conforming to CSA standards 200 V hp V hp (standard power ratings of 380 V hp phase CSA motors) 480 V hp V hp V hp V hp V hp For switching 3-phase capacitors 240 V kvar V kvar V kvar V kvar For switching the primaries of 3-phase transformers (LV/LV) Environment characteristics 208 V kva V kva V kva V kva Type LC1-V160 LC1-V320 LC1-V610 Shock resistance (1/2 sine wave = 11 ms) Contacts closed 10 gn 10 gn 10 gn Contacts open 10 gn 10 gn 10 gn Vibration resistance Hz 2 gn 2 gn 2 gn Operating altitude Above sea level Maximum m Below sea level Minimum m Ambient air temperature around the device Storage C For operation C at Uc Permissible for operation at Uc C Degree of protection Conforming to IEC 529 IP 00 IP 00 IP 00 Operating position Any Any Any Cabling Cable c.s.a. mm x 185 Key for hex. screws mm Allen Tightening torque N.m Control circuit characteristics Rated insulation voltage (Ui) To earth V Consumption Inrush VA Sealed VA Permissible control circuit voltage Uc Uc Uc 1

3 Characteristics (continued) Contactors 5 Type LC1-V160 LC1-V320 LC1-V610 Main pole characteristics Rated insulation voltage (Ui) V Rated impulse withstand voltage (Uimp) kv Conformity to standards EN IEC Approvals CSA Conventional thermal current (Ith) A voltage (Ie) y 40 C AC-1 A y 55 C AC-3 A y 55 C AC-4 A Electrical durability in number of operating cycles AC AC AC Mechanical durability In millions of operating cycles Maximum operating rate in operating cycles per hour Maximum making capacity (Irms) Maximum breaking capacity (Irms) Permissible short time rating Mechanical AC AC AC Ue = 1500 V To IEC 947 A Ue = 1500 V To IEC 947 A For 1 s A For 2 s A For 10 s A For 30 s A Short-circuit protection at le in cat. AC-3 max Auxiliary contact characteristics am fuse A Rated insulation voltage (Ui) V 690 Conventional thermal current (Ith) A 10 voltage (Ie) AC-15, 230 V A 0.78 AC-15, 400 V A 0.45 AC-15, 500 V A 0.35 DC-13, 24 V A 1.1 DC-13, 110 V A 0.24 DC-13, 220 V A 0.12 Cabling Cable c.s.a. mm Short-circuit protection Operating time (1) (at 100 % of Uc) gg fuse A 10 Closing C ms ± 5 Opening O ms ± 5 (1) The closing time C is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time O is measured from the moment the coil supply is switched off to the moment the main poles separate. 2

4 References Contactors 5 Power and control circuits a.c. supply Vacuum contactors Standard power ratings 50/60 Hz in category AC-3 Rated operational voltage Ie Instantaneous auxiliary contacts Basic reference. Complete with code indicating control circuit voltage (2) Weight 230 V 400 V 525 V 690 V 1000 V AC-3 AC-1 kw kw kw kw kw A A kg LC1-V160pp LC1-V LC1-V320pp LC1-V610pp Instantaneous auxiliary contact blocks (1) Number of contacts Maximum number of blocks per contactor Auxiliary contacts Reference Weight kg LA1-VN LA1-VN LA1-VN LA1-VN Accessories For assembling reversing contactors Description For use Reference Weight on kg Kit comprising : - 1 mechanical interlock. - 1 set of power connections. LC1-V160 LA9-V LC1-V320 LA9-V LA9-V975 LX1-V320pp Coils Rated voltage Voltage code Reference Weight V kg For contactors LC1-V FE7 LX1-V160FE P7 LX1-V160P V7 LX1-V160V R7 LX1-V160R X7 LX1-V160X For contactors LC1-V FE7 LX1-V320FE P7 LX1-V320P V7 LX1-V320V R7 LX1-V320R X7 LX1-V320X For contactors LC1-V FE7 LX1-V610FE P7 LX1-V610P V7 LX1-V610V R7 LX1-V610R X7 LX1-V610X (1) LC1-V160: auxiliary contact blocks mounted at the top of the contactor, with no change to the overall dimensions. LC1-V320 or LC1-V610: 2 auxiliary contact blocks mounted on the RH and LH side of the contactor, with no change to the overall dimensions.. ((2) Standard control circuit voltages. Volts 50/60 Hz Code FE7 P7 V7 R7 X7 3

