Proposed Construction of Basement Flood Risk Assessment. 35 Edwardes Square London W8 6HH

Size: px
Start display at page:

Download "Proposed Construction of Basement Flood Risk Assessment. 35 Edwardes Square London W8 6HH"

Transcription

1 Proposed Construction of Basement Flood Risk Assessment 35 Edwardes Square London W8 6HH 1

2 Introduction This FRA has been carried out in accordance with the National Planning Policy Statement (NPPF), the Royal Boroughs of Kensington & Chelsea, along with advice and guidance from the Environment Agency (EA) and CIRIA. The works within this Statement refer to the following operations Construction of a basement below rear garden. Proposed Development The proposals are as described above to construct a single storey basement under the rear garden of 35 Edwardes Square, London, W8 6HH. 2

3 Site Description The site occupies an area of approximately HA and is located on the western side of Edwardes Square. The site is within an urban area of London and is bounded by existing properties. The property is a four storey house with lower ground floor level and front / rear gardens. The site is located within flood zone 1. Proposed Lower Ground Floor Proposed Basement Layout 3

4 Geology of the Area The geology of the area consists of sand which overlies a London Clay Formation. Above Bedrock of the area Below Superficial deposits of the area 4

5 Flood Risk Assessment from Watercourses / Sea There is not a risk of flooding from watercourses and the sea as identified on the Environment Agency (EA) indicative flood outline map. The map shows that the site is within flood zone 1. Strategic Flood Risk Assessment (SFRA) Royal Borough of Kensington and Chelsea s SFRA, prepared by JBA in August 2009, concludes that the significant sources of flood risk within the Royal Borough of Kensington and Chelsea and London Borough of Hammersmith and Fulham are surface water and sewer flooding, and the residual risk which arises from a possible failure in the Thames tidal defences. While failure of the defences will have no impact to the proposed development as it is located outside the flood zones, sewer and surface water flooding must be considered in the design. Flood Risk from Groundwater The SFRA states that no records of historical groundwater flooding in this area have been found. The bedrock geology of the area consists of London Clay overlying a chalk aquifer; this impermeable cap to the aquifer should prevent incidents of deep groundwater flooding. The London Clay itself is overlain with superficial gravels in the lower part of the borough. These permeable gravels outline the historic floodplain of the River Thames and may contain a perched water table. If following rainfall, the water table within this gravel layer rises then localised groundwater flooding can result in excavations and basements. The proposed development above ground level is not at flood risk from groundwater considering that it is located well above the water table. The proposed basement will be constructed above the recorded groundwater level. However, engineering techniques such as cavity drainage could be required in order to eliminate the flood risk from groundwater at basement level. 5

6 Flood Risk from Surface Water and Sewers The SFRA provides data from a modelling exercise that was undertaken in the borough in order to identify surface water flow routes and locations where surface water may accumulate and cause flooding. The map below shows the affected areas from surface water flooding in the 100 year storm event as they were modelled for the SFRA. In addition to the modelling results shows the locations of properties which suffered flooding as a result of the 20th July 2007 event. There is a visible correlation between the modelling results (specifically the ponded areas) and the observed incidents. The map shows that the site is located within an area where the surface water flood depth is 0m in the 100 year storm event. The proposed basement is below this level and consequently at flood risk from surface water. The rear lightwell would be at risk if no flood protection measures are provided. 6

7 It is recommended a 200mm step to the external area be provided this will eliminate the flood risk to the basement from overland flows. Thames Water also provided details of sewer flooding on a postal area basis (Map 18). The site is within an area where flood incidents from sewers were reported within the last 10 years. Thames Water have stated that areas which have in the past been affected by such flooding should not be seen as areas to avoid future development and that the reverse is also true, that areas with no known flooding incidents should not always be viewed as the best place to accommodate new development. Surface and foul water from the basement is likely to be pumped into the ground floor drainage on site and drain to the public sewers by gravity. Non return valves will be provided at the pumping stations preventing backflows from the public sewers from flooding the proposed development. 7

8 Impact on Surface Waters The Hydrogeological Assessment that was prepared for the site in July 2014 by CGL confirms the majority of the proposed basement will be below the rear garden, which is currently covered by a paved area and lawn. The basement extension below the rear garden will be beneath a 1m thick attenuation layer immediately in the rear of the property and a 1.5m attenuation layer at the rear of the garden. The attenuation layer is typically formed of a granular drainage layer directly above the roof of the basement overlain by topsoil. This has been designed to allow infiltration and attenuation of surface water prior to discharge to the local drainage system. The proposed drainage measures will continue the current surface water storage and attenuation provided by the property. Impact on Ground Water The Hydrogeological Assessment that was prepared for the site in July 2014 by CGL confirms the ground investigation data of the site and surrounding area indicated that groundwater is likely to be located within the KPG and flowing in a south easterly direction towards the River Thames. The proposed basement formation is likely to be at approximately the same level as the groundwater table at the base of the KPG. However, there is likely to remain some 300mm of KPG beneath the basement formation and therefore, movement of groundwater within the KPG is unlikely to be adversely affected and will continue to flow beneath the proposed basement. 8

