1 INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC , Effective: DOCUMENT NO.: P/GI Revised: Previously Issued As: P/GI GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS The purpose of this Information Bulletin is to clarify the plan check and permitting process by the Los Angeles Department of Building and Safety (LADBS) for solar photovoltaic (PV) and solar water heating systems, hereby referred to as solar energy systems. I. BUILDING PLAN CHECK/PERMIT AND MATERIALS APPROVAL FOR SOLAR ENERGY SYSTEMS A. Zoning Requirements: Structures that support solar energy panels and associated equipment shall conform to the same Zoning Code requirements such as height, yards, HPOZ, Specific Plans, and ICOs, as for a building/structure. Water heater equipment accessory to the solar devices may be located with the same limitations as specified in the Information Bulletin P/ZC : Allowable Projections and Improvements in Required Yards. Allowable height projections shall comply with LAMC Section B3 (a), and Information Bulletin P/ZC B. Materials/Products Approval: 1. Solar Energy Systems Installed on Top of a Roof: Solar energy panels installed immediately above the roof of any building shall be non-combustible or shall have at least a Class C fire rating classification per UL 790, or class A fire rating per UL Testing and listing must be done by an approved listing agency. The roof where solar energy panels are installed shall have the code required fire rating classification. Access to the roof shall be provided in accordance with Information Bulletin P/MC Solar Energy Panels used as roofing material: Solar energy panels installed as roofing material of any building shall have the same required fire rating classification as the roof. 3. Solar Energy Systems Installed on Grade: Structural support for ground-mounted panels shall comply with the same zoning and building code requirements of a building. 4. Solar PV systems installed on top of a roof where the space between the solar PV panels and the roof has no use and no potential use are generally considered to be equipment. C. Grading Information: For ground-mounted installations, a grading pre-inspection is required for sites within the Special Grading Area (BOE Basic Grid Map A-13372) and Page 1 of 9
2 where grading is involved or where the drainage pattern is changed. Plans must indicate location of ground-mounted panels with respect to slopes. See to find out if the property is located within the Special Grading Area (BOE Basic Grid Map A-13372). D. Building Permits: A building permit is required for the structural support of all solar energy systems. Exception: A building permit is not required when all of the following requirements are met: 1. Solar energy device is roof mounted and does not exceed the existing building height at the highest point, 2. The solar energy device system weight does not exceed four pounds per square foot (4 psf), 3. The solar energy device is installed within 24 of the roof immediately below, 4. The maximum concentrated load imposed by a solar energy device support onto the roof structure is a maximum of 60 pounds (0.18 kn); and 5. For wood construction, the maximum spacing for supports of the solar energy devices shall be 48 on center, and shall be anchored to solid roof rafters or to solid blocking with a minimum of one 5 / 16 diameter lag screw embedded a minimum of 2 1 / 2 or as recommended by the manufacturer, whichever is more stringent. For other types of construction, the support shall be approved by the Department. E. Building Plan Check: Structural support of solar energy devices requiring a building permit shall be submitted to Building Plan Check for approval. 1. Complete plans shall be submitted showing dimensions and location of the supporting structure in relation to the property lines and any adjacent building. 2. Substantiating design calculations are required for supporting member sizes, connection details, and design loads imposed on the roof or other support. 3. Where the solar panel/collector surface inhibits superimposed concentrated loads, the weight of the collector may replace part of the code required live load. Regardless of the weight of the solar panel or collector, a minimum of one half of code required live load shall be used for design. 4. The wind load on the vertical projection of the collector shall be included in the analysis. Page 2 of 9