5 Dimensions, mounting, schemes Contactors 5 Dimensions, mounting LC1-V Ø Ø , , LC1-V xØ10, ,5 2xØ8,5x19 2xØ8 2xØ8, ,5 63, , LC1-V xØ8,5x xØ8,5 9, Schemes LC1-V160 32, LC1-V320, V610 Auxiliary contact blocks LA1-VN11 1N/O & 1N/C LA1-VN02 2N/C LA1-VN20 2N/O LA1-VN11X 1N/O 14 13/NO 22 21/NC 52 51/NC 62 61/NC 34 33/NO 44 43/NO 04 03/NO coil/ bobine NC A2 2/T1 4/T2 6/T A2 2/T1 4/T2 6/T A1 1/L1 3/L2 5/L3 03/NO 13/NO 21/NC A1 1/L1 3/L2 5/L3 13/NO 21/NC 4

6 produced by Product and Corporate Communications South Africa Reference: cat001/02 South Africa (Pty) Ltd Reg No 71/02841/07 Corner Bekker & Montrose Roads Midrand Private Bag X139 Halfway House, 1685 Tel Fax Branches: Cape Town Durban Port Elizabeth Kenya Reunion Zambia Zimbabwe

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

Type: DILM32 10(24V50HZ) Article No.: 277247

Type: DILM32 10(24V50HZ) Article No.: 277247 Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

Type: DILM9 10(24VDC) Article No.: 276705

Type: DILM9 10(24VDC) Article No.: 276705 Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50

More information

D-Line Contactors, Overload Relays and Accessories

D-Line Contactors, Overload Relays and Accessories D-Line Contactors, Overload Relays and Accessories Class 850 CONTENTS Description......................................................Page General Information...............................................

More information

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase

More information

Catalog. Modular DIN rail components Installation contactors

Catalog. Modular DIN rail components Installation contactors Catalog Modular DIN rail components Installation contactors 0 CDC00C00 Installation contactors Benefits and features Overview Ordering details ESB installation contactors ESB0 ESB ESB0 ESB 7 EN installation

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Technical catalogue. Modular DIN rail components Installation contactors

Technical catalogue. Modular DIN rail components Installation contactors Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a

More information

Safety automation solutions

Safety automation solutions Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V, Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41

More information

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary

More information

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data.

Micro Contactors. Micro Contactor Relays. Micro Contactors With Solder Pins. Coil voltages. Micro Reversing Contactor. Technical Data. Micro Contactors Micro Contactor Relays 0 Micro Contactors Micro Contactors With Solder Pins Coil voltages Micro Reversing Contactor 3 Technical Data 4 Dimensions 8 9 Micro Contactor Relays 4pole C Operated

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

Safety detection solutions

Safety detection solutions Presentation, actuator operated etal, types CS A, CS B, CS C and CS E Plastic, double insulated, turret head, types CS P or CS PA or CS TA and CS TE etal, types CS A, CS B, CS C, CS E with or without locking

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1 MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

Pendant control stations 6

Pendant control stations 6 Characteristics 6 Environment Conformity to standards EN/IEC 6097-5-1 EN/IEC 600-, UL 508, CSA C- n EN/IEC 6097-5-5 and EN/ISO 850 for versions with trigger action Emergency stop Product certifications

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

PSR The compact range Description

PSR The compact range Description Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

