General Specification for Synchronous Modular Meters
|
|
- Jonah Carpenter
- 8 years ago
- Views:
Transcription
1 Verantwortlich: Dokument-Betreuung: Letzte Bearbeitung: tlz-projektgruppe Wisy / MW Freigabe zur Veröffentlichung: Ja General Specification for Synchronous Modular Meters Version 1.03 Page 1/186
2 History Version Date Comment Responsible Corrected version after review as a submission for approval tlz Project Group Corrected version after discussion in tlz WG dated tlz Project Group Corrected version after discussion with L+G dated tlz Project Group Development basis for the tlz pilot project tlz Project Group Incorporation of all alterations/supplements involved Appendix B, SML was removed completely tlz Project Group 1.02 Feb. 08 Revison for publication as from 1 March 2008 tlz Project Group Incorporation of all changes/additions occurring during the course of the tlz pilot project Inclusion of feedback from the FNN expert network Conformity of Metering Systems Detailing the reboot behaviour at KM modules in conjunction with writing certain parameters Addition of network masks for parameterisation of RAW-TCP and Adaptation of the functioning of the load profile collector in the event of a power failure over a register period change (see Para. (109) and Fig. 39) tlz Project Group Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 2/186
3 List of contents i List of illustrations 8 ii List of tables 10 iii List of abbreviations 14 1 Foreword 19 2 Execution Basic concept 21 3 Standards, documents, terms and definitions Standards Documents Literature Calibration-law requirements, requirements and information Terms and definitions Reference time Statutory time Data protocols, useful load Data protocols, pull mode Data protocols, push mode Measured-value tuples Correcting a period generator Period generator / Clock generator Registration period Seconds index Operating seconds counter Signature Synchronising a period generator SyM² metering device Reference-arrow system and identification of the measured variables 28 4 Requirements Overview SyM² basic device, general requirements SyM² additional module, general requirements Metrology Adjustment Testing (incoming inspection, calibration) LED for outputting energy-proportional pulses Register Electromagnetic compatibility 35 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 3/186
4 4.4. Device clock Clock generator and seconds index (clocked measured-value tuples) Reference time Measured-value tuples of the SyM² basic devices Power reserve Accuracy Synchronous load profile recording Basic principle Load profile collector Queries on the load profile / Filling up registration periods Registration period and registration period generator Synchronisation to the desired RP raster Application note on the commissioning process Optical operational readiness Display and controls Display Directly displayed information Rolling-display information Operational readiness Display test Operational display for the energy flow Phase display Operational display for the seconds index Rating plate Housing and terminal design Modularised basic principle SyM² basic device Mechanical construction SyM² basic device, terminal design Lead-sealing SyM² additional module Mechanical construction Special requirements for the IW module Special requirements for the KM module Optional additional modules Data interfaces Overview SyM² basic device and local bus interface SyM² additional module and local bus interface device, interface for MDE read-out ( service interface ) Protocols and Code Number system Overview Signature Overview Hash code calculation 68 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 4/186
5 Crypto-algorithm for signing the measured-value tuples Crypto-algorithm for firmware downloading Additional functional requirements General Software / Firmware Remote Software (Firmware) Download Process for data transmission at firmware downloading Access protection Access level protection Functional error monitoring Signalling operationally entailed events 82 5 Functional behaviour Data interfaces Local bus (lower layers, integrated supply) Requirements for MAC addressing Requirements for using broadcasts Requirements for the RJ45 sockets (operational display) Requirements for the integrated module supply Wide-area interfaces Protocols (network and higher layers) Plug n play protocol Automatic assignment of IP addresses Automatic bonding of SyM² additional module to SyM² basic devices Requirements for the transport protocols at the local bus User Datagram Protocol Transmission Control Protocol Application protocol SML SML options used with SML_PublicOpen SML options used with SML_ProfilePack and SML_ProfileList SML options used with SML_GetProcPar SML options used with SML_SetProcPar Transport of SML files via IP telemetry Device classes SyM²-specific error numbers used Synchronisation operations per data interface Detecting existing bus subscribers SyM² modules Watchdog Reading/writing characteristics per OBIS SyM² basic device Requirements for the interface to the local bus Requirements for the plug n play protocol Requirements for the application data protocol (SML) Status word 109 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 5/186
6 Requirements for the statutory-calibration logbook IW module Requirements for the interfaces to the local bus Requirements for the plug n play protocol Requirements for the application data protocol (SML) Status word Requirements for the switching outputs Requirements for the operational displays with the IW module KM module Requirements for the interface to the local bus Requirements for the plug n play protocol Requirements for the application data protocol (SML) Direct TCP transmission ( RAW-TCP ) Operating logbook Requirements for the application data protocol with PSTN Requirements for the application data protocol with GSM Requirements for the application data protocol with GPRS Requirements for the application data protocol with LAN / DSL Requirements for the operational displays with PSTN Requirements for operational displays with the variants GSM / GPRS Requirements for the operational displays in the case of LAN / DSL Characteristics of a push operation Functional behaviour of a push operation Functional behaviour for a pull operation Process for establishing the time reference with PULL and PUSH NK/HS module Requirements for the interfaces to the local bus Requirements for the plug n play protocol Requirements for the application data protocol (SML) Requirements for the auxiliary supply Requirements for the operational displays at the NK/HS Service interface Requirements Detailed stipulations Appendix A, list of Code Numbers used General data Code numbers for describing telemetry characteristics ( OBIS-T ) General device characteristics Device characteristics, interfaces Classification Type of interface Names Attributes in detail List of the Code Numbers used in SyM² metering devices 173 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 6/186
7 7 Appendix B, Manufacturer s Declaration Appendix C, general hints, informative Notes on applications Global application Notes on utilising the push mode Communication options Explanations on load profile recording and seconds index Ethernet interfaces at the local bus (informative) Creating the time reference (informative) 186 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 7/186
8 List of illustrations Fig. 1: Variants of a SyM² metering device. 21 Fig. 2: Function concept for a SyM² metering device. 22 Fig. 3: Definition of the terms import and delivery (see also DIN EN ). 28 Fig. 4: Assignment of seconds index to statutory time under ideal conditions. 36 Fig. 5: Mechanism for registration period synchronisation. 43 Fig. 6: Flow diagram for filing measured-value tuples in the load profile memory (1/2). 44 Fig. 7: Flow diagram for filing measured-value tuples in the load profile memory (2/2). 45 Fig. 8: Display of the SyM², depiction informative, arrangement normative. 48 Fig. 9: Arrangement of the information on the additional plate (informative). 52 Fig. 10: SyM² basic device with terminal shroud. 53 Fig. 11: SyM² basic device without terminal shroud. 54 Fig. 12: Construction of the SyM² basic device (Fig. 1/4). 55 Fig. 13: Construction of the SyM² basic device (Fig. 2/4). 56 Fig. 14: Construction of the SyM² basic device (Fig. 3/4). 57 Fig. 15: Construction of the SyM² basic device (Fig. 4/4). 58 Fig. 16: Construction of the current and voltage terminals. 59 Fig. 17: Constructional framework stipulations for the SyM² additional module (Fig. 1/2). 61 Fig. 18: Constructional framework stipulations for the SyM² additional module (Fig. 2/2). 62 Fig. 19: Arrangement and labelling of the switching outputs for the IW module (informative). 63 Fig. 20: Standard applications for SyM² metering devices. 65 Fig. 21: Basic concept for the protocol for the data interface(s) 67 Fig. 22: Authenticity and integrity with remote firmware downloading (variant: not subject to mandatory calibration). 72 Fig. 23: Authenticity and integrity with remote firmware downloading (variant: subject to compulsory calibration). 73 Fig. 24: Process for firmware downloading. 78 Fig. 25: Arrangement of the operational displays at a RJ45 socket. 85 Fig. 26: State machine for assigning IP addresses. (informative). 90 Fig. 27: State machine for bonding a SyM² additional module to a SyM² basic device (informative). 93 Fig. 28: Functioning with UDP-Broadcast requests. 94 Fig. 29: IW module, physical and logical interfaces(s). 114 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 8/186
