PROPER SIZING OF IT POWER AND COOLING LOADS WHITE PAPER

Size: px
Start display at page:

Download "PROPER SIZING OF IT POWER AND COOLING LOADS WHITE PAPER"

Transcription

1 WHITE PAPER #23 PROPER SIZING OF IT POWER AND COOLING LOADS WHITE PAPER CONTRIBUTORS: JOHN BEAN, APC RON BEDNAR, EMERSON NETWORK POWER RICHARD JONES, CHATSWORTH PRODUCTS ROBB JONES, CHATSWORTH PRODUCTS PHIL MORRIS, SUN MICROSYSTEMS DAVID MOSS, DELL DR. MICHAEL PATTERSON, INTEL JOE PRISCO, IBM WADE VINSON, HP JOHN WALLERICH, DELL

2 PAGE 2 TABLE OF CONTENTS: I. Introduction...3 II. Today s Data Centers...3 III. Nameplate Power Rating Misconceptions...3 IV. Nameplate Versus Actual...5 V. Cooling Load Calculations...6 VI. Energy Effi ciency Focus New Tools...6 VII. Tool Links...8 VIII. Proper Use of Calculating Tools...9 IX. Summary/Conclusion...9 X. References...10

3 PAGE 3 I. INTRODUCTION Between 2000 and 2006, energy requirements for data centers doubled, and they are on track to double again by In the same time period, typical per-rack heat densities went from 1 kw to 7 kw, and they are estimated to exceed 20 kw per rack by This places tremendous importance on a data center facility planner s ability to properly budget for future power and cooling infrastructure requirements. In the past, facilities planners used IT equipment nameplate ratings values as a method to plan power and cooling capacity requirements, which resulted in over-built, under-utilized, ineffi cient infrastructure. Today s energy costs and effi ciency demands necessitate a more accurate method of determining those requirements. This white paper has been developed to introduce the reader to the many new and highly accurate software tools available for estimating power and cooling capacity requirements. II. TODAY S DATA CENTERS The inaccuracy of data centers standard process for estimating the power consumption of IT equipment has led to the under- and over-provisioning of circuits, power distribution units (PDUs), and uninterruptible power supplies (UPSs) as well as the cooling systems needed to remove the energy dissipated. This can have a signifi cant impact on power distribution effi ciencies, total power consumption, service availability, and operational costs. In an attempt to simplify this process and to help improve power consumption accuracy, the majority of IT vendors have made power and cooling estimation tools available for their various equipment models and confi gurations. Prior to the proliferation of those tools, the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) suggested the use of the thermal report, which provided the end user with power-draw and cooling-load estimates heat removal and airfl ow rates for minimal, typical, and maximum load confi gurations 1. But even that signifi cant step forward was still subject to errors based on different server confi gurations and the exact complement of hardware options (CPU, hard drives, memory, I/O confi gurations, etc.) The minimum baseline has since been expanded upon by system manufacturers. III. NAMEPLATE POWER RATING MISCONCEPTIONS Prior to the ASHRAE thermal report, the buyer or data center architect had little-to-no information on the expected power consumption of a server, so the default value was initially the nameplate value. Yet the term nameplate is often misused. When discussing server power draw and cooling loads, nameplate is frequently used (albeit incorrectly) to describe the value from the server data sheet for the power supply (generally the output of the power supply listed in watts). The technically correct description of nameplate value is the value from the system rating label (see Figure 1). The nameplate on a piece of IT equipment is a marking from a third-party agency that indicates that the equipment complies with a set of requirements set forth by a product safety standard such as IEC (Information technology equipment - Safety - Part 1: General requirements). Figure 1 shows an example of a nameplate found on a piece of IT equipment.

