9Section. contents. TE Controls. Safety Relays 9.2. Signal Towers 9.5. Hazardous Area Equipment 9.6 Safety Products. Pilz Omron...9.
|
|
- Cuthbert Harrell
- 7 years ago
- Views:
Transcription
1 contents Safety Relays 9.2 Pilz Omron Section Signal Towers 9.5 Hazardous Area Equipment 9.6 Safety Products
2 Safety Relays Safety Products Safety Relays Emergency Stop Relays, Safety Gate Monitors PNOZ 1 Emergency stop relay and safety gate monitor in accordance with VDE 0113, EN and IEC Features: Single-channel or dual-channel without detection of shorts. Not designed for operation via semiconductor outputs. 90mm, P-75-housing, DIN rail mounting Positive-guided relay outputs: 3 safety contacts (N/O) 1 auxiliary contact (N/C) Connections for E STOP button Safety gate limit switch reset button LED s for channel 1 and channel 2 Increase in the number of safety contacts available by connecting expanding modules Operating Modes Single-channel operation Dual-channel operation Automatic reset Manual reset PNOZ 1 Voltage Order No. Part No. Each 24VDC PNOZ 1 24VDC VAC PNOZ 1 24VAC VAC PNOZ 1 110VDC VAC PNOZ 1 230VAC PNOZ X3 Emergency stop relay and safety gate monitor in accordance with VDE 0113, EN and IEC Features: Monitored manual or automatic reset can be selected 1 semiconductor output (K1/K2) Each AC unit can be operated with 24VDC Safety gate function with N/C-N/O combination Only dual-channel operation will detect shorts across the input contacts 45mm, P-93-housing, DIN rail mounting Positive-guided relay outputs: 3 safety contacts (N/O) 1 auxiliary contact (N/C) Connections for E STOP button Safety gate limit switch reset button Semiconductor output signals ready for operation LED s for channel 1 channel 2 and power Increase in the number of safety contacts available by connecting expanding modules Operating Modes Single-channel operation Dual-channel operation Automatic reset Monitored manual reset PNOZ X3 Voltage Order No. Part No. Each 24VAC/24VDC PNOZ X3 24VAC24VDC VAC/24VDC PNOZ X3 110VAC24VDC Contact your local sales office for other products in this range and for confirmation of price. s correct at time of printing but may vary subject to changes in manufacturers list prices. E. & O. E. All prices are exclusive of V.A.T.
3 Safety Relays Emergency Stop Relays, Safety Gate Monitors PNOZ XV2 Emergency stop relay and safety gate monitor in accordance with VDE 0113, EN and IEC Features: Input wiring compatible with the PNOZ X3 Dual-channel wiring with detection of shorts across the input contacts Monitored manual or automatic reset can be selected 2 Delay-off safety contacts Supply Voltage: 24VDC Time Reset 45mm, P-93 housing, DIN rail mounting Positive-guided relay outputs: 2 instantaneous safety contacts (N/O) 2 delayed safety contact (N/C) Connections for E STOP button Safety gate limit switch reset button LED s for power, channel 1 and channel 2, CH.1 IN and CH.2 Increase in the number of safety contacts available by connecting expanding modules Safety Products Operating Modes Single-channel operation Dual-channel operation Automatic reset Monitored manual reset PNOZ XV2 Voltage Order No. Part No. Each 24VDC PNOZ XV2 24VDC PZE 9 Expanding module in accordance with VDE 0113, EN and IEC and IEC to increase the number of safety contacts available Features: Diverse Dual-channel operation with short circuit detection possible 90mm, P-93 housing, DIN rail mounting Relay outputs, positive-guided: 8 safety contacts (N/O) 1 auxiliary contact (N/C) LED s for power, channel 1 and channel 2 Connection for feedback control loop Operating Modes E STOP button Safety gate limit switch Two-hand relays All base units must have a feedback control loop PZE 9 Voltage Order No. Part No. Each 24VDC PZE 9 24VDC VAC PZE 9 24VAC VAC PZE 9 110VAC Safety Relays Contact your local sales office for other products in this range and for confirmation of price. s correct at time of printing but may vary subject to changes in manufacturers list prices. E. & O. E. All prices are exclusive of V.A.T. 9.3