9 Fig. 30: KM module, how the logbook for operating events works. 142 Fig. 31: Temporal structure of a push operation (start after operational readiness). 151 Fig. 32: Temporal structure of a push operation (behaviour after synchronisation). 152 Fig. 33: Process for establishing the time reference with PULL / PUSH. 159 Fig. 34: Plug connector assignments for the service interface (view into the socket). 162 Fig. 35: Basic circuitry for the adapter cable for the service interface 163 Fig. 36: Standard operating case for SyM². 178 Fig. 37: Seconds index plus read-out during undisturbed operation (e.g.: RP = 15, time from one beginning-second index to one end-second index). 180 Fig. 38: Seconds index plus read-out during undisturbed operation (e.g.: RP = 15, period from a beginning seconds index to and end seconds index). 181 Fig. 39: S-I plus read-out in the event of a power cut and power reserve correct (e.g.: RP = 15, time from one beginning-second index to one end-second index). 182 Fig. 40: S-I plus read-out in the event of a power cut and power reserve exhausted (e.g. RP = 15, time from one beginning-second index to one end-second index). 183 Fig. 41: Direct Ethernet link between SyM² basic device and KM module. 184 Fig. 42: Connection variants between SyM² basic device, KM module and IW module. 184 Fig. 43: Ethernet links when using an NK/HS module. 185 Fig. 44: Overview for establishing the time reference. 186 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 9/186
10 List of tables Tab. 1: Overview of standards adduced 24 Tab. 2: SyM² basic device, overview of performance features required. 31 Tab. 3: SyM² additional module, general performance features. 33 Tab. 4: Specification for the behaviour of the metrological LED. 34 Tab. 5: Specification of the measured values to be supplied by the register 35 Tab. 6: Calculating the signature for the measured-value group +A, R1 and R4. 38 Tab. 7: Forming the signature auxiliary meter reading for the measured-value group +A, R1 and R4. 39 Tab. 8: Calculating the signature for Measured-Value Group -A, R2 and R3. 39 Tab. 9: Forming the signature auxiliary meter reading for Measured-Value Group -A, R2 and R3. 40 Tab. 10: Specification for the display 47 Tab. 11: List of the information outputted in a direct display (not rolling). 48 Tab. 12: List of information outputted in rolling mode. 49 Tab. 13: Specification of the particulars to be supplied on the rating plate. 51 Tab. 14: Construction of the terminals for the SyM² basic device. 59 Tab. 15: Construction of the terminals for the IW module. 63 Tab. 16: Parameters for the ECC algorithm for the signature of the measured-value tuples. 69 Tab. 17: Parameters for the ECC algorithm for firmware downloading. 70 Tab. 18: Data structure for remote firmware downloading (transmission). 74 Tab. 19: Data structure for the Activate firmware order. 75 Tab. 20: Data structure for status request for a firmware download (response). 76 Tab. 21: Data structure for initialising firmware downloading (request). 77 Tab. 22: Overview of access protection. 79 Tab. 23: Overview of the levels in access level protection. 80 Tab. 24: List of writable data for each access level. 81 Tab. 25: List of writable data for each access level. 81 Tab. 26: Data structure for transmitting manufacturer-specific event logbooks. 82 Tab. 27: Specification for the local bus (lower protocol layers). 83 Tab. 28: Specification for operational displays at the RJ45 sockets.. 85 Tab. 29: Basic features of the integrated module supply. 86 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 10/186
11 Tab. 30: Parameters of the integrated module supply. 87 Tab. 31: Time behaviour for connecting the supply voltage at PoE. 87 Tab. 32: SyM² modules approved as sinks for the integrated module supply. 88 Tab. 33: Specification of the protocols used. 89 Tab. 34: State machine for assigning IP addresses. 90 Tab. 35: State machine for bonding a SyM² additional module to a SyM² basic device. 92 Tab. 36: List of the UDP ports used with a SyM² metering device. 94 Tab. 37: List of the TCP ports used with a SyM² metering device. 95 Tab. 38: SyM² modules, data structure for emptying the load profile memory. 97 Tab. 39: List of SyM² device classes. 99 Tab. 40: List of SyM²-specific note/error numbers. 99 Tab. 41: Data structure for triggering a synchronous token. 100 Tab. 42: Basic behaviour for the SyM² basic device. 103 Tab. 43: Specification for local bus interface for the SyM² basic device. 103 Tab. 44: Specification for the plug n play play protocol for the SyM² basic device. 103 Tab. 45: List of the directly readable/writable characteristics. 104 Tab. 46: SyM² basic device, data structure for retrieving the device identification. 104 Tab. 47: SyM² basic device, data structure for answering special measured-value tuples. 105 Tab. 48: SyM² basic device, data structure for retrieving special measured-value tuples. 105 Tab. 49: SyM² basic device, data structure for answering special measured-value tuples. 106 Tab. 50: SyM² basic device, data structure for retrieving additional measured values. 106 Tab. 51: SyM² basic device, data structure for response on additional measured values. 108 Tab. 52: SyM² basic device, data structure for the order for key pair calculation. 108 Tab. 53: SyM² basic device, data structure for emptying the statutory-calibration logbook. 108 Tab. 54: SyM² basic device, data structure for the order for switching over the LED function. 109 Tab. 55: Specification for the status bits used. 111 Tab. 56: Specification for the statutory-calibration logbook for the SyM² basic device. 112 Tab. 57: Basic requirements for the IW module. 112 Tab. 58: IW module, how pulse forwarding works. 113 Tab. 59: IW module, functioning for the registration period output. 114 Tab. 60: Specification for the physical local bus interfaces of an IW module. 114 Tab. 61: Specification for the plug n play- protocol for the IW module. 115 Tab. 62: IW module, list of the directly readable/writable characteristics. 116 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 11/186
12 Tab. 63: IW module, data structure for retrieving device identification. 117 Tab. 64: IW module, data structure for answering device identification. 117 Tab. 65: IW module, status word. 118 Tab. 66: Specification for the switching outputs of an IW module. 119 Tab. 67: IW module, behaviour of the operational display. 120 Tab. 68: KM module, data structure for requesting the NTP parameters. 123 Tab. 69: KM module, data structure with reply / for setting the NTP parameters. 124 Tab. 70: Specification for the phys. interface local bus of a KM module. 124 Tab. 71: Specification for plug n play protocol for the KM module. 125 Tab. 72: KM module, list of the directly readable/writable characteristics. 126 Tab. 73: KM module, data structure for retrieving the WAN operating parameters. 126 Tab. 74: KM module, data structure for reading /writing the WAN parameters. 127 Tab. 75: KM module, data structure for reading / writing the PSTN parameters. 128 Tab. 76: KM module, data structure for reading / writing the AT-Hayes strings. 129 Tab. 77: KM module, data structure for retrieving the GSM/GPRS operating parameters. 130 Tab. 78: KM module, data structure for reading / writing the GSM parameters. 131 Tab. 79: KM module, data structure for reading /writing permissible GSM/GPRS providers. 132 Tab. 80: KM module, data structure for reading / writing the GPRS provider parameters. 133 Tab. 81: KM module, data structure for reading / writing the LAN/DSL operating parameters. 133 Tab. 82: KM module, data structure for reading / writing the LAN/DSL parameters. 136 Tab. 83: KM module, data structure for retrieving the IP-T operating parameters. 136 Tab. 84: KM module, data structure for reading / writing the IP-T parameters. 138 Tab. 85: KM module, data structure for the Execute command reset order. 139 Tab. 86: Specification of status bits for the KM module. 140 Tab. 87: Optional data structure for parameterising the RAW-TCP transport channel. 141 Tab. 88: List of the characteristics to be recorded in the operating logbook. 143 Tab. 89: KM module, coding of the operating logbook events. 144 Tab. 90: KM module, operational displays with the variant PSTN. 147 Tab. 91: KM module, operational displays with the variants GSM / GPRS. 148 Tab. 92: KM module, operational displays with the variants LAN / DSL. 149 Tab. 93: Data structure for the characteristics of a push operation. 151 Tab. 94: List of possible push services. 152 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 12/186
13 Tab. 95: List of possible push sources. 153 Tab. 96: Data structure for addressing a particular push source. 154 Tab. 97: Data structure for transporting the installation parameters. 155 Tab. 98: Data structure for establishing the time reference (Request CMD_GetTimebase ). 157 Tab. 99: Data structure for establishing the time reference (response). 158 Tab. 100: Specification for the physical local bus interfaces of an NK/HS module. 160 Tab. 101: Specification for the plug n play protocol for the NK/HS module. 160 Tab. 102: NK/HS module, operational displays. 161 Tab. 103: Detailed specifications for the physical execution of the service interface. 162 Tab. 104: List of the code numbers (ranges) additionally defined with the SyM². 165 Tab. 105: List of OBIS-T code numbers for general device characteristics. 166 Tab. 106: Coding for classification of interfaces (OBIS, Value Group B ). 166 Tab. 107: List of relevant types / subtypes for OBIS-T. 167 Tab. 108: OBIS-T, list of attributes with administration data. 168 Tab. 109: Identification of tariff-linked information and preceding values. 169 Tab. 110: Particulars of the measured variable with OBIS-T. 171 Tab. 111: Particulars of the metering method with OBIS-T. 172 Tab. 112: List of SyM²-specific code numbers from OBIS-T (Part 1/3, stated in hex). 173 Tab. 113: List of SyM²-specific code numbers from OBIS-T (Part 2/3, stated in hex). 174 Tab. 114: List of SyM²-specific code numbers from OBIS-T (Part 3/3, stated in hex). 175 Tab. 115: List of SyM²-specific Code Numbers from OBIS-T for the Value Group B (stated in hex). 175 Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 13/186
