Installation manual MMU-AP0182H2UL MMU-AP0212H2UL MMU-AP0242H2UL MMU-AP0302H2UL MMU-AP0362H2UL MMU-AP0422H2UL AIR CONDITIONER (MULTI TYPE) Indoor Unit

Size: px
Start display at page:

Download "Installation manual MMU-AP0182H2UL MMU-AP0212H2UL MMU-AP0242H2UL MMU-AP0302H2UL MMU-AP0362H2UL MMU-AP0422H2UL AIR CONDITIONER (MULTI TYPE) Indoor Unit"

Transcription

1 AIR CONDITIONER (MULTI TYPE) Installation manual Indoor Unit Model name: 4-way Cassette type MMU-AP0182H2UL MMU-AP0212H2UL MMU-AP0242H2UL MMU-AP0302H2UL MMU-AP0362H2UL MMU-AP0422H2UL Installation manual Air conditioner (Multi type) 1 English Manuel d installation Climatiseur (Type multi) 19 Français

2 1-EN 1 4-way Cassette type 4-way Cassette type 2-EN Please read this manual thoroughly before installation work and install the products correctly. This Manual describes the installation method of the indoor unit. For installation of the outdoor unit, refer to the of the outdoor unit. ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly refrigerant. Contents 1 Accessory Parts Precautions for Safety Selection of Installation Place Installation Drain Piping Work Refrigerant Piping and Evacuation Electrical Connection Applicable Controls Test Run Troubleshooting Accessory Parts Accessory parts Part name Q ty Shape Usage 1 This manual (Hand over to customers) Heat insulating pipe 2 For heat insulation of pipe connecting section Installation pattern 1 For confirmation of ceiling opening and indoor unit position Installation gauge For positioning of ceiling position Washer 4 For hanging-down unit Eccentric washer 4 For hanging-down unit Hose band 1 For connecting drain pipe Heat insulator 1 For heat insulation of drain connecting section Flexible hose 1 For adjusting center of drain pipe Separate sold parts The Ceiling panel and remote control are sold separately. For the installation of these products, follow the s supplied with them. The wireless type remote control is designed to be installed by attaching a wireless remote control kit (sold separately) to the standard panel. (The wireless remote control kit consists of a wireless remote control and adjust corner caps with a signal receiving unit.)

3 4-way Cassette type 4-way Cassette type 2 Precautions for Safety Installing, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start--up, and service this equipment. Untrained personnel can perform basic maintenance functions such as cleaning heat exchanger. All other operations should be performed by trained service personnel. Before working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment. Follow all safety codes.wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby during brazing. Use care in handling, rigging, and setting bulky equipment. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety--alert symbol. When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.understand these signal words: DANGER, WARNING, and. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual. WARNING Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in water leakage, electric shock or fire. Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body. Connect ground wire. (grounding work) Incomplete grounding may cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires. Turn off all the circuit breaker before attempting any electrical work. Failure to do so may cause electric shock. Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the air conditioner is operated with the valve open and without the refrigerant pipe, the compressor sucks air and the refrigeration cycle is overpressurized, which may cause a burst or injury. When moving the air conditioner for the installation into another place, do not enter any gaseous matter other than the specified refrigerant into the refrigeration cycle. If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons. Perform installation work properly according to the. Inappropriate installation may result in water leakage, electric shock or fire. When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level. Install the air conditioner securely in a location where the base can sustain the weight adequately. Perform the specified installation work to guard against an earthquake. If the air conditioner is not installed appropriately, accidents may occur due to the falling unit. If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate. After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate. Electrical work must be performed by a qualified electrician in accordance with the. Use an exclusive power supply for the air conditioner at the rated voltage. An insufficient power supply capacity or inappropriate installation may cause fire. Use the specified wires for wiring connect the terminals. Securely fix them to prevent external forces applied to the terminals from affecting the terminals. Conform to the regulations of the local electric company when wiring the power supply. For the refrigerant recovery work (collection of refrigerant from the pipe to the compressor), stop the compressor before disconnecting the refrigerant pipe. If the refrigerant pipe is disconnected while the compressor is working with the valve open, the compressor sucks air and the refrigeration cycle is overpressurized, which may cause a burst or injury. THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER. The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle. To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant. Accordingly the exclusive tools are required for the new refrigerant (R410A). For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter. Tighten the flare nut with a torque wrench in the specified manner. Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage. Wear heavy gloves during the installation work to avoid injury. EN 3-EN 2 4-EN

4 5-EN 3 4-way Cassette type 4-way Cassette type 6-EN 3 Selection of Installation Place WARNING Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is not enough, the unit may fall down resulting in injury. Install the air conditioner at a height 8 (2.4 m) or more from the floor. If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous because you may contact with revolving fan or active electricity. Do not install in a location where flammable gas may leaks are possible. If the gas leak and accumulate around the unit, it may ignite and cause a fire. Upon approval of the customer, install the air conditioner in a place that satisfies the following conditions. Place where the unit can be installed horizontally. Place where a sufficient servicing space can be ensured for safety maintenance and check. Place where drained water will not cause any problem. Avoid installing in the following places. Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot spring). (Should the unit be used in these places, special protective measures are needed.) A restaurant kitchen where a lot of oil is used or place near machines in a factory (Oil adhering to the heat exchanger and resin part (turbo fan) in the indoor unit may reduce the performance, generate mist or dew drop, or deform or damage resin parts.) Place where organic solvent is used nearby. Place close to a machine generating high frequency. Place where the discharged air blows directly into the window of the neighbor house. (Outdoor unit) Place where noise of the outdoor unit is easily transmitted. (When the outdoor unit is installed on the boundary with the neighbor, pay due attention to the level of noise.) Place with poor ventilation. (Before air duct work, check whether value of fan speed, static pressure and duct resistance are correct.) Do not use the air conditioner for special purposes such as preserving food, precision instruments, or art objects, or where breeding animals or growing plants are kept. (This may degrade the quality of preserved materials.) Place where any of high-frequency appliances (including inverter devices, private power generators, medical equipment, and communication equipment) and inverter-type fluorescent light is installed. (A malfunction of the air conditioner, abnormal control, or problems due to noise to such appliances/equipment may occur.) When the wireless remote control is used in a room equipped with an inverter-type fluorescent light or at a place exposed to direct sunlight, signals from the remote control may not be received correctly. Place where organic solvent is used. Place near a door or window exposed to humid outside air (Dew drop may form.). Place where special spray is used frequently. Installation space Secure the specified space in the figure for installation and servicing. Model MMU- AP018, AP021, AP024, AP030 Type AP036, AP042 Type 0.6 (15) 15 or more (0.6) or more A Selection of installation place unit: in (mm) Continual operation of the indoor unit under high-humidity conditions as described below, dew may condense and water may drop. Especially, high-humidity atmosphere (dew point temperature: 73.4 F (23 C) or more) may generate dew inside the ceiling. 1. Unit is installed inside the ceiling with slated roof. 2. Unit is installed at a location using inside of the ceiling as fresh air take-in path. 3. Kitchen Advice Set a service check opening panel at right side of the unit (size: 17.7" 17.7" ( mm) or more) for piping, maintenance, and servicing. If installing a unit at such place, put insulating material (glass wool, etc.) additionally on all the positions of the indoor unit which come to contact with high-humidity atmosphere (1000) (39.4) or or more more Obstacle (1000) (39.4) or more or more Check port x 17.7 (450 ( ) x 450) 7.9 (200) 200 (7.9) A in (mm) 10.7 (271) or more 13.1 (334) or more Check port Check port 17.7 x (450 x 450) ( ) Check port port must must be be located located on on the the Fresh Fresh air air inlet box side, if it is installed. if it is installed When the humidity inside the ceiling seems to be higher than 80%, attach a heat insulator to the side (top) surface of the indoor unit. (Use a heat insulator that is 0.4" (10 mm) or more thick.) (200) (7.9)

5 4-way Cassette type 4-way Cassette type Ceiling height Model MMU- Possible installed ceiling height AP018, AP021, AP024, AP030 Type Up to 12 6 (3.8 m) AP036, AP042 Type Up to 15 1 (4.6 m) When the height of the ceiling exceeds the distance of the item Standard/4-way in below table, the warm air is difficult to reach the floor. It is necessary to change the setup value of the high ceiling setting or discharge direction. Height list of ceiling possible to be installed Unit : ft (m) Model MMU- AP018 Type AP021, AP024, AP030 Type AP036, AP042 Type High ceiling setup No. of discharge direction 4-way 3-way 2-way 4-way 3-way 2-way 4-way 3-way 2-way Set data Standard (Factory default) (2.8) (3.2) (3.5) (3.0) (3.3) (3.6) (3.9) (4.2) (4.5) 0000 High ceiling (1) High ceiling (2) 10 6 (3.2) 11 6 (3.5) 11 6 (3.5) 12 6 (3.8) 12 6 (3.8) (3.3) (3.6) 11 6 (3.5) 12 6 (3.8) 12 6 (3.8) 13 9 (4.2) 14 9 (4.5) 14 5 (4.4) 15 1 (4.6) 15 1 (4.6) Use a Air discharge direction kit (sold separately) to change discharge directions. Discharge directions are limited. Follow the supplied with the Air discharge direction kit. Air discharge direction kit (sold separately) When an air conditioner with 2-way/3-way discharge system is used, a strong wind blows directly if the ceiling height is lower than the standard. Change the SET DATA according to height of the ceiling. When the high ceiling (1) or (2) with 4-way discharge system is used, the draft is apt to be felt due to drop of the discharge temperature. The lighting time of the filter sign (notification of filter cleaning) on the remote control can be changed according to installation conditions. When it is difficult to obtain satisfactory heating due to location place of the indoor unit or the structure of the room, the detection temperature of heating can be raised. Refer to "8. Applicable Controls" in this manual for the setting procedure. Discharge direction As shown in the figure below, air discharge directions can be selected according to the shape of the room and the location of the indoor unit installation. 3 directions 2 directions EN 7-EN 4 8-EN