4 Safety Relays Safety Products G7S Safety relay with forcibly guided contacts Contact rating 3A (240 V resistive) Forcibly guided mechanism which ensures a minimum of 0.5 mm between contacts even when one is welded Conforms to safety circuit described in EN For use in press machines, machine tools, lift controls and other production machinery G7S Contact configuration Control Voltage Part No. Each 4NO+ 2NC 24VDC G7S4A2B NO+ 3NC 24VDC G7S3A3B Accessories/Bases Description Part No. Each DIN Rail/surface mounting P7S14F Solder Mounting P7S14A 4.51 PCB P7S14P 3.66 G9S Safety Relay Unit Contact rating 3A (240 V resistive) Ideal for safety circuits for doors and emergency stop controls Slim design DIN Rail mounted Enclosed to IP40 Conforms to safety circuit described in EN 945-1, EN & EN G9S Contact Time Type Configuration Delay Voltage Part No. Each Single channel input DPST-NO 24VDC G9S VDC Two channel input DPST-NO 24VDC G9S VDC PST-NO 24VDC G9S VDC VAC G9S VAC PST-NO 24VDC G9S VDC VAC G9S VAC sec 24VDC G9S 321 T01 24VDC VAC G9S 321 T01 240VAC OFF delay 3 NO inst. + 2 NO timed 10sec 24VDC G9S 321 T10 24VDC VAC G9S 321 T10 240VAC sec 24VDC G9S 321 T30 24VDC VAC G9S 321 T30 240VAC D4DS Safety Door limit switch Uses special operation key to positively separate contacts. Low cost switch meets many European safety directives. D4DS Series Type Description Part No. Each Safety Relays Safety Switch Interlock Slide Operation Key Hinge Operation Key DPDB NO/NC, 10A D4DS 15FS DPDB 2-NC, 10A D4DS 1AFS DPDB NO/NC, 10A, 2 Conduit entry D4DS 55FS DPDB 2-NC, 10A, 2 Conduit entry D4DS 5AFS For D4DL/S Switch Horizontal Mounting D4DS K For D4DL/S Switch Vertical Mounting D4DS K For D4DL/S Switch Vertical Mounting (Horizontal Adjustment) D4DS K For D4DL/S Switch Vertical Mounting (Horizontal & Vertical Adjustment) D4DS K Contact your local sales office for other products in this range and for confirmation of price. s correct at time of printing but may vary subject to changes in manufacturers list prices. E. & O. E. All prices are exclusive of V.A.T.
5 Signal Towers Signal Towers Plug together light/audible signal towers. Easily user configured using selectable links in each module to provide up to 5 independently switched sections in each tower. Quick and easy to assemble. IP54 as standard - IP65 with optional sealing gaskets. Insert Colour Type Voltage Part No. Each Continuous Light module (without Bulb) All SL L V AC SL BL Flashing Light Module (bulb inc.) V AC SL BL V AC SL BL V DC SL FL Strobe Light Module (Flash Tube inc.) V AC SL FL V AC SL FL Acoustic Indicator Continuous Tone Pulsed Tone 12-36V AC/DC SL A V AC/DC SL A V AC/DC SL AP V AC/DC SL AP V DC SL L Filament Bulb V AC/DC SL V AC SL L Multi LED 18-30V AC/DC SL LED Basic Module All SL B Safety Products Accessories Description Part No. Each 100mm Tube SL F Stand 250mm Tube SL F mm Tube SL F mm Tube SL F Wall Fixing Bracket SL FW Sealing gasket (increases to IP65) SL IP Each signal tower consists of a basic module (SL-B) = (SL-F...) = 1-5 modules. Signal Towers Part No. Completion When ordering complete the Part No. by adding the following:- Colour Red Green Yellow Blue White Code R G Y B W Signal Towers Contact your local sales office for other products in this range and for confirmation of price. s correct at time of printing but may vary subject to changes in manufacturers list prices. E. & O. E. All prices are exclusive of V.A.T. 9.5
6 Hazardous Area Equipment Safety Products Hazardous Area Equipment Control Stations Type of Protection EExde IICT6 Certificate of Conformity PTB No. Ex-87.B.1009 Degree of Protection IP66 (IP65 with double pushbutton) Rated Voltage 690VAC Rated Current 16A Terminals -Connection 2 x 2.5mm 2 -PE 4 x 4mm 2 1 Gang Contacts Description NO NC Cable Entry Part No. Each Red Mushroom Head Pushbutton (Stayput Stop) x M20 GHG R labelled EMERGENCY STOP Red Mushroom Head Pushbutton (Key Release) x M20 GHG R labelled EMERGENCY STOP Double Pushbutton Unit labelled 0,I,START,STOP x M20 GHG R Gang Contacts Description NO NC Cable Entry Part No. Each Standard Pushbuttons labelled 0,I,START,STOP Start + Red Mushroom Head Pushbutton (Stayput Stop) x M20 GHG R x M20 GHG R Single, Double and Triple gang units can be assembled to suit your individual requirements from the following range of Components:- Pushbuttons Mushroom Head Pushbuttons - either pull release or key release Double Pushbuttons Selector Switches - either 2 or 3 position Signal Lamps - Available in all colours and voltages Measuring Instruments Installation Switches Type of Protection EExde IICT6 Certificate of Conformity PTB No. Ex-91.C.1017 Degree of Protection IP66 Rated Voltage 250VAC Rated Current 16A Terminals -Connection 2 x 2.5mm 2 -PE 4 x 2.5mm 2 Installation Switches Contact