LOW-PRESSURE EXCESS FLOW NATURAL GAS VALVES PLUMBING CODE APPLICATION REQUIREMENTS

Size: px
Start display at page:

Download "LOW-PRESSURE EXCESS FLOW NATURAL GAS VALVES PLUMBING CODE APPLICATION REQUIREMENTS"

Transcription

1 LOW-PRESSURE EXCESS FLOW NATURAL GAS VALVES UNIFORM PLUMBING CODE APPLICATION REQUIREMENTS Prepared For: Carl Strand Strand Earthquake Consultants 1436 S. Bentley Avenue, #6 Los Angeles, CA and James C. McGill Smart Safety Systems 4312 Lisa Drive Union City, CA Prepared By: J. Marx Ayres, P.E. Consulting Mechanical Engineer 1180 South Beverly Drive, Suite 600 Los Angeles, California (310) January 21, 2002

2 Low-Pressure EFVs Table of Contents Section Table Of Contents Page Table of Contents Tables & Figures (see attached) ii Execu t Ive Summary "'f' 111 IV Acknowledgements V 1 Introduction Background 1.2 Purpose 1.3 Excess Flow Valves 2 Calculations UPC Requirements 2.2 Spitzglass Formula 2.3 Pipe System 2.4 Certifications 2.5 Spread Sheet Calculations 3 Discussion Conclusions & Recommendations 4-1 Appendices A & B i J. Marx Ayres, P.E. Page i

3 Low-Pressure EFVs Table of Contents Tables & Figures Tables Page 2-1 Low-Pressure EFVs UMAC Quake Breaker At Meter UMAC Quake Breaker At Meter & At Each Appliance Sanders At Meter Sanders At Meter And At Each Appliance UMAC Quake Breaker At Meter & Magne-Flo At Each Appliance Sanders At Meter & Magne-Flo At Each Appliance Pressure-Drop Calculations Without EFVs 2-21 Figures 2-1 Model of Residential Piping System Isometric Piping Diagram of EFV At Meter Isometric Piping Diagram of EFV At Meter & At Each Appliance Isometric Piping Diagram Without EFV UMAC Quake Breaker At Meter UMAC Quake Breaker At Meter & At Each Appliance Sanders At Meter Sanders At Meter & At Each Appliance UMAC Quake Breaker At Meter & Magne-Flo At Each Appliance Sanders At Meter & Magne-Flo At Each Appliance Pressure-Drop Calculations Without EFVs 2-22 J. Marx Ayres, P.E. Page ii

4 Low-Pressure EFVs Executive Summary Executive Summary The performance of low-pressure gas systems in buildings during earthquakes, and the potential for fire due to pipe breaks or leaks, are vital public life/safety issues. Manufactured products designed to shut-off or limit the supply of gas during an earthquake have been developed and installed. Earthquake-actuated seismic gas shut-off valves (SGSVs), which are generally installed downstream from the gas utility meters, have been mandated by some Building Codes. Excess flow valves (EFVs), which are designed to limit the flow of gas when the pressure-drop across the valves exceeds their manufacturer's specified limit, have been developed for installation downstream from the meter or at each flexible appliance connector. The installation and operation of gas systems on customers' premises is regulated by the National Fuel Gas Code and local Building Codes. The Uniform Plumbing Code (UPC) requires that each low-pressure gas system be so designed that the total pressure drop between the meter (or other point of supply) and any outlet, when full demand is being supplied to all outlets, will at no time exceed 0.5" of water column (WC) pressure. For low-pressure (6" to 8" WC) systems with 250 CFH maximum demand and 250 Ft. maximum length from the meter (or other point of supply) to the most distant outlet, pipe sizing tables are provided. The UPC also provides for pressure-drop calculations on each pipe section, fitting, valve, or control device, following basic fluid flow engineering formulas to meet the 0.5" maximum total pressure-drop criteria. The pressure drops required to actuate (Le., close) EFVs are determined by certified testing laboratories following the CSA U.S. No Requirements. The purpose of this study was to determine the impact of these valves when applied in a model residential building with 7.0" WC pressure gas service. Plan check calculations were prepared for the gas system with and without EFVs (manufactured by UMAC, Sanders, & Brass Craft / Magne-Flo) located: (1) downstream of the meter, and (2) at the meter and at each appliance connector. Spitzglassformula pressure-drop calculations for all components in the system were prepared, and the results of the spread sheet calculations are presented in tabular and graphical form. Difficulties in obtaining EFV and appliance - connector pressure - drop data are discussed. J. Marx Ayres, P.E. Page iii

5 Low-Pressure EFVs Executive Summary The study's conclusions and recommendations are: When EFVs are installed in typically sized low-pressure gas systems, the total pressure drop of the systems will exceed the UPC maximum allowed 0.5" WC. Building Codes should require plan checks for any low-pressure gas systems using one or more EFVs. Pressure drops across flexible appliance connectors should be listed with a defined number and radii of bends or loops. For flexible appliance connectors that are provided with an attached or encapsulated EFV, the pressure drops should be listed both with and without the EFV. J. Marx Ayres, P.E. Pageiv

6 Low-Pressure EFVs Acknowledgements Acknowledgements This report was prepared by J. Marx Ayres, P.E., Past President of Ayres, Ezer & Varadi, Consulting Engineers, now renamed AEV Inc. Technical assistance was provided by Ivan Varadi, C.I.P.E., Vice President and Director of Plumbing & Fire Protection Engineering at AEV. The assistance of Carl Strand, President of Strand Earthquake Consultants, in providing background information, product brochures, and test reports obtained from State agencies is gratefully acknowledged. J. Marx Ayres, P.E. Page v

7 Low-Pressure EFVs Introduction Section 1 Introduction 1.1 Background The performance inside buildings of gas systems during earthquakes and the potential for fire due to failure of one or more system components (pipe segments, fittings, valves, flexible appliance connectors, or appliances), has been the subject of intense study by government agencies, utilities, researchers, and design engineers. Manufactured products designed to shut-off or limit the supply of gas during an earthquake have been developed and installed. Seismic gas shut-off valves (SGSVs), which close when they detect a certain level of ground or pipe shaking, are generally installed downstream from gas-utility meters in low - pressure lines serving buildings. Excess flow valves (EFVs) are designed to restrict the flow of gas when they detect a sufficiently large drop in pressure on the downstream side of the valve, which may occur due to a downstream pipe failure. EFVs, normally used in gas-utility high-pressure lines upstream from the meter, have been developed for application downstream from the meter (like the SGSVs) and also at each appliance connection. Building Codes & Standards, which are designed to regulate an industry and protect the public, are revised and upgraded after each major earthquake. Most of the Standards developed by professional organizations follow strict consensus procedures that define manufacturing performance and testing requirements. Building Codes define the minimum standards and construction procedures allowed by the governmental agency having jurisdiction. Organizations that develop and publish Standards, Codes, and Certifications that are of interest in this study include: American Gas Association (AGA) American National Standards Institute (ANSI) American Society of Civil Engineers (ASCE) American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE) American Society of Plumbing Engineers (ASPE) California Division of the State Architect (DSA) Canadian Gas Association (CGA) Canadian Standard Association (CSA) International Approval Services (IAS) International Association of Plumbing & Mechanical Officials (IAPMO) National Fire Protection Association (NFPA) On July 3, 1997, the CSA, an independent North American Standards-development, product-certification, and management-systems-regulation organization, acquired IAS (formerly a joint venture of AGA and CGA). The professional organizations that develop Standards operate through Technical or Task Committees (TC's) where members are appointed to represent most of the J. Marx Ayres, P.E. Page 1-1