4 PAGE 4 FIGURE 1. EXAMPLE NAMEPLATE The nameplate includes, at a minimum, rated input voltage, rated input amperage, kilovolt-ampere (kva), frequency, and phase information. It is important to note that the wattage does not appear on the nameplate. The purpose of the nameplate is twofold: To give information necessary for the preparation of the electrical installation (e.g., circuit breakers, receptacles, wiring methods) to ensure adherence with electrical codes. To provide assurance to the installer or user who plugs the equipment into the mains that the equipment is suitable for installation at a particular location within the data center. Manufacturers derive the nameplate value in many different ways to ensure compliance with a product safety standard. The value could be based on the line cord assembly that is used to provide power to the IT equipment or the DC output power rating on the power supply unit (PSU). The nameplate value chosen may be a result of the cost of manufacturing: many OEMs standardize their power supplies on a smaller number of PSUs, which can result in substantial gaps between nameplate values and actual power consumed for a given piece of IT equipment. Also, power consumption can vary based on device confi gurations additional components such as memory can increase the actual power draw of equipment. The same power supply may be used in a server with low-voltage CPUs and minimal memory as in the same server model that is confi gured with the highest memory and CPU confi gurations. Regardless of how they are chosen, nameplate values are generally accepted as representing power consumption levels that exceed actual power consumption of equipment under normal usage. Therefore, these over-infl ated values do not support realistic power prediction. Unfortunately, nameplate value (regardless of whether it is the incorrect use of the data sheet PSU description or the proper defi nition above) is still frequently used by data center planners in the design, planning, and deployment of power and cooling systems. This practice often results in excessive capital expense and operational costs due to lower effi ciencies that result from overestimating resource requirements. Many of these planners mistakenly use the nameplate value because it is either on the data sheet when they are ordering or always available and clearly visible on any piece of IT equipment when installed. There is also a misconception that devices upstream from the IT equipment (such as PDUs and/or UPSs) must be sized to accommodate the sum of all the nameplate ratings. As discussed above, the nameplate rating generally does not refl ect actual power consumption and using it as an indicator leads to grossly over-provisioned power distribution systems. Typically, any electrical loads hardwired into a system are, by code, limited to 80% of the upstream components capacity. However, because the server has a plug, it is

5 PAGE 5 considered portable and the management of the load then falls to the owner. In this case, a better design practice would be to use the peak-measured or maximum-measured manufacturer s reported draw for the specifi c IT equipment confi guration and ensure that the sum of those loads does not exceed 80% of the rating of the upstream panel. Also, it is important to check with the local code authority having jurisdiction for any specifi c ruling that would preclude this practice. There are some specifi c geographies, instances, and tools that can allow higher loadings when the diversity of the load (frequency of equipment peak power occurring at the same time) is known, but these are outside the scope of this paper. In general, the electrical loading should be sized based on IT equipment peak measured or maximum measured power consumption levels and not nameplate values. IV. NAMEPLATE VERSUS ACTUAL Servers, PSU Rating vs peak draw Actual "50%" PSU Nameplate (Watts) Peak draw (Watts) FIGURE 2. PSU NAMEPLATE RATING VERSUS PEAK POWER DRAW The above fi gure shows 51 servers and their power supplies tested by the U.S. Environmental Protection Agency 3. The nameplate rating (Y axis) is plotted against peak draw (X axis). Consider, for example, the large group of 1000 W PSUs in the fi gure. There were 23 of these, which indicates the manufacturer s propensity to use standard-size components at the next-greater size rather than exactly matching the expected load. Also noteworthy is the range of actual power draw found for these servers. The low end was roughly 160 watts compared to a high end of about 580 watts all using the same 1000 W power supply. With only the knowledge of the nameplate value in hand, many data center managers use a method of de-rating in order to estimate actual power consumption. In doing so, they establish actual power consumption as a percentage of the nameplate value. Some use a simple nameplate divided by 2 (nameplate/2) convention for estimating power loads. If that method were accurate, then the peak draw values would be 50% of the PSU nameplate

