Evidence of Performance Airborne sound insulation of fire rated products
|
|
- Lora Fisher
- 7 years ago
- Views:
Transcription
1 Evidence of Performance Airborne sound insulation of fire rated products Test Report PR01 (PB 01-E03-04-en-02) Client Product Designation Material Sealing material Diameter of opening Basic element Hilti Entwicklungsgesellschaft mbh Hiltistr Kaufering Germany Pipe DN 60 resp. cable bunch with Hilti FS-ONE MAX in penetration Hilti FS-ONE MAX Single component, water based fire rated-sealant 100 mm (1 and/or. 2 pcs.) Metal stud partition Double stud framing, double clad Basis EN ISO : A1:2012 EN ISO : 2010 EN ISO : 2013 Additional ASTM E ASTM E Test report no PR01 (PB 01-E03-04-de-02) dated Instructions for use This test report serves to verify the sound insulation of fire rated products. ift Rosenheim Dr. Joachim Hessinger, Dipl.-Phys. Head of Testing Department Building Acoustics Weighted normalized sound level difference of small building elements D n,e,w Spectrum adaption terms C and C tr Pipe DN 60 with Hilti FS-ONE MAX D n,e,w (C; C tr ) = 71 (-4; -9) db Pipe DN 60 + cable bunch with Hilti FS-ONE MAX D n,e,w (C; C tr ) = 70 (-3; -8) db Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer Building Acoustics Validity The data and results given relate solely to the tested and described specimen. Testing the sound insulation does not allow any statement to be made on any further characteristics of the present construction regarding performance and quality. Notes on publication The ift Guidance Sheet "Conditions and Guidance for the Use of ift Test Documents" applies. The cover sheet can be used as abstract. Contents The test report contains a total of 17 pages: 1 Object 2 Procedure 3 Detailed results 4 Instructions for use Data sheets (5 pages) / 695
2 Evidence of Performance Airborne sound insulation of fire rated products Page 2 of 17 1 Object 1.1 Description of test specimen Product Pipe DN 60 resp. cable bunch with Hilti FS-ONE MAX in penetration Product designation Hilti FS-ONE MAX Material Single component, water based fire rated-sealant Type of mineral wool boards ISOVER Protect BSP 40 Test variants - Test of double stud framing without openings - Test with opening Ø = 100 mm and installed pipe DN 60 with Hilti FS-ONE MAX - Test with 2 openings Ø = 100 mm and installed pipe and cable bunch with Hilti FS-ONE MAX Metal stud partition Manufacturer* Metal stud partition mounted by ift Laboratory for Building Acoustics Date of manufacture 21st of October 2014 Sampling by ift Laboratory for Building Acoustics at builder s merchant Dimensions (W x H) 1,250 mm 1,500 mm Total thickness 155 mm Structure 50 mm metal studs, mineral fibre insulation 40 mm 5 mm air 50 mm metal studs, mineral fibre insulation 40 mm Stud framing metal studs from 50 mm C-wall channel section (CW 50x50x06) Cladding Knauf Piano sound insulation board F, screw-fastened Cavity insulation ISOVER Protect BSP 40, mounted between stud framing Penetration Clear opening Diameter 100 mm (1 and/or 2 pcs) Built-in components (test variant 1) Pipe Steel pipe DN 60 (60 x 5.3 mm) Insulation* ISOVER darning wool (mineral wool) Fire rated product* Hilti fire rated-sealant FS-ONE MAX Installation - Pipe placed into opening, pipe projects on both sides approx. 235 mm from partition, the open ends of the pipe were closed on both sides - Annular gap filled with ISOVER darning wool and sealed on both sides with Hilti fire rated-sealant FS-ONE MAX, insertion depth approx. 13 mm (approx. ½ inch)
3 Evidence of Performance Airborne sound insulation of fire rated products Page 3 of 17 Built-in components (test variant 2) Together with test variant 1 Cable bunch* each 1 x NYY-J 5x1.5 RE N2XH-J 5x1.5 RE NYCWY 4 x 185SM/95 Telecommunication cable bunch Empty conduit steel Ø 16 mm Empty conduit plastic Ø 16 mm Insulation* ISOVER darning wool (mineral wool) Fire rated product* Hilti fire rated-sealant FS-ONE MAX Installation - Cable bunch fixed with cable ties and placed into opening, the cable sections project on both sides approx. 150 mm 250 mm from partition wall, the open ends of the empty conduits were closed on both sides - Annular gap filled with ISOVER darning wool and sealed on both sides with Hilti fire rated-sealant FS-ONE MAX, insertion depth approx. 13 mm (approx. ½ inch) The description is based on inspection of the test specimen at ift Laboratory for Building Acoustics. Item designations / numbers as well as material specifications were provided by the client. Additional data provided by the client are marked with * 1.2 Mounting to test rig Test rig Mounting of test specimen Mounting conditions Sealing Drying time Window test rig Z-Wall with suppressed flanking transmission acc. to EN ISO : 2010; the test rig includes a mounting frame with a continuous acoustic break which is sealed in the test opening with closed-cell permanently resilient sealant. Mounted by ift Laboratory for Building Acoustics and employees of the client. The wall element was mounted by employees of ift Laboratory for Building Acoustics. Wall element mounted in test opening of window test rig ( Zwall ) on source room. The acoustic separation wasn t bridged. The wall element was sealed on both sides with sealant Type Perennator 2001 S grey. Built-in components were sealed towards partition with elastic sealant. Rendering of the gypsum plasterboards was not necessary because the opening was in one board (without joints). Sealant (with the help of hot air blowers) approx. 0.5 h
