Nortrax David Manchester Road, Ottawa FAN ASSISTED COPPER TUBE BOILERS 21 May 2014 Project: PART 1 - GENERAL...

Size: px
Start display at page:

Download "Nortrax 23 52 23 190 David Manchester Road, Ottawa FAN ASSISTED COPPER TUBE BOILERS 21 May 2014 Project: 13-104-070 PART 1 - GENERAL..."

Transcription

1 21 May 2014 PART 1 - GENERAL WORK INCLUDED QUALITY ASSURANCE APPROVALS... 1 PART 2 - PRODUCTS HEATING BOILERS BOILER SEQUENCE CONTROL... Error! Bookmark not defined BOILER SCHEDULE... Error! Bookmark not defined. PART 3 - EXECUTION INSTALLATION STARTUP... 4 INDEX

2 21 May 2014 Page 1 PART 1 - GENERAL 1.1. WORK INCLUDED.1 Comply with Division 1, General Requirements and all documents referred to therein..2 Provide all labour, materials, products, equipment and services to supply and install the heated water boilers and controls indicated on the Drawings and specified in this Section of the Specifications QUALITY ASSURANCE.1 Manufacture and install in accordance with governing codes and regulations and the following reference standards:.1 Provincial Boiler and Pressure Vessels Act.2 CSA Standard B.51 (latest edition): Code for the construction and Inspection of Boilers and Pressure Vessels.3 ASME: Boiler and Pressure Vessel Code, Section IV.4 Canadian Electrical Code.5 Piping to ANSI Standards.6 Provincial Environmental and Energy Acts.7 CSA/CGA B149 Natural Gas Installation Code.2 Provide factory tests to confirm specified construction, and proper operation of unit APPROVALS.1 Obtain and pay for Environmental Protection Act Permit..2 Submit to the Owner Canadian registration number of the unit attesting to units meeting the requirements of the Authorized Inspection Agency. PART 2 - PRODUCTS 2.1. HEATING BOILERS.1 Provide natural gas fired hydronic hot water heating boilers of proven and certifiable low NOx design with ASHRAE 90.1 approval. Boilers shall be, constructed in accordance with ASME standards complete with approval stamp for 160 psi working pressure..2 Boilers shall be certified and listed by CSA International under the latest edition of the harmonized ANSI Z21.13 test standard for the U.S. and Canada and shall bear a CGA Seal as a hydronic boiler..3 Meet performance requirements shown on schedules. Minimum efficiency 85%..4 Provide boilers constructed as follows:

3 21 May 2014 Page 2.1 The boiler shall bear the ASME "H" stamp for 160 psi working pressure and shall be National Board listed. There shall be no banding material, bolts, gaskets or "O" rings in the header configuration. The 316L stainless steel combustion chamber shall be designed to drain condensation to the bottom of the heat exchanger assembly. A built-in trap shall allow condensation to drain from the heat exchanger assembly. The complete heat exchanger assembly shall carry a ten (10) year limited warranty..2 The boiler shall be certified and listed by C.S.A. International under the latest edition of the harmonized ANSI Z21.13 test standard for the U.S. and Canada. The boiler shall comply with the energy efficiency requirements of the latest edition of the ASHRAE 90.1 Standard and the minimum efficiency requirements of the latest edition of the BTS2000 Standard. The boiler shall operate at a minimum of 94% thermal efficiency at full fire. The boiler shall operate up to 98% thermal efficiency with return water temperatures at 100 F or below. The boiler shall be certified for indoor installation. The boiler s Thermal Efficiency shall be verified through third party testing by the Hydronics Institute Division of AHRI and listed in the AHRI Certification Directory..3 The boiler shall be constructed with a heavy gauge steel jacket assembly, primed and pre-painted on both sides. The combustion chamber shall be sealed and completely enclosed, independent of the outer jacket assembly, so that integrity of the outer jacket does not affect a proper seal. A burner/flame observation port shall be provided. The burner shall be a premix design and constructed of high temperature stainless steel with a woven metal fiber outer covering to provide modulating firing rates. The boiler shall be supplied with a gas valve designed with negative pressure regulation and be equipped with a variable speed blower system, to precisely control the fuel/air mixture to provide modulating boiler firing rates for maximum efficiency. The boiler shall operate in a safe condition at a derated output with gas supply pressures as low as 4 inches of water column. The boiler shall be equipped with leveling legs..4 The boiler shall utilize a 24 VAC control circuit and components. The control system shall have an electronic display for boiler set-up, boiler status, and boiler diagnostics. All components shall be easily accessed and serviceable from the front and top of the jacket. The boiler shall be equipped with; a temperature/pressure gauge, high limit temperature control certified to UL353, ASME certified pressure relief valve, outlet water temperature sensor, return water temperature sensor, a UL 353 certified flue temperature sensor, outdoor air sensor, low water flow protection and built-in adjustable freeze protection..5 The boiler shall feature the Smart System control with a Multi-Colored Graphic LCD display with Navigation Dial and Soft Keys for, password security, three loop temperature setpoints with individual outdoor air reset curves, pump delay with adjustable freeze protection, pump exercise, and USB PC port connection. The boiler shall be capable of controlling a variable speed boiler pump to keep a constant Delta T at all modulation rates. The boiler shall have the capability to accept a 0-10 VDC input connection for BMS control of modulation or setpoint, enable disable of the boiler, variable system pump signal and a 0-10VDC output of boiler modulation rate. The Boiler shall have a built-in Cascade with sequencing options for lead lag or efficiency optimized modulation logic, with both capable of rotation while maintaining modulation of up to eight boilers

