Evidence of Performance Airborne sound insulation of fire rated products

Size: px
Start display at page:

Download "Evidence of Performance Airborne sound insulation of fire rated products"

Transcription

1 Evidence of Performance Airborne sound insulation of fire rated products Test Report PR01 (PB 01-E03-04-en-02) Client Product Designation Material Sealing material Diameter of opening Basic element Hilti Entwicklungsgesellschaft mbh Hiltistr Kaufering Germany Pipe DN 60 resp. cable bunch with Hilti FS-ONE MAX in penetration Hilti FS-ONE MAX Single component, water based fire rated-sealant 100 mm (1 and/or. 2 pcs.) Metal stud partition Double stud framing, double clad Basis EN ISO : A1:2012 EN ISO : 2010 EN ISO : 2013 Additional ASTM E ASTM E Test report no PR01 (PB 01-E03-04-de-02) dated Instructions for use This test report serves to verify the sound insulation of fire rated products. ift Rosenheim Dr. Joachim Hessinger, Dipl.-Phys. Head of Testing Department Building Acoustics Weighted normalized sound level difference of small building elements D n,e,w Spectrum adaption terms C and C tr Pipe DN 60 with Hilti FS-ONE MAX D n,e,w (C; C tr ) = 71 (-4; -9) db Pipe DN 60 + cable bunch with Hilti FS-ONE MAX D n,e,w (C; C tr ) = 70 (-3; -8) db Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer Building Acoustics Validity The data and results given relate solely to the tested and described specimen. Testing the sound insulation does not allow any statement to be made on any further characteristics of the present construction regarding performance and quality. Notes on publication The ift Guidance Sheet "Conditions and Guidance for the Use of ift Test Documents" applies. The cover sheet can be used as abstract. Contents The test report contains a total of 17 pages: 1 Object 2 Procedure 3 Detailed results 4 Instructions for use Data sheets (5 pages) / 695

2 Evidence of Performance Airborne sound insulation of fire rated products Page 2 of 17 1 Object 1.1 Description of test specimen Product Pipe DN 60 resp. cable bunch with Hilti FS-ONE MAX in penetration Product designation Hilti FS-ONE MAX Material Single component, water based fire rated-sealant Type of mineral wool boards ISOVER Protect BSP 40 Test variants - Test of double stud framing without openings - Test with opening Ø = 100 mm and installed pipe DN 60 with Hilti FS-ONE MAX - Test with 2 openings Ø = 100 mm and installed pipe and cable bunch with Hilti FS-ONE MAX Metal stud partition Manufacturer* Metal stud partition mounted by ift Laboratory for Building Acoustics Date of manufacture 21st of October 2014 Sampling by ift Laboratory for Building Acoustics at builder s merchant Dimensions (W x H) 1,250 mm 1,500 mm Total thickness 155 mm Structure 50 mm metal studs, mineral fibre insulation 40 mm 5 mm air 50 mm metal studs, mineral fibre insulation 40 mm Stud framing metal studs from 50 mm C-wall channel section (CW 50x50x06) Cladding Knauf Piano sound insulation board F, screw-fastened Cavity insulation ISOVER Protect BSP 40, mounted between stud framing Penetration Clear opening Diameter 100 mm (1 and/or 2 pcs) Built-in components (test variant 1) Pipe Steel pipe DN 60 (60 x 5.3 mm) Insulation* ISOVER darning wool (mineral wool) Fire rated product* Hilti fire rated-sealant FS-ONE MAX Installation - Pipe placed into opening, pipe projects on both sides approx. 235 mm from partition, the open ends of the pipe were closed on both sides - Annular gap filled with ISOVER darning wool and sealed on both sides with Hilti fire rated-sealant FS-ONE MAX, insertion depth approx. 13 mm (approx. ½ inch)

3 Evidence of Performance Airborne sound insulation of fire rated products Page 3 of 17 Built-in components (test variant 2) Together with test variant 1 Cable bunch* each 1 x NYY-J 5x1.5 RE N2XH-J 5x1.5 RE NYCWY 4 x 185SM/95 Telecommunication cable bunch Empty conduit steel Ø 16 mm Empty conduit plastic Ø 16 mm Insulation* ISOVER darning wool (mineral wool) Fire rated product* Hilti fire rated-sealant FS-ONE MAX Installation - Cable bunch fixed with cable ties and placed into opening, the cable sections project on both sides approx. 150 mm 250 mm from partition wall, the open ends of the empty conduits were closed on both sides - Annular gap filled with ISOVER darning wool and sealed on both sides with Hilti fire rated-sealant FS-ONE MAX, insertion depth approx. 13 mm (approx. ½ inch) The description is based on inspection of the test specimen at ift Laboratory for Building Acoustics. Item designations / numbers as well as material specifications were provided by the client. Additional data provided by the client are marked with * 1.2 Mounting to test rig Test rig Mounting of test specimen Mounting conditions Sealing Drying time Window test rig Z-Wall with suppressed flanking transmission acc. to EN ISO : 2010; the test rig includes a mounting frame with a continuous acoustic break which is sealed in the test opening with closed-cell permanently resilient sealant. Mounted by ift Laboratory for Building Acoustics and employees of the client. The wall element was mounted by employees of ift Laboratory for Building Acoustics. Wall element mounted in test opening of window test rig ( Zwall ) on source room. The acoustic separation wasn t bridged. The wall element was sealed on both sides with sealant Type Perennator 2001 S grey. Built-in components were sealed towards partition with elastic sealant. Rendering of the gypsum plasterboards was not necessary because the opening was in one board (without joints). Sealant (with the help of hot air blowers) approx. 0.5 h

4 Evidence of Performance Airborne sound insulation of fire rated products Page 4 of Representation of test specimen The structural details were examined solely on the basis of the characteristics to be classified. Source room \\sift01\iftello_daten_rw\ablage\vo \projekt\pr01\prüfberichte\ pr01 PB 01 Fig. 1 Photos of metal stud partition mounted to window test rig, taken by ift Laboratory for Building Acoustics Source room Fig. 2 Receiving room Mounting of test variant 1 Receiving room