4 Evidence of Performance Airborne sound insulation of fire rated products Page 4 of Representation of test specimen The structural details were examined solely on the basis of the characteristics to be classified. Source room \\sift01\iftello_daten_rw\ablage\vo \projekt\pr01\prüfberichte\ pr01 PB 01 Fig. 1 Photos of metal stud partition mounted to window test rig, taken by ift Laboratory for Building Acoustics Source room Fig. 2 Receiving room Mounting of test variant 1 Receiving room
5 Evidence of Performance Airborne sound insulation of fire rated products Page 5 of 17 Source room \\sift01\iftello_daten_rw\ablage\vo \projekt\pr01\prüfberichte\ pr01 PB 01 fig 3 Mounting of test variant 2 Cable bunch fig 4 Receiving room Pipe Details of built-in components
6 Evidence of Performance Airborne sound insulation of fire rated products Page 6 of 17 2 Procedure 2.1 Sampling Sampling Quantity Manufacturer Manufacturing plant Batch number Date of sampling Procedure of sampling \\sift01\iftello_daten_rw\ablage\vo \projekt\pr01\prüfberichte\ pr01 PB 01 Responsible for sampling Delivery at ift ift registration number Carton box Fig. 5 The samples were selected by the client 1 carton box with 12 cartridges ea. 300 ml Hilti Industriegesellschaft für Befestigungssysteme mbh Hilti Werk 6, fire rated production, Hilti Str.6, Kaufering B # July 2014 Official sampling on 29 July 2014 at production plant by auditors Mr. Rüdiger Dederichs (FM) and Mr. Karl Bohn (UL USA). The sealing (see fig. 5) of the marked-up samples was removed by an employee of ift Laboratory for Building Acoustics on the date of testing ( ). Mr. Stefan Rump 22 October 2014 by the client Carton box + single cartridge with batch number delivered samples, sealed and marked up
7 Evidence of Performance Airborne sound insulation of fire rated products Page 7 of Method(s) Basis EN ISO : A1 : 2012 Acoustics; Laboratory measurement of sound insulation of building elements - Part 1: Application rules for specific products (ISO :2010+Amd.1:2012) EN ISO :2010 Acoustics; Laboratory measurement of sound insulation of building elements - Part 2: Measurement of airborne sound insulation (ISO :2010) EN ISO : 2013 Acoustics; Rating of sound insulation in buildings and of building elements - Part 1: Airborne sound insulation Correspond/s to the national German standard/s: DIN EN ISO : , DIN EN ISO : and DIN EN ISO : Additional basis ASTM E Standard test method for laboratory measurement of airborne sound transmission loss of building partitions and elements ASTM E Classification for rating sound insulation Boundary conditions Deviation Test noise Measuring filter As specified by the standards. Upon request by the client additional evaluations of the STC were carried out in accordance with ASTM E There are no deviations from the test method/s and/or test conditions acc. to EN ISO The volume of the test room falls below the minimum volume of 80 m³ as defined in ASTM E The linear flow resistance of the insulating material was not determined. Pink noise One-third-octave band filter
8 Evidence of Performance Airborne sound insulation of fire rated products Page 8 of 17 Measurement limits Low frequencies Background noise level Maximum sound insulation The dimensions of the receiving room were smaller than recommended for testing in the frequency range from 50 Hz to 80 Hz as per EN ISO :2010 Annex A (informative). A moving loudspeaker was used. The background noise level in the receiving room was determined during measurement and the receiving room level L 2 corrected by calculation as per EN ISO : 2010 Clause 4.3. For evaluation of the normalized level difference of the penetration through the wall the sound insulation of the wall alone was taken as maximum sound insulation. The difference between normalized sound level difference and maximum sound insulation of the test setup is partly smaller than 15 db. For normalized sound level difference it was corrected by calculation as per EN ISO :2010 Annex A. The graphs presented in the Annex include maximum sound insulation. Measurement of reverberation time Measurement equation A Measurement of sound level difference Measurement equation Measurement equation D n,e Arithmetical mean: 6 measurements each of 2 loudspeaker positions with rotating microphone (total of 12 measurements). V A = 0, 16 m² T Minimum of 2 loudspeaker positions and rotating microphones. S R = L1 L lg db A A, = L1 L2 +10 lg in db A 0 D n e KEY A Equivalent absorption area in m² A 0 Reference absorption area (10 m²) L 1 Sound pressure level source room in db L 2 Sound pressure level receiving room in db R Sound reduction index in db D n,e Normalized sound level difference of small building elements in db T Reverberation time in s V Volume of receiving room in m³ S Testing area of the specimen in m²
9 Evidence of Performance Airborne sound insulation of fire rated products Page 9 of Test apparatus Device Type Manufacturer Integrating sound meter Type Nortronic 830 Norsonic-Tippkemper Microphone preamplifiers Type 1201 Norsonic-Tippkemper Microphone unit Type 1220 Norsonic-Tippkemper Calibrator Type 1251 Norsonic-Tippkemper Dodecahedron loudspeakers Own production - Amplifier Type E120 FG Elektronik Rotating microphone boom Own production / Type 231-N-360 Norsonic-Tippkemper The ift Laboratory for Building Acoustics participates in comparative measurements at the Physikalisch-Technische Bundesanstalt (PTB) in Braunschweig every three years, the last one was in April The sound level meter used, Series No , was calibrated by the Dortmund Eichamt (calibration agency) on 8 March The calibration is valid until 31 December The sound level meter used, Series No , was DKD calibrated by the company Norsonic Tippkemper (DKD - Deutscher Kalibrierdienst German Calibration Service ) on 14 March Testing Date 22 October 2014 Operating Testing Officer Mr. Stefan Bacher