14 Units: List of abbreviations (1) In regard to physical measured variables and units, the agreements made in the SI (see DIN 1301, Part 1) shall apply. Relevant abbreviations: (2) Arabic numerals can be appended to the following abbreviations, enabling a distinction to be made between multiply occurring instances of the same function / same signal. (3) Abbreviations relevant to labelling are identified with a in the first column. A Active energy, +A Active energy, customer imports from grid, -A Active energy, customer delivers to grid, AC alternating current, AL Application Layer, ARP Address Resolution Protocol, ASCII American Standard Code for Information Interchange, ASN.1 Abstract Syntax Notation One, AT advanced technology, BER BDEW BM BV Basic Encoding Rules, Bundesverband der Energie- und Wasserwirtschaft e.v., Basic module, Reactive-power consumption. CCITT Comité Consultatif International Télégraphique et Téléphonique, Cl. Accuracy Class, CR Carriage Return, DC DCF77 DHCP DIN DKE direct current, Long-wave transmitter, Dynamic Host Configuration Protocol, Deutsches Institut für Normung e.v. (German Standardisation Institute), Deutsche Elektrotechnische Kommision im DIN, (German Electrical Engineering Commission in DIN), Device Language Message Specification, Domain Name System, Digital Subscriber Line, Data interface, DLMS DNS DSL DSS DÜ Data transmission, DZ Three-phase current meter, ECC elliptic curve cryptosystem, EDIFACT Electronic Data Interchange For Administration, Commerce and Transport, (E) DIN Draft version of a DIN standard, EDM Energy data management, ehz electronic domestic meter, Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 14/186
15 EL el. EN EnWG EVU FNN FTP G GARP GMRP GPRS GSM GW HS HTTP HTTPS HW External load profile collector, electrical, European Standard, Germany Energy Industry Act (Energiewirtschaftsgesetz), Power utility, Network Technology / Network Operations Forum in the VDE File Transfer Protocol, Flag power reserve exhausted, Generic Attribute Registration Protocol, GARP Multicast Registration Protocol, General Packet Radio Service, Global System for Mobile Communications, Gateway, Auxiliary voltage, Hypertext transfer protocol, Hypertext Transfer Protocol Secure, Hardware port, I Current, IARP Inverse Address Resolution Protocol, I b Rated current for directly connected meters, ICC-ID Integrated Circuit Card Identifier (SIM-Identifier) ICMP Internet Control Message Protocol, ID Identification Number, IEC International Electrotechnical Commission, IEEE Institute of Electrical and Electronics Engineers, IETF Internet Engineering Task Force IGMP Internet Group Management Protocol, I max Limit current of meters, IMEI International Mobile Equipment Identity, IMSI International Mobile Subscriber Identity, Imp Pulses, Imp/kvarh Pulses per kvarh, Imp/kWh Pulses per kwh, I N Rated current for indirectly connected meters, IP Internet Protocol, ISO International Organisation for Standardisation, IW Pulse Forwarding Module, KM Communication module, KZ Code number, L1, L2, L3 Phase conductor, LAN Local Area Network, LC Liquid Crystal, Flüssigkristall, LCD Liquid Crystal Display / Flüssigkristallanzeige, LED Light Emitting Diode, Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 15/186
16 LF LSB Line Feed, Least Significant Bit, niederwertigstes Bit, MAC Media Access Control, M-Bus Metering Bus MDE Mobile data acquisition device, MDI Medium Dependent Interface MDI-X Medium Dependent Interface, crossed, MDI(X) used only as Auto-MDI(X): automatic detection whether MDI or MDI-X is to be encountered, MID Measuring Instruments Directive, MSB Most Significant Bit, höchstwertigstes Bit, MSCONS Metered Services CONSumption report message, MSN Multiple Subscriber Number, N N NAT NIC NK NK NTP OBIS OBIS-T OSI P P PD PDP PHY PIN PoE PUK PnP RPA RPC RPL PPP PPPoE PSE PSTN PTB Neutral conductor, Flag restoration of supply, Network Address Translation, Network Interface Card, Decimal places, Network nodes, Network Time Protocol, Object Identification System, OBIS Telemetry, Open Systems Interconnection Reference Model, Active power, Flag in private area, Powered Device (sink as per IEEE802.3af), Packet Data Protocol, Physical interface, Personal Identifiation Number, Power over Ethernet, Personal Unblocking Key, Plug and Play, Registration Period output, Registration Period Counter, Registration Period Length, Point-to-Point Protocol, Point-to-Point Protocol over Ethernet, Power Supply Equipment (Quelle nach IEEE802.3af), Public Switched Telephone Network, Physikalisch-Technische Bundesanstalt (German Federal Institute of Physics), R1 Reactive energy, Quadrant I, R2 Reactive energy, Quadrant II, R3 Reactive energy, Quadrant III, R4 Reactive energy, Quadrant IV, Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 16/186
17 RAB RAW RARP RFC RG RP RPL RS232 S SHA-1 SEZ SFTP S-I SIM SML SMS SMTP STD SV SyM² TAB TAE TAG TCP TL tlz TP TRMS Output pulse constant for reactive energy, Output pulse constant for active energy, Reverse Address Resolution Protocol, Request for Comment, Radio Government, Registration period, Registration period length, Serial interface, Flag Synchronisation, Secure Hash Algorithm, Standard energy quantity meter, Secure File Transfer Protocol, Seconds index, Subscriber Identity Module, Smart Message Language, Short Message Service, Simple Mail Transfer Protocol, Standard, Service interface, Synchronous Modular Meter, Technical connection conditions, Telecommunication connection unit, Feature / Designation / Identification when coding data elements, Transmission Control Protocol, Type-Length, Clocked load profile meter, Twisted-Pair Cable, True Root Mean Square, U Voltage, UDP User Datagram Protocol, U n Rated voltage (see DIN EN ), V VDE VDEW VDN VK VL VNB VZS Flag provisional value, Verband der Elektrotechnik Elektronik Informationstechnik e.v., (Confederation of the German Electrical Engineering, Electronics and Information Technology Industries) Verband der Elektrizitätswirtschaft VDEW e.v., (Confederation of the German Electricity Industry) Verband der Netzbetreiber VDN e.v. at the VDEW (German Confederation of Network Operators), Number of places before the decimal point, Billing list, Distribution network operator, Consumer reference-arrow system, Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 17/186
18 WAN Wide Area Network, WELMEC Western European Legal Metrology Cooperation, WV Active energy, time integral 1 as per OBIS, WZ AC meter, XML ZFA ZM ZVEI Extensible Markup Language, Remote meter readout, Additional modules, Zentralverband Elektrotechnik- und Elektronikindustrie (German Confederation of the Electrical Engineering and Electronics Industries). Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 18/186
19 1 Foreword (4) The general specification for Synchronous Modular Meters (SyM² ) serves to provide development engineers at the meter manufacturers and the staff dealing with invoicing metering equipment at network operators, metering point operators and vendors with a harmonised working document for load profile meters featuring a clocked registration period. (5) The goals of the SyM² have been defined as follows under the paramount consideration of cost reduction in operations management: - Modularised device concept with mounted or integrated function units and a standardised interface, and thus installation of only those elements specifically required on site plus continual easy adaptation to new developments. - use of meter readings in place of increments / power mean values, - dispensing with the maximum metering mechanism, - dispensing with integrated tariff control, - reducing the influence of the device clock by changing to a seconds index, - separation into a compulsory-calibration register and additional modules not subject to compulsory calibration for upgrading transparency by returning to simple measured values, - reducing the complexity of the individual modules, - firmware download utilising the concepts of the WELMEC guideline. - (6) This first version of the general specification for Synchronous Modular Meters is based on the empirical feedback from previous versions from VDEW General Specification 2.x, which has proved to be problematical and ultimately cost-intensive, due particularly to the wide multiplicity of variations agreed there. The SyM² general specification replaces the versions of the tlz specification drawn up previously during the course of development work. (7) The empirical feedback available has likewise revealed that the conformity already targeted in the past for data interfaces in regard to the protocols actually implemented by the manufacturers could not be achieved. The differences discernible in the field are attributable to the high level of complexity involved, and in numerous degrees of freedom ultimately not adequately restricted with the existing VDEW general specification. A further goal for the new system technology is accordingly to fill in the existing definition gaps and to specify new and simpler approaches. (8) As the third goal, the new system technology of the SyM² incorporates experience gained with the many device clocks distributed in the field. In this context, it must be noted that the synchronism of these device clocks necessarily stipulated can be provided only with a high outlay on engineering and organisation, with a concomitant increase in cost-intensity. The Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 19/186