6 9-EN 5 4-way Cassette type 4-way Cassette type 10-EN 4 Installation Strictly comply with the following rules to prevent damage of the indoor units and human injury. Do not put a heavy article on the indoor unit. (Even units are packaged) Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering cloth or other soft cloth to not damage the unit. To move the indoor unit, hold the hooking metals (4 positions) only. Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts). Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified. External view Ceiling bottom surface 7.4" (187) 33.1" (840) 2.2" (57) 2.4" (61) 1.1" (28.5) Ceiling bottom surface Knockout for Auxiliary fresh air flange For Ø3.9" (100) Z view Electrical control 1.2" (30) 10.6" (269) 2.5" (64) Ceiling bottom surface Ceiling panel (sold separately) 33.1" (840) Unit external dimension 16.1" (408) 16.4" (416.5) 27.2" ± 0.8" (690 ± 20) Hanging bolt pitch 33.9" " ( ) Ceiling opening dimension 37.4" (950) Panel external dimension Ceiling opening dimension 12.7" (323) 33.9" " ( ) 30.7" (780) Hanging bolt pitch 37.4" (950) Panel external dimension 9.5" (241.5) 2.8" (72) 5.2" (132) Ceiling bottom surface Refrigerant pipe connecting port (Liquid) B Refrigerant pipe connecting port (Gas) C 10.4" (263) 4.1" (105) Drain pipe connecting port 1.6" (40) Hanging bolt 3/8" (M10) (To be procured locally) 6.8" (172) 4.4" (112) Unit: in (mm) 2.3" (58) 1.7" (42) Hole for power supply wire Conduit hole (knockout) Hole for remote control wires 9.9" (251) 11.1" (281) 12.1" (306) Ceiling bottom surface 7.4" (189) Opening a ceiling and installation of hanging bolts Consider the piping/wiring after the unit is hung to determine the location of the indoor unit installation and orientation. After the location of the indoor unit installation has been determined, open the ceiling and install hanging bolts. The dimensions of the ceiling opening and hanging bolt pitches are given in the outline drawing and the attached installation pattern. When a ceiling already exists, lay the drain pipe, refrigerant pipe, control wires, and remote control wires to their connection locations before hanging the indoor unit. Procure hanging bolts and nuts for installing the indoor unit (these are not supplied). Hanging bolt 3/8" (M10) 4 pieces Nut 3/8" (M10) 12 pieces Using the installation pattern (accessory) The installation pattern is provided inside the packaging cap. <For existing ceiling> Use the installation pattern positioning a ceiling opening and hanging bolts. <For new ceiling> Use the installation pattern to position the ceiling opening when a ceiling is hanged. After the hanging bolts have been installed, install the indoor unit. Hook the four holes in the installation pattern to the panel fixing screws of the indoor unit. Before hanging a ceiling, open the ceiling along the outside dimensions of the installation pattern. Panel fixing screw Treatment of ceiling The ceiling differs according to structure of building. For details, consult your constructor or interior finish contractor. In the process after the ceiling board has been removed, it is important to reinforce ceiling foundation (frame) and to keep horizontal level of installed ceiling correctly in order to prevent vibration of ceiling board. 1. Cut and remove the ceiling foundation. 2. Reinforce the cut surface of ceiling foundation, and add ceiling foundation for fixing the end of ceiling board. Installation of hanging bolt Use 3/8 (M10) hanging bolts (4 pcs, to be local procure). Matching to the existing structure, set pitch according to size in the unit external view as shown below. New concrete slab Install the bolts with insert brackets or anchor bolts. (Blade type bracket) (Slide type bracket) Rubber Anchor bolt (Pipe hanging anchor bolt) Steel flame structure Use existing angles or install new support angles. Hanging bolt Hanging bolt Support angle Existing concrete slab Use a hole-in anchors, hole-in plugs, or a hole-in bolts. Unit: in (mm) Model MMU- A B C Model MMU- A B C AP018 Type 10.1 (256) Ø1/4 (6.4) Ø1/2 (12.7) AP030 Type 10.1 (256) Ø3/8 (9.5) Ø5/8 (15.9) AP021 Type 10.1 (256) Ø3/8 (9.5) Ø5/8 (15.9) AP036 Type 12.6 (319) Ø3/8 (9.5) Ø5/8 (15.9) AP024 Type 10.1 (256) Ø3/8 (9.5) Ø5/8 (15.9) AP042 Type 12.6 (319) Ø3/8 (9.5) Ø5/8 (15.9) hole Installation pattern (Accessory)

7 4-way Cassette type 4-way Cassette type Installation of ceiling opening and hanging bolt Attach a nut (3/8" (M10): not supplied) and the Ø1.3" (34 mm) washer (supplied) to each hanging bolt. Insert a washer on both sides of the T groove of the hanging bracket of the indoor unit, and hang the indoor unit. Check that the four sides of the indoor unit are level using a level vial (levelness: 0.2" (5 mm) or less). Detach the installation gauge (accessory) from the installation pattern. Using the installation gauge, check and adjust the positional relation between the indoor unit and the ceiling opening (1) ( (10-35 mm): 4 sides) and the hanging-up height (2) ( (12-17 mm): 4 corners). (How to use the installation gauge is printed on the gauge.) Hanging bolt 3/8 (M10) Nut 3/8 (M10) Eccentric washer (Accessory) Level * Install with the marking UP facing up. Hanging bolt Hanging bracket * Procure hanging bolts and nuts locally. Washer (Accessory) To prevent the bolt from falling off (for safety), be sure to set it just under the hanging bracket as shown in the figure. Nut 3/8 (M10) Level vial (levelness: 0.2 (5 mm) or less) Hanging bolt Ceiling board Hanging bracket (1) (10-35 mm) Installation gauge (1) (10-35 mm) (2) (12-17mm) Ceiling board (2) (12-17 mm) Installation gauge Before installation of the indoor unit, remove the tape that holds the fan and bell mouth. Running the unit without removing the tape may damage the fan motor. Installation of ceiling panel (sold separately) Install the ceiling panel according to Installation Manual attached with it after piping/wiring work has completed. Check that installation of indoor unit and ceiling opening part is correct, and then install it. Joint the connecting sections of ceiling panel, ceiling surface, ceiling panel and indoor unit closely. Any gap between them will cause air leakage and the generate condensation or water leakage. Remove the adjust corner caps at the four corners of the ceiling panel, and then install the ceiling panel onto the indoor unit. Securely fix the claws of the four adjust corner caps. Improper fitting of the claws may cause water leakage. Installation of remote control (Sold separately) For installation of the wired remote control, follow the attached with the remote control. Pull out the remote control cord together with the refrigerant pipe or drain pipe. Pass the remote control cord through upper side of the refrigerant pipe and drain pipe. Do not leave the remote control at a place exposed to the direct sunlight and near a stove. Wireless remote control The sensor of indoor unit with wireless remote control can receive a signal by distance within approx. 23 (7 m). Based upon it, determine a place where the remote control is operated and the installation place. Operate the remote control, confirm that the indoor unit receives a signal surely, and then install it. Keep 3 3 (1 m) or more from the devices such as television, stereo, etc. (Disturbance of image or noise may generate.) To prevent a malfunction, select a place where is not influenced by a fluorescent light or direct sunlight. Two or more (Up to 6 units) indoor units with wireless type remote control can be installed in the same room. Within 23 (7m) EN 11-EN 6 12-EN

8 13-EN 7 4-way Cassette type 4-way Cassette type 14-EN 5 Drain Piping Work Following the, perform the drain piping work so that water is properly drained, and apply a heat insulation so as not to cause a dew drop. Inappropriate piping work may result in water leakage in the room and wet of furniture. Piping/Heat insulating material Require the following materials for piping and heat insulating at site. Piping Heat insulator Flexible hose Hard vinyl chloride pipe VP25 (Outer dia.: Ø1.3" (32 mm)) Foam polyethylene: Thickness 0.4" (10 mm) or more Use the attached flexible hose to adjust center discrepancy of the hard vinyl chloride pipe or to adjust the angle. Do not use the flexible hose as stretched, or do not deform it more extent than that in the following figure. Fix the soft end of the flexible hose with the attached hose band. Use the flexible hose on a horizontal level. OK Max 45 Max 45 NO GOOD Riser (Trap) 90 Bend Perform heat insulation of the drain pipes of the indoor unit. Perform heat insulation of the connecting part with the indoor unit. An incomplete heat insulation causes dew drop. Set the drain pipe with downward slope (1/100 or more), and do not make swelling or trap on the piping. It may cause an abnormal sound. For length of the traversing drain pipe, restrict to 65 7 (20 m) or less. In case of a long pipe, provide support brackets with interval of (1.5-2 m) in order to prevent waving. Heat insulator (1.5-2 m) 1/100 or more downward Arched shape Trap Support bracket NO GOOD Set the collective piping as shown in the below figure. As long as possible (3.9 (100 mm)) VP25 VP25 VP25 VP30 or more Downward slope 1/100 or more Do not apply force to the connecting part of the drain pipe. The hard vinyl-chloride pipe cannot be directly connected to the drain pipe connecting port of the indoor unit. For connection with the drain pipe connecting port, fix the attached flexible hose with the hose band, otherwise a damage or water leak is caused on the drain pipe connecting port. Drain pipe connecting port (Hard socket) Adhesive inhibited: Use the attached flexible hose and hose band for connecting the drain hose to the clear drain socket. If applying the adhesive, socket will be damaged and cause water leakage. Drain pipe connecting port (Transparent) Soft socket Attached hose band Align the attached hose band to the end of hose, set the tightening position upward, and then tighten it. Flexible hose (Accessory) Connecting drain pipe VP25 vinyl chloride pipe (To be local procure) Attached flexible hose Hard socket Socket for VP25 (To be local procure) VP25 vinyl chloride pipe (To be local procure) Socket for VP25 vinyl chloride pipe (To be local procure) Connect a hard socket (procured locally) to the hard socket of the attached supplied flexible hose. Connect a drain pipe (procured locally) to the connected hard socket. Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage. It takes some time until the adhesive is dried and hardened (refer to the manual of the adhesive). Do not apply stress to the joint with the drain pipe during this time period. Drain up When a down-gradient cannot be secured for the drainpipe, drain-up piping is possible. The height of the drain pipe must be 33.5" (850 mm) or less from the bottom of the ceiling. Take the drain pipe out of the drain pipe joint with the indoor unit in 11.8" (300 mm) or less, and bend up the pipe vertically. Immediately after the pipe is bent up vertically, lay the pipe making a down-gradient. Set downward grading immediately after raising up vertically. Check the draining In the test run, check that water drain is properly performed and water does not leak from the connecting part of the pipes. Check draining also when the unit is installed in heating period. By using a pitcher or hose, pour water ( gal ( cc)) into the discharge port before installation of the ceiling panel. Pour water gradually so that water does not spread on the motor of the drain pump (300 mm) or less Rising up 26.0 (661 mm) or less Rising up 33.5 (850 mm) or less Underside of ceiling Pour water gently so that it does not spread around inside the indoor unit, which may cause a malfunction.

