ANALYSIS OF LEAKAGE INFLUENCE WITHIN CAPILLARY HEAT PIPE RECUPERATIVE HEAT EXCHANGER

Size: px
Start display at page:

Download "ANALYSIS OF LEAKAGE INFLUENCE WITHIN CAPILLARY HEAT PIPE RECUPERATIVE HEAT EXCHANGER"

Transcription

1 INFRASTRUKTURA I EKOLOGIA TERENÓW WIEJSKICH INFRASTRUCTURE AND EKOLOGY OF RURAL AREAS Analysis of leakage influence Nr 3/2007, POLSKA AKADEMIA NAUK, Oddział w Krakowie, s Komisja Technicznej Infrastruktury Wsi Daniel Adamovsky, Pavel Neuberger, Radomír Adamovsky ANALYSIS OF LEAKAGE INFLUENCE WITHIN CAPILLARY HEAT PIPE RECUPERATIVE HEAT EXCHANGER Summary The paper analyses the leakage of air-to-air recovery heat exchanger consisting of 00 capillary thermal tubes.5 m long and aligned in ten rows. The operation of the recovery exchanger prototype was tested in a pigsty. The analysis focuses on how the exchanger leakage affects the heat utilisation efficiency of the air ducted from the pigsty, changes in supply/exhaust air flow rate ratio, supply air temperature, thermal output obtained, and exchanger s total thermal and mass balances. The results obtained in in-process measurements and the mass and thermal balances show that the exchange leakage causes the outside supply air to contain % of the pigsty exhaust air. The percentage of the pigsty air increases with the increase of mass flow rates of supply and exhaust air. This leakage resulted particularly in a major change in supply and exhaust air mass flow rates, higher moisture content, temperature and thermal flow of the air conducted in the pigsty. The change in air flow rates resulted in ventilation change so that the overpressure ventilation took place instead of balanced ventilation. This change led to increased thermal losses by air penetrating through leaks in the peripheral building structures. Increased supply air moisture content made it necessary to increase ventilation intensity in order to meet the required pigsty air parameters with respect of animal wellbeing and protection of peripheral building structures against dampness deterioration. The thermal flow increase of the air conducted in the pigsty due to the high enthalpy of the pigsty air mixed resulted in the higher secondary heat utilisation efficiency. The actual efficiency, however, was considerably lower. The differences of % between the exchanger s measured and actual thermal efficiency according to relation (6) and those of % between the exchanger s measured and actual running efficiency (3) increase as the ratio of supply and exhaust air mass flow rates increase. Key words: exchanger; recuperation; thermal performance; blending efficiency; thermal efficiency; thermal balance; mass balance 2

2 Daniel Adamovsky, Pavel Neuberger, Radomír Adamovsky 22 INTRODUCTION A negative result of leaking separation walls or heat-exchange surfaces of air-to-air type recuperation exchangers is blending of the exhaust air with the supply air. This problem becomes significant in stables. Leaking exchanger separation walls can lead to increased concentration of noxious gases, humidity and also undesirable micro-organisms inside the stable. Untightness of air-to-air recuperation heat exchangers is objectively expressed in terms of the air blending efficiency, introduced by Marquardt (983): E x x e2 e m = [-] () xi xe where in relation (): x e2 is moisture content of outdoor air behind the exchanger [ kg. x e is moisture content of outdoor air before the exchanger [ kg. x i is moisture content of stable air before the exchanger [ kg. da da kg.]; kg.]; kg da.]. The issues of leaking plate exchangers in local ventilation units were studied by Manz, Huber, Helfefinger [200]. They analysed the effects of leakages and blending of air streams on the efficiency of utilising heat from the exhaust air. Between 5 and 24% of exhaust air was added to the supply air in the test units. This resulted in reduced efficiency of heat utilisation from the exhaust air by as much as 24%, with the minimum drop 3%. The issues of identifying leaks in central ventilation units were studied by Roulet et al. [200]. To find leaks, they used visualisation gases injected into the air stream. A 7% leakage was found in the exchanger. The whole unit showed a 20% leakage. Due to the leakages, the efficiency dropped on average by 45%. Adamovský, Hutla, Blažek [996] studied the effects of leakages and contamination of heat-exchange surfaces on the efficiency of a gravitational heat pipe heat exchanger in a stable used for breeding Broiler chickens. During the first six days of the breeding process, exchanger leakages combined with an intensive fouling of heat-exchange surfaces, resulted in a drop in thermal efficiency by 5.8% a day. Kára Adamovský [2000] studied the changes in air blending efficiency in a calf breeding stable as a function of operation time. In a new exchanger, blending efficiency E m = was obtained, measured according to relation (). After months of the exchanger operation in the mode without condensation of air moisture from the exhaust air, the blending efficiency dropped to E m = When running the exchanger with partial condensation of the air moisture, the efficiency dropped after 9 months of operation to only E m =