8 Low-Pressure EFVs Introduction interested parties in a specific industry, (Le., manufacturers, application design engineers, users, installers, and governmental agencies). The industry discussions regarding SGSVs and EFVs are currently focused in the ASCE-25 Task Committee on Earthquake Safety Issues for Gas Systems. The ASCE-25 TC is an ad hoc committee consisting of ASCE-25 members and others, and was formed by the California Seismic Safety Commission (SSC) to study the use of seismic gas safety valves as well as products and methods related to earthquake safety. 1.2 The purpose of this study was to assist in the evaluation of EFV applications in building low-pressure natural gas systems. The specific assignment was to prepare plan-check calculations for a typical residential installation using the test results submitted by the manufacturers to the California Office of the State Fire Marshal and the DSA. The technical approach was to select a model building and prepare pipe-sizing calculations for the gas system both with and without EFVs. The residential system shown on page 105 of the 1979 edition of the Uniform Plumbing Code (UPC) was selected as the model. The pressure-drop calculations presented in this study are limited to natural gas systems with specific gravity of 0.6 at 60 F. See Section 2.0. The component and system pressure drops using natural gas at other specific gravities, and / or vaporous propane gas with specific gravity of 1.53 at 60 F., were not a part of this study. 1.3 Low-Pressure EFVs Low-pressure (LP) EFVs are designed for installation downstream of the gas-utility pressure regulator and meter, or at the end of the gas line after the gas cock at the entry to the flexible appliance connector. They are constructed with a mechanical means that is intended to prevent gas flow in excess of 80% to 110% of their manufacturer's specified closing flow rate at the system's normal operating pressure. The manufacturers of LPEFVs included in this study are UMAC (Quake Breaker, Gas Breaker, & GASP brands), Sanders Valve, and Brass Craft (Magne-Flo brand). J. Marx Ayres, P.E. Page 1-2

9 Low-Pressure EFVs Calculations Section 2 Calculations 2.1 UPC Requirements The requirements for gas pressure regulators and piping size are based on a natural gas having a specific gravity (SG) of at standard conditions (60 F and 14.7 Psi) supplied at 6" to 8" WC pressure at the outlet of the meter (UPC Section ). The maximum demand shall not exceed 250 cubic feet per hour (CFH), and the maximum length of piping between the meter and the most distant outlet shall not exceed 250 feet. The size of each section of pipe and each outlet of any system shall be determined by means of UPC Table 12-3 (Section ). UPC Table 12-3 is based on the maximum delivery capacity in CFH of iron pipe size (IPS) carrying natural gas with a maximum pressure drop of 0.5" WC pressure. This table-simplified "longest run" method was developed by NFPA and AGA (National Fuel Gas Code NFPA 54; ANSI Z 223.1). For conditions other than those covered in UPC Section , the size of each piping system shall be determined by standard engineering methods acceptable to the Administrative Authority. Each such system shall be so designed that the total pressure drop between the meter (or other point of supply) and any outlet, when full demand is being supplied to all outlets, will at no time exceed 0.5" WC pressure. This type of calculation is often referred to as the "pressuredrop" method. 2.2 Spitzglass Formula The design of piping systems for gas is a fluid-flow problem. Where the required flow rate is determined, the pressure losses due to friction are calculated, and the required residual pressure at each appliance is known. Using basic engineering formulae, the engineer can tabulate the various quantities, establish the pipe sizes for each section of piping, and determine the pressure and flow rate at any point in the system. The flow rate of gas (at standard conditions) in a pipe with pressures not exceeding 1 Psi (28" WC) can be computed using the following Spitzglass formula (ASPE Data Book, 1999, Page 8, Equation 1-24): Q = 3550 K I hsl Q K (.ll-\yz SU Q = 3550 Where [ d5h ] SL (1 + 3;t + O.03d) hs dl Q = Gas =Pressure =Specific =Length =Inside flow pipe of gravity rate drop pipe diameter (In ofcfh) Inches Feet) the(in gas Inches) WC) J. Marx Ayres, P.E. Page 2-1

10 Low-Pressure EFVs Calculations The length used in the formula must be corrected to allow for the additional resistance to flow caused by valves and fittings in the piping. The pressure drops expressed in "equivalent lengths" of pipe for standard pipe fittings are available in the UPC and other piping design handbooks. Pressure drops through control valves and other devices inserted into the system should be obtained from their manufacturer's published data, because flow patterns through valves can vary significantly. 2.3 Pipe System The model piping system with connected appliances and pipe sized by the "longest run" method per UPC Table 12-3 is shown in Figure 2-1. The typical residential customer receives gas from the serving utility at 6" - 8" WC pressure. In California, the Southern California Gas Company (SCG) provides gas at 8" WC pressure to their residential customers and Pacific Gas & Electric (PG&E) provides gas at 7" WC pressure. For purposes of this study, the pressure-reducing valve (regulator) was set at 7-1/2" WC pressure and 0.5" WC pressure drop was assumed through a typical meter. Thus the pressure entering the piping system is 7" WC. The piping is terminated at each appliance with a shut-off cock and a flexible metal connector. Isometric drawings of the piping system with EFVs are shown in Figures 2-2 and 2-4. The UPC limits the piping system's total pressure drop from the meter to the outlet to a maximum of 0.5" WC. The outlet is not clearly defined in the Code, but it is interpreted to mean the shut-off cock at the end of the piping system. If an EFV is inserted into the piping system at the appliance, it would be located upstream from the shut-off cock. If the EFV is located downstream from the shut-off cock, its pressure drop must be included in the 0.5" WC maximum total pressure loss. Note that in the following isometric piping diagrams, the EFV is located downstream from the shut-off cock as a practical matter to facilitate maintenance or replacement. 2.4 Certifications The design, construction, and performance of all gas-system components (appliances, flexible connectors, SGSVs, EFVs, and other devices) must be tested following a published standard and certified (listed) by a recognized agency. In the U.S. gas industry, the criteria is established in the National Fuel Gas Code, (ANSI Z 223.1/NFPA 54) and other ANSI.CGA standards. The manufactured products are tested by approved laboratories (such as AGA) to assure that they meet that criteria. The currently accepted criteria for EFVs are published in the CSA U.S. No Requirements. It should be noted that the Requirements were developed by the CSA non-consensus "industry standard" development function and not their "consensus standard" development function. The performance of listed appliance connections for low-pressure (8" WC or less) systems based on 0.2" WC pressure drop for various lengths and flow rates, are presented in UPC Table The appliance connectors offered by one manufacturer (Brass Craft) are tested and listed per ANSI Z / CGA 6.10 for pressures that do not exceed 0.5 psi (14" WC) and are based on 0.5" WC pressure drop for various straight lengths and flow rates (expressed in BTU/HR with 0.64-SG, 1000-BTU/CF gas). See Appendix A. J. Marx Ayres, P.E. Page 2-2