6 PAGE 6 values and fall on the 50% line in Figure 2, yet review of Figure 2 clearly shows this is not the case. This example shows how the nameplate/2 practice could result in incorrect power and cooling load estimates, as well as the over-sizing (or under-sizing) of both electrical systems and cooling systems. Some of the data points fall on or near the 50% line, but the number that do is far less than the number that do not. The issue is further complicated by the redundancy (or lack thereof) in PSUs. A typical server operation with redundant PSUs has both PSUs operational and carrying 50% of the load. In the case of one failing, the functioning PSU can rapidly ramp to 100% of the server load. Two important aspects should be noted. First, the total connected load from the dual PSU nameplates is now double the non-redundant load and can add to far greater over-sizing if not clearly understood. Second, dual power supplies will typically increase server consumption, due to the PSU being lower down the utilization curve, which can mean lower effi ciency. This added power needs to be factored in. Clearly, rule-of thumb methods such as nameplate/2, PSU divided by 2, and others cannot account for this level of detail. V. COOLING LOAD CALCULATIONS Data center planners and managers also use IT equipment s power predictions to calculate cooling load. All of the inaccuracies involved in using nameplate data for power load calculations are repeated in the cooling load analysis. In sizing the cooling infrastructure, both the cooling load (kw or BTU/hr) and airfl ow rates (m3/ hour of CFM) need to be determined. To further complicate the problems created by using nameplate data, planners and managers use an estimated, historical, or rule-of-thumb differential temperature (deltat) across the servers. From that deltat and the estimated power load, they calculate an airfl ow rate. Unfortunately, that airfl ow rate is based on two inaccurate estimates (nameplate and an assumed deltat). VI. ENERGY EFFICIENCY FOCUS NEW TOOLS As a result of the focus on energy effi ciency, most IT vendors now provide power measurement and power estimation tools that can help to identify a more accurate power consumption value for their IT equipment. That value is based either on actual measurements (a power meter) or an estimation tool (hardware options and utilization). Ideally, measuring the power consumed by IT equipment provides the most accurate method for determining the power and cooling load that IT equipment places on a data center. IT equipment manufacturers provide power meters that are internal and external to IT equipment. These can be used to show trends in power consumption over long periods of time under many workloads. Measuring power consumption allows for realtime measurement of application intensity and other factors that have an impact on power consumption, such as inlet ambient temperature and/or operating voltage. Vendors power and cooling estimation tools are best for planning power and cooling loads for new equipment being placed in the data center. The values found in vendor planning tools are typically the result of using this approach, with an added margin for error that will yield much more useful power consumption estimates. Application loading or utilization within the planning tool is offset from a peak power consumption level based on some type of proxy application, such as an industry benchmark or stress program. It is the deviation from actual usage to this proxy that adds one level of inaccuracy. Another factor that increases inaccuracy is the variation of power consumption in electronic components that vary from lot-to-lot. Although vendors tools typically yield results that are far better than common de-rating methods, their results tend to be somewhat conservative as compared with actual power measurements from the IT equipment.

7 PAGE 7 An additional benefi t of power and cooling estimation tools is that some tools provide more accurate estimations of the specifi c airfl ow rates for the server confi guration, utilization, and inlet air temperature. The airfl ow rates combined with the heat released by the equipment will provide the information that planners need to size the cooling infrastructure. Table 1 below is a typical example of the results obtainable by using a vendor estimation tool compared to the value that would likely have been derived from using a nameplate de-rating estimate. Equipment Design Input Tool Output 1U server Power 370 watts 208V AC power (power factor.98) Flow rate 32 CFM Dual socket quad core processor Weight 46 lbs 8 GB memory Current 1.78 A 2 disk drives deltat 37.3 F Dual power supplies Operating condition: 25 C server inlet temperature, typical workload TABLE 1. TOOL EXAMPLE Using the confi guration above, the sample vendor s power estimate is 370 watts. Per the vendor s guidance, this estimate would still be conservative, even for a virtualized load that typically operates at a higher level of processor utilization. General-purpose servers running at lower utilization levels would measure up to 20% less in terms of total power consumed. The tool estimates a worst-case confi guration for the same server to be 490 watts under full load, but that power estimate would increase to 555 watts if the server were running a more processor-intensive load, such as HPC (high performance computing) cluster computing. Furthermore, if the system were running a processor-intensive load at a maximum inlet temperature of 35 C (95 F), the power estimate would increase to 620 watts due to the electrical ineffi ciencies that result from running at high temperatures. This server has a power supply nameplate value of 670 watts. If, for example, the server power supply was actually delivering 650 watts of DC power, and it was running at 85% effi ciency, then it would be consuming 765 watts and releasing approximately 2610 BTUs (1 W of load requires BTUs to cool) of heat into the room. This example demonstrates that there are many parameters that affect power consumption, including, but not limited to, server confi guration, processor selection, memory amount and confi guration, number of drives, peripherals, I/O, processor utilization, and inlet temperature. The sophistication of vendor estimation tools continues to grow and provide the end user with an increasingly accurate method of predicting power and cooling loads.