3 5. Provide a note on the plan, No guardrails are required for installed solar energy devices pursuant to LAMC All roof penetrations shall be sealed using approved methods and products to prevent water leakage. F. Ballasted PV System: PV panels in a ballasted system are typically not attached to the roof and rely on their weight, aerodynamics, and friction to counter the effect of wind and seismic forces. In some cases, ballasted systems have few attachment points to supplement the friction forces. A ballasted solar array system can be used on flat roofs without a positive connection when the following requirements are met: 1. The seismic design of solar ballasted photovoltaic arrays shall fully comply with Report PV ( from the Structural Engineers Association of California (SEAOC). The displacement for unattached arrays can be determined by the following methods: 1. Prescriptive design method per Section 7 of Report PV Nonlinear response history analysis per Section 9 of Report PV Shake table testing per Section 9 of Report PV The wind design of solar ballasted Photovoltaic arrays shall fully comply with Report PV ( from the SEAOC. The wind load design factor for unattached arrays can be determined by the following methods: 1. Prescriptive pressure coefficient GC rn per Section 3 of Report PV Wind tunnel tests per Section 5 of Report PV A sliding test shall be performed by an LA City approved test agency ( to determine the dynamic coefficient of friction having the same type of roofing material under critical roof slopes and dry/wet conditions. The tests shall conform to the applicable requirements of ASTM G The Engineer of Record shall provide gravity load and lateral load analysis to justify that the addition of the ballasted rooftop solar array systems will not increase the demand on roof framing members by more than 5% and the demand on building lateral force-resisting systems and elements by more than 10% per LABC Sections and Otherwise, the building structural systems shall be upgraded to comply with current code standards. 5. An affidavit of Maintenance of Building for Ballasted Photovoltaic Solar Arrays shall be signed by the building owner and shall be recorded at the County Recorder s Office to agree to maintain the location of arrays, number of ballasts, separation between array and any roof structures, setback from the roof edges, Page 3 of 9
4 and maintenance of the original roofing material. Any changes from the approved conditions shall be made with all required building and electrical permits. 6. The form, Modification of Building Ordinance, will be required for any of the following cases : (1) to allow the use of friction resistance in lieu of a positive anchorage connection to the roof as required per Section 13.4 of ASCE 7, (2) to allow the use of the prescriptive methodologies in Reports PV1 and PV2 in lieu of the nonlinear time history analysis and wind tunnel test, (3) to waive a peer review for the non-linear time history analysis when the design is based on the results of non-linear time history procedure, and the design forces being used are no less than 50% of the prescriptive method required in PV1, (4) to waive a peer review for the wind tunnel data collection methods, data analysis, array and building modeling when the design is based on the results of wind tunnel test, and the design forces being used are no less than 50% of the prescriptive method required in PV2. G. Building Area and Height Limitations: 1. Solar photovoltaic panels supported by a structure, with no potential use underneath shall not constitute additional story or additional floor area and may exceed the height limit when constructed on a roof top of a building provided the following conditions are met: a. For all occupancies, the highest point of the structure/panel shall meet the lower of the two values below: i. 3' above the allowable building height per this code. ii. 3' above the roof of the building immediately below. b. For installations on flat roofs in other than Group R-3 and R-4 occupancies, the highest point of the structure/panel shall meet the lower of the two values below: i. 10' above the allowable building height per this code. ii. 10' above the roof of the building immediately below. 2. Solar photovoltaic panels supported by a structure over parking stalls shall not constitute additional story or additional floor area and may exceed the height limit as specified in Sections G.1.a and G.1.b above when the following conditions are met (see Figure -1 on page 10): a. The area within the perimeter of the photovoltaic array has maximum rectangular dimension of 40 feet by 150 feet. b. The distance between solar photovoltaic array structures is a minimum 10 feet clear. c. The driveway aisle separating solar photovoltaic array structures has a minimum width of 25 feet clear. Page 4 of 9
5 d. Solar photovoltaic array structure is used only for parking purposes with no storage. e. Completely open on all sides (other than necessary structural supports) with no interior partitions. H. Construction Classification: Noncombustible structural members supporting solar photovoltaic panels are not required to meet the fire resistance rating for the following: 1. Photovoltaic panel supported by a structure and having no use underneath. Signs may be provided, as determined by the enforcing agency prohibiting any use underneath including storage. 2. Solar photovoltaic (PV) panels supported by non-combustible framing that have sufficient uniformly distributed and unobstructed openings throughout the top of the array (horizontal plane) to allow heat and gases to escape, as determined by the enforcing agency. 