20 idea of a clockless meter, better designated as a Synchronous Modular Meter, was taken on board and has resulted in a significant reduction of the complexity previously obtaining (9) The overall aim of this general specification foris to make available device designs that are interchangeable on a cross-manufacturer basis, forming a standard. This reduces possible installation, read-off, operator control and data transmission errors, and in the medium term leads to standardisation of the approval procedure at the Physikalisch-Technische Bundesanstalt. Against this background the multiplicity of variants is reduced. (10) In accordance with technical progress and the agreements possible in each case on specifying further components of the electronic meter, the intention is to publish revised versions of the tlz specification. Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 20/186
21 2 Execution (11) This general specification fordescribes SyM² basic devices and SyM² additional module, designed predominantly for billing purposes in the special-agreement customer category. For this purpose, the SyM² basic devices must be approved. (12) These metering devices are designed as four-quadrant meters Basic concept (13) The SyM² implements the goal of system technology for acquiring electrical variables. The term SyM² accordingly denotes an ensemble of components, grouped into a mandatory and an optional category, with the mandatory category containing the actual register ( SyM² basic device ) and an integrated load profile collector, to which opt ional categories can be added using additinalö modules ( SyM² additional module ). (14) The SyM² additional module can be mounted on the SyM² basic device or in other environments. For this operational case, only an adapter needs to be defined for connecting the SyM² additional module to this different environment. (15) Against this background, the basic concept for the SyM² can be outlined with the following variant tree: SyM 2 -Messeinrichtung SyM 2 -Basisgerät: (Pflichtmodul) Messwerk mit integriertem Signaturelement, integrierter Anzeige und integriertem Lastgang... in der Variante: direkter Anschluss Legende:... in der Variante: halbindirekter Anschluss genau eine der Varianten muss vorhanden sein, keine, eine oder mehrere der Varianten können vorhanden sein.... in der Variante: indirekter Anschluss... in den optionalen Varianten: mit einem oder mehreren Zusatzmodulen, wobei dieses Pflichtenheft eine Liste von grundlegenden Zusatzmodulen definiert und das Konzept generell so angelegt ist, dass Hersteller bedarfsweise weitere Zusatzmodule anbieten können. Fig. 1: Variants of a SyM² metering device. (16) Within these variants, different constellations are possible, whose number shall be minimised in line with the objectives of this general specification for. Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 21/186
22 SyM 2, optionale Module Bedienen die Schnittstellen zur Außenwelt, können per Software-Download beliebig administriert werden, unterliegen nicht den eichrechtlichen Regularien Privates oder öffentliches Kommunikationsnetz für Fernzugriffe Protokoll SML SyM 2 -Zusatzmodule Lastgangsammler Kommunikationstechnik (beinhaltet Zugangsschutz zur Messeinrichtung) Synchron- / Impuls-Ein- / Ausgänge Netzteil mit Spannungsweitbereichseingang zur Versorgung der Zusatzmodule Einheitliche, offen standardisierte und rückwirkungsfreie Schnittstelle im Sinne einer Bus-Struktur. SyM 2 -Basismodul (Pflichtmodul, Messwerk) Skizze hier für die Variante: direkter Anschluss vom Netz L1 L2 L3 N 1.8.x Logbuch Messwerk (eichrechtlich gesichert, Anzeige / Signatur integriert, Logbuch für Firmwaredownload, integrierter Lastgangsammler) zum Kunden Fig. 2: Function concept for a SyM² metering device. (17) The logbook function unit in the SyM² basic device required solely for verification of firmware downloads performed. Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 22/186
23 3 Standards, documents, terms and definitions (18) It should quite generally be noted that the lists of standards and documents given below are to be understood merely as a guideline bibliography. Development work on the devices must always be adapted to suit the ongoing statutory stipulations and standards, with the tlz specification defining the documents to be used for actual device development work Standards (19) This document references the standards listed below: DIN 1301, Part Units, Part 1: unit names, unit symbols DIN ISO General tolerances; tolerances for length and angle dimensions without individual tolerance entries DIN Lead-seal screws for electricity meters DIN Electricity meters, signs DIN Electricity meters, multi-rate tariff switches and ripple control receivers; circuit numbers, terminal designations, schematics DIN Electricity meters in insulating-material housings, for direct connection, up to 60 A limit current; principal dimensions for three-phase-current meters E DIN Meter data communication IP telemetry DIN Meter slots; dimensions on the basis of a raster system DIN Pin-end connectors for solder-free connections, insulated, for copper conductors DIN EN Draft AC electricity meters Part 1: General Requirements, Tests and Test Conditions (VDE ) Metering Devices (Accuracy Classes A, B and C) DIN EN (VDE ) Draft AC electricity meters - Part 3: Special requirements Electronic active power consumption meters of Accuracy Classes A, B and C DIN EN Environmental tests - Part 2: Tests; Test Eh: Hammer Tests (IEC :1997); German Version EN :1997 DIN EN Basic and safety rules for man-machine interfaces, identification coding principles for display devices and operator controls DIN EN Symbols for AC meters DIN EN (DIN VDE 0470 T.1) Degrees of protection through housing (IP code) DIN EN Tests for assessing the fire hazard - Part 2-11: Tests with the glow-wire; tests with the glow-wire on the ignitability of end-products (IEC :2000); German Version EN :2001 DIN EN Information technology equipment Safety Part 1: General Requirements (IEC :2005, modified); German Version EN :2006 DIN EN (VDE 0609 T. 1) Connection material Electrical copper conductors; Safety requirements for screw terminals and screwless terminals, Part 1: General Requirements DIN EN Acceptance-testing for electronic meters KC. 1+2 DIN EN IEC AC electricity meters General Requirements, Tests and Test Conditions, Part 11: Metering devices Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 23/186
24 DIN EN (VDE 0418 T. 3-21) IEC DIN EN (VDE ) IEC DIN EN (VDE ) IEC AC electricity meters; Special Requirements, Part 21: Electronic active-power meters of Accuracy Classes 1 and 2 (previously DIN EN 61036, VDE 0418 Part 7, from 01/01) AC electricity meters - Special Requirements - Part 22: Electronic active-power meters of Accuracy Classes 0.2 S and 0.5 S (previously DIN EN from 02/94) AC electricity meters Special Requirements - Part 23: Electronic reactive power consumption meters of Accuracy Classes 2 and 3 (formerly DIN EN from 11/96) DIN EN AC electricity meters - Special Requirements - Part 52: Symbols (IEC :2005); German Version EN :2005 DIN EN VDE AC electricity meters - tariff and load control - Part 21: special requirements for time switches (IEC :2004); German Version EN :2004 DIN EN Electricity meters, meter reading transmission, Part 21: data transmission for fixed and mobile connections (3 rd edition of IEC 61107, formerly IEC 1107) IEC DIN EN /03 Measuring electrical energy - meter reading transmission, tariff and load control - Part 62: Interface Classes (IEC :2002) DIN EN Measuring electrical energy meter reading transmission, Part 61: OBIS Object Identification System CCITT-CRC Standard of CCITT for checksum calculation IEEE 802.3u Base-Tx, Category 5 Cables IEEE 802.3af 2005 Power over Ethernet RFC UDP in accordance with Standard STD 0006 RFC IP in accordance with Standard STD 0005 RFC ICMP in accordance with Standard STD 0005 RFC TCP in accordance with Standard STD 0007 RFC ARP in accordance with Standard STD 0037 RFC Network Time Protocol (Version 3) Specification, Implementation and Analysis RFC IARP in accordance with Draft Standard, formerly RFC 1293, replaced by RFC 2390 RFC US Secure Hash Algorithm 1 (SHA1) RFC Dynamic Configuration of IPv4 Link-Local-Address ISO Information technology - 8-bit-single-byte-coded character sets - Part 15: Latin Alphabet No. 9 ISO Cross-recesses for screws (ISO 4757:1983); German Version EN ISO 4757:1994 Tab. 1: Overview of standards adduced 3.2. Documents (20) The recommendations, announcements, requirements and information specified here are valid only in the latest version in each case. Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 24/186
25 (21) The publication times quoted document the status of The list is to be regarded merely as an introduction; the actual status and scope must be obtained from the approval bodies involved Literature [1] Directive 2004/22/EC of the European Parliament and of the Council dated 31 March 2004 on metering devices, appearing in the Gazette of the European Union L 135/1, MID [2] SML Smart Message Language, Version Calibration-law requirements, requirements and information [3] PTB Requirements: Requirements for electronic ancillary equipment PTB-A , Metering devices for electricity PTB-A ] Cross-section guideline Statutory metrology / general provisions 2002 published in Federal Gazette No. 108a dated 15 June [5] WELMEC 7.2, Issue 1 Software Guide (Measuring Instruments Directive) WELMEC Terms and definitions (22) The alphabetically sorted list below places some terms in relation to their special use in the contest of the general specification for Synchronous Modular Meters (SyM²) Reference time (23) The reference time is the statutory time at the moment when the ongoing seconds index is read off. (24) The statutory time and the seconds index are brought together either in the central software or in the communication equipment on the spot. (25) This mechanism enables us to dispense with a calendar feature within the SyM² basic device and nonetheless be able to always establish a relationship between measured-value formation and time. Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 25/186
