5.0 Reference: Application, Volume I, Chapter 5, Heritage Contract
|
|
- Baldwin Sims
- 7 years ago
- Views:
Transcription
1 1 5.0 Reference: Application, Volume I, Chapter 5, Heritage Contract : Provide a comprehensive explanation of the application of the Equipment Health Rating process to transformers and generators and provide examples of the output and how it has been used. RESPONSE: Equipment Health Rating (EHR) is an objective, repeatable equipment health evaluation system. EHR enables comparison of the health of BC Hydro generation assets. EHR has been developed to evaluate the following types of equipment: generators, exciters, turbines, governors, unit circuit breakers, unit transformers and coatings. Evaluation of the health criteria and test and inspection data is completed by a team of asset specialists. The EHR system uses test and inspection data and other information to determine the condition or health of assets. The result is a technical evaluation of the asset resulting in a letter grade; Good, Fair, Poor, Unsatisfactory (G,F,P,U), as follows: Good no noticeable deterioration/defects; Fair some deterioration/defects exist (function not affected); Poor serious deterioration/defects exist in at least some portions of the asset (function affected); and Unsatisfactory extensive deterioration/defects (no longer functions as required). In addition, the EHR process includes a "technical prescription" which is BC Hydro's asset specialists' recommendations on what needs to be done to restore the asset to Good condition, including a cost estimate and time period in which the work should be completed. This identifies future expenditures. The technical prescription details the following: What? the intervention recommendation (e.g. replacement); When? the intervention timing (e.g. 2 to 5 years); Cost? a budget estimate of the intervention cost; How Long? an estimate of the time required to implement the intervention; and Benefits a high level description of the benefits of the intervention.
2 2 The EHR results, along with economic, environmental and social risks are used to assess and prioritize investments. The Latent Risk Matrix shown below is used as a tool for investment prioritization.
3 4
4 5 The following examples illustrate the application of EHR for: GM Shrum unit transformers; and Mica generators. Example 1. GM Shrum Unit Transformers The EHR for assessing the condition of transformers includes the following criteria, and test and inspection data: 1. Age Gas in Oil Analysis Winding Insulation Megger Reading Winding Doble Power Factor Reading Furan Analysis Moisture Content. Bushing Doble Power Factor Test. Insulating Oil kv Breakdown Insulating Oil Power Factor (100 deg C) Insulating Oil Interfacial Tension Insulating Oil Moisture Content. Tank Surface Defects and Leaks 3. Known Problems The results for GM Shrum T1 B-Phase Unit Transformer are as follows: 1. Age The transformer is approximately 35 years old. The Gas in Oil Analysis indicates that the transformer paper insulation is overheating leading to premature failure. The Bushing Doble Power Factor Test indicates that the high voltage C1 bushing power factor is high indicating that insulation has deteriorated reducing the overall transformer performance. The Furan Analysis indicates that the paper insulation is ageing. The Moisture Content tests were not conclusive, indicating uncertainty with this particular test.
5 6 3. Known Problems This transformer suffers from a severe known problem of low voltage lead overheating. As a result, the most significant health measures indicated that the transformer is in "Unsatisfactory" condition and the technical prescription included a recommendation to replace the transformer. Replacement of the GM Shrum unit transformers rated "Unsatisfactory" is in progress. Example 2. Mica Generators The Equipment Health Rating for assessing the condition of generators includes the following criteria, and test and inspection data: 1. Forced Outages Stator Winding Insulation Resistance and Polarization Index Test Stator Winding High-Voltage Direct-Current Step Test Stator Winding Partial Discharge Test Rotor Winding Insulation Resistance and Polarization Index Test Rotor Pole Drop Test Stator Winding, Core and Support Inspection Rotor Winding, Core and Support Inspection 3. Trends of Condition Index Tests and Inspections 4. Age compared to industry life expectancy 5. Design 6. Spare Parts Availability 7. Technical Support 8. Safety 9. Environmental
6 7 The results for Mica Unit 4 Generator are as follows: 1. Forced Outages Mica Unit 4 has suffered four significant forced outages primarily due to core related problems. In particular, moving laminations cut into the stator winding insulation causing failures. On a number of occasions similar problems were discovered during inspections and were repaired prior to a failure occurring. Stator Winding High-Voltage Direct-Current Step Test results identify weaknesses in the stator winding insulation system. The winding insulation system has failed during tests because of weakness caused by moving laminations. Stator Winding Partial Discharge tests show that the stator winding continues to age at a faster than normal rate. Rotor tests show that the rotor is considered to be in acceptable and expected condition for its age and operation. Inspection of the stator core studs since commissioning has revealed core waves and lamination movement. A core stud was found to be broken during a routine maintenance inspection. Subsequent tests devised by Powertech Labs have identified and quantified core stud cracking. The stud cracking is a considered to be a significant problem and is caused by fatigue. Unit G4 also has a particular problem with the lower stator core laminations migrating radially inward cutting into the winding insulation. 4. Age The generator was commissioned in Design Stator core waves, lamination movement, and stud cracking are directly related to the generator design. This was verified by the Mica Stator Advisory Board Report dated 04 Dec As a result, the most significant health measures indicated that the generator is in "Unsatisfactory" condition and the technical prescription included a recommendation to replace the generator stator.
