IPS Magneto-Thermal protection device for electric loads.

Size: px
Start display at page:

Download "IPS Magneto-Thermal protection device for electric loads."

Transcription

1 Magneto-Thermal protection device for electric loads. S.r.l. via Landa, Monte San Pietro (BO) Italia tel Fax USER S MANUAL The ALMA S.r.l.company can modify the device and this manual without notice Codice Manuale M00 S.r.l.

2 RESET button Pushing RESET button you have deleting of the alarm state and restoring of the operation for all channels. It is equivalent to the rearmament of a thermal protection. Obviously, if the condition that generated the alarm has not been removed, the channel will be again in alarm. MAN/AUT and SEL buttons The MAN/AUT and SEL buttons are to select a channel and force its activation in manual mode. The SEL button is to select a channel. The indication for the selected channel is the turning on of the related red led. So pushing the button SEL once, the red led related with the fisrt channel (L1) will turn on, pushing it one more time the turned on red led will go to right until the L4 channel is selected. Pushing the button one more time no channel will be selected. No channel will be selected even if no button is pushed within about 10 seconds. It is not possible selecting channels if an alarm condition is active, so before using selection button push the RESET button to deactivate all alarms. When a channel is selected, pushing the MAN/AUT button it is possible to force it in the manual or automatic operation. The manual operation selection is indicated by the turning on of the related green led of the selected channel. When the green led related to a channel is turned on the channel is forced to manual operation. When the green led related to a channel is turned off the channel is forced to automatic operation: it is conditioned to the closure of the external contact. Solution of problems In this paragraph we give you some suggestions to solve anomalies you can meet using the device. Problem Solution Figure index Figure 1 Equivalent electric scheme of device s 4 functionality Figure Frontal view 6 Figure 3 Back view and accessories 7 Figure 4 Dimensions 7 Figure 5 Electrical connections 8 Figure 6 External activation 9 The device doesn t turn on The device doesn t turn on loads without receiving the external signal The device turning on is indicated by the led in the bottom on the right side of the frontal panel. Verify the connection of power supply. Verify there is line voltage. Verify power supply values are compliance with those specified in this manual. If the problem persists please contact the device distributor. Verify the effective turning on and off of the input led in the frontal panel. Verify connections of each load trying to force them in the manual operation. Push the RESET button to delete all the memorized alarm conditions. 10 3