4 21 May 2014 Page 3 without utilization of an external controller. Supply voltage shall be 120 volt / 60 hertz / single phase..6 The boiler shall be equipped with two terminal strips for electrical connection. A low voltage connection board with 42 data points for safety and operating controls, i.e., Auxiliary Relay, Auxiliary Proving Switch, Alarm Contacts, Runtime Contacts, Manual Reset Low Water Cutoff, Flow Switch, High and Low Gas Pressure Switches, Tank Thermostat, Three Wall Thermostat/Zone Controls, System Supply Sensor, Outdoor Sensor, Building Management System Signal, Modbus Control Contacts and Cascade Control Circuit. A high voltage terminal strip shall be provided for supply voltage. The high voltage terminal strip plus integral relays are provided for independent pump control of the System pump, the Boiler pump and the Domestic Hot Water pump..7 The boiler shall be installed and vented with a:.1 Direct Vent Sidewall system with a horizontal sidewall termination of both the vent and combustion air. The flue shall be PVC, CPVC or Stainless Steel sealed vent material terminating at the sidewall with the manufacturers specified vent termination. A separate pipe shall supply combustion air directly to the BOILER from the outside. The air inlet pipe may be PVC, CPVC, ABS, Galvanized, Dryer Vent, or Stainless Steel sealed pipe. The air inlet must terminate on the same sidewall with the manufacturer s specified air inlet cap. The BOILER s total combined air intake length shall not exceed 100 equivalent feet. The BOILER s total combined exhaust venting length shall not exceed 100 equivalent feet..8 Additional standard equipment shall include a flow switch, high temperature limit control, an air pressure switch to monitor low air and blocked flue conditions, low voltage transformer with a five amp circuit breaker for the 24 volt control circuit, a 50 PSI ASME pressure relief valve and a temperature / pressure gauge. All units must be factory tested and complete with a quality test report shipped with the unit. Supply Voltage to boiler at 120 volts..9 All components shall be easily accessed and serviceable and have multi-pin plug in type connectors to ease service, troubleshooting and lower removal and replacement costs. Indicating lights shall be provided for power on, pre purge, trial for ignition, flame failure, low air and individual stage operation. The ignition module shall provide status indication visible from the unit control panel. PART 3 - EXECUTION 3.1. INSTALLATION.1 Follow manufacturer's erection, operation and maintenance instructions..2 Provide wiring between boiler control panels and sequence controller. Iinstall and wire controls for boilers and any loose control components.3 Provide, to the appropriate trade, steel angle inserts to be placed in the housekeeping pads for the support of the boilers.