11 Low-Pressure EFVs Calculations The performance data and description of the LPEFVs included in this study are presented in Table 2-1. See Appendix B for the available manufacturer's literature and CSA-certification test data. Note that the UMAC test data are based on 0.6-SG with 1000-BTU/CF gas; and the Sanders and Magne-Flo test data are based on 0.64-SG 1000-BTU/CF gas. The calculations shown in Section 2.5 used the CSA's 0.64-SG based pressure drop (h) without correction to 0.6 SG, which would have an insignificant impact on the calculated pressure drops. Calculations were also prepared so the performance of the various LPEFVs could be compared using the same values for SG and BTU/CF. 2.5 Spread-Sheet Calculations The Spitzglass formula used in the Excel Spread-Sheet calculations is as follows: Q hd KS L Where Q = ={D".5/(1 3550(K){(h =Gas =The =Specific Inside Length pressure flow pipe of +(3.6/D)+(0.03)(D)]}".5 gravity rate pipe )/(S)(L)y.5 diameter drop (In (In ofcfh) the Feet) (In (In gas Inches) WC) The calculations were performed using the pipe sizes shown in the model depicted in Figure 2-1 with (1) an EFV only at the meter, and (2) an EFV at the meter and at each appliance. See piping isometric diagrams shown in Figures 2-2 and 2-3. The data points shown on the diagrams are identified as sections in the left column of Tables 2-2 through 2-8, which present the calculated pressure drops in the longest run (i.e., the piping between the meter and the most remote outlet). Pressure drops that were interpolated from Table 2-1 were used for the UMAC, Sanders, and Magne-Flo EFVs. Flexible-connector pressure drops from Brass Craft for straight-length applications were used for all flexible connectors. Pressure drops calculated for the model system without the EFVs are presented in Table 2-8. Note that the " WC total pressure drop for the piping system without flexible connectors meets the UPC maximum 0.5" WC requirement. This would be expected because the lines were sized per UPC Table 12-3, which was designed to help prevent low-pressure systems from exceeding 0.5" WC total pressure-drop. Also note that all of the systems with one or more EFVs exceed the UPC 0.5" WC maximum total pressure drop requirement. The system pressure drops for the various configurations are presented graphically in Figures 2-4 through J. Marx Ayres, P.E. Page 2-3

12 ro :E I '"0.., (l) /Jl /Jl s::.., (l) m." Jl () o s:: IIIō' ::I /Jl c.. s: III.., CD /Jl :0 m " " " Brand Name Manufacturer Max 289, , ,000 26,000 Omni Not Rate Load " Magnetic Vertical Inlet 275, , ,000 Specified Required Spring mounting 125,000 Directional 70,000 Gravity DP -at ,400 Range, 289, Capacity (1/2" B/Hr , , , Max Automatic Across Closure Reset (2) or Quake Load, CFH 3/4 Force Valve 1 Flow SV-1B NPT) xi Inches Breaker 1 Inlet 3/4#(3) 1 & xi outlet 3/4 1(1) 1.0 (5/8" 0.5 or 1/2" flare) 70,000 C-1 Table 2-1 Low-Pressure EFVs Notes: (1) The GASP and Gas Breaker brands have the same performance characteristics as the Quake Breaker brand. (2) Inlet 0.5" - WC minimum /2-Psi maximum. 0.6-SG 1000-BTU/CF gas. (3) Valve can be configured in 6 ways using various size washers for a range of minimum and maximum flow rates; 7" - WC system pressure, 0.64-SG 1000-BTU/CF gas; valves actuate within 80%-110% of the closure flow rate, with a 5-CFH bypass flow. (4) 0.5-Psi system pressure; 0.64-SG 1000-B/CF gas; 1-CFH bypass flow. '"0 III lc (l) I\,) 01:>0

13 G= 5' 1/.2' 6B GAS REFRIG. 3 CFH ro ;,.., CD (II (II c.., m" CD < (II o III 0" c," Figure 2-1 c.. III l> '<.., CD Y' :tj rn Model of Residential Piping System FURNACE 136 CFH OD 30 GAL YJATER HEATER 27 CFH OA C = 20' 3/4' H = 10' 112' l' (225 CFH) B = 20' 3/4' (89 CFH) D = 10' 1/2' (30 CFH) F = 10' A=10' E= 15' 112' - -:."'" I J GAS METER l' 225 CFH 6C RANGE " 59 CFH "'tj III CO CD N I CJl iii' roto' ::J (II

14 HEATER.' Figure 2-2 c.. :s: III» '<., CD en Isometric Piping Diagram EFV At Meter ro I "'0., CD en en s::., CD m "T1 <en "'0 rn en 4. S COCK - METER

15 Figure 2-3 t.. s: l:u» '<., CD l/l :u rn Isometric Piping Diagram EFV At Meter & At Each Appliance YATER HEATER ro ::E -b., CD l/l l/l c:., CD m"< l/l FLEX, CONECTOR <TYP,) EFV <TYP,) GAS COCK (TYP,) --l METER GAS COCK

16 ro I '"tj... CD (JI (JI I::., CD m"<(ji (') (") I:: :!: o ::J (JI.' Figure 2-4 (.. :s::» '<... CD (JI Isometric Piping Diagram Without EFV '"tj!'l later HEATER '"tj co CD I\J I ():)

17 Low-Pressure EFVs Calculations Table 2-2 Pressure-Drop Calculations With UMAC Quake Breaker At Meter SECT d RES NOMINAL SKh FT d PRESS INWC ACTUAL QL INWC 1.1 TOT PRESS DROP PRESS DROP EXCLUDING FLEX CONNECTOR J. Marx Ayres, P.E. Page 2-9

