1 Solar PV Safety for the Fire Service Bill Brooks, Brooks Engineering Panel Lead: Code Official Panel, Solar ABC s

2 Presentation Overview Brief overview of PV system equipment Fire issues with PV systems Case Studies Field inspection issues of concern 2011 NEC Language to help firefighters 2012 IFC and NFPA1 updates for PV Proposals for 2014 NEC and 2015 IFC and NFPA1

3 Photovoltaic System Basics characteristics and equipment

4 Connect Cells To Make Modules One silicon solar cell produces about 0.5 volts. 36 cells connected together have enough voltage to charge 12 volt batteries. 60- to 72-cell modules are common for gridconnected systems operating at about Volts each. Module is the basic building block of systems. Can connect modules together to get any power configuration (limited by voltage).

5 Current (amps) Current varies with irradiance Performance at Different Irradiances W/m2, 25 oc 800 W/m2, 25 oc 600 W/m2, 25 oc 400 W/m2, 25 oc 200 W/m2, 25 oc Voltage (volts)

6 Integrated PV Modules

7 Photo by M. Paiss Framed, BIPV, Flexible Photo courtesy of Uni-Solar

8 Inverters - Residential Photo courtesy of Independent Energy Systems

9 Locations will vary Photo by M. Paiss Disconnects will vary Photo courtesy of Independent Energy Systems

10 Photo courtesy of E.Oakes Microinverter

11 Standoff-Mounted Arrays

12

13

14 The Patio Cover

15

16 EBay Headquarters, San Jose, CA

17

18 TYPICAL COMMERCIAL COMPONENTS Inverter(s) and Disconnecting Means

19 TYPICAL COMMERCIAL COMPONENTS Inverter(s) and Disconnecting Means (multiple inverters)

20 TYPICAL COMMERCIAL COMPONENTS Array (PV Modules and Mounting Equipment)

21 TYPICAL COMMERCIAL COMPONENTS Array (PV Modules and Mounting Equipment)

22 Wiring (conductors, combiner boxes, conduit, disconnects)

23 TYPICAL COMMERCIAL COMPONENTS Wiring (conductors, combiner boxes, conduit, disconnects)

24 PV Combiner Boxes

25 Current Code Activities California s guidelines are reasonable for suburban departments that routinely fight fires from rooftops regardless of regional location. Both the IFC and UFC (NFPA 1) adopted language similar to the California document for the upcoming 2012 editions of these codes. The 2011 NEC includes several updates to address fire service concerns. The solar industry and the fire fighting community need to work together to refine construction codes and standard operating procedures for firefighters.

26 Basic hazard info for Firefighters Electrical Shock Trips and Slips Dead Load

27 Case Study: Bakersfield Mercantile Fire, April 2009 Photo courtesy of KCFD

28 Membrane roofing & foam over metal decking Photo courtesy of KCFD

29 Photos courtesy of KCFD This is 3 in. conduit

30 Arcing present Acring Photo courtesy of KCFD

31 Case Study: Simi Valley BIPV Fire - March 2009 Photo courtesy of VCFD

32 Possible shading issues Photos courtesy of VCFD

33 Overhaul necessary, but Photo courtesy of VCFD

34 Photo courtesy of VCFD Is this wise?

35 Ensuring the fire is out is the job of the fire service. Photo courtesy of J.Davis

36 Great labeling unable to secure utilities Photo courtesy of M. Paiss

37 Key Points Identify & communicate the PRESENCE of a PV system. Key components of a PV system: Array, Inverter, Conduit, Labeling. Safely operate around a PV system Isolate power to degree possible Stay away from damaged system Request Solar Contractor to secure system

38 Next Steps with Fire Officials Educate officials about 2011 NEC updates. Provide basic PV operational-level training so they better understand the technology and hazards. Developed white paper with recommendations for implementation of guidelines. (solarabcs.org) Work with developments of NFPA 1 and the IFC F-30 documents to help see that regulations are properly implemented.