10 Evidence of Performance Airborne sound insulation of fire rated products Page 10 of 17 3 Detailed results The values of the measured sound reduction index of the wall element as well as the measured normalized sound level difference of small building elements of the tested elements are plotted as a function of frequency in the annexed data sheet and tabled. They are used to calculate the weighted sound reduction index R w / the weighted normalized sound level difference D n,e,w and the spectrum adaptation terms C and C tr for the frequency range 100 Hz to 3,150 Hz, as described in Table 1. Additional to the rating according to EN ISO a weighting according to ASTM E was carried out. The sound transmission class STC according to ASTM E for the frequency range from 125 Hz up to 4,000 Hz was calculated as follows: Table 1 Results of acoustic tests Data Component / Modification Testing standard / Results in db / Reference surface sheet No. EN ISO EN ISO E EN ISO E Normalized sound level difference of Sound insulation of penetration, evaluation with respect to a reference Sound insulation of the element without penetrations penetrations area of S=1.88 m² 1) D n,e,w (C; C tr ) R w (C; C tr ) STC R w (C; C tr ) STC A 0 = 10 m² S = 1.88 m² S = 1.88 m² S = 1.88 m² S = 1.88 m² 1 Metal stud partition (-3; -8) 59 2 Metal stud partition with bore; pipe DN 60 with Hilti fire rated-sealant FS-ONE MAX 3 Metal stud partition with bole; pipe DN 60 with Hilti fire rated-sealant FS-ONE MAX 4 Metal stud partition with 2 bores; pipe DN 60 and cable bunch with Hilti fire rated- Sealant FS-ONE MAX 5 Metal stud partition with 2 bores; pipe DN 60 and cable bunch with Hilti fire rated- Sealant FS-ONE MAX (-3;-8) (-4;-9) (-2;-8) (-3;-8)
11 Evidence of Performance Airborne sound insulation of fire rated products Page 11 of 17 1) For the evaluation of the sound insulation of the penetration as a weighted sound reduction index and STC the measured values of the normalized sound level difference (D n,e resp. D n,e,w evaluated with a correction of maximum sound insulation according to Clause 2.2) were evaluated with a reference area of 1.88 m². Referring to the tested values presented in Table 1 line 2 to 5 a correction for maximum sound insulation was performed by calculation (see Clause 2.2). Without this correction the following values were determined for the sound insulation of the wall element with penetrations: Table 2 Results of acoustic tests (additional information) Data Component / Modification Testing standard / Results in db / sheet Reference area No. EN ISO E Sound insulation of the wall element with penetrations - Metal stud partition with bore; pipe DN 60 with Hilti fire rated-sealant FS-ONE MAX - Metal stud partition with 2 bores; pipe DN 60 and cable bunch with Hilti fire rated-sealant FS-ONE MAX (without correction for a maximum sound insulation) R w (C; C tr ) STC S = 1.88 m² S = 1.88 m² 62 (-3; -8) (-3; -8) 61 4 Instructions for use 4.1 Safety margin according to DIN 4109 Basis DIN 4109: Sound insulation in buildings, requirements and verifications This test report is not an evidence of suitability as per DIN 4109: A calculated value is not indicated. 4.2 Constructions products list As set out by the German Bauregelliste (Construction Products List), evidence of compliance in Germany is possible only in the form of an AbP (national technical test certificate). This test report cannot be used as a subtest to be included in a national technical test certificate (AbP).
12 Evidence of Performance Airborne sound insulation of fire rated products Page 12 of Test standards The standard series EN ISO 10140:2010 supersedes those, until the respective date, applicable parts of the standards series EN ISO 140 which describe laboratory tests. According to the two standard series, the test methods are identical. Assessments as per ASTM E were based on sound insulation testing as per EN ISO (previous EN ISO 140-3). For some details there are deviations from test standard ASTM E 90-09, in particular as regards the required room volume (min. 80 m³). ift Rosenheim Laboratory for Building Acoustics
13 Sound reduction index according to ISO Laboratory measurements of airborne sound insulation of building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition without opening Total thickness Area related mass 155 mm 50.0 kg/m² Test date 22 October 2014 Test surface S 1.25 m x 1.50 m = 1.88 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V R = 67.5 m³ Maximum sound reduction index (not specified) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 19 C / 57% RH / 959 hpa x f in Hz R in db , , , , , , , , x Background noise level difference < 6 db Sound reduction index R in db Rating according to EN ISO (in third octave bands): R w (C; C tr ) = 62 (-3; -8) db C 50-3,150 = -4 db; C 100-5,000 = -2 db; C 50-5,000 = -3 db C tr,50-3,150 = -13 db; C tr,100-5,000 = -8 db; C tr,50-5,000 = -13 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 13 of 17 Data Sheet 1 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve Frequency range corresp. to reference curve as per EN ISO Frequency f in Hz Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000