7 8 The replacement of Mica Unit 4 Stator is listed in Chapter 11, 11-12, Table Note that the reference in the table is incorrectly labelled as Mica Units 1 to 4 Stator Replacement instead of Mica Unit 4 Stator Replacement.
Hydro Plant Risk Assessment Guide
September 2006 Hydro Plant Risk Assessment Guide Appendix E5: Transformer Condition Assessment E5.1 GENERAL Power transformers are key components in the power train at hydroelectric powerplants and are
More informationElectrical Maintenance Workshop
Electrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003 Transformer Maintenance & Testing Purpose This presentation provides an overview of the major considerations
More informationEXPERIENCE AND BENEFIT OF USING EL-CID FOR TURBINE-GENERATORS
EXPERIENCE AND BENEFIT OF USING EL-CID FOR TURBINE-GENERATORS Electric Power Research Institute Motor & Generator Predictive Maintenance & Refurbishment Conference Orlando, Florida November 28-30, 1995
More informationEnhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
More informationPower transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission
Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up
More informationVision 2050 An Asset Management Strategy. Jaclyn Cantler Manager, Transmission Planning, PHI
1 Vision 2050 An Asset Management Strategy Jaclyn Cantler Manager, Transmission Planning, PHI 2 Agenda Case for Change About Vision 2050 Status Closing System Design Cybersecurity Interface with distributed/dispersed
More informationTransformer Fleet Management with e-terraassetcare
Transformer Fleet Management with e-terraassetcare Jean-Michel AGNIER jean-michel.agnier@alstom.com Alstom-Grid - http://www.alstom.com/ Asset Management Development Director Alstom Group Thermal Power
More informationGenerator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
More informationDC MOTOR ANALYSIS & TROUBLESHOOTING
DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,
More informationOn-line PD Monitoring Makes Good Business Sense
On-line PD Monitoring Makes Good Business Sense An essential tool for asset managers to ensure reliable operation, improve maintenance efficiency and to extend the life of their electrical assets. Executive
More informationTHE VALUE OF POWER FACTOR TESTING
THE VALUE OF POWER FACTOR TESTING Nov 1, 2005 12:00 PM by John Bleyer and Phillip Prout, National Grid NATIONAL GRID DISCOVERED A HIGH POWER FACTOR DURING ACCEPTANCE TESTING of a new 40-MVA transformer
More informationMicalastic insulation for high voltage hydro generators
Micalastic insulation for high voltage hydro generators Voith Hydro is a global leader in hydro power equipment and services for both new and modernization. For more than 140 years, our name has been synonymous
More informationPower-factor testing of rotating machinery is another valuable test
Feature Power-Factor Testing of Stator Winding Insulation: Understanding the Test Technique and Interpretation of Results Power-factor testing of rotating machinery is another valuable test technique providing
More informationTurbine Optimization Programs to Extend Outage Periods and Manage Equipment Breakdown Risk
Turbine Optimization Programs to Extend Outage Periods and Manage Equipment Breakdown Risk by John A. Latcovich, Jr. Fleet Manager, Rotating Equipment The Hartford Steam Boiler Inspection and Insurance
More informationGE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry
GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry Brian Sparling, SMIEEE GridTech 2007, Delhi February 5-6, 2007 The
More informationBasics of Electricity
Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components
More informationCONTINUOUS AUTOMATED FLUX MONITORING FOR TURBINE GENERATOR ROTOR CONDITION ASSESSMENT
CONTINUOUS AUTOMATED FLUX MONITORING FOR TURBINE GENERATOR ROTOR CONDITION ASSESSMENT Abstract J. Kapler, S. Campbell, M. Credland Iris Power Engineering Inc. Toronto, Canada Flux monitoring via permanently
More informationSYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.