39 Field Inspection

40 Appropriate signs installed Sign construction Photovoltaic Power Source AC point of connection inverter matches one-line alternative power system Optional Standby System (if battery-backed unit)

41 Signs and Labels

42 Signs and Labels

43 Wire Management

44 Wire Management

45 What you can t see won t hurt you??

46 Electrical Code Enforcement

47 Correct Fuses??

48 Access Pathways & Good Installation

49 Nice Work

50 New 2011 Relevant NEC Requirements (E) (E) Circuit Routing. Photovoltaic source and PV output conductors, in and out of conduit, and inside of a building or structure, shall be routed along building structural members such as beams, rafters, trusses, and columns where the location of those structural members can be determined by observation. Where circuits are imbedded in built-up, laminate, or membrane roofing materials in roof areas not covered by PV modules and associated equipment, the location of circuits shall be clearly marked.

51 New 2011 Relevant NEC Requirements (E) (New) Wiring methods shall not be installed within 25 cm (10 in.) of the roof decking or sheathing except where directly below the roof surface covered by PV modules and associated equipment. Circuits shall be run vertically from the roof penetration point to supports a minimum of 25 cm (10 in.) below the roof decking. Informational Note: The 25 cm (10 in.) requirement is to prevent accidental damage from saws used by firefighters for roof ventilation during a structure fire.

52 New 2011 Relevant NEC Requirements (E) (New-continued) Where flexible metal conduit (FMC) or metal clad cable (MC) smaller than metric designator 21 (trade size 3 4) containing PV power circuit conductors is installed across ceilings or floor joists, the raceway or cable shall be protected by substantial guard strips that are at least as high as the raceway or cable. Where run exposed, other than within 1.8 m (6 ft) of their connection to equipment, these wiring methods shall closely follow the building surface or be protected from physical damage by an approved means.

53 Understanding the 2012 International Fire Code and NFPA1 PV Regulations Developed by Bill Brooks, PE

54 Fire Service Contributors Vickie Sakamoto, CAL FIRE-OSFM Kevin Reinertson, CAL FIRE-OSFM Matthew Gatewood, Los Angeles Fire Department Denise Enea and Marshall Hird, Woodside Fire Department Jim Hone, Santa Monica Fire Department Kent Miller, Port of Stockton Ken Kwong and Elizabeth Brueck, Sacramento Fire Department Lisa Beaver, SMUD Ron Keefer, Menlo Park Fire Department Tim Ippolito, Roseville Fire Department Wes Kitchel, Santa Rosa Fire Department Scott Poster, County of Los Angeles Fire Department Ed Hadfield, Coronado Fire Department William Bigariani, San Francisco Fire Department

55 Solar and other Contributors CalSEIA Sue Kateley, CalSEIA Gary Gerber, Sun Light & Power Edgar Becerra, Sharp Solar Colin Murchie, SunEdison John Hostetter, REC Solar, Inc. Mark Mrohs, Kurt Johnson, Gary Neate, Dylan Anderson, and Carl Lenox, SunPower Peter Rive, SolarCity Kirk Uhler and Carl Woods, SolarPower, Inc. Additional Participants Bill Brooks, Brooks Engineering John Taeker, Underwriters Laboratories

56

57 1.0 MARKING (IFC ) Marking is needed to provide emergency responders with appropriate warning and guidance with respect to isolating the solar electric system. This can facilitate identifying energized electrical lines that connect the solar modules to the inverter, as these should not be cut when venting for smoke removal. Materials used for marking should be weather resistant. Use UL 969 as standard to weather rating (UL listing of markings is not required). Vinyl signs need to meet UL969 requirements while plastic and metal engraved signs do not need to meet the UL standard.

58 Examples of Plastic Engraved and Vinyl Signs

59 Sign Requirements MARKING CONTENT: CAUTION SOLAR CIRCUIT (NEC and IFC uses Warning: Photovoltaic Power Source) RED BACKGROUND, WHITE LETTERING, MINIMUM 3/8 LETTER HEIGHT, ALL CAPITAL LETTERS, ARIAL OR SIMILAR FONT, NON-BOLD, REFLECTIVE, WEATHER RESISTANT MATERIAL (durable adhesive materials meet this requirement)

60

61

62 2.0 ACCESS, PATHWAYS AND SMOKE VENTILATION (IFC ) Section 2.0 relates to fire departments that engage in vertical ventilation operations. Some departments are beginning to limit vertical ventilation for lightweight construction. Other buildings already have automatic roof vents making roof access unnecessary. Metal and concrete decked buildings are rarely trenched, so access to vents and skylights is all that may be necessary.