14 Sound reduction index according to ISO Laboratory measurements of airborne sound insulation of building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition with opening Ø = 100 mm Filled with pipe DN 60 with Hilti fire-rated sealant FS- ONE MAX on both sides Special features: A correction for maximum sound insulation by calculation of test value was performed Test date 22 October 2014 Test surface S 1.25 m x 1.50 m = 1.88 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V R = 67.5 m³ Maximum sound reduction index R w,max = 62 db (related to test area) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 20 C / 60% RH / 959 hpa x f in Hz R in db 50 > > > > > > > > > > > > > ,000 > ,250 > ,600 > ,000 > ,500 > ,150 > ,000 > ,000 > 71.6 x Background noise level difference < 6 db Flanking transmission effect Sound reduction index R in db Rating according to EN ISO (in third octave bands): R w (C; C tr ) = 63 (-3; -8) db C 50-3,150 = -4 db; C 100-5,000 = -2 db; C 50-5,000 = -3 db C tr,50-3,150 = -13 db; C tr,100-5,000 = -8 db; C tr,50-5,000 = -13 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 14 of 17 Data Sheet 2 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve maximum sound insulation Frequency range corresp. to reference curve as per EN ISO Frequency f in Hz Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000
15 Normalized sound level difference acc. to ISO Laboratory measurements of airborne sound insulation of small building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition with opening Ø = 100 mm Filled with pipe DN 60 with Hilti fire-rated sealant FS- ONE MAX on both sides Special features: A correction for maximum sound insulation by calculation of test value was performed Test date 22 October 2014 Reference absorption area A 0 = 10 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V R = 67.5 m³ Maximum sound insulation D n,e,w,max = 70 db (related to A 0 = 10 m²) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 16 C / 57% RH / 966 hpa x f in Hz D n,e in db 50 > > > > > > > > > > > > > ,000 > ,250 > ,600 > ,000 > ,500 > ,150 > ,000 > ,000 > 78.9 x Background noise level difference < 6 db Flanking transmission effect Normalized sound level difference D n,e in db Frequency f in Hz Rating according to EN ISO (in third octave bands): D n,e,w (C; C tr ) = 71 (-4; -9) db C 50-3,150 = -5 db; C 100-5,000 = -3 db; C 50-5,000 = -4 db C tr, = -14 db; C tr,100-5,000 = -9 db; C tr,50-5,000 = -14 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 15 of 17 Data Sheet 3 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve maximum sound insulation Frequency range corresp. to reference curve as per EN ISO Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000
16 Sound reduction index according to ISO Laboratory measurements of airborne sound insulation of building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition with 2 openings Ø = 100 mm Filled with pipe DN 60 resp. cable bunch with Hilti firerated sealant FS-ONE MAX on both sides Special features: A correction for maximum sound insulation by calculation of test value was performed Test date 22 October 2014 Test surface S 1.25 m x 1.50 m = 1.88 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V R = 67.5 m³ Maximum sound reduction index R w,max = 62 db (related to test area) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 20 C / 59% RH / 959 hpa x f in Hz R in db 50 > 34, ,7 80 > 30, ,4 125 > 44,3 160 > 46,4 200 > 44,4 250 > 50,9 315 > 56,0 400 > 60,9 500 > 63,8 630 > 64,5 800 > 65,4 1,000 65,8 1,250 65,6 1,600 66,3 2,000 66,5 2,500 > 68,2 3,150 > 68,3 4,000 > 70,9 5,000 > 70,9 x Background noise level difference < 6 db Flanking transmission effect Sound reduction index R in db Frequency f in Hz Rating according to EN ISO (in third octave bands): R w (C; C tr ) = 62 (-2; -8) db C 50-3,150 = -5 db; C 100-5,000 = -1 db; C 50-5,000 = -4 db C tr,50-3,150 = -14 db; C tr,100-5,000 = -8 db; C tr,50-5,000 = -14 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 16 of 17 Data Sheet 4 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve maximum sound insulation Frequency range corresp. to reference curve as per EN ISO Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000
17 Normalized sound level difference acc. to ISO Laboratory measurements of airborne sound insulation of small building elements Client: Hilti Entwicklungsgesellschaft mbh, Kaufering (Germany) Product designation Hilti FS-ONE MAX Design of test specimen 5 mm Air Metal stud partition with 2 openings Ø = 100 mm Filled with tube DN 60 resp. cable bunch with Hilti firerated sealant FS-ONE MAX on both sides Special features: A correction for maximum sound insulation by calculation of test value was performed Test date 22 October 2014 Reference absorption area A 0 = 10 m² Partition wall Double-leaf concrete wall, insert frame Test noise pink noise Volumes of test rooms V S = 104 m³ V E = 67.5 m³ Maximum sound insulation D n,e,w,max = 70 db (related to A 0 = 10 m²) Mounting conditions Element inserted in test opening closed by a wall unit. Climate in test rooms 20 C / 59% RH /959 hpa x f in Hz D n,e in db 50 > > > > > > > > > > > , , , , ,500 > ,150 > ,000 > ,000 > 78.2 x Background noise level difference < 6 db Flanking transmission effect Normalized sound level difference D n,e in db Rating according to EN ISO (in third octave bands): D n,e,w (C; C tr ) = 70 (-3; -8) db C 50-3,150 = -5 db; C 100-5,000 = -2 db; C 50-5,000 = -4 db C tr,50-3,150 = -15 db; C tr,100-5,000 = -8 db; C tr,50-5,000 = -15 db Test report no.: PR01 (PB 01-E03-04-en-02) Page 17 of 17 Data Sheet 5 ift Rosenheim, Laboratory for Building Acoustics Shifted reference curve Measurement curve maximum sound insulation Frequency range corresp. to reference curve as per EN ISO Frequency f in Hz Mr. Stefan Bacher, Dipl.-Ing. (FH) Operating Testing Officer 4000