Description Arrangement Cable Entry Part No Each On - Off 2 Pole Switch 2 NO 2 x M20 GHG R Change-over Switch 1CO 2 x M20 GHG R Safety Switches Type of Protection EExde IICT6 Certificate of Conformity 10A PTB No. Ex-88.B A and 40A PTB No. Ex-96.D A PTB No. Ex-85.B A and 180A PTB No. Ex-86.B.1071 Degree of Protection IP66 Rated Voltage 690V Safety Switches Auxiliary Current Rating Main Poles Cable 230V 400V` 500V 690V Poles NO NC Entry Part No Each x M20 GHG R x M20 GHG R x M25 GHG R x M25 GHG R x M25 GHG R x M32 GHG R x M50 +1 x M25 GHG R x M40 GHG R x M x M25 GHG R0001 1, Contact your local sales office for other products in this range and for confirmation of price. s correct at time of printing but may vary subject to changes in manufacturers list prices. E. & O. E. All prices are exclusive of V.A.T.
7 Hazardous Area Equipment Junction Boxes Type of Protection Certificate of Conformity Degree of Protection Rated Voltage eazk 96 Series EExe II T6 / EEXe(ia) IIC T6 / EExia IIC T6 PTB No. Ex-96.D.3120 IP66 690V Type Cable Entry Part No Each 4 x (4 x 4mm 2 ) + 1 PE (4 x 4 mm 2 ) 2 x M25 GHG R x (4 x 4mm 2 ) + 1 PE (4 x 4 mm 2 ) 4 x M x Blanking plugs GHG R x (4 x 4mm 2 ) + 2 PE (4 x 4 mm 2 ) 6 x M x Blanking plugs and internal earth plate for metal glands GHG R Safety Products Terminal Boxes can be assembled to suit your exact requirements. Please consult your local branch for further details. Mounting Plates Equipment for Size 1 1 Gang pushbutton Stations: GHG Installation Switches: GHG273 Safety Switch: 10A Junction Boxes: GHG Equipment for Size 2 2 Gang pushbutton station: GHG Safety Switch: 20A 4Pole Junction Boxes: GHG Equipment for Size 3 Safety Switch: 20A 6Pole, 40A & 80A Mounting Plates Size Mounting Part No Each Wall GHG R Channel GHG R Pipe GHG R Wall GHG R Channel GHG R Pipe GHG R Wall GHG R Channel GHG R Pipe GHG R Label Holder with blank Designation label (Pk of 50) GHG R Plugs and Sockets Type of Protection EExde IICT6 Certificate of Conformity 16A 110 & 240V PTB No.Ex-87.B A 415V PTB No.Ex-85.B A PTB No.Ex-85.B A PTB No.Ex-86.B.1021 Degree of Protection IP66 (63A-IP65) Plugs and Sockets Current Rating Voltage Poles Description Part No Each Wall Socket GHG V P+N+PE Coupler GHG V Plug GHG V Wall Socket GHG V P+N+PE Coupler GHG V Plug GHG V Wall Socket GHG V P+PE Coupler GHG V Plug GHG V Wall Socket GHG V P+PE Coupler GHG V Plug GHG V Wall Socket GHG V P+N+PE Coupler GHG V Plug GHG V P+PE Wall Socket GHG V Plug GHG V P+N+PE Wall Socket GHG V Plug GHG V Hazardous Area Equipment Contact your local sales office for other products in this range and for confirmation of price. s correct at time of printing but may vary subject to changes in manufacturers list prices. E. & O. E. All prices are exclusive of V.A.T. 9.7
8 Hazardous Area Equipment Safety Products Hazardous Area Equipment For batteries see page 6.15 Lighting-ELLK 92 Series Type of Protection Ex eds IIC T4 Certificate of Conformity PTB 96 ATEX 2144 Degree of Protection IP66 Rated Voltage VAC VAC (2 x 58W) Non-emergency - Bi-pin Lamps Wiring Type Part No Each 2 x 18W Loop in - Loop out ELLK 92018/18 L Through wire ELLK 92018/18 T x 36W Loop in - Loop out ELLK 92036/36 L Through wire ELLK 92036/36 T x 58W Through wire ELLK T x 58W Through wire ELLK 92058/58 T Type of Protection Ex edms ib IIC T4 Certificate of Conformity PTB 96 ATEX 2144 Degree of Protection IP66 Rated Voltage VAC Intelligent Emergency - Bi-pin Lamps Wiring Type Part No Each 2 x 18W Through wire ELLK 92018/18 NIT Loop in - Loop out ELLK 92036/36 NIL x 36W Through wire ELLK 92036/36 NIT Portable Lamps Type Battery Explosion Category Part No Each Stabex mini 2 x AA sized Dry cells EEx ia e IIC T5 (zone 1 & 2) Stabex HF 2 x D sized Dry cells EEx ia e IIC T4 (zone 1 & 2) Stabex M0 2 x D sized Dry cells EEx ib ed IIC T6 (zone 0, 1 & 2) HE 8 EURO PLUS 3.6V/5Ah Rechargeable EEx e ib IIC T4 (zone 1 & 2) V Plug-in Charger HE 8 N EN 3.6V/4Ah Rechargeable NiCd EEx e ib IIC T4 (zone 1 & 2) Plug-in Charger SEB 8 L 4.8V/7Ah Rechargeable NiCd EEx e ib IIC T4 (zone 1 & 2) v Plug-in Charger Contact your local sales office for other products in this range and for confirmation of price. s correct at time of printing but may vary subject to changes in manufacturers list prices. E. & O. E. All prices are exclusive of V.A.T.
9 contents IP Rating Chart 10.2 Utilisation Categories 10.3 Section 10 Motor Rating Chart 10.4 Fuse Rating Chart 10.5 Motor Rating Chart 9.4 Technical Data