8 PAGE 8 VII. TOOL LINKS As mentioned above, actual power measurements are ideal, but many IT vendors produce power estimation tools and calculators that can be used for planning purposes. Cautionary note Updates to calculators may occur without notice. While The Green Grid will attempt to keep the reference links below as up-to-date as possible, readers should contact the supplier to verify they have the latest version. Company Link Comments HP TOOL: gurator/powercalcs.asp HP also has a white paper on the tool (see second link) WHITE PAPER: r+calculator&url=http%3a//h20000.www2.hp.com/bc/ docs/support/supportmanual/c /c pdf%3fjumpid%3dreg_r1002_usen&pos=1 Dell PLANNING FOR ENERGY REQUIREMENTS: This link includes instructions and Data Center planning tools IBM Calculator for the blades and modular product lines (x86 architecture server systems and rack storage), the tool can be downloaded at: powerconfi g/ For the Power Processor-based server systems, an online tool is available at the following link: Sun Power Tool: Calculators powercalculators.jsp Cisco Power Tool: Calculator fcc?type= &realmoid= a a3-a dc90000&GUID=&SMAUTHREASON=0& METHOD=GET&SMAGENTNAME=$SM$GDuJAbSsi7kExzQD RfPKUItt%2bPcjKOjTGlbtk%2fRp7BdNYLiP9lyOBjXBU5PAxIX D&TARGET=http%3A%2F%2Ftools.cisco.com%2Fcpc%2F TABLE 2. POWER/COOLING ESTIMATION TOOLS Registration required

9 PAGE 9 VIII. PROPER USE OF CALCULATING TOOLS Remember that many of these vendor estimation tools are estimators. Because there are so many factors that affect power draw, it is nearly impossible to exactly match a tool to the actual results that will be seen in every data center. If more exact power or cooling planning information is needed, there is no substitute for real-time measurement using the particular system installed in a controlled fashion and running its normal workload and utilization levels. The tools may be used for electrical and cooling load planning instead of nameplate or maximum measured values, and they will yield far more accurate predictions than those derived from other estimating methods. However, detailed attention should be paid to individual server confi gurations and their power systems and potential system upgrades. For example, changes to the memory confi guration or additional PCI cards over the life of the server could affect the amps from an electrical circuit, the heat released, and the server airfl ow or deltat. Finally, when using tool estimators for data center planning and design purposes, keep in mind that while cooling systems can handle short increases in heat load in the room, an increase in amperage draw from a server that is over the limit of a circuit breaker will create a problem far more quickly. Servers can temporarily run on an increased intake air temperature, and typically a cooling system has the ability to react to that short temperature spike and provide extra cooling. If a spike in amperage draw over the circuit breaker limit occurs, that server and others around it may go down due to tripped breakers in the rack-level power distribution or in a fl oor PDU. Know what safety factors have been designed into your data center. Use the online tools to get good estimates for power draw and heat load, but also measure your units once installed to verify that the tools were correct. IX. SUMMARY/CONCLUSION Measuring power consumed by IT equipment provides the most accurate method for determining the power and cooling load that IT equipment places on a data center. However, vendors provide power and cooling calculators that can be used to determine a more accurate estimation of load based on hardware confi guration and utilization. The Green Grid highly recommends the use of power meters and power calculators for ensuring that equipment resource infrastructures are sized properly to accommodate the actual electrical and heat loads. Due to planning calculator tools inability to refl ect your specifi c application, the accuracy of your planning/ deployment process can be increased by factoring in your understanding of the differences between the tools estimates and your own application-based measurements. If future capacity requirements are unknown, refer to ASHRAE 90427, Datacom Equipment Power Trends and Cooling Applications (2005) 2. In summary, using nameplate values to estimate power resource requirements or space-cooling loads can produce highly unreliable results, including substantial under-sizing (miscalculating) or over-sizing (using the label as is without understanding hardware options and equipment utilization) of electrical systems and cooling systems. Miscalculations also can result in loss of service or excessive cost of operations. The more accurate the power consumption data that can be established, the more effi cient and reliable the electrical distribution systems can be. In addition, accurate data helps improve service availability and optimize operational costs for power and cooling systems

