Instructions for assembly and use MULTICAL 601

Size: px
Start display at page:

Download "Instructions for assembly and use MULTICAL 601"

Transcription

1 Instructions for assembly and use MULTICAL 601

2 1.1 MID labelling Standard conditions of operation/measuring rates: Meter θ: 10 C 180 C Θ: 3K 170K A pair of resistance temperature sensors θ: 10 C 150 C Θ: 3K 140K Flow meter θ: 15 C 130 C Mechanical environment: M1 (solid installation with minimal vibrations). Electromagnetic environment: E1 a E2 (house units, light industry, and industry). Signalling cables from the meter must be lead at a minimum distance of 25 cm from other installations. Climatic environment: This product is intended for interior installation only; it must be installed in a non-condensing environment. The temperature of the environment must be between 5 and 55 C. Maintenance and repair: The keeper is allowed to exchange the communication module, battery, temperature sensors (a pair), and the flow meter. The temperature sensor pair and flow meter are verified separately (independent from the calculator), and thus can be exchanged individually. All repairs require a consequent verification in an accredited laboratory. MULTICAL 601, type 67-B/C/D is suitable for the Pt500 temperature sensors MULTICAL 601, type 67-A is suitable for the Pt100 temperature sensors Battery for an exchange: Kamstrup MULTICAL 601, type 67-A/B/C can be connected to the ULTRAFLOW flow meter; to a unit with an electronic collector; or to a flow meter with a Reed contact. MULTICAL 601, type 67-D, must be connected to a flow meter with an active 24 V impulse output. No matter what the flow meter type is, the imp/l must be the same on both the flow meter and calculator.

3 MULTICAL 601 & ULTRAFLOW English Kamstrup A/S Industrivej 28, Stilling, DK-8660 Skanderborg PHONE NO.: FAX:

4 1. General information Before installing the power meter, study this guide carefully. In case the meter is not properly installed, the Kamstrup Company withdraws all its warranty commitments. Please, notice that it is necessary to meet the following installation conditions: - ULTRAFLOW compression stage: PN16/PN25/PN40, see the ; labelling. The flow meter labelling does not concern the accessories supplied. - Kamstrup compression stage of DS temperature sensors: - The compression stage of stainless steel containers: PN16 PN25/PN40 according to the type If the medium temperature exceeds 90 C, we recommend using flange meters, and mounting the MULTICAL 601 on a wall. 2. Temperature sensor assembly Temperature sensors used for measuring supply and return temperatures form a pair; they must never be separated form each other. MULTICAL 601 is usually supplied with mounted temperature sensors. According to the EN 1434 and OIML R75 standards, their cable length must not be changed. If the sensors need to be exchanged, the complete pair must always be replaced. The red marked sensor must be placed in the supply piping. The other sensor has a blue marking, and must be mounted into the return piping. 2.1 Container sensors It is best to mount the container sensors into T-shaped branches or 45 Y-branches. The end of the container must be placed in the direction of flow, and in the centre of water flow.

5 Temperature sensors must be inserted all the way to the bottom of the containers. If a short period of response is required, a non-setting heat conductive paste may be used. Insert the plastic case of the sensor cable into the sensor container, and fasten the cable with the supplied M4 screw, which has an opening for a sealing wire. The screw is only to be tightened with your fingers. Seal the containers using the seal and wire. 2.2 Short direct temperature sensors Short direct sensors can be mounted into special ball valves or special T-parts. Both contain threads up to the R1 size, and a built-in M10 clutch for a short direct sensor. For assembly into existing heating installations equipped with standard T-shaped branches, the Kamstrup A/S Company is able to supply brass inserts of R½ and R¾ size, suitable for short direct sensors. Short direct sensors can also be installed directly into all ULTRAFLOW machine versions, with G¾ and G1 threads, on the flow parts of the meter. Fasten the brass sensor inserts lightly (to ca 4 Nm), using a 12 mm wrench, and seal the sensors with seal and wire.