9 Scope for Mitigation The following flood risk reduction measures will be applied to the development: As a precaution it has been agreed with the Building Owner they would subscribe to the Environment Agency s Flood Warning service and ensure that this services is made available to all occupants of the proposed building. The agency operates a 24 hour telephone service on that provides frequently updated flood warnings and associated floodplain information. In addition, this information can also be found at agency.gov.uk/floodline along with recommendations on what steps should be taken to prepare for floods, what to do when warnings are issued, and how best to cope with the aftermath of floods. All utility services such as fuse boxes, metres, main cables, gas pipes, phone lines and sockets will be positioned as high as practical. Central heating pipe work shall be easily accessible to allow easy maintenance in event of possible flood. Sewage Backflow Prevention Basements can be damaged by the backflow of sewage. The causes can include severe storms, breakdown of pumping plant or blocked pipelines. Anti flood (or non return) valves have been designed to prevent backflow from surcharging sewers. Wherever there is danger from rising water backing up into a property through the drainage system the valve will close off the backflow automatically to prevent flood damage. An anti flood valve is to be installed as a simple and effective way to eliminate backflow through drainage systems. The flap(s) in the valve opens to allow discharge. In a potential flood situation, the rising water levels seals the flap(s) shut. Damp proofing of Basement Floor The damp proofing of the Basement Level where this is immediately below the surrounding ground level will be by a patent membrane system similar to that provided by DELTA. This allows any surface water to drain down behind the membrane and is then pumped out by sump pumps located within the basement floor. The proposed development will have a non return valve installed at the valves sewer connections to prevent backing up within the pipes should the system become overwhelmed with flood water. All utility services such as fuse boxes, metres, mains cables, gas pipes, phone lines and sockets will be positioned as high as practical. Central heating pipe work shall be easily accessible to allow for easy maintenance in the event of a possible flood. 9

10 Conclusions The site falls within flood zone 1; Areas with low potential risk of flooding from rivers (annual probability lower than 0.1% for fluvial flooding), which are already developed. These areas will generally be suitable for residential developments. Engineering techniques such as cavity drainage will prevent groundwater from flooding the basement. Non return valves will be provided preventing backflows from the public sewers flooding. Flood mitigation measures will be used at the new light well preventing flood water from entering the basement. The proposed basement as confirmed in the Hydrology Report will not affect the local hydrogeology and therefore will not increase the flood risk on site and the surrounding areas. The proposed basement as confirmed in the Hydrology Report will have negligible impact on surface and groundwater flow and local ground stability. Therefore, the proposed development has an acceptable flood risk within the terms and requirements of PPS25. From the evidence seen in the flood maps, it is reasonable to conclude that any development to create a single storey basement would not be damaged by any flooding. 10

11 Product Datasheet June 2012 Sewage backflow prevention There are 2 million properties at risk from flooding in the UK. Many will be directly affected by river or coastal flooding, but more homes are damaged indirectly by the backflow of sewage. The causes can include severe storms, breakdown of pumping plant or blocked pipelines. The Marley anti-flood (or non-return) valves have been designed to prevent backflow from surcharging sewers. Wherever there is danger from rising water backing up into a property through the drainage system the valve will close off the backflow automatically to prevent flood damage. The financial losses caused by sewage flooding events can be in the region of 30,000 to 50,000 per property. In less than 30 minutes a house or basement flat can flood with untreated sewage to a depth greater than 1 metre. An anti-flood valve is particularly suitable for the following places: Low-lying coastal, lake or valley areas Properties connected to a high flow rate sewage system Private discharge systems connected to public sewers supplied with pumping stations Where non-pressure flow control is needed Simple installation, effective operation The anti-flood valves are produced in both PVCu and ABS Plastic and are corrosion resistant. As well as preventing back flow in the system, the anti-flood valve also stops rodent penetration. Installation The Marley anti-flood valve is easy to install within the drainage system. When installing, ensure the valve is set horizontally, as a fall is already built in. Also check that the direction of the flow matches that indicated by the arrow on the cover of the valve. The valve should be installed in a chamber to allow access for maintenance. Emergency closure device The valve can be locked in the closed position for added security (no through drainage allowed) for holiday periods, if required. Operation When backflow occurs in the system the non-return valve closes automatically. For the system to function correctly ensure the handle is on open. Regular flow rate is regained when the backflow ceases. Maintenance The emergency closure device mentioned above should be tested once every six months. In case of a blockage, remove the cover, clean the constituent parts, check the gaskets and replace any damaged parts. It is essential that the valve is accessible at all times. The Marley anti-flood valve should be serviced once every twelve months. marley.co.uk

12 The Marley double-flap valve meets the requirements of Building Regulations, Document H1 Marley anti-flood valves An anti-flood valve is a simple and effective way to eliminate backflow through drainage systems. The flap(s) in the valve opens to allow discharge. In a potential flood situation, the rising water levels seals the flap(s) shut. Normal use Anti-flooding situation The Marley anti-flood valve range: Size Colour Code Width L1 L2 L3 L4 110 Orange USW Single flap Size Colour Code Width L1 L2 L3 L4 110 Black USW Black USW Double flap All of the Marley anti-flood valves conform to BS EN All sizes are in mm USW120 USW130/140 Top Inspection Cover Tested with 5 metres head of water. Slide-Inflap Support All parts are removable for periodic servicing. Closing Lever Locking device for long periods of non-use (holidays) Main Body Rigid PVC injection moulded with structural ribs. Socket inlet with elastomeric ring seal. Spigot outlet. Removable lock Inspection cover Waste flow direction arrow Co-moulded seal Internal Shape Built-in invert. No reduced crossed flow section. Flap Gasket Twin-lip profile to maintain integrity. Plastic Flap Rigid PVC injection moulded. Removable for servicing. Inspection Chamber Full access for pipe cleaning or rodding. Design enables uninterrupted flow. Low offset (7mm) suitable for installing in an existing drainage system Removable double flap, prevents rat ingress Stable base Co-moulded seal Closing handle No screws Lenham, Maidstone, Kent ME17 2DE Tel: marketing@marleypd.com marley.co.uk

WEST LONDON PIPELINE AND STORAGE LIMITED AND UNITED KINGDOM OIL PIPELINES LIMITED

WEST LONDON PIPELINE AND STORAGE LIMITED AND UNITED KINGDOM OIL PIPELINES LIMITED WEST LONDON PIPELINE AND STORAGE LIMITED AND UNITED KINGDOM OIL PIPELINES LIMITED WLPS BUNCEFIELD REBUILD Flood Risk Assessment Green Lane Hemel Hempstead Hertfordshire HP2 7HZ September 2009 Prepared