5 Evidence of Performance Airborne sound insulation of fire rated products Page 5 of 17 Source room \\sift01\iftello_daten_rw\ablage\vo \projekt\pr01\prüfberichte\ pr01 PB 01 fig 3 Mounting of test variant 2 Cable bunch fig 4 Receiving room Pipe Details of built-in components

6 Evidence of Performance Airborne sound insulation of fire rated products Page 6 of 17 2 Procedure 2.1 Sampling Sampling Quantity Manufacturer Manufacturing plant Batch number Date of sampling Procedure of sampling \\sift01\iftello_daten_rw\ablage\vo \projekt\pr01\prüfberichte\ pr01 PB 01 Responsible for sampling Delivery at ift ift registration number Carton box Fig. 5 The samples were selected by the client 1 carton box with 12 cartridges ea. 300 ml Hilti Industriegesellschaft für Befestigungssysteme mbh Hilti Werk 6, fire rated production, Hilti Str.6, Kaufering B # July 2014 Official sampling on 29 July 2014 at production plant by auditors Mr. Rüdiger Dederichs (FM) and Mr. Karl Bohn (UL USA). The sealing (see fig. 5) of the marked-up samples was removed by an employee of ift Laboratory for Building Acoustics on the date of testing ( ). Mr. Stefan Rump 22 October 2014 by the client Carton box + single cartridge with batch number delivered samples, sealed and marked up

7 Evidence of Performance Airborne sound insulation of fire rated products Page 7 of Method(s) Basis EN ISO : A1 : 2012 Acoustics; Laboratory measurement of sound insulation of building elements - Part 1: Application rules for specific products (ISO :2010+Amd.1:2012) EN ISO :2010 Acoustics; Laboratory measurement of sound insulation of building elements - Part 2: Measurement of airborne sound insulation (ISO :2010) EN ISO : 2013 Acoustics; Rating of sound insulation in buildings and of building elements - Part 1: Airborne sound insulation Correspond/s to the national German standard/s: DIN EN ISO : , DIN EN ISO : and DIN EN ISO : Additional basis ASTM E Standard test method for laboratory measurement of airborne sound transmission loss of building partitions and elements ASTM E Classification for rating sound insulation Boundary conditions Deviation Test noise Measuring filter As specified by the standards. Upon request by the client additional evaluations of the STC were carried out in accordance with ASTM E There are no deviations from the test method/s and/or test conditions acc. to EN ISO The volume of the test room falls below the minimum volume of 80 m³ as defined in ASTM E The linear flow resistance of the insulating material was not determined. Pink noise One-third-octave band filter

8 Evidence of Performance Airborne sound insulation of fire rated products Page 8 of 17 Measurement limits Low frequencies Background noise level Maximum sound insulation The dimensions of the receiving room were smaller than recommended for testing in the frequency range from 50 Hz to 80 Hz as per EN ISO :2010 Annex A (informative). A moving loudspeaker was used. The background noise level in the receiving room was determined during measurement and the receiving room level L 2 corrected by calculation as per EN ISO : 2010 Clause 4.3. For evaluation of the normalized level difference of the penetration through the wall the sound insulation of the wall alone was taken as maximum sound insulation. The difference between normalized sound level difference and maximum sound insulation of the test setup is partly smaller than 15 db. For normalized sound level difference it was corrected by calculation as per EN ISO :2010 Annex A. The graphs presented in the Annex include maximum sound insulation. Measurement of reverberation time Measurement equation A Measurement of sound level difference Measurement equation Measurement equation D n,e Arithmetical mean: 6 measurements each of 2 loudspeaker positions with rotating microphone (total of 12 measurements). V A = 0, 16 m² T Minimum of 2 loudspeaker positions and rotating microphones. S R = L1 L lg db A A, = L1 L2 +10 lg in db A 0 D n e KEY A Equivalent absorption area in m² A 0 Reference absorption area (10 m²) L 1 Sound pressure level source room in db L 2 Sound pressure level receiving room in db R Sound reduction index in db D n,e Normalized sound level difference of small building elements in db T Reverberation time in s V Volume of receiving room in m³ S Testing area of the specimen in m²

9 Evidence of Performance Airborne sound insulation of fire rated products Page 9 of Test apparatus Device Type Manufacturer Integrating sound meter Type Nortronic 830 Norsonic-Tippkemper Microphone preamplifiers Type 1201 Norsonic-Tippkemper Microphone unit Type 1220 Norsonic-Tippkemper Calibrator Type 1251 Norsonic-Tippkemper Dodecahedron loudspeakers Own production - Amplifier Type E120 FG Elektronik Rotating microphone boom Own production / Type 231-N-360 Norsonic-Tippkemper The ift Laboratory for Building Acoustics participates in comparative measurements at the Physikalisch-Technische Bundesanstalt (PTB) in Braunschweig every three years, the last one was in April The sound level meter used, Series No , was calibrated by the Dortmund Eichamt (calibration agency) on 8 March The calibration is valid until 31 December The sound level meter used, Series No , was DKD calibrated by the company Norsonic Tippkemper (DKD - Deutscher Kalibrierdienst German Calibration Service ) on 14 March Testing Date 22 October 2014 Operating Testing Officer Mr. Stefan Bacher