6 3. Information E codes MULTICAL 601 continuously monitors a range of important functions. In case of serious damage in the measuring system or installation, an Info note appears on the display. The information code can be read by pressing and holding the left top button, until the Info note shows up on the display. The information code only appears if there is an error. Information Time of Code Description response 000 No error Supply voltage disconnected T1 temperature sensor out of the measuring range 1 to 10 min. 004 T2 temperature sensor out of the measuring range 1 to 10 min. 032 T3 temperature sensor out of the measuring range 1 to 10 min. 064 Cold water system leak 24 hrs 256 Heating system leak 24 hrs 512 Heating system crack Ca 120 sec 4. Assembly of the flow section Before the assembly of the flow section, carefully wash the system and remove protective lids (plastic diaphragms). The correct flow meter position (in supply and return piping) is shown on the label of the MULTICAL 601 front. The direction of the flow is marked with an arrow on the side of the flow meter. Pipe union and sealing must be mounted as given in the picture. ULTRAFLOW does not require any direct sections in front of and behind the meter; however, to reach the optimal installation conditions, we recommend the following: Dimensions Recommendation DN15 to DN80 qp 0.6 to qp 40 Min. 5 x DN in front of the meter DN100 to DN250 qp 60 to qp 1000 Min. 10 x DN in front of the meter Min. 3 x DN in front of the meter CEN CR installation requirements must be followed.

7 To prevent cavitations, the ULTRAFLOW operating pressure must be min. 1.5 bar for qp min. 2.5 bar for qs (4.5 bar for DN80). This requirement is valid for temperatures up to approx. 80 C. ULTRAFLOW must not be exposed to pressures lower than the pressure of surrounding environment (vacuum). 4.1 ULTRAFLOW assembly ULTRAFLOW must be installed in either horizontal or vertical position, or under any angle in between these two positions. ULTRAFLOW can be rotated up to ±45, according to the piping axis. ULTRAFLOW must not be mounted so that the black plastic cover is pointed either up or down.

8 Assembly example: MULTICAL can be mounted in two positions using angle bracket. The angle bracket needs to be ordered separately Dampness and condensation In case ULTRAFLOW is installed in a damp environment, it must be turned in a 45 angle to the piping axis, as you can see below. If condensation is to be expected (e.g. in cooling systems), the ULTRAFLOW, which is protected from condensation must be used. 5. Calculator assembly The MULTICAL 601 calculator can be assembled in three different ways: 5.1 Compact assembly The calculator is mounted straight onto the flow part. If needed, an angle bracket can be used. After the assembly, the calculator must be sealed with a seal and a wire. If the condensation is high (e.g. in cooling systems), we recommend to mount the calculator on a wall. See also paragraph 4.1 ULTRAFLOW assembly.

9 5.2 Separate assembly on the wall The bracket for wall mounting enables you to mount MULTICAL 601 directly onto a straight wall. Use the bracket for marking and drilling two holes, 6 mm in diameter, into the wall. 5.3 Assembly in a panel MULTICAL 601 can be mounted straight into panels, using the panel assembly set Kamstrup, no (192 x 144 mm). 6. Power supply MULTICAL 601 can be powered by a built-in lithium battery; 24 VAC internal supply module; or 230 VAC internal power module. Two conductors from the battery or main voltage module are connected to 60 and 61 calculator clips. When connecting the conductors, polarity must be kept; connect the red conductor into clip no. 60 (+), and black conductor into clip no. 61 (-). 6.1 Battery supply MULTICAL 601 is connected to a lithium battery (cell D). The battery is marked with installation year, e.g. 2007, and production year. Optimum battery life is reached if the battery is not exposed to temperatures above 30 C, e.g. by placing it on a wall. Lithium battery voltage remains constant for most of its life (ca 3.65 V). The remaining battery capacity thus cannot be determined by voltage measuring. The battery cannot be, and is not allowed to be, recharged; it also must not be shortcircuited. Empty batteries must be handed in for required liquidation, e.g. to the Kamstrup Company.