More information

Recommendations for future developments

Recommendations for future developments C Recommendations for future developments C.1 Reducing flood risk through site layout and design C.1.1 C.1.2 Flood risk should be considered at an early stage in deciding the layout and design of a site

More information

Vital Earth Composting Facility Flood Risk and Drainage Statement

Vital Earth Composting Facility Flood Risk and Drainage Statement Vital Earth Flood Risk and Drainage Statement Final December 2011 Prepared for Vital Earth Ltd Revision Schedule Flood Risk and Drainage Statement December 2011 Rev Date Details Prepared by Reviewed by

More information

FLOOD RISK ASSESSMENT AND DRAINAGE STRATEGY

FLOOD RISK ASSESSMENT AND DRAINAGE STRATEGY FLOOD RISK ASSESSMENT AND DRAINAGE STRATEGY London Rd. WATERLOOVILE FOR McCarthy & Stone Ltd. July 2010 Such Salinger Peters Ltd 30558-1- Flood Risk Assessment & Drainage Strategy Contents Paragraph Page

More information

London Borough of Waltham Forest LOCAL FLOOD RISK MANAGEMENT STRATEGY. Summary Document

London Borough of Waltham Forest LOCAL FLOOD RISK MANAGEMENT STRATEGY. Summary Document LOCAL FLOOD RISK MANAGEMENT STRATEGY Summary Document October 2013 Local Flood Risk Management Strategy Summary 1 Introduction 2 Partner responsibilities 3 What do we know about flooding in the borough?

More information

Chapter 9: Water, Hydrology and Drainage Land West of Uttoxeter

Chapter 9: Water, Hydrology and Drainage Land West of Uttoxeter Chapter 9: Water, Hydrology and Drainage Land West of Uttoxeter ENVIRONMENTAL STATEMENT: VOLUME 1 9.1 INTRODUCTION 9.1.1 This Chapter considers the effects of the Project on surface water and groundwater

More information

Flood Risk Assessment and Drainage Statement

Flood Risk Assessment and Drainage Statement Trinity College, Cambridge Proposed Relocation of Felixstowe Rifle Range, Land north of Nicholas Road, Trimley St Mary, Felixstowe Quality Assurance Site name: Client name: Proposed Relocation of Felixstowe

More information

Groundwater Flooding: a UK Perspective

Groundwater Flooding: a UK Perspective Groundwater Flooding: a UK Perspective David Macdonald British Geological Survey Maclean Building Crowmarsh Gifford Wallingford OX10 8BB Tel 01491 838800 NERC All rights reserved Talk outline Definition

More information

Proposed Re-development, At 321 London Road, Wyberton. Flood Risk Assessment - Revised

Proposed Re-development, At 321 London Road, Wyberton. Flood Risk Assessment - Revised Proposed Re-development, At 321 London Road, Wyberton Flood Risk Assessment - Revised Prepared By: C Mason C.Eng M.I.C.E May 2015 Contents Page No. 1. Introduction 2 2. Site Description 2 3. Flood Hazard

More information

Littleport Co-located Schools

Littleport Co-located Schools Littleport Co-located Schools February 2015 Morgan Sindall Littleport Co-located Schools 330763 BNI BSE 003 C P:\Cambridge\Murdoch\EST\PROJECTS\330763 Littleport Co-located Schools\12.0 Documents\12.2

More information

INFRASTRUCTURE, FLOOD PROTECTION AND REMEDIATION. Infrastructure Flood Protection Remediation Policies

INFRASTRUCTURE, FLOOD PROTECTION AND REMEDIATION. Infrastructure Flood Protection Remediation Policies INFRASTRUCTURE, FLOOD PROTECTION AND REMEDIATION Infrastructure Flood Protection Remediation Policies DRAFT POOLBEG PLANNING SCHEME 196 FIGURE 9.1: UTILITIES WAYLEAVES Electricity Cables 8m Wayleave for

More information

Westminster City Council s Residential Basement Report Prepared for Westminster City Council July 2013

Westminster City Council s Residential Basement Report Prepared for Westminster City Council July 2013 Westminster City Council s Residential Basement Report Prepared for Westminster City Council July 2013 Alan Baxter Westminster City Council s Residential Basement Report Prepared for Westminster City

More information

Flooding in London. Figure 1 New commercial and residential developments on the Thames floodplain

Flooding in London. Figure 1 New commercial and residential developments on the Thames floodplain Flooding in London Abstract London faces a major risk of flooding. London s floods are caused by a mixture of river processes, tidal flooding and drains/sewers unable to cope with the volume of water.

More information

Proposed Residential Development Land off Cody Road Waterbeach Cambridgeshire. Flood Risk Assessment

Proposed Residential Development Land off Cody Road Waterbeach Cambridgeshire. Flood Risk Assessment Land off Cody Road Waterbeach Cambridgeshire Cedar Barn, White Lodge, Walgrave, Northampton, NN6 9PY T: F: E: W: 01604 781811 01604 781999 mail@jppuk.net jppuk.net Proposed Residential Development Land

More information

City of Edmonton Page 1 of 5 Foundation Drain Discharge Collection System Guideline November, 2005

City of Edmonton Page 1 of 5 Foundation Drain Discharge Collection System Guideline November, 2005 City of Edmonton Page 1 of 5 This guideline will apply to all new developments involving singledetached, semi-detached or duplex houses in the City of Edmonton effective January 1, 2006. Preamble: This

More information

List of Figures List of Abbreviations Executive Report

List of Figures List of Abbreviations Executive Report Table of Contents List of Figures List of Abbreviations Executive Report (ii) (iii) (iv) 1. INTRODUCTION... 1 1.1 BACKGROUND TO THE GDSDS... 1 1.2 BACKGROUND INVESTIGATIONS... 1 1.3 REPORT OBJECTIVES...