63 Purpose of Section 2.0 Access and spacing requirements should be observed in order to: Ensure access to the roof Provide pathways to specific areas of the roof Provide for smoke ventilation opportunities area Provide emergency egress from the roof

64 Exceptions to Section 2.0 Local jurisdictions may create exceptions to this requirement where access, pathway or ventilation requirements are reduced due to: Proximity and type of adjacent exposures Alternative access opportunities (as from adjoining roofs) Ground level access to the roof area in question

65 Exceptions to Section 2.0 (cont.) Adequate ventilation opportunities beneath solar array (as with significantly elevated or widelyspaced arrays) Adequate ventilation opportunities afforded by module set back from other rooftop equipment (shading or structural constraints may leave significant areas open for ventilation near HVAC equipment, for example.) Automatic ventilation device. New technology, methods, or other innovations that ensure adequate fire department access, pathways and ventilation opportunities.

66 Roof Ventilation Residential Roof Layouts Ventilation (IFC ) 3 space along ridge of roof Ridge setback based on enough room to make 2 wide ventilation cut. ASCE 7, Minimum Design Loads for Buildings, requires this setback in high wind locations (e.g. eastern seaboard) No rooftop disconnect requirement. (see appendix) Each roof face treated independently. PV array and wiring is off limits to fire fighters.

67

68 Roof Access Residential with Single Ridge (IFC ) Single ridge needs two 3 pathways on array faces along edge of load bearing exterior wall.

69 Full Gable

70

71

72 Access Commercial (IFC ) Commercial flat roof with no roof dimension more than 250 feet 4 space around perimeter wall. Commercial flat roof with a roof dimension more than 250 feet 6 space around perimeter wall. No rooftop disconnect requirement for fire fighters.

73 Pathways and Ventilation Commercial (IFC & ) Minimum 4 pathway on center access of building in both directions. A 4 access to skylights, roof hatches, and fire standpipes shall be provided to the perimeter wall. Commercial rooftop arrays shall be no greater than 150 by 150 feet in distance in either axis. Array off limits to fire fighters.

74 Commercial < 250

75 Commercial > 250

76 LOCATION OF DC CONDUCTORS (IFC ) To limit the hazard of cutting live conduit in venting operations, DC wiring should be run in metallic conduit or raceways when located within enclosed spaces in a building and should be run, to the maximum extent possible, along the bottom of load-bearing members. Intent is to stay away from common ventilation locations near ridge. Staying under load-bearing members minimizes likelihood of saws cutting wiring system.

77

78 Commercial Systems: Difficult Access Example

79

80

81

82

83

84 Future Code Activities NFPA tasked NEC Code Making Panel 4 to discuss and develop proposals for firefighter safety for 2014 NEC. Proposals submitted in November One NEC proposal would require module-level shutdown on all PV systems on buildings IBC proposals due in January Other I- Code proposal deadlines throughout Efforts underway to refine current language. The solar industry and the fire fighting community need to work together to refine construction codes and standard operating procedures for firefighters.

85 Craig Allyn Rose Photography - Emergencyphoto.com CONCLUSION

Developed by CA Matt Paiss, and Bill Brooks, PE

Developed by CA Matt Paiss, and Bill Brooks, PE Understanding the Cal Fire Solar Photovoltaic Installation Guideline Developed by CA Matt Paiss, and Bill Brooks, PE Presentation Overview Brief Overview of History of PV Firefighter Issues State Fire

More information

SOLAR PHOTOVOLTAIC INSTALLATION GUIDELINE (In partnership with interested local fire officials, building officials, and industry representatives)

SOLAR PHOTOVOLTAIC INSTALLATION GUIDELINE (In partnership with interested local fire officials, building officials, and industry representatives) CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL SOLAR PHOTOVOLTAIC INSTALLATION GUIDELINE (In partnership with interested local fire officials, building officials,

More information

Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10

Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10 Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10 This document was developed by the Orange County Fire Chiefs Association, Orange County Fire Marshal Committee.