3. Solar photovoltaic panels supported by a structure over parking stalls where the panels constitute the roof and all the following conditions are met (see Figure -1 on page 10): a. The area within the perimeter of the solar photovoltaic array has maximum rectangular dimension of 40 feet by 150 feet. b. The distance between solar photovoltaic array structures is a minimum of 10 feet clear. c. The driveway aisle separating solar photovoltaic array structures has a minimum width of 25 feet clear. d. Solar photovoltaic array structure is used only for parking purposes with no storage. e. Completely open on all sides (other than necessary structural supports) with no interior partitions. II. ELECTRICAL PLAN CHECK AND PERMIT FOR SOLAR PHOTOVOLTAIC SYSTEMS A. Permits: An Electrical permit is required for the installation of solar photovoltaic systems. B. Product Approval: The solar photovoltaic system shall be tested and listed by a recognized electrical testing laboratory. A list of approved testing agencies is C. Materials: Electrical wiring shall comply with the applicable provisions of the 2014 Los Angeles Electrical Code (2014 LAEC). Page 5 of 9
6 D. Electrical Plan Check: Approval from Electrical Plan Check is required for all photovoltaic system installations. Exception: Plan check for installing solar PV systems is not required if all of the conditions listed below are met (permits for these systems will be issued by the Express Permit Counter following the procedure outlined in Section II-F): 1. The installation is in a one or two family dwelling. 2. A maximum of 2 strings are installed per inverter. 3. The total capacity of the photovoltaic system being installed is 10 KW or less. 4. No DC combiner box is installed (other than the box that is part of and is listed with the inverter). 5. No GFCI or AFCI over current devices are installed in the Alternate Current (AC) output of the inverter. 6. Modules shall be roof mounted crystalline or multi-crystalline material. 7. AC Power system shall be 120/240 volts single phase. 8. The minimum service panel size shall meet one of the following: 100 amps for systems with a maximum 20 amperes dedicated AC branch circuit, or 150 amps for systems having a maximum 30 (or two 15) amperes dedicated AC branch circuit(s), or 200 amps for systems having a maximum 40 (or two 20) amperes dedicated AC branch circuit(s). 9. The rating of the service panel shall not exceed 225 amperes. 10. No AC modules, storage batteries, hybrid systems, micro-inverters, building integrated photovoltaic, or photovoltaic roll roofing are installed. Counter Plan Check: Solar installations, up to 14KW, in 1 & 2 family dwellings will be reviewed at the Electrical Plan Check Counter provided a completed LADBS Photovoltaic Standard Plan and related specifications are submitted. Regular Plan Check: Systems that do not qualify for the Express Permit or Counter Plan Check process will be required to be submitted through the regular plan check process. A complete set of plans in accordance with Section of the Los Angeles Electrical Code shall be required at the time of submittal. Page 6 of 9
7 E. REQUIRED APPROVALS AND CLEARANCES: 1. Fire Department (LAFD) Approval: An approval from LAFD is required for electrical permits pertaining to solar photovoltaic systems. LAFD s installation guidelines are 2. Zoning Clearance(s): Approval from the Zoning counter, by means of a clearance, is required for all Express permits and electrical plan check applications pertaining to solar photovoltaic systems. The Zoning Counter staff shall determine if the site is within a Specific Plan, HPOZ, ICO or CRA area; or if it involves a historical monument and refer customers to the appropriate agency by creating the required clearances, if applicable. Once all the clearances are approved by the appropriate agency, the Zoning Plan Check Counter staff shall approve the zoning clearance in PCIS and direct customers to the Express Permit Counter (for Express permits) or to the Electrical Plan Check counter (for electrical plan check applications) to complete the process. 3. APPROVAL FROM LOS ANGELES DEPARTMENT OF WATER AND POWER (LADWP): LADBS will not refer plan check or permit applicants to LADWP. It is the responsibility of the applicant/installer to ensure all required approvals from LADWP are obtained. For LADWP s requirements and information regarding Solar PV Systems installation, refer to F. Process for Obtaining an Electrical Permit: 1. Permit for Solar PV Systems which do not require an Electrical Plan Check (Express Permits): These permits are issued by the Express Permit Counter. Prior to permit issuance, the Express Permit Counter staff shall refer all permit applications for photovoltaic systems to the Los Angeles Fire Department (LAFD) for approval. In addition, the Express Permit Counter staff shall initialize the permit application for photovoltaic system(s); create a clearance summary sheet for Zoning Approval, and direct customers to the Zoning counter to obtain clearance approval. For Express Permits, the applicant is required to complete forms E and E PV (attached). The Express Counter staff shall ensure the completed E PV form is returned to the applicant, along with the issued permit, to present to the field inspector. 2. Photovoltaic Systems requiring Plan Check: Solar PV systems that require electrical plan check will be processed by the Electrical Plan Check Section. Prior to plan approval, the Electrical Plan Check staff shall refer all permit applications for photovoltaic systems to the Los Angeles Fire Department (LAFD) for approval. In addition, the staff shall create a clearance summary sheet for Zoning Approval, and direct customers to the Zoning Counter to obtain clearance approval. III. MECHANICAL PLAN CHECK AND PERMIT FOR SOLAR WATER HEATING SYSTEMS Page 7 of 9