Test Report. Nr. 1370-001-12 dated 16.02.2012. Sound Absorption Coefficient in the Reverberation Room. Lammengatan 2 SE-360 30 Lammhult Sweden
Test Report Nr. 1370-001-12 dated 16.02.2012 Sound Absorption Coefficient in the Reverberation Room Customer: Abstracta AB Lammengatan 2 SE-360 30 Lammhult Sweden Test Object: Arrangement of Acoustic Panels
More informationLightweight Partition Design for Residential and Commercial Buildings
Lightweight Partition Design for Residential and Commercial Buildings Stanley D. Gatland II, CertainTeed Corporation, Valley Forge, Pennsylvania Guidelines are presented for the design and proper installation
More informationAirborne Sound Insulation
Airborne Sound Insulation with XL2-TA Sound Level Meter This application note describes the verification of the airborne sound insulation in buildings with the XL2-TA Sound Level Meter. All measurements
More informationCERTIFICATE OF APPROVAL No CF 5055 ARABIAN VERMICULITE INDUSTRIES
CERTIFICATE OF APPROVAL No CF 5055 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 1 st Industrial Area,
More informationASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 8 TEST : Whisper Industries, L.L.C. Report Date: August 14, 2008 Date: July 9, 2008 Number: RESULT
More informationSOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS
NOISE TECHNICAL FACT SHEET FACT SHEET 5 SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS The sound insulation of exterior walls and roof-ceiling systems refers to their ability to reduce external
More informationSOUND TRANSMISSION CLASS TEST REPORT Series/Model: VL-WDW11 VistaLuxe Awning
ACOUSTIC Page 1 of 5 SOUND TRANSMISSION CLASS TEST REPORT Series/Model: VL-WDW11 VistaLuxe Awning Prepared for: Koble & Kolbe Millwork Co., Inc. Attn: Ms. Tasha Verhasselt 1323 South 11th Avenue Wausau,
More informationTremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
More informationSOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR1 Teutonic Outswing Vinyl Entrance Door
ACOUSTIC Page of 5 9/8/204 SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR Teutonic Outswing Vinyl Entrance Door Prepared for: Kolbe and Kolbe Millwork Co., Inc. Attn: Ms. Tasha Verhasselt 323
More informationSOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR2 Teutonic Outswing Vinyl Entrance Door
ACOUSTIC Page of 5 SOUND TRANSMISSION CLASS TEST REPORT Series/Model: T-DR2 Teutonic Outswing Vinyl Entrance Door Prepared for: Kolbe and Kolbe Millwork Co., Inc. Attn: Ms. Tasha Verhasselt 323 South th
More informationEuropean Organisation for Technical Approvals
Warrington Certification Limited, Holmesfield Road, Warrington, WA1 2DS Tel. +44 (0) 1925-646777 Fax +44 (0) 1925-646667 Member of EOTA Authorised and notified according to Article 10 of the Council Directive
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010. TYPE: Single Hung Window
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 6010 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC B2706.01
More informationE6211.02-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: TREX COMPANY, LLC. Series/Model: Trex Seclusion
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: TREX COMPANY, LLC Series/Model: Trex Seclusion Type: Sound Barrier Fence Summary of Test Results Data File No. Description STC OITC E6211.01 Trex
More informationEvidence of Performance. Class 2. Class 5A. Class C4 / B4. Test Report No. 15-003655-PR01. ift Rosenheim 16.12.2015
Evidence of Performance Test Report No. 15-003655-PR01 (PB-A01-02-en-01) Client Product Designation Performance-relevant product details Overall dimensions (W x H) Special features Alüminyum San. Tic.
More informationSection 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01
Section Built-up Metal Roofs Rail and bracket system Product: Earthwool FactoryClad range Bu01 Standing seam system Product: Earthwool FactoryClad range and Earthwool Universal Slab Bu02 Built-up Metal
More informationProRox Slabs (formerly known as RW slabs)
Slabs (formerly known as RW slabs) Versatile thermal acoustic insulation slabs ROCKWOOL's Slabs are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation. They are
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: T24000. TYPE: Two-Lite Storefront
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: T24000 TYPE: Two-Lite Storefront Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC C5774.01
More informationManual Analysis Software AFD 1201
AFD 1200 - AcoustiTube Manual Analysis Software AFD 1201 Measurement of Transmission loss acc. to Song and Bolton 1 Table of Contents Introduction - Analysis Software AFD 1201... 3 AFD 1200 - AcoustiTube
More informationPassive Fire Protection
Firestopping Passive Fire Protection FS20 Firestop Compound 6 hour fire rated penetration seals for electrical and mechanical services FS20 Firestop Compound FS20 Firestop Compound is a Fire-Rated Penetration
More informationENVIRONMENTAL INFORMATION APR 1200 products are made from glass mineral wool, one of the most environmentally friendly insulants available.