5 21 May 2014 Page 4.4 Pipe relief valves and drains from each unit to funnel floor drain or hub drain. Make required piping, electrical, venting, and control connections STARTUP.1 Manufacturers representative to provide start-up assistance service for contractor under the direction of the consultant complete with flue gas analysis showing NOx emissions for submission with start up report..2 System commissioning shall be the responsibility of the contractor and payment for any equipment commissioning shall be the responsibility of the contractor..3 Manufacturers representative to also provide for one half day (4 hours) of maintenance and operating instructions for the owners representative and include for training on troubleshooting potential problems. Provide engineering consultant adequate notice prior to start-up assistance and instruction sessions and provide a written start up report of installation results. END OF SECTION

Up To 99% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY

Up To 99% Thermal Efficiency HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY HIGH EFFICIENCY COMMERCIAL BOILERS WITH MODBUS PROTOCOL, CASCADING SEQUENCER AND FRONT-END LOADING CAPABILITY 7 INPUTS FROM 1.5 TO 5.0 MILLION BTU/HR FIRING RATE MODULATION UP TO 25:1 DIRECT-VENT FLEXIBILITY

More information

Versatility ::::::::::::::::::::::::::::::::::::::: the best. mod/con Performance. and UP TO. www.knightheatingboiler.com

Versatility ::::::::::::::::::::::::::::::::::::::: the best. mod/con Performance. and UP TO. www.knightheatingboiler.com the best mod/con Performance UP TO 96 % DOE AFUE Efficiency and Versatility Now with Floor and Wall Mount Models www.knightheatingboiler.com ::::::::::::::::::::::::::::::::::::::: a Legendary Performer

More information

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger

More information

DESIGNER S HIGH EFFICIENCY GUIDE SYNC COMMERCIAL BOILERS. Up to 98% Thermal Efficiency. www.lochinvar.com

DESIGNER S HIGH EFFICIENCY GUIDE SYNC COMMERCIAL BOILERS. Up to 98% Thermal Efficiency. www.lochinvar.com DESIGNER S HIGH EFFICIENCY GUIDE SYNC COMMERCIAL BOILERS Up to 98% Thermal Efficiency www.lochinvar.com Table of Contents 1 Combustion & Ventilation Air Page 2 2 Venting... Page 5 3 Gas.... Page 13 4 Water......

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

Commercial Gas Water Heater

Commercial Gas Water Heater Commercial Gas Water Heater 3-Year Limited Tank/1-Year Limited Parts Warranty* The Polaris has a high grade 444 stainless steel tank with brass connections for years of dependable, trouble-free service

More information

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH Centauri Condensing Fire Tube Water Boiler 399 to 1000 MBH Pre-mix surface burner with up to a 7-to-1 turndown NOx levels as low a 5 ppm at full rate Operates on 4" gas pressure shown with optional gauges

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600

More information

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR

High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR High Efficiency Copper Finned Tube Boilers 750,000-2,000,000 BTU/HR The heat transfer innovators. THE RELIANCE COPPER FINNED TUBE HYDRONIC BOILER FEATURES Copper Fin-Tube Heat Exchanger Up to 88% Thermal

More information

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The

More information

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459 SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters CYCLONE Mxi MODULATING MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable

More information

NAVIEN AMERICA INC. 17855 FITCH AVENUE

NAVIEN AMERICA INC. 17855 FITCH AVENUE Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx

More information

Originators of the Flexible Water Tube design

Originators of the Flexible Water Tube design BRYAN FLEXIBLE WATER TUBE AB SERIES STEAM AND WATER BOILER 900,000 TO 3,000,000 BTUH FORCED DRAFT GAS, OIL OR DUAL FUEL FIRED Water Boiler AB120-W-FDGO Steam Boiler AB250-S-150-FDG Originators of the Flexible

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters UP TO 96% THERMAL EFFICIENCY, DIRECT-VENT FEATURES TM BTH-120 through BTH-500 The A. O. Smith Cyclone Xi family of products represents the industry s most technologically advanced commercial water heaters.