3 Power supply The power supply connection is performed connecting the power voltage to terminals eumerated with 46 and 48. The nominal allowed voltage is 0 Vca to 30 Vca at 50 Hz frequency. Terminal 47 has to be connected with the ground reference. The device does not provide internal fuses, so you must provide an external adequate protection. The device power supply is protected from momentary over-voltages. Damages due to a wrong power supply are not covered by guarantee. Loads supply The loads supply is realized connecting power supply to terminals enumerated with 30 and 3. Terminal 31 has to be connected to the ground reference. Maximum current supported is 8 A and maximum tension is 50 Vca. Loads connection Loads connection is realized connecting them in couples to terminals 33 to 40, as indicated in figure 5. Each channel supports a maximum current of A. Anyway, current will be limited by the value set by the overload protection system (thermal funcionality). POWER L ALARM Figure 5 L3 L POWER SUPPLY L1 Alarm relay output connection Figure 5 shows the position of the relay at rest (device off). The alarm relay operates in intrinsic security, so it is activated at the device turning on, and it is deactivated when an alarm condition occurs. In this way you have a signal of no-controlled device when it is turned off. External activation The terminals 41 and 4 provide connection to external activation of operation: when you close the contacts on these terminals the device controls loads activation. The external contact has to be clean, i.e. without tension. In those applications where the NEX device controls the transformers temperatures and the device is used to turn on the ventilation fans, you must connect terminal 13 of the NEX device to terminal 41 of, and terminal 15 of NEX to terminal 4 of (see figure 7 option 1). In this way each time the temperature of one probe exceeds the threshold the relay of the NEX will activate and will turn on the ventilation fans. If you want the ventilation fans to be turned on even if a probe malfunction or a NEX malfunction occurs, you must connect paralleling also the contact of the generic 8 Inputs 1 input for loads supply. Maximum current 8A 1 digital input for extern contact without tension. It is for the external activation command Input connections with removable terminals for wire of 1,5 mm section and capacity of 8A/50Vac Outputs 1 output relay with 5 A and 0 Vca contacts for short circuit or overload alarms 4 outputs for 4 loads supply of maximum A each Output connection with removable terminals for wire of 1,5 mm section Device dimensions Frontal dimensions of 96 mm x 96 mm compliance with DIN requirements. Maximum depth 150 mm Assembling on the front of the electric panel Panel cut-out 9 mm x 9 mm ABS self-estinguishing container Frontal panel in anti-scratch poly-carbonate with keyboard and signal leds Perfomances Working temperature 0 C to +50 C Humidity lower than 95% no-condensing Compliance with requirements Device funcionality self-diagnostic Alarm signal for working anomalies Displaying and data management 4 green leds to signal working state of load 1 green led to signal the external input state 1 green led to signal device access state 4 red leds to signal alarms for each supply channel 1 reser button to reset alarms. It is equivalent to the rearmament of a thermal protection. buttons to select channel and to force manual operation. Cautions avoid power supply out of the device nominal range avoid the device working in room with conditions out of the nominal ones previously reported and in particular in presence of condensing humidity. 5

4 Index Figure index 3 Introduction 4 Device Overview 4 Technical specifications 4 Precauzioni 5 Installation instructions 6 Device and accessories description 6 Frontal panel 6 Back panel and accessories 6 Mechanical installation 7 Electrical connections 7 Power Supply 8 Loads supply 8 Loads connections 8 Alarm relay output connection 8 External activation 8 Instructions for use 9 Led 9 Buttons 9 Reset button 10 MAN/AUT and SEL buttons 10 Solution of problems 10 Guarantee conditions 11 Guarantee conditions The thermal protection devices are covered by guarantee for a period of 4 months since the consignment date for anomalies due to production defects. The guarantee consists in the free repair or substitution of the components that have been damaged in the devices' construction, arrived at our office carriage paid. The product's guarantee declines in the following cases: device's damages deriving from negligence, use or installation not compliance with the instructions furnished in the user's manual wrong power supply damages due to changes in the line voltage to which the device is connected as in the case of discharges caused by thunderbolts or other external phenomena tampering with the device damages due to accidental causes or to negligence non-payment of the device The guarantee period is determined on the basis of the serial number written on the device's label so that it has not to be cancelled nor modified. Parts subjected to wear by use are not covered by guarantee. Furthermore, removal and re-installation costs are not covered by guarantee, as transport costs and risks and any other direct or indirect cost due to repair of the device you consider damaged. The constructor declines any responsibility for harms done to persons, animals or things directly or indirectly coming out from a proper or improper use of the device. The device's repair or substitution is subjected to the unobjectionable constructor's opinion. When the guarantee period falls the damaged device's repair will involve the debit entry for the damaged components substitution and for the labour. For any dispute the competent Court is the one of Bologna (Italy). 11