3 Analysis of leakage influence The objective of our study was to determine leakages in a prototype capillary heat pipe heat exchanger, and analyse the effects of these leakages on the utilisation of heat from the exhaust air, changes in the ratio of the supply and exhaust air, the achieved thermal output and overall thermal and mass balance of the exchanger.. Measurement method METHODS The prototype recuperation capillary heat pipe exchanger was tested in a stable used for breeding pigs. The exchanger was assembled from 00 aluminium heat tubes arranged in 0 rows on a plane. The effective tube length was 455 mm. The tubes were filled with ammoniac. The transversal as well as longitudinal spacing of the tubes in rows was 64 mm. The cross-sectional area of the supply as well as exhaust air flow was m 2. The fans were powered by two-speed electric motors. Schematic diagram of the exchanger measurements is shown in fig.. t e2 ; φ e2 ; x e2 t i ; φ i ; x i V τ,e,ma t e ; φ e ; x e t i2 ; φ i2 ; x i2 V τ,i,ma Figure. Schematic diagram of capillary heat pipe heat exchanger measurements AGRA 630/2 axial fan; 2. AGRA 465/2 axial fan 23

4 Daniel Adamovsky, Pavel Neuberger, Radomír Adamovsky Legend to Fig. : t i temperature of stable air before the exchanger [ C ]; φ i relative humidity of stable air before the exchanger [-]; x i moisture content of stable air before the exchanger [ kg. kg da. ]; t i2 temperature of stable air behind the exchanger [ C ]; φ i2 relative humidity of stable air behind the exchanger [-]; x i2 moisture content of stable air behind the exchanger [ kg. kg da. ]; t e temperature of outdoor air before the exchanger [ C ]; φ e relative humidity of outdoor air before the exchanger [-]; x e moisture content of outdoor air before the exchanger [ kg. kg da. ]; t e2 temperature of outdoor air behind the exchanger [ C ]; φ e2 relative humidity of outdoor air behind the exchanger [-]; x e2 moisture content of outdoor air behind the exchanger [ kg. kg da. ]; V τ,i,ma volumetric flow of stable air behind the exchanger [ m 3. s ]; V τ,e,ma volumetric flow of outdoor air behind the exchanger [ m 3. s ]. 2. Theoretical analysis Blending of exhaust stable air and outdoor air occurs when x e2 > x e. The volumetric flow of exhaust stable air ΔV τ,i,ma, which is added to the outdoor supply air can be derived from the exchanger mass equilibrium equation: Δ m [ kg.s ] (2) τ, i,da xi,2 + mτ,e,da xe = mτ,e,da xe2 m τ, e,da mτ,e,da Δmτ,i,da = [ kg da. s ] (3) Δm τ,i,da is mass flow of stable air added to supply air, converted to kg of dry air [ kg da. s ]; xi + xi2 xi,2 = is median moisture content [ kg. kg da.]; 2 m τ,e,da is the actual mass flow (without added air) of outdoor air, converted to kg of dry air [ kg da. s ]; m τ,e,da is measured mass flow of outdoor air, converted to kg of dry air [ kg da. s ]. Index: i is air removed from the stable; e outdoor air supplied to the stable; da dry air; ma moist air. 24

5 For mass flows of dry air m τ,da, the following equation applies: m m V = ρ τ,ma τ,ma ma τ,da = [ ( + x) ( + x) V τ,ma is volumetric air flow [ m 3. s ]; 3 ρ ma is density of air [ kg. m ]; x is moisture content of air [ kg. kg da. ] Analysis of leakage influence kg da. s ] (4) By substituting relation (4) into equations (2) and (3), we get for ΔV τ,i,ma the following equation: ΔV ( xe2 xe ) ( x x ) ( + xi,2 ) ρ e2 τ,e, ma ( + x ) ρ = [ m 3. s ] (5) τ, i,ma V i,2 e e2 i,2 ti + ti2 3 ρ i,2 is the median of air densities at temperature ti,2 = [ kg.m ]. 2 The actual volumetric air flows V τ,i, ma and V τ,e, ma we calculate from equations: V = [ m 3. s ] (6) τ, i,ma Vτ,i,ma + ΔVτ,i,ma V = [ m 3. s ] (7) τ, e,ma Vτ,e,ma ΔVτ,i,ma Thermal output Q τ,r, which was obtained by heat transmission through the exchanger wall between stable air and outdoor air is determined by equation: h e2 h e ( h ) Q τ [W ] (8), R = m τ,e,sv e2 he is specific enthalpy of outdoor air after being heated in the exchanger [ J.kg da ]; is specific enthalpy of outdoor air before being heated in the exchanger [ J.kg da ]. Recuperated thermal output Q τ,r can be calculated from the equilibrium equations of thermal outputs inside the exchanger. On the left side of the equation there is the actual output Q τ,e supplied by the flow of outdoor air, thermal 25