8 A. Permits: A plumbing permit is required for solar water heating systems. B. Product Approval: Solar water heating systems (pumps, storage tanks, tank liners, heat exchangers, mixing valves, collectors, etc.) shall be tested and listed by a recognized testing agency. A list of approved testing agencies is Tanks for potable water shall be constructed of approved materials similar to those allowed for potable water piping. Tanks shall meet the Plumbing Code, the Uniform Solar Energy Code and NSF 61. Heat exchangers shall meet the requirements of the Plumbing Code and the Uniform Solar Energy Code. C. Mechanical Plan Check: Approval from Mechanical Plan Check is required for installations on water systems that have a 2 or larger supply. D. Zoning Clearance(s): Approval from the Zoning counter, by means of a clearance, is required for all Express permits and mechanical plan check applications pertaining to solar water heating systems. The Zoning Counter staff shall determine if the site is within a Specific Plan, HPOZ, ICO or CRA area; or if it involves a historical monument (i.e. CEQA review) and refer customers to the appropriate agency by creating the required clearances, if applicable. Once all the clearances are approved by the appropriate agency, the Zoning Plan Check Counter staff shall approve the zoning clearance in PCIS and direct customers to the Express Permit Counter (for Express permits) or to the Mechanical Plan Check counter (for plumbing plan check applications) to complete the process. E. Process for Obtaining a Plumbing Permit: 1. Process for Obtaining a Plumbing Permit that does not require Mechanical Plan Check: These permits are issued by the Express Permit Counter. Prior to permit issuance, the Express Permit Counter staff shall initialize the permit application for the solar water heating system, create a clearance summary sheet for Zoning Approval, and direct the customer to LADBS Zoning Counter to obtain clearance approval. 2. Solar water heating systems requiring Mechanical Plan Check: Systems that require mechanical plan check will be processed by the Mechanical Plan Check Section. Prior to plan check approval, the Mechanical Plan Check staff shall initialize the permit application for the solar water heating system, create a clearance summary sheet for Zoning Approval, and direct the customer to LADBS Zoning Counter to obtain clearance approval. Page 8 of 9
9 25' min. driveway 10' min. 25' min. driveway 40' Max 150' max. Figure 1 Page 9 of 9
D. Permits: A building permit is required for the structural support of all solar energy device installations.
INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC 91.1301, 93.690 Effective: 06-13-2011 DOCUMENT NO.: P/GI 2011-027 Revised: Previously Issued As: P/MC 2002-001 GUIDELINES FOR PLAN
More informationGUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS
INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC 91.1301, 93.690 Effective: 01-01-2014 DOCUMENT NO.: P/GI 2014-027 Revised: 12-16-2015 Previously Issued As: P/GI 2011-027 GUIDELINES
More informationRESIDENTIAL PHOTOVOLTAIC SUBMITTAL REQUIREMENTS
DEVELOPMENT AND RESOURCE MANAGEMENT DEPARTMENT BUILDING AND SAFETY SERVICES 2600 Fresno Street, Third Floor Fresno, California 93721-3604 (559) 621-8082 FAX (559) 498-4357 RESIDENTIAL PHOTOVOLTAIC SUBMITTAL
More informationSOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
More informationPERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS
Butte County Department of Development Services PERMIT CENTER 7 County Center Drive, Oroville, CA 95965 Main Phone (530)538-7601 Permit Center Phone (530)538-6861 Fax (530)538-7785 FORM NO DBP-71 PERMIT
More informationEXPRESS PERMITS (No Plan Check Required)
EXPRESS PERMITS (No Plan Check Required) Following are the lists of different types of construction for which an express permit can be issued. Express permits can be issued where work does not require
More informationSolar Water Heating and Solar Electric Generators Installed on One or Two Family Dwellings
Solar Water Heating and Solar Electric Generators Installed on Category: Residential Construction Revised: [Paul L. Scarlett], Director Responsible Bureau Section: Development Services Center 1900 SW Fourth
More informationLos Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM
Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM The following is the Los Angeles Fire Department s minimum requirement for Solar Photovoltaic System Installations. The City of
More informationGuideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10
Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10 This document was developed by the Orange County Fire Chiefs Association, Orange County Fire Marshal Committee.