10 Ingress Protection Technical Data Ingress Protection Ingress Protection Digit Degrees of protection against solid foreign objects (1st characteristic numeral) No Protection Protected against foreign objects of 50mm Ø and greater. Protected against access to hazardous parts with the back of a hand. Protected against solid foreign objects of 12.5mm Ø and greater. Protected against access to hazardous parts with a finger. Protected against solid foreign objects of 2.5mm Ø and greater. Protected against access to hazardous parts with a tool. Protected against solid foreign objects of 1mm Ø and greater. Protected against access to hazardous parts with a wire. Dust-protected. Ingress of dust is not totally prevented, but dust shall not penetrate in a quality to interfere with satisfactory operation of the apparatus or to impair safety. Dust-tight. No ingress of dust. Digit Degrees of protection against ingress of water (2nd characteristic numeral) No Protection Protected against vertically falling water drops. Vertically falling drops shall have no harmful effects. Protected against vertically falling water drops when enclosure tilted up to 15. Vertically falling drops shall have no harmful effects when the enclosure is tilted at an angle up to 15 on either side of the vertical. Protected against spraying water. Water sprayed at an angle up to 60 on either side of the vertical shall have no harmful effects. Protected against splashing water. Water projected in splashes against the enclosure from any direction shall have no harmful effects. Protected against water jets. Water projected in jets against the enclosure from any direction shall have no harmful effects. Protected against powerful water jets. Water projected in powerful jets against the enclosure from any direction shall have no harmful effects. Protected against the effects of temporary immersion in water. Ingress of water in quantities causing harmful effects shall not be possible when the enclosure is temporarily immersed in water under standardised conditions of pressure and time. Protected against the effects of continuous immersion in water. Ingress of water in quantities causing harmful effects shall not be possible when the enclosure is continuously immersed in water under conditions which shall be agreed between manufacturer and user but which are more severe than for numeral
11 Utilisation Chart Utilisation categories: A contactor duty is characterised by the utilisation category. Utilisation categories for contactor relays according to IEC : Alternating current : AC 11 Making and breaking for normal and occasional utilisation conditions Direct current : DC 11 Making and breaking for normal and occasional utilisation conditions Technical Data Utilisation categories for contactor relays according to IEC : Alternating current : AC-12 AC-13 AC-14 AC-15 Control of resistive loads and solid state loads with isolation by opto couplers. Control of solid state loads with transformer isolation. Control of small electromagnetic loads (< 72VA) Control of small electromagnetic loads (> 72VA) Direct current : DC-12 Control of resistive loads and solid state loads with isolation by opto couplers. DC-13 Control of electromagnets. DC-14 Control of electromagnetic loads having economy resistors in circuit. Utilisation categories for contactors according to IEC : Alternating current : AC 1 AC 3 AC 3 AC 4 Non-inductive or slightly inductive loads, resistance furnaces. Slip-ring motors: starting, plugging. Squirrel-cage motors: starting, switching-off motors during running. Squirrel-cage motors: starting, plugging, inching. Direct current : DC 1 Non-inductive or slightly inductive loads, resistance furnaces. DC 2 Shunt motors: starting, switching-off motors during running. DC 3 Shunt motors: starting, plugging, inching. DC 4 Series motors: starting, switching-off motors during running. DC 5 Series motors: starting, plugging, inching. Utilisation categories for contactors according to IEC : Alternating current : AC 1 AC 3 AC 3 AC 4 AC 5a AC 5b AC 6a AC 6b AC 8a AC 8b Non-inductive or slightly inductive loads, resistance furnaces. Slip-ring motors: starting, switching off Squirrel-cage motors: starting, switching-off motors during running. Squirrel-cage motors: starting, plugging, inching. Switching of discharge lamp controls. Switching of incandescent lamps. Switching of transformers. Switching of capacitor banks. Hermetic refrigerant compressor motor control with manual resetting of overload releases Hermetic refrigerant compressor motor control with automatic resetting of overload releases Direct current : DC 1 Non-inductive or slightly inductive loads, resistance furnaces. DC 3 Shunt motors : starting, plugging, inching. Dynamic breaking of d.c. motors DC 5 Series motors : starting, plugging, inching. Dynamic breaking of d.c. motors DC 6 Switching of incandescent lamps. Utilisation Chart 10.3