6 Daniel Adamovsky, Pavel Neuberger, Radomír Adamovsky Q τ output Δ, i communicated to the supplied outdoor air by blending it with the stable air, and thermal output. On the right side of the equation there is Q τ Q τ output,e 2 supplied to the stable. The following relation applies:, R In equation (9): Qτ + Δ = [W ] (9), e Qτ,i + Qτ,R Qτ,e2 V ρ Qτ [W ] (0) τ,e,ma e, e = h e e ( + x ) ΔV ρ ΔQτ ( h ) [W ] () τ,i,ma i,2, i = i,2 he,2 ( + xi,2 ) h i,2 is air enthalpy corresponding to air temperature h e,2 is air enthalpy corresponding to air temperature τ,e,ma e2, e2 = h e2 e2 ( + x ) ti + 2 ti 2 t 2 te + e2 [ J.kg da ]; [ J.kg da ]. V ρ Qτ [W ] (2) The efficiency of utilising heat present in the stable exhaust air, determined by the ratio between the gained thermal output Q τ,r and the overall performance which can be obtained from the cooled air Q τ,i Q τ,e, we have defined from the equation [Adamovský et al. 2004]: Qτ,R η R = [-] (3) Q Q τ,i τ,e For thermal flows Q τ,i and Q τ,e the following applies: Q τ [W ] (4), i = m τ,i,da hi Q τ [W ] (5), e = m τ,e,da he h i is specific enthalpy of stable air before the exchanger [ J.kg da ]. 26

7 Analysis of leakage influence Thermal efficiency η R,t which eliminates the effect of mass flows, was calculated using the following relation: t t e2 e η R,t = [-] (6) ti te To calculate the actual temperature t e2 achieved by mere heating of the air by mentioned above thermal output Q τ,r, we used the relation [Marquart 983]: t t E t e2 m i e2 = [ C] (7) Em RESULTS AND DISCUSSION Table summarises the results of measurements and solving equations (2) through to (7). The values with upper line are based on actual volumetric flows V τ,i,ma and V τ,e, ma, which eliminate thermal flows and enthalpies generated by adding exhaust air into the supply outdoor air. The following arises from the measured values and calculations: share of ΔV τ,i,ma in V τ,e,ma for the given exchanger is %; with growing V /, ΔV τ,i,ma /V τ,e,ma increases τ, i,ma Vτ,e, ma increase in ΔV τ,i,ma /V τ,e,ma corresponds to increasing difference Δ xe = xe2 xe. With ΔVτ, i,ma 0,3 Vτ,e, ma, Δ xe > g kg da ; thermal efficiency η Rt decreases with increasing ΔV τ,i,ma /V τ,e,ma ; differences between the actual η Rt and measured η Rt thermal efficiency (6) are in the range %, and increase with increasing ΔV τ,i,ma /V τ,e,ma ; ratio ratio Q Q Q τ,e2 τ,e2 τ,r ΔQ Q τ,i Q τ,e τ,e actual efficiency decreases with increasing ΔV τ,i,ma /V τ,e,ma ; increases with increasing ΔV τ,i,ma /V τ,e,ma ; η R is significantly lower than η R. 27

8 Daniel Adamovsky, Pavel Neuberger, Radomír Adamovsky Table. Results of process measurement and calculation Measurement number Results of measurement t i [ C ] φ i [-] x i [ ] g.kg da t i2 [ C ] φ i2 [-] x i2 [ g. ] kg da V τ,i,ma [ m 3. s ] t e [ C ] φ e [-] x e [ ] g.kg da t e2 [ C ] φ e2 [-] x e2 [ g. ] kg da V τ,e,ma [ m 3. s ] V τ,i,ma /V τ,e,ma [-] s Results of calculation ΔV τ,i,ma [ m. ] V τ [ m 3. s ] ,i,ma V τ, e, [ ma 3. s m ] Q τ,e2 [ kw ] Q τ [ kw ],e ΔQ τ,i [ kw ] Q τ,r [ kw ] t [ C ] e2 η R,t [-] η R,t [-] η R [-] η [-] R V, i,ma / Vτ,e,ma τ [-]