APR 1200 Acoustic Partition Roll CI/Sfb Ref: APR002 Glass mineral wool roll designed to provide high levels of sound insulation in walls and floors to meet Part E (England & Wales) and Section 5 (Scotland)
More informationAMF Line; wall absorbers Wall mounted acoustic designs PERFORMANCE CEILINGS. M ore s c op e f or i n n ovat i on MADE IN GERMANY
PERFORMANCE CEILINGS M ore s c op e f or i n n ovat i on AMF Line; wall absorbers Wall mounted acoustic designs MADE IN GERMANY 138568_Prospekt Wandabsorber_GB int.indd 1 Acoustic elements on the wall
More informationCERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
More informationRockwool Flexi Insulation Application Guide
Pitched roof Rafters InterMediate floors INTERNAL partitions external Framed walls separating floors Separating Walls Rockwool Flexi Insulation Application Guide Ground floor The perfect fit for any framed
More informationSealfire W1000 Compound. (2 references for the same product) Fire Stopping and Sealing Product: Penetration Seals
UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. Phone : +44 1483 302130 Fax : +44 1483 302230 Email : Inform.NB@uk.ul.com Website
More informationFiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationThe Role of Acoustics in Curtain Wall Design:
The Role of Acoustics in Curtain Wall Design: Strategies to Achieve Desired Performance Criteria April 22, 2015 John LoVerde, Principal VENEKLASEN ASSOCIATES, INC. Goals Basics of Acoustics Ratings in
More informationSound absorption and acoustic surface impedance
Sound absorption and acoustic surface impedance CHRISTER HEED SD2165 Stockholm October 2008 Marcus Wallenberg Laboratoriet för Ljud- och Vibrationsforskning Sound absorption and acoustic surface impedance
More informationSection 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with
Section Separating Floors Timber frame floor with I-Beams Product: Earthwool Acoustic Roll and Floorfoam Easy Edge Strip Timber frame floor with solid timber joists Product: Earthwool Acoustic Roll and
More informationPAGE 2. Figure 1: Difference between PWL ins and SPL 1m
PAGE 1 Pipe noise J.H. Granneman and R.P.M. Jansen, Peutz Consulting Engineers, The Netherlands, emphasise the need for an adequate pipe noise control procedure, with reference to the design phase, insulation
More informationTechnical Data Sheet W13. Edition 2005-03. Knauf Fire Walls
Technical Data Sheet W13 Edition 2005-03 Knauf Fire Walls Knauf Fire Wall A2 - GKF two/ three layer cladding Knauf Fire Wall A1 - Fireboard two layer cladding The structural, statical properties, and characteristic
More informationEnclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: sales@durasystems.com. The Passive Fire Protection Specialists
Enclosures Sturdy single and double wall fire protection construction Impact resistant Fast & easy installation Pre-manufactured and modular Available in galvanized, stainless steel & other specialty metals
More informationCheck-list for auditors. Audit visit at candidate registered laboratories
Check-list for auditors Audit visit at candidate registered laboratories 1 Contents Introduction Laboratory documentation required by the standard(s), available for inspection by the auditor Items to be
More informationFireWall. High performance fireresistant. FireWall. www.british-gypsum.com
FireWall FireWall High performance fireresistant wall system FireWall is a non-loadbearing wall which provides up to 240 minutes fire resistance. It is used in certain ground floor basement situations
More informationROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016
Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.
More informationEvidence of Performance Resistance to wind load Watertightness Air permeability
Evidence of Performance Resistance to wind load Watertightness Air permeability Test Report 102 43093/1e Client Product YILDIZPEN PLASTIK SAN. VE TIC. LTD. STI. A.O.S.B 10039 Street No:18 Çigli Izmir Turkey
More informationRetardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318
Fire Barrier Moldable Putty+ Pads 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 e-mail: info@fireretardantsinc.com Visit Our Web Site at www.fireretardantsinc.com Protecting
More informationComplete Firestop Systems Guide
Complete Firestop Systems Guide Passive Fire Protection products are tested to various test requirements, please check with your local building code for the requirements within your municipality. Firestop
More informationMass Loaded Vinyl A review of the performance and cost in acoustical applications
Mass Loaded Vinyl A review of the performance and cost in acoustical applications Overview Driven by building codes and occupants expectations, many rooms in commercial and residential construction require
More informationControlling the Transmission of Impact Sound through Floors
Construction Technology Update No. 35 Controlling the Transmission of Impact Sound through Floors by A.C.C. Warnock This Update presents guidelines for controlling the transmission of impact sound through
More informationINTER-NOISE 2006 3-6 DECEMBER 2006 HONOLULU, HAWAII, USA
INTER-NOISE 2006 3-6 DECEMBER 2006 HONOLULU, HAWAII, USA An effective new approach to isolate plumbing stub-outs in residential construction Jeffrey P. Kwolkoski, P.E., INCE Bd. Cert. a D. L. Adams Associates,
More informationTest equipment for temperature and its reduction
Data sheet 90.2721 Page 1/6 Test equipment for temperature and its reduction Pt100 precision RTD temperature probe Calibrated temperature measuring chain with precision display device Calibrations as service
More informationPART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
More informationAcoustical proprieties of light brick walls and its effects on flanking transmission
Acoustical proprieties of light brick walls and its effects on flanking transmission G. Semprini a and L. Barbaresi b a University, DIENCA Dept. Facoltà di Ingegneria, Viale Risorgimento, 136 Bologna,
More informationDiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered
Electrical Temperature Measurement DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered WIKA Data Sheet TE 60.75 Applications Machinery, plant and tank construction
More informationMaterial test chamber with mechanical convection
FP series 400 Material test chambers Material test chamber with mechanical convection A BINDER material test chamber with mechanical convection of the FP series provides reliably short drying times and
More informationEcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationSPEECH INTELLIGIBILITY and Fire Alarm Voice Communication Systems
SPEECH INTELLIGIBILITY and Fire Alarm Voice Communication Systems WILLIAM KUFFNER, M.A. Sc., P.Eng, PMP Senior Fire Protection Engineer Director Fire Protection Engineering October 30, 2013 Code Reference
More informationAcoustic Terms, Definitions and General Information
Acoustic Terms, Definitions and General Information Authored by: Daniel Ziobroski Acoustic Engineer Environmental and Acoustic Engineering GE Energy Charles Powers Program Manager Environmental and Acoustic
More informationFire Barriers & Fire Stopping
Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire
More informationMineral fibreglass insulation
Isover MULTIMAX 30 Specification code: MW - EN 13162 - T5 - MU1 - WS - WL(P) - AF r 5 TeChNICaL SPeCIFICaTION Insulating slabs made of Isover fibreglass wool. The production method is based on the fibering
More informationEcophon Focus A. System range. Size, mm. XL 2000x600. XL 1800x600. XL 2400x600 T15 T24 Thickness (THK) Inst. Diagr. 1200x600 1200x1200 1600x600
Ecophon Focus A For applications where a robust suspended ceiling system is required. Ecophon Focus A has an exposed grid system. Each tile is easily demountable. The systems consist of Ecophon Focus A
More informationpinta ACOUSTIC PANEL [1/7]
[1/7] Too much echo in the workplace? Staff unable to concentrate on their work? The answer is: ACOUSTIC PANEL. Service Call our telephone hotline for advice on your individual situation. Animated installation
More informationFire Stopping and Sealing Product: Penetration Seals
UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. Phone : +44 1483 302130 Fax : +44 1483 302230 Email : Inform.NB@uk.ul.com Website
More informationAcoustic performance of dwellings and specifics for lightweight constructions Professor Eddy Gerretsen
Acoustic performance of dwellings and specifics for lightweight constructions Professor Eddy Gerretsen Content Introduction Performance quantities Construction principles What performance is required Does
More informationOptiffuser. High-performance, high bandwidth lightweight 1D diffuser.