RY2 miniature industrial relays

RY2 miniature industrial relays 6 RY2 Relays of general application For plug-in sockets, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting Flat insert connectors - faston x 0,5 mm Recognitions, certifications, directives: RoHS,

More information

Manual Motor Starter MS 116 up to 16 A Technical Data

Manual Motor Starter MS 116 up to 16 A Technical Data Manual Motor Starter MS 116 up to 16 A Technical Data Type MS 116 Standards: Major International IEC 60 947-4-1 / IEC 60 947-2 and European Standards EN 60 947-4-1 / EN 60 947-2 Approvals, Certificates

More information

Catalog January. Heavy industrial power applications Motor contactors and starters

Catalog January. Heavy industrial power applications Motor contactors and starters Catalog January Heavy industrial power applications Motor contactors and starters 2006 General contents 0 Heavy Industrial Power Applications Motor Contactors and Starters 1 Contactors and Starters, Type

More information

Technicaldata General

Technicaldata General Currenttransformer-operatedoverloadrelay,60-90A,1N/O+1N/C Partno. ZW7-90 Articleno. 002618 CatalogNo. XTOT090C3S Deliveryprogramme Product range ZW7 current transformer-operated overload relays Description

More information

Safety dialogue solutions

Safety dialogue solutions General Presentation Emergency stop trip wire switches Emergency stop trip wire switches are designed to: b avert hazards (dangerous phenomena) at the earliest possible moment, or to reduce risks which

More information

Pluggable interface relays CR-P Pcb relays

Pluggable interface relays CR-P Pcb relays 2CDC 293 034 F0004 1 2 4 3 Features 9 different supply s: DC versions: 12 V, 24 V, 48 V, 110 V AC versions: 24 V, 48 V, 110 V, 120 V, 230 V Output contacts: 1 c/o (16 A) or 2 c/o (8 A) Cadmium-free contact

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

Relés e Contatores de Estado Sólido SIRIUS

Relés e Contatores de Estado Sólido SIRIUS Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico

More information

HS5D. Miniature Interlock Switches First in. Head Removal Detection Function for Safer Performance. First in. the Industry.

HS5D. Miniature Interlock Switches First in. Head Removal Detection Function for Safer Performance. First in. the Industry. y HS5D First in the Industry Miniature Interlock Switches First in the Industry Head Removal Detection Function for Safer Performance (*based on IDEC research, July 09) New Generation Miniature Interlock

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Installation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC 103002 C0201

Installation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC 103002 C0201 Technical Catalogue Installation Contactors Type ESB abb ABB STOTZ-KONTAKT GmbH 1 CDC 10300 C001 ABB STOTZ-KONTAKT GmbH CDC 10300 C001 Low Voltage Products and Systems We ensure safety and comfort for

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide

IEC style contactors - long electrical and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide - long al and mechanical life Complete range from mini-contactors to 630 Amp i n d u c t i ve AC3 ra t i n g s Wide range coils +0% to -30% Finger safe terminals Four-pole versions available NO + NC and

More information

Plug and Socket Devices CES 63 A Series 8579

Plug and Socket Devices CES 63 A Series 8579 www.stahl.de > Switch socket / plug 63 A > Large switch handle with clear switch position indication padlockable in 0- and I-position > Low insertion and withdrawal forces through individually encapsulated

More information

Contact expander modules

Contact expander modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:

More information

Preventa Machine Safety Products

Preventa Machine Safety Products Preventa Machine Safety Products Catalog 2009 200 Supplement Safety Relay Modules 2 Contents Preventa safety relay modules Selection guide 2 Electrical Ratings 6 Types XPSAC and XPSAXE For Emergency stop

More information

Switching Devices Contactors and Contactor Assemblies Special Applications

Switching Devices Contactors and Contactor Assemblies Special Applications Switching Devices Contactors and Contactor Assemblies Special Applications Price groups PG 1B, 1H /2 Introduction Contactors for special applications / SIRIUS 3RT1 contactors for resistive loads (AC-1),