26 Statutory time (26) The time information provided by the PTB shall be used as the statutory time Data protocols, useful load (27) The term useful load defines the proportion of information to be transmitted in the context of the goal during data transmission (see Section 5). Usually, however, the data telegrams will require additional elements, such as control characters or framework information, which also have to be transmitted, but do not serve the actual use Data protocols, pull mode (28) In the context of the tlz specification, Pull denotes the conventional paradigm for data transmission, in which a client (e.g. control centre, MDE,...) sends a command to the metering device and this responds with a message. (29) This classic mechanism (apart from exceptions) does not provide for any unrequested activities of the metering devices themselves for filing messages in a control centre. Here, the metering device shall always follow the request Data protocols, push mode (30) Modelled on E DIN : The push mode denotes a unidirectional operating mode in which one of the two communication partners sends a singular and self-contained information unit to its counterpart. (31) For the push mode, stipulations are filed in the SyM² metering device by means of settable variables, on the basis of which a communication device automatically (e.g. once a day) sends a load profile to an addressee using a standard protocol. (32) This form of automatic outputting and filing of messages on a server filed locally in the metering device is designated as push in the context of the tlz specification Measured-value tuples (33) The term measured-value tuples is used to denote a group of data elements, consisting of measured values, particulars of metering device identification of the status, of the time (Seconds Index) and with the signatures for protecting the group. (34) Measured-value tuples shall be outputted periodically by SyM² basic devices Correcting a period generator (35) The correction of a period generator denotes a one-off change in the duration of the ongoing period, and thus does not signify a change in the setpoint value for the period duration. (36) If the duration of a cycle is changed on a one-off basis, this may signify both a shortening and a lengthening of the duration actually needed. Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 26/186
27 Period generator / Clock generator (37) Period generator or clock generator are designations for functional units of the metering device that, depending on the application involved, are able to generate different time intervals. (38) Clock generators used in the context of this document always generate a (theoretically infinite) chain of intervals of the same duration. (39) The term period generator is used in the sense of the classical registration period (see Section 3.3.9), while the term clock generator is utilised for the concept of the seconds index (see Section 4.5) Registration period (40) The registration period denotes the time needed for forming an element of (load) profile recording. It typically used intervals of 1, 3, 5, 10, 15, 30 or 60 minutes. When examples in the context of this document refer to the registration period, a period of 15 minutes is always assumed. In the SyM² basic device, only one registration period is managed Seconds index (41) The term seconds index ( S-I ) is used to denote a natural number growing strictly monotonously in a mathematical sense over the entire lifetime of the SyM² basic device whose aim is to ensure unambiguous assignment of the moment of a measured-value acquisition to the statutory time assumed as the reference system. (42) The time basis for generating the seconds index follows the normative framework stipulations for accuracy (see Section 4.5.4) Operating seconds counter (43) The term operating seconds counter is used to denote a natural number growing strictly monotonously in a mathematical sense over the entire lifetime of the SyM² additional module, whose aim is to ensure an unambiguous assignment of the moment of an event to the statutory time assumed as a reference system. (44) The time basis for generating the operating seconds counter shall follow the stipulations for accuracy laid down in this general specification (see Section 4.5.4) Signature (45) The term signature or signature element, in the context of this general specification, denotes an initially colloquial protection, whose actual form (hash code, public key procedure,...) is specified in more detail in Section (46) The tasks of the signatures in the context of this general specification are to assure the authenticity and integrity of the contents for the measured-value tuple of the SyM² basic device and to protect the firmware to be transported in remote firmware downloading. Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 27/186
28 Synchronising a period generator (47) The term synchronisation of a period generator describes the adaptation of the period generator to an external time raster SyM² metering device (48) The term SyM² metering device denotes a group of SyM² basic device(s) and optional SyM² additional module. (49) The components of a SyM² metering device shall always be connected to each other via a jointly used local bus Reference-arrow system and identification of the measured variables (50) Regarding identification of measured values and other data, the specification laid down for OBIS shall apply within the framework of this. For the definition of the transmission direction of active energy, the specification of the consumer reference arrow system VZS shall apply. (51) The VZS assumes that the customer imports energy from the distribution network (+A). Kunde Netzbetreiber Bezug: Kunde bezieht aus dem Verteilnetz, der Zähler 'sieht': +A Verteilnetz Zählpunkt Lieferung: Kunde liefert in das Verteilnetz, der Zähler 'sieht': -A Verteilnetz Zählpunkt Fig. 3: Definition of the terms import and delivery (see also DIN EN ). Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 28/186
29 4 Requirements 4.1. Overview (52) The SyM² is a three-phase-current meter for direct, semi-indirect or indirect connection with the following performance features: SyM² basic device, general requirements Task / Size Specification Housing Insulating material, flame-retardant in accordance with DIN EN Protection Class Stackability Meter type Function of the register for active-power consumption How the register works for reactive-power consumption Metering Type of connection IP 51 with terminal shroud fitted Devices shall be stackable, regardless of the manufacturer involved, with the terminal shroud fitted, see Section Q meter. In accordance with DIN EN The test for accuracy in the presence of harmonics shall be defined in broad conformity with the stipulations laid down in the standard for activepower metering. Special requirement: As an additional error for fundamental components and harmonics. the limits specified in Section 4.2 must be complied with. Measurement shall always be made as a total over all phase conductors. Direct connection for voltage and current or direct connection for voltage and indirect connection via current transformer, or indirect connection via current and voltage transformer. The SyM² can be operated without damage to the meter in a 4-wire network with zero removed. In this operating mode, too, metrological accuracy must be retained for operation symmetrically in regard to the voltage. The SyM² must be executed as a four-wire meter for three- and four-wire operation. When operated in a 3-wire network, an external auxiliary circuit in accordance with DIN (metering set types M3 and M6) must be used, without any necessity to perform configuration at the SyM². 1 1 Measurement of the phase angle cannot be guaranteed with this type of connection. Im Auftrag für die tlz-projektgruppe, EMSYCON GmbH, Dr. M. Wisy, Seite 29/186
SML. Smart Message Language. Version 1.02
SML Smart Message Language Version 1.02 Please note: the English translation is for informational purposes only. In cases of doubt, the German version shall apply. Seite 1/37 History Version Date Comment
More informationChapter 5. Data Communication And Internet Technology
Chapter 5 Data Communication And Internet Technology Purpose Understand the fundamental networking concepts Agenda Network Concepts Communication Protocol TCP/IP-OSI Architecture Network Types LAN WAN
More informationPolyphase kwh Electricity Meter
Polyphase kwh Electricity Meter Model Type: 5192B USER MANUAL Issue 1.0 E & O E AMPY Automation Ltd. July 2003 doc. ref. CSD 093 Contents 1 Introduction 2 1.1 Purpose 2 2 Definitions 2 2.1 References 2
More informationUSER MANUAL. PingBrother EPIW104 managed passive poe switch & IP watchdog
USER MANUAL PingBrother EPIW104 managed passive poe switch & IP watchdog CONTENT Content... 2 Chapter 1... 3 1.1 Preface... 3 1.2 CE mark warning... 3 1.3 FCC warning... 4 Chapter 2... 5 2.1 Physical description...