12 Motor Rating Chart Technical Data Motor Rating Chart Motor Ratings and Motor Rated Current The currents shown in the table below are those given for standard three phase squirrel cage motors r.p.m. 50Hz Values quoted are for guidance only. They can vary depending on the number of poles and design. Motor Ratings Motor Rated Current at KW HP V 240V 380V 415V 440V 500V 600V V / / / / / / /
13 Fuse Rating Chart Fuse Rating chart Direct-on-line starting Recommended Recommended fuse link fuse link Motor FLC Amp Type gg Type gm From to Amp Amp M M M M M M M M M M M M M M M670 Technical Data Assisted starting - Star-delta, auto-transformer, etc. Recommended fuse link Motor FLC Amp Type gg From to Amp These recommendations apply for ambient temperatures up to 35ºC. Suitable adjustments to the recommended ratings may be necessary if any of the following conditions occur singly or in combination: a) Starting currents in excess of the assumed ones. b) Long run up times due to high inertia loads. c) Larger number of starts per operating cycle (the recommendations allow for two starts in rapid succession and up to eight starts per hour). d) High enclosure temperature. Fuse Rating Chart 10.5
14 Telemecanique The complete solution for complete control Telemecanique is a UK market leader and world expert in industrial control and automation. It provides complete solutions, with its range of components, programmable logic controllers, variable speed drives and communications software. In addition, it offers power distribution through prefabricated busbar trunking. For further information on Telemecanique automation and control products please contact your local hte Controls distributor.
15 The Iboco Cable Trunking System offers the optimum solution to simplify and accelerate panel building. Iboco is represented exclusively in the UK by h. from
16 Notes
7 Lighting Technology
7 Lighting Technology Series HS6145 For use in Zone 1 and Zone 2 Comply with requirements of Fire Department standard DIN 14 462 Battery state display Deep discharge protection Open circuit monitor Light
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More informationA good connection. International approvals.
E X - P L U G S A N D R E C E P T A C L E S A to A Plastic version for Zone and Zone A good connection Providing electrical energy there, where it is most needed even in hazardous areas for the Zones,,
More informationPNOZsigma - Base units
PNOZsigma - Base units Register Login Sensors Control and Communication Electronic monitoring relays Safety Relays PNOZ X PNOZsigma PNOZelog PNOZmulti PNOZpower Configurable control systems Programmable
More informationLinear Luminaire with LED Series EXLUX 6402/2
> Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the
More informationPLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357
Series Features: Color coding and pin configuration makes it physically impossible to mate plugs and receptacles of different voltages and current ratings (per IEC 60 309-2). Interlocked switch mechanism
More informationR4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
More informationLinear Luminaire for Fluorescent Lamps Series EXLUX 6001
> As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened
More informationPlug and Socket Devices SolConeX 16 A Series 8570
www.stahl.de > Switch socket / plug 16 A > Minimal force required to insert and remove > Can be optionally equipped with an auxiliary contact for control and signalling purposes > arge switching handle
More informationType: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
More informationCM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way
More informationComponents for System Solutions E9/5. Ex d Enclosure System Made of Light Metal or Stainless Steel, "Flameproof Enclosure" Series 8264. www.stahl.