18 Low-Pressure EFVs Calculations a0 «0I"- 0::: " I- 0::: m UJ 0::: 0::: UJ ::::s::: :2: <9, <' " ::::s::: -Yo. «UJ c? "" <?" «<5> 0" ->'", "/ 0:2: I- 0Z ::l I UJ UJ 0...J "'< C 0::: 0fl. ::I: L".&" P" 0 0!:i ""V'v> "'< 6'6> UJ <' -Yo. I9S.&, C' 015" 0 "{...J C' ' L ui 0L{) <D <0.,f 1--'U J. Marx Ayres, P.E. Page 2-10

19 Low-Pressure EFVs Calculations Table 2-3 Pressure-Drop Calculations With UMAC Quake Breaker At Meter And At Each Appliance SECT d RES NOMINAL SKh FT d1 PRESS INWC ACTUAL QL INWC TOT PRESS DROP PRESS DROP EXCLUDING FLEX CONNECTOR J. Marx Ayres, P.E. Page 2-11

20 Low-Pressure EFVs Calculations " Zc«c UJ u«:2: D::: :Ju :Jo. r.n L' :::c S'" +.;y/. 'Y "/ «u I- D::: v"!;;:!;;: D::: "1'Y.;y -Yo. "'/ c? "'" "" e " 0 «aj «UJ U:J UJ < Oz :2:0. «::i ' "'< 0" 0'6, :::c«z0...j I a. D::: r.n0l() q 0 <9 U0D::: :J r.n -Yo. < "/ 0 <.ci.,r ui " C' <9, 0',) J.;y 0 "{ 6'6> ' I- /v.-u J. Marx Ayres, P.E. Page 2-12

21 Low-Pressure EFVs Calculations Table 2-4 Pressure-Drop Calculations With Sanders At Meter SECT d RES NOMINAL SKh FT dactual PRESS INWC QL INWC 0.5 TOT PRESS DROP PRESS DROP EXCLUDING FLEX CONNECTOR J. Marx Ayres, P.E. Page 2-13

22 Low-Pressure EFVs Calculations «I- 0 W...I ::i!: " " 0:: EL' 1.9 I-L' (J) 0 & 0L' Wz :I:!;( c? 0L' p.,,,) z0 U 0:: " u «c. (J) 0L!)...I I W 0'<t l!'i r-...: <0,,) cd "<l' (J) w0:: "'< C' 1.9 :lsl' V" s <9 L' -Yo. 0 L'L' 0, p., ->'L', -Yo. <9, 6'6> "? -ty), '''( E C' /v J. Marx Ayres, P.E. Page 2-14

23 Low-Pressure EFVs Calculations Table 2-5 Pressure-Drop Calculations With Sanders At Meter And At Each Appliance SECT d RES NOMINAL SKh FT d PRESS INWC ACTUAL QL INWC TOT PRESS DROP PRESS DROP EXCLUDING FLEX CONNECTOR J. Marx Ayres, P.E. Page 2-15

24 Low-Pressure EFVs Calculations «z u " 0z «c /. L y; W $1..( 0-0 U ::i C W w:;) UJ w [>..( "{ a. a. Ua. Zi= 0::: 0.6..( '1'y; -Yo. c? L'..( U'b. \9 :!: C UJ " 6' Z«I-...J I 00 C'.6, U'b. \9 0..( «...J U0::: UJ 0::: w :;) :I: UJ <9..(..( < -Yo. "/ 0..( (' 6' '1'y; L' 0r--: 0l!') 0l!') <9,..n -q' c.d ' /V"U 00 N e::s C) LL J. Marx Ayres, P.E. Page 2-16

25 Low-Pressure EFVs Calculations Table 2-6 Pressure-Drop Calculations With UMAC Quake Breaker At Meter And Magne-Flo At Each Appliance SECT d RES NOMINAL SKh FT d PRESS INWC ACTUAL QL INWC TOT PRESS DROP PRESS DROP EXCLUDING FLEX CONNECTOR Notes: (1) Pressure-drop calculation for Magne-Flo 5/8" valve Given 1" 70CFH (Table 2-1) Ratio: Q=(hY.5 h@27 CFH: 70/27=(1)A.5/(h)A.5 =O.62106"WC J. Marx Ayres, P.E. Page 2-17

26 ro I "'1J ci III III s:: ci m "T1 <III (") III C'l s:: III o ::s III Figure 2-9 c.. s: III ci 1Il :0 m :::.. -III 0U... ::J a.. (J) Ql 6.0 J: s:: wa:: (.) G ::s "'1J III lq CD I\.) " ':? '"fl,,,". 'l: ",'v.l ":1 0' x <t:f cp 0 ".v " ro','v 0 '\,««foj,,-( OJ,,<:J,,-( PRESSURE-DROP CALCULATIONS WITH UMAC QUAKE BREAKER AT METER AND MAGNE FLO AT EACH APPLIANCE " '" \;f",," "fl, 0*- 0"'\,,'" cp,,":1 o C::J 0,,",, v,.s;

27 Low-Pressure EFVs Calculations Table 2-7 Pressure-Drop Calculations With Sanders At Meter And Magne-Flo At Each Appliance SECT d RES NOMINAL SKh FT d 1225 PRESS INWC ACTUAL L Q INWC TOT PRESS DROP PRESS DROP EXCLUDING FLEX CONNECTOR Notes: (1) Pressure-drop calculation for Magne-Flo 5/8" valve Given: 1" 70 CFH (Table 2-1) Ratio: Q=(hy.5 h@ 27 CFH: 70/27=(1 )A.5(h)A.5 = "wc J. Marx Ayres, P.E. Page 2-19

28 ro.=- w 0:: ::J 5.5 en en w 0:: Il. en c.. s: III 7.5 Figure !' (1) :-c rn 7.0 ::E ;,... (1) 1Il 1Il r::::... (1) m "T1 <1Il '265 E. ::::l '0 ()... Ql... III s: 6.0.c: (J < '"C III (Q (1) I\) I I\) o 4.0 &a 00 V)- C1l "CJ C:J (j x"'::" ",,'1-- 0*",,,'" 00 x!',,":1 C:J 0 PRESSURE-DROP CALCULATIONS WITH SANDERS AT METER AND MAGNE-FLO AT EACH APPLIANCE (j,,,,0 _. O '" C; <v+ «.v (') III 0" r:::: III-0" ::::l 1Il

29 Low-Pressure EFVs Calculations Table 2-8 Pressure-Drop Calculations Without EFVs SECT d RES lkvi-' u_vv NOMINAL SKh FT U.t5LL U.::> d PRESS 89 INWC ACTUAL QL 225 L,f0.5 INWC U.::>t51 PRESS DROP EXCLUDING FLEX CONNECTOR J. Marx Ayres, P.E. Page 2-21

30 Low-Pressure EFVs Calculations em LJoul)3nSS3d S" c I z :::I: W < >LL en "< < W e:( :J0 :J U...J 0i= ud.. 0 <6> 6'6> I- en c:: c:: :J enw ",< <9, <9 L' 0L'L' " o O> 0 tsl tslt>-0 L' '..< C'L' +0. c? {y +0. "< Sis 6 0CD Lr.l 0Lr.l /V"k Page 2-22 J. Marx Ayres, P.E.