More information

Advanced Heating & Hot Water Systems. Ultra High Efficiency Energy Star Listed Condensing Boiler

Advanced Heating & Hot Water Systems. Ultra High Efficiency Energy Star Listed Condensing Boiler Advanced Heating & Hot Water Systems A Trailblazing Energy Star Listed Boiler that Installs like a Mid-Efficiency Boiler with the Performance of a High-Efficiency Product Ultra High Efficiency Energy Star

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4

More information

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially

More information

F9MXE. Product Specifications

F9MXE. Product Specifications 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Select models earn the ENERGY STAR (See below, indicated with check mark.) Xtra SEER ECM blower motor Supports

More information

PART 11: START-UP PROCEDURES FOR THE INSTALLER

PART 11: START-UP PROCEDURES FOR THE INSTALLER PART 11: START-UP PROCEDURES FOR THE INSTALLER NOTICE It is important to note that the user can adjust the heat curve down by adjusting the central heating temperature to a lower setting. 212 CENTRAL HEATING

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Commercial Semi-Instantaneous Water Heaters

Commercial Semi-Instantaneous Water Heaters FEATURES HWI Models A. O. Smith s HWI models are available for operation with steam or boiler water as the energy source. They are factory assembled with components sized, piped and checked at the factory

More information

Light Duty Commercial Electric Water Heater

Light Duty Commercial Electric Water Heater Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and

More information

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled

More information

Series GM. Peerless Boilers. Residential/Commercial Gas Boilers

Series GM. Peerless Boilers. Residential/Commercial Gas Boilers Peerless Boilers Series GM Residential/Commercial Gas Boilers The Series GM cast iron, hot water boiler is ideal for use in large residences or commercial applications. This gas-fired, atmospheric boiler

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air

More information

Y-200 Multi-Stage Sequencer

Y-200 Multi-Stage Sequencer Y-200 Multi-Stage Sequencer Designed for use with single or multiple space heating or hot water supply systems, the Y-200 is offered in 4- and 8-stage configurations and is available loose or factory-mounted

More information

G9MXE. Product Specifications

G9MXE. Product Specifications Up to 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL Up to 96% AFUE, all models all positions California NOx approved Select models earn the ENERGY STAR (See below, indicated with check mark.)

More information

Commercial Boiler Systems and Controls

Commercial Boiler Systems and Controls Commercial Boiler Systems and Controls Condensing Non-condensing Hybrid Systems Steel Medium Mass Copper Instantaneous Electric Riverside R HYDRONICS An introduction to hybrid boiler systems What is a

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION 1 2 3 4 5 Inadequate or no earth ground sensed by the Intelli-Vent control. Power supply to Intelli-Vent control has reversed polarity. Pressure switch circuit remaining closed for more than 5 seconds

More information

G234X-55 Conventional Gas Boiler

G234X-55 Conventional Gas Boiler Engineering Submittal Sheet Boiler Overview C US Engineering Specifications There shall be provided and installed a quantity of Buderus G234X-55 fl oor standing hot water boiler(s), suitable with natural

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

TANKLESS WATER HEATER INSTALLATION DIAGRAMS TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water

More information

ASME Packaged Indirect Fired Water Heater

ASME Packaged Indirect Fired Water Heater Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining

More information

Service Manual Models: 80-285

Service Manual Models: 80-285 KB-SER-08 Service Manual Models: 80-285 Starting Serial #H07H10040039 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this

More information

RECON WATER HEATER INSTALLATION FORM

RECON WATER HEATER INSTALLATION FORM RECON WATER HEATER INSTALLATION FORM Please complete ONE (1) form for each SITE and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: STARTUP@AERCO.COM.

More information

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents

More information

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE Hot Water Boilers and Controls Why Condensing Boilers are Different Presented Oct. 14, 2008 Long Island Chapter, ASHRAE H.W. Boilers and Controls Major types of boilers Advantages and disadvantages Resistance

More information

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S NATURAL GAS 40-130 MBH INPUT Due to continuous product improvement, specifications are subject to change

More information

DESIGNER S GUIDE EFFICIENCY+ BOILER

DESIGNER S GUIDE EFFICIENCY+ BOILER DESIGNER S GUIDE EFFICIENCY+ BOILER 150,000 300,000 BTU/HR Dear Specifier/Project Manager, At Lochinvar, we have long recognized the importance of innovation to any product or service. Those who enter

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for

More information

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00 RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

Condensing Boilers. High Efficiency. Proven Reliability, American-Made Home Heating Comfort. ANYWHERE UNMATCHED

