Dust Explosion Fundamentals: Ignition Criteria and Pressure Development
|
|
|
- Tyrone Green
- 10 years ago
- Views:
Transcription
1 Dust Explosion Fundamentals: Ignition Criteria and Pressure Development Robert Zalosh Firexplo Wellesley, MA Basic Concepts The five ingredients required for a dust explosion are: Combustible particulates sufficiently small to burn rapidly when ignited A suspended cloud of these combustible particulates at a concentration above the Minimum Explosible Concentration (MEC) Confinement of the dust cloud by an enclosure or partial enclosure Oxygen concentration greater than the Limiting Oxygen Concentration (LOC) for the suspended dust cloud Delayed ignition source of adequate energy or temperature to ignite the suspended cloud. The National Fire Protection Association (NFPA) has had several definitions of combustible dusts over the years. The current definition in NFPA 654 is a combustible particulate solid that presents a fire or deflagration hazard when suspended in air or some other oxidizing medium over a range of concentrations, regardless of particle size or shape. Previous editions of NFPA 654 and the 2004 edition of the NFPA Glossary of Terms define a combustible dust as any finely divided solid material that is 420 microns or smaller in diameter (material passing a U.S. No. 40 Standard Sieve) and presents a fire or explosion hazard when dispersed in air. The reason for the revision is that many combustible fiber segments, flat platelets, and agglomerates do not readily pass through a No. 40 sieve, but they can be dispersed to form a combustible dust cloud. In practice, questions of combustibility as well as particle size often arise when evaluating the potential explosion hazard of marginally small particles or mixtures of combustible and noncombustible particulates. Many laboratories doing dust explosibility tests have developed dust explosibility screening tests, also called Go/No Go tests, to deal with these questions. Chapter 4 of the CCPS Guidelines for Safe Handling of Powders and Bulk Solids describes some of these tests. The ASTM E27.05 Subcommittee is currently working on a revision to the ASTM E Standard Test Method for Pressure and Rate of Pressure Rise for Combustible Dusts to provide a standardized Go/No Go test for potentially combustible particulates. MEC values are determined in the U.S. per the ASTM E1515 test procedure involving tests with various dust concentrations and a pyrotechnic igniter in a 20-liter sphere. The MEC corresponds to the smallest concentration that produces a pressure at least twice as large as the initial pressure at ignition. Eckhoff (2003) reports that MEC values are not very sensitive to particle diameter for diameters less than about 60 μm, but increase significantly with increasing diameter above this approximate threshold. The majority of the materials listed in Eckhoff Table A.1 (2003) have MEC values in the range 30 to 125 g/m 3. These concentrations are sufficiently high that a 2 m thick cloud can prevent seeing a 25 watt bulb on the other side of the cloud (Eckhoff, 2003, p.9).
2 The confinement needed for a dust explosion is usually from the process equipment or storage vessel for the powder or dust. In the case of fugitive dust released from equipment and containers, the room or building itself can represent the confinement. Often, the dust cloud occupies only a fraction of the equipment or building volume, and the resulting explosion hazard is called a partial volume deflagration hazard. Pressures produced from partial volume deflagrations and the corresponding deflagration venting design bases are described in NFPA 68. Example applications include dust collectors and spray driers. LOC values for combustible dusts are also determined via tests in a 20-liter vessel, and the ASTM E27 Technical Committee is drafting an ASTM standard for LOC values. LOC values for various combustible powders and dusts listed in NFPA 69 Table C.1(b) are mostly in the range 9 v% to 12 v% O 2. Paragraph of NFPA 69 requires that the oxygen concentration for an inerted process system should be less than the measured LOC by at least 2 volume percent for systems in which the oxygen concentration is continually monitored and no greater than 60% of the LOC if the oxygen concentration is not monitored. Ignition Criteria Hot Temperatures One hot temperature ignition scenario entails a dust cloud accidentally entering a hot oven or furnace. This occurred in the CTA Acoustics phenolic resin dust explosion incident investigated by the U.S. Chemical Safety Board (CSB, 2005). The resin dust cloud in that incident was generated during cleaning of fugitive dust from the area around the oven. The minimum dust cloud oven ignition temperature is determined by oven tests described in ASTM E1491. These include a vertical oven called the Godbert-Greenwald furnace and a horizontal oven called the BAM furnace. BAM furnace minimum Auto-Ignition Temperatures (AITs) are usually 20 o C to 60 o C lower than the corresponding dust cloud ignition temperatures measured in the Godbert-Greenwald furnace. Most of the Godbert-Greenwald dust cloud ignition temperatures listed in Eckhoff s Table A.1 are in the range 420 o C to 660 o C. When the high temperature is on a hot surface of limited area, the required surface ignition temperature is higher than the standard furnace tests. Figure 1 shows some test data for surface areas in the range 20 mm 2 to 1000 mm 2, and comparison with the BAM furnace data.