5 Introduction Congratulations for your choice to purchase (Intelligent Power Switch), the magneto-thermal device for electrical loads. This manual gives you the informations to install and use the device. For an useful usage of this manual we suggest you to read it near the device to directly verify the instructions. We moreover suggest you to keep the manual for future use. Device Overview. The device supports the functionalties of magneto-thermic and of manual/automatic switch for four distinct electrical loads. It was developed to satisfy requirements of the insulated resin transformers users who use fans for convection cooling, but it can be used in any situation where you have 4 different electrical loads and you need a magnetothermal control. The principal functionality of this device are represented in the scheme in figure 1. In details the device supports these functionalities: 1 digital input to receive external signals Leds to visualize alarms and operation state of loads 3 buttons for settings Non volatile memory to save user's settings 4 outputs to supply the electrical loads 1 relay output for short circuit or overload alarms. M A extern contact M 0 A alarm to terminal and 3 of the NEX device, as represented by option of figure 7 (you must connect he normally closed, because it works in intrinsic security i.e. On the relay drop). NEX A Instructions for use opzione 1 opzione NEX A Figure 6 allarme generico 3 4 ALL MAN / AUT RESET L1 L L3 L4 The device provides functionalities of a magneto-thermic for four loads maximum and can be externally supplied by another control device or by a button for loads activation. The device verifies there are no short-circuits, otherwise it turns off all loads and signals an alarm state. The device measures the current absorption of each load connected to it and if they exceed the memorized threshold the device turns off the related channel and signals an alarm. Using buttons you can force the manual activation (independently from external activation) for single loads. A1 A MAN AUT A3 NEX SEL ON The system has been developed for an easy manual or automatic arrangement of loads and for a fast diagnostic in case of anomalies. The device has been realized compliance with the electromagnetic compatibility requirements. Technical specifications Power supply Nominal line voltage 0 Vac at Hz Maximum line voltage 50 Vac Maximum power absorption 5VA Protection against line noises L1 L L3 L4 Figure 1 Led Each channel has related leds on frontal panel: one red and one green. For each channel the red led signals an alarm situation (blinking led) or to indicate the selected channel (fixed light) for the manual activation; the green led indicates the manual operation state. If the device measures an overload situation on a channel, it will turn off the channel and turn on the related red led blinking. If the device reveals a short-circuit situation, it will turn off all channels and all red leds will blink at a higher frequency than the one they blink at in overload conditions. On the device there is also a green led to indicate the digital input state for external activation: it is on when the external contact is closed. Another green led indicates the state of device on. Buttons On the device there are 3 buttons to provide the following functionalities. 4 9

6 POWER VIA LANDA, /B MONTE SAN PIETRO (BO) ITALY TELEFONO: VIA L4 L3 ALARM L POWER POWER SUPPLY SUPPLY L Installation instructions For a right operation, the device has to be installed compliance to the requirements reported in the Technical Specifications paragraph. The device provides fixing accessories and removable terminals for electrical connections. Device and accessories description Figure represents the scheme of the device. Frontal Panel 1. 4 red leds group to signal alarm state for each supply channel. 4 green leds group to signal the operation state for each supply channel 3. Green led to signal the digital input state:external operation command 4. Reset button to delete alarms 5. MAN/AUTO button to force manual operation 6. SEL button to select the manual operation channel 7. Led to signal the operation state of the device 3 1 ALL MAN / AUT RESET L1 L L3 L4 MAN AUT SEL ON 7 3. Power supply connector 4. 4 electrical loads supply connectors 5. Supply connector needed for loads 6. Removable terminals for wiring harness 1 7. Clips for device clamping Mechanical installation The device provides a black selfextinguishing ABS container. The device dimensions are compliance to the standard of DIN 43700: 96 mm x 96 mm section and a maximum depth of 150 mm. The dimensions of the panel perforation are 9 mm x 9 mm. The fixing is carried out using the clamps provided with the device. See Figure Rear view and accessories Figure 3 Electrical connections All the connections are carried out with the removable terminals provided with the device for a simplified wiring harness. For the wiring harness you can refer to the figure 5 and to the terminals numeration Front view Figure 89,5 x 87,5 mm 4,03 mm ALL MAN / AUT RESET L1 L L3 L4 MAN AUT SEL ON 96 mm 6,3 mm 9 mm 4,7 mm Back panel and accessories 1. Digital input connector for the external operation command. Alarm relay output connector 140 4,54 mm 150 7,01mm 6,3 96 mm Figure 4 94,7 mm 6 7