10 Evidence of Performance Airborne sound insulation of fire rated products Page 10 of 17 3 Detailed results The values of the measured sound reduction index of the wall element as well as the measured normalized sound level difference of small building elements of the tested elements are plotted as a function of frequency in the annexed data sheet and tabled. They are used to calculate the weighted sound reduction index R w / the weighted normalized sound level difference D n,e,w and the spectrum adaptation terms C and C tr for the frequency range 100 Hz to 3,150 Hz, as described in Table 1. Additional to the rating according to EN ISO a weighting according to ASTM E was carried out. The sound transmission class STC according to ASTM E for the frequency range from 125 Hz up to 4,000 Hz was calculated as follows: Table 1 Results of acoustic tests Data Component / Modification Testing standard / Results in db / Reference surface sheet No. EN ISO EN ISO E EN ISO E Normalized sound level difference of Sound insulation of penetration, evaluation with respect to a reference Sound insulation of the element without penetrations penetrations area of S=1.88 m² 1) D n,e,w (C; C tr ) R w (C; C tr ) STC R w (C; C tr ) STC A 0 = 10 m² S = 1.88 m² S = 1.88 m² S = 1.88 m² S = 1.88 m² 1 Metal stud partition (-3; -8) 59 2 Metal stud partition with bore; pipe DN 60 with Hilti fire rated-sealant FS-ONE MAX 3 Metal stud partition with bole; pipe DN 60 with Hilti fire rated-sealant FS-ONE MAX 4 Metal stud partition with 2 bores; pipe DN 60 and cable bunch with Hilti fire rated- Sealant FS-ONE MAX 5 Metal stud partition with 2 bores; pipe DN 60 and cable bunch with Hilti fire rated- Sealant FS-ONE MAX (-3;-8) (-4;-9) (-2;-8) (-3;-8)

11 Evidence of Performance Airborne sound insulation of fire rated products Page 11 of 17 1) For the evaluation of the sound insulation of the penetration as a weighted sound reduction index and STC the measured values of the normalized sound level difference (D n,e resp. D n,e,w evaluated with a correction of maximum sound insulation according to Clause 2.2) were evaluated with a reference area of 1.88 m². Referring to the tested values presented in Table 1 line 2 to 5 a correction for maximum sound insulation was performed by calculation (see Clause 2.2). Without this correction the following values were determined for the sound insulation of the wall element with penetrations: Table 2 Results of acoustic tests (additional information) Data Component / Modification Testing standard / Results in db / sheet Reference area No. EN ISO E Sound insulation of the wall element with penetrations - Metal stud partition with bore; pipe DN 60 with Hilti fire rated-sealant FS-ONE MAX - Metal stud partition with 2 bores; pipe DN 60 and cable bunch with Hilti fire rated-sealant FS-ONE MAX (without correction for a maximum sound insulation) R w (C; C tr ) STC S = 1.88 m² S = 1.88 m² 62 (-3; -8) (-3; -8) 61 4 Instructions for use 4.1 Safety margin according to DIN 4109 Basis DIN 4109: Sound insulation in buildings, requirements and verifications This test report is not an evidence of suitability as per DIN 4109: A calculated value is not indicated. 4.2 Constructions products list As set out by the German Bauregelliste (Construction Products List), evidence of compliance in Germany is possible only in the form of an AbP (national technical test certificate). This test report cannot be used as a subtest to be included in a national technical test certificate (AbP).

12 Evidence of Performance Airborne sound insulation of fire rated products Page 12 of Test standards The standard series EN ISO 10140:2010 supersedes those, until the respective date, applicable parts of the standards series EN ISO 140 which describe laboratory tests. According to the two standard series, the test methods are identical. Assessments as per ASTM E were based on sound insulation testing as per EN ISO (previous EN ISO 140-3). For some details there are deviations from test standard ASTM E 90-09, in particular as regards the required room volume (min. 80 m³). ift Rosenheim Laboratory for Building Acoustics

13 Sound reduction index according to ISO Laboratory measurements of airborne sound insulation of building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition without opening Total thickness Area related mass 155 mm 50.0 kg/m² Test date 22 October 2014 Test surface S 1.25 m x 1.50 m = 1.88 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V R = 67.5 m³ Maximum sound reduction index (not specified) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 19 C / 57% RH / 959 hpa x f in Hz R in db , , , , , , , , x Background noise level difference < 6 db Sound reduction index R in db Rating according to EN ISO (in third octave bands): R w (C; C tr ) = 62 (-3; -8) db C 50-3,150 = -4 db; C 100-5,000 = -2 db; C 50-5,000 = -3 db C tr,50-3,150 = -13 db; C tr,100-5,000 = -8 db; C tr,50-5,000 = -13 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 13 of 17 Data Sheet 1 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve Frequency range corresp. to reference curve as per EN ISO Frequency f in Hz Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000

14 Sound reduction index according to ISO Laboratory measurements of airborne sound insulation of building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition with opening Ø = 100 mm Filled with pipe DN 60 with Hilti fire-rated sealant FS- ONE MAX on both sides Special features: A correction for maximum sound insulation by calculation of test value was performed Test date 22 October 2014 Test surface S 1.25 m x 1.50 m = 1.88 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V R = 67.5 m³ Maximum sound reduction index R w,max = 62 db (related to test area) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 20 C / 60% RH / 959 hpa x f in Hz R in db 50 > > > > > > > > > > > > > ,000 > ,250 > ,600 > ,000 > ,500 > ,150 > ,000 > ,000 > 71.6 x Background noise level difference < 6 db Flanking transmission effect Sound reduction index R in db Rating according to EN ISO (in third octave bands): R w (C; C tr ) = 63 (-3; -8) db C 50-3,150 = -4 db; C 100-5,000 = -2 db; C 50-5,000 = -3 db C tr,50-3,150 = -13 db; C tr,100-5,000 = -8 db; C tr,50-5,000 = -13 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 14 of 17 Data Sheet 2 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve maximum sound insulation Frequency range corresp. to reference curve as per EN ISO Frequency f in Hz Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000

15 Normalized sound level difference acc. to ISO Laboratory measurements of airborne sound insulation of small building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition with opening Ø = 100 mm Filled with pipe DN 60 with Hilti fire-rated sealant FS- ONE MAX on both sides Special features: A correction for maximum sound insulation by calculation of test value was performed Test date 22 October 2014 Reference absorption area A 0 = 10 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V R = 67.5 m³ Maximum sound insulation D n,e,w,max = 70 db (related to A 0 = 10 m²) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 16 C / 57% RH / 966 hpa x f in Hz D n,e in db 50 > > > > > > > > > > > > > ,000 > ,250 > ,600 > ,000 > ,500 > ,150 > ,000 > ,000 > 78.9 x Background noise level difference < 6 db Flanking transmission effect Normalized sound level difference D n,e in db Frequency f in Hz Rating according to EN ISO (in third octave bands): D n,e,w (C; C tr ) = 71 (-4; -9) db C 50-3,150 = -5 db; C 100-5,000 = -3 db; C 50-5,000 = -4 db C tr, = -14 db; C tr,100-5,000 = -9 db; C tr,50-5,000 = -14 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 15 of 17 Data Sheet 3 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve maximum sound insulation Frequency range corresp. to reference curve as per EN ISO Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000