31 Low-Pressure EFVs Discussion Section 3 Discussion 3.1 CSA U.S. a. The CSA U.S. Requirements No are for EFVs that are designed to limit the flow of gas in the event that the flow through the valve exceeds the level specified by the manufacturer. The criteria are for valves with nominal sizes of 2" or smaller, maximum operating pressures of 250 psi or less, and capability of operating in 32 to 125 F environments. The test requirements include the size of by-pass area in automatic reset type valves to allow for equalization of pressures. The closing flow rates are based on 0.64-SG, 1000-BTU/CF gas. The performance requirements include specified operational positions of the valve, maximum operating pressures, leakage rates not to exceed 20 CC/Hr at 1-1/2 times the maximum operating pressure, 10 CFH maximum bypass rate, and operation to reduce the flow of gas through the device to no more than its bypass flow rate (which must be no more than 2 CFH for manual reset type EFVs, and no more than 10 CFH for automatic reset type EFVs) whenever the flow reaches that particular device's closing flow rate, which can be anything between 80% and 110%, inclusive, of the manufacturer's specified closing flow rate for that model. b. The procurement of the CSA test results and other manufacturer literature was difficult. The latest UMAC and Sanders data were obtained from attachments to the Los Angeles Mechanical Testing Laboratory's Research Reports, and the Magne-Flo data from submissions to the DSA. 3.2 Appliance Connectors a. b. CSA U.S. test data for appliance connectors were not available, and publications from one manufacturer provided CSA pressure-drop data for straight flexible metal tubing without bends that normally occur in the field. See Appendix A. The published data provided flow capacities at 0.5" WC pressure-drop with 0.64-SG, 1000/BTU/CF gas per ANSI Z CGA 6.10 for 3/8",1/2", and 5/8" nominal 0.0. connectors. The UPC Table provides capacities of "listed" appliance connectors in 8" WC or less systems based on 0.2" WC pressure drop with 1100 BTU/CF gas. Note 3 under UPC Table states that tests were based on complete assemblies, including fittings and valves. The test configuration, definition of valve type, and test data were not available to the author, so all of the spread sheet calculations incorporated 0.5" WC pressure drop for the appliance connectors. It should be noted that Brass Craft has recently purchased Magne-Flo and plans to offer the EFVs with their flexible connectors. If this is true, their connector and EFV should be tested and listed as a unit. 3.3 Pressure Drops J. Marx Ayres, P.E. Page 3-1

32 Low-Pressure EFVs Discussion The objective of this study was to determine the impact of EFVs on the upe 0.5" we maximum piping system pressure-drop allowance. Examination of Tables 2-2 through 2-8 and Figures 2-2 through 2-11 allows the reader to identify the various pressure drops, starting with a 7" we service. It should be noted that minimum pressures necessary for safe and efficient appliance operation can vary from 5" to 3-1/2" we. It is known that the designer can in some circumstances use larger size pipe to off-set the EFV pressure losses, but it is not practical due to the additional construction costs. J. Marx Ayres, P.E. Page 3-2

33 Low-Pressure EFVs Conclusions Section 4 Conclusions & Recommendations 4.1 Conclusions 1. When EFVs are installed in typically sized low-pressure gas systems, the total pressure drop of the systems will exceed the UPC maximum allowed 0.5" WC pressure drop. 4.2 Recommendations 1. Building Codes should require mechanical plan checks for any low-pressure gas systems using one or more EFVs. 2. Pressure drops across flexible appliance connectors should be listed with a defined number and radii of bends or loops. 3. If a flexible connector is provided with an EFV, the pressure drops should be listed both with and without the EFV. J. Marx Ayres, P.E. Page 4-1

SIZING AND CAPACITIES OF GAS PIPING

SIZING AND CAPACITIES OF GAS PIPING CALIFORNIA RESIDENTIAL CODE MATRIX ADOPTION TABLE APPENDIX A SIZING AND CAPACITIES OF GAS PIPING (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state

More information

SIZING AND CAPACITIES OF GAS PIPING

SIZING AND CAPACITIES OF GAS PIPING APPENDIX A (IFGS) SIZING AND CAPACITIES OF GAS PIPING (This appendix is informative and is not part of the code.) A.1 General. To determine the size of piping used in a gas piping system, the following

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS MARSHA L. BROWN PRESIDENT PEDRO BIRBA VICE-PRESIDENT VAN AMBATIELOS HELENA JUBANY ELENORE A. WILLIAMS November 14, 2007 CITY OF LOS ANGELES CALIFORNIA ANTONIO

More information

SIZING AND CAPACITIES OF GAS PIPING (Not Adopted by the State of Oregon)

SIZING AND CAPACITIES OF GAS PIPING (Not Adopted by the State of Oregon) (IFGS) SIZING AND CAPACITIES OF GAS PIPING (Not Adopted by the State of Oregon) (This appendix is informative and is not part of the code. This appendix is an excerpt from the 2006 International Fuel Gas

More information

Gas Line Sizing. Z Maximum gas demand shall be determined by adding all of the equipment Btu ratings from appliances connected on the system.

Gas Line Sizing. Z Maximum gas demand shall be determined by adding all of the equipment Btu ratings from appliances connected on the system. Gas Line Sizing When sizing Gas piping systems certain factors must be considered. They are: Z It shall provide sufficient gas to meet the maximum demand of the gas equipment. Piping must be sized to supply

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

Introduction to Water Pipe Sizing

Introduction to Water Pipe Sizing ONTARIO PLUMBING INSPECTORS ASSOCIATION INC. In the public service since 1920 Introduction to Understanding the Many Methods to Size Water Pipe Presented by: Rainier Bratsch-Blundel, CPSI Plumbing Professor

More information

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger

More information

PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS. Second Edition. Prepared by

PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS. Second Edition. Prepared by PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS Second Edition Prepared by NAHB Research Center, Inc. 400 Prince Georges Boulevard Upper Marlboro, MD 20774-8731 DISCLAIMER This

More information

CSST Flexible Gas Pipe. System Design and Installation Manual

CSST Flexible Gas Pipe. System Design and Installation Manual CSST Flexible Gas Pipe System Design and Installation Manual Suggested Tools for Installation of HOME-FLEX Use to cut HOME-FLEX tubing to desired length. Tubing Cutter Use to remove yellow protective jacket

More information

Saves time. Saves money. Up to 2 size for commercial gas piping.