More informationRCP2 Portfolio Overview Document
RCP2 Portfolio Overview Document Portfolio: Expenditure Class: Base Capex Expenditure Category: Grid Replacement & Refurbishment As at date: 15 November 2013 Expenditure Forecast Real 2012/13 NZ$ (m) 2015-2016
More informationESCOM BY G.KALINDE SUBSTATIONS ENGINEER
ESCOM BY G.KALINDE SUBSTATIONS ENGINEER Balance Shareholder and Customer Interests Balance Short and Long Term Serviceability Understand trade-offs between Value and Risk Apply Asset Management Tools Build
More informationDISTRIBUTION OPERATIONS AND MAINTENANCE
EB-00-00 Filed: 00 Aug Page of DISTRIBUTION OPERATIONS AND MAINTENANCE PREVENTIVE MAINTENANCE Preventive Maintenance is intended to maintain or improve customer service reliability, extend equipment life
More informationOnline Hydro Machinery Monitoring Protection, Prediction and Performance Monitoring Solutions
Online Hydro Machinery Monitoring Protection, Prediction and Performance Monitoring Solutions 2011, Emerson Process Management. The contents of this publication are presented for informational purposes
More informationAPS Substation Maintenance. October 8, 2009
APS Substation Maintenance October 8, 2009 Substation Criticality Ranking Criticality Ranking Tiers Equipment ranked by access, consequence, replacement cost, replacement time, redundancy, safety, and
More informationWet Stator Units for Oil and Gas Upgrade and support services
Wet Stator Units for Oil and Gas Upgrade and support services Electro-submersible Pump Maintenance Sulzer has the in-house capability to provide specialist service support to the upstream oil and gas industry
More informationMonitoring, Diagnostics, or Changing Condition?
PTPiREE Conference May 12 14 th 2015, Gdansk Poland Monitoring, Diagnostics, or Changing Condition? Mark Tostrud, PE Brian D. Sparling, SMIEEE Ty A. Foren, MBA Dynamic Ratings Inc. Globally, the fundamental
More informationService Power Technologies. Retrofitting A future-oriented concept in lifecycle management
Retrofitting A future-oriented concept in lifecycle management Retrofit solutions for gas-insulated switchgear > 50 kv to 170 kv ABB-supplied high-voltage substations generally have a service life of approx.
More informationPractical Transformers: Operation, Maintenance and Testing
Practical Transformers: Operation, Maintenance and Testing YOU WILL GAIN: 4 hour live, practical online course Saturday, 2 nd May, 2015 8.00AM WST; 10.00AM AEST An understanding of the fundamental theory
More informationFAULT FINDING MANUAL. For Stamford AC Generators
FAULT FINDING MANUAL For Stamford AC Generators 1 SAFETY PRECAUTIONS Test procedures recommended in this manual assume that the reader is fully conversant with electrical safety principles, and is familiar
More information. Failure. Analysis... Report...
. Failure. Analysis... Report..... for (Generation Company) (Station) Purchase Order Number XXXX (Dated XX/XX/XXXX) Report N-XXXX-FA, Revision 0 Schulz Electric Company Job Number N-XXXX Motor ID Number
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
More informationA S Y N C H R O N O U S M O T O R S
ASYNCHRONOUS M O T O R S S E R I E S INDAR ASYNCHRONOUS MOTORS S E R I E S WHO WE ARE Indar Electric s trajectory is endorsed by the construction of thousands of motors for the different industrial sectors.