16 Sound reduction index according to ISO Laboratory measurements of airborne sound insulation of building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition with 2 openings Ø = 100 mm Filled with pipe DN 60 resp. cable bunch with Hilti firerated sealant FS-ONE MAX on both sides Special features: A correction for maximum sound insulation by calculation of test value was performed Test date 22 October 2014 Test surface S 1.25 m x 1.50 m = 1.88 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V R = 67.5 m³ Maximum sound reduction index R w,max = 62 db (related to test area) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 20 C / 59% RH / 959 hpa x f in Hz R in db 50 > 34, ,7 80 > 30, ,4 125 > 44,3 160 > 46,4 200 > 44,4 250 > 50,9 315 > 56,0 400 > 60,9 500 > 63,8 630 > 64,5 800 > 65,4 1,000 65,8 1,250 65,6 1,600 66,3 2,000 66,5 2,500 > 68,2 3,150 > 68,3 4,000 > 70,9 5,000 > 70,9 x Background noise level difference < 6 db Flanking transmission effect Sound reduction index R in db Frequency f in Hz Rating according to EN ISO (in third octave bands): R w (C; C tr ) = 62 (-2; -8) db C 50-3,150 = -5 db; C 100-5,000 = -1 db; C 50-5,000 = -4 db C tr,50-3,150 = -14 db; C tr,100-5,000 = -8 db; C tr,50-5,000 = -14 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 16 of 17 Data Sheet 4 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve maximum sound insulation Frequency range corresp. to reference curve as per EN ISO Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000

17 Normalized sound level difference acc. to ISO Laboratory measurements of airborne sound insulation of small building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition with 2 openings Ø = 100 mm Filled with tube DN 60 resp. cable bunch with Hilti firerated sealant FS-ONE MAX on both sides Special features: A correction for maximum sound insulation by calculation of test value was performed Test date 22 October 2014 Reference absorption area A 0 = 10 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V E = 67.5 m³ Maximum sound insulation D n,e,w,max = 70 db (related to A 0 = 10 m²) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 20 C / 59% RH /959 hpa x f in Hz D n,e in db 50 > > > > > > > > > > > , , , , ,500 > ,150 > ,000 > ,000 > 78.2 x Background noise level difference < 6 db Flanking transmission effect Normalized sound level difference D n,e in db Rating according to EN ISO (in third octave bands): D n,e,w (C; C tr ) = 70 (-3; -8) db C 50-3,150 = -5 db; C 100-5,000 = -2 db; C 50-5,000 = -4 db C tr,50-3,150 = -15 db; C tr,100-5,000 = -8 db; C tr,50-5,000 = -15 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 17 of 17 Data Sheet 5 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve maximum sound insulation Frequency range corresp. to reference curve as per EN ISO Frequency f in Hz Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000

Test Report. Nr. 1370-001-12 dated 16.02.2012. Sound Absorption Coefficient in the Reverberation Room. Lammengatan 2 SE-360 30 Lammhult Sweden

Test Report. Nr. 1370-001-12 dated 16.02.2012. Sound Absorption Coefficient in the Reverberation Room. Lammengatan 2 SE-360 30 Lammhult Sweden Test Report Nr. 1370-001-12 dated 16.02.2012 Sound Absorption Coefficient in the Reverberation Room Customer: Abstracta AB Lammengatan 2 SE-360 30 Lammhult Sweden Test Object: Arrangement of Acoustic Panels

More information

Lightweight Partition Design for Residential and Commercial Buildings

Lightweight Partition Design for Residential and Commercial Buildings Lightweight Partition Design for Residential and Commercial Buildings Stanley D. Gatland II, CertainTeed Corporation, Valley Forge, Pennsylvania Guidelines are presented for the design and proper installation

More information

Airborne Sound Insulation

Airborne Sound Insulation Airborne Sound Insulation with XL2-TA Sound Level Meter This application note describes the verification of the airborne sound insulation in buildings with the XL2-TA Sound Level Meter. All measurements

More information

CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES

CERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES CERTIFICATE OF APPROVAL No CF 5055 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 1 st Industrial Area,

More information

ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 8 TEST : Whisper Industries, L.L.C. Report Date: August 14, 2008 Date: July 9, 2008 Number: RESULT

More information

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS NOISE TECHNICAL FACT SHEET FACT SHEET 5 SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS The sound insulation of exterior walls and roof-ceiling systems refers to their ability to reduce external

More information

SOUND TRANSMISSION CLASS TEST REPORT Series/Model: VL-WDW11 VistaLuxe Awning

SOUND TRANSMISSION CLASS TEST REPORT Series/Model: VL-WDW11 VistaLuxe Awning ACOUSTIC Page 1 of 5 SOUND TRANSMISSION CLASS TEST REPORT Series/Model: VL-WDW11 VistaLuxe Awning Prepared for: Koble & Kolbe Millwork Co., Inc. Attn: Ms. Tasha Verhasselt 1323 South 11th Avenue Wausau,

More information

Tremco Fire Protection Systems Group Technical Bulletin

Tremco Fire Protection Systems Group Technical Bulletin Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,

More information

SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR1 Teutonic Outswing Vinyl Entrance Door

SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR1 Teutonic Outswing Vinyl Entrance Door ACOUSTIC Page of 5 9/8/204 SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR Teutonic Outswing Vinyl Entrance Door Prepared for: Kolbe and Kolbe Millwork Co., Inc. Attn: Ms. Tasha Verhasselt 323

More information

SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR2 Teutonic Outswing Vinyl Entrance Door

SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR2 Teutonic Outswing Vinyl Entrance Door ACOUSTIC Page of 5 SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR2 Teutonic Outswing Vinyl Entrance Door Prepared for: Kolbe and Kolbe Millwork Co., Inc. Attn: Ms. Tasha Verhasselt 323 South th

More information

European Organisation for Technical Approvals

European Organisation for Technical Approvals Warrington Certification Limited, Holmesfield Road, Warrington, WA1 2DS Tel. +44 (0) 1925-646777 Fax +44 (0) 1925-646667 Member of EOTA Authorised and notified according to Article 10 of the Council Directive

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC B2706.01

More information

E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion

E6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex

More information

Evidence of Performance. Class 2. Class 5A. Class C4 / B4. Test Report No. 15-003655-PR01. ift Rosenheim 16.12.2015

Evidence of Performance. Class 2. Class 5A. Class C4 / B4. Test Report No. 15-003655-PR01. ift Rosenheim 16.12.2015 Evidence of Performance Test Report No. 15-003655-PR01 (PB-A01-02-en-01) Client Product Designation Performance-relevant product details Overall dimensions (W x H) Special features Alüminyum San. Tic.

More information

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01 Section Built-up Metal Roofs Rail and bracket system Product: Earthwool FactoryClad range Bu01 Standing seam system Product: Earthwool FactoryClad range and Earthwool Universal Slab Bu02 Built-up Metal

More information

ProRox Slabs (formerly known as RW slabs)

ProRox Slabs (formerly known as RW slabs) Slabs (formerly known as RW slabs) Versatile thermal acoustic insulation slabs ROCKWOOL's Slabs are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation. They are

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T24000 TYPE: Two-Lite Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC C5774.01

More information

Manual Analysis Software AFD 1201

Manual Analysis Software AFD 1201 AFD 1200 - AcoustiTube Manual Analysis Software AFD 1201 Measurement of Transmission loss acc. to Song and Bolton 1 Table of Contents Introduction - Analysis Software AFD 1201... 3 AFD 1200 - AcoustiTube

More information

Passive Fire Protection

Passive Fire Protection Firestopping Passive Fire Protection FS20 Firestop Compound 6 hour fire rated penetration seals for electrical and mechanical services FS20 Firestop Compound FS20 Firestop Compound is a Fire-Rated Penetration

More information

ENVIRONMENTAL INFORMATION APR 1200 products are made from glass mineral wool, one of the most environmentally friendly insulants available.

ENVIRONMENTAL INFORMATION APR 1200 products are made from glass mineral wool, one of the most environmentally friendly insulants available. APR 1200 Acoustic Partition Roll CI/Sfb Ref: APR002 Glass mineral wool roll designed to provide high levels of sound insulation in walls and floors to meet Part E (England & Wales) and Section 5 (Scotland)

More information

AMF Line; wall absorbers Wall mounted acoustic designs PERFORMANCE CEILINGS. M ore s c op e f or i n n ovat i on MADE IN GERMANY

AMF Line; wall absorbers Wall mounted acoustic designs PERFORMANCE CEILINGS. M ore s c op e f or i n n ovat i on MADE IN GERMANY PERFORMANCE CEILINGS M ore s c op e f or i n n ovat i on AMF Line; wall absorbers Wall mounted acoustic designs MADE IN GERMANY 138568_Prospekt Wandabsorber_GB int.indd 1 Acoustic elements on the wall

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

Rockwool Flexi Insulation Application Guide

Rockwool Flexi Insulation Application Guide Pitched roof Rafters InterMediate floors INTERNAL partitions external Framed walls separating floors Separating Walls Rockwool Flexi Insulation Application Guide Ground floor The perfect fit for any framed

More information

Sealfire W1000 Compound. (2 references for the same product) Fire Stopping and Sealing Product: Penetration Seals

Sealfire W1000 Compound. (2 references for the same product) Fire Stopping and Sealing Product: Penetration Seals UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. Phone : +44 1483 302130 Fax : +44 1483 302230 Email : Inform.NB@uk.ul.com Website

More information

Fiberglas, Exterior Wall Thermal Insulation

Fiberglas, Exterior Wall Thermal Insulation PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

The Role of Acoustics in Curtain Wall Design:

The Role of Acoustics in Curtain Wall Design: The Role of Acoustics in Curtain Wall Design: Strategies to Achieve Desired Performance Criteria April 22, 2015 John LoVerde, Principal VENEKLASEN ASSOCIATES, INC. Goals Basics of Acoustics Ratings in

More information

Sound absorption and acoustic surface impedance

Sound absorption and acoustic surface impedance Sound absorption and acoustic surface impedance CHRISTER HEED SD2165 Stockholm October 2008 Marcus Wallenberg Laboratoriet för Ljud- och Vibrationsforskning Sound absorption and acoustic surface impedance

More information

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with Section Separating Floors Timber frame floor with I-Beams Product: Earthwool Acoustic Roll and Floorfoam Easy Edge Strip Timber frame floor with solid timber joists Product: Earthwool Acoustic Roll and

More information

PAGE 2. Figure 1: Difference between PWL ins and SPL 1m

PAGE 2. Figure 1: Difference between PWL ins and SPL 1m PAGE 1 Pipe noise J.H. Granneman and R.P.M. Jansen, Peutz Consulting Engineers, The Netherlands, emphasise the need for an adequate pipe noise control procedure, with reference to the design phase, insulation

More information

Technical Data Sheet W13. Edition 2005-03. Knauf Fire Walls

Technical Data Sheet W13. Edition 2005-03. Knauf Fire Walls Technical Data Sheet W13 Edition 2005-03 Knauf Fire Walls Knauf Fire Wall A2 - GKF two/ three layer cladding Knauf Fire Wall A1 - Fireboard two layer cladding The structural, statical properties, and characteristic

More information

Enclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: sales@durasystems.com. The Passive Fire Protection Specialists

Enclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: sales@durasystems.com. The Passive Fire Protection Specialists Enclosures Sturdy single and double wall fire protection construction Impact resistant Fast & easy installation Pre-manufactured and modular Available in galvanized, stainless steel & other specialty metals

More information

Check-list for auditors. Audit visit at candidate registered laboratories

Check-list for auditors. Audit visit at candidate registered laboratories Check-list for auditors Audit visit at candidate registered laboratories 1 Contents Introduction Laboratory documentation required by the standard(s), available for inspection by the auditor Items to be

More information

FireWall. High performance fireresistant. FireWall. www.british-gypsum.com

FireWall. High performance fireresistant. FireWall. www.british-gypsum.com FireWall FireWall High performance fireresistant wall system FireWall is a non-loadbearing wall which provides up to 240 minutes fire resistance. It is used in certain ground floor basement situations

More information

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016 Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.