Saves time. Saves money. Up to 2 size for commercial gas piping. Flexible Gas Piping by OmegaFlex Saves time. Saves money. Up to 2 size for commercial gas piping. Cost-effective, safe and completely reliable, TracPipe/CounterStrike is the ideal pipe for new construction,

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information

Electrical Connection. Provide Proper Electrical Supply. Electrical Requirements. Connecting using the supplied cord and plug

Electrical Connection. Provide Proper Electrical Supply. Electrical Requirements. Connecting using the supplied cord and plug Electrical Connection When installed the range must be electrically grounded in accordance with local codes or; in the absence of local codes with the National Electrical Code ANSI/NFPA 70, latest edition.

More information

What to Expect From the Examination. How to Study the Plumbing Codes

What to Expect From the Examination. How to Study the Plumbing Codes Texas State Board of Plumbing Examiners Plumbing Inspector Examination Review Course The following Examination Review Course is designed to assist an applicant in preparing for the Plumbing Inspector examination.

More information

Method to Determine PERFORMANCE OF INDIRECT-FIRED WATER HEATERS March 2003 Edition

Method to Determine PERFORMANCE OF INDIRECT-FIRED WATER HEATERS March 2003 Edition Supplement to TESTING STANDARD Method to Determine PERFORMANCE OF INDIRECT-FIRED WATER HEATERS March 2003 Edition [NOTE: This supplement incorporates testing and calculations to determine heat source friction

More information

PLBG/GAS SAFETY Information Bulletin

PLBG/GAS SAFETY Information Bulletin PLBG/GAS SAFETY Information Bulletin November 2012 P/G-08-02-PLBG/GAS [Rev 3] Page 1 of 11 SUBJECT: REQUIREMENTS FOR COMBINATION HEATING SYSTEMS: DUAL PURPOSE WATER (POTABLE) HEATER (COMBO UNIT) Safety

More information

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC)

Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC) Valve Proving System VPS 504 Series S06 (120 VAC) Series S05 (24 VDC) VPS 504 S06 (120 VAC) is: CSA Certified File # 1637485 CSA Requirement No. 4-01 (USA) Technical Information Letter R-15 (Canada) UL

More information

One of the fundamental design elements that every

One of the fundamental design elements that every Preliminary Design Information Before starting the water system design, you must assemble a collection of information. This includes information from the owner, the local utility, and the architect. Things

More information

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners M/MR Modulating Valves design certified For Atmospheric, Infrared, and Direct Fired urners TALE OF CONTENTS Description/Specifications... 1 Introduction... 2 Direct Fired Applications (Negative Pressure)...

More information

PLUMBING RE-SUBMITTAL 22 11 17

PLUMBING RE-SUBMITTAL 22 11 17 PLUMBING RE-SUBMITTAL 22 11 17 ACADEMIC BUILDING & PATRIOT S CASA TEXAS A&M UNIVERSITY - SAN ANTONIO, TX NO. 25-3122, VAC NO. 39019 OWNER: ARCHITECT: MEP ENGINEER: GENERAL CONTRACTOR: PLUMBING CONTRACTOR:

More information

SIZING OF WATER PIPING SYSTEM

SIZING OF WATER PIPING SYSTEM SIZING OF WATER PIPING SYSTEM SECTION E101 GENERAL E101.1 Scope. E101.1.1 This appendix outlines two procedures for sizing a water piping system (see Sections E103.3 and E201.1). The design procedures

More information

Arapahoe County Residential Water Heater Installation and Inspection Guide

Arapahoe County Residential Water Heater Installation and Inspection Guide Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

Watts Spacemaker. Sa f e t y Wa t e r He a t e r. Enclosures Stands Restraints

Watts Spacemaker. Sa f e t y Wa t e r He a t e r. Enclosures Stands Restraints Watts Spacemaker Sa f e t y Wa t e r He a t e r Installation Products Enclosures Stands Restraints Ta b l e o f Co n t e n t s / In t r o d u c t i o n / Seismic Zo n e s Table of Contents Seismic Zones

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters CYCLONE Mxi MODULATING MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable

More information

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.

More information

DOUBLE SEAT BRONZE BODY HIGH CAPACITY

DOUBLE SEAT BRONZE BODY HIGH CAPACITY PS593DB HEAVY DUTY BRONZE GLOBE CONTROL VALVES DB DOUBLE SEAT BRONZE BODY HIGH CAPACITY 1, 1-1/4, 1-1/2, and 2 Union Ends ANSI Class 250 Body Rating ANSI Class II Close off Bronze or Stainless Steel Trim

More information

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage

More information

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing) CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

NAVIEN AMERICA INC. 17855 FITCH AVENUE

NAVIEN AMERICA INC. 17855 FITCH AVENUE Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:

More information

GAS DISTRIBUTION PRODUCTS STEEL SERVICE TEES

GAS DISTRIBUTION PRODUCTS STEEL SERVICE TEES GAS DISTRIBUTION PRODUCTS STEEL SERVICE TEES CONTINENTAL INDUSTRIES ABOUT US THE ULTIMATE CONNECTION Our Company Continental Industries, headquartered in Tulsa, Oklahoma, was formed in 1958 and is today

More information

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID

More information

Instantaneous gas water heater

Instantaneous gas water heater Instantaneous gas water heater Models W 125...T1 installation operation maintenance The Bosch instantaneous water heater is a high efficiency, space saving answer to your water heating needs. All Bosch

More information

CHAPTER II. This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192.

CHAPTER II. This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192. CHAPTER II REGULATOR AND RELIEF DEVICES This chapter contains a simplified description of the pipeline safety requirements. The complete text can be found in 49 CFR Part 192. BASIC CONCEPT In understanding

More information

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases

More information

TECHNICAL MANUAL GDS8 & GHS8

TECHNICAL MANUAL GDS8 & GHS8 TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as

More information

Technical Solution Sheet 5.03 5: Cold Water Plumbing

Technical Solution Sheet 5.03 5: Cold Water Plumbing 5: Cold Water Plumbing Drawings of Typical Water and Fire Services, Pipe Materials and Private Service AIM The aim of this technical solution is to inform practitioners on the typical requirements for

More information

Static Pressure Losses in 6, 8, and 10 Non-Metallic Flexible Duct

Static Pressure Losses in 6, 8, and 10 Non-Metallic Flexible Duct Static Pressure Losses in 6, 8, and 10 Non-Metallic Flexible Duct Kevin Weaver, EIT, Graduate Research Assistant* Charles Culp, Ph.D., P.E., ASHRAE Fellow, Associate Professor Texas A&M University ABSTRACT

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600

More information

ASX7-4-IOM-7 J30-08579

ASX7-4-IOM-7 J30-08579 INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT

More information

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

Commercial Gas Water Heaters

Commercial Gas Water Heaters UP TO 96% THERMAL EFFICIENCY, DIRECT-VENT FEATURES TM BTH-120 through BTH-500 The A. O. Smith Cyclone Xi family of products represents the industry s most technologically advanced commercial water heaters.