More informationDGA - Method in the Past and for the Future
DGA - Method in the Past and for the Future Page 2 May 2012 1970 1973 Doerenburg introduced the differentiation between electrical and thermal failure mode and introduced ratios for fault gases with similar
More information4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152
4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING HI POTENTIAL TETS None of the windings, either rotating or stationary should
More informationStandard for an Electrical Preventive Maintenance (EPM) Program
Recommended Maintenance Practices for Electrical Distribution System Equipment Hartford Steam Boiler One State Street P.O. Box 5024 Hartford, CT 06102-5024 Tel: (800) 472-1866 www.hsb.com April 2013 Introduction
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationHeavy Duty Alternator Charging System Troubleshooting
Heavy Duty Alternator Charging System Troubleshooting Alternator Charging System Troubleshooting Squealing noises under the hood? Headlight bulbs blow out repeatedly or dim? Is the dash voltmeter gauge
More informationUnit 33 Three-Phase Motors
Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation
More informationTAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
More informationUnderstanding Insulation Resistance Testing
Understanding Insulation Resistance Testing Why have an insulation testing program? A regular program of testing insulation resistance is strongly recommended to prevent electrical shocks, assure safety
More informationPowerformer chosen for Swedish combined heat and power plant
Powerformer chosen for Swedish combined heat and power plant Powerformer, a radically new type of generator developed by ABB, has been chosen for a combined heat and power plant in Eskilstuna, Sweden.
More informationAssessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO
April 2, 2014 Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO Todd Goyette, P.E., POWER Engineers Mousa Hejazi, P.E., Pepco Holdings Inc. 1 Pepco Quick Facts First incorporated in
More informationInstructions For SF 6 Refill Kit
S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Instructions For SF 6 Refill Kit TABLE OF CONTENTS Section Page Section Page INTRODUCTION..................................
More informationPhysical Address: City: State: Zip Code:
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (For Small Generator Facilities with Electric Nameplate Capacities of 10 MW and less) Applicant Contact
More informationFAULT FINDING MANUAL For Self Excited and Separately Excited Generators
FAULT FINDING MANUAL For Self Excited and Separately Excited Generators SAFETY PRECAUTIONS Before testing the generating set, read the generating set Installation Manual, and this Fault Finding Manual,
More informationA.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
More informationApplication for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (See ARSD chapter 20:10:36 for the requirements for a Tier 2, Tier 3, or Tier 4 Interconnection.) Applicant/Interconnection
More informationTechnical Electrical Field Service Support. Knowledge + Experience = Power. Field Service
Technical Electrical Field Service Support Knowledge + Experience = Power Field Service WRE Field Service Wismer & Rawlings Electric Ltd. Substation Testing and Commissioning Mission Statement To be recognized
More informationAC-Synchronous Generator
Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to
More informationElectrical Predictive and Preventative Maintenance
Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types
More informationIESO Supply Deliverability Guidelines
PUBLIC IMO_GDL_0021 IESO Supply Deliverability Guidelines Issue 3.0 This document is to be used to evaluate long-term system adequacy and connection assessments Public Disclaimer The posting of documents
More informationSECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES
SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES 611-1 Description. This Section sets forth Contract acceptance procedures for installations of traffic control signals and devices
More informationDIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
More informationSIEMENS Transmission and Distribution
TITLE Long Term Maintenance and Care for S36A E. C. Wright 02/09/04 This document is to be used in conjunction with Installation, Operation and Maintenance Schedule IOMS 635. Its aim is to provide guidance
More informationELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
More informationBUSINESS POLICY ELECTRIC SERVICE PRACTICES SP 1.1 INTRODUCTION
ELECTRIC SERVICE PRACTICES SP 1.1 INTRODUCTION The Saskatchewan Power Corporation (SaskPower) exists to provide electrical power to its customers. SaskPower's service area extends into most parts of Saskatchewan
More informationWINDING RESISTANCE TESTING
WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991
More informationService Life of Stator Winding Insulation as an Important Quality Feature of Large Hydro Generators
------------------------------ Operating Experience ----------------------------- Service Life of Stator Winding Insulation as an Important Quality Feature of Large Hydro Generators Wolf-Dietrich Blecken,
More informationRutland 913 Windcharger Fault Finding Guide
Rutland 913 Windcharger Fault Finding Guide Document No. SM-133 Issue A LOW VOLTAGE CHARGE CURRENT? TE 4 REGULATOR TE 5 REG RETURN REG TO MANUFACTURER CHARGE CURRENT INTERMITTENT CHARGE CURRENT SUFFICIENT
More informationICM Project Station Infrastructure and Equipment
EB 0 00 Schedule B. ( pages) ICM Project Station Infrastructure and Equipment (THESL) EB 0 00 Schedule B. I EXECUTIVE SUMMARY 0. Project Description Many Municipal Substations (MS) located outside of downtown
More information4 DEDICATED SINGLE PHASE LIMA MAC GENERATOR LIGHT TOWER DUTY MODELS 250MSL1278 AND 250MSL1299 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING
HI POTENTIAL TESTS 4 DEDICATED SINGLE PHASE LIMA MAC GENERATOR LIGHT TOWER DUTY MODELS 250MSL1278 AND 250MSL1299 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING None of the windings, either rotating or
More information12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
More informationPump Maintenance - Repair
Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.