9 4-way Cassette type 4-way Cassette type Heat exchanger Tool for pouring water Bottle Drain pan Float switch connector (3P) (CN34: red) Insert the hose end between the heat exchanger and the drain pan, and then bend the hose downward. Water ( gal ( cc)) After the electric work has finished, pour water during COOL mode operation. If the electric work has not yet finished, pull out the float switch connector (CN34: Red) from the electrical control box, and check draining by plugging the single phase 208/230 V power to the terminal blocks L1 and L2. If doing so, the drain pump motor operates. Test water drain while checking the operation sound of the drain pump motor. (If the operation sound changes from continuous sound to intermittent sound, water is normally drained.) After the check, the drain pump motor runs, connecting the float switch connector. (In case of check by pulling out the float switch connector, be sure to return the connector to the original position.) Perform heat insulating As shown in the figure, cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit without gap. Cover the drain pipe seamlessly with a heat insulator to be procured locally so that it overlaps with the attached heat insulator of the drain connecting section. Wrap the attached heat insulator seamlessly from the surface of the indoor unit. Heat insulator of the drain connecting section (Accessory) Heat insulator (procured locally) * Direct the slits and seams of the heat insulator upward to avoid water leakage. 6 Refrigerant Piping and Evacuation Refrigerant Piping 1. Use copper pipe with 0.03" (0.8 mm) or more thickness. (In case pipe size is Ø5/8" (15.9 mm), with 0.04" (1.0 mm) or more.) 2. Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut attached to the main unit of the air conditioner, and use it. When the refrigerant pipe is long, provide support brackets at intervals of (2.5-3 m) to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated. IMPORTANT 4 POINTS FOR PIPING WORK 1. Remove dust and moisture from the inside of the connecting pipes. 2. Tight connection (between pipes and unit) 3. Evacuate the air in the connecting pipes by using VACUUM PUMP. 4. Check the gas leakage. (Connected points) Pipe size Model name Pipe size MMU- Gas side Liquid side AP018 type 1/2" (12.7 mm) 1/4" (6.4 mm) AP021, AP024, AP030, AP036, AP042 type 5/8" (15.9 mm) 3/8" (9.5 mm) Permissible Piping Length and Height Difference They vary according to the outdoor unit. For details, refer to the attached to the outdoor unit. Flaring Cut the pipe with a pipe cutter. Remove burrs completely. Remaining burrs may cause gas leakage. Insert a flare nut into the pipe, and flare the pipe. As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A are recommended. However, the conventional B tools can be used by adjusting projection margin of the copper pipe. Projection margin in flaring: B (Unit: in (mm)) Rigid (Clutch type) R410A tool Outer dia. of copper pipe used R410A 1/4 (6.4), 3/8 (9.5) /2 (12.7), 5/8 (15.9) (0-0.5) Conventional tool used R410A ( ) Flaring dia. meter size: A (Unit: in (mm)) A (0.4) Outer dia. of copper pipe R410A 1/4 (6.4) 0.36 (9.1) 3/8 (9.5) 0.52 (13.2) 1/2 (12.7) 0.65 (16.6) 5/8 (15.9) 0.78 (19.7) Power terminals CN34 (RED) Black Black L1 L2 208/ Red White Pull out connector CN34 (Red) from P.C. board. * In case of flaring for R410A with the conventional flare tool, pull it out approx. 0.02" (0.5 mm) more than that for R22 to adjust to the specified flare size. The copper pipe gauge is useful for adjusting projection margin size. A EN 15-EN 8 16-EN

10 17-EN 9 4-way Cassette type 4-way Cassette type 18-EN Tightening connection Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions. Unit: ft lbs (N m) Outer dia. of copper pipe Tightening torque 1/4" (6.4 mm) (14-18) 3/8" (9.5 mm) (33-42) 1/2" (12.7 mm) (50-62) 5/8" (15.9 mm) (63-77) Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22. (Approx. 1.6 times) Use a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque. Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle. Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure. Work using double spanner Tightening with an excessive torque may crack the nut depending on installation conditions. Tighten the nut within the specified tightening torque. Piping with outdoor unit Shape of valve differs according to the outdoor unit. For details of installation, refer to the Installation Manual of the outdoor unit. Leak check test, evacuation and other procedure For leak check test, evacuation, addition of refrigerant, and gas leak check, refer to the attached to the outdoor unit. Do not supply power to the indoor unit until the leak check test and evacuation are completed. (If the indoor unit is powered on, the pulse motor valve is fully closed, which extends the time for vacuuming.) Open the valve fully Open the valve of the outdoor unit fully. For details, refer to the attached to the outdoor unit. Heat insulation process Apply heat insulation for the pipes separately at liquid side and gas side. For the heat insulation to the pipes at gas side, use the material with heat-resisting temperature 248 F (120 C) or higher. Apply the attached heat insulation to the pipe connecting section of the indoor unit securely without gap. Apply the heat insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of the pipe. (The pipe exposed to the outside may causes water leak.) Wrap heat insulator with its slits facing up (ceiling side). Wrap the pipe with the attached heat insulator without any gap between the indoor unit. The seam must be faced upward (ceiling side). 7 Electrical Connection WARNING 1. Use predefined wire and connect them certainly. Keep the connecting terminal free from external force. Improper wire connection or clamping may result in exothermic, fire or malfunction. 2. Connect ground wire. (grounding work) Incomplete grounding cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires. 3. Install appliance in accordance with national wiring regulations. Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire. Consult local building codes, NEC (National Electrical Code) or CEC (Canadian Electrical Code) for special requirements. If incorrect/incomplete wiring is carried out, it will cause an electrical fire or smoke. Install circuit breaker is not tripped by shock waves. If circuit breaker is not installed, an electric shock may be caused. Use the cord clamps attached to the product. Do not damage or scratch the conductive core and inner insulator of power and control wires when peeling them. Use the power cord and control wire of specified thickness, type, and protective devices required. Do not connect 208/230 V power to the terminal blocks (U1, U2, A, B etc.) for control wiring. (Otherwise, the system will fail.) Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe. The coating may melt resulting in an accident. Do not turn on the circuit breaker of the indoor unit until vacuuming of the refrigerant pipes completes. For power supply wiring, strictly conform to the Local Regulation in each country. Run the refrigerant piping line and control wiring line in the same line. Power supply wire and control wires specifications Power supply wire and interconnecting wires are procured locally. For the power supply specifications, follow to the table below. If capacity is little, it is dangerous because overheat or seizure may be caused. power supply For the power supply of the indoor unit, prepare the exclusive power supply separated from that of the outdoor unit. Power supply Power supply 208/ Control wiring, Central control wiring 2-core with non-polarity wires are used for the control wiring between indoor unit and outdoor unit and Central control wiring. To prevent noise trouble, use 2-core shielded wire. The length of the communication line means the total length of the control wire length between indoor and outdoor units added with the central control wire length. Heat insulation pipe (Accessory) Union Flare nut Heat insulator of the pipe

11 4-way Cassette type 4-way Cassette type Power supply wire Recommended wire diameter and wire length for power supply wire. Power supply wiring Electric characteristics Wire size: 2 AWG12 Ground 1 AWG12 or thicker Up to (50m) MCA : Minimum Circuit Amps MOCP : Maximum Overcurrent Protection (Amps) Model Power Supply Voltage Range (V) MCA MOCP Min Max (A) (A) MMU-AP0182H2UL MMU-AP0212H2UL MMU-AP0242H2UL /230V-1-60Hz MMU-AP0302H2UL MMU-AP0362H2UL MMU-AP0422H2UL Wiring between indoor and outdoor units NOTE An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the header unit. Wiring example Outdoor Power supply Ground L1L2L3 N terminal U1U2U3U4U5U6 Outdoor Power supply 208/ / Circuit breaker Header outdoor unit Ground L1L2L3 N terminal Circuit breaker Follower outdoor unit U1U2U3U4U5U6 Control wire Control wiring between indoor units, and outdoor unit (2-core shielded wire) Wire size (Up to (1000m)) AWG16 (Up to (2000m)) AWG14 Control wiring between outdoor units Control wiring between indoor and outdoor units Control wiring between indoor units Remote control wiring 2-core with non-polarity wire is used for wiring of the remote control wiring and group remote controls wiring. Remote control wiring, remote control inter-unit wiring Wire size: AWG20 Ground Ground Ground Ground L1L2 U1U2 A B L1L2 U1U2 A B L1L2 U1U2 A B L1L2 U1U2 A B Total wire length of remote control wiring and remote control In case of wired type only inter-unit wiring = L + L1 + L2 + Ln In case of wireless type included Total wire length of remote control inter-unit wiring = L1 + L2 + Ln Remote control wiring L Remote control L1 L2 Remote control inter-unit wiring Ln (Max. 8 units) Up to (500m) Up to (400m) Up to (200m) Indoor power supply Disconnect switch per NEC 208/ Circuit breaker A B Remote control Disconnect switch per NEC A B Remote control Disconnect switch per NEC A B Remote control Disconnect switch per NEC The remote control wire (Communication line) and AC208/230V wires cannot be parallel to contact each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise or other factor. NOTE Use copper supply wire. Use UL wire rated 600V for the power supply. Use UL wire rated 300V for the remote control wires and control wires. EN 19-EN EN