More information

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08

The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08 Air Volume Requirement Air conditioning systems are engineered with a specific amount of indoor air passing across the surface of the evaporator coil. The amount of air is measured in cubic feet per minute.

More information

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494 THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494 1. BEFORE YOU BEGIN IMPORTANT INSTRUCTIONS READ AND SAVE FOR THE CONSUMER WARNING: Risk of scalding or other severe injury. Before completing installation,

More information

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

TANKLESS WATER HEATER INSTALLATION DIAGRAMS TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water

More information

Recreational Vehicles

Recreational Vehicles Recreational Vehicles Gas pressure Regulators & Accessories 2012 EDITION RE-01 Recreational vehicles Product index 1 - Introduction P.4 1.1 Pressure Gas Regulators P.4 1.2 Installations P.4 1.3 Backflow

More information

Gas Valves. Thermocouples. Pilots. Thermopiles. Water Heating WH/HVAC PRODUCT INFORMATION

Gas Valves. Thermocouples. Pilots. Thermopiles. Water Heating WH/HVAC PRODUCT INFORMATION WH/HVAC PRODUCT INFORMATION Gas Valves Thermocouples Pilots Thermopiles Water Heating Visit www.uni-line.com for detailed information on our complete product offering WH/HVAC MILLIVOLT PRODUCT 7500 INFORMATION

More information

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459 SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work

More information

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes

More information

SPERRYN GAS CONTROLS DELTA FLUID PRODUCTS LIMITED

SPERRYN GAS CONTROLS DELTA FLUID PRODUCTS LIMITED SPERRYN GAS CONTROLS DELTA FLUID PRODUCTS LIMITED Domestic and Non-Domestic Meter Regulators G940/G941 - Domestic Meter Regulator Domestic regulator offering high performance in a compact unit. Sizes:

More information

CSA GROUP 8501 EAST PLEASANT VALLEY ROAD CLEVELAND, OHIO 44131

CSA GROUP 8501 EAST PLEASANT VALLEY ROAD CLEVELAND, OHIO 44131 This is to attest that CSA GROUP 8501 EAST PLEASANT VALLEY ROAD CLEVELAND, OHIO 44131 Testing Laboratory TL-266 has met the requirements of the IAS Accreditation Criteria for Testing Laboratories (AC89),

More information

LPM-06 CONVERSION KIT

LPM-06 CONVERSION KIT LPM-06 CONVERSION KIT TWO-STAGE FURNACE NATURAL GAS TO L.P. GAS CONVERSION Goodman Manufacturing Company, L.P. 2009-2011 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com -or- www.amana-hac.com

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996

Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 CITY OF SAN JOSE BUILDING DIVISION POLICY Policy on Water Heater Installations Policy No. UPC 510-1-94 Effective: September 1, 1995 Revised: February 10, 1996 All new and replacement water heaters installed

More information

Engineering Specifications

Engineering Specifications PUREFLOW PEX PRODUCTS PART 1 GENERAL 1.1 SUMMARY 1.1.1 This specification covers Branch & Main, Parallel Water Distribution Systems (MANABLOC), Cross-linked Polyethylene tubing and fittings using PEX Press

More information

BLADDER SURGE CONTROL SYSTEM

BLADDER SURGE CONTROL SYSTEM PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures

More information

CHAPTER 2 HYDRAULICS OF SEWERS

CHAPTER 2 HYDRAULICS OF SEWERS CHAPTER 2 HYDRAULICS OF SEWERS SANITARY SEWERS The hydraulic design procedure for sewers requires: 1. Determination of Sewer System Type 2. Determination of Design Flow 3. Selection of Pipe Size 4. Determination

More information

A COMPARISON OF WATER LEAK DETECTION AND SHUTOFF SYSTEMS

A COMPARISON OF WATER LEAK DETECTION AND SHUTOFF SYSTEMS A COMPARISON OF WATER LEAK DETECTION AND SHUTOFF SYSTEMS By Charles Ergle January 16, 2012 As every appraiser knows, water damage is the single highest continual source of claims at Chubb. Fires happen,

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information

Commercial & Industrial Propane Regulators and Meters

Commercial & Industrial Propane Regulators and Meters Commercial & Industrial Propane Regulators and Meters Master Distributor for First Stage Regulators P32* Field adjustable 60 Mesh screen on inlet 1/4 FNPT 250 PSI Excellent stability P37* Patented balance

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

Pressure Switch for gas and air

Pressure Switch for gas and air Switch for gas and air GAO-A4 GMH-A4 GML-A4 UL Listed UL 353 File # MH 16628 CSA Certified CSA C22.2 No. LR 53222 Certification file # 201527 FM Approved Class 3510, 3530 File # J.I. 1Y919.AF Commonwealth

More information

The Unique Accelabar Flow Meter

The Unique Accelabar Flow Meter The Unique Accelabar Flow Meter The Accelabar is a new and unique flow meter that combines two differential pressure technologies to produce operating ranges never before attainable in a single flow meter.

More information

Green Plumbing and Mechanical Code Supplement

Green Plumbing and Mechanical Code Supplement Green Plumbing and Mechanical Code Supplement Doug Kirk IAPMO Director of Green Plumbing Curriculum [email protected] 1 IAPMO Green Uniform Codes - developed with critical eye on sustainability 2007-

More information

CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY

CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft CITY of LOS ANGELES DEPARTMENT of BUILDING and SAFETY Draft Los Angeles Plumbing Code (LAPC) 2008 California Plumbing Code (CPC) 2007 Uniform Plumbing Code (UPC) 2006 Major Code Changes Preliminary

More information

Electric Water Heater

Electric Water Heater Electric Water Heater Operation and Installation Manual (LIMITED WARRANTY AND TANK REPLACEMENT POLICY) The following information should be noted at time of installation and retained for future reference.

More information

248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS

248 CMR: BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS 248 CMR 5.00: AMENDMENTS TO NFPA 54 Section 5.01: Modifications to Chapter 1, Administration 5.02: Modifications to Chapter 2, Referenced Publications 5.03: Modifications to Chapter 3, Definitions 5.04:

More information

Types 66R and 66RR Low-Pressure Relief Valves

Types 66R and 66RR Low-Pressure Relief Valves November 2009 Types 66R and 66RR Low-Pressure Relief Valves W1953 W1908 TYPE 66R RELIEF VALVE TYPE 66RR RELIEF VALVE Figure 1. Typical Constructions Introduction Types 66R and 66RR low-pressure throttling

More information

1.- L a m e j o r o p c ió n e s c l o na r e l d i s co ( s e e x p li c a r á d es p u é s ).