More informationSolar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
More informationSolar Water Heating and Photovoltaic Electrical Systems Installed on One or Two Family Dwellings
Solar Water Heating and Photovoltaic Electrical Systems Installed on One or Two Family Dwellings I. BACKGROUND As awareness of renewable energy and green building options increases, solar energy systems
More informationHow To Plan Out An Array Of Solar Panels
CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013
More informationINSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
More informationCITY OF SONOMA TOOLKIT DOCUMENT #1a
CITY OF SONOMA TOOLKIT DOCUMENT #1a Your City logo here Submittal Requirements for Solar Domestic Water Heating Installations 30 kwth or Less for One- and Two-Family Dwellings This information bulletin
More informationCounty of Riverside Building and Safety Department
County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project
More informationRegional and Site Assumptions This document is based on the following regional and site assumptions:
Structural Criteria for Residential Rooftop Solar Energy Installations Use of this document This toolkit document includes a one-page list of structural criteria for over-the-counter or online approval,
More informationSolar America Board for Codes and Standards
Impacts on Photovoltaic Installations of Changes to the 2012 International Codes A Solar ABCs White Paper May 2011 Solar America Board for Codes and Standards www.solarabcs.org Solar America Board for
More informationSOLAR PV SYSTEMS PERMITTING PROCESS
Department of Consumer and Regulatory Affairs SOLAR PV SYSTEMS PERMITTING PROCESS How to Reach Us 1100 4 th Street, SW Washington, DC 20024 dcra@dc.gov Permit Center Hours Monday, Tuesday, Wednesday &
More informationCity of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationSubmittal Requirements for Solar Photovoltaic Installations 10 kw or Less in One and Two Family (Duplex) Dwellings
CITY OF SONOMA TOOKIT DOCUMENT #1 Submittal Requirements for Solar Photovoltaic Installations 10 kw or Less in One and Two Family (Duplex) Dwellings This information bulletin is published to guide applicants
More informationDollars & Sense of Compliance!
CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors
More informationCITY OF LOS ANGELES CALIFORNIA
BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI
More informationThe City of Basehor, Kansas
The City of Basehor, Kansas Residential and Miscellaneous Permits This list provides general information regarding permit requirements for various residential construction and maintenance activities. The
More informationHow To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
More informationResidential Decks. Planning and Development Services Department
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: permitservices@opkansas.org Planning and Development Services Department Residential Decks
More informationRACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012
RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationFlorida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS
Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44
More informationResidential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
More informationResidential Plan Routing Information
Residential Plan Routing Information BUILDING INSPECTIONS 800 4th AVENUE EAST WEST FARGO, ND 58078 PHONE: 701-433-5480 The building Inspection s Department receives and issues all applications for building
More informationSOLAR ENERGY PERMIT. 1. Two (2) page Building Permit Application (signed and notarized); 2. Disclosure Affidavit (signed and notarized);
Town of Riverhead Building Department 201 Howell Avenue, Riverhead, New York 11901 (631) 727-3200 Ext. 213, 268, 283 Fax: 631-208-8039 www.townofriverheadny.gov SOLAR ENERGY PERMIT 1. Two (2) page Building
More informationThe replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
More informationBOROUGH OF OAKLAND COUNTY OF BERGEN STATE OF NEW JERSEY ORDINANCE 13-CODE-685
BOROUGH OF OAKLAND COUNTY OF BERGEN STATE OF NEW JERSEY ORDINANCE 13-CODE-685 AN ORDINANCE TO AMEND, SUPPLEMENT AND REVISE THE CODE OF THE BOROUGH OF OAKLAND, LAND USE, CHAPTER 59 ENTITLED LAND USE AND
More informationDoe Residence - 5.64 kw DC Roof Mounted Photovoltaic System
EQUIPMENT SUMMARY 20 LG 300W solar panels 1 SMA SE6000AUS Inverter Everest Solar Systems Cross Rail Racking System QuickMount PV Quick Hook Curved Tile Mount QMCTH SHEET INDEX T01 COVER PV01 SITE MAP &
More informationKITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
More informationCHAPTER 11 STORM DRAINAGE
CHAPTER 11 STORM DRAINAGE SECTION 11 GENERAL 11.1 Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. 11.2 Where required. All roofs,
More informationHow To Mount An Ecosa Series Solar Panel
(including PanelClaw ) This Guide is valid in North America only (ETL listed; conforms to UL Standard 1703) PanelClaw is a registered trademark of PanelClaw, Inc. SM-0050revA ELECTRICAL EQUIPMENT CHECK
More informationALL STAR ELECTRIC COMPANY 10,000 Trumbull SE, Suite #F Albuquerque, NM 87123 (505) 856-1010 voice & fax NM License 21880 www.allstarelec.