12 21-EN 11 4-way Cassette type 4-way Cassette type 22-EN Wire connection Connect the wires matching the terminal numbers. Incorrect connection causes a trouble. Pass the control wires and remote control wires through the bushing of the indoor unit. The low-voltage circuit is provided for the control and remote control. (Do not connect the high-voltage circuit) Remove the cover of the electrical control box by taking off the mounting screws (2 positions) and pushing the hooking section. (The cover of the electrical control box remains hanged to the hinge.) Remove the 2 screws from the wire cover. Attach the conduit pipe to the conduit plate with a lock nut. Connect the power supply wires and control wiring and remote control wire to the terminal block of the electrical control box. Secure the ground wire with the ground screw. Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electrical control box. (Do not apply tension to the connecting section of the terminal block.) Mount the wire cover without catching the wires. (The wire cover should be mounted before the ceiling panel.) Mount the cover of the electrical control box without catching the wires. (Mount the cover after wiring on the ceiling panel.) Power supply wires and ground wire 1. Strip the wire ends. Power supply wire: 0.4 (10 mm) Ground wire: 0.8 (20 mm) 2. Match the wire colors with the terminal numbers on the indoor units and circuit breakers terminal blocks and firmly screw the wires to the corresponding terminals. 3. Secure the ground wire with the ground screw. 4. Fix the wires with a cord clamp. Unit: in (mm) 0.8 (20) 1.2 (30) Control wires Because a Wiring box has little space, a cover of control wires (2-core shielded wire) should be removed up to 5.9 (150mm). Ground screw for shielded wire (control wire) L1 L2 0.4 (10) Wiring box Ground wire Control wires (2-core shielded wire) Cover 5.5 (140) Shield wire Bushing of control and remote control wires Conduit pipe Conduit plate Piping Knockout Lock nut Side D (Space: 0.33 (8.5 mm)) Conduit connection hole Hinge Electrical control box cover Wire cover Side C (Space: 0.16 (4 mm)) Ground screw Screws at 2 positions Power supply terminal block L1 L2 Cord clamp Louver connector (CN510: White) Ground screw for shielded wire (control wire) U1 U2 A B Remote control terminal block Firmly tighten the screws of the terminal block. Keep the wire length as shown in figure below when it is connected to the terminal block. Power supply wires and control wire 0.08 (2) or less 5.9 (150) Address setup 0.4 (9) Set up the addresses as per the supplied with the outdoor unit. Wiring on the ceiling panel According to the of the ceiling panel, connect the connector (20P: White) of the ceiling panel to the connector (CN510: White) on P.C. board of the electrical control box. Insert the wire to Side C.

13 4-way Cassette type 4-way Cassette type 8 Applicable Controls When this air conditioner is used for the first time, it takes approx. 5 minutes until the remote control becomes available after power-on. This is normal. <When power is turned on for the first time after installation> It takes approx. 5 to 10 minutes until the remote control becomes available. Approx. 5 to 10 minutes Power on SETTING flashes SETTING goes out Remote control is available <When power is turned on for the second (or later) time> It takes approx. 3 to 10 minute until the remote control becomes available. Approx. 3 to 10 minutes Power on SETTING flashes SETTING goes out Remote control is available Normal settings were made as factory default. Change the indoor unit settings as required. Use the wired remote control to change the settings. * The settings cannot be changed using the wireless remote control, simple wired remote control, or central control system. Therefore, install the wired remote control to change the settings. Changing applicable control setting Basic procedure for changing settings Change the settings while the air conditioner is not working. (Stop the air conditioner before making settings.) Procedure 1 Push button and temp. setup button simultaneously for 4 seconds or more. After a while, the display flashes as shown in the figure. Confirm that the CODE No. is [01]. If the CODE No. is not [01], push button to erase the display content, and repeat the procedure from the beginning. (No operation of the remote control is accepted for a while after button is pushed.) (While air conditioners are operated under the group control, is displayed first. When button is pushed, the indoor unit number displayed following ALL is header unit.) Procedure 2 Each time button is pushed, indoor unit numbers in the control group change cyclically. Select the indoor unit to change settings for. The fan of the selected unit runs and the louvers start swinging. The indoor unit can be confirmed for which to change settings. 2 (* Display content varies with the indoor unit model.) Procedure 3 Specify CODE No. [ ] with temp. setup / buttons. Procedure 4 Select SET DATA [ ] with timer time / buttons. Procedure 5 Push button. When the display changes from flashing to lit, the setup is completed. To change settings of another indoor unit, repeat from Procedure 2. To change other settings of the selected indoor unit, repeat from Procedure 3. Use button to clear the settings. To make settings after button was pushed, repeat from Procedure 2. Procedure 6 When settings have been completed, push button to determine the settings. When button is pushed, SETTING flashes and then the display content disappears and the air conditioner enters the normal stop mode. (While SETTING is flashing, no operation of the remote control is accepted.) Installing indoor unit on high ceiling When an indoor unit is installed on a ceiling higher than the standard height, make the high-ceiling setting for fan speed adjustment. Follow to the basic operation procedure ( ). For the CODE No. in Procedure 3, specify [5d]. Select the SET DATA for Procedure 4 from the Height list of ceiling possible to be installed table on page 4 in this manual. Remote control-less setting Change the high-ceiling settings with the DIP switch on the receiver section P.C. board. For details, refer to the manual of the wireless remote control kit. The settings can also be changed with the switch on the indoor P.C. board. * However, once the setting is changed, setting to 0001 or 0003 is possible but setting to 0000 requires a SET DATA change to 0000 using the wired remote control (sold separately) with the normal switch setting (factory default). SW501-1 SW501-2 MCU(IC501) SW501-1 SW501-2 SET DATA High ceiling setting OFF OFF 0000 Standard (factory default) ON OFF 0001 High ceiling (1) OFF ON 0003 High ceiling (3) Restore the factory default To return the DIP switch settings to the factory default, set SW501-1 and SW501-2 to OFF, connect a separately sold wired remote control, and then set the data of CODE No. [5d] to EN 23-EN EN

14 25-EN 13 4-way Cassette type 4-way Cassette type 26-EN Filter sign setting According to the installation condition, the lighting time of the filter sign (Notification of filter cleaning) can be changed. Follow to the basic operation procedure ( ). For the CODE No. in Procedure 3, specify [01]. For the [Set data] in Procedure 4, select the SET DATA of filter sign lighting time from the following table. SET DATA Filter sign lighting time 0000 None H H (Factory default) H H To secure better effect of heating When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator or other device to circulate heat air near the ceiling. Follow to the basic operation procedure ( ). For the CODE No. in Procedure 3, specify [06]. For the set data in Procedure 4, select the SET DATA of shift value of detection temperature to be set up from the table below. SET DATA Detection temp shift value 0000 No shift F (+1 C) F (+2 C) (Factory default) F (+3 C) F (+4 C) F (+5 C) F (+6 C) Horizontal louver direction 1. Push and TEMP. buttons for at least four seconds when the air conditioner is not working. flashes. Indicates CODE No Select an indoor unit to be set by pushing button (left side of the button). number changes each time the button is pushed. 1-1 The fan of the selected unit runs and the louvers start swinging. 3. Change the CODE No. to 45 with TEMP. buttons. 4. Select louver direction setting with TIME buttons. SET DATA Not display Louver direction setting Smudge reducing position (Air direction to reduce ceiling contamination) Cold draft preventive position (Prevent cold draft) [Factory default] 5. Push button to check the setting. The display state changes from flashing to lighting, and the setting is fixed. 6. Push button to end the setting. * When the cold draft position is selected, ceiling contamination is less reduced. Swing mode 1. Push for four seconds or more when the air conditioner is not working. flashes. Indicates CODE No. F0. 2. Select an indoor unit to be set with (left side of the button). Each time the button is pushed, unit numbers change as follows: 1-1 Not display The fan of the selected unit runs and the louvers start swinging. 3. Select a swing mode with TIME buttons. SET DATA 1-2 SET DATA Swing of louvers 0001 Standard swing (Factory default) 0002 Dual swing 0003 Cycle swing Do not set the swing SET DATA to (This setting may cause a failure of the louvers.) About Dual swing Dual means that louvers 01 and 03 are directed and swing in one direction and louvers 02 and 04 are directed and swing in the opposite direction. (When louvers 01 and 03 are directed downward, louvers 02 and 04 are directed upward.) About Cycle swing The four louvers swing independently at respective timings. Refrigerant pipe Drain pipe Push button. 5. Push button to complete the setting.

15 4-way Cassette type 4-way Cassette type Louver lock (No swing) 1. Push (right side of the button) for four seconds or more when the air conditioner is not working. flashes. Indicates CODE No. F1. 2. Select an indoor unit to be set with (left side of the button). Each time the button is pushed, unit numbers change as follows: The fan of the selected unit runs and the louvers start swinging Select a louver to lock with TEMP. buttons. 4. Select the louver direction not to swing with TIME buttons. SET DATA (1) 0001 (4) (2) 0002 (5) 0005 * When (4) or (5) is selected, dew drop may occur during cooling mode. 5. Determine the setting by pushing button. When the setting has been determined, lights up. 6. Push button to complete the setting (SET DATA) 1-3 (3) 0003 Cancel louver lock Set the louver direction to 0000 of the louver lock setup procedure above. SET DATA 0000 When the setting is cancelled, goes out. Other operations are the same as those in Louver lock (No swing). Remote control sensor The temperature sensor of the indoor unit senses room temperature usually. Set the remote control sensor to sense the temperature around the remote control. Select items following the basic operation procedure ( ). Specify [32] for the CODE No. in Procedure 3. Select the following data for the SET DATA in Procedure 4. SET DATA Remote control sensor Not used (factory setting) When flashes, the remote control sensor is defective. Select the SET DATA [0000] (not used) or replace the remote control. Group control Used In a group control, a remote control can control up to maximum 8 units. The wired remote control only can control a group control. The wireless remote control is unavailable for this control. For wiring procedure and wires of the individual line (Identical refrigerant line) system, refer to Electric work in this Manual. Wiring between indoor units in a group is performed in the following procedure. Connect the indoor units by connecting the remote control wires from the remote control terminal blocks (A, B) of the indoor unit connected with a remote control to the remote control terminal blocks (A, B) of the other indoor unit. (Non-polarity) For address setup, refer to the attached to the outdoor unit. 9 Test Run Before test run Before turning on the circuit breaker, carry out the following procedure. 1) By using 500V-megger, check that resistance of 1MΩ or more exists between the terminal block L1 to L2 and the ground (grounding). If resistance of less than 1MΩ is detected, do not run the unit. 2) Check the valve of the outdoor unit being opened fully. To protect the compressor at activation time, leave power-on for 12 hours or more be for operating. Before starting a test run, be sure to set addresses following the supplied with the outdoor unit. Execute a test run Operate the unit with the remote control as usual. For the procedure of the operation, refer to the attached Owner s Manual. A forced test run can be executed in the following procedure even if the operation stops by thermo.-off. In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to the usual operation. Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices. Wired remote control 1,5 2, 4 3 Procedure 1 Push button for 4 seconds or more. [TEST] is displayed on the display part and the selection of mode in the test mode is permitted. Procedure 2 Push button. Procedure 3 Select the operation mode with button, [COOL] or [HEAT]. Do not run the air conditioner in a mode other than [COOL] or [HEAT]. The temperature controlling function does not work during test run. The detection of error is performed as usual. Procedure 4 After the test run, push button to stop a test run. (Display part is same as procedure 1.) Procedure 5 Push check button to cancel (release from) the test run mode. ([TEST] disappears on the display and the status returns to a normal.) EN 27-EN EN