> Installation chamber can be fully used > Up to three mounting levels can be used > Saving of weight > Compact > Easy to combine > 26 enclosure versions > 15 window versions www.stahl.de 10303E00 The
More informationknow-how Giant in distributing electricity for industry Prisma GK
Prisma GK Giant know-how in distributing electricity for industry Installation system up to 630A for electrical power distribution and circuit control. Prisma GK: technology and innovation for an IP55
More informationE-STOP relays, safety gate monitors
Unit features Safety features gang engertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
More informationProducts and solutions for lifting systems
Products and solutions for lifting systems 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric headquarters founded
More informationmecotron Safety relay ESTOP-2 For emergency stop monitoring
E0006 000824 Safety relay E-2 For emergency stop monitoring Description The safety module E-2 for emergency stop monitoring is used for safety breaking one or more circuits and is designed to be incorporated
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
More informationCircuit Breakers. NRC Series. NRC Series. 900 www.idec.com
Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,
More informationE-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O),
More informationType Sealing Poles Contacts Rated voltage Model Standard d Flux-tight 4 poles oes 3PST-NO, SPST-NC 24 VDC G7SA-3A1B 3PST-NO, 3PST-NC
Safety Relay Slim Safety Relays Conforming to EN Standards The forcibly guided contact in the assures safe operation (EN50205 Class A, approved by VDE.) Ideal for use in safety circuits in press machinery,
More informationInductive Sensors Single or Dual Loop Detectors Type LD with teach-in
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation
More informationThyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
More informationMULTIFUNCTION TIME RELAY CRM-93H
4 MULTIFUNCTION TIME RELAY CRM-93H - 10 functions Features: Universal supply voltage AC/DC 12-240V 10 functions: - 5 time functions controlled by supply voltage - 4 time functions controlled by control
More informationPlug and Socket Devices CES 63 A Series 8579
www.stahl.de > Switch socket / plug 63 A > Large switch handle with clear switch position indication padlockable in 0- and I-position > Low insertion and withdrawal forces through individually encapsulated
More informationE-STOP relays, safety gate monitors
Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection
More information8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More informationContact expansion modules
Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 4 safety contacts
More informationABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011
, 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.
More informationContact expander modules
Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:
More informationUM-X Field display for continous level sensors
Technical Documentation Field display for continous level sensors 10/2007 Edition: 1 Item No.: 207120 FAFNIR GmbH Bahrenfelder Str. 19 D-22765 Hamburg Telephone: +49 (0)40-39 82 07-0 Fax: +49 (0)40-3 90
More information40.3. Control Relays and Timers
.3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories
More informationControl Devices Catalogue. Control Devices. Preferred and Standard Products
Control Devices Catalogue Control Devices Preferred and Standard Products KOP.J Timer Electronic 22.5 mm Characteristics Mounting KOP.J 22.5 mm mono or multifunction high immunity to interference surface
More informationSKR - industry relay
SKR - industry relay the universal relay SKR the time module STM the socket The strengths of the SKR industry relay lie in the mature and thoughtout construction. Over-average contact safety and life time,
More informationMasterseal Plus TM. ingress protected wiring devices. technical hotline +44 (0) 1268 563720. www.mkelectric.com IP66. Improved catch.
Masterseal Plus TM technical hotline +44 (0) 268 63720 Improved catch Rear drill holes Available in grey, white and black Fixed gasket speds installation gasket Now has all the features and logic plus
More information9 Control Equipment. Control Button Series 8082
9 Control Equipment Control Button 01706E00 contact elements enable contact blocks to be combined easily; using an actuator in the 8602 series, regardless of the type of actuator, up to 4 contact elements
More informationYour Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.
Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description
More informationSeries 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
More informationE-STOP relays, safety gate monitors
Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous
More informationTransformers from 25va to 500kva. Standard despatch in days not weeks
Transformers from 25va to 500kva Standard despatch in days not weeks JMS Transformers Ltd 20 Ivatt Way Westwood Business Park Peterborough PE3 7PG UK Tel: +44 (0)1733 760000 Fax +44 (0)1733 760004 e-mail:
More informationSafety automation solutions
Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO
More informationREB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The
More informationFIREDEX 2200. Conventional Fire Panels
68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class
More informationWolflite Safety Handlamp H-251E
Wolflite Safety Handlamp H-251E & H-251 Mk1 & Mk2 Wolflite Safety Handlamp H-251E H 18Y H 17 H 31Y H 21A H 30 H 24 H 26 H 19 H 25 H 03 H 15Y H 22 H 104 H 29 H 66 H 13 H 14 H 09 H 12 H 48 H 11 H 62 H 63
More informationAmmeter / Voltmeter Series 8402, 8403, 8405, 8404
/, 8403, 8405, 8404 > Fast comparison of measured with set values > s available, 8403 and 8402 www.stahl.de, 8403, 8405, 8404 10073E00 The ammeters and voltmeters from R. STAHL are explosion protected,
More informationAmmeter / Voltmeter Series 8402, 8403, 8405, 8404
/, 8403, 8405, 8404 > Fast comparison of measured with set values > s available, 8403 and 8402 www.stahl.de, 8403, 8405, 8404 10073E00 The ammeters and voltmeters from R. STAHL are explosion protected,
More informationProducts and solutions for pumping, irrigation and piping
Products and solutions for pumping, irrigation and piping 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric
More informationFerrostat Speed Sensor Series DSF Explosion Proof Versions EEx
Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx DSF..10.**.HV Ex ATEX Operating Instructions 374E-64368 Valid from lot nr. 0103 General Function Use in potentially explosive environment
More informationACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
More informationE-STOP relays, safety gate monitors
Unit features Unit description Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Gertemerkmale Positive-guided relay outputs: 3 safety contacts (N/O),
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 15 mm
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element
More informationESB and EN installation contactors Application handbook
ESB and EN installation contactors Application handbook 2 2CDC103022M0201 Content 1 Basic function of installation contactors 4 2 Modular DIN rail components 5 3 ESB/EN Installation contactors 6 4 Technical
More informationMureva Assembly surface mounted wiring devices
1.0 Waterproof Assembly surface Switches P124543 P124547 External dimensions : 72 x 72 x 47 mm.. Assembly surface rockers become illuminated using bulbs and indicators in option. They can carry a label
More informationSafety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
More informationMini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear
Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC
More information2.8. Ex-Recess-mounted, ceiling emergency light fittings in compact metal design
.8 Ex-Recess-mounted, ceiling emergency light fittings in compact metal design RLF/RLF-INOX 50 18-58 W / RLF/RLF-INOX 50... N 18-36 W (Zone 1,, 1, ) The explosion-protected lighting concept for clean rooms
More informationMICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features
Central 48 V DC Power Supplies for PoE-Components MICROSENS Description Active network equipment which is supporting the Power-over-Ethernet functions, typically requires a powerful 48 V DC power supply.
More informationDORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
More informationRedundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
More informationStandards, formulae, tables
Page Marking of electrical equipment - Protective measures -4 Overcurrent protection of cables and conductors -1 Electrical equipment of machines -1 Measures for risk reduction -7 Protection types for
More informationSMS 4 / SMS 5 safety mat Product information
SMS 4 / SMS 5 safety mat Product information SMS 4 / SMS 5 safety mats Safety mats are used for the protection of man on machinery and plants with hazardous movements. Typical fields of application are,
More informationEX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL
PRODUCT NAME: CP/PB -150- EXPLOSION-PROOF-MANUAL CALL POINT/ PUSH BOTTON DOC NO.: EX-TECH SAS-12-CP-PB150-TM REV01 EXPLOSION-PROOF MANUAL CALL POINT/ PUSH BOTTON II 2GD EPL Gb, Db Ex d IIC T6, IP66 Ex
More informationEXLUX ECOLUX C-LUX LIGHTING. Explosion Protected Fluorescent Lighting Fixtures for Hazardous and Corrosive Applications
EXLUX ECOLUX C-LUX LIGHTING 6000 6008 6400 6408 6600 6608 6500 Explosion Protected Fluorescent Lighting Fixtures for Hazardous and Corrosive Applications Features: Electronic Ballasts For Fluorescent Bipin
More informationOperating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
More informationOperating Instructions
D-TEK Vehicle Loop Detector Operating Instructions This product is an accessory or part of a system. Always read and follow the manufacturer s instructions for the equipment you are connecting this product
More informationProgrammable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2
Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male
More informationSafe timer relay/contact expansion modules
??Gertebild Bildunterschrift Contact expander module for increasing the number of available contacts, Pulse-on timer relay for step-by-step control of movement sequences, Delay-on energisation timer for
More informationProducts and solutions for machine builders (OEM) 100% electricity
Products and solutions for machine builders (OEM) 100% electricity www.lovatoelectric.com Tra dition and innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric headquarters
More information2010-2011. Shortform Catalogue. Solutions for appliance & electronic applications. rocker switches. lever. switches. push. switches.