10 PAGE 10 X. REFERENCES 1. ASHRAE 90431, Thermal Guidelines for Data Processing Environments (2004) %25datacom%25 ) 2. ASHRAE 90427, Datacom Equipment Power Trends and Cooling Applications (2005) %25datacom%25 ) 3. United States Environmental Protection Agency, Energy Star for Workstations 4. Find an ENERGY STAR Compliant Computer: nd_a_ product.showproductgroup&pgw_code=co 5. ENERGY STAR Framework Document Framework_Document pdf XI. ABOUT THE GREEN GRID The Green Grid is a non-profi t trade organization of IT professionals formed to address the issues of power and cooling in datacenters. The Green Grid seeks to defi ne best practices for optimizing the effi cient consumption of power at the IT equipment and facility levels, as well as the manner in which cooling is delivered at these levels. The association is funded by four levels of membership, and activities are driven by end-user needs. The Green Grid does not endorse any vendor-specifi c products or solutions but seeks to provide industry-wide recommendations on best practices, metrics, and technologies that will improve overall data center energy effi ciencies.

The Real Cost of Manual Asset Management

The Real Cost of Manual Asset Management The Real Cost of Manual Asset Management No Limits Software White Paper #3 By David Cole 2011 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,

More information

Dynamic Power Variations in Data Centers and Network Rooms

Dynamic Power Variations in Data Centers and Network Rooms Dynamic Power Variations in Data Centers and Network Rooms By Jim Spitaels White Paper #43 Revision 2 Executive Summary The power requirement required by data centers and network rooms varies on a minute

More information

Solutions to Make Your Data Center Energy Effi cient

Solutions to Make Your Data Center Energy Effi cient Common $en e: Solutions to Make Your Data Center Energy Effi cient Energy effi ciency is a life style. It s also common sense. In a data center, the name of the game is effi ciency and how many compute

More information

GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE

GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE WHITE PAPER #6 GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE EDITORS: CHRISTIAN BELADY, MICROSOFT CONTRIBUTORS: ANDY RAWSON, AMD JOHN PFLEUGER, DELL TAHIR CADER, SPRAYCOOL PAGE 2 ABSTRACT

More information

Understanding Date Center. Power Usage Effectiveness

Understanding Date Center. Power Usage Effectiveness Understanding Date Center Power Usage Effectiveness This Dell Technical White Paper explains how to understand Power Usage Effectiveness (PUE) and how it applies to your Data Center. George Richards Dell

More information

Power Distribution Considerations for Data Center Racks

Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical

More information

Dynamic Power Variations in Data Centers and Network Rooms

Dynamic Power Variations in Data Centers and Network Rooms Dynamic Power Variations in Data Centers and Network Rooms White Paper 43 Revision 3 by James Spitaels > Executive summary The power requirement required by data centers and network rooms varies on a minute

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

HP Power Advisor utility: a tool for estimating power requirements for HP ProLiant server systems

HP Power Advisor utility: a tool for estimating power requirements for HP ProLiant server systems HP Power Advisor utility: a tool for estimating power requirements for HP ProLiant server systems technology brief Abstract... 2 Introduction... 2 Key power parameters... 2 Input line voltage... 2 Device

More information

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Increasing Data Center Efficiency by Using Improved High Density Power Distribution Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill

More information

Calculating Total Power Requirements for Data Centers

Calculating Total Power Requirements for Data Centers Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT

More information

USAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE)

USAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE) WHITE PAPER #22 USAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE) EDITORS: JON HAAS, INTEL JAMIE FROEDGE, EMERSON NETWORK POWER CONTRIBUTORS: JOHN PFLUEGER, DELL

More information

Calculating power requirements for HP ProLiant rack-mounted systems

Calculating power requirements for HP ProLiant rack-mounted systems Calculating power requirements for HP ProLiant rack-mounted systems technology brief Abstract... 2 Introduction... 2 Key parameters... 2 Input line voltage... 2 Device VA rating... 3 Device input power...