3 Figure 1 Hot surface ignition temperature versus surface area (Eckhoff Figure 5.25) Examples of hot surface ignitions in dust explosion incidents include overheated failed bearings and driers. Clearly, the former would require a surface temperature much higher than the ignition temperature measured in the standard oven tests, but the latter might require a lower temperature than the standardized tests because of the possibility of a dust layer remaining in the drier for a long time. An aerated cell test described by Abbot (1990) and the CCPS Guidelines reference (2005) has been developed for drier hot layer ignition scenarios. The aerated cell test produces an exotherm onset temperature at which oxidation reactions leading to layer fires first occur. Most of the exotherm onset data reported by Abbot (1990) were in the range 125 o C to 175 o C. These temperatures are lower than the dust layer minimum hot surface ignition temperatures measured in the more common tests conducted in ambient air (ASTM E2021). Burning Embers and Agglomerates Smoldering or flaming particulate embers or agglomerates (also called smoldering nests) are often produced by frictional heating, e.g. during sanding or cutting, by local heating associated with hot work on equipment and ducts containing dust deposits, by powder accumulations on drier walls, and by small heat sources, e.g. a portable lamp, accidentally embedded in a particulate pile. If the hot embers or agglomerates remain stationary in a larger pile of combustible particulates, a larger fire can develop. On the other hand, if the embers/agglomerates are exposed to combustible dust cloud in an enclosure (perhaps a silo/hopper being filled), there is a potential for the ignition of a dust explosion. Tabulations of ignition sources involved in 426 German dust explosions from 1965 to 1985 (Eckhoff, 2003, Tables 1.6 and 1.7) indicate that smoldering nests were the most prevalent cause of those dust explosions in silos (28%), and in dryers (29%), and the second most frequent ignition source in dust collector explosions (11%). Zalosh et al. (2005) describe one dust explosion incident in which the hot nest was caused by some bolts falling into a hammermill used for pharmaceuticals production. More recent research (Gummer and Lunn, 2003) has shown that the ignitions in most of these reported incidents were probably due to flaming, rather than smoldering nests/agglomerates since the only dust cloud material that could be ignited by smoldering agglomerates banked up in a 10 cm diameter tray was sulfur, which has an exceptionally low AIT ( o C). Previous experiments cited by Gummer and Lunn
4 indicated that a minimum agglomerate burning area of 75 cm 2 and a minimum burning temperature of 900 o C were required to ignite dust clouds with AITs below 600 o C. The occurrence of agglomerate smoldering versus flaming combustion and versus selfextinguishment depends on the amount of air access and the coherence of the agglomerate. Burning agglomerate transport experiments reviewed by Gummer and Lunn (2003), showed that glowing agglomerates could be transported large distances through otherwise empty piping with air transport velocities of 10 and 20 m/s, but the glowing was extinguished rapidly when nonburning dust was added to the flow. The glowing particles were not able to ignite the flowing dust even though the dust concentration was above the MEC. Other tests showed that burning nests did not ignite fine sawdust in the transport duct, but did ignite the sawdust cloud when it reached the filter media dust collector at the end of the duct. Several vendors provide so-called spark/ember detection and extinguishing systems to prevent ignitions by burning agglomerates transported through ducting. Optical detectors sense the radiant energy from the burning embers or agglomerates, and the control module triggers water spray through nozzles situated at an appropriate distance downstream of the detector. Annex C of NFPA 654 describes these systems. Self-Heating Certain particulate materials are prone to self-heating that can potentially lead to spontaneous ignition. The predominant chemical reaction is low level oxidation. Examples of materials that can self-heat by oxidation at relatively low temperatures include ABS resin powder, activated carbon, coal (particularly Powder River Basin coal), and various chemical intermediates. Materials such as freshly manufactured/dried wood chips, anhydrous calcium hypochlorite, and hops are subject to self-heating by moisture absorption/condensation. Organic peroxides and other potentially unstable chemicals can self-heat by exothermic decomposition. Various agricultural materials, such as bagasse and soybeans, start self-heating by microbiological processes. In many of these and other materials, multiple self-heating mechanisms overlap and it is difficult to distinguish the dominant mechanism at a given temperature. Self-heating is typically manifested as smoldering in the interior of a large storage pile of particulates or in an accumulated layer in a dryer. If the smoldering particulates in the pile or dryer are subsequently disturbed and exposed to air, the smoldering can evolve into flaming. When the flaming nest or agglomerate is then transported to a hopper or dust collector, it can ignite the suspended dust cloud as discussed in the preceding section. Various laboratory tests have been developed to determine self-heating onset temperatures for different sample sizes and configurations. These include particulate basket tests in an isothermal oven, heated air flow tests with a slow rate of air temperature rise, and material in a package test to determine the Self-Accelerating Decomposition Temperature. Application of laboratory selfheating data to plant conditions requires use of appropriate volume scaling methods described in handbook references including Babrauskas (2003), the CCPS Guidelines (2005), and Gray (2002). In addition to showing how the self-heating onset temperature decreases with increasing size of the particulate pile or layer, the scaling relationships also can be used to assess how the expected time-to-ignition increases with the pile or layer size. The combination of laboratory data and the scaling equations can then be used to establish appropriate plant level precautions to prevent self-heating and spontaneous ignition.
5 Impact/Friction Impact and frictional heating during combustible powder processing and during maintenance/repairs involving cutting and grinding have been responsible for igniting many dust explosions. Grinders, hammermills, and other size reduction equipment are particularly prone to ignitions during operation. Blenders with rotating element tip speeds greater than 1 m/s are also vulnerable to this scenario. Tramp metal stuck in a screw conveyor or a particle classifier represents another frictional ignition scenario. The vulnerability of a combustible dust to impact/friction ignition is characterized in terms of the material spark Minimum Ignition Energy (MIE) and cloud Auto-Ignition Temperature (AIT). Testing to measure MIE values is described in ASTM E2019. Figure 2 shows the relationship between MIE and AIT values to determine which dusts can be ignited by impact or frictional contact between steel surfaces. For example, a dust with an MIE of 10 J should be immune to steel-steel frictional or impact ignitions as long as its AIT is greater than 275 o C. Dusts with lower MIE values but have larger AIT values still may not be prone to steel impact or frictional ignitions per Figure 2. Eckhoff (2003) cautions that simple MIE versus AIT correlations cannot be applicable to steel grinding and impact conditions that may be very different from the experiments leading to Figure 2 and similar plots. Babrauskas (2003) presented data on the minimum frictional force needed to ignite various dust clouds. Figure 2 Boundaries for steel surface frictional and impact ignition of dust clouds (from Babrauskas, 2003) One common friction ignition scenario is a blender with a rotating helical screw impeller. Jaeger (2001) provided guidance on how the mixing speed and blender fill level can be used to control frictional ignition hazards. He states that there is a negligible chance of ignition when the fill level is greater than 70%, no matter what the impeller tip speed is. When the tip speed is greater than 10 m/s and the fill level is less than 70%, there is a high probability of dust cloud ignition. At tip speeds between 1 m/s and 10 m/s and fill levels less than 70%, Jaeger provides a MIE versus AIT relationship analogous to that in Figure 2, to show which combustible dusts can be blended without any likelihood of ignition. Single impact spark ignition experiments described by Eckhoff (2003) have shown that the probability of igniting a corn starch dust cloud increased with increasing impact energy, and that it also depended on the impact velocity. Lower speed impacts produced a much greater probability of ignition than higher speed impacts for a given impact energy. The metal combinations involved in the impact also play an important role in the probability of ignition.