2010-2011 Solutions for appliance & electronic applications Shortform Catalogue rocker lever push vandal resistant slide door snap-action & safety rotary IEC sockets fuseholders indicators A trading name
More informationSafety detection solutions
Presentation, actuator operated etal, types CS A, CS B, CS C and CS E Plastic, double insulated, turret head, types CS P or CS PA or CS TA and CS TE etal, types CS A, CS B, CS C, CS E with or without locking
More informationFloodlight Range Installation Guide
SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected
More information48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
More informationSwitches and Indicators. Swisstac
Switches and Indicators Switches and Indicators Index Series Description Page 583 Product Assembly Page 584 Mounting Instruction Page 585 Product Range - pushbuttons for standard mounting - pushbuttons
More informationINDICATOR LAMPS & LED REPLACEMENT LAMPS
INDICATOR LAMPS & LED REPLACEMENT LAMPS Neon indicators (internal resistor) 120VAC 55-452-0 Red lens 120VAC 55-453-0 Amber lens 120VAC 55-455-0 Green lens 120VAC Neon indicators (internal resistor) 120VAC
More informationG7SA. Ordering Information. Slim Plug-In Safety Relay. Slim Safety Relay for Machine Control. H Slim body only 13 x 24 x 50 mm
Slim Plug-In Safety Relay Slim Safety Relay for Machine Control H Slim body only 13 x 24 x 50 mm (six poles) H Four-pole and six-pole models are available H Terminal arrangement simplifies PCB pattern
More information38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
More informationMasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
More informationBARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
More information38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
More informationReference. 910 402 230 V, 50 Hz A10 415 120 V,60 Hz. 916 402 230 V, 50/60 Hz A16 418 120 V, 50/60 Hz. 910 103 230 V, 50 Hz A10 104 120 V, 60 Hz
Rex - analog time switches MicroRex - 3 modules for DIN rail mounting Rex - analog time switches MicroRex - module for DIN rail mounting 926 428 A0 4 MicroRex T3 24 hour program, synchronous motor 92 429
More informationPower Generation. Power Control PCL System Generator Set Control
Power Generation Power Control PCL System Generator Set Control Solid State Control The Power Control PCL system uses the latest solid state control technology. Designed for the budget-conscious installation
More informationE-STOP relays, safety gate monitors
Unit features Unit description Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
More informationPower Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
More informationWD-AMX Water Detection Controllers
Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation
More informationSeries 427. 1/16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS
Series 427 1/16 DIN Multi-Mode Bar Graph Display Timer PRODUCT HIGHLIGHTS Digital Setting with 0.1% Accuracy Unique LED Bargraph Indicates Time Cycle in 20% Increments 8 Field Selectable Modes of Operation
More informationETZGAR CONVEYOR COMPANY Controls Section v12.05
Section 7 Controls Page Description 7-1 Controls Index 7-2 Motor Data, Enclosure Rating and Abbreviations 7-3 Controls Safety Guidelines 7-4 Fixed Speed Controls Packages 7-5 Three Phase AC Variable Speed
More informationCQM1-SF200/CS1W-SF200
Safety Relay Unit ( I/O Unit Type) CQM1-SF200/CS1W-SF200 CSM_CQM1-SF200_CS1W-SF200_DS_E_2_1 A Safety Relay Unit That Functions as a I/O Unit. Less Installation Space and Wiring Required. Safety Relay Unit
More informationApplication Technique. Safety Function: Magnetic Door Switch Monitoring
Application Technique Safety Function: Magnetic Door Switch Monitoring Products: MC1 Magnetically-coded Door Switch, Guardmaster Dual-input Safety Relay Safety Rating: CAT. 3, PLd to EN ISO 13849-1: 2008
More informationE&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.
SAFETY Industrial DESCRIBE hazards and precautions taken to avoid injury in the workplace. Example #1: All of the following are common PPE used to perform maintenance activities EXCEPT: a. Safety Glasses
More informationConventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
More informationDaker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationMOUNTING AND OPERATING INSTRUCTIONS
MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall
More informationSECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationShort Range Wireless Switch System Handheld 8 Installation and Operations Guide
Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...
More informationCB200W Water Leak Detection Panel Application Guide
Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical
More informationVoltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
More informationPNOZ s3. Safety relays. Operating Manual-21395-EN-10
Safety relays Operating Manual- Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions
More informationALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL
ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL INTRODUCTION... 2.. TECHNICAL DATA... 3 ACCESSORIES... 5. INSTALLATION... 7 OPERATION... 12. TECHNICAL INFORMATION... 13 MAINTENANCE... 14. CONFIGURATIONS...
More informationPreventa Machine Safety Products
Preventa Machine Safety Products Catalog 2009 200 Supplement Safety Relay Modules 2 Contents Preventa safety relay modules Selection guide 2 Electrical Ratings 6 Types XPSAC and XPSAXE For Emergency stop
More information