More information

Holistic, Energy Efficient Datacentre Design @ Cardiff Going Green Can Save Money

Holistic, Energy Efficient Datacentre Design @ Cardiff Going Green Can Save Money Holistic, Energy Efficient Datacentre Design @ Cardiff Going Green Can Save Money Dr Hugh Beedie CTO ARCCA & INSRV The Context Introduction Drivers to Go Green Where does all the power go? Before the equipment

More information

ENERGY STAR Data Center Storage Version 1.0. Stakeholder Update. 02 February 2010

ENERGY STAR Data Center Storage Version 1.0. Stakeholder Update. 02 February 2010 ENERGY STAR Data Center Storage Version 1.0 Stakeholder Update 02 February 2010 Agenda Development Schedule Overview Draft 1 Considerations Partner Commitments Definitions Product Family Taxonomy PSU Criteria

More information

Power and Cooling Capacity Management for Data Centers

Power and Cooling Capacity Management for Data Centers Power and Cooling Capacity for Data Centers By Neil Rasmussen White Paper #150 Executive Summary High density IT equipment stresses the power density capability of modern data centers. Installation and

More information

Green HPC - Dynamic Power Management in HPC

Green HPC - Dynamic Power Management in HPC Gr eenhpc Dynami cpower Management i nhpc AT ECHNOL OGYWHI T EP APER Green HPC Dynamic Power Management in HPC 2 Green HPC - Dynamic Power Management in HPC Introduction... 3 Green Strategies... 4 Implementation...

More information

Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation

Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation One Dell Way Round Rock, Texas 78682 www.dell.com Dell Enterprise White Paper Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation January, 2008

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Measuring Power in your Data Center

Measuring Power in your Data Center RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There

More information

Data Center Energy Efficiency Looking Beyond PUE

Data Center Energy Efficiency Looking Beyond PUE Data Center Energy Efficiency Looking Beyond PUE No Limits Software White Paper #4 By David Cole 2011 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,

More information

THE GREEN GRID METRICS: DATA CENTER INFRASTRUCTURE EFFICIENCY (DCIE) DETAILED ANALYSIS

THE GREEN GRID METRICS: DATA CENTER INFRASTRUCTURE EFFICIENCY (DCIE) DETAILED ANALYSIS WHITE PAPER #14 THE GREEN GRID METRICS: DATA CENTER INFRASTRUCTURE EFFICIENCY (DCIE) DETAILED ANALYSIS EDITOR: GARY VERDUN, DELL CONTRIBUTORS: DAN AZEVEDO, SYMANTEC HUGH BARRASS, CISCO STEPHEN BERARD,

More information

Managing Power Usage with Energy Efficiency Metrics: The Available Me...

Managing Power Usage with Energy Efficiency Metrics: The Available Me... 1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount

More information

Power and Cooling Innovations in Dell PowerEdge Servers

Power and Cooling Innovations in Dell PowerEdge Servers Power and Cooling Innovations in Dell PowerEdge Servers This technical white paper describes the Dell Energy Smart Architecture and the new and enhanced features designed into Dell PowerEdge 12 th generation

More information

Global Headquarters: 5 Speen Street Framingham, MA 01701 USA P.508.872.8200 F.508.935.4015 www.idc.com

Global Headquarters: 5 Speen Street Framingham, MA 01701 USA P.508.872.8200 F.508.935.4015 www.idc.com WHITE PAPER Solutions for the Datacenter's Thermal Challenges Sponsored by: IBM and Intel Jed Scaramella January 2007 Matthew Eastwood IDC OPINION Global Headquarters: 5 Speen Street Framingham, MA 01701

More information

Implementing Energy Efficient Data Centers

Implementing Energy Efficient Data Centers Implementing Energy Efficient Data Centers By Neil Rasmussen White Paper #114 Executive Summary Electricity usage costs have become an increasing fraction of the total cost of ownership (TCO) for data

More information

Motherboard- based Servers versus ATCA- based Servers

Motherboard- based Servers versus ATCA- based Servers Motherboard- based Servers versus ATCA- based Servers Summary: A comparison of costs, features and applicability for telecom application hosting After many years of struggling for market acceptance, it

More information

Increasing Energ y Efficiency In Data Centers

Increasing Energ y Efficiency In Data Centers The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Server Technology Inc.