More information

Greater Dublin Strategic Drainage Study Regional Drainage Policies - Volume 2 New Development

Greater Dublin Strategic Drainage Study Regional Drainage Policies - Volume 2 New Development 7 SPECIFICATIONS There is currently no Irish specification for construction of drainage works, or water supply works. There are several publications that give guidance on drainage works, such as the Building

More information

DRAINAGE MANAGEMENT PLAN. HERTFORDSHIRE RESIDUAL WASTE TREATMENT PLANT Hertfordshire County Council

DRAINAGE MANAGEMENT PLAN. HERTFORDSHIRE RESIDUAL WASTE TREATMENT PLANT Hertfordshire County Council DRAINAGE MANAGEMENT PLAN HERTFORDSHIRE RESIDUAL WASTE TREATMENT PLANT Hertfordshire County Council EMPLOYER: Veolia Environmental Services (UK) Plc Veolia House 154A Pentonville Road London N1 9PE Copy

More information

Action plans for hotspot locations - Ash Study

Action plans for hotspot locations - Ash Study Appendix 9 Action plans for hotspot locations - Ash Study Ash Vale North 1. Local evidence indicates the culvert could not discharge during December 2013 because the outlet was blocked on the western side

More information

Rainwater is directed away from walls at surface. Any water infiltrating is captured in drains below foundation

Rainwater is directed away from walls at surface. Any water infiltrating is captured in drains below foundation Ground Surface Rainwater is directed away from walls at surface. Any water infiltrating is captured in drains below foundation Ground Surface Soil Ground Water Level Basement Wall Groundwater drains to

More information

Sutton Harbour Holdings PLC. March 2007

Sutton Harbour Holdings PLC. March 2007 Sutton Harbour Holdings PLC March 2007 Contents!! " # # $ % % &'(&'' ) ) ( * + ', *!$ -,!'! #. / $$ #% 00& ' 00&1 $ Executive Summary!! " WSP Development and Transportation has been engaged by Sutton

More information

London Borough of Croydon Local Flood Risk Management Strategy

London Borough of Croydon Local Flood Risk Management Strategy London Borough of Croydon Local Flood Risk Management Strategy Summary 2014-2020 Introduction In response to the severe flooding across large parts of England and Wales in summer 2007, the Government has

More information

1.2 This technical note provides a preliminary investigation into the Flood Risk and provides outline drainage strategies.

1.2 This technical note provides a preliminary investigation into the Flood Risk and provides outline drainage strategies. ODYSSEY MARKIDES TECHNICAL NOTE PROJECT : CHAILEY HOUSE, BLEWBURY JOB NO. : 14-216 NOTE TITLE : PRELIMINARY FLOODING AND DRAIANGE AUTHOR : STEVEN ROOTH APPROVED : ANDREAS MARKIDES DATE : 02/09/2014 1.0

More information

NOVEMBER 2009 [ISSUE 5]

NOVEMBER 2009 [ISSUE 5] 375 401 BRIGHTON ROAD CROYDON FLOOD RISK ASSESSMENT CLIENT: TRITHING LTD [ISSUE 5] Head Office: Unit 2 York House Edison Park Dorcan Way Swindon Wiltshire SN3 3RB Tel. 01793 619965 Fax. 01793 619967 Email:

More information

Strategic Flood Risk Assessment

Strategic Flood Risk Assessment local development framework Strategic Flood Risk Assessment LOCAL DEVELOPMENT FRAMEWORK ROYAL BOROUGH OF KINGSTON UPON THAMES Level 1 and 2 April 2011 Contents Executive Summary 5 Part 1 - Aiding Planning

More information

1 in 30 year 1 in 75 year 1 in 100 year 1 in 100 year plus climate change (+30%) 1 in 200 year

1 in 30 year 1 in 75 year 1 in 100 year 1 in 100 year plus climate change (+30%) 1 in 200 year Appendix C1 Surface Water Modelling 1 Overview 1.1 The Drain London modelling was designed to analyse the impact of heavy rainfall events across each London borough by assessing flow paths, velocities

More information

Development at 2 St Albans Road, Kingston, London, KT25HQ

Development at 2 St Albans Road, Kingston, London, KT25HQ Development at SuDS Report. Prepared for: Report prepared by: Dave Alonso Divine Ideas (UK) ltd Date: August 2015 Project/Issue number: Appendices Attached: 1510/01/SuDS A, B & C Divine Ideas (UK) Ltd

More information

FLOOD RISK AND SURFACE WATER DRAINAGE ASSESSMENT HILLHOUSE RESTORATION SITE, OFF JAMESON ROAD, THORNTON CLEVELEYS ON BEHALF OF NPL ESTATES

FLOOD RISK AND SURFACE WATER DRAINAGE ASSESSMENT HILLHOUSE RESTORATION SITE, OFF JAMESON ROAD, THORNTON CLEVELEYS ON BEHALF OF NPL ESTATES FLOOD RISK AND SURFACE WATER DRAINAGE ASSESSMENT HILLHOUSE RESTORATION SITE, OFF JAMESON ROAD, THORNTON CLEVELEYS ON BEHALF OF NPL ESTATES Integra Consulting Engineers Limited NS / 2543 Fountain House

More information

9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES. Hunter Underground Systems

9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES. Hunter Underground Systems 9.00 THE USE OF HUNTER LAND DRAINAGE PERFORATED PIPES Hunter Underground Systems 9.01 General 9.02 Surface water Drainage 9.03 Groundwater Drainage 9.04 Dispersal of Septic Tank Effluent 9.01 The use of

More information

September 2007. September 2013. Consulting Structural and Civil Engineers. 100 St John Street London EC1M 4EH. info @ akt-uk.com www.akt-uk.