More informationCryptography in Metrology
Cryptography in Metrology Experiences, Applications and new Developments Norbert Zisky Content Metrology needs security Secure electronic exchange of measurement data Secure bidirectional communication
More informationTK800-Series Industrial GPRS / UMTS / LTE Router
The new generation LTE with 100 Mbps LTE standard for high transmission rates and good network coverage in sparsely populated areas Dynamic Multipoint VPN GRE, L2TP, IPSec, DMVPN, OpenVPN Simple and fast
More informationDocumentation. M-Bus 130-mbx
Documentation M-Bus 130-mbx Introduction The mx M-Bus module is part of the mx Smart Slot communications family. With the integrated SmartSlot technology, mx systems ag offers automatic consumer data read-out
More informationWELMEC European cooperation in legal metrology
WELMEC 11.2 Issue 1 WELMEC European cooperation in legal metrology Guideline on time depending consumption measurements for billing purposes (interval metering) May 2010 1 WELMEC European cooperation in
More informationEthernet. Customer Provided Equipment Configuring the Ethernet port.
Installing the RDSP-3000A-NIST Master Clock. Ethernet Connect the RJ-45 connector to a TCP/IP network. Equipment The following equipment comes with the clock system: RDSP-3000A-NIST Master Clock Module.
More informationABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
More informationGuide to TCP/IP, Third Edition. Chapter 3: Data Link and Network Layer TCP/IP Protocols
Guide to TCP/IP, Third Edition Chapter 3: Data Link and Network Layer TCP/IP Protocols Objectives Understand the role that data link protocols, such as SLIP and PPP, play for TCP/IP Distinguish among various
More informationChapter 2 - The TCP/IP and OSI Networking Models
Chapter 2 - The TCP/IP and OSI Networking Models TCP/IP : Transmission Control Protocol/Internet Protocol OSI : Open System Interconnection RFC Request for Comments TCP/IP Architecture Layers Application
More informationEthernet. Ethernet. Network Devices
Ethernet Babak Kia Adjunct Professor Boston University College of Engineering ENG SC757 - Advanced Microprocessor Design Ethernet Ethernet is a term used to refer to a diverse set of frame based networking
More informationConvenient Charging of Electric Vehicles
Technical Article Convenient Charging of Electric Vehicles Smart Charging with MICROSAR IP enables flexible charging processes and easy payment Compared to conventionally powered vehicles, electric vehicles
More informationTK700 +70 C -25 C 95% RH EMC TK701G TK701U TK704G TK704U TK704W. TK-Series Cellular Router
+70 C -25 C 95% RH EMC TK701G TK701U TK704G TK704U TK704W The industrial 2G GPRS- and 3G UMTS routers offered by Welotec enables the access to Ethernet devices or a local network remotely via mobile network
More informationChapter 2 TCP/IP Networking Basics
Chapter 2 TCP/IP Networking Basics A network in your home or small business uses the same type of TCP/IP networking that is used for the Internet. This manual provides an overview of IP (Internet Protocol)
More informationModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.
IntesisBox ModBus Server - KNX Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. Integrate KNX based lighting control into your SCADA, BMS, PLC "talking" Modbus. Master
More information1 Data information is sent onto the network cable using which of the following? A Communication protocol B Data packet
Review questions 1 Data information is sent onto the network cable using which of the following? A Communication protocol B Data packet C Media access method D Packages 2 To which TCP/IP architecture layer
More informationQuick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W)
Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Table of Contents Introduction.. Power Over Ethernet (PoE) & Features.... Unpacking and
More informationProtocol Specification & Design. The Internet and its Protocols. Course Outline (trivia) Introduction to the Subject Teaching Methods
The Internet and its Protocols Protocol Specification & Design Robert Elz kre@munnari.oz.au kre@coe.psu.ac.th http://fivedots.coe.psu.ac.th/~kre/ Friday: 13:30-15:00 (Rm: 101)???: xx:x0-xx:x0 (Rm:???)
More information784 INTELLIGENT TRANSPORTATION SYSTEMS NETWORK DEVICES. (REV 11-17-11) (FA 1-5-12) (7-12)
784 INTELLIGENT TRANSPORTATION SYSTEMS NETWORK DEVICES. (REV 11-17-11) (FA 1-5-12) (7-12) SUBARTICLE 784-1.2.2 (of the Supplemental Specifications) is deleted and the 784-1.2.2 Networking Standards: Ensure
More informationOn the M-BUS Interface you can add up to 60 M-BUS Devices (60 unit loads).
EMU M-BUS Logger Index Introduction... 3 Installation... 3 M-BUS Interface... 3 Power supply... 3 LAN... 3 Beginning of operation... 4 Configuration... 7 General Settings... 7 M-BUS Configuration... 9
More informationVirtual KNX/EIB devices in IP networks
WEINZIERL ENGINEERING GmbH WEINZIERL ENGINEERING GMBH F. Heiny, Dr. Y. Kyselytsya, Dr. Th. Weinzierl Bahnhofstr. 6 D-84558 Tyrlaching Tel. +49 (0) 8623 / 987 98-03 E-Mail: info@weinzierl.de Web: www.weinzierl.de
More informationProcess Control and Automation using Modbus Protocol
Process Control and Automation using Modbus Protocol Modbus is the fundamental network protocol used in most industrial applications today. It is universal, open and an easy to use protocol. Modbus has
More information3.1 RS-232/422/485 Pinout:PORT1-4(RJ-45) RJ-45 RS-232 RS-422 RS-485 PIN1 TXD PIN2 RXD PIN3 GND PIN4 PIN5 T+ 485+ PIN6 T- 485- PIN7 R+ PIN8 R-
MODEL ATC-2004 TCP/IP TO RS-232/422/485 CONVERTER User s Manual 1.1 Introduction The ATC-2004 is a 4 Port RS232/RS485 to TCP/IP converter integrated with a robust system and network management features
More informationInternetworking and IP Address
Lecture 8 Internetworking and IP Address Motivation of Internetworking Internet Architecture and Router Internet TCP/IP Reference Model and Protocols IP Addresses - Binary and Dotted Decimal IP Address
More informationUsers manual. TCW181B-CM_R1 Page 1
Ethernet controller TCW181B-CM Users manual 1. Short description TCW181B-CM is 8-channel Ethernet relay board, which is designed to work in IP-based networks and managed by WEB interface or SNMP programs.
More informationUIP1868P User Interface Guide
UIP1868P User Interface Guide (Firmware version 0.13.4 and later) V1.1 Monday, July 8, 2005 Table of Contents Opening the UIP1868P's Configuration Utility... 3 Connecting to Your Broadband Modem... 4 Setting
More informationFollow these steps to prepare the module and evaluation board for testing.
2 Getting Started 2.1. Hardware Installation Procedure Follow these steps to prepare the module and evaluation board for testing. STEP1: Plug the EG-SR-7100A module into the sockets on the test board.
More informationIndoor / Outdoor Antenna
z300 High Precision NTP Time Server Indoor / Outdoor Antenna High Precision NTP Time Server with PoE (Indoor or Outdoor use) synchronized by GPS Revision 4 ZTI / 1 boulevard d'armor / BP 20254 / 22302
More informationBL compact multiprotocol station for Industrial Ethernet SSI interface BLCEN-1M12MT-1SSI
Compact fieldbus I/O module in IP69K EtherNet/IP, Modbus TCP, or PROFINET slave Integrated Ethernet switch 10 Mbps / 100 Mbps Two males M12, 4-pin, D-coded, for fieldbus connection 2 rotary switches for
More informationPCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
More informationE350 series 2. Electricity Meters IEC/MID Residential. ZxF100Ax/Cx. User Manual
Electricity Meters IEC/MID Residential ZxF100Ax/Cx E350 series 2 User Manual Date: 20.12.2011 File name: D000027979 E350 ZxF100Ax Cx series 2 User Manual EN.docx Landis+Gyr D000027979 EN n 2/54 Revision
More informationABB RTU560A Series CMU & Modules
ABB RTU560A Series CMU & Modules 1KGT 150 648 V1.02 March 4, 2012 Slide 1 Contents RTU560A rack solutions March 4, 2012 Slide 2 560CSR01 Available for wall mounting and swing frame Supports redundant power
More informationApplication/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
More informationSSVP SIP School VoIP Professional Certification
SSVP SIP School VoIP Professional Certification Exam Objectives The SSVP exam is designed to test your skills and knowledge on the basics of Networking and Voice over IP. Everything that you need to cover
More informationAppendix B Network, Routing, Firewall, and Basics
Appendix B Network, Routing, Firewall, and Basics This chapter provides an overview of IP networks, routing, and networking. Related Publications As you read this document, you may be directed to various
More informationComputer Network. Interconnected collection of autonomous computers that are able to exchange information
Introduction Computer Network. Interconnected collection of autonomous computers that are able to exchange information No master/slave relationship between the computers in the network Data Communications.