INSTRUCTION MANUAL VRT-200. TECSYSTEM S.r.l. Via Cristoforo Colombo, 5/C 20094 Corsico (MI) phone +39-02 - 48601011 / 4581861 Fax: +39-02 48600783

INSTRUCTION MANUAL VRT-200. TECSYSTEM S.r.l. Via Cristoforo Colombo, 5/C 20094 Corsico (MI) phone +39-02 - 48601011 / 4581861 Fax: +39-02 48600783 INSTRUCTION MANUAL VRT-200 TECSYSTEM S.r.l. Via Cristoforo Colombo, 5/C 20094 Corsico (MI) phone +39-02 - 48601011 / 4581861 Fax: +39-02 48600783 http://www.tecsystem.it R.3 27/03/03 VRT200 protection

More information

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

TT 49 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR 06050. TECNOLOGIC S.p.A.

TT 49 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR 06050. TECNOLOGIC S.p.A. TT 49 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER INDEX..2 2 2. 2.2 2.3 3 3. 3.2 3.3 3.4 4 4. 4.2 4.3 4.4 4.5 5 5. 5.2 6 6. 6.2 7 7. 7.2 7.3 7.4 7.5 INSTRUMENT DESCRIPTION GENERAL DESCRIPTION FRONT PANEL

More information

ZC-24DO CANopen I/O Module: 24 Digital Outputs

ZC-24DO CANopen I/O Module: 24 Digital Outputs Z-PC Line EN ZC-24DO CANopen I/O Module: 24 Digital Outputs Installation Manual Contents: - General Specifications - Technical Specifications - Installation Rules - Electrical connections - DIP-switches

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.:

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.: Documento: M-010.1-MGAS-ENG Edizione: 01/1997 Rev.: A.1 a Division of Pittway Corporation FRONT PANEL & VISUAL INDICATIONS GENERAL TROUBLE GENERAL PROGRAMMING IN PROGRESS ENABLE/ALARM/TROUBLE (ZONE 1 ALARM

More information

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142

More information

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new

More information

www.sebury.com.cn Digital Keypad Use s Manual

www.sebury.com.cn Digital Keypad Use s Manual K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

REGULINE 600VA / 1000VA REGULATOR USER MANUAL REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL

ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL INTRODUCTION... 2.. TECHNICAL DATA... 3 ACCESSORIES... 5. INSTALLATION... 7 OPERATION... 12. TECHNICAL INFORMATION... 13 MAINTENANCE... 14. CONFIGURATIONS...

More information

PD 100A. Printing data system

PD 100A. Printing data system PD 100A Printing data system Operating instructions ENGLISH IMPORTANT: Read these instructions carefully before installing and using the device; do not forget following all additional information. Keep

More information

ECP 208. Cold Rooms Controllers USER S MANUAL

ECP 208. Cold Rooms Controllers USER S MANUAL ECP 208 Cold Rooms Controllers USER S MANUAL INDEX DESCRIPTION... 3 FUNCTIONING... 4 PARAMETERS SETTING... 4 FRONTAL SETTING CONTROLS... 4 MAIN FEATURES... 5 LAYOUT AND TERMINAL BLOCKS... 6 OPTIONS...

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

Doc.No. NDP 192U-02. Electric Pump Controller CE-124P. Instruction Manual

Doc.No. NDP 192U-02. Electric Pump Controller CE-124P. Instruction Manual Doc.No. NDP 192U-02 Electric Pump Controller CE-124P Instruction Manual 1. Parts Name and Function 1) POWER LED Indicate that CE-124P is powered up. 2) START/STOP KEY (SELECTOR KEY) Used to start and stop

More information

I STAR COMPUTER CO., LTD

I STAR COMPUTER CO., LTD I STAR COMPUTER CO., LTD Mini Redundant Power Supply 300W+300W for IPC-Computer Model No. TC-300R8 Table of content 1. Introduction...1 2. Specification 2.1 Input Voltage...1 2.2 DC Output...1 2.3 PS-ON