Server Technology Inc. Server Technology Inc. Efficiency Gains with 480V/277V Power at the Cabinet Level White Paper STI-100-012 2011-May-2 Headquarters Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 United States

More information

IMPACT OF VIRTUALIZATION ON DATA CENTER PHYSICAL INFRASTRUCTURE

IMPACT OF VIRTUALIZATION ON DATA CENTER PHYSICAL INFRASTRUCTURE WHITE PAPER #27 IMPACT OF VIRTUALIZATION ON DATA CENTER PHYSICAL INFRASTRUCTURE EDITOR: DENNIS BOULEY, APC BY SCHNEIDER ELECTRIC PAGE 2 EXECUTIVE SUMMARY Data center virtualization, which includes storage,

More information

abstract about the GREEn GRiD

abstract about the GREEn GRiD Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.

More information

Electrical Efficiency Modeling for Data Centers

Electrical Efficiency Modeling for Data Centers Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate

More information

Power Efficiency Metrics for the Top500. Shoaib Kamil and John Shalf CRD/NERSC Lawrence Berkeley National Lab

Power Efficiency Metrics for the Top500. Shoaib Kamil and John Shalf CRD/NERSC Lawrence Berkeley National Lab Power Efficiency Metrics for the Top500 Shoaib Kamil and John Shalf CRD/NERSC Lawrence Berkeley National Lab Power for Single Processors HPC Concurrency on the Rise Total # of Processors in Top15 350000

More information

Data Center Efficiency in the Scalable Enterprise

Data Center Efficiency in the Scalable Enterprise FEATURE SECTION: POWERING AND COOLING THE DATA CENTER Data Center Efficiency in the Scalable Enterprise 8 DELL POWER SOLUTIONS Reprinted from Dell Power Solutions, February 2007. Copyright 2007 Dell Inc.

More information

Buyer s Guide to Dell Power Distribution Units

Buyer s Guide to Dell Power Distribution Units Buyer s Guide to Dell Power Distribution Units With data center devices smaller than ever, often served by dual- or triple-power supplies, a single rack of equipment might produce 80 or more power cords

More information

Electrical Efficiency Modeling of Data Centers

Electrical Efficiency Modeling of Data Centers Electrical Efficiency Modeling of Data Centers By Neil Rasmussen White Paper 113 Executive Summary The conventional models used to estimate electrical efficiency of data centers are grossly inaccurate

More information

Measuring Energy Efficiency in a Data Center

Measuring Energy Efficiency in a Data Center The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics

More information

DECREASING DATACENTER AND OTHER IT ENERGY

DECREASING DATACENTER AND OTHER IT ENERGY The Green Grid Opportunity DECREASING DATACENTER AND OTHER IT ENERGY USAGE PATTERNS february 16, 2007 white paper 1 Gartner analysts advise enterprises to make the most efficient use of existing systems

More information

Datacenter Design Issues

Datacenter Design Issues Datacenter Design Issues Topics Power Cooling Floor loading Wiring Density Power Higher voltage = better efficiency Fewer conversions = better efficiency Power factor correction 3 phase power (polyphase(

More information

Server Technology Intl.

Server Technology Intl. Server Technology, Inc. 3-Phase Power in the Data Center White Paper STI-100-005 North America/ASIA EMEA Server Technology, Inc. Server Technology Intl. 1040 Sandhill Drive Sienna Court Reno, NV 89521

More information

Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell

Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell Solve your IT energy crisis WITH AN ENERGY SMART SOLUTION FROM DELL overcome DATA center energy challenges IT managers share a common and pressing problem: how to reduce energy consumption and cost without

More information

Optimizing Power Distribution for High-Density Computing

Optimizing Power Distribution for High-Density Computing Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Three-Phase Electric Power Distribution for Computer Data Centers

Three-Phase Electric Power Distribution for Computer Data Centers Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of

More information

A Comparison of AC and DC Power Distribution in the Data Center Transcript

A Comparison of AC and DC Power Distribution in the Data Center Transcript A Comparison of AC and DC Power Distribution in the Data Center Transcript Slide 1 Welcome to the Data Center University course on the A Comparison of AC and DC Power Distribution in the Data Center. Slide