9 Analysis of leakage influence CONCLUSIONS The results of testing the prototype recuperation capillary heat pipe exchanger proved leaks in the exchanger separation walls. Those leaks in the separation wall were manifested by increased value of the thermal flow and moisture content of the air supplied to the stable and also by a significant change in the V τ,i,ma /V τ,e,ma ratio. The increased value of thermal flow of the air supplied to the stable, caused by high enthalpy of the added stable air had an impact on the secondary heat utilisation efficiency η R. This acquired higher values. The actual efficiency η R was lower. Increasing moisture content of the supplied outdoor air induced increased ventilation intensity. The reason for this was to maintain the required parameters of the stable air to provide comfort for the animals and to protect peripheral building structures against damage by moisture. Change in the V τ,i,ma /V τ,e,ma ratio lead to change in the character of ventilation. Instead of the designed equal-pressure ventilation when V τ, i,ma / V τ,e, ma, overpressure ventilation took place, V τ,i,ma /V τ,e,ma <. This change resulted in increased thermal losses due to uncontrolled infiltration of air through the building s peripheral walls. No negative consequences of blending the exhaust air with the supply air, which may have lead to increased concentrations of unsuitable or harmful microorganisms in the stable air, have been proven. We came across the problem of leaking heat-exchange surfaces also when testing plate recuperation exchangers, as well as gravitation heat pipe heat exchangers. REFERENCES Adamovský, R., Hutla, P., Blažek, M Analysis of heat efficiency of recuperation exchangers in microclimate exacting stables. Scientia Agriculturae Bohemica, vol. 27, no. 4, p Adamovský, R., Adamovský, D., Herák, D Exergy of heat flows of the air-to-air plate heat exchanger. Res. Agr. Eng., 2004, 50, (4), ISSN Kára, J., Adamovský, R Analysis of changes of thermic efficiency during operation of the table recuperation exchangers. Scientia Agriculturae Bohemica, vol. 3, no. 4, p Marquardt, G Wärmerückgewinnung aus Forluft, VEB Verlag Technik, Berlin, 48 p. Manz, H., Huber, H., Helfenfinger, D., 200. Impact of air leakages and short circuits in ventilation units with heat recovery on ventilation efficiency and energy requirements for heating. Energy and Buildings, no. 33, p Roulet, C.-A., Hejdy, F. D., Foradini, F., Pobiti M.-C., 200 Real heat recovery with air handling units. Energy and Buildings, no. 33, p

10 Daniel Adamovsky, Pavel Neuberger, Radomír Adamovsky Daniel Adamovsky, C.Sc. Czech Technical University, Faculty of Civil Engineering, Prague, Czech Republic Pavel Neuberger, C.Sc. Prof. Radomír Adamovsky, C.Sc., Ph.D Czech University of Life Sciences, Faculty of Engineering, Prague, Czech Republic Rewiever: Prof. Jerzy Gruszczyński, Dr.Sc., Ph.D 30

THE OPTIMISATION OF BIOMASS COMBUSTION IN SMALL BOILERS

THE OPTIMISATION OF BIOMASS COMBUSTION IN SMALL BOILERS The optimisation of biomass INFRASTRUKTURA I EKOLOGIA TERENÓW WIEJSKICH INFRASTRUCTURE AND ECOLOGY OF RURAL AREAS Nr 6/28, POLSKA AKADEMIA NAUK, Oddział w Krakowie, s. 63 69 Komisja Technicznej Infrastruktury

More information

AIR STREAMS IN BUILDING FOR BROILERS

AIR STREAMS IN BUILDING FOR BROILERS AIR STREAMS IN BUILDING FOR BROILERS PAVEL KIC - MILAN ZAJÍČEK ABSTRACT The Fluent CFD software is used to do numerical analysis of existing poultry house during the summer and winter periods. Principal

More information

saving energy in comfort Factsheet Recair Enthalpy

saving energy in comfort Factsheet Recair Enthalpy saving energy in comfort Factsheet Recair Enthalpy Introduction Enthalpy Exchanger The enthalpy exchanger is able to transfer both sensible heat and latent heat (moisture) from the cooled to the heated

More information

New Trends in the Field of Automobile Air Conditioning

New Trends in the Field of Automobile Air Conditioning New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic

More information

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)

More information

Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems

Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems Abstract Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems M. Jaradat, R. Heinzen, U. Jordan, K. Vajen Kassel University (Germany), Institute

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

Installation, operation and maintenance manual TX 35A

Installation, operation and maintenance manual TX 35A Installation, operation and maintenance manual TX 35A Rev.10 may 2012 Page 1 of 18 1.0.0 Table of contents INSTALLATION, OPERATION AND MAINTENANCE MANUAL...1 1.0.0 TABLE OF CONTENTS...2 2.0.0 ILLUSTRATIONS...2