6 Steel-steel impacts and aluminum-steel impacts did not ignite corn starch dust clouds, whereas titanium impacts against rusty steel did ignite dusts with MIE values below roughly 10 mj. The titanium-rusty steel impacts produced thermite reaction sparks, while the aluminum-rusty steel impacts did not. Electrical Equipment Electrical equipment and wiring can potentially ignition dust clouds by sparks, arcs, or heated surfaces. Dust Ignitionproof equipment is enclosed in a manner that excludes dusts and does not permit arcs, sparks, or heat otherwise generated or liberated inside of the enclosure to cause ignition of exterior accumulations or atmospheric suspensions of a specified dust on or in the vicinity of the enclosure. UL 1203 describes the design, fabrication, and testing required to certify electrical equipment as Dust Ignitionproof. When electrical equipment and wiring is used in locations in which combustible dusts can be present, there is a need to establish the Class II hazardous location classification of the area. Per NFPA 70, a Class II Division 1 location is one in which combustible dust is in the air under normal operating conditions in quantities to produce explosive or ignitable mixtures, or where mechanical failure or abnormal operation of machinery or equipment might cause such explosive or ignatible mixtures to be produced, and might also provide a source of ignition through simultaneous failure of electrical equipment (NFPA 70 definition). There are three possible conditions for the existence of a Class II Division 2 location. The first condition is a location in which combustible dust due to abnormal operations may be present in the air in quantities sufficient to produce explosive or ignitable mixtures. The second and third conditions refer to dust accumulations that could be either suspended or ignited during equipment malfunctions or abnormal operations. Class II locations are further classified as Group E, F, or G depending on the type of dust material. NFPA 499 provides guidance and examples for the assignment of appropriate Class II Division 1 and 2 classifications for combustible powder and dust processing and handling operations. NFPA 70 Article permits Dust Ignitionproof electrical equipment in Class II Division 1 and 2 areas. Similarly, intrinsically safe electrical equipment (in which all circuits cannot produce a spark or thermal effect capable of igniting a dust cloud per UL 913) is also allowed in these areas. Dusttight equipment is permitted in Class II Division 2 areas. Article 502 of NFPA 70 describes the types of acceptable wiring in Class II Division 1 and 2 locations. Threaded metal conduit together with dusttight boxes and fittings is one acceptable method commonly used. The use of electrical sealing putty at boundaries of Class II areas is also described in Article 502. Electrostatic Discharges Electrostatic discharges occur are preceded by charge accumulation on insulated surfaces, ungrounded conductors (including human bodies), or particulate materials with high resistivities. The subsequent electrostatic discharge is only an ignition threat if it is sufficiently energetic in comparison to the Minimum Ignition Energy of the pertinent dust cloud. Different types of electrostatic discharges have correspondingly different maximum discharge energy capacities as listed in Table 1.
7 Table 1 Types of Electrostatic Discharge Type of Discharge Maximum Energy 1 (mj) Examples Corona 0.1 Wires, Type D Bulk Bags Brush 1-3 Flexible boots and socks Bulking Brush 1-10 Piles of powders with resistivities > 10 9 Ω-m in hopper or silo Propagating Brush Boots, plastic pipe or duct Spark > 10,000 Ungrounded conductor, e.g. baghouse cage, or person, e.g. packager 1. Maximum energies are from Figure of NFPA Since combustible dust MIE values are substantially greater than 0.1 mj, corona discharges are not an ignition threat. In fact, Type D bulk bags are deliberately designed and fabricated to safely dissipate accumulated charges via corona discharges. A recent study by Glor and Schwenzfeuer (2005) has shown that brush discharges were not able to ignite clouds of dusts with MIE values less than 1 mj, thus correcting a different impression obtained from earlier studies. Since brush discharges do ignite flammable vapors, they are an ignition threat for hybrid dust-vapor mixtures such as occur in processes with flammable solvents. The most hazardous situation for a bulking brush discharge ignition is filling a hopper with a high resistance material combination of large particles with diameters over 1 mm together with fines with a MIE less than 10 mj. Some of the dusts listed in Eckhoff s Table A.1 (2003) with MIE values less than 10 mj include certain wood dusts (with 39 weight % < 20 μm), naphthalene with a median diameter of 95 μm, zinc stearate with a 13 μm median diameter, and toner with median diameter of 23 μm and less. Transport and processing of these easily ignitable dusts require special precautions to prevent brush and bulking brush discharges. Precautions provided in NFPA 77 Chapter 9 and in Britton s (1999) chapter 6 are especially important for these dusts. A propagating brush discharge can occur when a charged non-conductor is in direct contact with a conductive surface, such as a metal surface coated with a plastic film or a layer of high resistivity powder (Glor, 2005). The Propagating brush discharge occurs when the surface charge density is sufficiently large to cause electrostatic breakdown at the nonconductor surface. Streamers carry the surface charge to a central region where it intensifies as shown in Figure 4. Propagating brush discharges can ignite dusts with MIE values less than about 3 J. Figure 3 Propagating brush discharge (from Britton, 1999)
