1 Basic Electrical Theory 2 Cy Dodimead Earthing: The direct physical connection to earth The thing to remember is that the earth (ground we stand on) is an even better conductor of electricity than the wires used for transporting it around the house. Given the chance of a better conductor and a shorter route, electricity will take it. This means that if you place yourself between the two, it will travel through you to get there. The whole of the world may be considered as a vast conductor which is at reference (Zero) potential. (potential here being the difference between two voltages) People are usually more or less in contact with earth, so if other parts which are open to touch become charged at a different voltage from earth a shock hazard exists. When we have a voltage of potential difference of 230V, we have raised the voltage to 230V above zero. When do we earth? At all times (except in very exceptional circumstances). Why do we earth? In order to provide the shortest path to earth for the current in the event of a fault. Also the BS th edition states a circuit protective conductor shall be run to and terminated at each point in the wiring. Earthing arrangements: Internal standard IEC distinguishes three families of earthing arrangements, using the two-letter codes. TN, TT and IT. The driest letter indicates the connection between earth and the power supply equipment (generator to transformer) T = direct connecting of a point with earth (Latin: Terra) I = no point is connecting with earth (isolation), exempt perhaps via a high impedance. the second letter indicates the connecting between earth and the electrical device being supplies: T = direct connecting of a point with earth N = direct connection to neutral at the origin of installation, which is connected to the earth.

2 TN-S / TN-C-S / TT T stands for Terra which is earth in latin. N stands for direct connection to neutral at the origin or installation, which is connected to the earth 2nd T stands for direct connection of a point of earth C stands for combined in relation to the neutral and the earth S stands for separate in relation to the neutral and the earth For a 3 phase intake you will usually have a TN-C-S system. On a start connection this is known as a 3 phase 4 wire. Reasons for bonding/earthing: CPC = Circuit protective conductor (Earth) 1. Sufficient current should flow under and earth fault so that the protective device (fuse or a circuit breaker) operates within a pre-defined time. 2. While the fault exists metal work could rise to a high potential 3. Bonding occurs to enable exposed and extraneous metal work to be linked together. This gives us an equipotential zone. PAT test: Portable Appliance Test An item that has passed the PAT test means the item is electrically safe to use. Class 1 appliance: These appliances must have their chassis connected to an electrical earth by an earth conductor (CPC). A fault in the appliance which causes a live conductor to contact the casing will cause a cut tent to flow in the earth conductor. This cut tent should trip an over current device i.e fuse. Class 2 appliance: A class 2 or double insulated electrical appliance is one which has been designed in such a sway that it does not requite a softy connection to electrical earth. The basic requirement is that no single failure can result in dangerous voltage becoming exposed so that it might cause electric shock and the is achieved without trying on an earthed metal casing. This is usually achieved at least in part by having who layers of insulating material surrounding live parts of by using reinforced insulation. In Europe, a double insulated appliance must be labelled Class 2, double insulated or bear the double insulation symbol a square inside another square) Class 3 appliance: A Class 3 appliance is designed to be supplies dorm a SELV (Separated Extra-Low Voltage power source. The voltage from a SELV supply is low enough that under normal conditions a person can safely come into contact with it with ought risk of electrical shock. The extra safety features built into Class 1 and Class 2 appliances are therefor not required.

3 Earthing and Audio: Mains cables carry relatively high alternating currents that can be induced into audio cables running alongside them, even if the audio cable is well screened. The longer this distance the cables run alongside each other, the greater the amount of interface (usually hum) that will be induced int the signal cable. When audio and mains cables must cross, try to arrange the crossing to be at right angles as this is the angle of minimum coupling. Ground Loop: in an electrical system, a ground loop usually refers to a current, generally unwanted, in a conductor connecting two points that are supposed to be at the same potential, often ground (Earth), but are actually at different potential. A group loop in the power or video signal occurs when some components in the same system are receiving its power from a different ground than other components, or the ground potential between two pieces of equipment is not identical. They can also create an electric shock hazard, since ostensibly Grounded parts of the equipment, which are often accessible to users, are not at ground potential. Balancing 3 phase loads: A balanced three phase load will have the same current on al phases and therefor cancel each other out. If there is an unbalanced load then the remaining current will have to pass down the neutral conductor. Example: L1 = 100A L2 = 50A L3 = 130A kva is Apparent Power kva = Kilo Volt amps kva x 1000 / 400 / 1.73 = Amps 3 phase kva x 1000 / 230 = Amps 1 phase or google kva calculator. Basic protection: The neutral conductor is taking the excess current 70A BS 7671 says Protection against electric shock under fault-free conditions This is the enclosure of electrical parts to stop the exposure of live parts.