16 29-EN 15 4-way Cassette type 4-way Cassette type 30-EN Wireless remote control Procedure 1 Turn on the power of the air conditioner. When power is turned on for the first time after installation, it takes approx. 5 minutes until the remote control becomes available. In the case of subsequent power-on, it takes approx. 1 minute until the remote control becomes available. Execute a test run after the predetermined time has passed. Procedure 2 Push ON/OFF button on the remote control, select [COOL] or [HEAT] with MODE button, and then select [HIGH] with FAN button. Procedure 3 Cooling test run Heating test run Set the temperature to 64 F Set the temperature to 86 F (18 C) with the temp. setup (30 C) with the temp. setup buttons. buttons. <Overview of test run operations using the wireless remote control> Cooling test run: ON/OFF 64 F (18 C) 66 F (19 C) 64 F (18 C) 66 F (19 C) 64 F (18 C) 66 F (19 C) 64 F (18 C) (test run) ON/OFF Heating test run: ON/OFF 86 F (30 C) 84 F (29 C) 86 F (30 C) 84 F (29 C) 86 F (30 C) 84 F (29 C) 86 F (30 C) (test run) ON/OFF Always select [HIGH] fan speed , 4, 5, 6 2,7 10Troubleshooting Confirmation and check When an error occurred in the air conditioner, the check code and the indoor appear on the display part of the remote control. The check code is only displayed during the operation. If the display disappears, operate the air conditioner according to the following Confirmation of error log for confirmation. Check code Indoor in which an error occurred The numbers in CODE No. indicate CODE No. [01] (latest) [04] (oldest). Do not push button because all the error log of the indoor unit will be deleted. Procedure 3 Push button to return to the usual display after confirmation. 1. Check the errors according to the above procedure. 2. Ask an authorized dealer or qualified service (maintenance) professional to repair or maintain the air conditioner. Procedure 4 Cooling test run After confirming a signal receiving sound beep immediately set the temperature to 66 F (19 C) with the temp. setup buttons. Procedure 5 Heating test run After confirming a signal receiving sound beep immediately set the temperature to 84 F (29 C) with the temp. setup buttons. Confirmation of error log When an error occurred on the air conditioner, the error log can be confirmed with the following procedure. (The error log is stored in memory up to 4 errors.) The log can be confirmed from both operating status and stop status. Cooling test run After confirming a signal receiving sound beep immediately set the temperature to 64 F (18 C) with the temp. setup buttons. Heating test run After confirming a signal receiving sound beep immediately set the temperature to 86 F (30 C) with the temp. setup buttons. Procedure 6 Repeat procedures Indicators Operation (green), Timer (green), and Ready (orange) in the wireless receiver section flash in approx. 10 seconds, and the air conditioner starts operation. If any of these indicators does not flash, repeat procedures 2 to 5. Procedure 7 Upon completion of the test run, push ON/OFF button to stop operation. 2 3 Procedure 1 Push and buttons simultaneously for 4 seconds or more, the following display appears. If [Service check] is displayed, the mode enters in the error log mode. [01: Order of error log] is displayed in CODE No. window. [Check code] is displayed in CHECK window. [ address in which an error occurred] is displayed in Unit No. 1 Procedure 2 Push button. The error log stored in memory is displayed in order.

17 4-way Cassette type 4-way Cassette type Check codes and parts to be checked Check method On the remote control (Wired remote control, Central control remote control) and the interface P.C. board of the outdoor unit (), a check display LCD (Remote control) or 7-segment display (on the outdoor interface P.C. board) to display the operation is provided. Therefore the operation status can be known. With this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the table below. Check code list The following list shows each check code. Find the check contents from the list according to part to be checked. To check from indoor remote control: See Wired remote control display in the list. To check from outdoor unit: See Outdoor 7-segment display in the list. To check from indoor unit with a wireless remote control: See Sensor block display of receiving unit in the list. Wired remote control display Check code Wireless remote control Outdoor 7-segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash IPDU : Intelligent Power Drive Unit : Lighting, : Flashing, : Goes off ALT. : Flashing is alternately when there are two flashing LED. SIM : Simultaneous flashing when there are two flashing LED. Check code name Judging device E01 Communication error between indoor and remote control Remote control (Detected at remote control side) E02 Remote control transmission error Remote control E03 E04 E06 E06 No. of indoor units in which sensor has been normally received Communication error between indoor and remote control (Detected at indoor side) Communication circuit error between indoor/ outdoor (Detected at indoor side) Decrease of No. of indoor units E07 Communication circuit error between indoor/ outdoor (Detected at outdoor side) E08 E08 Duplicated indoor addresses Duplicated indoor addresses Indoor / E09 Duplicated header remote controls Remote control E10 Communication error between indoor MCU Indoor E12 E12 01: Indoor/Outdoor communication 02: Communication between outdoor units Automatic address start error E15 E15 Indoor is nothing during automatic addressing E16 E16 00: Capacity over Capacity over / No. of connected indoor units 01 ~:No. of connected units E18 Communication error between indoor units Indoor E19 E19 00: Header is nothing Outdoor header units quantity error 02: Two or more header units E20 E20 01: Outdoor of other line connected 02: Indoor of other line connected Other line connected during automatic address E23 E23 Sending error in communication between outdoor units E25 E25 Duplicated follower outdoor addresses E26 No. of outdoor units which E26 received signal normally Decrease of No. of connected outdoor units E28 E28 Detected outdoor unit number Follower outdoor unit error Indoor Indoor Wired remote control display A3-IPDU Fan IPDU E31 E31 07 IPDU communication error A 0B 0C 0D 0E 0F : IPDU error F01 ALT Indoor TCJ sensor error Indoor F02 ALT Indoor TC2 sensor error Indoor F03 ALT Indoor TC1 sensor error Indoor F04 F04 ALT TD1 sensor error F05 F05 ALT TD2 sensor error F06 F06 TE1 sensor ALT TE1 sensor error TE2 sensor TE2 sensor error F07 F07 ALT TL sensor error F08 F08 ALT TO sensor error F10 ALT Indoor TA sensor error Indoor F12 F12 ALT TS1 sensor error F13 01: Comp. 1 side F13 02: Comp. 2 side ALT TH sensor error IPDU 03: Comp. 3 side F15 F15 ALT Outdoor temp. sensor miswiring (TE1, TL) F16 F16 ALT Outdoor pressure sensor miswiring (Pd, Ps) F22 F22 ALT TD3 error F23 F23 ALT Ps sensor error F24 F24 ALT Pd sensor error F29 SIM Indoor other error Indoor F31 F31 SIM Indoor EEPROM error H01 H02 H01 H02 01: Comp. 1 side 02: Comp. 2 side 03: Comp. 3 side 01: Comp. 1 side 02: Comp. 2 side 03: Comp. 3 side Compressor break down Compressor trouble (lock) H03 01: Comp. 1 side H03 02: Comp. 2 side Current detect circuit system error IPDU 03: Comp. 3 side H05 H05 TD1 miswiring H06 H06 Low pressure protective operation H07 H07 Oil level down detective protection H08 H08 Check code Wireless remote control Outdoor 7-segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash 01: TK1 sensor error 02: TK2 sensor error 03: TK3 sensor error 04: TK4 sensor error Check code name Oil level detective temp sensor error Judging device H15 H15 TD2 miswiring IPDU IPDU EN 31-EN EN

18 33-EN 17 4-way Cassette type 4-way Cassette type 34-EN Wired remote control display H16 H16 Check code Wireless remote control Outdoor 7-segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash 01: TK1 oil circuit system error 02: TK2 oil circuit system error 03: TK3 oil circuit system error 04: TK4 oil circuit system error Check code name Oil level detective circuit error Judging device H25 H25 TD3 miswiring L03 SIM Indoor center unit duplicated Indoor L04 L04 SIM Outdoor line address duplicated L05 SIM Duplicated indoor units with priority (Displayed in indoor unit with priority) L06 L06 No. of indoor units with priority SIM Duplicated indoor units with priority (Displayed in unit other than indoor unit with priority) L07 SIM Group line in individual indoor unit Indoor L08 L08 SIM Indoor group/address unset Indoor, L09 SIM Indoor capacity unset Indoor L10 L10 SIM Outdoor capacity unset L17 L17 SIM Outdoor unit model unmatch error L20 SIM Duplicated central control addresses Indoor L28 L28 SIM Over No. of connected outdoor units A3-IPDU Fan IPDU L29 L29 07 SIM No. of IPDU error A 0B 0C 0D 0E 0F : IPDU error Wired remote control display P18 P18 ALT Discharge temp. TD3 error P19 P19 Detected outdoor unit number ALT 4-way valve inverse error P20 P20 ALT High-pressure protective operation P22 P26 P29 0 :IGBT circuit 1 :Location detection circuit error 3 :Motor lock-up error 4 : Motor current was detected. C :Abnormal temperature was P22 D E P26 P29 detected by the TH sensor. :TH sensor error :Inverter DC voltage error (outdoor unit fan) Caution) Although letters 0 to F appear at locations indicated by, please ignore them. 01: Comp. 1 side 02: Comp. 2 side 03: Comp. 3 side 01: Comp. 1 side 02: Comp. 2 side 03: Comp. 3 side P31 P31 ALT Error detected by TCC-LINK central control device TCC-LINK : TOSHIBA Carrier Communication Link. ALT Outdoor fan IPDU error IPDU ALT G-TR short protection error IPDU ALT Comp position detective circuit system error IPDU Other indoor unit error (Group follower unit error) Check code Wireless remote control Wired remote Outdoor 7-segment display Sensor block display of receiving unit Check code name Judging device control display Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC-LINK central control device TCC-LINK C06 Receiving error in TCC-LINK central control device TCC-LINK C12 Batch alarm of general-purpose equipment control General-purpose interface equipment P30 Check code Wireless remote control Outdoor 7-segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash Check code name Differs according to error contents of unit with occurrence of alarm Group control branching unit error (L20 is displayed) Duplicated central control addresses Judging device Indoor TCC-LINK L30 L30 Detected indoor address SIM Indoor outside interlock Indoor L31 Extended I/C error P01 ALT Indoor fan motor error Indoor P03 P03 ALT Discharge temp. TD1 error 01: Comp. 1 side P04 P04 02: Comp. 2 side ALT High-pressure SW system operation IPDU 03: Comp. 3 side P05 00: Detected phase loss P05 01: Comp. 1 side 02: Comp. 2 side ALT Phase loss error/interruption of power supply Inverter DC voltage (Vdc) error 03: Comp. 3 side P07 01: Comp. 1 side P07 02: Comp. 2 side ALT Heat sink overheat error IPDU, 03: Comp. 3 side P10 P10 Detected indoor address ALT Indoor overflow error Indoor P12 ALT Indoor fan motor error Indoor P13 P13 ALT Outdoor liquid back detection error P15 01: TS condition P15 02: TD condition ALT Gas leak detection P17 P17 ALT Discharge temp. TD2 error