More information

Solar Panel Installations

Solar Panel Installations Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

Understanding the Cal Fire Solar Photovoltaic Installation Guideline

Understanding the Cal Fire Solar Photovoltaic Installation Guideline Understanding the Cal Fire Solar Photovoltaic Installation Guideline Prepared for: Solar America Board for Codes and Standards (available soon at www.solarabcs.org) Brooks Engineering 873 Kells Circle

More information

Understanding the Cal Fire

Understanding the Cal Fire Understanding the Cal Fire Prepared by: Bill Brooks, P.E. Brooks Engineering Solar America Board for Codes and Standards www.solarabcs.org Solar America Board for Codes and Standards Report Understanding

More information

Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM

Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM The following is the Los Angeles Fire Department s minimum requirement for Solar Photovoltaic System Installations. The City of

More information

How To Plan Out An Array Of Solar Panels

How To Plan Out An Array Of Solar Panels CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013

More information

County of Riverside Building and Safety Department

County of Riverside Building and Safety Department County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project

More information

RESIDENTIAL PHOTOVOLTAIC SUBMITTAL REQUIREMENTS

RESIDENTIAL PHOTOVOLTAIC SUBMITTAL REQUIREMENTS DEVELOPMENT AND RESOURCE MANAGEMENT DEPARTMENT BUILDING AND SAFETY SERVICES 2600 Fresno Street, Third Floor Fresno, California 93721-3604 (559) 621-8082 FAX (559) 498-4357 RESIDENTIAL PHOTOVOLTAIC SUBMITTAL

More information

SOLAR PV SYSTEMS PERMITTING PROCESS

SOLAR PV SYSTEMS PERMITTING PROCESS Department of Consumer and Regulatory Affairs SOLAR PV SYSTEMS PERMITTING PROCESS How to Reach Us 1100 4 th Street, SW Washington, DC 20024 dcra@dc.gov Permit Center Hours Monday, Tuesday, Wednesday &

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a

More information

Solar Photovoltaic (PV) Systems

Solar Photovoltaic (PV) Systems ARTICLE 690 Solar Photovoltaic (PV) Systems INTRODUCTION TO ARTICLE 690 SOLAR PHOTOVOLTAIC (PV) SYSTEMS You ve seen, or maybe own, photocell-powered devices such as night lights, car coolers, and toys.

More information

Doe Residence - 5.64 kw DC Roof Mounted Photovoltaic System

Doe Residence - 5.64 kw DC Roof Mounted Photovoltaic System EQUIPMENT SUMMARY 20 LG 300W solar panels 1 SMA SE6000AUS Inverter Everest Solar Systems Cross Rail Racking System QuickMount PV Quick Hook Curved Tile Mount QMCTH SHEET INDEX T01 COVER PV01 SITE MAP &

More information

City of San Diego Residential Photovoltaic Systems Inspection Guidelines

City of San Diego Residential Photovoltaic Systems Inspection Guidelines City of San Diego Residential Photovoltaic Systems Inspection Guidelines The purpose of inspections by DSD staff is to ensure compliance with the California Electrical Code (CEC), other applicable codes

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS

PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS Butte County Department of Development Services PERMIT CENTER 7 County Center Drive, Oroville, CA 95965 Main Phone (530)538-7601 Permit Center Phone (530)538-6861 Fax (530)538-7785 FORM NO DBP-71 PERMIT

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

Solar Ready Residential Installation Requirements

Solar Ready Residential Installation Requirements Solar Ready Residential Installation Requirements Developed by Energy Trust of Oregon V6.11/14 Table of Contents 1 Purpose... 2 2 General... 2 3 Solar Access & Solar Roof Area... 2 4 Solar Electric...