September 2007. September 2013. Consulting Structural and Civil Engineers. 100 St John Street London EC1M 4EH. info @ akt-uk.com www.akt-uk. Consulting Structural and Civil Engineers 100 St John Street London EC1M 4EH T +44 (0) 20 7250 7777 F +44 (0) 20 7250 7555 info @ akt-uk.com www.akt-uk.com 3290 A031234 The 196-222 Joseph Kings Bloggs

More information

CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD NORTH RIDGEVILLE, OH 44039 (440) 353-0819 WWW.NRIDGEVILLE.ORG

CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD NORTH RIDGEVILLE, OH 44039 (440) 353-0819 WWW.NRIDGEVILLE.ORG CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD NORTH RIDGEVILLE, OH 44039 (440) 353-0819 WWW.NRIDGEVILLE.ORG WHY IS THERE WATER IN MY BASEMENT? There are two major sources of water in a basement as the

More information

Newbiggin House Farm,

Newbiggin House Farm, Newbiggin House Farm, Near Waberthwaite Flood Investigation Report 32 Flood Event 30/8/2012 Cumbria County Council Version Undertaken by Reviewed by Approved by Date Preliminary Colin Parkes Anthony Lane

More information

London Road, Rayleigh Essex Flood Risk Assessment Addendum

London Road, Rayleigh Essex Flood Risk Assessment Addendum FINAL Countryside Properties (UK) Limited Submitted by AECOM 6-8 Greencoat Place London SW1P 1PL London Road, Rayleigh Essex Flood Risk Assessment May 2015 i Limitations AECOM Infrastructure & Environment

More information

SANITARY SEWER BACKUP. Causes & Prevention

SANITARY SEWER BACKUP. Causes & Prevention SANITARY SEWER BACKUP Causes & Prevention A. PURPOSE The purpose of this publication is twofold: 1. It provides homeowners with basic information on the causes of sanitary sewer backups. 2. It provides

More information

Flood Risk Assessment and Drainage Impact Assessment: Planning Guidance for Developers

Flood Risk Assessment and Drainage Impact Assessment: Planning Guidance for Developers Flood Risk Assessment and Drainage Impact Assessment: Planning Guidance for Developers Development and Regeneration Services Glasgow City Council 229 George Street Glasgow G1 1QU May 2011 1. Introduction...-

More information

90 Brighton Road, Surbiton, Surrey

90 Brighton Road, Surbiton, Surrey 90 Brighton Road, Surbiton, Surrey Civil and Structural Engineering Basement Feasibility Report Mixed Use Scheme 108802-REP-002 March 2015 Contents 1. Executive Summary... 3 2. Site Description and Constraints...

More information

East Riding of Yorkshire Council

East Riding of Yorkshire Council East Riding of Yorkshire Council Lead Local Flood Authority Interim Standing Advice Revision A - April 2015 1. Introduction From April 2015 the Lead Local Flood Authority (LLFA) became a statutory consultee

More information

Downspout Disconnection Program FAQs

Downspout Disconnection Program FAQs Why is the Village making downspout disconnection mandatory? A mandatory downspout disconnection has been the law for several years in La Grange Park. All gutter downspouts must be disconnected from the

More information

How To Prevent Flooding From Groundwater

How To Prevent Flooding From Groundwater Flooding from groundwater Practical advice to help you reduce the impact of flooding from groundwater We are the Environment Agency. It s our job to make people aware of flooding from rivers and the sea,

More information

DISTRICT OF COLUMBIA WATER AND SEWER AUTHORITY. a guide to PREVENTING SEWER BACKUPS AND FLOODING

DISTRICT OF COLUMBIA WATER AND SEWER AUTHORITY. a guide to PREVENTING SEWER BACKUPS AND FLOODING DISTRICT OF COLUMBIA WATER AND SEWER AUTHORITY a guide to PREVENTING SEWER BACKUPS AND FLOODING Sewer backups and flooding can damage District homes and businesses. Sewer blockages are most commonly found

More information

Jay R. Smith Mfg. Co.

Jay R. Smith Mfg. Co. Jay R. Smith Mfg. Co. Automatic Backwater Valve SMITH CUSTOMER DRIVEN FLOOD-GATE FEATURES Index Page Flood-Gate Features and Applications 2 How Flood-Gate Works 3 Flood-Gate Operation & Approvals 4 Valve

More information

Mandatory Weeping Tile Disconnection to Reduce the Impact of Basement Flooding

Mandatory Weeping Tile Disconnection to Reduce the Impact of Basement Flooding Mandatory Weeping Tile Disconnection to Reduce the Impact of Basement Flooding May 26, 2011 Kyle Chambers, P.Eng. Environmental and Engineering Services Department City of London kjchambe@london.ca 519-661-2500

More information

Managing Surface Water Flooding in Paddock Wood Briefing note - June 2011

Managing Surface Water Flooding in Paddock Wood Briefing note - June 2011 Managing Surface Water Flooding in Paddock Wood Briefing note - June 2011 Information for Editors What is the reason for this initiative? 1. Legal Requirements The main drivers are the Flood Risk Regulations

More information

CHAPTER 11 STORM DRAINAGE

CHAPTER 11 STORM DRAINAGE CHAPTER 11 STORM DRAINAGE SECTION 11 GENERAL 11.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. 11.2 Where required. All roofs,

More information

Protect Your Home From Flooding. A guide for Lethbridge Residents

Protect Your Home From Flooding. A guide for Lethbridge Residents Protect Your Home From Flooding A guide for Lethbridge Residents Every year, millions of litres of water flow into the City of Lethbridge s stormwater and wastewater collection systems from residential

More information

London Borough of Merton Local Flood Risk Management Strategy

London Borough of Merton Local Flood Risk Management Strategy Local Flood Risk Management Strategy Summary 2014-2020 Introduction In response to the severe flooding across large parts of England and Wales in summer 2007, the Government has recently enacted the Flood

More information

Shower and Floor Gullies Channel Drain and Tile Drain SECTION

Shower and Floor Gullies Channel Drain and Tile Drain SECTION Shower and Floor Gullies Channel Drain and Tile Drain SECTION 2 Shower and Floor Gullies, Channel Drain and Tile Drain 29 General Information Shower and Floor Gullies McAlpine has responded to market conditions

More information

Flood Risk Management in Southwark

Flood Risk Management in Southwark Flood Risk Management in Southwark 1 Presented to Borough & Bankside Community Council 25 th April 2012 By Flood and Drainage Team Agenda Item 11 IN BRIEF Background Legislation What have we done? What

More information

2 ND SEPTEMBER 2014. Report of the Bi-Borough Executive Director for Transport and Technical Services

2 ND SEPTEMBER 2014. Report of the Bi-Borough Executive Director for Transport and Technical Services London Borough of Hammersmith & Fulham COMMUNITY SAFETY, ENVIRONMENT & RESIDENTS SERVICES POLICY & ACCOUNTABILITY COMMITTEE 2 ND SEPTEMBER 2014 SURFACE WATER MANAGEMENT PLAN (SWMP) Report of the Bi-Borough

More information

Prepare a drainage system layout and specification notes for a low- rise building.