More information

How To Get A Passive House

How To Get A Passive House Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2015 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Product

More information

A heat pipe heat recovery heat exchanger for a mini-drier

A heat pipe heat recovery heat exchanger for a mini-drier A heat pipe heat recovery heat exchanger for a mini-drier A Meyer Department of Mechanical Engineering, University of Stellenbosch, Stellenbosch R T Dobson Department of Mechanical Engineering, University

More information

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A Int. J. Mech. Eng. & Rob. Res. 213 Jyoti Soni and R C Gupta, 213 Research Paper ISSN 2278 149 www.ijmerr.com Vol. 2, No. 1, January 213 213 IJMERR. All Rights Reserved PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION

More information

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =

More information

AIR MOVEMENT CHARACTERISTICS INSIDE A COW BARN WITH NATURAL VENTILATION UNDER NO-WIND CONDITIONS IN THE WINTER SEASON

AIR MOVEMENT CHARACTERISTICS INSIDE A COW BARN WITH NATURAL VENTILATION UNDER NO-WIND CONDITIONS IN THE WINTER SEASON INFRASTRUKTURA I EKOLOGIA TERENÓW WIEJSKICH INFRASTRUCTURE AND ECOLOGY OF RURAL AREAS Air movement characteristics Nr 11/2010, POLSKA AKADEMIA NAUK, Oddział w Krakowie, s. 159 164 Komisja Technicznej Infrastruktury

More information

Testing methods applicable to refrigeration components and systems

Testing methods applicable to refrigeration components and systems Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University

More information

Condensing Boiler Efficiency

Condensing Boiler Efficiency Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2

More information

Under sill units. Type FSL-B-ZAS

Under sill units. Type FSL-B-ZAS .1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract

More information

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Thermal Mass Availability for Cooling Data Centers during Power Shutdown 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,

More information

Performance Test of Solar Assisted Solid Desiccant Dryer

Performance Test of Solar Assisted Solid Desiccant Dryer Performance Test of Solar Assisted Solid Desiccant Dryer S. MISHA 1,2,*, S. MAT 1, M. H. RUSLAN 1, K. SOPIAN 1, E. SALLEH 1, M. A. M. ROSLI 1 1 Solar Energy Research Institute, Universiti Kebangsaan Malaysia,

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com. Vicot Solar Air Conditioning V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.cn Cooling, heating, and domestic hot water. Return on investment

More information

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D) Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Test Report No. C1319LPEN

Test Report No. C1319LPEN Institut für Solartechnik Hochschule für Technik Rapperswil Oberseestrasse 10, CH 8640 Rapperswil Tel +41 55 222 48 21, Fax +41 55 222 48 44 www.solarenergy.ch Ordered by: Thermics S.r.l. Via dell'olmo

More information

MODELING, SIMULATION AND DESIGN OF CONTROL CIRCUIT FOR FLEXIBLE ENERGY SYSTEM IN MATLAB&SIMULINK

MODELING, SIMULATION AND DESIGN OF CONTROL CIRCUIT FOR FLEXIBLE ENERGY SYSTEM IN MATLAB&SIMULINK MODELING, SIMULATION AND DESIGN OF CONTROL CIRCUIT FOR FLEXIBLE ENERGY SYSTEM IN MATLAB&SIMULINK M. Pies, S. Ozana VSB-Technical University of Ostrava Faculty of Electrotechnical Engineering and Computer

More information

CO 2 41.2 MPa (abs) 20 C

CO 2 41.2 MPa (abs) 20 C comp_02 A CO 2 cartridge is used to propel a small rocket cart. Compressed CO 2, stored at a pressure of 41.2 MPa (abs) and a temperature of 20 C, is expanded through a smoothly contoured converging nozzle

More information

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015 Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes

Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes Jonathan Coulter, Bruce Davis, Cyrus Dastur, Melissa Malkin-Weber and Tracy Dixon Advanced Energy,

More information

MECHANICAL ENGINEERING EXPERIMENTATION AND LABORATORY II EXPERIMENT 490.07 ENGINE PERFORMANCE TEST

MECHANICAL ENGINEERING EXPERIMENTATION AND LABORATORY II EXPERIMENT 490.07 ENGINE PERFORMANCE TEST MECHANICAL ENGINEERING EXPERIMENTATION AND LABORATORY II EXPERIMENT 490.07 ENGINE PERFORMANCE TEST 1. Objectives To determine the variation of the brake torque, brake mean effective pressure, brake power,