Condensing Boilers. High Efficiency. Proven Reliability, American-Made Home Heating Comfort. ANYWHERE UNMATCHED High Efficiency Condensing Boilers Proven Reliability, American-Made Home Heating Comfort. Look for this logo throughout this literature to see the unique features that set U.S. Boiler Company apart from

More information

Commercial Electric Water Heater

Commercial Electric Water Heater MODEL SE Commercial Electric Water Heater 6-120 Gallon Capacity, up to 58 KW in all Three Phase Voltages, Over 6 KW in all Single Phase Voltages Features Heavy Duty Construction Hydrastone cement lining

More information

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating

More information

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS WARNING Improper installation, adjustment, alteration, service, or maintenance of this product can cause

More information

High efficiency, cast-iron gas boiler

High efficiency, cast-iron gas boiler SENTRY High efficiency, cast-iron gas boiler LOWER PROFILE MAKES PROBLEM INSTALLATIONS EASY SENTRY High efficiency, cast-iron gas boiler A smarter choice for informed The boiler you choose for your home

More information

Boiler Preparation, Start-Up and Shutdown

Boiler Preparation, Start-Up and Shutdown Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.

More information

Service Manual Models: 150-500

Service Manual Models: 150-500 Models: 150-500 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Armor Water Heater Installation and Operation

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

TANKLESS DURABILITY Tankless Product Guide

TANKLESS DURABILITY Tankless Product Guide TANKLESS DURABILITY Tankless Product Guide Energy-efficient, plentiful, and endless supply of hot water. Compact size and wall-mounted to free up valuable floor space. SAVE ENERGY. SAVE SPACE. PAGE [ 2

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary Installation Service Statement of Work - 1 - Cooling Start-up Service Cooling Start-up Service Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details

More information

Factory owners must ensure the boiler is:

Factory owners must ensure the boiler is: Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised

More information

Vitodens 200, B2HA / B2HB - Product Introduction

Vitodens 200, B2HA / B2HB - Product Introduction - Product Introduction Foil 2, 10/2015 Viessmann Manufacturing Wall Mounted, Gas-Fired Condensing Boiler Foil 3, 10/2015 Viessmann Manufacturing A member of the Viessmann family of heating products Condensing

More information

OTF Oil Fired Pool Heater

OTF Oil Fired Pool Heater OTF Oil Fired Pool Heater Installation Operation Maintenance Manual Service Policy 722010 Congratulations on the purchase of your new pool heater. In order to maintain peak performance of your pool heater

More information

INSTALLATION OPERATION AND SERVICE MANUAL

INSTALLATION OPERATION AND SERVICE MANUAL INSTALLATION OPERATION AND SERVICE MANUAL GAS FIRED WALL HUNG & FLOOR MOUNT RESIDENTIAL COMMERCIAL STAINLESS STEEL BOILERS DynaMax SERIES HYDRONIC HEATING Models; DMH081, 101, 151, 201, 251, 211, 261,

More information

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing) CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.

More information

One Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty

One Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty One Year Warranty ELECTRIC Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches Fused Ceramic Shield tank lining is corrosion-resistant for years of dependability. Adjustable

More information

Arapahoe County Residential Water Heater Installation and Inspection Guide

Arapahoe County Residential Water Heater Installation and Inspection Guide Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

Service Handbook Commercial / Residential gas water heater

Service Handbook Commercial / Residential gas water heater Service Handbook Commercial / Residential gas water heater 500 Tennessee Waltz Parkway Ashland City, TN 37015 FOR MODELS: BTX 100, GDHE 50 SERIES 120 & 121 INSTALLATION CONSIDERATIONS - PRE SERVICE CHECKS

More information

SIOUX HYBRID WATER HEATER

SIOUX HYBRID WATER HEATER SIOUX Hybrid Water Heater for the Concrete Industry SIOUX HYBRID WATER HEATER Patent Pending Maximizing the Benefits of Coil and Direct-Fired Heating Technologies Higher Discharge Temperature True High-Efficiency

More information

GTS Gas-to-Steam Humidification System

GTS Gas-to-Steam Humidification System GTS Gas-to-Steam Humidification System Gas has lowest energy operating costs The industry s first and best-selling gas-to-steam (GTS ) humidifier continues to be your best choice for reducing energy costs

More information

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions. B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary

More information

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL

PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL Boiler Manual A. INSTALLING EXHAUST VENT AND INTAKE AIR VENT B. GENERAL n DANGER The Elite Heating Boiler must be vented as detailed in this section.