ALL STAR ELECTRIC COMPANY 10,000 Trumbull SE, Suite #F Albuquerque, NM 87123 (505) 856-1010 voice & fax NM License 21880 www.allstarelec.com On-Site Power System Specialists: Photovoltaics, Wind Turbine
More informationBUILDING SAFETY UNIT
POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential
More informationNumber of Sides Required to Have a Handrail
Excerpt from 2012 B.C. Building Code HANDRAILS & GUARDS 9.8.7. Handrails 9.8.7.1. Required Handrails 1) Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and ramps in accordance
More informationLOS ANGELES CITY FIRE DEPARTMENT
LOS ANGELES CITY FIRE DEPARTMENT Division 5 Permit LOCATION INFORMATION FD USE ONLY Date of Use: Date Granted PERMIT # Date Expires Name Phone#: City: Los Angeles State: California Zip: 90089 CONTRACTOR
More informationClark County Fire Prevention
Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF
More informationTOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL)
LOS ANGELES BASIN CHAPTER OF ICC MONTHLY CHAPTER MEETING ALHAMBRA, CA TOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL) RON TAKIGUCHI, P.E. BUILDING OFFICIAL -CITY
More informationSOLAR ENERGY FACILITIES ZONING AMENDMENTS
SOLAR ENERGY FACILITIES ZONING AMENDMENTS 1. In Section 10, Special Regulations, of the Zoning Bylaw, insert a new Section 10.06, to be entitled Solar Energy Facilities and to read as follows: SECTION
More informationES-A Series Photovoltaic Panels
Guide This Guide is valid in North America only (ETL listed; conforms to UL Standard 1703) ELECTRICAL EQUIPMENT CHECK WITH YOUR INSTALLER Evergreen Solar ES-A Series photovoltaic (PV, solar electric) panels
More informationPLUMBING ROUGH IN INSPECTION
This Program is made Possible through the Code Officials Education & Training Fund. Revenue for the Fund comes from Assessments on Building Permits. Please turn down cell phones and put pagers on vibrate.
More informationWind effects on roof-mounted solar photovoltaic arrays: CFD and wind-tunnel evaluation
Wind effects on roof-mounted solar photovoltaic arrays: CFD and wind-tunnel evaluation Robert N. Meroney a and David E. Neff b a Colorado State University, Fort Collins, CO, USA, Robert.Meroney@ColoState.Edu
More informationGENERAL BUILDING PERMIT INFORMATION FOR: RESIDENTIAL ALTERATIONS & ADDITIONS
GENERAL BUILDING PERMIT INFORMATION FOR: RESIDENTIAL ALTERATIONS & ADDITIONS INFORMATION GUIDELINE 1 Jan, 2014 CITY OF ESCONDIDO BUILDING DIVISION 201 N. BROADWAY, ESCONDIDO, CA 92025 (760) 839-4647 GENERAL
More informationCharter Township of Shelby Harry Reese Building Director
Charter Township of Shelby Harry Reese Building Director Phone: (586) 731-5969 52700 Van Dyke Fax: (586) 803-2099 Shelby Township, MI 48316-3572 E-mail: building@shelbytwp.org OUTLINE PROCEDURES FOR PRIVATE
More informationRESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
More information#1258. WHEREAS, the Board of Commissioners of the Township of Haddon has determined the following:
#1258 ORDINANCE OF THE TOWNSHIP OF HADDON, COUNTY OF CAMDEN AND STATE OF NEW JERSEY SUPPLEMENTING, AMENDING AND REVISING CHAPTER 142-38 OF THE TOWNSHIP OF HADDON ENTITLED, CONDITIONAL USES WHEREAS, The
More informationSHARP SOLAR Frequently Asked Questions for PV Integrators Revised 05/04/2010
SHARP SOLAR Frequently Asked Questions for PV Integrators Revised 05/04/2010 How do I determine the PTC rating of a module? PTC refers to PVUSA Test Conditions, which were developed to test and compare
More informationCHAPTER 11 STORM DRAINAGE
CHAPTER STORM DRAINAGE SECTION PC 0 GENERAL 0. Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be
More information9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards.