8 Sparks are the most energetic type of electrostatic discharge. Spark prevention requires rigorous grounding and bonding of conductive objects such as duct sections and connections to hoppers. FM Global Data Sheet 5-8 also recommends maintaining humidity levels at 60% to 70% as another spark prevention measure. Pressure Development in Dust Deflagrations Pressures in Single Enclosures Deflagration pressures resulting from an ignition in process equipment depend on the dust material, particle size distribution, and concentration distribution within the enclosure, and the size and location of equipment openings that allow the burning and unburned dust to be vented. If there were no openings in the equipment, the deflagration pressure would correspond to the pressures measured in ASTM E1226 tests. Since these pressures are greater than 2 bar gauge, even at concentrations near the MEC, most process equipment cannot withstand the closed vessel deflagration pressure. Pressures at the worst-case dust concentration often range from 7 to 10 bar. Therefore, NFPA 654 paragraph requires process equipment with an explosion hazard to be equipped with one of six specified alternative methods of explosion protection. The most commonly used dust explosion protection method is deflagration venting. The effectiveness of deflagration vents depends on the level of turbulence in the process vessel and the vessel size and shape as well as the vent design and the dust characteristics cited above. NFPA 68 Chapter 7 provides dust deflagration design requirements. Deflagrations Involving Interconnected Equipment When process vessels are connected by pipe and ducting, a dust explosion ignited in one vessel can often propagate into the interconnected vessels. Pressures produced in the interconnected vessels can be significantly greater than the pressure that would be experienced in isolated vessels. The reason for the enhanced deflagration pressure in a totally enclosed system is that the initiating explosion pressurizes the interconnected vessels, so that the deflagration that eventually occurs when the flame reaches the dust cloud in the other vessels starts at a higher initial pressure. This effect is called pressure piling. Lunn et al. (1996) conducted interconnected vessel tests with coal dust and toner that had P max values of 7.7 bar g and 7.1 bar g, respectively, in single closed vessel tests. When the explosions were initiated in a 20 m 3 vessel and allowed to propagate via a 25 cm diameter pipe into a 4 m 3 vessel with a dust cloud, the measured pressures were 16 to 20 bar g, i.e. more than twice the P max values. Inter-vessel deflagration propagation and pressure piling does not always occur. Lunn et al. (1996) did not observe deflagration propagation in tests with a 15 cm diameter pipe, and later vented explosion tests using a pipe with a sharp 90 degree elbow produced pressure enhancement in only one of many tests conducted (Skjold, 2007). However, when the deflagration does propagate into the interconnected vessels, the jet flame ignition of the dust cloud in the second vessel produces a much more rapid rate of burning and associated pressure rise. The more rapid burning and pressure rise can render explosion venting or explosion suppression systems ineffective in the second vessel. Hence, there is often a need for explosion isolation systems to supplement the installed explosion protection for an individual vessel. NFPA 69 provides the requirements for various types of passive and active explosion isolation systems.
9 Secondary Dust Explosions Most of the casualties from dust explosions occur when the initiating explosion within some equipment or enclosure breaches the equipment/enclosure and causes a secondary explosion in the surrounding building. The secondary explosion occurs when dust deposits on exposed surfaces in the building are lifted by the blast wave emanating from the breached equipment/enclosure, and then are ignited by the flame vented from the breached equipment/enclosure. Figure 4 shows a dust cloud formed when an air blast wave propagated over a corn starch layer in experiments conducted by Scherpa (2002). Air blast velocities of 12 to 48 m/s lifted 13% to 44% of the deposited cornstarch. Figure 4. Corn starch dust cloud produced from air blast over dust layer (from Scherpa, 2002) These secondary dust explosions are particularly devastating because they produce large burning dust clouds and pressures beyond the strength of most buildings. The two critical prevention measures are the installation of effective explosion protection for the combustible powder/dust processing and handling equipment (including explosion isolation), and minimizing combustible dust layer accumulations on equipment and building surfaces. NFPA 654 provides requirements for maximum allowable dust layer thicknesses and surface areas with dust accumulations. Some of the other papers at this Symposium offer guidance on how different types of industrial facilities are attempting to meet these requirements, and possibly improve them. References Abbot, J. Prevention of Fires and Explosions in Dryers, Institute Chem Engrs, ASTM E , Standard Test Method for Pressure and Rate of Pressure Rise for Combustible Dusts, American Society for Testing and Materials, ASTM E , Standard Test Method for Minimum Autoignition Temperature of Dust Clouds, American Society for Testing and Materials, ASTM E , Standard Test Method for Minimum Explosible Concentrations of Combustible Dusts, American Society for Testing and Materials, ASTM E Standard Test Method for Minimum Ignition Energy of a Dust Cloud in Air, American Society for Testing and Materials, ASTM E Standard Test for Hot Surface Ignition Temperature of Dust Layers, American Society for Testing and Materials, Babrauskas, V., Ignition Handbook, Fire Science Publishers, Britton, L., Avoiding Static Ignition Hazards in Chemical Operations, AIChE CCPS, 1999.