More information3. Three phase winding technology
3. Three phase winding technology VATech Hydro, Austria Prof. A. Binder 3/1 Single layer winding Per slot only one coil side is placed. Coils manufactured as: a) Coils with identical coil span: W = τ p
More informationPump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationPANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual
PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual A Regal Brand TABLE OF CONTENTS INTRODUCTION 2 General Data 2 Initial Inspection 2 SAFETY 2 INSTALLATION 3 Location / Environment
More informationUnderground vs. Overhead Transmission and Distribution
electric power engineering Underground vs. Overhead Transmission and Distribution Your Power System Specialists June 9, 2009 1 NATIONAL TRENDS Municipalities have passed laws requiring new distribution
More informationAchieving Operational Efficiencies through On-Line Substation Monitoring. Vince Polsoni Powerstream Inc. Manager Station Sustainment EDIST 2016
Achieving Operational Efficiencies through On-Line Substation Monitoring Vince Polsoni Powerstream Inc. Manager Station Sustainment EDIST 2016 1 Agenda Maintenance Monitoring Equipment CMMS Data Historian
More informationReconstruction Support after the Great East Japan Earthquake
Advanced Maintenance, Energy Saving, Environment Reconstruction Support after the Great East Japan Earthquake Kan Kumagai Keyword Earthquake disaster reconstruction, Temporary restoration, Reuse, Diagnosis
More informationFederal Wage System Job Grading Standard for Electrical Equipment Repairing, 2854. Table of Contents
Federal Wage System Job Grading Standard for Electrical Equipment Repairing, 2854 Table of Contents WORK COVERED... 2 WORK NOT COVERED... 2 TITLES... 3 GRADE LEVELS... 3 HELPER AND INTERMEDIATE JOBS...
More information3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
More informationSECTION 263235 STANDBY GENERATOR TESTING AND COMMISSIONING
SECTION 263235 STANDBY GENERATOR TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standby generators. 2. Automatic Transfer Switches (ATS). 3. System start-up services. 4.
More informationPreventive and Predictive Maintenance
Preventive and Predictive Maintenance 700ZB00102 4-1 Preventive/Predictive Maintenance The guiding principle of PPM is the regular and systematic application of engineering knowledge and maintenance attention
More informationTesting of Power Transformers. Routine tests, Type tests and Special tests
Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests
More informationABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
More informationMaintenance Matters. Window and Door Replacement
Number 13 Maintenance Matters building maintenance bulletin Window and Door Replacement As part of the ongoing maintenance of your home or multi-unit residential building, windows and doors will eventually
More informationEmergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
More informationMaintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
More informationAppendix B Audit Forms for PdM Program Assessment
Copyright 2008 MasteringMaintenance.com. All rights reserved. Appendix B Audit Forms for PdM Program Assessment Contents include audit forms for assessing the following elements of a PdM Program: Overall
More informationCase Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives
Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives G.C. Stone, I. Culbert, H.G. Sedding Qualitrol-Iris Power Mississauga, Ontario, Canada Abstract On-line partial discharge
More informationSALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT
SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT Overview In all drying out of electrical windings, the regulation of temperature should be controlled carefully. Maximum drying temperatures on windings should
More informationNETWORK OUTPUT MEASURES CONSULTATION
NETWORK OUTPUT MEASURES CONSULTATION Great Britain s electricity transmission network transmits high-voltage electricity from where it is produced to where it is needed throughout the country. It broadly
More informationUnderstanding the Alternator
http://www.autoshop101.com THIS AUTOMOTIVE SERIES ON ALTERNATORS HAS BEEN DEVELOPED BY KEVIN R. SULLIVAN PROFESSOR OF AUTOMOTIVE TECHNOLOGY AT SKYLINE COLLEGE SAN BRUNO, CALIFORNIA ALL RIGHTS RESERVED
More informationWHAT IS INFRARED (IR) THERMOGRAPHY
WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical
More informationThe State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities
Generator Testing in Nursing Facilities Introduction Recent emergencies and natural disasters have emphasized the need to ensure that nursing facilities have an adequate EPSS in place should the loss of
More informationSMART ASSET MANAGEMENT MAXIMISE VALUE AND RELIABILITY
SMART ASSET MANAGEMENT MAXIMISE VALUE AND RELIABILITY Electrical equipment is a critical component of your asset portfolio. Beyond its financial value, it plays an even greater role in your business performance.