Section 9.8. Stairs, Ramps, Handrails and Guards 9.8.1. Application 9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and
More informationADDENDUM #1(BID PACKAGE # 3)
H2Engineering, Inc. 114 East Fifth Avenue Tallahassee, FL 32303 Phone 850.224.7922 Fax 850.224.5876 ADDENDUM #1(BID PACKAGE # 3) To: Jeff Williams From: Peter Lindstrom Co: Leon County Date: October 04,
More information215 28. Solar Photovoltaic Installation Bylaw Mount Washington, Massachusetts
215 28. Solar Photovoltaic Installation Bylaw Mount Washington, Massachusetts 1.0 Purpose The purpose of this section is to provide a permitting process for solar photovoltaic installations so that they
More informationSection 43. Lead Paint Risk Factor NONE WATER HEATER STORAGE ELECTRIC
WATER HEATER STORAGE ELECTRIC Lead Paint Risk Factor NONE TABLE OF CONTENTS PART 1: INSTALLATION REQUIREMENTS FOR CONVENTIONAL HOMES... 1 WATER HEATER REPAIRS... 1 1. APPLIANCE REPAIR... 1 WATER HEATER
More informationREVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
More informationRELOCATION OF BUILDINGS
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LABC Chapter 83 Effective: 01-01-2014 DOCUMENT NO.: P/BC 2014-099 Revised : 05-24-2016 Previously Issued As: P/BC 2011-099 RELOCATION OF BUILDINGS
More information2. What building projects are exempted? (permit not required)
BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and
More informationBUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
More informationTENT AND STAGE CUSTOMER ASSISTANCE GUIDE
TENT AND STAGE CUSTOMER ASSISTANCE GUIDE Charles County Government Department of Planning & Growth Management P.O. Box 2150 La Plata, MD 20646 (301) 645 0692 / (301) 870 3935 Fax: (301) 645 0575 Web Site:
More informationCity of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level
More informationsdci 420 Seattle Permits Tip www.seattle.gov/sdci Solar Energy Systems GREEN PERMIT REQUIREMENTS Building Permit Types of Solar Energy Systems
GREEN sdci Seattle Department of Construction and Inspections Tip 420 Seattle Permits part of a multi-departmental City of Seattle series on getting a permit Solar Energy Systems Updated May 20, 2015 This
More informationGuidelines for Earthquake Bracing Residential Water Heaters
Guidelines for Earthquake Bracing Residential Water Heaters Department of General Services Division of the State Architect In accordance with the Health and Safety Code Section 19215, the Division of the
More informationMANUFACTURED HOUSING USED AS DWELLINGS
MANUFACTURED HOUSING USED AS DWELLINGS SECTION AE101 SCOPE AE101.1 General. These provisions shall be applicable only to a manufactured home used as a single dwelling unit and shall apply to the following:
More informationCOMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS Permit applicants shall submit three (3) COMPLETE SETS of plans and specifications with each application for a permit. Plans and specifications
More informationCity of San Diego Residential Photovoltaic Systems Inspection Guidelines
City of San Diego Residential Photovoltaic Systems Inspection Guidelines The purpose of inspections by DSD staff is to ensure compliance with the California Electrical Code (CEC), other applicable codes
More information2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
More informationBuilding Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
More informationORDINANCE NO. 2015-413
ORDINANCE NO. 2015-413 AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF LOS ALTOS ADDING CHAPTER 12.70 TO TITLE 12 IN THE MUNICIPAL CODE TO STREAMLINE THE PERMITTING PROCESS FOR RESIDENTIAL SOLAR ENERGY
More informationUpper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 APPLICATION for ZONING and BUILDING PERMIT APPLICATION INSTRUCTIONS:
More informationOregon Administrative Rules, Chapter 918-2016 Compilation- Building Codes Division DIVISION 695
DIVISION 695 Hist.: DC 2-1983, f. & ef. 1-3-83; Renumbered from 814-020- PLUMBING LICENSING AND CERTIFICATION 0040; BCD 6-1998, f. 3-2-98, cert. ef. 4-1-98, Renumbered from 918-690-0055; BCD 21-1998, f.
More informationSolar Photovoltaic SPECIFICATION, CHECKLIST AND GUIDE. Renewable Energy Ready Home
Solar Photovoltaic SPECIFICATION, CHECKLIST AND GUIDE Renewable Energy Ready Home Table of Contents About the Renewable Energy Ready Home Specifications Assumptions of the RERH Solar Photovoltaic Specification...