More information

Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6. User s manual

Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6. User s manual Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6 User s manual Index Safety Warnings... 2 1 Introduction... 3 2 General Characteristics... 4 3 Receipt and site selection... 4 4 EXTERNAL

More information

Universal control module for motorized devices

Universal control module for motorized devices Ref: MOD-0105-N The MOD-0105-N is a universal module for motorized devices, blinds, awnings, curtains, doors, etc.. Allows, with vivimat BUS, the local or remote control of a motorized devices, ensuring

More information

DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D

DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D ELECTRONICS AB DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D & HIGH&VOLTAGE& FIXED&GAIN& BROADBAND & 800Vpp&60mA& 100x& DC&to&ca&200&kHz & LOW&OUTPUT&IMPEDANCE& HIGH&SLEW&RATE &

More information

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Introduction. Refrigerant Leak Detecting System. Feature and Benefits PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for

More information

Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy. Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com

More information

ML 1012 v.1.2 ML13,8V/1A Buffer power supply module, linear.

ML 1012 v.1.2 ML13,8V/1A Buffer power supply module, linear. ML 1012 v.1.2 ML13,8V/1A Buffer power supply module, linear. EN Edition: 6 from 10.03.2014 Supercedes the edition: 5 from 16.09.2013 Features: uninterrupted supply of 13,8VDC/1A supply voltage: external

More information

Operation Manual. 150 Watt Halogen Light Source for Endoscopy Model # s ESS-150, ESS-150A ESS-220, ESS-220A

Operation Manual. 150 Watt Halogen Light Source for Endoscopy Model # s ESS-150, ESS-150A ESS-220, ESS-220A Operation Manual 150 Watt Halogen Light Source for Endoscopy Model # s ESS-150, ESS-150A ESS-220, ESS-220A Endoscopy Support Services, Inc. Croton River Executive Park Route 22, Bldg. 3 Brewster, NY 10509

More information

How To Use A Power Supply Unit (Upu)

How To Use A Power Supply Unit (Upu) BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.

More information

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS + Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

MANUAL PC1000R INFO@APART-AUDIO.COM

MANUAL PC1000R INFO@APART-AUDIO.COM MANUAL PC1000R INFO@APART-AUDIO.COM Features The APart PC1000R is a professional multisource CD/USB/SD card music player, equipped with balanced and unbalanced analog outputs, coaxial and optical digital

More information

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description

More information

PowlVac Vacuum Integrity Tester

PowlVac Vacuum Integrity Tester Instructions IB-60025B PowlVac Vacuum Integrity Tester POWELL ELECTRICAL MANUFACTURING COMPANY 8550 MOSLEY DRIVE HOUSTON, TEXAS 77075 USA PHONE (713) 944-6900 FAX (713) 947-4453 www.powellelectric.com

More information

MTS Power Products MIAMI FL 33142 ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual

MTS Power Products MIAMI FL 33142 ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual MTS Power Products MIAMI FL 33142 ATS-22AG Automatic Transfer Switch And Control PLC Operator s Manual Dedicated Single Phase Transfer Switch With Touch Screen Controls Normal Power Connections Emergency

More information

PSDC 08128. PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

PSDC 08128. PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC. PSDC 08128 v.1.2 PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC. EN** Edition: 9 from 25.05.2015 Supersedes the edition: 8 from 12.12.2014 the 8x 1A/12V DC power output for powering

More information

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,

More information

Uninterruptible Power Supply

Uninterruptible Power Supply 96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features

More information

Operation Manual for Users

Operation Manual for Users Operation Manual for Users Model No.: FLTAMFMRCD!!!!!!!!!! ATTENTION!!!!!!!!!! THE RESET BUTTON MUST BE PRESSED TO ENSURE PROPER OPERATION. SEE INSTRUCTION MANUAL Table of Contents Table of Contents ---------------------------------------------------------------------------------------------