10 6.2 Main voltage modules Modules belong to the safety class ll, and are connected with a double-wire conductor (without grounding) through the calculator cable grommet; the calculator is placed to the right from the connection base. Use a 5 to 10 mm outer diameter connecting cable, and secure proper disassembly and assembly of the voltage cable releaser. Max. fuse allowed: 6 A Assembly regulations must be followed during the assembly. 24 VAC 230 VAC For example, a 230/24 V transformer, This module is used for direct type can be used. connection to the electric network. NOTE! MULTICAL 601 cannot be supplied from a 24 VDC. 7. Function test After completion of the electric meter assembly, check its functionality. Activate water flow through the heating system, by opening heat regulators and taps. Press top MULTICAL 601 button, and verify the temperature and water flow figures on the display.

11 8. Electric connection The polarity of T1, T2 and T3 temperature sensors is not important. When connecting ULTRAFLOW and electronic sensor units, use the colours given for V1 and V2 flow meters. Flow meters with Reed-contact output need to be connected to clips 11-10, or V1 V Blue Red SIG Yellow Clip number Standard heat and cold measurements Heat measurement and leak records T1 5-6 Sensor in supply piping (red) Sensor in supply piping (red) T2 7-8 Sensor in return piping Sensor in return (blue) piping (blue) V Flow meter in supply or Flow meter in supply return piping piping V Flow meter in return piping T Container/heat exchanger temperature Energy measurement in open systems Sensor in supply piping (red) Sensor in return piping (blue) Flow meter in supply piping Flow meter in return piping Reference sensor (grey) 9. Insert modules MULTICAL 601 can be extended with a range of functions, using the insert modules. Individual modules are briefly described below. 9.1 Data/impulse inputs Data outputs are used, for example, for computer connection. The signal is passive and galvanic ally separated using opto-electric coupling elements. Transmission to RS232 level requires a connection of data cable (D-Sub 9F) or (USB), through the following connection: 62 Brown (DAT) 63 White (REQ) 64 Green (GND)

12 NOTE! If data reading is to be compatible with MULTICAL 66-CDE, a top module needs to be used in MULTICAL 601. Impulse inputs can be used for connecting both electric and water meters. Please, bear in mind the maximum impulse frequency and correct impulse codes (l/impulse and Wh/impulse), which are selected in FF and GG configuration Input A Input B 9.2 M-Bus, type /08/20 M-Bus can be connected into a star-shape, ring, or bus line. According to the M-Bus Master supply, and total cabling resistance, up tpo 250 meters can be connected. Cable resistance Cable capacity < 29 Ohm < 180 nf M-Bus network is connected to clips 24 and 25. The polarity is not important. M-Bus is supplied with impulse inputs. of NOTE! /08 requires the installation top module. 9.3 Radio/impulse inputs, type A/0B/25/26 The radio module is used for wireless communication over a licence-free radio frequency; it is available for both interior and exterior antennas. Further information on the radio module are given in Radio technical description ( ). Impulse inputs of this module are identical with the above mentioned modules. NOTE! A/0B requires the installation of top module. Type includes radio and router functions.

13 9.4 Analogue output Type , see Assembly guide (DK-GB-DE). 9.5 Lon Works Type , see Assembly manual (DK) or (GB). 9.6 Top modules Type 67-01: RTC (Real Time Clock) The top module consists of real time clock and backup battery. When the MULTICAL 601 is placed in the supply console, and the voltage is low, current date and time are transferred from the top module into the calculator. Top module is recommended for applications which need to have the correct date/time in permanent memory, as well as time controlled tariffs. The real time clock and backup battery represent standard equipment of all other top modules. This module does not use screws. Type 67-02: RTC + Energy + Hourly data recorder This top module counts the differences between heat energy in both supply and return piping, and hot supply water energy in open systems. This module also consists of an hourly data recorder. This module does not use screws. Type 67-06: RTC + compatibility with 66-C + 2 impulse outputs (CE and CV) Top module secures MULTICAL 601 compatibility with MULTICAL 66-C, which allows using most original basic modules for MULTICAL 66-C in the MULTICAL 601. Moreover, the top module has two independent impulse outputs for energy (CE) and capacity (CV). Impulse resolution reflects display data (defined by CCC-code). E.g.: CCC=119 (qp 1.5): 1 impulse/kwh and 1 impulse/0.01 m3. Impulse outputs are optically isolated, and have 30 VDC and 10 ma.