Optiffuser High-performance, high bandwidth lightweight 1D diffuser. General product information The Optiffuser comes in packs of four panels. Two positives and two negatives (see page 5) per package.
More informationVIPAC ENGINEERS & SCIENTISTS
VIPAC ENGINEERS & SCIENTISTS Vipac Engineers & Scientists Limited A.B.N. 33 005 453 627 The Victorian Technology Centre Private Bag 16, Port Melbourne, VIC, 3207, AUSTRALIA Telephone +61 3 9647 9700, Facsimile
More informationThe Case for Cross Laminated Timber: Part 2
Learning Objectives The Case for Cross Laminated Timber: Part 2 Opportunities and Challenges for a New Class of Timber Product 1. Review answers to common questions regarding the design and construction
More informationFlamesafe Firestopping Products. Firestopping Products. http://flamesafe.rectorseal.com
Flamesafe Firestopping Products Firestopping Products http://flamesafe.rectorseal.com Engineering Tested By Fire RectorSeal Firestopping Products Since the birth of the firestopping industry almost three
More informationROCKWOOL Rigid, Semi-rigid and Flexible Slabs are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation.
Rigid, Semirigid and Flexible Slabs Versatile thermal acoustic insulation slabs ROCKWOOL are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation. They are manufactured
More informationfire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors
fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors Roxul Safe n Sound Sound Control and Fire Safety From One Batt Insulation Roxul
More informationTesting laboratory HVAC. Test report No.: HP-06525-e
Testing laboratory HVAC Test report No.: HP-62-e Objective: Sound measurements on an air distribution box and an air inlet Client: RoomAir AG Thurstrasse 14 Postfach 81 Frauenfeld Date: 26-6-2 This report
More informationUnderwriters Laboratories Testing Information
Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum
More informationRetrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise
Baltimore, Maryland NOISE-CON 2010 2010 April 19-21 Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise Scott Harvey
More informationEcophon Focus Ds. System range. XL 1800x600. Size, mm. XL 2400x600 T24 Thickness (THK) XL 2000x600. 1200x600 1200x1200 1600x600 M206, M208, M238
Ecophon Focus Ds For applications where a suspended ceiling with a concealed grid is required, but individual tiles must be easily demountable. Ecophon Focus Ds has a concealed grid and syetrical edge
More informationModule 3.7. Thermal bridging
Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal
More informationGPD Rubber Press Seals
GPD Rubber Press Seals Leading in in ideas SYSTEM-TECHNIK GPD Rubber Press Seals Design Available with a rubber thickness of 30 mm for sealing against non-pressing water and a rubber thickness of 60 mm
More informationBuilding Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings
BUILDING ENVELOPE DESIGN BY ROXUL Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB Exterior
More informationColor logos Reverse logos Acoustics Black only logos
Acoustics ACOUSTICS General The basic purpose of architectural acoustics is to provide a satisfactory environment in which the desired sounds are clearly heard by the intended listeners and the unwanted
More informationFire Protection. CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8. Floor Assembly No.