More information

Solar America Board for Codes and Standards

Solar America Board for Codes and Standards Impacts on Photovoltaic Installations of Changes to the 2012 International Codes A Solar ABCs White Paper May 2011 Solar America Board for Codes and Standards www.solarabcs.org Solar America Board for

More information

TOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL)

TOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL) LOS ANGELES BASIN CHAPTER OF ICC MONTHLY CHAPTER MEETING ALHAMBRA, CA TOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL) RON TAKIGUCHI, P.E. BUILDING OFFICIAL -CITY

More information

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC 91.1301, 93.690 Effective: 01-01-2014 DOCUMENT NO.: P/GI 2014-027 Revised: 11-07-2014 Previously Issued As: P/GI 2011-027 GUIDELINES

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

Expedited Permit Process for PV Systems AC Module

Expedited Permit Process for PV Systems AC Module Module The Solar America Board for Codes and Standards (Solar ABCs) Expedited Permit Process provides a means to differentiate systems that can be permitted quickly and easily due to their similarity with

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

Complete Solar Photovoltaics Steven Magee. Health and Safety

Complete Solar Photovoltaics Steven Magee. Health and Safety Health and Safety Health and safety around solar photovoltaic systems is very important. In the DC circuit you will find up to 600 volts in residential and commercial systems. In utility systems you may

More information

Codes and Compliance Requirements

Codes and Compliance Requirements The Solar Decathlon Rules and Regulations Committee will review the teams drawings and submittals to ensure compliance with all applicable codes and Solar Decathlon Regulations. This document highlights

More information

Solar Water Heating and Photovoltaic Electrical Systems Installed on One or Two Family Dwellings

Solar Water Heating and Photovoltaic Electrical Systems Installed on One or Two Family Dwellings Solar Water Heating and Photovoltaic Electrical Systems Installed on One or Two Family Dwellings I. BACKGROUND As awareness of renewable energy and green building options increases, solar energy systems

More information

Page & Turnbull imagining change in historic environments through design, research, and technology

Page & Turnbull imagining change in historic environments through design, research, and technology DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED

More information

Submittal Requirements for Solar Photovoltaic Installations 10 kw or Less in One and Two Family (Duplex) Dwellings

Submittal Requirements for Solar Photovoltaic Installations 10 kw or Less in One and Two Family (Duplex) Dwellings CITY OF SONOMA TOOKIT DOCUMENT #1 Submittal Requirements for Solar Photovoltaic Installations 10 kw or Less in One and Two Family (Duplex) Dwellings This information bulletin is published to guide applicants

More information

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC 91.1301, 93.690 Effective: 01-01-2014 DOCUMENT NO.: P/GI 2014-027 Revised: 12-16-2015 Previously Issued As: P/GI 2011-027 GUIDELINES

More information

Installation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar

Installation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar Installation Guide of Sunrise Solartech PV Modules Term 2013 Contents Purpose of this guide General Safety precaution for installing a solar Photovoltaic system Product Identification Mechanical Installation

More information

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the

More information

BUILDING INTEGRATED PHOTOVOLTAICS

BUILDING INTEGRATED PHOTOVOLTAICS BUILDING INTEGRATED PHOTOVOLTAICS STEVE COONEN DEFINITION Building Integrated Photovoltaics (BIPV) Grid Connected BIPV Schematic AC Loads DC Disconnect Inverter Electrical Distribution Panel AC Disconnect

More information

Building Construction. Lightweight construction. Conventional Construction

Building Construction. Lightweight construction. Conventional Construction Ventilation 53 Building Construction The firefighter s ability to safely and efficiently ventilate a building through its roof will depend to some degree on the firefighter s understanding of roof construction.