10 CCPS, Guidelines for Safe Handling of Powders and Bulk Solids, AIChE Center for Chemical Process Safety, CSB, Investigation Report. Combustible Dust Fire and Explosions, CTA Acoustics, Inc., Chemical Safety Board, February Eckhoff, R., Dust Explosions in the Process Industries, 3 rd Edition, Gulf Professional Publishing, Gray, B., Spontaneous Combustion and Self-Heating, SFPE Handbook of Fire Protection Engineering, 3 rd Edition, pp , SFPE, NFPA, Glor, M., Electrostatic Ignition Hazards in the Process Industries, J. of Electrostatics, v 63, pp , Glor, M. and Schwenzfeuer, K., Direct Ignition Tests with Brush Discharges, J. of Electrostatics, v 63, pp , Gummer, J. and Lunn, G., Ignitions of Explosive Dust Clouds by Smouldering and Flaming Agglomerates, J. of Loss Prevention in the Process Industries, v. 16, pp 27-32, Jaeger, N., Safety strategy against potential hazards due to the handling of powders in a blending unit, J. Loss Prevention in the Process Industries, v. 14, pp , Lunn, G., Holbrow, P., Andrews, S., and Gummer, J., Dust explosions in totally enclosed interconnected vessel systems, J. Loss Prevention in the Process Industries, v. 9, pp , NFPA 68, Explosion Protection by Deflagration Venting, National Fire Protection Association, NFPA 69, Standard on Explosion Prevention Systems, NFPA 70, National Electrical Code, National Fire Protection Association, NFPA 77, Recommended Practice on Static Electricity, NFPA 499, Recommended Practice for the Classification of Combustible Dusts and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas, National Fire Protection Association, NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids, National Fire Protection Association, Scherpa, T., Secondary Dust Cloud Formation from an Initiating Blast Wave, WPI M.S. Thesis, Skjold, T., "Review of the DESC project," Journal of Loss Prevention in the Process Industries v. 20: , UL 913, Standard for Safety, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III, Division 1, Hazardous (Classified) Locations, Underwriters Laboratories, UL 1203, Explosionproof and Dust-Ignitionproof Electrical Equipment for Hazardous (Classified) Locations, Underwriters Laboratories, Zalosh, R., Grossel, S., Kahn, R., and Sliva, D., Safely Handle Powdered Solids, Chemical Engineering Progress, v. 101, pp , 2005.
Combustible Dust. Overview
Combustible Dust Michael Wacker Industrial Hygienist Madison, WI Area OSHA Office Overview History of Combustible dust What is combustible dust Some recognized hazards OSHAs Combustible Dust NEP What does
9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration
OSHA Combustible Dust Inspections Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration Overview Background Information OSHA Combustible
ARE YOU IN COMPLIANCE WITH THE OSHA COMBUSTIBLE DUST DIRECTIVE? Revised March 18, 2009
Kidde Fenwal, Inc. Industrial Explosion Protection Group A UTC Fire & Security Company 400 Main Street Ashland, MA 01721 Tel 508-881-2000 Fax 508-485-3115 www.fenwalprotection.com FENWAL Protection Systems
AIHA Professional Development Conference by Daniel Brechko, Managing Consultant
AIHA Professional Development Conference by Daniel Brechko, Managing Consultant 952-334-9580 [email protected] Basics: Fire vs. Explosion OSHA NEP and NFPA 654 What is a combustible dust? Hazard
WEEKLY SAFETY MEETING All Euramax Subsidiaries COMBUSTIBLE DUST. Safety Meeting Contents. Meeting Notice. Leaders Guide.
Safety Meeting Contents Meeting Notice Leaders Guide Employee Handout Employee Quiz Meeting Sign-In Sheet Employee Puzzle PRIOR TO THE WEEKLY MEETING: - Post the meeting notice by the timeclock - Read
Combustible Dust Ensuring Safety and Compliance. Brian Edwards, PE Conversion Technology Inc. ENVIRONMENTAL & SAFETY CONSULTING ENGINEERS
Combustible Dust Ensuring Safety and Compliance Prepared for: REGION IV VPPPA Presented by: Brian Edwards, PE Conversion Technology Inc. ENVIRONMENTAL & SAFETY CONSULTING ENGINEERS 1 Scope of Discussion
Combustible Dust Fire and Explosion Protection:
Combustible Dust Fire and Explosion Protection: NFPA 654 Requirements, Explanations and Issues Georgia State Fire Marshal Fire Safety Seminar Robert Zalosh Presentation Thursday, July 16, 2009 [email protected]
Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems
Technical Bulletin Gas & Air Recommendations Regarding the Handling of Norit GL 50 in Flue Gas Clean up Systems 1. Introduction Norit GL 50 is a powdered activated carbon widely used for the removal of
Combustible Dust Booklet
Introduction In general, over 70% of organic dusts are explosible if given an adequate ignition source and appropriate dust/air concentration. Unless the material is combustible and finely divided (generally
COMBUSTIBLE DUST EXPLOSIONS
COMBUSTIBLE DUST EXPLOSIONS Most people would not think that dust made up of ordinary materials such as food could explode, but under certain circumstances it can. On 7 February 2008, a violent explosion
Combustible Dust: - The Basics You Need to Know. Presented by: Mary Ann Heaney, CIH, CSP ohsm, llc.
Combustible Dust: - The Basics You Need to Know Presented by: Mary Ann Heaney, CIH, CSP ohsm, llc. Why the Current Focus? 2003-3 catastrophic dust explosions January - 7 Fatalities, 38 injured 2006 US
Combustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.
Combustible Dust - Things that go Boom W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: [email protected] Presentation Objectives After attending this presentation you will: Learn
5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment
Two Documents are used for the Classification of Combustible Dusts and Hazardous Locations: NFPA 499-Recommended Practices for the Classification of Combustible Dusts and Hazardous Locations for Electrical
Explosion Prevention
Explosion Prevention Question: Many food and industrial products produced by member companies are dry powders or crystals. If mishandled, some of these products may form an explosive mixture of air and
Electrical Classification
Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to
Combustible dust. How to use this guide. Combustible Dust
INDUSTRIAL HYGIENE Combustible dust How to use this guide The purpose of this guide is to provide an overview of the dangers of combustible dust explosions along with tools and resources to recognize,
During Various Aluminum Fabricating Operations
Guidelines for Handling Aluminum Fines Generated During Various Aluminum Fabricating Operations F-1 Guidelines for Handling Aluminum Fines Generated During Various Aluminum Fabricating Operations SCOPE
Is This Combustible Dust?