More information

Evidence of Performance Resistance to wind load Watertightness Air permeability

Evidence of Performance Resistance to wind load Watertightness Air permeability Evidence of Performance Resistance to wind load Watertightness Air permeability Test Report 102 43093/1e Client Product YILDIZPEN PLASTIK SAN. VE TIC. LTD. STI. A.O.S.B 10039 Street No:18 Çigli Izmir Turkey

More information

Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 Fire Barrier Moldable Putty+ Pads 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 e-mail: info@fireretardantsinc.com Visit Our Web Site at www.fireretardantsinc.com Protecting

More information

Complete Firestop Systems Guide

Complete Firestop Systems Guide Complete Firestop Systems Guide Passive Fire Protection products are tested to various test requirements, please check with your local building code for the requirements within your municipality. Firestop

More information

Mass Loaded Vinyl A review of the performance and cost in acoustical applications

Mass Loaded Vinyl A review of the performance and cost in acoustical applications Mass Loaded Vinyl A review of the performance and cost in acoustical applications Overview Driven by building codes and occupants expectations, many rooms in commercial and residential construction require

More information

Controlling the Transmission of Impact Sound through Floors

Controlling the Transmission of Impact Sound through Floors Construction Technology Update No. 35 Controlling the Transmission of Impact Sound through Floors by A.C.C. Warnock This Update presents guidelines for controlling the transmission of impact sound through

More information

INTER-NOISE 2006 3-6 DECEMBER 2006 HONOLULU, HAWAII, USA

INTER-NOISE 2006 3-6 DECEMBER 2006 HONOLULU, HAWAII, USA INTER-NOISE 2006 3-6 DECEMBER 2006 HONOLULU, HAWAII, USA An effective new approach to isolate plumbing stub-outs in residential construction Jeffrey P. Kwolkoski, P.E., INCE Bd. Cert. a D. L. Adams Associates,

More information

Test equipment for temperature and its reduction

Test equipment for temperature and its reduction Data sheet 90.2721 Page 1/6 Test equipment for temperature and its reduction Pt100 precision RTD temperature probe Calibrated temperature measuring chain with precision display device Calibrations as service

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

Acoustical proprieties of light brick walls and its effects on flanking transmission

Acoustical proprieties of light brick walls and its effects on flanking transmission Acoustical proprieties of light brick walls and its effects on flanking transmission G. Semprini a and L. Barbaresi b a University, DIENCA Dept. Facoltà di Ingegneria, Viale Risorgimento, 136 Bologna,

More information

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered Electrical Temperature Measurement DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered WIKA Data Sheet TE 60.75 Applications Machinery, plant and tank construction

More information

Material test chamber with mechanical convection

Material test chamber with mechanical convection FP series 400 Material test chambers Material test chamber with mechanical convection A BINDER material test chamber with mechanical convection of the FP series provides reliably short drying times and

More information

EcoTouch Insulation with PureFiber Technology

EcoTouch Insulation with PureFiber Technology PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

SPEECH INTELLIGIBILITY and Fire Alarm Voice Communication Systems

SPEECH INTELLIGIBILITY and Fire Alarm Voice Communication Systems SPEECH INTELLIGIBILITY and Fire Alarm Voice Communication Systems WILLIAM KUFFNER, M.A. Sc., P.Eng, PMP Senior Fire Protection Engineer Director Fire Protection Engineering October 30, 2013 Code Reference

More information

Acoustic Terms, Definitions and General Information

Acoustic Terms, Definitions and General Information Acoustic Terms, Definitions and General Information Authored by: Daniel Ziobroski Acoustic Engineer Environmental and Acoustic Engineering GE Energy Charles Powers Program Manager Environmental and Acoustic

More information

Fire Barriers & Fire Stopping

Fire Barriers & Fire Stopping Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire

More information

Mineral fibreglass insulation

Mineral fibreglass insulation Isover MULTIMAX 30 Specification code: MW - EN 13162 - T5 - MU1 - WS - WL(P) - AF r 5 TeChNICaL SPeCIFICaTION Insulating slabs made of Isover fibreglass wool. The production method is based on the fibering

More information

Ecophon Focus A. System range. Size, mm. XL 2000x600. XL 1800x600. XL 2400x600 T15 T24 Thickness (THK) Inst. Diagr. 1200x600 1200x1200 1600x600

Ecophon Focus A. System range. Size, mm. XL 2000x600. XL 1800x600. XL 2400x600 T15 T24 Thickness (THK) Inst. Diagr. 1200x600 1200x1200 1600x600 Ecophon Focus A For applications where a robust suspended ceiling system is required. Ecophon Focus A has an exposed grid system. Each tile is easily demountable. The systems consist of Ecophon Focus A

More information

pinta ACOUSTIC PANEL [1/7]

pinta ACOUSTIC PANEL [1/7] [1/7] Too much echo in the workplace? Staff unable to concentrate on their work? The answer is: ACOUSTIC PANEL. Service Call our telephone hotline for advice on your individual situation. Animated installation

More information

Fire Stopping and Sealing Product: Penetration Seals

Fire Stopping and Sealing Product: Penetration Seals UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. Phone : +44 1483 302130 Fax : +44 1483 302230 Email : Inform.NB@uk.ul.com Website

More information

Acoustic performance of dwellings and specifics for lightweight constructions Professor Eddy Gerretsen

Acoustic performance of dwellings and specifics for lightweight constructions Professor Eddy Gerretsen Acoustic performance of dwellings and specifics for lightweight constructions Professor Eddy Gerretsen Content Introduction Performance quantities Construction principles What performance is required Does

More information

Optiffuser. High-performance, high bandwidth lightweight 1D diffuser.