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

BOROUGH OF OAKLAND COUNTY OF BERGEN STATE OF NEW JERSEY ORDINANCE 13-CODE-685

BOROUGH OF OAKLAND COUNTY OF BERGEN STATE OF NEW JERSEY ORDINANCE 13-CODE-685 BOROUGH OF OAKLAND COUNTY OF BERGEN STATE OF NEW JERSEY ORDINANCE 13-CODE-685 AN ORDINANCE TO AMEND, SUPPLEMENT AND REVISE THE CODE OF THE BOROUGH OF OAKLAND, LAND USE, CHAPTER 59 ENTITLED LAND USE AND

More information

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured. SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation

More information

Understanding Emergency Power Off (EPO)

Understanding Emergency Power Off (EPO) Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

Understanding the Fire Hazards of Photovoltaic Systems

Understanding the Fire Hazards of Photovoltaic Systems Allianz Global Corporate & Specialty Tech Talk Volume 8 July 2012 Understanding the Fire Hazards of Photovoltaic Systems Allianz Risk Consulting Introduction Living on Earth is expensive, but it does include

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

D. Permits: A building permit is required for the structural support of all solar energy device installations.

D. Permits: A building permit is required for the structural support of all solar energy device installations. INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC 91.1301, 93.690 Effective: 06-13-2011 DOCUMENT NO.: P/GI 2011-027 Revised: Previously Issued As: P/MC 2002-001 GUIDELINES FOR PLAN

More information

Fire Barriers & Fire Stopping

Fire Barriers & Fire Stopping Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC 262-945-4567 Lauzon.lsc@gmail.com Web: Lauzon-LSC.com Environmental Part 2 Life Safety Code Chapter 8 Fire Barriers & Fire Stopping 1 Fire

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

Supplement - Protocol for Photovoltaic (PV) Plans March 11, 2016

Supplement - Protocol for Photovoltaic (PV) Plans March 11, 2016 Please read this entire protocol to be sure submitted materials will be complete, and procedures followed correctly. (1) PRINTED PLANS versus EMAILED PLANS Plans submitted printed on paper will be scanned

More information

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance WHITE PAPER Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance Overview Enphase has developed a new microinverter family that includes the M250 and new

More information

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.) Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection

More information

Chapter 6 ROOF-CEILING SYSTEMS

Chapter 6 ROOF-CEILING SYSTEMS Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;

More information

Regional and Site Assumptions This document is based on the following regional and site assumptions:

Regional and Site Assumptions This document is based on the following regional and site assumptions: Structural Criteria for Residential Rooftop Solar Energy Installations Use of this document This toolkit document includes a one-page list of structural criteria for over-the-counter or online approval,

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Solar Water Heating and Solar Electric Generators Installed on One or Two Family Dwellings

Solar Water Heating and Solar Electric Generators Installed on One or Two Family Dwellings Solar Water Heating and Solar Electric Generators Installed on Category: Residential Construction Revised: [Paul L. Scarlett], Director Responsible Bureau Section: Development Services Center 1900 SW Fourth

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

Electrical safety of grid-connected solar installations in Western Australia December 2011

Electrical safety of grid-connected solar installations in Western Australia December 2011 Electrical safety of grid-connected solar installations in Western Australia December 2011 Level 1, 303 Sevenoaks Street (cnr Grose Avenue) Cannington, Western Australia 6107 PO Box 135 Cannington WA 6987

More information

Errata NFPA 70. Proposed 2014 Edition

Errata NFPA 70. Proposed 2014 Edition Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes

More information

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new

More information

sdci 420 Seattle Permits Tip www.seattle.gov/sdci Solar Energy Systems GREEN PERMIT REQUIREMENTS Building Permit Types of Solar Energy Systems

sdci 420 Seattle Permits Tip www.seattle.gov/sdci Solar Energy Systems GREEN PERMIT REQUIREMENTS Building Permit Types of Solar Energy Systems GREEN sdci Seattle Department of Construction and Inspections Tip 420 Seattle Permits part of a multi-departmental City of Seattle series on getting a permit Solar Energy Systems Updated May 20, 2015 This

More information

POST AND FRAME STRUCTURES (Pole Barns)

POST AND FRAME STRUCTURES (Pole Barns) POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:

More information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to

More information

How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System

How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System July 28, 2003 We are pleased to provide the following joint statement by CII,

More information

Best Management Practices for Solar Installation Policy

Best Management Practices for Solar Installation Policy Process Improvements Step 1-1A: Streamline Permitting Best Management Practices for Solar Installation Policy in Kansas City and Beyond Provide a central information source for potential solar customers