1 of 5 8/6/2012 1:16 PM Is This Combustible Dust? Thursday, 19 July 2012 Dust explosions and fires are serious hazards in the process industries that have lead to loss of life, injury to plant personnel
Use of Combustible Dust Risk Assessments in the Agricultural and Food Processing Industries. by Douglas Moilanen
1 Use of Combustible Dust Risk Assessments in the Agricultural and Food Processing Industries by Douglas Moilanen A Research Paper Submitted in Partial Fulfillment of the Requirements for the Master of
Assessing the Potential for a Dust Explosion and Navigating the Current Regulatory Environment
Assessing the Potential for a Dust Explosion and Navigating the Current Regulatory Environment Ali Reza, P.E., CFI David Clayton, Ph.D., P.E. Exponent, Inc. 5401 McConnell Avenue Los Angeles, CA 90066
Anew combustible dust standard from the National. Get ready for NFPA 652: The new combustible dust standard
As appeared in October 2014 PBE www.powderbulk.com Get ready for NFPA 652: The new combustible dust standard Jack Osborn Airdusco Inc. This NFPA committee member and dust collection expert summarizes what
NFPA Combustible Dust Compliance and the Industrial Ventilation System
NFPA Combustible Dust Compliance and the Industrial Ventilation System Presented By: Tom Kroeger PE [email protected] Kirk & Blum, a CECO Environmental Company Marty Schloss PE [email protected]
Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered
COMBUSTIBLE DUST in the WOOD PRODUCTS INDUSTRY
COMBUSTIBLE DUST in the WOOD PRODUCTS INDUSTRY Produced by NWCEP, Inc. This material was produced under grant SH23597SH2 from the Occupational Safety and Health Administration, U.S. Department of Labor.
Group A/B Dust Explosion Classification Chilworth Hazard and Risk Profile (CHARP) - Standard package of tests
Item Description Item Remarks Explosion severity analysis (20L sphere): Triplicate test Explosion severity analysis (20L sphere): Single series screening test Explosion severity analysis (20L sphere):
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Illinois Manufacturers Best Practices January 2016 Webinar
Illinois Manufacturers Best Practices January 2016 Webinar Combustible Dust Housekeeping: Stay Safe & Compliant January 28, 2016 Combustible Dust Housekeeping: Stay Safe & Compliant Andrew Luessenhop,
Combustible Dust CAN HURT YOU
Michael A. Serpe CSP SafetyFirstna, Inc. [email protected] 773-447-3982 Joseph P. Howicz CSP, CFPS [email protected] 847 609 9956 Combustible Dust CAN HURT YOU In this presentation we will
A strategic guide to characterisation & understanding
Hazards Control & Assessment Safety Guide A strategic guide to characterisation & understanding Handling Dusts & Powders Safely 2006-2013 Chilworth Technology Ltd - All rights reserved First published
Combustible Dust Basics
By Christopher A. Jarc, P.E., PMP, LEED A.P. (with Contributions from The Hixson Baking Industry Team) Abstract From woodworking to metalworking, petrochemicals to fertilizers, any industry that can create
The Minimum Ignition Energy of Coal Dust in an Oxygen Enriched Atmosphere
739 A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 31, 2013 Guest Editors: Eddy De Rademaeker, Bruno Fabiano, Simberto Senni Buratti Copyright 2013, AIDIC Servizi S.r.l., ISBN 978-88-95608-22-8;
A.17. OXIDIZING PROPERTIES (SOLIDS)
A.17. OXIDIZING PROPERTIES (SOLIDS) 1. METHOD 1.1. INTRODUCTION It is useful to have preliminary information on any potentially explosive properties of the substance before performing this test. This test
Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation
Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation No. 2008-02-I-IA (September 2008) Key Lessons for Safe Handling and Storage of Flammables Ensure that equipment, such as fill
How to be Sure Your Dust Collector Design and Installation are NFPA Compliant. Presented by: Jeff Kice Kice Industries, Inc.
How to be Sure Your Dust Collector Design and Installation are NFPA Compliant Presented by: Jeff Kice Kice Industries, Inc. Who is the NFPA? National Fire Protection Association Nonprofit international
Hazardous Substance Class Definitions & Labels
Hazardous Substance Class Definitions & Labels In the IMDG Code, substances are divided into 9 classes. A substance with multiple hazards has one 'Primary Class' and one or more 'Subsidiary Risks'. Some
Combustible Dust. The Basics. Presented by: Mary Ann Heaney, CIH, CSP ohsm, llc.
Combustible Dust The Basics Presented by: Mary Ann Heaney, CIH, CSP ohsm, llc. Why the Recent Focus? 2003-3 catastrophic dust explosions January - 7 FataliGes, 38 injured 2006 US Chemical Safety and Hazard
The Status of Combustible Dust Regulation
The Status of Combustible Dust Regulation Mark Haskins, CSP Practical Safety Solutions, LLC For CBIA Wellness Health and Safety Conference March 31, 2011 Learning Objectives During this presentation you
Combustible Dust... Elements of Dust Hazard Assessment
Session No. 506 Introduction Combustible Dust... Elements of Dust Hazard Assessment Walter S. Beattie, CSP, CFPS, CSHM Pottstown, PA Presentation: June 25, 2013 On July 29, 2008, Mr. John S. Bresland,
IGNITION OF DUST CLOUDS AND DUST DEPOSITS BY FRICTION SPARKS AND HOTSPOTS
IGNITION OF DUST CLOUDS AND DUST DEPOSITS BY FRICTION SPARKS AND HOTSPOTS R L Rogers 1, S Hawksworth 2, M Beyer 3, C Proust 3, D Lakic 3, J Gummer 2 and D Raveau 3 1 INBUREX GmbH, D-59067 Hamm, Germany
Safety Data Sheet for Whole Grain
SECTION 1: IDENTIFICATION Safety Data Sheet for Whole Grain PRODUCT NAME: SDS NUMBER: WHOLE GRAIN GRAIN SYNONYMS/OTHER MEANS OF IDENTIFICATION: INTENDED USE: FOOD MANUFACTURER: (company name) EMERGENCY
EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT
EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES
Ex q Powder Filling. This is a technique primarily used for oil filled switch-gear. The spark is formed under oil and venting is controlled.