Optiffuser. High-performance, high bandwidth lightweight 1D diffuser. Optiffuser High-performance, high bandwidth lightweight 1D diffuser. General product information The Optiffuser comes in packs of four panels. Two positives and two negatives (see page 5) per package.

More information

VIPAC ENGINEERS & SCIENTISTS

VIPAC ENGINEERS & SCIENTISTS VIPAC ENGINEERS & SCIENTISTS Vipac Engineers & Scientists Limited A.B.N. 33 005 453 627 The Victorian Technology Centre Private Bag 16, Port Melbourne, VIC, 3207, AUSTRALIA Telephone +61 3 9647 9700, Facsimile

More information

The Case for Cross Laminated Timber: Part 2

The Case for Cross Laminated Timber: Part 2 Learning Objectives The Case for Cross Laminated Timber: Part 2 Opportunities and Challenges for a New Class of Timber Product 1. Review answers to common questions regarding the design and construction

More information

Flamesafe Firestopping Products. Firestopping Products. http://flamesafe.rectorseal.com

Flamesafe Firestopping Products. Firestopping Products. http://flamesafe.rectorseal.com Flamesafe Firestopping Products Firestopping Products http://flamesafe.rectorseal.com Engineering Tested By Fire RectorSeal Firestopping Products Since the birth of the firestopping industry almost three

More information

ROCKWOOL Rigid, Semi-rigid and Flexible Slabs are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation.

ROCKWOOL Rigid, Semi-rigid and Flexible Slabs are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation. Rigid, Semirigid and Flexible Slabs Versatile thermal acoustic insulation slabs ROCKWOOL are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation. They are manufactured

More information

fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors

fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors Roxul Safe n Sound Sound Control and Fire Safety From One Batt Insulation Roxul

More information

Testing laboratory HVAC. Test report No.: HP-06525-e

Testing laboratory HVAC. Test report No.: HP-06525-e Testing laboratory HVAC Test report No.: HP-62-e Objective: Sound measurements on an air distribution box and an air inlet Client: RoomAir AG Thurstrasse 14 Postfach 81 Frauenfeld Date: 26-6-2 This report

More information

Underwriters Laboratories Testing Information

Underwriters Laboratories Testing Information Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum

More information

Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise

Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise Baltimore, Maryland NOISE-CON 2010 2010 April 19-21 Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise Scott Harvey

More information

Ecophon Focus Ds. System range. XL 1800x600. Size, mm. XL 2400x600 T24 Thickness (THK) XL 2000x600. 1200x600 1200x1200 1600x600 M206, M208, M238

Ecophon Focus Ds. System range. XL 1800x600. Size, mm. XL 2400x600 T24 Thickness (THK) XL 2000x600. 1200x600 1200x1200 1600x600 M206, M208, M238 Ecophon Focus Ds For applications where a suspended ceiling with a concealed grid is required, but individual tiles must be easily demountable. Ecophon Focus Ds has a concealed grid and syetrical edge

More information

Module 3.7. Thermal bridging

Module 3.7. Thermal bridging Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal

More information

GPD Rubber Press Seals

GPD Rubber Press Seals GPD Rubber Press Seals Leading in in ideas SYSTEM-TECHNIK GPD Rubber Press Seals Design Available with a rubber thickness of 30 mm for sealing against non-pressing water and a rubber thickness of 60 mm

More information

Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings BUILDING ENVELOPE DESIGN BY ROXUL Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB Exterior

More information

Color logos Reverse logos Acoustics Black only logos

Color logos Reverse logos Acoustics Black only logos Acoustics ACOUSTICS General The basic purpose of architectural acoustics is to provide a satisfactory environment in which the desired sounds are clearly heard by the intended listeners and the unwanted

More information

Fire Protection. CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8. Floor Assembly No.

Fire Protection. CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8. Floor Assembly No. BULLETIN No. 28 (a) Fire Protection CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8 Floor Assembly No. NRC764-FF22 Fire Endurance Period 1 74 minutes Sound

More information

INSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings

INSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings INSULATION FOR PRE-ENGINEERED METAL BUILDINGS ROXUL SAFE 55 & 65 and ROXUL PLUS MB Insulation for Pre-Engineered Metal Buildings ROXUL SAFE AND ROXUL PLUS MB Exterior Wall Insulation for Pre-Engineered

More information

Dubai Municipality Standard DMS 1: Part 5: 2004

Dubai Municipality Standard DMS 1: Part 5: 2004 Specification for precast concrete blocks Part 5: Normal-weight concrete-polystyrene sandwich masonry blocks Issue Date Revision Revision Description Prepared by Approved by Authorized by 19/12/2004 Issue

More information

CASE STUDY. Sarakasi Theatre Nairobi, Kenya Room Acoustical Measurements and Modelling. Africa Room Acoustics DIRAC and ODEON

CASE STUDY. Sarakasi Theatre Nairobi, Kenya Room Acoustical Measurements and Modelling. Africa Room Acoustics DIRAC and ODEON CASE STUDY Sarakasi Theatre Nairobi, Kenya Room Acoustical Measurements and Modelling Africa Room Acoustics DIRAC and ODEON In November 2008, room acoustical measurements were performed inside the Sarakasi

More information

Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings Building Envelope Design using ROXUL Building Envelope Design using ROXUL (BEDR ) FIREWALL and ROXUL PLUS MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB

More information

Technical Application Document. Hilti HIT-RE 500-SD

Technical Application Document. Hilti HIT-RE 500-SD Technical Application Document Technical Evaluation Report 3/10-649 Injection system for rebar connections Hilti HIT-RE 500-SD Subject to European Technical Approval ATE-09/0295 Holder of approval: HILTI