More informationBasic Networking Concepts. 1. Introduction 2. Protocols 3. Protocol Layers 4. Network Interconnection/Internet
Basic Networking Concepts 1. Introduction 2. Protocols 3. Protocol Layers 4. Network Interconnection/Internet 1 1. Introduction -A network can be defined as a group of computers and other devices connected
More informationManual. IP Sensor and Watchdog IPSW2210. I P S W 2 2 1 0 M a n u a l P a g e 1. Relay Output. Power input. 12VDC adapter LED Indicators. 2 Dry.
IP Sensor and Watchdog IPSW2210 Manual Relay Output Power input 12VDC adapter LED Indicators 1 wire 2 Dry Output Green : Power Yellow: Link temperature & humidity contact inputs LED indicator sensor input
More informationCompTIA Network+ (Exam N10-005)
CompTIA Network+ (Exam N10-005) Length: Location: Language(s): Audience(s): Level: Vendor: Type: Delivery Method: 5 Days 182, Broadway, Newmarket, Auckland English, Entry Level IT Professionals Intermediate
More informationDL TC72 Communication Protocols: HDLC, SDLC, X.25, Frame Relay, ATM
DL TC72 Communication Protocols: HDLC, SDLC, X.25, Frame Relay, ATM Objectives: Base training of an engineer for the installation and maintenance of Digital Telecommunications and Internetworking systems.
More informationIT4405 Computer Networks (Compulsory)
IT4405 Computer Networks (Compulsory) INTRODUCTION This course provides a comprehensive insight into the fundamental concepts in data communications, computer network systems and protocols both fixed and
More informationUser s Manual TCP/IP TO RS-232/422/485 CONVERTER. 1.1 Introduction. 1.2 Main features. Dynamic DNS
MODEL ATC-2000 TCP/IP TO RS-232/422/485 CONVERTER User s Manual 1.1 Introduction The ATC-2000 is a RS232/RS485 to TCP/IP converter integrated with a robust system and network management features designed
More informationCSCI 362 Computer and Network Security
The Purpose of ing CSCI 362 Computer and Security Introduction to ing Goals: Remote exchange and remote process control. A few desirable properties: Interoperability, Flexibility, Geographical range, Scalability,
More informationThe Product Description of SmartAX. MT882 ADSL2+ Router
The Product Description of SmartAX MT882 ADSL2+ Router HUAWEI Huawei Technologies Co., Ltd Table of Contents Product Description...1 1. Preface...1 2. Highlights...1 3. Features and Benefits...2 4. Technical
More information48 GE PoE-Plus + 2 GE SFP L2 Managed Switch, 375W
GEP-5070 Version: 1 48 GE PoE-Plus + 2 GE SFP L2 Managed Switch, 375W The LevelOne GEP-5070 is an intelligent L2 Managed Switch with 48 x 1000Base-T PoE-Plus ports and 2 x 100/1000BASE-X SFP (Small Form
More informationIT4504 - Data Communication and Networks (Optional)
- Data Communication and Networks (Optional) INTRODUCTION This is one of the optional courses designed for Semester 4 of the Bachelor of Information Technology Degree program. This course on Data Communication
More information5235 Single Phase Credit Meter
Electricity Meters Residential BS / IEC British Standard 5235 Single Phase Credit Meter User Manual & Technical Specification Date: 20/11/08 Filename: 5235 User Manual Q Pulse No:IB047 Landis+Gyr Page
More information5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...
More informationQuick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
More informationDECT Gigaset N510 IP PRO
DECT Gigaset N510 IP PRO SUMMARY Summary... 1 1. System Features of the DECT Gigaset N510 IP Pro... 2 Base Station Gigaset N510 IP Pro... 2 Environmental Requirements... 3 The base should be placed in
More informationTelemetry system for cathodic protection equipment of underground metal pipelines
RECOMMENDATION PCRA 009 June 2010 Rev. 0 Committee for Cathodic Protection and Associated Coatings Telemetry system for cathodic protection equipment of underground metal pipelines DISCLAIMER: The present
More informationVOIP-211RS/210RS/220RS/440S. SIP VoIP Router. User s Guide
VOIP-211RS/210RS/220RS/440S SIP VoIP Router User s Guide Trademarks Contents are subject to revise without prior notice. All trademarks belong to their respective owners. FCC Warning This equipment has
More informationInstallation and setup guide V 1.0
V o I P G S M G A T E BlueGate SIP 1 Installation and setup guide V 1.0 1. General description 1.1 Technical parametres Dimensions 100 x 130 x 37 mm Weight 850 g Operating position various Operating condition
More informationSSVVP SIP School VVoIP Professional Certification
SSVVP SIP School VVoIP Professional Certification Exam Objectives The SSVVP exam is designed to test your skills and knowledge on the basics of Networking, Voice over IP and Video over IP. Everything that
More informationENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION
ENET-710 ENET-710 - Ethernet Module JAN / 06 ENET-710 FOUNDATION E N E T 7 1 0 ME smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is
More informationBroadband Phone Gateway BPG510 Technical Users Guide
Broadband Phone Gateway BPG510 Technical Users Guide (Firmware version 0.14.1 and later) Revision 1.0 2006, 8x8 Inc. Table of Contents About your Broadband Phone Gateway (BPG510)... 4 Opening the BPG510's
More informationMulti-Homing Security Gateway
Multi-Homing Security Gateway MH-5000 Quick Installation Guide 1 Before You Begin It s best to use a computer with an Ethernet adapter for configuring the MH-5000. The default IP address for the MH-5000
More informationAgenda. Distributed System Structures. Why Distributed Systems? Motivation
Agenda Distributed System Structures CSCI 444/544 Operating Systems Fall 2008 Motivation Network structure Fundamental network services Sockets and ports Client/server model Remote Procedure Call (RPC)
More informationLevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual
LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual Ver. 1.0.0-0711 1 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital
More informationIndustrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter
ICS-2 S15 Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter Cost Effective Solution for RS-232 / RS-422 / RS-485 to Industrial Ethernet Application PLANET ICS-210x series Smart Media Converter
More informationData Link Protocols. TCP/IP Suite and OSI Reference Model
Data Link Protocols Relates to Lab. This module covers data link layer issues, such as local area networks (LANs) and point-to-point links, Ethernet, and the Point-to-Point Protocol (PPP). 1 TCP/IP Suite
More informationWEB CONFIGURATION. Configuring and monitoring your VIP-101T from web browser. PLANET VIP-101T Web Configuration Guide
WEB CONFIGURATION Configuring and monitoring your VIP-101T from web browser The VIP-101T integrates a web-based graphical user interface that can cover most configurations and machine status monitoring.
More informationPower over Ethernet technology for industrial Ethernet networks
Power over Ethernet technology for industrial Ethernet networks Introduction Ethernet networking has grown beyond office and home usage to become a very successful protocol suite used in many industrial
More informationNetworking 4 Voice and Video over IP (VVoIP)
Networking 4 Voice and Video over IP (VVoIP) Course Objectives This course will give delegates a good understanding of LANs, WANs and VVoIP (Voice and Video over IP). It is aimed at those who want to move
More informationIntesisBox KNX Modbus TCP master
IntesisBox KNX TCP master Gateway for integration of TCP slave devices into KNX control systems. Integrate any TCP slave device into KNX. KNX TCP slave EIB Bus IntesisBox Ethernet slave LinkBoxEIB Configuration
More informationFOUNDATION Fieldbus High Speed Ethernet Control System
FOUNDATION Fieldbus High Speed Ethernet Control System Sean J. Vincent Fieldbus Inc. Austin, TX, USA KEYWORDS Fieldbus, High Speed Ethernet, H1, ABSTRACT FOUNDATION fieldbus is described in part by the
More informationNotes Odom, Chapter 4 Flashcards Set: http://www.flashcardmachine.com/1162711/b41c
EDTECH 552 (SP11) Susan Ferdon Notes Odom, Chapter 4 Flashcards Set: http://www.flashcardmachine.com/1162711/b41c telco Leased Line CSU/DSU Local Telephone Company Owns the cables and has right of way
More informationCCNA 1: Networking Basics. Cisco Networking Academy Program Version 3.0
CCNA 1: Networking Basics Cisco Networking Academy Program Version 3.0 Table of Contents CCNA 1: NETWORKING BASICS...1 TARGET AUDIENCE...3 PREREQUISITES...3 COURSE DESCRIPTION...3 COURSE OBJECTIVES...3
More informationBNI IOL-709-000-K006 BNI IOL-710-000-K006. IO-Link Sensor-Hub analog User s Guide
BNI IOL-709-000-K006 BNI IOL-710-000-K006 IO-Link Sensor-Hub analog User s Guide Inhalt 1 Notes to the user 2 1.1 About this guide 2 1.2 Structure of the guide 2 1.3 Typographical conventions 2 Enumerations
More informationAlgemene Theorie en Vaardigheden 2. April 2014 Theaterschool OTT-2 1
Les 6 Showcontrol April 2014 Theaterschool OTT-2 1 OSI layers versus equipment Layer 1: Physical Network Interface Card (NIC) Hub (multiport repeater) Modem (modulator/demodulator, converts signals) Layer
More informationManagement Software. Web Browser User s Guide AT-S106. For the AT-GS950/48 Gigabit Ethernet Smart Switch. Version 1.0.0. 613-001339 Rev.