14 Type 67-07: RTC + M-Bus An M-Bus can be connected into a star, ring, or bus line. According to M-Bus Master supply and cable length/diameter, up to 250 meters with primary addressing can be connected; even more can be connected if secondary addressing is used. Network conductor resistance: < 29 Ohm Network conductor capacity: < 180 nf Polarity of clips 24 and 25 connection is not important. Primary addresses usually consist of the last numbers in a customer number ( ),and can be changed using METERTOOL software. Type 67-08: RTC + hourly data recorder + impulse outputs This top module has two impulse outputs for capacity and energy, which can be freely configured. They are suitable for capacity and energy impulses for heat, cold, or combined meters. Impulse resolution reflects display data (defined by CCC-code). E.g.: CCC=119 (qp 1.5): 1 impulse/kwh and 1 impulse/0.01 m 3. Impulse outputs are optically isolated, and have 30 VDC and 10 ma. Energy (CE) is usually connected to clip 16-17; capacity (CV) is then connected to clip However, other combinations can be selected using METERTOOL software, which is also used to select the impulse duration 32 or 100 ms. Moreover, this module also includes an hourly data recorder. Type 67-09: RTC + capacity + hourly data recorder This top module counts the difference between heat energy in supply and return piping, and hot supply water energy in open systems. Figure difference dv=v1-v2. This module also includes an hourly data recorder. This module does not use screws.

15

16

How To Use A Multi-Line Calculator With A Power Supply And Power Supply (Kamstrup)

How To Use A Multi-Line Calculator With A Power Supply And Power Supply (Kamstrup) Installation and User s Guide MULTICAL 601 & ULTRAFLOW 14 Cooling meter www.kamstrup.com Operation conditions Operation conditions/measuring ranges: Calculator θ: 2 C 180 C Θ: 3K 170K Temperature sensor

More information

MULTICAL 602 & ULTRAFLOW 14

MULTICAL 602 & ULTRAFLOW 14 Installation and User Guide MULTICAL 602 & ULTRAFLOW 14 Cooling meter www.kamstrup.com 1 Operation conditions Operation conditions/measuring ranges: Calculator q: 2 C 180 C DΘ: 3K 170K Temperature sensor

More information

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

SHARKY 775 COMPACT ENERGY METER ULTRASONIC APPLICATION The ultrasonic compact energy meter can be used for measuring the energy consumption in heating / cooling application for billing purposes. FEATURES 4 Approval for ultrasonic meter with dynamic

More information

CORONA E / FLYPPER ELECTRONIC METER MULTI-JET

CORONA E / FLYPPER ELECTRONIC METER MULTI-JET APPLICATION Fully electronic compact water meter with impeller scanning for recording volume. Highly accurate recording of all billing data at medium temperatures up to 90 C. FEATURES 4 Electronic sensor

More information

Installation and User Guide for MULTICAL 62. Water meter. www.kamstrup.com

Installation and User Guide for MULTICAL 62. Water meter. www.kamstrup.com Installation and User Guide for MULTICAL 62 Water meter www.kamstrup.com 123456 MULTICAL 62 Water meter English installation Kamstrup A/S Industrivej 28, Stilling, DK-8660 Skanderborg Tel: +45 89 93 10

More information

MOUNTING AND OPERATING INSTRUCTIONS

MOUNTING AND OPERATING INSTRUCTIONS MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall

More information

HYDRUS ULTRASONIC METER

HYDRUS ULTRASONIC METER HYDRUS APPLICATION HYDRUS is a static water meter based on the ultrasonic technology. This technology enables accurate calculation of water consumption and eliminates measuring deviations caused by sand,

More information

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

SHARKY 775 COMPACT ENERGY METER ULTRASONIC APPLICATION The ultrasonic compact energy meter can be used for measuring the energy consumption in heating / cooling application for billing purposes. FEATURES 4 Approval for ultrasonic meter with dynamic

More information

MULTICAL 602 DATA SHEET

MULTICAL 602 DATA SHEET Complete range of communication modules High Power RadioRouter module Data loggers Info loggers Data backup in case of power failure EN 1434 MID-2004/22/EC M12 0200 Heat and cooling meters with unlimited