More informationDELAWARE TOWNSHIP ORDINANCE #2011-06LU
DELAWARE TOWNSHIP ORDINANCE #2011-06LU AN ORDINANCE SUPPLEMENTING AND AMENDING THE LAND USE ORDINANCE OF THE TOWNSHIP OF DELAWARE BY PERMITTING SOLAR ENERGY SYSTEMS. #2011-06LU WHEREAS, it is the purpose
More informationSINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
More informationAdult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:
Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION
More informationThe purpose of this document is to provide standards for persons requesting or subject to County building inspections.
STANDARD OPERATING PROCEDURE BUILDING & SITE DEVELOPMENT Number: 310.1 Approval: Yves Khawam Effective Date: December 27, 2006 Subject: Requirements for County building inspections Page 1 of 7 1.0 PURPOSE:
More informationCOMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
More informationPOST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
More informationWHEN IS A PERMIT REQUIRED?
WHEN IS A PERMIT REQUIRED? Any owner, builder, contractor, or other authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,
More informationArapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
More informationNOTICE OF INTENT Department of Revenue Policy Services Division. Income Tax Credits for Wind or Solar Energy Systems (LAC: 61:I.
NOTICE OF INTENT Department of Revenue Policy Services Division Income Tax Credits for Wind or Solar Energy Systems (LAC: 61:I.1907) Under the authority of R.S. 47:287.785, R.S. 47:295, R.S. 47:1511, and
More informationSOLAR PHOTOVOLTAIC INSTALLATION GUIDELINE (In partnership with interested local fire officials, building officials, and industry representatives)
CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL SOLAR PHOTOVOLTAIC INSTALLATION GUIDELINE (In partnership with interested local fire officials, building officials,
More informationPERMITS REQUIRED & PERMIT EXEMPTIONS
PERMITS REQUIRED & PERMIT EXEMPTIONS This guideline is intended to assist the applicant in determining what types of construction work require a permit. The 1997 California Uniform Administrative Code,
More informationBuilding Mechanical Inspector Senior Building Mechanical Inspector Principal Building Mechanical Inspector Chief Building Mechanical Inspector - 2
THE CITY OF LOS ANGELES CIVIL SERVICE COMMISSION CLASS SPECIFICATION 10-25-85 BUILDING MECHANICAL INSPECTOR, 4251 SENIOR BUILDING MECHANICAL INSPECTOR, 4253 PRINCIPAL BUILDING MECHANICAL INSPECTOR, 4255
More informationTop 10+ Mistakes of DWV plumbing design
Top 10+ Mistakes of DWV plumbing design Listed below are the some of the most frequently missed items, noticed by our inspectors, at plumbing rough-in when non-plumbers attempt plumbing design. Most of
More informationMOBILE HOME LAW. Revised November 2001
MOBILE HOME LAW Revised November 2001 TABLE OF CONTENTS: SECTION 1: SECTION 2: SECTION 3: SECTION 4: SECTION 5: SECTION 6: SECTION 7: SECTION 8: SECTION 9: SECTION 10: SECTION 11: SECTION 12: INTENT DEFINITIONS
More informationMaximum Floor Area and Maximum Development Area
TOWN OF LOS ALTOS HILLS 26379 Fremont Road Los Altos Hills, CA 94022 Phone: (650) 941-7222 www.losaltoshills.ca.gov Maximum Floor Area and Maximum Development Area Revised-7/31/13 INSTRUCTIONS FOR WORKSHEET
More informationResidential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet
Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet 1. Definitions a. AHJ Authority Having Jurisdiction. The Fire Chief or Fire Marshal of a given Fire District
More informationChapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
More informationFILING REQUIREMENTS EXCERPTS FROM THE ZONING ORDINANCE SOLAR ENERGY SYSTEMS
County of San Diego, Planning & Development Services APPLICANT S GUIDE FOR A SOLAR ENERGY SYSTEM ZONING DIVISION These guidelines provide information on how to apply for a Solar Energy System. Review the
More information2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
More informationAll substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.
2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other
More informationFocus of the Guidebook
PURPOSE AND USE OF THIS GUIDE California Solar Permitting Guidebook Improving Permit Review and Approval for Small Solar Systems May 12, 2015 Bill Brooks, Principal, Brooks Engineering Designed to help
More informationSupplemental Plan Check Corrections Sheet for Bicycle Parking Ordinance (Effective 3/13/2013)
Supplemental Plan Check Corrections Sheet for Bicycle Parking Ordinance (Effective 3/13/2013) Plan Check PCIS application number: - - Job Address Zone: P.C. Engineer (E-mail: firstname.lastname@lacity.org)
More informationCertification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
More informationRESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
More informationAPPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET
Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing
More information