Prepare a drainage system layout and specification notes for a low- rise building. STUDENT MATERIALS Prepare a drainage system layout and specification notes for a low- Outcome 1 - rise building. In this outcome you will study the technology of below and above ground drainage systems.

More information

Household customer. Wastewater flooding guidelines. www.thameswateruk.co.uk

Household customer. Wastewater flooding guidelines. www.thameswateruk.co.uk Household customer Wastewater flooding guidelines www.thameswateruk.co.uk We are very sorry that you have recently suffered wastewater flooding to your property. This leaflet has been designed to answer

More information

Report Reference: gauges below. Recommendations are on page 2 and information about flood resistance and Sample resilience measures is on page 4.

Report Reference: gauges below. Recommendations are on page 2 and information about flood resistance and Sample resilience measures is on page 4. Flood Report This report is issued for the property described as: Flood Risk Assessment FURTHER ACTION Sample Street, Sample Town, UK Professional Opinion The Site falls within an area which has an elevated

More information

Thames Water key Messages for London Borough of Ealing 25 th October 2005

Thames Water key Messages for London Borough of Ealing 25 th October 2005 Thames Water key Messages for London Borough of Ealing 25 th October 2005 Item 1: Drainage & ownership The area of drainage is complex. Thames Water, the Local Authority, the Environment Agency and property

More information

BASEMENT FLOODING. Prevention Guide for. Homeowners

BASEMENT FLOODING. Prevention Guide for. Homeowners BASEMENT FLOODING Prevention Guide for Homeowners 1 Did You Know? Floods are the most common hazards in Canada. Water damage is a common cause of loss for homeowner insurance. A heavy rainfall can result

More information

Mr & Mrs Clarke Proposed Development at The River House, Balderstone Flood Risk Assessment

Mr & Mrs Clarke Proposed Development at The River House, Balderstone Flood Risk Assessment Proposed Development at The River House, Balderstone D2192-FRA-01 5 Nov 2015 PSA Design Ltd Consulting Engineers The Old Bank House 6 Berry Lane Longridge Preston PR3 3JA Tel. 01772 786066 Fax. 01772 786265

More information

Chippenham Surface Water Management Plan Intermediate Assessment of Groundwater Flooding Susceptibility

Chippenham Surface Water Management Plan Intermediate Assessment of Groundwater Flooding Susceptibility Chippenham Surface Water Management Plan Intermediate Assessment of Groundwater Flooding Susceptibility Phase 1 & 2 November 2011 Prepared for Revision Schedule Surface Water Management Plan Intermediate

More information

Home Drainage & Causes of Basement Flooding. Water

Home Drainage & Causes of Basement Flooding. Water Home Drainage & Causes of Basement Flooding Understanding Drainage There are two separate sewer systems Eavestroughs & Downspout Road Property Line Floor Drain Catch basin Access Cover Weeping Tile House

More information

Preventing water damage in the basement

Preventing water damage in the basement Preventing water damage in the basement Thousands of home insurance claims are filed every year. Some losses are major, others aren t, but they re always an inconvenience and usually avoidable! As prevention

More information

The Town of Lakeshore Basement Flooding Information to Residents

The Town of Lakeshore Basement Flooding Information to Residents The Town of Lakeshore Basement Flooding Information to Residents The following information is intended for residents that have homes connected to Municipal storm and sanitary sewers. However, rural residents

More information

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT Page 1 CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT CIVIC CENTRE 2141 MAJOR MACKENZIE DRIVE MAPLE ONTARIO L6A 1T1 905-832-2281 Page 2 SECTION 1 - GENERAL OBJECTIVES To provide

More information

Does Part of My Basement Floor Have to Be Removed to Install. Where Does the Water from the Sump Pump Go?...Page 5

Does Part of My Basement Floor Have to Be Removed to Install. Where Does the Water from the Sump Pump Go?...Page 5 PROTECTIVE PLUMBING - WHAT IS IT? TABLE OF CONTENTS Protective Plumbing What is it?...page 1 What is Foundation Drainage?...Page 2 What is a Sump Pumping System?...Page 4 Does Part of My Basement Floor

More information

CITY OF ST. CA THARINE S. cn- Olc.4 BY-LAW NO. WHEREAS the Council of the Corporation of the City of St. Catharines, is

CITY OF ST. CA THARINE S. cn- Olc.4 BY-LAW NO. WHEREAS the Council of the Corporation of the City of St. Catharines, is ~: ~,,' " CITY OF ST. CA THARINE S BY-LAW NO. cn- Olc.4 A By-law to regulate sanitary and storm drainage. WHEREAS the Council of the Corporation of the City of St. Catharines, is authorized by the provisions

More information

Community of Tavistock July 16, 2005 Flooding Event Questionnaire

Community of Tavistock July 16, 2005 Flooding Event Questionnaire Community of Tavistock July 16, 2005 Flooding Event Questionnaire 1. Name, Street Address and Phone Number (Please Print) Tel. No. 2. Were you home during the rain storm in question: Yes No 3. a) Was there

More information

Creating the environment for business

Creating the environment for business 1. Introduction 1.1 Introduction to Water Cycle Strategies (WCS) 1.1.1 Background The water cycle describes the pathways and processes through which water moves through the natural and built environment,