More information

T0118 T2118 T3118. Instruction Manual

T0118 T2118 T3118. Instruction Manual Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity

More information

Toroidal Conductivity Sensor

Toroidal Conductivity Sensor Instruction Sheet PN 51A-/rev.C June 2012 Toroidal Conductivity Sensor For additional information, please visit our website at www.emersonprocess.com/rosemountanalytical.com SPECIFICATIONS Wetted Materials:

More information

MULTICAL 21 DATA SHEET. Electronic ultrasonic cold and hot water meter

MULTICAL 21 DATA SHEET. Electronic ultrasonic cold and hot water meter Ultrasonic measurement Pinpoint accuracy Longevity Vacuum sealed construction Environment-friendly meter MID-2004/22/EC M12 0200 Electronic ultrasonic cold and hot water meter MULTICAL 21 is used for measurement

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description Photoelectrics, Background Suppression reflective with IR light Main features Description The PD30ET... stainless steel sensors are built with high-quality materials and designed for harsh environments.

More information

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001 Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

How To Use A Flowmeter

How To Use A Flowmeter INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection

More information

Laserlyte-Flex Alignment System

Laserlyte-Flex Alignment System Laserlyte-Flex Alignment System LaserLyte-Flex The LaserLyte-Flex Alignment System is a unique, interchangeable, low cost plug and play laser system. Designed specifically for aligning and positioning

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output

More information

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions

More information

Givare NC-SRS 280 och 880

Givare NC-SRS 280 och 880 Givare NC-SRS 280 och 880 Aratron AB/Nordic Control, 02 03 SRS280SEALED ROTARY SENSOR PERFORMANCE ±2 Resistance ±20% Hysteresis (repeatability) Accuracy Applied voltage maximum Resolution Output smoothness

More information

A99B Series Temperature Sensors

A99B Series Temperature Sensors FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors

More information

BM SERIES WAVE COMPACT 6.3 GHZ CW SERIES PULSE RADAR LEVEL INSTRUMENTS (6.3 GHz)

BM SERIES WAVE COMPACT 6.3 GHZ CW SERIES PULSE RADAR LEVEL INSTRUMENTS (6.3 GHz) CW SERIES PULSE RADAR LEVEL INSTRUMENTS (6.3 GHz) DESCRIPTION The Radar Level Meters of BM COMPACT WAVE 6.3 GHz series are excellent devices for no contact level measurement. The microwave impulses, emitted

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

Instructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version

Instructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version instrumentation for fluids Electromagnetic sensor Series FLOMID FX Instructions Manual! Conforms with the Pressure Equipment Directive 97/23/EC. 0830 This equipment is considered as being a pressure accessory

More information

Rotary actuators Rotary wing drives Series RAK. Brochure

Rotary actuators Rotary wing drives Series RAK. Brochure Brochure 2 Rotary wing drives, angle of rotation: 30-270 Rotary wing drive, double-acting axis geometry: single 4 Rotary wing drives, angle of rotation: 90-270 Rotary wing drive, double-acting axis geometry:

More information

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in 891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

QR12 (1.22 ) Diameter Optical Encoder

QR12 (1.22 ) Diameter Optical Encoder Improving the Quality of Life through the Power in Light QPhase QR12 (1.22 ) Diameter Optical Encoder Design Features: Low profile assembled height of Bearing design simplifies encoder attachment Resolutions

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Cable Plug acc. to DIN EN 175301-803, Form A

Cable Plug acc. to DIN EN 175301-803, Form A Cable Plug acc. to DIN EN 175301-803, Form A Complete program Contact form 18 mm Also available with LED indicator Optional 4-pin version for pressure switch or impulse valves respectively Versions with

More information

SONOMETER TM 1000 Ultrasonic compact heat meter

SONOMETER TM 1000 Ultrasonic compact heat meter Data sheet SONOMETER TM 000 Ultrasonic compact heat meter Description/Application MID examination certificate no. : DE-07-MI004-PTB02 The SONOMETER 000 is an ultrasonic static compact heat meter especially

More information

Instruction Manual. T3111 T3111L T3111P T3111Ex

Instruction Manual. T3111 T3111L T3111P T3111Ex www.cometsystem.cz Instruction Manual T3111 T3111L T3111P T3111Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with external probe and 4-20 ma outputs