Methods of explosion protection for electrical equipment Flammable atmospheres can be ignited by sparks or not surfaces arising from the use of electrical power. Other possible sources of ignition are
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants
Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants Ram K. Saini, P.E. Principal Engineer, Chuck Emma, P.E. Principal Engineer, Burns and Roe Enterprises,
12.85 Enforcement and Consultation Guidance for Combustible Dust Hazards December 30, 2008
DOSH DIIRECTIIVE Deeppaarrt tmeennt t oof f LLaabboorr aanndd Inndduusst I trri ieess Divvi issi ioonn oof f Occccuuppaat tioonnaal l Saaf feet tyy aanndd Heeaal lthh Keeping WA workers safe. 12.85 Enforcement
STORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders
STORE HAZARDOUS SUBSTANCES SAFELY Suitable containers incompatibles gas cylinders Oxy-Acetylene welding flammable substances 35 36 STORE HAZARDOUS SUBSTANCES SAFELY STORE HAZARDOUS SUBSTANCES SAFELY Storing
GUIDELINE FOR SAFETY IN THE HANDLING OF FLAMMABLE LIQUIDS
GUIDELINE FOR SAFETY IN THE HANDLING OF FLAMMABLE LIQUIDS September 2007 Replaces the July 2004 edition 1. Purpose Purpose of present Guideline is to specify conditions for the safe handling of flammable
The soot and scale problems
Dr. Albrecht Kaupp Page 1 The soot and scale problems Issue Soot and scale do not only increase energy consumption but are as well a major cause of tube failure. Learning Objectives Understanding the implications
WHITE PAPER Fire & safety performance standards
WHITE PAPER Fire & safety performance standards Terminologies describing Fire Performance Terminologies describing Fire Performance often present a challenge to understand as how they apply to a cable
FLAMMABLE AND COMBUSTIBLE LIQUIDS
GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
Combustible Dust in the Workplace An overview of its recognition, evaluation, and control
Combustible Dust in the Workplace An overview of its recognition, evaluation, and control Ignition Source Dispersion Deflagration Explosion FIRE Confinement Combustible Dust Oxygen in Air DIOSH Day- Peoria,
Reducing Injury and Damage Related to Electric Dryer Fires. Fire Containment Tests for the Second Edition of UL 2158
Reducing Injury and Damage Related to Electric Dryer Fires Fire Containment Tests for the Second Edition of UL 2158 Reducing Injury and Damage Related to Electric Dryer Fires: Fire Containment Tests for
Minimum Ignition Temperature of Hybrid Mixtures Of Burnable Dusts and Gases
25 th ICDERS August 2 7, 2015 Leeds, UK Minimum Ignition Temperature of Hybrid Mixtures Of Burnable Dusts and Gases Emmanuel Kwasi Addai, Dieter Gabel, Ulrich Krause Otto-von-Guericke-Universität, Institute
Approval Standard for Fume Exhaust Ducts or Fume and Smoke Exhaust Ducts
Approval Standard for Fume Exhaust Ducts or Fume and Smoke Exhaust Ducts Class Number 4922 April 2001 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended
How To Test For Premer Retardant
TEST REPORT NEBS COMPLIANCE CHOMERICS PREMIER CONDUCTIVE PLASTIC Prepared by: CHOMERICS R&D 84 DRAGON COURT WOBURN, MA 01801 Test Report Number: TR 1007 EN 0206 Chomerics Approved Signatory: This report
Combustible Dust Hazards
environmental failure analysis & prevention health technology development 1 Combustible Dust Hazards Scott E. Dillon American Foundry Society 24 th EH&S Conference August 15, 2012 Nashville, TN A leading
SAFETY DATA SHEET 安 全 数 据 单
SAFETY DATA SHEET 安 全 数 据 单 1. IDENTIFICATION OF THE SUBSTANCE/PREPARATION AND OF THE COMPANY/UNDERTAKING PRODUCT NAME: InnoPlus LDPE 2420D CHEMICAL NAME: Low Density Polyethylene MANUFACTURER: 14 Map
FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes
FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,
Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H*****
Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H***** FM 3046039 Class I Div 1, Groups A, B, C and D Class II Div 1, Groups E, F and G; Class III Class I, Zone 0, AEx ia IIC Ga, Ga/Gb, Gb Document ID:
Safe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
Chapter 15: EXPLOSIVES. An explosive article is an article containing one or more explosive substances.
Chapter 15: EXPLOSIVES DEFINITIONS 1. An explosive substance is a solid or liquid substance (or mixture of substances) which is in itself capable by chemical reaction of producing gas at such a temperature
CFPA-E No 31:2013 F. Protection against self-ignition and explosions in handling and storage of silage and fodder in farms CFPA-E -GUIDELINES
CFPA-E No 31:2013 F Protection against self-ignition and explosions in handling and storage of silage and fodder in farms Foreword The European fire protection associations have decided to produce common
To provide guidelines for the safe inspection of potential combustible worksites and for the safe collection and shipment of combustible dust
SUBJECT: Purpose: Scope: Combustible Dust To provide guidelines for the safe inspection of potential combustible worksites and for the safe collection and shipment of combustible dust This instruction
In accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
Presented by: Rich Perry Marsh Risk Consulting
Flammable and Combustible Liquids Presented by: Rich Perry Marsh Risk Consulting What s the Big Deal? Flammable and combustible liquids are easily ignited Ignite with explosive force Burn readily and give
Fire Testing of Recycled Materials for Building Applications
Fire Testing of Recycled Materials for Building Applications Robert H. White Abstract To gain wide market acceptance of new building products made from recycled materials, fire testing may be necessary.
Modelling of Electrostatic Ignition Hazards in Industry: too Complicated, not Meaningful or only of Academic Interest?