4 Fault protection: BS 7671 says Protection against electric shock under single-fault conditions Fuses: - BS 3036 Rewireable fuses - BS 1361/1362 cartridge fuse - BS 88 HBC fuse (High Breaking Capacity) MCB s: Miniature Circuit Breaker The sizes come in: 6A, 10A, 16A, 20A, 32A, 40A, 50A, 63A Types are B, C and D Type B trips between 3 and 5 time full load current. Type C trips between 5 and 10 times full load current. Type D trips between 10 and 20 times full load current. RCD s: All MCB s types use a magnetic fault protection, which trips the MCB. RCD s operate by measuring the current balance between two conductors using a differential current transformer. This measures the difference between the current flowing out of the live conductor and that returning through the neutral conductor. If these do not sum to Zero, there is a leakage of current to somewhere else. (to earth, or to another circuit), and the device will open its concats. Cables: H07RN-F 1. Fine stranded cu-conductor 2. Rubber insulation 3. Filler 4. Rubber outer sheath H05RN-F 1. Fine stranded cu-conductor 2. Rubber insulation 3. Rubber outer sheath IP - Ingress Protection: The IP Code or Ingress Protection Rating consist of lettert IP followed by two digits and an optional letter. As defined in inter nation standard IEC 60529, it classifies the degrees of protection provided against the intrusion of solid objects (including body parts like hands and fingers, disk, accidental contact and water in electrical enclosures.

5 The standard aims to provide users more details information than vague marketing turns such as waterproof. Levels: 0 = No protection 1 = >50mm any large surface of the body 2 = >12.5mm fingers similar objects 3 = 2.5mm tools thick wires 4 = >1mm most wires, screws etc. 5 = dust 6 = dust tight. Water protection: 0 = not protected 1 = dripping water 2 = dripping water rille up to 15 3 = spraying water 4 = splashing water 5 = water jets 6 = powerful water jets 7 = immersion up to 1m 8 = immersion beyond 1m

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

PROTECTION AGAINST ELECTRIC SHOCK by John Ware 16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

Grounding Demystified

Grounding Demystified Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%

More information

Section B: Electricity

Section B: Electricity Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn

More information

Are you aware. Outline

Are you aware. Outline Electrical Safety of Medical Equipment Hasan Al-Nashash School of Engineering American University of Sharjah (AUS) 1 Are you aware Electrocutions are the 5th leading cause of accidental death in the U.S.

More information

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

CHECKING AND TESTING ELECTRICAL INSTALLING WORK CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical

More information

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

6.0 Electrical Installations

6.0 Electrical Installations 6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is

More information

Screened cable and data cable segregation

Screened cable and data cable segregation December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;

More information

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry

More information

Instructions for Safe Use

Instructions for Safe Use Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety

More information

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC

More information

By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.

By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios. 16 Operation of portable generators Operation of portable generators By Mark Coles This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES

INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES 1 By kind permission of MK INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES By Mark Coles The IEE receives many enquiries relating to the inspection and testing of electrical

More information

Circuit Electrical Testing

Circuit Electrical Testing Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved

More information

Residual Current Circuit Breaker

Residual Current Circuit Breaker Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect

More information

Electrical safety for entertainers

Electrical safety for entertainers Electrical safety for entertainers Electrical safety for entertainers If you are an entertainer who uses electrical equipment for sound, lighting or other effects, this leaflet is for you. It sets out

More information

chapter8 Testing and commissioning Unit 2 outcome 2

chapter8 Testing and commissioning Unit 2 outcome 2 Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.