More information

LED...A70..4-..Q Series Sealed High-Intensity

LED...A70..4-..Q Series Sealed High-Intensity LED...A70..4-..Q Series Sealed High-Intensity Area Lights High-Power Lighting for use with PresencePLUS and Other Vision Systems Features Rugged, waterproof housing, rated IEC IP68 Compact area light for

More information

Turbine Flow Sensor Series VTR

Turbine Flow Sensor Series VTR Turbine Flow Sensor Series VTR SIKA Turbine Flow Sensor Series VTR Extra robust, impressively precise SIKA s VTR turbine flow sensor allows you to determine precisely, dependably and easily the flow rates

More information

Material: Weight: Bearing Life: Shaft Speed: Starting Torque: Mass Moment of Inertia: Shaft Loads:

Material: Weight: Bearing Life: Shaft Speed: Starting Torque: Mass Moment of Inertia: Shaft Loads: Automation / Mini Type SCH32F Hollow Shaft Encoder - Ø 32 mm Hollow Bore: Ø 6 mm to Ø 3/8 inch Resolution up to 5000 ppr IP 65 (IP 50 for IDC connector option) Electrical Specifications Code: Resolution:

More information

HG600/HG800. Hydro-Power Unit. Installation and Operation Guide

HG600/HG800. Hydro-Power Unit. Installation and Operation Guide HG600/HG800 Hydro-Power Unit Installation and Operation Guide Copyright 04 HydroSpin, All rights reserved. The data contained in this document is proprietary to HydroSpin. It is disclosed to the receiving

More information

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

The multi-functional integrator Supercal 531

The multi-functional integrator Supercal 531 The multi-functional integrator Supercal 531 Design The Supercal 531 integrator is suitable for connecting Pt 500 or Pt 100 temperature sensor pairs with 2 or 4-conducting wire techniques. Volume inputs

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered Electrical Temperature Measurement DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered WIKA Data Sheet TE 60.75 Applications Machinery, plant and tank construction

More information

Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual

Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual 0 P a g e H.264 Color or Day/Night SurroundVideo Installation Manual Inside the box: A. Arecont Vision SurroundVideo camera B. Mounting template C. RJ45 female to female coupler D. Hex key E. Security

More information

LMU-5000. Hardware and Installation Guide

LMU-5000. Hardware and Installation Guide LMU-5000 Hardware and Installation Guide Plan The Installation Verify Power, Ground and Ignition. Be sure to check each source (power, ground and ignition) to ensure that the proper signaling exists. This

More information

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description

More information

ATL Fuel Level Sender Probes

ATL Fuel Level Sender Probes T E C H N I C A L S P E C I F I C A T I O N The ATL EL-AD-151 (Resistance Output) and EL-AD-152 (Voltage Output) Fuel Level Senders are highly advanced sensors for continuously measuring the contents of

More information

USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1.

USER GUIDE. Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator. DM Engineering. Version 1. USER GUIDE Studio Hotline Multi-line System Phone Flasher and Door/Alert Indicator Input Module and Indicator Version 1.3 DM Engineering 2174 Chandler St. Camarillo, CA 91345-4611 805-987-7881 800-249-0487

More information

IFC 070 Technical Datasheet

IFC 070 Technical Datasheet IFC 070 Technical Datasheet Electromagnetic signal converter Battery driven with low energy consumption Quick and easy to install and operate External data logger and GSM module for remote data transfer

More information

SENSORS. Miniature Sensors - S3Z. Advanced line of miniature Asian style of photoelectric sensors. 40-300 mm background suppression

SENSORS. Miniature Sensors - S3Z. Advanced line of miniature Asian style of photoelectric sensors. 40-300 mm background suppression Advanced line of miniature Asian style of photoelectric sensors 4-3 background suppression.7 m proximity, 15 with narrow beam 4 m polarized retroreflective 3 m LASER through beam Standard 3-wire output