A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 31, 2013 Guest Editors: Eddy De Rademaeker, Bruno Fabiano, Simberto Senni Buratti Copyright 2013, AIDIC Servizi S.r.l., ISBN 978-88-95608-22-8; ISSN
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Fire Alarm System Accessories
Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer
Failure Analysis Associates. Cell Phone Usage At Gasoline Stations
Failure Analysis Associates Cell Phone Usage At Gasoline Stations Cell Phone Usage At Gasoline Stations Prepared for Motorola Corporation 2001 N. Division St. Harvard, IL 60033 Prepared by Exponent Failure
Waste Oil Collection / Storage
ENVIRONMENTAL & REGULATORY SERVICES Storage Tank Regulation Section P. O. Box 7837 Madison, Wisconsin 53707-7837 TDD #: (608) 264-8777 http://www.commerce.state.wi.us http://www.wisconsin.gov Jim Doyle,
SAFE TRANSFER OF POWDERS INTO FLAMMABLE LIQUIDS David E. Kaelin Sr., Senior Process Safety Specialist
Hazards Control & Assess- SAFE TRANSFER OF POWDERS INTO FLAMMABLE LIQUIDS SAFE TRANSFER OF POWDERS INTO FLAMMABLE LIQUIDS David E. Kaelin Sr., Senior Process Safety Specialist A major consideration in
Ethanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST Instruction: Check each test method for which you are requesting accreditation. An asterisk beside the NVLAP Test Method Code indicates that proficiency
NAN YA NYLON 66 Engineering Plastics. Flame Retardant.High Toughness.Heat Resistant. Impact Resistant.Moldability.Low Warpage
NAN YA NYLON 66 Engineering Plastics Flame Retardant.High Toughness.Heat Resistant. Impact Resistant.Moldability.Low Warpage Introduction NAN YA FR-NYLON 66 has water absorption propertieslike other nylons.
University of Pittsburgh Safety Manual Subject: COMBUSTIBLE METALS. EH&S Guideline Number: 02-005. Effective Date 09/10/13.
Page 1 of 7 These guidelines provide requirements for all University faculty, staff, and students using, handling, or storing combustible metals. These requirements are established to ensure faculty, staff
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program
LCT 1025 (08/08) Copyright 2008 Harleysville Mutual Insurance Company Page 1 of 5 All rights reserved
Bonding and Grounding of Flammable Liquid Containers Provided by Harleysville s Risk Control Department 800-523-6344 ext 8100 www.harleysvillegroup.com/riskcontrol Summary The movement of volatile liquids,
PAINT BOOTH LIGHTING
PAINT BOOTH LIGHTING PAINT BOOTH LIGHTING Lighting is comprised of many components that need to be considered when selecting the appropriate fixtures and lamps to accomplish a specific task. Selecting
Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A.
Safety issues of hydrogen in vehicles Frano Barbir Energy Partners 1501 Northpoint Pkwy, #102 West Palm Beach, FL 33407, U.S.A. Properties of hydrogen Hydrogen is an odorless, colorless gas. With molecular
INTERNATIONAL STANDARD
IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60
Newson Gale. Is it ever Safe to use Plastic Drums and Containers in Hazardous areas? White Paper. Author Details:
White Paper Is it ever Safe to use Plastic Drums Author Details: Mike O Brien, Head of Product Marketing for If you have any questions relating to the topics discussed in this article, you can contact
PBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
Designing your dust collection system to meet. triangle: fuel (combustible dust), an ignition source, and
As appeared in PBE December 2008 www.powderbulk.com Designing your dust collection system to meet NFPA standards Part I Gary Q. Johnson Workplace Exposure Solutions About 40 percent of combustible dust
Uline NFPA. SECTION 1 : CHEMICAL PRODUCT AND COMPANY IDENTIFICATION MSDS Name: Collapsible Bulk Containers
Uline NFPA HMIS Collapsible Bulk Containers Manufacturer MSDS Number: 70000000 1 1 0 HEALTH 1 FIRE 1 REACTIVITY 0 PPE SECTION 1 : CHEMICAL PRODUCT AND COMPANY IDENTIFICATION MSDS Name: Collapsible Bulk
List of Frequently Utilized Storage Tank Standards and Practices
List of Frequently Utilized Storage Tank Standards and Practices Below is a list of frequently used storage tank standards and practices from organizations that are referenced in 25 PA Code, Chapter 245.
Dust Collector Fire and Explosion Highlights Need for Combustible Dust Considerations In System Designs
The following article is courtesy of Baghouse.com Dust Collector Fire and Explosion Highlights Need for Combustible Dust Considerations In System Designs Posted on May 18, 2012 in Dust Collection, Dust
LESSON PLAN 1. Fire Science. Key Terms and Concepts. ash chemical reaction combustion Consumer Product Safety Commission endothermic exothermic
LESSON PLAN 1 Fire Prevention Fire and Fire Prevention Combustion occurs when the three elements of the fire triangle heat, fuel and oxygen are present. Understanding this basic chemical reaction can help
HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids
Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System July 28, 2003 We are pleased to provide the following joint statement by CII,
HAZARD CONTROL TECHNOLOGIES, INC. Coal Silo-Bunker Firefighting Procedures
HAZARD CONTROL TECHNOLOGIES, INC. Coal Silo-Bunker Firefighting Procedures This article was written in the May, 2012 edition of Coal People magazine and reviews the basic procedures for locating and mitigating
Fire Performance Standard
Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant
Classification of Hazardous Atmospheres
Classification of Hazardous s The following pages contain excerpts for your convenience. If more comprehensive information is required, consult with your Western Technology representative. HAZARDOUS LOCATION
Controlling Static Electricity in Modern Buildings
Controlling Static Electricity in Modern Buildings Graham Hearn Wolfson Electrostatics The problem of static electricity in commercial offices and stores is a relatively modern phenomenon. It represents
07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