More information

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for. The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

more than a breaker it s a breakthrough Compact NSX

more than a breaker it s a breakthrough Compact NSX Compact NSX, more than a breaker it s a breakthrough Compact NSX 100-630 A Intelligent outlook Today, we are living in an increasingly booming and fast changing world where energy is key. More than ever,

More information

3/2-way Solenoid Valve, direct-acting, NC or NO

3/2-way Solenoid Valve, direct-acting, NC or NO 3/2-way Solenoid Valve, direct-acting, NC or NO Electrical connection cable plug, Form A With or without manual override as standard Threaded port and sub-base s Impulse optional Type 6014 can be combined

More information

Bimetallic Overload Relay Specifications

Bimetallic Overload Relay Specifications Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions

More information

VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA

VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA Monitoring of phase sequence and phase loss Monitoring of asymmetry Temperature monitoring (PTC) Supply voltage 208-480 V AC Supply circuit = measuring circuit 2 change-over contacts Width 45 mm Control

More information

Contact expansion modules

Contact expansion modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 4 safety contacts

More information

ELECTROMAGNETIC DISC BRAKES

ELECTROMAGNETIC DISC BRAKES ELECTROMAGNETIC DISC BRAKES TYPE 66E 15/30 52.121 Hand release Lining wear adjustment Torque adjustment 4 holes ø13 DISC SIZE Ø A Braking torque Nm Regulated from (40-100%) Reaction on the shaft N Control

More information

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

FUSERBLOC. 20 to 1250 A Manual operation. 142 General Catalogue 2011-2012 SOCOMEC. Fuse combination switches

FUSERBLOC. 20 to 1250 A Manual operation. 142 General Catalogue 2011-2012 SOCOMEC. Fuse combination switches FUSERBLOC Fuse combination switches appli_8_a fuser_548_a cat fuser_59_a cat fuser_52_a cat 2 to 25 A Manual operation Function FUSERBLOC are manually operated multipolar fuse combination switches. They

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011 , 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

CATALOG #250 WWW.DANAHERSPECIALTYPRODUCTS.COM

CATALOG #250 WWW.DANAHERSPECIALTYPRODUCTS.COM CATALOG #250 WWW.DANAHERSPECIALTYPRODUCTS.COM TABLE OF CONTENTS Vacuum Control... Low Voltage, Medium Voltage... A NEMA Control - Heavy Duty... TM, 5000... B NEMA Control - General Duty... HP... C Pilot

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Telemecanique Zelio Relay complementary and easy to assemble

Telemecanique Zelio Relay complementary and easy to assemble Telemecanique Zelio Relay complementary and easy to assemble Get more with the world s Power & Control specialist RS interface relays Compact dimensions, enabling multiplication of contacts in electrical

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features gang engertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

PNOZsigma - Base units

PNOZsigma - Base units PNOZsigma - Base units Register Login Sensors Control and Communication Electronic monitoring relays Safety Relays PNOZ X PNOZsigma PNOZelog PNOZmulti PNOZpower Configurable control systems Programmable

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O),

More information

Cable Plug acc. to DIN EN 175301-803, Form A

Cable Plug acc. to DIN EN 175301-803, Form A Cable Plug acc. to DIN EN 175301-803, Form A Complete program Contact form 18 mm Also available with LED indicator Optional 4-pin version for pressure switch or impulse valves respectively Versions with

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD

NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD Shanghai Liangxin Electrical CO.,LTD Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Zip: 200137 Tel: 86-21-5012789 Fax: 86-21-58675966 E-mail: client@sh-liangxin.com LINE 1 LINE 3 LINE 5

More information

Softstarters Type PSR

Softstarters Type PSR Catalog Softstarters Softstarters ABB Softstarters General To the left: A combination with PSR and a manual Motor Starter MS116 Above: PSR16, PSR30 and PSR 45 1 ABB Automation Products serve customers

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

Thermal-Magnetic Circuit Breaker 3120-...-M1-..

Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous

More information

Electric Rotary Actuator - On/Off or programmable control actuator

Electric Rotary Actuator - On/Off or programmable control actuator Electric Rotary Actuator - On/Off or programmable control actuator Direct mounting on quarter-turn valves Manual override standard Corrosion resistant Adjustable limit switches Multi-voltage version Type

More information

Plug and Socket Devices SolConeX 16 A Series 8570

Plug and Socket Devices SolConeX 16 A Series 8570 www.stahl.de > Switch socket / plug 16 A > Minimal force required to insert and remove > Can be optionally equipped with an auxiliary contact for control and signalling purposes > arge switching handle

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Energy Management Energy Meter Type EM23 DIN

Energy Management Energy Meter Type EM23 DIN Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy

More information

RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu,

RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu, APPROVAL SHEET CUSTOMER ituner CUSTOMER P/N DESCRIPTION EDAC MODEL 12V/6.6A SERIES NO. (E17) EA10953A DATE 2010-06-22 REVISION 0 APPROVED DESIGN PREPARE RoHS CONCLUSION APPROVED CONDITON CUSTOMER S APP

More information

Electro-pneumatic control valves

Electro-pneumatic control valves Electropneumatic control valves 7 Miniature solenoid valves for alternating current Conform to the Low Voltage Directive or mounting on subbase or footprint in accordance with CNOMO recoendation E 066120N

More information

mecotron Safety relay ESTOP-2 For emergency stop monitoring

mecotron Safety relay ESTOP-2 For emergency stop monitoring E0006 000824 Safety relay E-2 For emergency stop monitoring Description The safety module E-2 for emergency stop monitoring is used for safety breaking one or more circuits and is designed to be incorporated

More information

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units Automotive Powering business worldwide Aerospace Eaton delivers the hundreds of power distribution products that are answering the demands of today s fast changing world. We help our customers worldwide

More information

Safety Relays ESM/ESM-F

Safety Relays ESM/ESM-F Safety Relays ESM/ESM-F More than safety. Safety More than safety. Emil Euchner, the company s founder and inventor of the multiple limit switch, circa 1928. Around the world the Swabian specialists in

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

CQM1-SF200/CS1W-SF200

CQM1-SF200/CS1W-SF200 Safety Relay Unit ( I/O Unit Type) CQM1-SF200/CS1W-SF200 CSM_CQM1-SF200_CS1W-SF200_DS_E_2_1 A Safety Relay Unit That Functions as a I/O Unit. Less Installation Space and Wiring Required. Safety Relay Unit

More information

US Breaker Brand 3 Pole AC Contactors (Square D Telemecanique LC1 Replacements)

US Breaker Brand 3 Pole AC Contactors (Square D Telemecanique LC1 Replacements) 4 NC1 D09-D18 NC1 -D32 US Breaker Brand 3 Pole AC Contactors (Square D Telemecanique LC1 Replacements) Standards: UL508, CSA C22.2, IEC 60947, and CE Marked Integral DIN Rail & Base Mounting in One Compact

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

Type Sealing Poles Contacts Rated voltage Model Standard d Flux-tight 4 poles oes 3PST-NO, SPST-NC 24 VDC G7SA-3A1B 3PST-NO, 3PST-NC

Type Sealing Poles Contacts Rated voltage Model Standard d Flux-tight 4 poles oes 3PST-NO, SPST-NC 24 VDC G7SA-3A1B 3PST-NO, 3PST-NC Safety Relay Slim Safety Relays Conforming to EN Standards The forcibly guided contact in the assures safe operation (EN50205 Class A, approved by VDE.) Ideal for use in safety circuits in press machinery,

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection

More information