19 4-way Cassette type 4-way Cassette type WARNINGS ON REFRIGERANT LEAKAGE Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below. Total amount of refrigerant (lbs (kg)) Min. volume of the indoor unit installed room (ft 3 (m 3 )) Concentration limit (lbs/ft 3 (kg/m 3 )) Important NOTE 2 : The standards for minimum room volume are as follows. (1) No partition (shaded portion) (2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door). Outdoor unit Refrigerant piping (3) If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object. Refrigerant piping The concentration limit of R410A which is used in multi air conditioners is 0.019lbs/ft 3 (0.3kg/m 3 ). NOTE 1 : If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device. e.g., charged amount ((22lbs) 10kg) Outdoor unit e.g., charged amount (33lbs (15kg)) Room A Room B Room C Room D Room E Room F For the amount of charge in this example: The possible amount of leaked refrigerant gas in rooms A, B and C is 22lbs (10kg). The possible amount of leaked refrigerant gas in rooms D, E and F is 33lbs (15kg). Very small room Small room Medium room Large room Mechanical ventilation device - Gas leak detector Outdoor unit NOTE 3 : The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 8.9ft (2.7m) high) 48 Range below the density limit of d lbs/ft 3 (0.3kg/m 3 ) (countermeasures not 36 needed) Min. indoor floor area Range above the density limit of 0.019lbs/ft 3 (0.3kg/m 3 ) (countermeasures needed) Total amount of refrigerant lbs EN 35-EN 18

20 Confirmation of Indoor Unit Setup Prior to delivery to the customer, check the address and setup of the indoor unit, which has been installed in this time and fill the check sheet (Table below). Data of four units can be entered in this check sheet. Copy this sheet according to the No. of the indoor units. If the installed system is a group control system, use this sheet by entering each line system into each installation manual attached to the other indoor units. This check sheet is required for maintenance after installation. Fill this sheet and then pass this to the customers. setup check sheet Room name Room name Room name Room name Model Model Model Model Check indoor unit address. (For check method, refer to Applicable controls in this manual.) * In case of a single system, it is unnecessary to enter the indoor address. (CODE No.: Line [12], Indoor [13], Group [14], Central control [03] ) Line Indoor Group Line Indoor Group Line Indoor Group Line Indoor Group Central control address Central control address Central control address Central control address Various setup Various setup Various setup Various setup Have you changed high ceiling setup? If not, fill check mark [ ] in [NO CHANGE], and fill check mark [ ] in [ITEM] if changed, respectively. (For check method, refer to Applicable controls in this manual.) * In case of replacement of short plugs on indoor microcomputer P.C. board, setup is automatically changed. High ceiling setup (CODE No. [5d]) STANDARD [0000] HIGH CEILING 1 [0001] HIGH CEILING 2 [0003] High ceiling setup (CODE No. [5d]) STANDARD [0000] HIGH CEILING 1 [0001] HIGH CEILING 2 [0003] Have you changed lighting time of filter sign? If not, fill check mark [ ] in [NO CHANGE], and fill check mark [ ] in [ITEM] if changed, respectively. (For check method, refer to Applicable controls in this manual.) Filter sign lighting time (CODE No. [01]) NONE [0000] 150H [0001] 2500H [0002] 5000H [0003] 10000H [0004] Filter sign lighting time (CODE No. [01]) NONE [0000] 150H [0001] 2500H [0002] 5000H [0003] 10000H [0004] Have you changed detected temp. shift value? If not, fill check mark [ ] in [NO CHANGE], and fill check mark [ ] in [ITEM] if changed, respectively. (For check method, refer to Applicable control in this manual.) Detected temp. shift value setup (CODE No. [06]) NO SHIFT [0000] +1 C 1.8 F [0001] +2 C 3.6 F [0002] +3 C 5.4 F [0003] +4 C 7.2 F [0004] +5 C 9.0 F [0005] +6 C 10.8 F [0006] Detected temp. shift value setup (CODE No. [06]) NO SHIFT [0000] +1 C 1.8 F [0001] +2 C 3.6 F [0002] +3 C 5.4 F [0003] +4 C 7.2 F [0004] +5 C 9.0 F [0005] +6 C 10.8 F [0006] High ceiling setup (CODE No. [5d]) STANDARD [0000] HIGH CEILING 1 [0001] HIGH CEILING 2 [0003] Filter sign lighting time (CODE No. [01]) NONE [0000] 150H [0001] 2500H [0002] 5000H [0003] 10000H [0004] Detected temp. shift value setup (CODE No. [06]) NO SHIFT [0000] +1 C 1.8 F [0001] +2 C 3.6 F [0002] +3 C 5.4 F [0003] +4 C 7.2 F [0004] +5 C 9.0 F [0005] +6 C 10.8 F [0006] High ceiling setup (CODE No. [5d]) STANDARD [0000] HIGH CEILING 1 [0001] HIGH CEILING 2 [0003] Filter sign lighting time (CODE No. [01]) NONE [0000] 150H [0001] 2500H [0002] 5000H [0003] 10000H [0004] Detected temp. shift value setup (CODE No. [06]) NO SHIFT [0000] +1 C 1.8 F [0001] +2 C 3.6 F [0002] +3 C 5.4 F [0003] +4 C 7.2 F [0004] +5 C 9.0 F [0005] +6 C 10.8 F [0006] Incorporation of parts sold separately Incorporation of parts sold separately Incorporation of parts sold separately Incorporation of parts sold separately Have you incorporated the following parts sold separately? If incorporated, fill check mark [ ] in each [ITEM]. (When incorporating, the setup change is necessary in some cases. For setup change method, refer to attached to each part sold separately.) Panel Panel Panel Standard panel Standard panel Standard panel Others ( ) Others ( ) Others ( ) Others ( ) Others ( ) Others ( ) Standard panel Others ( ) Others ( ) Panel EH

Installation manual MMU-AP0071MH2UL MMU-AP0091MH2UL MMU-AP0121MH2UL MMU-AP0151MH2UL MMU-AP0181MH2UL AIR CONDITIONER (MULTI TYPE) Indoor Unit

Installation manual MMU-AP0071MH2UL MMU-AP0091MH2UL MMU-AP0121MH2UL MMU-AP0151MH2UL MMU-AP0181MH2UL AIR CONDITIONER (MULTI TYPE) Indoor Unit AIR CONDITIONER (MULTI TYPE) Installation manual Indoor Unit Model name: Compact 4-way Cassette type MMU-AP0071MH2UL MMU-AP0091MH2UL MMU-AP0121MH2UL MMU-AP0151MH2UL MMU-AP0181MH2UL Installation manual

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions

More information

Installation Manual MMD-AP0184H-E MMD-AP0244H-E MMD-AP0274H-E MMD-AP0364H-E MMD-AP0484H-E AIR CONDITIONER (MULTI TYPE) Indoor Unit.

Installation Manual MMD-AP0184H-E MMD-AP0244H-E MMD-AP0274H-E MMD-AP0364H-E MMD-AP0484H-E AIR CONDITIONER (MULTI TYPE) Indoor Unit. AIR CONDITIONER (MULTI TYPE) Indoor Unit Model name: Concealed Duct High Static Pressure Type MMD-AP0184H-E MMD-AP0244H-E MMD-AP0274H-E MMD-AP0364H-E MMD-AP0484H-E English SMMS Concealed Duct High Static

More information

AIR CONDITIONER (SPLIT TYPE) Installation Manual. Indoor Unit RAV-SM2242DT-E RAV-SM2802DT-E. Model name: Concealed Duct High Static Pressure Type

AIR CONDITIONER (SPLIT TYPE) Installation Manual. Indoor Unit RAV-SM2242DT-E RAV-SM2802DT-E. Model name: Concealed Duct High Static Pressure Type AIR CONDITIONER (SPLIT TYPE) Indoor Unit Model name: Concealed Duct High Static Pressure Type RAV-SM2242DT-E RAV-SM2802DT-E Air conditioner (Split type) 1 English Manuel d installation Climatiseur (Type

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,

More information

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into

More information

Installation manual. Branch kit 1:3 RBC-TRP100E AIR CONDITIONER (SPLIT TYPE) Model name: Installation manual. Air conditioner (Split type) 1 English

Installation manual. Branch kit 1:3 RBC-TRP100E AIR CONDITIONER (SPLIT TYPE) Model name: Installation manual. Air conditioner (Split type) 1 English AIR CONDITIONER (SPLIT TYPE) Installation manual Branch kit 1:3 Model name: RBC-TRP100E Installation manual Air conditioner (Split type) 1 English Manuel d installation Climatiseur (Type split) 24 Français

More information

AIR CONDITIONER (MULTI-SPLIT TYPE) Installation Manual. Indoor Unit. Model name:

AIR CONDITIONER (MULTI-SPLIT TYPE) Installation Manual. Indoor Unit. Model name: EG55760001-00 AIR CONDITIONER (MULTI-SPLIT TYPE) Installation Manual Indoor Unit Model name: RAS-M07G3DV Series RAS-M10G3DV Series RAS-M13G3DV Series RAS-M16G3DV Series English Español