More information

Unit 4: Electricity (Part 2)

Unit 4: Electricity (Part 2) Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State

More information

FREQUENTLY ASKED QUESTIONS

FREQUENTLY ASKED QUESTIONS September 2011 FREQUENTLY ASKED QUESTIONS Wiring Rules The new edition of the Australian/New Zealand Standard for Wiring Rules (AS/NZS 3000:2007) was released in November 2007 and revised by Amendment

More information

Electrical Resistance Resistance (R)

Electrical Resistance Resistance (R) Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed

More information

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE

More information

NEW ZEALAND ELECTRICAL CODE OF PRACTICE REPAIR AND MAINTENANCE OF DOMESTIC ELECTRICAL APPLIANCES BY THE OWNER OF THE APPLIANCE

NEW ZEALAND ELECTRICAL CODE OF PRACTICE REPAIR AND MAINTENANCE OF DOMESTIC ELECTRICAL APPLIANCES BY THE OWNER OF THE APPLIANCE NZECP 50:2004 ISSN 0114-0663 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR REPAIR AND MAINTENANCE OF DOMESTIC ELECTRICAL APPLIANCES BY THE OWNER OF THE APPLIANCE Issued by: Deputy Secretary Energy Safety

More information

Introduction to Data Centre Design

Introduction to Data Centre Design Introduction to Data Centre Design Barry Elliott BSc RCDD MBA CEng Earthing, grounding and bonding November 09 Earthing what s the point Safety from electrical hazards Reliable signal reference within

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Explosion proof enclosures

Explosion proof enclosures 1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without

More information

Model 1756 Test Lead Kit

Model 1756 Test Lead Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you

More information

Electrical installation condition reporting:

Electrical installation condition reporting: Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations FUSED 4 Issue 3 This is one of a series of Best Practice Guides produced by the Electrical

More information

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi One of the most common errors uncovered by product safety engineers stems from manufacturers and designers failing to fully

More information

LOXONE 12 Channel Amplifier

LOXONE 12 Channel Amplifier LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications. ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications. Ensuring operational continuity To ensure the operational continuity of an electrical

More information

Nexus Technology Review -- Exhibit A

Nexus Technology Review -- Exhibit A Nexus Technology Review -- Exhibit A Background A. Types of DSL Lines DSL comes in many flavors: ADSL, ADSL2, ADSL2+, VDSL and VDSL2. Each DSL variant respectively operates up a higher frequency level.

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

A Guide to 17th Edition Testing

A Guide to 17th Edition Testing Seaward, Bracken Hill, South West Industrial Estate, Peterlee, County Durham, SR8 2SW United Kingdom Tel: +44 (0) 191 586 3511 Fax: +44 (0) 191 586 0227 Email: sales@seaward.co.uk Web: www.seaward.co.uk

More information

Electrical safety and you

Electrical safety and you Electrical safety and you A brief guide Introduction Electricity can kill or severely injure people and cause damage to property. Every year many accidents at work involving electric shock or burns are

More information

Guidance notes for the installation of electrical supply in mobile trailers for breast screening

Guidance notes for the installation of electrical supply in mobile trailers for breast screening NHS Breast Cancer Screening Programme Cancer Screening Programmes Guidance notes for the installation of electrical supply in mobile trailers for breast screening B Mansfield, CP Lawinski NHSBSP PUBLICATION

More information

White Paper: Electrical Ground Rules

White Paper: Electrical Ground Rules Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment

More information

Elementary circuits. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Elementary circuits. Resources and methods for learning about these subjects (list a few here, in preparation for your research): Elementary circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

GUIDE TO THE AM2 EXAM

GUIDE TO THE AM2 EXAM AM2 GUIDE TO THE AM2 EXAM What is AM2? AM2 or the Achievement Measurement 2 is a practical performance skill test administered by the National Electrotechnical Training (NET). You must take the AM2 test

More information

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist

More information

Sample. What Electricity Can Do LESSON 2. Overview and Objectives. Background

Sample. What Electricity Can Do LESSON 2. Overview and Objectives. Background What Electricity Can Do Overview and Objectives Background Light bulbs are such an integral part of everyday life that most people can t imagine being without them. Because people tend to take light bulbs

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Cat7/Class F New Installation Concept New infrastructure. Handbook

Cat7/Class F New Installation Concept New infrastructure. Handbook Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle

More information

Parallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected

Parallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected This sample chapter is for review purposes only. Copyright The Goodheart-Willcox Co., Inc. All rights reserved. Electricity Objectives After studying this chapter, you will be able to answer these questions:.