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning

More information

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Kai Sirén and Ala Hasan Helsinki University of Technology, Finland Corresponding email: kai.siren@tkk.fi

More information

Research on the Air Conditioning Water Heater System

Research on the Air Conditioning Water Heater System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions

Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions M. Bianchi Janetti 1, F. Ochs 1 and R. Pfluger 1 1 University of Innsbruck, Unit for Energy Efficient Buildings,

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES Vol. XX 2012 No. 4 28 34 J. ŠIMIČEK O. HUBOVÁ NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES Jozef ŠIMIČEK email: jozef.simicek@stuba.sk Research field: Statics and Dynamics Fluids mechanics

More information

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS J J Brasz, Carrier Corporation, Syracuse, NY, 13221, USA joost.j.brasz@carrier.utc.com I K Smith and N Stosic

More information

The final numerical answer given is correct but the math shown does not give that answer.

The final numerical answer given is correct but the math shown does not give that answer. Note added to Homework set 7: The solution to Problem 16 has an error in it. The specific heat of water is listed as c 1 J/g K but should be c 4.186 J/g K The final numerical answer given is correct but

More information

Chapter 8: Heat Exchangers

Chapter 8: Heat Exchangers Chapter 8: Heat Exchangers Section 8.1: Introduction to Heat Exchangers 8.1-1 (8-1 in text) Dry air at T a,in = 30 C, and atmospheric pressure is blown at V a = 1.0 m 3 /s through a cross-flow heat exchanger

More information

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A Jignesh K. Vaghela Assistant Professor, Mechanical Engineering Department, SVMIT, Bharuch-392001, (India) ABSTRACT

More information

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Air-sourced 90 Hot Water Supplying Heat Pump HEM-90A Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A" Takahiro OUE *1, Kazuto OKADA *1 *1 Refrigeration System & Energy Dept., Compressor Div., Machinery Business Kobe Steel has developed an air-sourced

More information

Frost Damage of Roof Tiles in Relatively Warm Areas in Japan

Frost Damage of Roof Tiles in Relatively Warm Areas in Japan Frost Damage of Roof Tiles in Relatively Warm Areas in Japan Influence of Surface Finish on Water Penetration Chiemi IBA Hokkaido Research Organization, Japan Shuichi HOKOI Kyoto University, Japan INTRODUCTION

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not

More information

Split units TH with hermetic compressors

Split units TH with hermetic compressors Split units TH with compressors Refrigeration units in split variant. Available with screw or solder terminal. Condensing unit with sound insulated weatherproof housing for outdoor installation. Split

More information

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 26 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

Continuous flow direct water heating for potable hot water

Continuous flow direct water heating for potable hot water Continuous flow direct water heating for potable hot water An independently produced White Paper for Rinnai UK 2013 www.rinnaiuk.com In the 35 years since direct hot water systems entered the UK commercial

More information

Home inspectors are not mold inspectors, however they do inspect for defects that

Home inspectors are not mold inspectors, however they do inspect for defects that CONDENSATION IN THE WALLS Home inspectors are not mold inspectors, however they do inspect for defects that can result in mold. Mold grows in wet or damp environments. Defects that result in a wet or damp

More information

Moisture Content in Insulated Basement Walls

Moisture Content in Insulated Basement Walls Moisture Content in Insulated Basement Walls Peter Blom,PhD, SINTEF Building and Infrastructure; peter.blom@sintef.no, www.sintef.no/byggforsk Sverre B. Holøs M.Sc. SINTEF Building and Infrastructure;

More information

KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE

KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE ADVANCED ENGINEERING 3(2009)1, ISSN 1846-5900 KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE Cibulka, J. Abstract: This paper deals with the design of Kinetic Energy Recovery Systems

More information

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range

More information

Experimental Evaluation Of The Frost Formation

Experimental Evaluation Of The Frost Formation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Evaluation Of The Frost Formation Yusuke Tashiro Mitsubishi

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine G Vicatos J Gryzagoridis S Wang Department of Mechanical Engineering,

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

Design of Cold Storage Structure For Thousand Tonne Potatoes

Design of Cold Storage Structure For Thousand Tonne Potatoes International Journal of Agriculture and Food Science Technology. ISSN 2249-3050 Volume 5, Number 3 (2014), pp. 171-178 Research India Publications http://www.ripublication.com Design of Cold Storage Structure

More information

Review on Experimental Analysis and Performance Characteristic of Heat Transfer In Shell and Twisted Tube Heat Exchanger

Review on Experimental Analysis and Performance Characteristic of Heat Transfer In Shell and Twisted Tube Heat Exchanger Review on Experimental Analysis and Performance Characteristic of Heat Transfer In Shell and Twisted Tube Heat Exchanger Nitesh B. Dahare Student, M.Tech (Heat power Engg.) Ballarpur Institute of Technology,