More information

English DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL. Français. R410A Split Series. Español MODELS FTXS15LVJU FTXS18LVJU FTXS24LVJU

English DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL. Français. R410A Split Series. Español MODELS FTXS15LVJU FTXS18LVJU FTXS24LVJU English DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Español Français MODELS FTXS15LVJU FTXS18LVJU FTXS24LVJU Safety Precautions Read these Safety Precautions carefully to ensure

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

Floor Type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA. English

Floor Type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA. English Floor Type Air-Conditioner MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA INSTALLATION MANUAL This manual only describes the installation of indoor unit. When installing the outdoor unit, refer to the installation manual

More information

Ductless Split Air Conditioner

Ductless Split Air Conditioner Ductless Split Air Conditioner Installation Manual Indoor HSU09VHG(DB)-W HSU12VHG(DB)-W HSU18VHH(DB)-W HSU24VHG(DB)-W Outdoor HSU09VHG(DB)-G HSU12VHG(DB)-G HSU18VHH(DB)-G HSU24VHG(DB)-G Table of Contents

More information

Reverse Cycle Inverter Split System Air Conditioner

Reverse Cycle Inverter Split System Air Conditioner Reverse Cycle Inverter Split System Air Conditioner Model Number TAC-09CHSA/JAI5 INSTALLATION MANUAL Contents 03 Warranty Details 04 Welcome 05 General Safety Instructions 06 Product Overview 07 Selecting

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL FRANCAIS ESPAÑOL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring

More information

ROOM AIR CONDITIONER INSTALLATION MANUAL

ROOM AIR CONDITIONER INSTALLATION MANUAL ROOM AIR CONDITIONER INSTALLATION MANUAL ( Split Type) Please read this installation manual completely before installing the product When the power cord is damaged, replacement work shall be performed

More information

CEILING CASSETTE FAN COIL UNIT

CEILING CASSETTE FAN COIL UNIT CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and

More information

OPTIONAL SLENDER REMOTE CONTROL

OPTIONAL SLENDER REMOTE CONTROL DAIKIN ROOM AIR CONDITIONER Operation Manual OPTIONAL SLENDER REMOTE CONTROL BRC944A2B READ BEFORE OPERATION Safety Precautions...2 Names of Functions of Parts...4 Preparation before Operation...5 OPERATION

More information

Split Type Room Air Conditioner. KSWM units

Split Type Room Air Conditioner. KSWM units OWNER S MANUAL Split Type Room Air Conditioner KSWM units Please read the operating instructions and safety precautions carefully and thoroughly before installing and operating your room air conditioner.

More information

Instruction manual for Firstline FCS12000CH

Instruction manual for Firstline FCS12000CH Instruction manual for Firstline FCS12000CH Contents Introduction... 2 Safety Awareness... 3 Safety Awareness... 4 Name of Parts... 5 Name of Parts... 6 Remote Controller Preparation... 7 Operation of

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Céliera Corporation. All rights reserved. Unauthorized duplication, reproduction prohibited. CONTENTS SAFETY PRECAUTIONS...

More information

Cooktop Low-Profile Ventilation Hoods

Cooktop Low-Profile Ventilation Hoods INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............

More information

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner

More information

AIR CONDITIONER (SPLIT TYPE) Installation manual. Outdoor Unit. English. Model name:

AIR CONDITIONER (SPLIT TYPE) Installation manual. Outdoor Unit. English. Model name: AIR CONDITIONER (SPLIT TYPE) Installation manual Outdoor Unit Model name: RAV-SM2244AT7 RAV-SM2244AT7Z RAV-SM2244AT7ZG RAV-SM2244AT8-E RAV-SM2244AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT7 RAV-SM2804AT7Z RAV-SM2804AT7ZG

More information

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

Owner s Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E. Model name:

Owner s Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E. Model name: AIR CONDITIONER (SPLIT TYPE) Indoor Unit Not accessible to the general public Model name: 4-way Air Discharge Cassette Type RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E Air conditioner (Split

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA USER S MANUAL FH052EAV1 FH070EAV1 E HNIKA PORTUGUÊS ENGLISH ESPAÑOL ITALIANO DEUTSCH FRANÇAIS System Air Conditioner (Cooling and Heating) E S F I P D G DB98-29263A(1) Safety Precautions Register your

More information

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with

More information

RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM1604UT-E

RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM1604UT-E AIR CONDITIONER (SPLIT TYPE) Owner s Manual Indoor Unit Model name: For commercial use 4-way Cassette Type RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM1604UT-E Owner s Manual English

More information

SYSTEM Inverter Air Conditioners

SYSTEM Inverter Air Conditioners OPERATION MANUAL SYSTEM Inverter Air Conditioners MODEL Ceiling Suspended type FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU Read these instructions carefully before installation. Keep this manual in a handy place

More information

USER S MANUAL. Duct Type Series. Free Joint Multi Air Conditioner (Cooling and Heating) FUEA Series E S F I P D G DB98-29565A(1) ENGLISH ESPAÑOL

USER S MANUAL. Duct Type Series. Free Joint Multi Air Conditioner (Cooling and Heating) FUEA Series E S F I P D G DB98-29565A(1) ENGLISH ESPAÑOL USER S MANUAL Duct Type Series MH MH FEEA Series FUEA Series ENGLISH ESPAÑOL PORTUGUÊS E HNIKA DEUTSCH ITALIANO FRANÇAIS Free Joint Multi Air Conditioner (Cooling and Heating) E S F I P D G DB98-29565A(1)

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug

More information

AIR CONDITIONER OUTDOOR UNIT

AIR CONDITIONER OUTDOOR UNIT AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL For authorized personnel only. MANUEL D'INSTALLATION Pour le personnel agréé uniquement. English Français MANUAL DE INSTALACIÓN Solo para personal autorizado.

More information

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE

More information

1. BEFORE INSTALLATION

1. BEFORE INSTALLATION ENGLISH SPLIT-TYPE AIR CONDITIONERS INSTALLATION MANUAL JG79A191H03 MSZ-GE06/09/12/15/18NA MSY-GE09/12/15/18NA When installing multi units, refer to the installation manual of the multi unit for outdoor

More information

CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS

CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS Please read this instruction sheet completely before installing the product. When the power cord is damaged, replacement work should be

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table

More information

Packaged Terminal Air Conditioner Wall Sleeve Installation

Packaged Terminal Air Conditioner Wall Sleeve Installation Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation

More information

Split Air Conditioner

Split Air Conditioner Split Air Conditioner Thank you for choosing our product. For proper operation, please read and keep this manual carefully. If you have lost the Owner s Manual, please contact the local agent or visit

More information

LUCCI AIRFUSION QUEST II CEILING FAN

LUCCI AIRFUSION QUEST II CEILING FAN LUCCI AIRFUSION QUEST II CEILING FAN WITH IR REMOTE INSTALLATION OPERATION MAINTENANCE WARRANTY INFORMATION CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. V1.0 QUEST II IR

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS

CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS CEILING CASSETTE TYPE AIR CONDITIONERS INSTALLATION INSTRUCTIONS (Refrigerant : R-407C) This unit is charged with new refrigerant, R-407C. Be sure to use proper tools for R-407C, when installing the unit.

More information

Installation Instructions

Installation Instructions CNPVU CNRVU Uncased Coils Upflow - Downflow Heating - Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET

SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET (PART NO. 97474700) For authorized service personnel only. This installation instruction sheet describes how to install the outdoor unit only.

More information

RAV-SP404ATP-E RAV-SP454ATP-E RAV-SP564ATP-E RAV-SP564ATJP-E

RAV-SP404ATP-E RAV-SP454ATP-E RAV-SP564ATP-E RAV-SP564ATJP-E AIR CONDITIONER (SPLIT TYPE) Installation manual Outdoor Unit For commercial use Model name: RAV-SP404ATP-E RAV-SP454ATP-E RAV-SP564ATP-E RAV-SP564ATJP-E English - 1 - Original instruction Please read

More information

PORTABLE AIR CONDITIONER

PORTABLE AIR CONDITIONER PORTABLE AIR CONDITIONER MAC 7500 Owner s Manual Air Conditioner Dehumidifier Oscillating Fan Please read this owner s manual carefully before operating the unit. POWERED BY 66126113.p65 17 INTRODUCTION

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by

More information

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual Instruction Manual OPC-LM1-IL Option Card for Encoder of Line Driver Output CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual

More information

Accessory Manual Ventilation Section Model Comfort Circle

Accessory Manual Ventilation Section Model Comfort Circle Accessory Manual Ventilation Section Model Comfort Circle Manual version:. R a Copyright and trademarks All the information and drawings in this manual are the property of Biddle and may not be used (other

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102

USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 USER INSTRUCTIONS FOR 10 LITRE PORTABLE DEHUMIDIFIER MODEL NO. DHMD102 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE

More information

Refrigeration Installation 101

Refrigeration Installation 101 Refrigeration Installation 101 Hundreds of Installations Refrigerated Cases 2 Compressor Racks 3 Condensing Units 4 Walk-in Boxes 5 Some were done very well 6 Some had some issues... 7 8 Some seemingly

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

AIR CONDITIONER OUTDOOR UNIT

AIR CONDITIONER OUTDOOR UNIT AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL For authorized personnel only. MANUEL D'INSTALLATION Pour le personnel agréé uniquement. English Français MANUAL DE INSTALACIÓN Solo para personal autorizado.

More information

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and

More information

OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)

OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type) OPERATION MANUAL (Ceiling mounted duct type) VAM50FB VAM500FB VAM650FB VAM800FB VAM000FB VAM500FB VAM000FB 8 7 6 9 5 7 5 0 6 8 6 9 0 5 5 7 7 6 7 A A B B 5 6 5 6 7 VAM50F VAM800F VAM500F VAM500F VAM000F

More information

Dehumidifier Users manual. For Models: DH45S DH65S

Dehumidifier Users manual. For Models: DH45S DH65S Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but

More information

CEILING CASSETTE DUCTLESS SYSTEM

CEILING CASSETTE DUCTLESS SYSTEM CEILING CASSETTE DUCTLESS SYSTEM INSTALLATION MANUAL Models: CAS12HP230V1AC -12,000 BTUH CAS18HP230V1AC -18,000 BTUH CAS24HP230V1AC - 24,000 BTUH Thank you for choosing the Gree Ceiling Cassette for your

More information

Power supply unit Model: PAC-SC50KUA

Power supply unit Model: PAC-SC50KUA Building Air Conditioning Control System Power supply unit Model: PAC-SC50KUA Installation Manual Contents 1. Safety precautions... 1 2. Product feature... 2 1. Specification... 2 2. Appearance... 2 3.