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

How To Power A Schen

How To Power A Schen Automation / Mini Type SCH32F Hollow Shaft Encoder - Ø 32 mm Hollow Bore: Ø 6 mm to Ø 3/8 inch Resolution up to 5000 ppr IP 65 (IP 50 for IDC connector option) Electrical Specifications Code: Resolution:

More information

Model 201 Wiegand Touchpad Reader Installation Guide

Model 201 Wiegand Touchpad Reader Installation Guide Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without

More information

USB-ISS-UV/VIS Integrated Sampling System Installation and Operation Instructions

USB-ISS-UV/VIS Integrated Sampling System Installation and Operation Instructions USB-ISS-UV/VIS Integrated Sampling System Installation and Operation Instructions Description The USB-ISS-UV/VIS Integrated Sampling System is a snap-on, direct-attach 1 cm cuvette holder and UV/VIS/NIR

More information

FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES

FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES 01D351-GB FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES DOLOMIT FLOAT SWITCHES The DOLOMIT float switches find application in liquid level control in tanks and wells; they require connection

More information

Instruction book IQAN-MDM. Publ. no. HY17-8328/UK Edition June, 2007

Instruction book IQAN-MDM. Publ. no. HY17-8328/UK Edition June, 2007 Instruction book IQAN-MDM Publ. no. HY17-8328/UK Edition June, 2007 Contents 1 Introduction...............................................................3 Safety symbols................................................................

More information

Typical Aluminum GFM Mass Flow Meter

Typical Aluminum GFM Mass Flow Meter MASS FLOW METERS Design Features n Rigid metallic construction. n Maximum pressure of 1000 psig (70 bars). n Leak integrity 1 x 10-9 of helium. n NIST traceable certification. n Built-in tiltable LCD readout.

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

photoelectric highlights www.automation.datalogic.com

photoelectric highlights www.automation.datalogic.com photoelectric miniature sensors S8 series The new S8 series of compact sensors offers excellent detection performances, usually associated with sensors that have larger dimensions and a higher price. The

More information

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE 4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation

More information

SHARKY 775 Ultrasonic Compact Energy Meter. Installation and User Guide

SHARKY 775 Ultrasonic Compact Energy Meter. Installation and User Guide SHARKY 775 Ultrasonic Compact Energy Meter Installation and User Guide for software version F01-001 1 Contents 1 General... 4 1.1 About this Installation and User Guide... 4 1.1.1 Target groups...4 1.1.2

More information

Directory chapter 04

Directory chapter 04 M Directory chapter 04 D-Sub Mixed subminiature D connectors New Page D-Sub mixed connector system general information................... 04.02 Contact arrangements............................................

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles Clear Glass Sensor Optimum Sensor for Detecting Transparent Glass and Plastic Bottles E3S-CR67/62 Retroreflective Sensor smoothly detects 5-mm gaps. Detects transparent bottles that have a lens effect.

More information

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp. EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium

More information

VOYAGER 570G. 744A Sprayer Control

VOYAGER 570G. 744A Sprayer Control VOYAGER 570G 744A Sprayer Control U S E R M A N U A L U S E R M A N U A L Table of Contents CHAPTER 1 - INTRODUCTION...1 SYSTEM CONFIGURATIONS...1 KIT CONTENTS...3 CONTROL HOUSING ASSEMBLY...5 CHAPTER

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Electronic Pressure Switch EDS 300

Electronic Pressure Switch EDS 300 Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5

More information

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17) 17 Engine-Lubrication (Page GR-17) Lubrication system components, removing and installing Oil filter housing, disassembling and assembling Oil pan, removing and installing Oil pressure and oil pressure

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living 2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

Submersion/Insertion Toroidal Sensor

Submersion/Insertion Toroidal Sensor Instruction Sheet PN 51A-228/rev.P December 2010 Model 228 Submersion/Insertion Toroidal Sensor For additional information, please visit our website at www.emersonprocess.com/raihome/liquid/. CAUTION SENSOR/PROCESS

More information

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

PSACH 01246 v.1.0 PSACH 24VAC/6A/1x6A HERMETIC AC power supply for CCTV

PSACH 01246 v.1.0 PSACH 24VAC/6A/1x6A HERMETIC AC power supply for CCTV PSACH 01246 v.1.0 PSACH 24VAC/6A/1x6A HERMETIC AC power supply for CCTV EN Edition: 2 from 12.12.2013 Supersedes the edition: 1 from 18.06.2013 Features: power output 24V AC/6A or 27V AC/ 5,5A power voltage