More information

Sound pr. (db(a)) Phone: +90 216 394 12 82 Pressure hpa 960.075. Fax: +90 216 394 12 87 Capacity kw 1200.000

Sound pr. (db(a)) Phone: +90 216 394 12 82 Pressure hpa 960.075. Fax: +90 216 394 12 87 Capacity kw 1200.000 Hybrid-Re-Cooler V-2x8 - Offer no. 1328 Sound power (db(a)) Sound pr. (db(a)) Company Schenkel & Partner GmbH 1 Branch Ingenieurbüro Street Bahnhofstrasse 44 Country/ZIP/City 8 Zürich Installation Credit

More information

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture

More information

Test Report No. C908LPEN

Test Report No. C908LPEN Institut für Solartechnik Hochschule für Technik Rapperswil Oberseestrasse 10, CH 8640 Rapperswil Tel +41 55 222 48 21, Fax +41 55 222 48 44 www.solarenergy.ch Ordered by: Changzhou He Jia Solar Energy

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications

A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications Mustafa Jaradat, Klaus Vajen, Ulrike Jordan Institut für Thermische Energietechnik, Universität Kassel, 34125 Kassel,

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

SBi 2013:14. Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings

SBi 2013:14. Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings SBi 2013:14 Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings Rouzbeh Norouzi,

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

AIR CONDITIONING TECHNOLOGY

AIR CONDITIONING TECHNOLOGY AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air

More information

Rittal White Paper 305: Selecting Air Conditioners for Industrial Enclosures By: Judith Koetzsch Mark Corcoran, Editor

Rittal White Paper 305: Selecting Air Conditioners for Industrial Enclosures By: Judith Koetzsch Mark Corcoran, Editor Rittal White Paper 305: Selecting Air Conditioners for Industrial Enclosures By: Judith Koetzsch Mark Corcoran, Editor Executive Summary Choosing the right air conditioners for enclosures can have a tremendous

More information

Rate of Heating Analysis of Data Centers during Power Shutdown

Rate of Heating Analysis of Data Centers during Power Shutdown 2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction,

More information

Technical Specification for Model RSK2503 (Z)-06A IR Belt Solar Cell Firing Furnace

Technical Specification for Model RSK2503 (Z)-06A IR Belt Solar Cell Firing Furnace Technical Specification for Model RSK2503 (Z)-06A IR Belt Solar Cell Firing Furnace TECHNICAL SPECIFICATION Model RSK 2503(Z)-06A IR Belt Solar Cell Firing Furnace Temperature Range 1. Max Temperature.

More information

A Prototype Alternative Ventilation System for Retrofit, Rehab and Renovation of Rural Alaska Houses

A Prototype Alternative Ventilation System for Retrofit, Rehab and Renovation of Rural Alaska Houses A Prototype Alternative Ventilation System for Retrofit, Rehab and Renovation of Rural Alaska Houses Robert L Crosby Jr, Biorealis Systems, Inc. Abstract: Bristol Bay Housing Authority (BBHA) currently

More information

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Moisture Control. It s The Dew Point. Stupid! Its not the humidity. Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR

More information

Test Code: 8297 / Version 1

Test Code: 8297 / Version 1 Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment

More information

Refrigeration Air Dryers ADQ. Capacity: 21-4200 m 3 /h

Refrigeration Air Dryers ADQ. Capacity: 21-4200 m 3 /h Refrigeration Air Dryers Capacity: 21-4200 m 3 /h Water Contamination in Compressed Air T he w a t er c o n t a i n e d i n a c o m p r e s s e d a i r s y s t e m w i l l va r y acc o r d i n g t o a

More information

Test Report No. C926LPEN

Test Report No. C926LPEN Institut für Solartechnik Hochschule für Technik Rapperswil Oberseestrasse 10, CH 8640 Rapperswil Tel +41 55 222 48 21, Fax +41 55 222 48 44 www.solarenergy.ch Ordered by: AMK-Collectra AG Bahnweg Nord

More information

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University THE PSYCHROMETRIC CHART: Theory and Application Perry Peralta NC State University PSYCHROMETRIC CHART Identify parts of the chart Determine moist air properties Use chart to analyze processes involving

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

FREESTUDY HEAT TRANSFER TUTORIAL 3 ADVANCED STUDIES

FREESTUDY HEAT TRANSFER TUTORIAL 3 ADVANCED STUDIES FREESTUDY HEAT TRANSFER TUTORIAL ADVANCED STUDIES This is the third tutorial in the series on heat transfer and covers some of the advanced theory of convection. The tutorials are designed to bring the