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support

More information

Operating Instructions Air Conditioner

Operating Instructions Air Conditioner F566272 Operating Instructions Air Conditioner CS-C18FFH CS-C28FFH CU-C18FFH CU-C28FFH ENGLISH Before operating the unit, read these operating instructions thoroughly and keep them for future reference.

More information

Installation Instructions

Installation Instructions Installation Instructions Accessory Ultraviolet (UV) Germicidal Lamp 1 & 2 Lamp Models 115-v & 208/230-v UV Lamp C03009 Fig. 1 Two Lamp Model UV Lamp NOTE: Read the entire instruction manual before starting

More information

AIR CONDITIONER (MULTI TYPE) Installation Manual. Outdoor Unit

AIR CONDITIONER (MULTI TYPE) Installation Manual. Outdoor Unit AIR CONDITIONER (MULTI TYPE) Installation Manual Outdoor Unit Model name: For commercial use MMY-MAP0806HT8P-E MMY-MAP1006HT8P-E MMY-MAP1206HT8P-E MMY-MAP1406HT8P-E

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer

More information

Hi Wall Split Air Conditioners

Hi Wall Split Air Conditioners R22 220-240V ~, 50Hz Hi Wall Split Air Conditioners 53KHET 12-18-24 Cool Only 53QHET 12-18-24 Heat Pump INSTALLATION MANUAL Carrier is committed to continuously improving its products according to national

More information

LG Floor Standing Type Air Conditioner INSTALLATION MANUAL

LG Floor Standing Type Air Conditioner INSTALLATION MANUAL website http://www.lgservice.com e-mail http://www.lgeservice.com/techsup.html LG Floor Standing Type Air Conditioner INSTALLATION MANUAL LG IMPORTANT Please read this installation manual completely before

More information

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump R-410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H)-System, DFC4(A/H)3-Outdoor, DFF4(A/H)H-Indoor Please read the operating instructions and safety precautions carefully

More information

Cooling system components, removing and installing

Cooling system components, removing and installing Engine BHW Cooling system components, removing and installing Page 1 / 24 19-1 Cooling system components, removing and installing Warning! When doing any repair work, especially in the engine compartment,

More information

SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL

SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL Thank you for choosing our Air Conditioner. Please read this OWNER'S MANUAL carefully prior to use and keep it for further reference. CONTENTS Contents

More information

DAIKIN ROOM AIR CONDITIONER FT50BSG FT60BSG MODELS. Operation Manual

DAIKIN ROOM AIR CONDITIONER FT50BSG FT60BSG MODELS. Operation Manual DAIKIN ROOM AIR CONDITIONER Operation Manual MODELS FT50BSG FT60BSG CONTENTS READ BEFORE OPERATION Safety Precautions... 2 Names of Parts Indoor unit, Opening the front grille... 5 Remote controller, Outdoor

More information

Room Air Conditioners

Room Air Conditioners User Manual Room Air Conditioners R410A Split Type Y Series DC INVERTER ECO940SD ECO120SD ECO1840SD Please read this installation manual completely before installing the product. When the power cord is

More information

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex Version C Single, Dual, Tri or Quad Zone Ductless Mini-Split System Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

Important Safeguards

Important Safeguards Table of Contents Important Safeguards...2 Product Layout...3 Preparing for Use...4 Air-conditioning without installation...4 Air-conditioning with installation...5 Control Panel...6 Operating from the

More information

SPLIT -TYPE ROOM AIR CONDITIONER

SPLIT -TYPE ROOM AIR CONDITIONER Before using your air conditioner, please read this manual carefully and keep it for future reference SPLIT -TYPE ROOM AIR CONDITIONER Please read this installation manual completely before installing

More information

Wall Mounted Mini Split Heat Pump Air Conditioner

Wall Mounted Mini Split Heat Pump Air Conditioner Wall Mounted Mini Split Heat Pump Air Conditioner OPERATING AND INSTALLATION MANUAL Model: KFIHP-09-ID / KFHIP-09-OD KFHHP-12-ID / KFHHP-12-OD Indoor Unit. Outdoor Unit. Thank you for selecting Soleus

More information

AIR CONDITIONER (SPLIT TYPE)

AIR CONDITIONER (SPLIT TYPE) INSTALLATION MANUAL AIR CONDITIONER (SPLIT TYPE) For general public use ENGLISH EN Indoor Unit RAS-07PKVP-E RAS-10PKVP-E RAS-13PKVP-E RAS-16PKVP-E RAS-18PKVP-E RAS-07PKVP-ND RAS-10PKVP-ND RAS-13PKVP-ND

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477

More information

Installation manual AIR CONDITIONER (SPLIT TYPE) Outdoor Unit

Installation manual AIR CONDITIONER (SPLIT TYPE) Outdoor Unit AIR CONDITIONER (SPLIT TYPE) Installation manual Outdoor Unit Model name: RAV-SP1104AT8-E RAV-SP1104AT8Z-E RAV-SP1104AT8ZG-E RAV-SP1404AT8-E RAV-SP1404AT8Z-E RAV-SP1404AT8ZG-E RAV-SP1604AT8-E RAV-SP1604AT8Z-E

More information

CENTRAL AIR CONDITIONER SPLIT SYSTEM

CENTRAL AIR CONDITIONER SPLIT SYSTEM CENTRAL AIR CONDITIONER SPLIT SYSTEM WITH ELECTRONIC CONTROL SERIES BS BS 30E BS 36 BS 43 INSTALLATION INSTRUCTIONS SUMMARY GENERAL...3 SELECTING THE LOCATION OF UNITS...5 RELATIVE LOCATION OF THE UNITS...5

More information

CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual

CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual Instruction Manual Option Card for Frequency Divider Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual and understand the description

More information

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split Multi System 16 SEER, Inverter System 9,000 to 18,000 BTU/Hr Single Split 4MXW8-A 4TXM6-A March2013 42 Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate

More information

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS

CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS CORNER FRIDGE REFRIGERATION UNIT INSTALLATION AND OPERATION INSTRUCTIONS D E F Y I N G C O N V E N T I O N Congratulations on your new Corner Fridge Your new corner fridge may have different functions

More information

Ceiling Fan Installation Instructions

Ceiling Fan Installation Instructions Ceiling Fan Installation Instructions 1525..series OWNER S MANUAL READ AND SAVE THESE INSTRUCTIONS Total fan wieght with light kit 1-1525-CUL-English INSTALLATION CH-545 Safety Tips WARNING: TO REDUCE

More information

R410A SPLIT SERIES DC INVERTER

R410A SPLIT SERIES DC INVERTER R40A SPLIT SERIES DC INVERTER Models ECO905SINV ECO205SINV ECO805SINV Read This Manual Inside you will find many helpful hints on how to use and maintain your air conditioner properly. Just a little preventative

More information

CAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN

CAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN BeoLab 4000 Guide CAUTION RISK OF ELECTRIC SHOCK DO NOT OPEN CAUTION: To reduce the risk of electric shock, do not remove cover (or back). No User-serviceable parts inside. Refer servicing to qualified

More information

AerAtron. Ceiling fans

AerAtron. Ceiling fans AerAtron Ceiling fans User Manual & Technical Specifications Models: e502 & e503 Electricians PLEASE FOLLOW THESES INSTRUCTIONS CAREFULLY & PAY SPECIAL ATTENTION TO THE NOTES NOTES WILL ASSIST WITH AN

More information

758 Heavy-duty Ratchet Guy Wire Cutter

758 Heavy-duty Ratchet Guy Wire Cutter INSTRUCTION MANUAL 758 Heavy-duty Ratchet Guy Wire Cutter Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Register this product

More information

15GAL STEEL OIL DRAIN WITH 110V PUMP

15GAL STEEL OIL DRAIN WITH 110V PUMP 15GAL STEEL OIL DRAIN WITH 110V PUMP OWNER S MANUAL WARNING: Read carefully and understand all ASSEMBLY AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety

More information

Table of Contents. www.hunterfan.com. What to Expect with. Preparation. Tools Needed. Wiring. Hanging the Fan. Blades. Motor Housing.

Table of Contents. www.hunterfan.com. What to Expect with. Preparation. Tools Needed. Wiring. Hanging the Fan. Blades. Motor Housing. www.hunterfan.com Table of Contents What to Expect with Your Installation 30 inches Hanging the Fan Wiring 8 Maintenance, Operation & Cleaning Light Kit 13??? 14 1 9 Troubleshooting 11 5 Blades Motor Housing

More information

PORTABLE AIR CONDITIONER

PORTABLE AIR CONDITIONER VERY IMPORTANT! MODEL: GDC-AC9RW / GDC-AC9RCS GDC-AC9RCW / GDC-AC12RW GDC-AC12RB / GDC-AC12RCB GDC-AC12RCW INSTRUCTIONS FOR USE PORTABLE AIR CONDITIONER Do not install and use your portable air conditioner

More information

HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL

HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL Models: CROWN09HP230V1A CROWN12HP230V1A CROWN18HP230V1A Thank you for choosing a Crown High-Wall Unit for your customer. Please

More information

AIR CONDITIONER (SPLIT TYPE)

AIR CONDITIONER (SPLIT TYPE) OWNER S MANUAL AIR CONDITIONER (SPLIT TYPE) For general public use ENGLISH EN Indoor Unit RAS-07PKVP-E RAS-10PKVP-E RAS-13PKVP-E RAS-16PKVP-E RAS-18PKVP-E RAS-07PKVP-ND RAS-10PKVP-ND RAS-13PKVP-ND RAS-16PKVP-ND

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL

DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL Service Information If service or parts are required, contact the nearest Norcold Service Center. To find an authorized Norcold Service Center

More information

AerAtron. Ceiling fans

AerAtron. Ceiling fans AerAtron Ceiling fans User Manual & Technical Specifications Models: e502 & e503 Australian edition 2011 Instructions...3 General precautions...3 Location and installation requirements for your fan...3

More information