More information

Protecting your property from Flooding. SCOTTISH ENVIRONMENT PROTECTION AGENCY www.sepa.org.uk

Protecting your property from Flooding. SCOTTISH ENVIRONMENT PROTECTION AGENCY www.sepa.org.uk SCOTTISH ENVIRONMENT PROTECTION AGENCY www.sepa.org.uk Protecting your property from Flooding Contents Introduction... 3 The sources of flooding... 4 Assessing the risk of flooding... 5 How water can enter

More information

good to know... SEWER BACKUP A guide to protecting your home

good to know... SEWER BACKUP A guide to protecting your home good to know... SEWER BACKUP A guide to protecting your home Maximize your insurance coverage Installing specific loss mitigation devices will maximize the coverage limit that is available to you on your

More information

Type of Sewer Systems. Solomon Seyoum

Type of Sewer Systems. Solomon Seyoum Type of Sewer Systems Solomon Seyoum 0 Learning objectives Upon completion of this lecture, the participants will be able to differentiate between types of sewer systems and discuss different aspects of

More information

Pollution Control NEW! NEW! Stormwater Attenuation Systems Sustainable Urban Drainage Solutions for Domestic & Commercial Applications. klargester.

Pollution Control NEW! NEW! Stormwater Attenuation Systems Sustainable Urban Drainage Solutions for Domestic & Commercial Applications. klargester. Pollution Control NEW! NEW! Stormwater Attenuation Systems Sustainable Urban Drainage Solutions for Domestic & Commercial Applications klargester.com Stormwater Attenuation Systems Sustainable Urban Drainage

More information

PRODUCT SELECTOR Pollution Control, Pumping and Rainwater Harvesting Systems

PRODUCT SELECTOR Pollution Control, Pumping and Rainwater Harvesting Systems PRODUCT SELECTOR Pollution Control, Pumping and Rainwater Harvesting Systems PACKAGE SEWAGE TREATMENT SYSTEM Clearwater treatment plants are ideal for single houses and employ the well proven aerobic biological

More information

1. Description. 2. List of Accessories included A B C F G H

1. Description. 2. List of Accessories included A B C F G H 1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin. The unit will start automatically. Please pay particular attention to the following: Possible danger to

More information

R E S I D E N T I A L H O U S I N G

R E S I D E N T I A L H O U S I N G HL 252 Rev. April 1997 R E S I D E N T I A L H O U S I N G CONTROLLING EXTERNALWATER PROBLEMS FOR RESIDENCES I II III IV V Lot Drainage Gutter Water Management Foundation Waterproofing Floor Slab Waterproofing

More information

Personal Tax Planning - What is a Resiliant or Resistance Measurement?

Personal Tax Planning - What is a Resiliant or Resistance Measurement? 1. Applicant Information Name of Applicant: Business Name (if applicable) Address: Postcode: Telephone Number Mobile: e-mail: 2. Property Flooded Address of property applying (if different from above),

More information

A13 Water Resources and Flood Risk

A13 Water Resources and Flood Risk A13 Water Resources and Flood Risk A13.1 A13.2 Water Resources Baseline Report (Mott MacDonald) A13.1 Crown copyright and database rights 2014 Ordnance Survey 100035971 Transport and Works Act 1992 London

More information

Royal Seal Gasketed Sewer Pipe

Royal Seal Gasketed Sewer Pipe Royal Seal Gasketed Sewer Pipe Royal Seal Gasketed Sewer Pipe Royal Seal gasketed sewer pipe with our specially designed Double Seal Locked-In (DSLI ) gasket is an extremely durable pipe with a leak proof

More information

Cambridge House, Henry Street, Bath BA1 1UR

Cambridge House, Henry Street, Bath BA1 1UR Flood Risk Assessment Cambridge House, Henry Street, Bath BA1 1UR For Full Planning application to BANES Council June 2011 Introduction This report is prepared as requested by B&NES to accompany the planning

More information

Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors

Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors Improving the flood resistance of your home Advice sheet 6: Flood-resilient This sheet provides guidance on identifying different types of floor, assessing the routes floodwater may enter, and describes

More information

First in Service First in Safety

First in Service First in Safety 7840 Nagle Avenue Morton Grove, Illinois 60053 847-470-5235 Fax - 847-965-9511 Wind Damage; Frequently Asked Questions: What can I do with branches that fall in my yard? Bring them out to the parkway;

More information

5.0 OVERVIEW OF FLOOD DAMAGE REDUCTION MEASURES

5.0 OVERVIEW OF FLOOD DAMAGE REDUCTION MEASURES 5.0 OVERVIEW OF FLOOD DAMAGE REDUCTION MEASURES Flood damage reduction consists of two basic techniques structural and non-structural. Structural methods modify the flood and take the flood away from people

More information

Bolton s Flood Risk Management Strategy

Bolton s Flood Risk Management Strategy Bolton s Flood Risk Management Strategy www.bolton.gov.uk Public Summary Bolton s Flood Risk Management Strategy Public Summary Introduction Over 5.5 million properties in England and Wales are at risk

More information

JULY 24, 2009 WEST-END FLOODING INVESTIGATION ACTION PLAN. Presentation to Insurance Companies 19 January 2012

JULY 24, 2009 WEST-END FLOODING INVESTIGATION ACTION PLAN. Presentation to Insurance Companies 19 January 2012 JULY 24, 2009 WEST-END FLOODING INVESTIGATION ACTION PLAN Presentation to Insurance Companies 19 January 2012 Topics of Discussion Investigation Levels of Service Cause of Flooding Analysis Undertaken

More information

Flood Risk Assessment Breakspear House, Hemel Hempstead. Kier Property. October 08

Flood Risk Assessment Breakspear House, Hemel Hempstead. Kier Property. October 08 Flood Risk Assessment Breakspear House, Hemel Hempstead. Kier Property October 08 Prepared by:... Approved by:... Simon Marcos Keith Searle Principal Engineer Associate Director Flood Risk Assessment Rev