More information

Service Manual Models: 150-800

Service Manual Models: 150-800 AW-SER Rev H Service Manual Models: 150-800 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Armor Water

More information

For installation guide see reverse of book

For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

INSTALLATION INSTRUCTIONS GEO-BOOSTER TM

INSTALLATION INSTRUCTIONS GEO-BOOSTER TM Table of Contents General Description 1 Parts list 1 Installation 2 New Ground Loop 2 Retrofit 4 Temporary 6 Troubleshooting 8 INSTALLATION INSTRUCTIONS GEO-BOOSTER TM General Description The Geo-Booster

More information

D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00

D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00 SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information

APG-4R_Layout 1 9/14/11 12:01 PM Page 1 APG-4R XL X F L

APG-4R_Layout 1 9/14/11 12:01 PM Page 1 APG-4R XL X F L XLF APG-4R YOUR NUMBER ONE SOURCE for any domestic hot water or hydronic space heating application start-up, service and maintain. Features such as slide out heat exchangers and burner trays help reduce

More information

Cast-Iron Performance Meeting today s commercial demands with effi ciency, strength and intelligent controls.

Cast-Iron Performance Meeting today s commercial demands with effi ciency, strength and intelligent controls. Cast-Iron Performance Meeting today s commercial demands with effi ciency, strength and intelligent controls. EFFICIENCY THAT CAN T BE COMPROMISED In a commercial market where efficiency is everything,

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance 2009 Heat Transfer Products, Inc. Phoenix Evolution Water Heater Models* PHE130-55 / PHE199-55 PHE130-80 / PHE199-80 PHE130-119 / PHE199-119 *A suffix of LP denotes propane

More information

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose: PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Better Boilers. www.ibcboiler.com

Better Boilers. www.ibcboiler.com Better Boilers FEATURING OUR IBC SUPREME SUPER COIL 316TI STAINLESS STEEL HEAT EXCHANGER. From the factory in Vancouver, our uniquely designed and engineered Super Coil VFC Heat Exchanger is the best Heat

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

User's Instructions. Alpha HE CB25/33 and HE SY25

User's Instructions. Alpha HE CB25/33 and HE SY25 User's Instructions Alpha HE CB25/33 and HE SY25 Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Boiler Range For Technical help or for Service call... ALPHA HELPLINE Tel:

More information

Medical Air Systems: Scroll

Medical Air Systems: Scroll GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing

More information

SOLI TANKLESS PRODUCT GUIDE

SOLI TANKLESS PRODUCT GUIDE SOLI TANKLESS PRODUCT GUIDE SAVE ENERGY. Energy-efficient, plentiful, and endless supply of hot water. SAVE SPACE. Compact size and wall-mounted to free up valuable floor space. SAVE MONEY. The smart

More information

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................

More information

OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE

OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203)

More information

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION When installing or using any high voltage electrical appliance, basic safety precautions

More information

Condensing Boiler Efficiency

Condensing Boiler Efficiency Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2

More information

GeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control

GeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control PARTS & ACCESSORIES GeniSys 12V Model 7556 Advanced 12 Vdc Burner Control Description / Applications The Beckett GeniSys TM 12V Advanced Burner Control is a 12 Vdc primary safety control for oil burners

More information

Mechanical Rooftop Custom Capabilities

Mechanical Rooftop Custom Capabilities Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition

More information

Air Conditioner Water Heater Model ACWH18

Air Conditioner Water Heater Model ACWH18 Air Conditioner Water Heater Model ACWH18 Installation Guide IMPORTANT! READ THIS FIRST! Commissioning of this unit must be done by a licensed HVAC technician. Commissioning includes making the electrical

More information

Electric Flow Boiler

Electric Flow Boiler Electric Flow Boiler EHC offer the most comprehensive range of electric boilers in the market and with our wealth of knowledge and technical expertise we have designed the Slim Jim Electric Flow Boiler

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex

More information

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage

More information