More informationResidual life aspects on GIS with the focus on SF 6
Residual life aspects on GIS with the focus on SF 6 Speaker: Karsten Pohlink 25. March 2015 The presentation refers to CIGRÉ WORKING GROUP B3.17 RESIDUAL LIFE CONCEPTS APPLIED TO HV GIS CIGRE Technical
More information100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
More informationAlstom Grid Services. Transformer lifecycle management GRID
Alstom Grid Services Transformer lifecycle management GRID Transformer services A COMPLETE RANGE OF SOLUTIONS As a critical component of networks, the power transformer is essential to high voltage electrical
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More informationGUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by
More informationIncipient Failure Detection in Power Transformers through Frequency Sweep Response
, October 24-26, 2012, San Francisco, USA Incipient Failure Detection in Power Transformers through Frequency Sweep Response Alberto Avalos Gonzalez, Jaime Cerda Jacobo, Servando Sanchez Ruíz Abstract
More informationELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
More informationJob Descriptions. Job Title Reports To Job Description TRANSMISSION SERVICES Manager, Transmission Services. VP Compliance & Standards
Updated July 11, 2013 Job Descriptions Job Title Reports To Job Description TRANSMISSION SERVICES VP Compliance & Standards Develops strategy and business plans for efficient, safe, reliable, regulatorycompliant
More informationHI TECH TRANSFORMER MAINTENANCE (PTY) LTD. COMPANY PROFILE AND OVERVIEW 19 March 2012
HI TECH TRANSFORMER MAINTENANCE (PTY) LTD COMPANY PROFILE AND OVERVIEW 19 March 2012 COMPANY BACKGROUND The company was founded in 1996. Ownership changed in 2005. Mainly provided site transformer maintenance
More informationS Y N C H R O N O U S G E N E R A T O R S
S E R I E S SYNCHRONOUS G E N E R A T O R S INDAR SYNCHRONOUS GENERATORS S E R I E S BZK INDAR ELECTRIC INDAR, EXPERIENCE AND COOPERATION INDAR Electric develops and manufactures electrical rotating machines
More informationAutonomous Maintenance
Autonomous Maintenance TPM & Autonomous Maintenance I run it, you fix it! I fix it, you run it! What is Maintenance? Why is Possible Utilization Rate Necessary? One way to look at Lean (JIT) production
More informationReducing Maintenance Costs Replacement of Small Fossil Generators in Russia
siemens.com/energy Reducing Maintenance Costs Replacement of Small Fossil Generators in Russia Russia Power 2014 4-6 March, 2014 Moscow, Russia Authors: Fabian Bremer Maren Stockhausen Dusan Jovic Siemens
More informationTuning Up DC Motors and Generators for Commutation and Performance
Tuning Up DC Motors and Generators for Commutation and Performance Rich Hall- National Electrical Carbon Western Mining Electrical Association June 8, 2007, Billings Montana Sometimes your machine may
More informationThe Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:
The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery
More informationWound Rotor Induction Motors 4-12 poles, up to 8000 kw, 11500 HP
Wound Rotor Induction Motors 4-12 poles, up to 8000 kw, 11500 HP ABB The Preferred Partner Egypt Cement Corporation, a major cement manufacturer, has chosen ABB wound rotor motors for all key applications
More information