Management Software AT-S106 Web Browser User s Guide For the AT-GS950/48 Gigabit Ethernet Smart Switch Version 1.0.0 613-001339 Rev. A Copyright 2010 Allied Telesis, Inc. All rights reserved. No part of
More informationProvides one channel for Ethernet over existing
LB304A LBPS301A LBPS304A Hardened Ethernet Extender Quick Start Guide Provides one channel for Ethernet over existing voice-grade copper twisted-pair wire. copper BLACK wire. BOX Customer Support Information
More informationINTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series
Communication system for the management of electrical installations INTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series MID Approval Technology for energy efficiency PLC Communications (Power Line Communication)
More informationAccess Point Configuration
Access Point Configuration Developed by IT +46 Based on the original work of: Onno Purbo and Sebastian Buettrich Goals Provide a general methodology to installation and configuration of access points Give
More informationComputer Networks CS321
Computer Networks CS321 Dr. Ramana I.I.T Jodhpur Dr. Ramana ( I.I.T Jodhpur ) Computer Networks CS321 1 / 22 Outline of the Lectures 1 Introduction OSI Reference Model Internet Protocol Performance Metrics
More informationCourse Overview: Learn the essential skills needed to set up, configure, support, and troubleshoot your TCP/IP-based network.
Course Name: TCP/IP Networking Course Overview: Learn the essential skills needed to set up, configure, support, and troubleshoot your TCP/IP-based network. TCP/IP is the globally accepted group of protocols
More informationICTTEN8195B Evaluate and apply network security
ICTTEN8195B Evaluate and apply network security Release 1 ICTTEN8195B Evaluate and apply network security Modification History Release Release 2 Comments This version first released with ICT10 Integrated
More informationRemote Monitoring Unit SC8100. Monitoring Unit SC8100
Monitoring Unit SC8100 Remote Monitoring Unit SC8100 Environmental monitoring of any facilities, control of security breaches, temperatures, smoke, water leakages, voltages and more. Compatible with all
More information6.40A AudioCodes Mediant 800 MSBG
AudioCodes Mediant 800 MSBG Page 1 of 66 6.40A AudioCodes Mediant 800 MSBG 1. Important Notes Check the SIP 3 rd Party Validation Website for current validation status. The SIP 3 rd party Validation Website
More information1.3. The network element must have the ability to be configured in a point to point, point to multi point, and daisy chain configuration.
DESCRIPTION This work shall consist of furnishing and installing 10/100 Ethernet over Twisted Pair (TWP) Copper Modems in accordance with the contract documents and as directed by the Engineer. MATERIALS
More informationProgramming made easy. talento plus
Technical specifications and other information are subject to change without notice. 82.01.1271.7 Programming made easy. Grässlin GmbH Bundesstraße 36 D-78112 St. Georgen Germany Phone: +49 (0) 7724 /
More informationPePWave Surf Series PePWave Surf Indoor Series: Surf 200, AP 200, AP 400
PePWave Surf Series PePWave Surf Indoor Series: Surf 200, AP 200, AP 400 PePWave Surf Outdoor Series: Surf AP 200/400-X, PolePoint 400-X, Surf 400-DX User Manual Document Rev. 1.2 July 07 COPYRIGHT & TRADEMARKS
More informationProcedure: You can find the problem sheet on Drive D: of the lab PCs. Part 1: Router & Switch
University of Jordan Faculty of Engineering & Technology Computer Engineering Department Computer Networks Laboratory 907528 Lab. 2 Network Devices & Packet Tracer Objectives 1. To become familiar with
More informationBIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter
BIT COMMANDER Serial RS232 / RS485 to Ethernet Converter (Part US2000A) Copyrights U.S. Converters 1 Contents Overview and Features... 3 Functions..5 TCP Server Mode... 5 Httpd Client Mode.5 TCP Auto mode....6
More informationUPPER LAYER SWITCHING
52-20-40 DATA COMMUNICATIONS MANAGEMENT UPPER LAYER SWITCHING Gilbert Held INSIDE Upper Layer Operations; Address Translation; Layer 3 Switching; Layer 4 Switching OVERVIEW The first series of LAN switches
More informationPCAN-MicroMod Universal I/O Module with CAN Interface. User Manual. Document version 2.1.0 (2014-01-16)
PCAN-MicroMod Universal I/O Module with CAN Interface User Manual Document version 2.1.0 (2014-01-16) Products taken into account Product Name Part number Model PCAN-MicroMod IPEH-002080 with firmware
More informationChapter 7: Computer Networks, the Internet, and the World Wide Web. Invitation to Computer Science, C++ Version, Third Edition
Chapter 7: Computer Networks, the Internet, and the World Wide Web Invitation to Computer Science, C++ Version, Third Edition Objectives In this chapter, you will learn about: Basic networking concepts
More informationEnergy Communication Unit (ECU)
Altenergy Power System Energy Communication Unit (ECU) Installation and User Manual (For ECU-3 V3.8) ALTENERGY POWER SYSTEM INC. All rights reserved TABLE OF CONTENTS 1.0 Introduction... 2 2.0 Installation...
More informationComputer Networking: A Survey
Computer Networking: A Survey M. Benaiah Deva Kumar and B. Deepa, 1 Scholar, 2 Assistant Professor, IT Department, Sri Krishna College of Arts and Science College, Coimbatore, India. Abstract- Computer
More informationOpenScape Business V2
OpenScape Business V2 Tutorial System Device@Home Configuration Version 1.1 Table of Contents 1. Configuration Overview 4 1.1. Network Scenario Description: 4 1.2. Configuration Steps 5 1.2.1. Overview
More informationTechnical Information POWER PLANT CONTROLLER
Technical Information POWER PLANT CONTROLLER Content The Power Plant Controller offers intelligent and flexible solutions for the control of all PV power plants in the megawatt range. It is suitable for
More informationTeltonika FM41XX. Configurator v. 1.0
Teltonika FM41XX Configurator v. 1.0 1. First steps Connect Teltonika FM41XX (PIN1 for plus and PIN11 ground ) to the voltage supply 10-30 V as shown below and GPS, GSM antennas. (GSM is long and thin,
More informationCSE 3461 / 5461: Computer Networking & Internet Technologies
Autumn Semester 2014 CSE 3461 / 5461: Computer Networking & Internet Technologies Instructor: Prof. Kannan Srinivasan 08/28/2014 Announcement Drop before Friday evening! k. srinivasan Presentation A 2
More information2. IP Networks, IP Hosts and IP Ports
1. Introduction to IP... 1 2. IP Networks, IP Hosts and IP Ports... 1 3. IP Packet Structure... 2 4. IP Address Structure... 2 Network Portion... 2 Host Portion... 3 Global vs. Private IP Addresses...3
More informationOSBRiDGE 5XLi. Configuration Manual. Firmware 3.10R
OSBRiDGE 5XLi Configuration Manual Firmware 3.10R 1. Initial setup and configuration. OSBRiDGE 5XLi devices are configurable via WWW interface. Each device uses following default settings: IP Address:
More informationConfiguration Management: Best Practices White Paper
Configuration Management: Best Practices White Paper Document ID: 15111 Contents Introduction High Level Process Flow for Configuration Management Create Standards Software Version Control and Management
More informationGPS NTP TIME SERVER Rack Version V2
GPS NTP TIME SERVER Rack Version V2 Description: Server is dedicated to synchronize network devices local time/date to Universal Time (UTC) Devices synchronizing own local time through the NTP V3 protocol.
More information1.Eastron SDM220Modbus Smart Meter Modbus Protocol Implementation V1.0
1.Eastron SDM220Modbus Smart Meter Modbus Protocol Implementation V1.0 1.1 Modbus Protocol Overview This section provides basic information for interfacing the Eastron Smart meter to a Modbus Protocol
More information