More information

Metal Pressfitting Pipe Systems

Metal Pressfitting Pipe Systems VdS Guidelines for water extinguishing systems VdS 2100-26-3en Requirements and test methods Part 3: Additional provisions for Pipe Systems made of galvanized steel VdS 2100-26-3en : 2012-04 (01) Publishing

More information

FIRESTOPPING & SMOKE SEALS

FIRESTOPPING & SMOKE SEALS SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of

More information

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER

TPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER PSUM These technical specifications determinate a range of manufactured sizes and models of fire shutters (further only shutters)

More information

Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G

Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G EN 215-1 HD 1215-2 Application RA 2910 built-in sensor RA 2920 tamperproof RA 5062 remote sensor temperature adjuster RA-FN

More information

Wardle Storeys. Reducing Rain Noise on Profiled Metal Roofing Systems Using DEDPAN DS2020 RDV

Wardle Storeys. Reducing Rain Noise on Profiled Metal Roofing Systems Using DEDPAN DS2020 RDV Wardle Storeys Reducing Rain Noise on Profiled Metal Roofing Systems Using DEDPAN DS2020 RDV Wardle Storeys (Blackburn) Ltd has developed a simple but effective new solution to significantly reduce rain

More information

Roxul Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK DD) Page 1 October 2013

Roxul Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK DD) Page 1 October 2013 Master Guide Specification (CAVITYROCK DD) Page 1 ROXUL GUIDE NOTE: This master specification section is based on ROXUL INC., CAVITYROCK DD. Standard application: Cavity wall. ROXUL GUIDE NOTE: This master

More information

LABORATORY MEASUREMENTS ON THE EFFICIENCY OF SOUND REDUCING FURNITURE PADS OF TYPE SILENT SOCKS

LABORATORY MEASUREMENTS ON THE EFFICIENCY OF SOUND REDUCING FURNITURE PADS OF TYPE SILENT SOCKS Report 08-113-R1 06/11/2008 4 pages, 1 appendix Akustikverkstan AB, St Bryne, 531 94 Järpås, tel +46 (0)6-59 37 99 pontus.thorsson@akustikverkstan.se LABORATORY MEASUREMENTS ON THE EFFICIENCY OF SOUND

More information

This European technical approval

This European technical approval Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors.

Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors. Fire & Soundproofing Insulation Roxul SAFE N SOUND Fire and Soundproofing Insulation for Interior Partition Walls and Floors. Roxul SAFE N SOUND Sound control and fire safety from one batt Insulation.

More information

Testing Panasonic s WM-61A Mike Cartridge

Testing Panasonic s WM-61A Mike Cartridge Tube, Solid State, Loudspeaker Technology Article prepared for www.audioxpress.com Testing Panasonic s WM-61A Mike Cartridge By George Danavaras This microphone study measures how distortion affects performance.

More information

Colorcoat Technical Paper Acoustic performance of pre-finished steel cladding systems

Colorcoat Technical Paper Acoustic performance of pre-finished steel cladding systems CI/SfB (4-) Nh2 (A3j) February 213 CI/SfB (4-) Nh2 (A3j) December 212 Colorcoat Technical Paper Acoustic performance of pre-finished steel cladding systems ACOUSTIC DESIGN Tata Steel has been developing

More information

Product Information Sheet

Product Information Sheet Distributed by Thermal Products Company, Inc. Product Information Sheet FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts) Introduction Unifrax s FyreWrap Elite 1.5 Duct Insulation

More information

C05. S03. P02 P08 FireWall. Including C05. S01. P02 Specialist partitions introduction

C05. S03. P02 P08 FireWall. Including C05. S01. P02 Specialist partitions introduction C05. S03. P02 P08 Including C05. S01. P02 Specialist partitions introduction C05 Specialist partitions Introduction Specialist partitions This section details specialist lightweight systems where high-security,

More information

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct

More information

MEMBRANE VACUUM MINI PUMPS

MEMBRANE VACUUM MINI PUMPS MEMBRANE VACUUM MINI PUMPS The mini pumps described in this page are membrane-type. They can be used both as vacuum pumps and compressors. In the latter version they can supply compressed air 100% oil-free

More information

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional

More information

TENSIONMETER ** code 183_LNRSTW **

TENSIONMETER ** code 183_LNRSTW ** Electronic tension meter for applications in textile and wire industry. 9 Tension ranges from 0.1-200 cn to 5-50 dan. Versatile instruments usable for applications in textile industry: e. g. 50 up to max.

More information

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method

More information

Composite Panel Firewall Systems

Composite Panel Firewall Systems Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.

More information

Built to Last. Built for Beauty. Good. Solid. Logix. TM

Built to Last. Built for Beauty. Good. Solid. Logix. TM Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a

More information

Façade acoustic design strategy Proposed residential development Irvin Avenue, Saltburn

Façade acoustic design strategy Proposed residential development Irvin Avenue, Saltburn strategy Proposed residential development Report Number: 1420.1 Version: A Date: 13 th October 2008 Prepared by: Checked by: Andrew Gibson Jack Harvie-Clark Apex Acoustics Limited Design Works William

More information

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court

More information

Manual lifting and handling

Manual lifting and handling Manual lifting and handling When installing British Gypsum products and systems care should be taken to ensure that appropriate methods of handling and lifting are adopted. The following guidance details

More information

Climate chamber with illumination

Climate chamber with illumination KBWF series (E5.2) Climate chambers with illumination Climate chamber with illumination The BINDER climate chamber with illumination of the KBW series achieves homogeneous light distribution with its natural

More information

Rockwool Cladding Roll

Rockwool Cladding Roll Rockwool Cladding Roll High performance industrial insulation has been specifically developed for use in lightweight cladding applications to commercial or industrial framed buildings. Cladding Roll U/F

More information

Characterization of acoustics in open offices - four case studies

Characterization of acoustics in open offices - four case studies Characterization of acoustics in open offices - four case studies J. S Keränen, P. Virjonen and V. O Hongisto Finnish Institute of Occupational Health, Lemminkäisenkatu 14-18 B, 5 Turku, Finland jukka.keranen@ttl.fi

More information