More information

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual

EPM3. Phase Sequence and Motor Rotation Tester. Users Manual EPM3 Phase Sequence and Motor Rotation Tester Users Manual 1 L1 L2 L3 2 3 A B C CAT 600V 3-PHASE TESTER 5 TEST M1 M2 BATT M3 EPM3 MOTOR ROTATION TESTER EPM3 MOTOR ROTATION DETERMINED WHILE FACING MOTOR

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1 BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -

More information

Car Alarm Series 2 B 2 Buttons

Car Alarm Series 2 B 2 Buttons Car Alarm Series 2 B 2 Buttons G22 SE (External - Shock Sensor) Version 3 Software 67 Plus www.geniuscaralarm.com 21 CAR ALARM GENIUS Series 2B 2 Buttons - G22 Se (External Shock Sensor) Module controlled

More information

COMPALARM AP GENERAL MAIN FEATURES

COMPALARM AP GENERAL MAIN FEATURES GENERAL The COMPALARM AP is a point alarm system, with as many normally closed input contacts. It givesthe possibility of selecting the alarm sequence according with 0 x 0 mm cells, fitted with ultra bright

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

Operating Manual UWAPS-TINY Series

Operating Manual UWAPS-TINY Series Operating Manual UWAPS-TINY Series Powecon Oy WWW.POWECON.FI 1/9 Table of content 1 Warranty...3 2 Safety information...3 3 Abbreviations and terminology...3 4 List of appendices...4 5 Introduction...4

More information

Current Monitoring Kit QUICK START GUIDE

Current Monitoring Kit QUICK START GUIDE Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...

More information

Back-UPS Pro 1300/1500 Installation and Operation

Back-UPS Pro 1300/1500 Installation and Operation Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a

More information

instabus KNX / EIB System System E F G H

instabus KNX / EIB System System E F G H Product name: Uninterruptible power supply (USV) 640 ma Design: REG (rail-mounted device) Article-no.: 1079 00 ETS search path: Gira Giersiepen / system components / power supply / power supply 640mA DRA

More information

VX 2400 Dimmer User's Manual

VX 2400 Dimmer User's Manual TM VX 2400 Dimmer User's Manual 21-2119C Manual Revision 1.01 Software Version 1.0 10 March 1994 Table of Contents 1. General Description...3 1.1. Standard Features:...3 2. Installing Options...4 2.1.

More information

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0 Form No. 74-00-4001 S168-195-001 Revision E DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0 INTRODUCTION Allied Healthcare Products, Inc. s Digital Alarm

More information

Current Monitoring Kit

Current Monitoring Kit Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added

More information

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply 1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,

More information

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS

More information

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05 RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,

More information

LED - Indicator Panels

LED - Indicator Panels energy management systems 09 LED - Indicator Panels Standard LED - Indicator Panels LM...72, LM...96, LM...144 page 9/1 Indicator panels with 3 color LEDs SM...96 page 9/9 LED - INDICATOR PANELS LED-Indicator

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.

More information

Single Channel Loop Detector

Single Channel Loop Detector Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop

More information

Online UPS. PowerWalker VFI 1000R/1U

Online UPS. PowerWalker VFI 1000R/1U Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

A/C-HEATER SYSTEM - AUTOMATIC

A/C-HEATER SYSTEM - AUTOMATIC A/C-HEATER SYSTEM - AUTOMATIC 1995 Volvo 850 1995-96 Auto. A/C-Heater Systems Volvo 850 * PLEASE READ THIS FIRST * WARNING: To avoid injury from accidental air bag deployment, read and carefully follow

More information

LEN s.r.l. Via S. Andrea di Rovereto 33 c.s. 16043 CHIAVARI (GE) Tel. +39 0185 318444 - Fax +39 0185 472835 mailto: len@len.it url: http//www.len.