More information

SHARP SOLAR Frequently Asked Questions for PV Integrators Revised 05/04/2010

SHARP SOLAR Frequently Asked Questions for PV Integrators Revised 05/04/2010 SHARP SOLAR Frequently Asked Questions for PV Integrators Revised 05/04/2010 How do I determine the PTC rating of a module? PTC refers to PVUSA Test Conditions, which were developed to test and compare

More information

Request for Proposals for Photovoltaic System Installation

Request for Proposals for Photovoltaic System Installation Request for Proposals for Photovoltaic System Installation Presented by: Prepared by: Location: Contact: Date: Capitol Hill Housing Foundation Bonneville Environmental Foundation, Renewable Energy Group

More information

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations

Connecting the Power of the Sun. DC Disconnects for Solar Photovoltaic Installations. DC disconnects for. solar photovoltaic installations Connecting the Power of the Sun DC Disconnects for Solar Photovoltaic Installations DC disconnects for solar photovoltaic installations Solar energy is heating up Interest in renewable energy sources has

More information

TECHNICAL NOTES. Property Insurance Research Group Forum on PV Panel Fire Risk: A Literature Review. Fire Protection Research Foundation June 2014

TECHNICAL NOTES. Property Insurance Research Group Forum on PV Panel Fire Risk: A Literature Review. Fire Protection Research Foundation June 2014 TECHNICAL NOTES Property Insurance Research Group Forum on PV Panel Fire Risk: A Literature Review Fire Protection Research Foundation June 2014 The Fire Protection Research Foundation One Batterymarch

More information

BUILDING SAFETY UNIT

BUILDING SAFETY UNIT POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential

More information

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun

DC disconnects for solar photovoltaic installations. Connecting the. power of the sun DC disconnects for solar photovoltaic installations Connecting the power of the sun Solar energy is heating up Interest in renewable energy sources has never been greater, and the fastest growing of these

More information

ADDENDUM #1(BID PACKAGE # 3)

ADDENDUM #1(BID PACKAGE # 3) H2Engineering, Inc. 114 East Fifth Avenue Tallahassee, FL 32303 Phone 850.224.7922 Fax 850.224.5876 ADDENDUM #1(BID PACKAGE # 3) To: Jeff Williams From: Peter Lindstrom Co: Leon County Date: October 04,

More information

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section

More information

Solar Photovoltaic SPECIFICATION, CHECKLIST AND GUIDE. Renewable Energy Ready Home

Solar Photovoltaic SPECIFICATION, CHECKLIST AND GUIDE. Renewable Energy Ready Home Solar Photovoltaic SPECIFICATION, CHECKLIST AND GUIDE Renewable Energy Ready Home Table of Contents About the Renewable Energy Ready Home Specifications Assumptions of the RERH Solar Photovoltaic Specification...

More information

MORE POWER. A BETTER INVESTMENT.

MORE POWER. A BETTER INVESTMENT. SUNPOWERCORP.COM US HEADQUARTERS SunPower Corporation 3939 N. 1st Street San Jose, California 95134 USA 1-800-SUNPOWER sunpowercorp.com MORE POWER. A BETTER INVESTMENT. Established Incorporated in 1985

More information

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing

More information

Photovoltaic Industry Technologies, Markets & Trends

Photovoltaic Industry Technologies, Markets & Trends Photovoltaic Industry Technologies, Markets & Trends AIAA Los Angeles Enterprise Chapter Joel Davidson Solutions in Solar Electricity Presentation Outline The Big Picture Brief History of PV Solar Array

More information

determining wind and snow loads for solar panels America s Authority on Solar

determining wind and snow loads for solar panels America s Authority on Solar determining wind and snow loads for solar panels America s Authority on Solar Determining wind and snow loads for solar panels 1 introduction As one of the largest and most established vertically integrated

More information

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850 Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:

More information

PV THERMAL SYSTEMS - CAPTURING THE UNTAPPED ENERGY

PV THERMAL SYSTEMS - CAPTURING THE UNTAPPED ENERGY PV THERMAL SYSTEMS - CAPTURING THE UNTAPPED ENERGY John Hollick Conserval Engineering Inc. 200 Wildcat Road Toronto Ontario jhollick@solarwall.com ABSTRACT PV modules generate electricity, but the electrical

More information

Solar Integrated Solar Roof Panel System Installation Manual

Solar Integrated Solar Roof Panel System Installation Manual Solar Integrated Solar Roof Panel System Installation Manual Solar Integrated 1837 E. Martin Luther King Jr. Blvd. Los Angeles, California 90058 Tel 323-231-0411 Fax 323-231-0517 www.solarintegrated.com

More information

Electrical Code (NEC) Snake Tray Cable Management Solutions

Electrical Code (NEC) Snake Tray Cable Management Solutions Cable Pathway Use and Selection and the National Electrical Code (NEC) By Eric J. Sadler, BSME MIT Snake Tray Cable Management Solutions References: All references to the NEC in this presentation are taken

More information

Dollars & Sense of Compliance!

Dollars & Sense of Compliance! CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors

More information

Solar Power System Installation Manual

Solar Power System Installation Manual Solar Power System Installation Manual Power-Save Energy Co. 3940-7 Broad St. #200 San Luis Obispo, CA 93401 866 297 7192 FOR INSTALLATION PERSONNEL Please read this manual carefully before installing

More information

Safety and Installation Instructions for AC Modules

Safety and Installation Instructions for AC Modules Safety and Installation Instructions for AC Modules United States and Canada Contents of this manual are subject to change without notice. For the latest guide please refer to www.sunpower.com/pvinstallguideacmodule

More information

2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes

2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 1) Tamper resistant receptacles. 2009 CEC Required in dwelling units 2012 CEC Expanded to child care facilities First introduced in the 2009

More information

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

Ducoterra Radiant Heating Panel Installation Manual

Ducoterra Radiant Heating Panel Installation Manual Ducoterra Radiant Heating Panel Installation Manual 1. Introduction Your new radiant heating panels are designed to heat living and working spaces rapidly and efficiently by radiant heating. Like the sun,

More information

Prism Solar Installation Manual

Prism Solar Installation Manual This installation manual applies to the following Prism Solar bifacial glass/glass models: B265(L), B260, B255, B250, B245, B200, B150, HB180. IMPORTANT: Read these instructions and the Prism Solar Design

More information

Builder Specifications for Solar Ready Homes

Builder Specifications for Solar Ready Homes Builder Specifications for Solar Ready Homes This document specifies the essential elements required to make a new home ready for the future installation of roof-mounted solar domestic hot water and photovoltaic

More information

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers 9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product

More information

YSmart Technology Co.,Ltd

YSmart Technology Co.,Ltd YSmart Technology Co.,Ltd GWV Series Grid Tie Microinverter User Manual The copyright of this user manual belong to YSmart TechnologyCompany Limited. Without the written permission of the copyright holder,

More information

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager FIRE RATED WIRING What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager INTRODUCTION OBC requirements for emergency power OBC requirements for emergency power for fire alarm systems and other building

More information

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional

More information

The Florida Building Code

The Florida Building Code Setting New Standards for Safety The Florida Building Code Florida Building Commission Florida Department of Community Affairs The Florida Building Code System The Florida Building Commission Florida Building

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

Model Number Electrical Compatibility Module Connector Type. M250-60-2LL-S22 60 cell PV module MC-4 Type 2 Locking

Model Number Electrical Compatibility Module Connector Type. M250-60-2LL-S22 60 cell PV module MC-4 Type 2 Locking TECHNICAL BRIEF M250 Microinverter System Installation Planning The M250 Microinverter The Enphase M250 Microinverter is a powerful and efficient grid-tied microinverter. It is compatible with most 60-cell

More information

FITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223

FITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223 FITNESS FACILITY WIRING SPECIFICATIONS NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223 CONTENTS: - Scope of work Summary - Equipment list - Technical specifications - Map of data

More information