More information

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li * Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting

More information

Energy and Buildings

Energy and Buildings Energy and Buildings 42 (2010) 1833 1840 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild Membrane heat exchanger in HVAC energy recovery

More information

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE. ACHP 104 Refrigeration & Air Conditioning Service II

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE. ACHP 104 Refrigeration & Air Conditioning Service II STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK COURSE OUTLINE ACHP 104 Refrigeration & Air Conditioning Service II Prepared By: Stan Skowronek CANINO SCHOOL OF ENGINEERING TECHNOLOGY

More information

Center for Energy Education Laboratory

Center for Energy Education Laboratory Paper ID #7072 Center for Energy Education Laboratory Dr. Robert Gilbert, Sinclair Community College Robert B. Gilbert, Ph.D., LEED AP, BA, is an Associate Professor of Energy Management Technology, and

More information

CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL BUILDING

CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL BUILDING 2000 Elsevier Science Ltd. All rights reserved., Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 767 CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL

More information

Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed

Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed Screw Compressors ESM 30 132 Fixed Speed & VS 30 132 Variable Speed Rely on GD to provide the perfect fit The perfect fit to maximise productivity The growing industrial demand for compressed air requires

More information

Mold Preventing I nterior System

Mold Preventing I nterior System interior insulation and renovation boards A system of components that have been designed to work perfectly together to repair damage caused by mold. The system consists of boards, insulation wedges, reveal

More information

CULTURAL HERITAGE AND FLOOD

CULTURAL HERITAGE AND FLOOD Central Europe towards Sustainable Building 2013 CULTURAL HERITAGE AND FLOOD Klára NEDVĚDOVÁ The Institute of Theoretical and Applied Mechanics, Academy of Sciences Czech Republic, v. v. i., Prosecká 809/76,

More information

Solar chilled drinking water sourced from thin air: modelling and simulation of a solar powered atmospheric water generator

Solar chilled drinking water sourced from thin air: modelling and simulation of a solar powered atmospheric water generator 20th International Congress on Modelling and Simulation, Adelaide, Australia, 1 6 December 2013 www.mssanz.org.au/modsim2013 Solar chilled drinking water sourced from thin air: modelling and simulation

More information

How To Know If A Refrigeration System Is Efficient

How To Know If A Refrigeration System Is Efficient Universitatea de Ştiinţe Agricole şi Medicină Veterinară Iaşi ASSESSMENT OF E SUBCOOLING CAPABILITIES OF A ERMOELECTRIC DEVICE IN A VAPOR COMPRESSION REFRIGERATION SYSTEM R. ROŞCA 1, I. ŢENU 1, P. CÂRLESCU

More information

Experimental study on frost growth and dynamic performance of air source heat pump system

Experimental study on frost growth and dynamic performance of air source heat pump system Available online at www.sciencedirect.com Applied Thermal Engineering 28 (2008) 2267 2278 www.elsevier.com/locate/apthermeng Experimental study on frost growth and dynamic performance of air source heat

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

Drying Parawood with Superheated Steam

Drying Parawood with Superheated Steam Drying Parawood with Superheated Steam Surachai Bovornsethanan and Somchai Wongwises Department of Mechanical Engineering, King Mongkut s University of Technology Thonburi (KMUTT) Bangmod, Bangkok 10160,

More information

A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING

A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING John Archibald American Solar Roofing Company 8703 Chippendale Court Annandale, Va. 22003 e-mail: jarchibald@americansolar.com

More information

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under

More information

THE EFFECT OF ENERGY RECOVERY ON INDOOR CLIMATE, AIR QUALITY AND ENERGY CONSUMPTION USING COMPUTER SIMULATIONS

THE EFFECT OF ENERGY RECOVERY ON INDOOR CLIMATE, AIR QUALITY AND ENERGY CONSUMPTION USING COMPUTER SIMULATIONS THE EFFECT OF ENERGY RECOVERY ON INDOOR CLIMATE, AIR QUALITY AND ENERGY CONSUMPTION USING COMPUTER SIMULATIONS A Thesis Submitted to the College of Graduate Studies and Research in Partial Fulfillment

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

Precision Mass Flow Metering For CVD Applications.

Precision Mass Flow Metering For CVD Applications. Precision Mass Flow Metering For CVD Applications. Ir. H.J. Boer Research Department of Bronkhorst High-Tech B.V. Nijverheidsstraat 1A, 7261 AK Ruurlo The Netherlands. Tel: +31 (0)573 458800 Fax: +31 (0)573

More information