BULLETIN No. 28 (a) Fire Protection CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8 Floor Assembly No. NRC764-FF22 Fire Endurance Period 1 74 minutes Sound
More informationINSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings
INSULATION FOR PRE-ENGINEERED METAL BUILDINGS ROXUL SAFE 55 & 65 and ROXUL PLUS MB Insulation for Pre-Engineered Metal Buildings ROXUL SAFE AND ROXUL PLUS MB Exterior Wall Insulation for Pre-Engineered
More informationDubai Municipality Standard DMS 1: Part 5: 2004
Specification for precast concrete blocks Part 5: Normal-weight concrete-polystyrene sandwich masonry blocks Issue Date Revision Revision Description Prepared by Approved by Authorized by 19/12/2004 Issue
More informationCASE STUDY. Sarakasi Theatre Nairobi, Kenya Room Acoustical Measurements and Modelling. Africa Room Acoustics DIRAC and ODEON
CASE STUDY Sarakasi Theatre Nairobi, Kenya Room Acoustical Measurements and Modelling Africa Room Acoustics DIRAC and ODEON In November 2008, room acoustical measurements were performed inside the Sarakasi
More informationBuilding Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings
Building Envelope Design using ROXUL Building Envelope Design using ROXUL (BEDR ) FIREWALL and ROXUL PLUS MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB
More informationTechnical Application Document. Hilti HIT-RE 500-SD
Technical Application Document Technical Evaluation Report 3/10-649 Injection system for rebar connections Hilti HIT-RE 500-SD Subject to European Technical Approval ATE-09/0295 Holder of approval: HILTI
More informationMetal Pressfitting Pipe Systems
VdS Guidelines for water extinguishing systems VdS 2100-26-3en Requirements and test methods Part 3: Additional provisions for Pipe Systems made of galvanized steel VdS 2100-26-3en : 2012-04 (01) Publishing
More informationFIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
More informationTPM 006/99 Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER
Revision 1 VALID FROM: 8/2/2013 REPLACEMENT FOR TPM 006/99 FIRE SHUTTER PSUM These technical specifications determinate a range of manufactured sizes and models of fire shutters (further only shutters)
More informationData sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G
Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G EN 215-1 HD 1215-2 Application RA 2910 built-in sensor RA 2920 tamperproof RA 5062 remote sensor temperature adjuster RA-FN
More informationWardle Storeys. Reducing Rain Noise on Profiled Metal Roofing Systems Using DEDPAN DS2020 RDV
Wardle Storeys Reducing Rain Noise on Profiled Metal Roofing Systems Using DEDPAN DS2020 RDV Wardle Storeys (Blackburn) Ltd has developed a simple but effective new solution to significantly reduce rain
More informationRoxul Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK DD) Page 1 October 2013
Master Guide Specification (CAVITYROCK DD) Page 1 ROXUL GUIDE NOTE: This master specification section is based on ROXUL INC., CAVITYROCK DD. Standard application: Cavity wall. ROXUL GUIDE NOTE: This master
More informationLABORATORY MEASUREMENTS ON THE EFFICIENCY OF SOUND REDUCING FURNITURE PADS OF TYPE SILENT SOCKS
Report 08-113-R1 06/11/2008 4 pages, 1 appendix Akustikverkstan AB, St Bryne, 531 94 Järpås, tel +46 (0)6-59 37 99 pontus.thorsson@akustikverkstan.se LABORATORY MEASUREMENTS ON THE EFFICIENCY OF SOUND
More informationThis European technical approval
Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating
More informationFire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors.
Fire & Soundproofing Insulation Roxul SAFE N SOUND Fire and Soundproofing Insulation for Interior Partition Walls and Floors. Roxul SAFE N SOUND Sound control and fire safety from one batt Insulation.
More informationTesting Panasonic s WM-61A Mike Cartridge
Tube, Solid State, Loudspeaker Technology Article prepared for www.audioxpress.com Testing Panasonic s WM-61A Mike Cartridge By George Danavaras This microphone study measures how distortion affects performance.
More informationColorcoat Technical Paper Acoustic performance of pre-finished steel cladding systems
CI/SfB (4-) Nh2 (A3j) February 213 CI/SfB (4-) Nh2 (A3j) December 212 Colorcoat Technical Paper Acoustic performance of pre-finished steel cladding systems ACOUSTIC DESIGN Tata Steel has been developing
More informationProduct Information Sheet
Distributed by Thermal Products Company, Inc. Product Information Sheet FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts) Introduction Unifrax s FyreWrap Elite 1.5 Duct Insulation
More informationC05. S03. P02 P08 FireWall. Including C05. S01. P02 Specialist partitions introduction
C05. S03. P02 P08 Including C05. S01. P02 Specialist partitions introduction C05 Specialist partitions Introduction Specialist partitions This section details specialist lightweight systems where high-security,
More informationINTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
More informationMEMBRANE VACUUM MINI PUMPS
MEMBRANE VACUUM MINI PUMPS The mini pumps described in this page are membrane-type. They can be used both as vacuum pumps and compressors. In the latter version they can supply compressed air 100% oil-free
More informationRESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
More informationTENSIONMETER ** code 183_LNRSTW **
Electronic tension meter for applications in textile and wire industry. 9 Tension ranges from 0.1-200 cn to 5-50 dan. Versatile instruments usable for applications in textile industry: e. g. 50 up to max.
More informationTEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
More informationComposite Panel Firewall Systems
Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.
More informationBuilt to Last. Built for Beauty. Good. Solid. Logix. TM
Built to Last. Built for Beauty. Good. Solid. Logix. TM Quality, Value and Service Introducing LOGIX Insulated Concrete Forms. Based on the simple concept of interlocking blocks, LOGIX ICF gives you a
More informationFaçade acoustic design strategy Proposed residential development Irvin Avenue, Saltburn
strategy Proposed residential development Report Number: 1420.1 Version: A Date: 13 th October 2008 Prepared by: Checked by: Andrew Gibson Jack Harvie-Clark Apex Acoustics Limited Design Works William
More informationPERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall
PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court
More informationManual lifting and handling
Manual lifting and handling When installing British Gypsum products and systems care should be taken to ensure that appropriate methods of handling and lifting are adopted. The following guidance details
More informationClimate chamber with illumination
KBWF series (E5.2) Climate chambers with illumination Climate chamber with illumination The BINDER climate chamber with illumination of the KBW series achieves homogeneous light distribution with its natural
More informationRockwool Cladding Roll
Rockwool Cladding Roll High performance industrial insulation has been specifically developed for use in lightweight cladding applications to commercial or industrial framed buildings. Cladding Roll U/F
More informationCharacterization of acoustics in open offices - four case studies
Characterization of acoustics in open offices - four case studies J. S Keränen, P. Virjonen and V. O Hongisto Finnish Institute of Occupational Health, Lemminkäisenkatu 14-18 B, 5 Turku, Finland jukka.keranen@ttl.fi
More information