1.- L a m e j o r o p c ió n e s c l o na r e l d i s co ( s e e x p li c a r á d es p u é s ). PROCEDIMIENTO DE RECUPERACION Y COPIAS DE SEGURIDAD DEL CORTAFUEGOS LINUX P ar a p od e r re c u p e ra r nu e s t r o c o rt a f u e go s an t e un d es a s t r e ( r ot u r a d e l di s c o o d e l a

More information

PMA ONLINE TRAINING Venting for Plumbing Systems

PMA ONLINE TRAINING Venting for Plumbing Systems PMA ONLINE TRAINING Venting for Plumbing Systems One Hour Continuing Education Venting PMA training disclaimer The information provided in this document is intended for use as a guideline and is not intended

More information

B. Shop Drawings: Diagram power, signal, and control wiring.

B. Shop Drawings: Diagram power, signal, and control wiring. SECTION 224500 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Emergency showers. 2. Eyewash equipment. 3. Eye/face wash equipment. 4. Combination units. 5. Water-tempering equipment. 1.2 SUBMITTALS

More information

C I T Y O F S E L M A F I R E D E P A R T M E N T

C I T Y O F S E L M A F I R E D E P A R T M E N T C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:

More information

Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves

Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves Pressure Locking & Thermal Binding In Wedge Gate & Parallel Slide Gate Valves CRANE Energy Flow Solutions TM Donald H. Johnson Crane Energy Flow Solutions 1 Crane Co. Resolution Made By Richard Teller

More information

SANITARY GRAVITY SEWER LINE TESTING. B. Section 02732 CCTV Inspection of Gravity Sewer Lines

SANITARY GRAVITY SEWER LINE TESTING. B. Section 02732 CCTV Inspection of Gravity Sewer Lines PART 1 GENERAL 1.1 SECTION INCLUDES A. Low Pressure Air Test B. Deflection Test 1.2 RELATED SECTIONS A. Section 02730 Sanitary Gravity Sewer Lines B. Section 02732 CCTV Inspection of Gravity Sewer Lines

More information

(a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems.

(a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems. 12.33 - CROSS-CONNECTION CONTROL. (a) Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems. (b) Definitions. The following definitions shall apply

More information

TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs

TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs TITLE 22 PART 17 CHAPTER 363 RULE 363.11 EXAMINING BOARDS TEXAS STATE BOARD OF PLUMBING EXAMINERS EXAMINATION AND REGISTRATION Endorsement Training Programs (a) General requirements for Course Providers

More information

APPENDIX A CONTROL VALVE TESTING PROCEDURES AND EQUATIONS FOR LIQUID FLOWS

APPENDIX A CONTROL VALVE TESTING PROCEDURES AND EQUATIONS FOR LIQUID FLOWS APPENDIX A CONTROL VALVE TESTING PROCEDURES AND EQUATIONS FOR LIQUID FLOWS Section A.1. Flow Coefficients Definition The flow coefficient or pressure loss coefficient is used to relate the pressure loss

More information

SCO TT G LEA SO N D EM O Z G EB R E-

SCO TT G LEA SO N D EM O Z G EB R E- SCO TT G LEA SO N D EM O Z G EB R E- EG Z IA B H ER e d it o r s N ) LICA TIO N S A N D M ETH O D S t DVD N CLUDED C o n t e n Ls Pr e fa c e x v G l o b a l N a v i g a t i o n Sa t e llit e S y s t e

More information

Owner Retain this manual in a safe place to provide your serviceman information if it becomes necessary.

Owner Retain this manual in a safe place to provide your serviceman information if it becomes necessary. INSTALLATION, OPERATING AND SERVICE MANUAL FOR EASY RADIANT WORKS HEATWAVE MODEL GH-25-40 GAS FIRED, VENTED INFRARED TUBE HEATER FOR RESIDENTIAL & COMMERCIAL / INDUSTRIAL APPLICATIONS. For Your Safety

More information

Flow controller with integrated control valve (PN 16, 25, 40*) AFQM, AFQM 6 - return and flow mounting

Flow controller with integrated control valve (PN 16, 25, 40*) AFQM, AFQM 6 - return and flow mounting Data sheet Flow controller with integrated control valve (PN 16, 5, 40*) AFQM, AFQM 6 - return and flow mounting Description AFQM 6 DN 40, 50 AFQM DN 65-15 AFQM DN 150-50 AFQM(6) is a self-acting flow

More information

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 thru inch (DN40 thru DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical

More information

GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center

GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center Heat pumps are used where geothermal water or ground temperatures are only slightly above normal, generally 50 to 90 o F. Conventional

More information

Vickers. Check Valves. Check Valves. Inline, right angle, manifold mounted, and pilot operated designs. Released 9/93

Vickers. Check Valves. Check Valves. Inline, right angle, manifold mounted, and pilot operated designs. Released 9/93 Vickers Check Valves Check Valves Inline, right angle, manifold mounted, and pilot operated designs Released 9/93 645 Introduction Vickers inline, right-angle, and manifold mounted check valves are direct

More information

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle

More information

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained). CITY OF MILPITAS Building & Safety Department 455 E. Calaveras Blvd. Milpitas, CA 95035 408-586-3240 www.ci.milpitas.ca.gov RESIDENTIAL AIR CONDITIONING, REPLACEMENT 1. PERMIT INFORMATION: The replacement

More information

CSA Group and Certification Marks

CSA Group and Certification Marks CSA Group and Certification Marks CSA Group Independent, not-for-profit, membership association in business since 1919, dedicated to advancing safety, sustainability and social good. One of the largest

More information

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409 Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam

More information

Addendum to Florida Academy Catalog for: HVAC Fundamentals HVAC Advanced Fundamentals

Addendum to Florida Academy Catalog for: HVAC Fundamentals HVAC Advanced Fundamentals Addendum to Florida Academy Catalog for: HVAC Fundamentals HVAC Advanced Fundamentals HVAC PROGRAMS The school s Heating, Ventilation, and Air Conditioning Programs provide training for entry level employment

More information

SECTION 5: SANITARY SEWER SYSTEM DESIGN

SECTION 5: SANITARY SEWER SYSTEM DESIGN SECTION 5: SANITARY SEWER SYSTEM DESIGN 5.01 GENERAL Sanitary sewer improvements shall be designed to serve the ultimate level of City development as defined in the General Plan and the Wastewater Facilities

More information