More information

Automotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim

Automotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim Automotive sensor simulator Operating manual AutoSim Contents Introduction.. page 3 Technical specifications.... page 4 Typical application of AutoSim simulator..... page 4 Device appearance... page 5

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm Electronic pressure measurement Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm WIKA data sheet PE 81.67 Applications Machine tools Hydraulics

More information

Before installation it is important to know what parts you have and what the capabilities of these parts are.

Before installation it is important to know what parts you have and what the capabilities of these parts are. INSTALLATION GUIDE Before installation it is important to know what parts you have and what the capabilities of these parts are. The Recon XZT is the smallest and most powerful gauge of its kind. With

More information

12 Volt 30 Amp Digital Solar Charge Controller

12 Volt 30 Amp Digital Solar Charge Controller 12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS

INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS VMC A4 INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS PRODUCT DATA SHEET FEATURES RF to 0-10 VDC out, analogue or PWM Maximal 3 digital inputs to RF RF communication with other equipment Wireless

More information

M-Bus. Technical Description

M-Bus. Technical Description M-Bus Technical Description Kamstrup A/S Industrivej 28, Stilling DK-8660 Skanderborg TEL: +45 89 93 10 00 FAX: +45 89 93 10 01 E-MAIL: energi@kamstrup.dk WEB: www.kamstrup.com 2 Contents 1. Technical

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

Installation Guide. WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers. February, 2011

Installation Guide. WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers. February, 2011 WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers Installation Guide February, 2011 Pace Scientific Inc www.pace-sci.com Tel: 704-799-0688 sales@pace-sci.com 1 Disclaimer The following warranty

More information

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR Installation and Operation Manual 1 ENGLISH Safety Instructions 2 Features 2-3 Specifications 3 Installation 4-5 Wiring Diagrams 6-7 Warranty 8

More information

Threaded Resistance Thermometers Model TR10-D, Miniature Design

Threaded Resistance Thermometers Model TR10-D, Miniature Design Electrical Temperature Measurement Threaded Resistance Thermometers Model TR10-D, Miniature Design WIKA Data Sheet TE 60.04 Applications Machine building, plant and tank construction Power transmission

More information

Instruction Sheet ACS-101. General Description. Specifications. Amplified Broadband UHF Combiner-Splitter. Overall. Antenna Splitter.

Instruction Sheet ACS-101. General Description. Specifications. Amplified Broadband UHF Combiner-Splitter. Overall. Antenna Splitter. ACS-101 Amplified Broadband UHF Combiner-Splitter General Description The ACS-101 (Antenna Combiner Splitter 10 to 1) is an amplified and filtered broadband splitter-combiner. It allows up to 10 base stations

More information

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2 Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male

More information

Wireless Indoor/ Outdoor Thermometer

Wireless Indoor/ Outdoor Thermometer Wireless Indoor/ Outdoor Thermometer Owner s Manual Please read before using this equipment. ˆ Contents FCC Information... 3 FCC Declaration of Conformity... 5 Preparation... 5 Installing Batteries...

More information

Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1

Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1 REMOTE METER TM Installation and Operation Manual. Digital Remote Meter for Monitoring System Performance. Version: RM-1 1098 Washington Crossing Road Washington Crossing, PA 18977 USA www.morningstarcorp.com

More information

USER MANUAL V5.0 ST100

USER MANUAL V5.0 ST100 GPS Vehicle Tracker USER MANUAL V5.0 ST100 Updated on 15 September 2009-1 - Contents 1 Product Overview 3 2 For Your Safety 3 3 ST100 Parameters 3 4 Getting Started 4 4.1 Hardware and Accessories 4 4.2

More information

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH

More information

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The

More information

PK-01. Standalone door control module. SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00

PK-01. Standalone door control module. SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00 Standalone door control module PK-01 Firmware version 1.00 pk-01_en 06/12 SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00 info@satel.pl www.satel.eu WARNINGS Read carefully

More information