More information

SANITARY SEWER SPECIFICATIONS

SANITARY SEWER SPECIFICATIONS SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,

More information

London Borough of Bexley. Bexley Strategic Flood Risk Assessment Level-1. Bexley SFRA Level-1 Report. August 2010

London Borough of Bexley. Bexley Strategic Flood Risk Assessment Level-1. Bexley SFRA Level-1 Report. August 2010 London Borough of Bexley Bexley Strategic Flood Risk Assessment Level-1 Bexley SFRA Level-1 Report Copyright and Non-Disclosure Notice The contents and layout of this report are subject to copyright owned

More information

Guide to working on Public Sewers

Guide to working on Public Sewers Guide to working on Public Sewers affected by Building Works Introduction Severn Trent Water Ltd requires the work to be done in order to protect the public sewer and minimise the risk of us having to

More information

Flood Risk & Surface Water Management. Page 1 of 20

Flood Risk & Surface Water Management. Page 1 of 20 Page 1 of 20 Flood Risk & Surface Water Management Flood Risk & Surface Water Management and the Planning Process Introduction The purpose of this document is to increase awareness of the potential of

More information

GUIDE TO SETTLEMENT OF CANTERBURY FLAT LAND CLAIMS

GUIDE TO SETTLEMENT OF CANTERBURY FLAT LAND CLAIMS GUIDE TO SETTLEMENT OF CANTERBURY FLAT LAND CLAIMS April 2013 i Introduction This guide focuses on repair methods for some of the types of land damage that occurred on flat residential land as a result

More information

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION 1. SCOPE Pipe subsoil drains shall be constructed in accordance with this specification and in conformity with the lines, grades and cross-sections shown

More information

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,

More information

Flood Repair and Renew Grant Guidance to Applicants

Flood Repair and Renew Grant Guidance to Applicants Flood Repair and Renew Grant Guidance to Applicants Purpose of the Fund Following an announcement by the Prime Minister on the 12 th February 2014, the Repair and Renew Grant (RRG) scheme has been established

More information

Flood Risk Assessment. For Application at: Brick House Farm Brick House Lane Hambleton Lancashire FY6 9BG

Flood Risk Assessment. For Application at: Brick House Farm Brick House Lane Hambleton Lancashire FY6 9BG Flood Risk Assessment For Application at: Brick House Farm Brick House Lane Hambleton Lancashire FY6 9BG Contents 1. Introduction 2. The Site 3. Flood Risk 4. Existing drainage 5. Proposed Development

More information

MAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT

MAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT Record MAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT Abandoned Gravity Private Combined Gravity Private Foul Gravity Private Surface Water Gravity Public Combined Gravity Public Foul Gravity Public

More information

Application for Repair and Renew Grant

Application for Repair and Renew Grant Application for Repair and Renew Grant 1. Applicant Information Name of Applicant: Business Name (if applicable) Address: Postcode: Telephone Number Mobile: e-mail: 2. Property Flooded Address of property

More information

Mitigating Basement Backups

Mitigating Basement Backups Mitigating Basement Backups Avon Lake Municipal Utilities 201 Miller Road Avon Lake, OH 44012 Tel: 440-933-6226 Emergency: 440-933-3229 www.avonlakewater.org April 28, 2011 This document was originally

More information

Land to the rear of the Black Bull Public House Flood Risk Assessment March 10, 2014 Version 1.0 Ref: RAB 148

Land to the rear of the Black Bull Public House Flood Risk Assessment March 10, 2014 Version 1.0 Ref: RAB 148 Land to the rear of the Black Bull Public House Flood Risk Assessment March 10, 2014 Ref: RAB 148 Lindsey Phillips Turnbull Tweedale Ltd 61 Oaken Lanes Codsall South Staffordshire WV8 2AW R A B C O N S

More information

Groundwater Flooding in Brighton and Hove City (February 2014)

Groundwater Flooding in Brighton and Hove City (February 2014) Section 19 Flood Investigations Report Groundwater Flooding in Brighton and Hove City (February 2014) May 2014 Revision Schedule Rev Date Details Author Checked and Approved by 1 April 2014 M Moran N Fearnley

More information

NON RETURN & FLAP VALVES

NON RETURN & FLAP VALVES RUR UK NON RTURN & P VVS RUR UK The Original and est - Rubber lexible ouplings and ushes INTROUTION P VVS The principle applications for flap valves are for surface water drainage associated with river,

More information

SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER

SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER Village of Shorewood, Wisconsin SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER Prepared By: Thomas A. Zoulek, P.E., LEED A.P. Vice President Mid City Plumbing & Heating

More information

OVER-HEAD SEWER ASSISTANCE GRANT

OVER-HEAD SEWER ASSISTANCE GRANT OVER-HEAD SEWER ASSISTANCE GRANT The Village of North Aurora has a vested interest in the proper operation of the North Aurora sanitary system. Understanding that some residential users of the sanitary

More information

PREVENTING WET OR FLO ODED BASEMENTS

PREVENTING WET OR FLO ODED BASEMENTS PREVENTING WET OR FLO ODED BASEMENTS TABLE OF CONTENTS Prevention Tips...Page 1 Why is there Water in my Basement?...Page 2 City of Saskatoon Sewer Systems...Page 3 Why Does Saskatoon Have Two Separate

More information

MARYLAND AVENUE BACKUPS DURING AUGUST 31, 2014 STORM EVENT COMMUNITY OUTREACH

MARYLAND AVENUE BACKUPS DURING AUGUST 31, 2014 STORM EVENT COMMUNITY OUTREACH MARYLAND AVENUE BACKUPS DURING AUGUST 31, 2014 STORM EVENT COMMUNITY OUTREACH MARYLAND AVENUE BACKUPS COMMUNITY OUTREACH MEETING AGENDA Introductions History of PWSA Actions August 31 Storm Impacts Short

More information