LEN s.r.l. Via S. Andrea di Rovereto 33 c.s. 16043 CHIAVARI (GE) Tel. +39 0185 318444 - Fax +39 0185 472835 mailto: len@len.it url: http//www.len. MA511 General Index 1 INTRODUCTION... 3 1.1 HARDWARE FEATURES:... 4 2 INTERFACE... 5 2.1 KEYBOARD... 6 2.2 POWER ON... 7 2.3 POWER OFF... 7 2.4 DETECTOR CONNECTION... 7 2.5 DETECTOR SUBSTITUTION...7 3

More information

Electronically Controlled Clutchless or Variable Drive Compressors

Electronically Controlled Clutchless or Variable Drive Compressors Electronically Controlled Clutchless or Variable Drive Compressors On many new air conditioning systems, such as Lexus, Cadillac, Chrysler, and others, a new type of compressor has been fitted. There are

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

User s Manual AURORA 1.2K/2.2K

User s Manual AURORA 1.2K/2.2K User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

APOLLO Plus PORTABLE DIMMER SERIES

APOLLO Plus PORTABLE DIMMER SERIES APOLLO Plus PORTABLE DIMMER SERIES USER S MANUAL Any reproduction by means or whole of this user manual in any way, is prohibited without the consent of ELECTRON S.A. ELECTRON S.A. reserves the right to

More information

Power Supplies 3. SDN-P DIN Rail Series

Power Supplies 3. SDN-P DIN Rail Series SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.

More information

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018 USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and

More information

Technical Data. back-up time in minutes 100% load 6 7 0 5 6 0 5 0 50% load 15 18 0 15 16 0 15 0

Technical Data. back-up time in minutes 100% load 6 7 0 5 6 0 5 0 50% load 15 18 0 15 16 0 15 0 The protectoq is a On-Line double conversion UPS-system according to IEC / EN 62040-3 (VFI-SS-111) with sinus wave output voltage in each operation mode, LCDindication, RS232 interface, USB-connection,

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

USER MANUAL. Model 6103 3U ForeFront Alarm Card SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007. An ISO-9001 Certified Company

USER MANUAL. Model 6103 3U ForeFront Alarm Card SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007. An ISO-9001 Certified Company USER MANUAL Model 6103 3U ForeFront Alarm Card An ISO-9001 Certified Company Part# 07M6103 Doc# 123011U Rev. A Revised 7/15/03 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007 CONTENTS 1.0

More information

C-Tech-10 Operation Manual

C-Tech-10 Operation Manual C-Tech-10 Operation Manual Project: SATS Model: SATS Serial #: SATS Job#: Notice This document contains information protected by copyright. All rights are reserved. The owner of the equipment for which

More information

SUB Universal water baths SBB Boiling baths JB, PB Unstirred water baths

SUB Universal water baths SBB Boiling baths JB, PB Unstirred water baths SUB Universal water baths SBB Boiling baths JB, PB Unstirred water baths Operating instructions Universal water baths SUB6: 6 litres SUB14: 14 litres SUB28: 28 litres SUB36: 36 litres Boiling baths SBB6:

More information

CM500 High Speed Cable Modem User Manual

CM500 High Speed Cable Modem User Manual User Manual February 2015 202-11472-04 350 East Plumeria Drive San Jose, CA 95134 USA Support Thank you for selecting NETGEAR products. After installing your device, locate the serial number on the label

More information

600-GD & 600-GDL 600 SERIES GAS DETECTOR

600-GD & 600-GDL 600 SERIES GAS DETECTOR 600-GD & 600-GDL 600 SERIES GAS DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS This page has been deliberately left blank. Page 1 Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING

More information

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL User s Guide Version 1.0 07/01/2009 Michael Stevens & Partners Ltd. has made

More information

Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P

Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P Distributed in the U.S.A. and Canada by CHENG USA, INC. Sales (574) 294-8997 Warranty Service (877) 294-8997