More information

Electrical Practices for Construction Work

Electrical Practices for Construction Work 1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in

More information

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if

More information

Good EMC Design Principles: cable routing

Good EMC Design Principles: cable routing Good EMC Design Principles: cable routing Keith Armstrong describes three important techniques for cable routing in metal cabinets, whether the cables are bundles of individual wires, or individual or

More information

FIRST STOP SAFETY 1 PAT-IT. Portable Appliance Tester. User Manual. Issue 1.6

FIRST STOP SAFETY 1 PAT-IT. Portable Appliance Tester. User Manual. Issue 1.6 FIRST STOP 1 PAT-IT Portable Appliance Tester User Manual Issue 1.6 First Stop Safety 11 Glaisdale Road Northminster Business Park Upper Poppleton York YO26 6QT t: 01904 791050 f: 01904 780054 e: info@firststopsafety.co.uk

More information

Maintaining portable electric equipment in low-risk environments

Maintaining portable electric equipment in low-risk environments Maintaining portable electric equipment in low-risk environments Introduction This leaflet explains the simple and sensible precautions that need to be taken to prevent danger from portable or movable

More information

Safety & Environmental Protection Services Guidance Note

Safety & Environmental Protection Services Guidance Note Safety & Environmental Protection Services Guidance Note A STEP-BY-STEP GUIDE TO VISUAL INSPECTION OF ELECTRICAL EQUIPMENT Why Inspect? The Health and Safety at Work etc Act 1974 and the Electricity at

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

Degrees of protection. IP codes. W.M.M. Menheere Holec Holland N.V. The Netherlands

Degrees of protection. IP codes. W.M.M. Menheere Holec Holland N.V. The Netherlands Degrees of protection IP codes W.M.M. Menheere Holec Holland N.V. The Netherlands 1 INDEX Introduction...3 1. The IEC protection code (International Protection IP)...3 2. Interpreting the IP code...3 3.

More information

Odyssey of the Mind Technology Fair. Simple Electronics

Odyssey of the Mind Technology Fair. Simple Electronics Simple Electronics 1. Terms volts, amps, ohms, watts, positive, negative, AC, DC 2. Matching voltages a. Series vs. parallel 3. Battery capacity 4. Simple electronic circuit light bulb 5. Chose the right

More information

Fire Protection Notice No. 9 ELECTRICAL SAFETY

Fire Protection Notice No. 9 ELECTRICAL SAFETY Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily

More information

Experts in what we do. Portable Appliance Testing A Practical Guide. www.seaward.co.uk

Experts in what we do. Portable Appliance Testing A Practical Guide. www.seaward.co.uk Experts in what we do. Portable Appliance Testing A Practical Guide www.seaward.co.uk PAT testing is changing Only Apollo 600 puts it in a risk-based health and safety setting On-board camera provides

More information

THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES

THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES What is Hipot? HIPOT is the short term for high potential (high voltage).

More information

Electrical Safety Tips. Help us keep you safe

Electrical Safety Tips. Help us keep you safe Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural

More information

CX Zoner Installation & User Guide

CX Zoner Installation & User Guide CX Zoner Installation & User Guide Cloud Electronics Limited 140 Staniforth Road, Sheffield, S9 3HF England Tel +44 (0)114 244 7051 Fax +44 (0)114 242 5462 e-mail info@cloud.co.uk web site http://www.cloud.co.uk

More information

Neutral Wire Facts and Mythology. White Paper #21

Neutral Wire Facts and Mythology. White Paper #21 Neutral Wire Facts and Mythology White Paper #21 Executive Summary This Technical Note discusses many common misunderstandings about the function of the neutral wire and its relation to power problems.

More information

GroundRod AC Substation Earthing Tutorial

GroundRod AC Substation Earthing Tutorial 1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities

More information

GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS

GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS 2008 EDITION www.st.gov.my CONTENTS Chapter Title Page 1. 1.1 1.2 1.3 Introduction Purpose References 4 4 5 2. Supply System 6 2.1 Electricity

More information

Building Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24

Building Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24 1 Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are safe. The introduction of the 17 th Edition

More information

Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables

Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

SEISMIC VELOCITY TRANSDUCER T1-40

SEISMIC VELOCITY TRANSDUCER T1-40 SEISMIC VELOCITY TRANSDUCER T1-40 Measurement of Omnidirectional Absolute Vibrations Certified according to ATEX 94/9/CE directive OPERATION Transducer T1-40 serves for seismic measurement of the absolute

More information

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont Test Before Touch Easier Said Than Done Ken Crawford, DuPont Kent Haggerty, Dupont Overview Test Before Touch (TBT) Principles Key Learnings by One Company One Method for Performing a TBT Induced Voltages

More information

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment Scott Aldous, Compliance Engineer What is Insulation Coordination? From IEC 60664-1, Edition 1.2: So what does that mean

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

Solving the Problem of Motor Protection from Moisture, Water and Dust in Commercial Refrigerators.