More information

PS 29M DUAL CHANNEL BELTPACK IN METAL CASE

PS 29M DUAL CHANNEL BELTPACK IN METAL CASE PS 29M DUAL CHANNEL BELTPACK IN METAL CASE USER MANUAL October 2013 This product is designed and manufactured by: ASL Intercom BV Zonnebaan 42 3542 EG Utrecht The Netherlands Phone: +31 (0)30 2411901 Fax:

More information

GSM ALARM SYSTEM USER MANUAL

GSM ALARM SYSTEM USER MANUAL GSM ALARM SYSTEM USER MANUAL 1. Instruction The alarm system is based on GSM network. With a GSM SIM card, it can be used wherever you want and no need to connect any wire, which is convenient and easy

More information

Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V

Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

LDG DTS-4/4R Desktop Coaxial Switch / Remote

LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 ldg@ldgelectronics.com www.ldgelectronics.com

More information

RAINCONTROL LCD Special

RAINCONTROL LCD Special RAINCONTROL LCD Special edition 1.1 01/2007 - code 5880 1/16 RAINCONTROL LCD SPECIAL... 3 RAINCONTROL SPECIAL LCD PANEL PRESENTATION... 4 AUTO... 5 LOW AND HIGH THRESHOLD SETTING... 6 LOW THRESHOLD...

More information

Photovoltaic Solar Energy Unit EESFB

Photovoltaic Solar Energy Unit EESFB Technical Teaching Equipment Photovoltaic Solar Energy Unit EESFB Products Products range Units 5.-Energy Electronic console PROCESS DIAGRAM AND UNIT ELEMENTS ALLOCATION Worlddidac Member ISO 9000: Quality

More information

帝 聞 企 業 股 份 有 限 公 司 DEE VAN ENTERPRISE CO., LTD. SP-235864 DSL-20WA 420024 1 Revision: A Date: 2011.10.24 FOR AC-DC LED DRIVER MODEL NO.

帝 聞 企 業 股 份 有 限 公 司 DEE VAN ENTERPRISE CO., LTD. SP-235864 DSL-20WA 420024 1 Revision: A Date: 2011.10.24 FOR AC-DC LED DRIVER MODEL NO. CUSTOMER: PART NUMBER: A200 APPROVAL SHEET FOR AC-DC LED DRIVER MODEL NO. DSL-20WA 420024 1 ORDER NO: SP-235864 承 認 書 确 認 后 請 簽 回 一 份 CUSTOMER APPROVED SIGNATURE DEE VAN ENTERPRISE CO., LTD (Head-Quarter)

More information

Multi-Range Programmable DC Power Supplies 9115 Series

Multi-Range Programmable DC Power Supplies 9115 Series Data Sheet 1200 W Multi-Range DC Power Supplies Features & Benefits Any 9115 series model can replace several supplies on your bench or in your rack. Unlike conventional supplies with fixed output ratings,

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

Installation and Operation Back-UPS 1250, 1300, 1500

Installation and Operation Back-UPS 1250, 1300, 1500 Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with

More information

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner

More information

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual. i800 AC Current Clamp Instruction Sheet Introduction The i800 AC Current Clamp, the Clamp, has been designed for use with multimeters, recorders, power analyzers, safety testers, etc., for accurate non-intrusive

More information

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems TDB301021en/06.2013 LIETRAXX -A etwork and system protection (S protection) for monitoring

More information

Advantages and Efficient Use of Programmable Sockets. By Miguel Rascon AC Power Senior Product Manager

Advantages and Efficient Use of Programmable Sockets. By Miguel Rascon AC Power Senior Product Manager Advantages and Efficient Use of Sockets By Miguel Rascon AC Power Senior Product Manager Abstract Emerson Network Power s most recent products feature programmable s embedded in the UPS to provide the

More information

15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE

15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer

More information