Solving the Problem of Motor Protection from Moisture, Water and Dust in Commercial Refrigerators. WHITE PAPER Solving the Problem of Motor Protection from Moisture, Water and Dust in Commercial Refrigerators. Saving Generation for the Next Generation Overview Moisture, and dust are common causes of

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

Handheld portable appliance testers

Handheld portable appliance testers PAT100 SERIES Handheld portable appliance testers PAT100 SERIES Handheld portable appliance testers Simple Tick/Cross, pass/fail indication plus measurement Battery powered with rechargeable options Includes

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

1 Introduction. 2 Hazards From Electricity

1 Introduction. 2 Hazards From Electricity Risk Assessment Application to Electrical Rigs A guide to assist the Competent Named person who will verify the safety of rigs consisting mainly of electrical equipment. 1 Introduction Every employer shall

More information

Balanced vs. Unbalanced Audio Interconnections

Balanced vs. Unbalanced Audio Interconnections Revised 7/2/08 Balanced vs. Unbalanced Audio Interconnections In discussing the characteristics and performance of various interconnect systems; two points should be kept in mind. Balance is defined in

More information

Electrical safety requirements in DC distribution systems

Electrical safety requirements in DC distribution systems Electrical safety requirements in DC distribution systems PAUL J.L.AN TICHELEN, DOMINIQUE WEYEN ITO Boeretang 200, 2400 Mol BELGIUM Abstract: This paper focuses on the safety requirements for the DC bus

More information

NZQA registered unit standard 15848 version 6 Page 1 of 5. Demonstrate and apply knowledge of safeguards for use with portable electrical appliances

NZQA registered unit standard 15848 version 6 Page 1 of 5. Demonstrate and apply knowledge of safeguards for use with portable electrical appliances Page 1 of 5 Title Demonstrate and apply knowledge of safeguards for use with portable electrical appliances Level 2 Credits 3 Purpose This unit standard covers knowledge of safeguards used in conjunction

More information

Earthing Guidance Notes

Earthing Guidance Notes Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head

More information

Cable Tray Selection-

Cable Tray Selection- Cable Selection- For allowable cable types see the Appendix page A-9. The following guidelines are based on the 2002 National Electrical Code, Article 392. I) Number of Multiconductor Cables rated 2000

More information

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it

More information

Guide to the Selection & Use of Residual Current Devices

Guide to the Selection & Use of Residual Current Devices Guide to the Selection & Use of Residual Current Devices ET214:2005 Edition 1 Electro-Technical Council of Ireland Limited Published by the Electro-Technical Council of Ireland Limited Date of Publication:

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

Achat 115MA full-range speaker. user manual

Achat 115MA full-range speaker. user manual Achat 115MA full-range speaker user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: info@thomann.de Internet: www.thomann.de

More information

1. Electrical Equipment A) Transformer

1. Electrical Equipment A) Transformer Standards and Basic Equipment Date : 15 November 2010 1. Electrical Equipment 2. Terminology 3. Code & Standard 1. Electrical Equipment A) Transformer A1) One Transformer and 11kV Switchgear in High Rise

More information

DIOCESE OF LINCOLN GUIDELINES

DIOCESE OF LINCOLN GUIDELINES DIOCESE OF LINCOLN GUIDELINES FOR ELECTRICAL INSTALLATIONS INSIDE CHURCHES Diocesan Advisory Committee for the Care of Churches Revised March 2006 Electrical Installations inside Churches As with all

More information

3053 Electrical Safety Training Program Course Outline

3053 Electrical Safety Training Program Course Outline 3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting

More information

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters 8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article

More information

TIG INVERTER INSTRUCTION MANUAL

TIG INVERTER INSTRUCTION MANUAL TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

chapter6 Basic electrical circuitry and applications Unit 2 Outcome 3

chapter6 Basic electrical circuitry and applications Unit 2 Outcome 3 Basic electrical circuitry and applications chapter6 Unit 2 Outcome 3 The primary role of an electrician is the installation of electrical circuits and applications. In order to install any type of application,

More information

Cable Size Selection for Energy Efficiency

Cable Size Selection for Energy Efficiency Cable Size Selection for Energy Efficiency Introduction The traditional method for determining the appropriate cable size for a particular installation involves the selection of the smallest size conductor

More information

Installation and safety instructions for AC/DC built-in devices

Installation and safety instructions for AC/DC built-in devices The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further

More information