More information

ENERGY STAR Program Requirements Product Specification for Computer Servers. Test Method Rev. Apr-2013

ENERGY STAR Program Requirements Product Specification for Computer Servers. Test Method Rev. Apr-2013 ENERGY STAR Program Requirements Product Specification for Computer Servers Test Method Rev. Apr-2013 1 OVERVIEW The following test method shall be used for determining compliance with requirements in

More information

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing

More information

Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment

Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment By Neil Rasmussen White Paper #27 Revision 2 Executive Summary Decisions made regarding the distribution of 208V or 120V power

More information

Guidelines for Specification of Data Center Power Density

Guidelines for Specification of Data Center Power Density Guidelines for Specification of Data Center Power Density By Neil Rasmussen White Paper #120 Executive Summary Conventional methods for specifying data center density are ambiguous and misleading. Describing

More information

Intelligent Power Optimization for Higher Server Density Racks

Intelligent Power Optimization for Higher Server Density Racks Intelligent Power Optimization for Higher Server Density Racks A Baidu* Case Study with Intel Intelligent Power Technology White Paper Digital Enterprise Group Q1 2008 Intel Corporation Executive Summary

More information

Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs

Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs Paul Yeaman, V I Chip Inc. Presented at the Darnell Digital Power Forum September 2007 Abstract An increasing focus on datacenter

More information

Data Center Management

Data Center Management Data Center Management Searching for the Optimum Solution Management of assets in the data center is incomplete, inaccurate, and difficult to maintain with today s technology No Limits Software White Paper

More information

Measuring Processor Power

Measuring Processor Power White Paper Intel Xeon Processor Processor Architecture Analysis Measuring Processor Power TDP vs. ACP Specifications for the power a microprocessor can consume and dissipate can be complicated and may

More information

Data Center Power Distribution and Capacity Planning:

Data Center Power Distribution and Capacity Planning: Data Center Power Distribution and Capacity Planning: Understanding what you know and don t know about power usage in your data center 2009, Raritan Inc. About This Series Raritan, a leading provider of

More information

WHITE PAPER Server Innovations: Examining DC Power as an Alternative for Increasing Data Center Efficiency and Reliability

WHITE PAPER Server Innovations: Examining DC Power as an Alternative for Increasing Data Center Efficiency and Reliability Global Headquarters: 5 Speen Street Framingham, MA 01701 USA P.508.872.8200 F.508.935.4015 www.idc.com WHITE PAPER Server Innovations: Examining DC Power as an Alternative for Increasing Data Center Efficiency

More information

Green Data Center and Virtualization Reducing Power by Up to 50% Pages 10

Green Data Center and Virtualization Reducing Power by Up to 50% Pages 10 Green Data Center and Virtualization Reducing Power by Up to 50% Pages 10 Issue August 2007 Contents Executive Summary 2 Blade for Blade, Power is the Same 3 PAN Lowers Power by Reducing Server/CPU Count

More information

Electrical Systems. <Presenter>

Electrical Systems. <Presenter> Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF

More information

Building the Energy-Smart Datacenter

Building the Energy-Smart Datacenter Building the Energy-Smart Datacenter How Dell PowerEdge servers, services, tools and partnerships can help customers save money by saving energy. As businesses grow, they need more computational capacity.

More information

Power efficiency and power management in HP ProLiant servers

Power efficiency and power management in HP ProLiant servers Power efficiency and power management in HP ProLiant servers Technology brief Introduction... 2 Built-in power efficiencies in ProLiant servers... 2 Optimizing internal cooling and fan power with Sea of

More information

Four secrets to avoiding data center downtime

Four secrets to avoiding data center downtime Four secrets to avoiding data center downtime Four secrets to avoiding data center downtime 2 INTRODUCTION 3 POWER GENERATION & DELIVERY SYSTEMS 4 BREAKER TRIP ON FAILOVER 5 BREAKER TRIP DURING RESTART

More information

High-Efficiency AC Power Distribution for Data Centers

High-Efficiency AC Power Distribution for Data Centers High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies

More information

Statistical Profiling-based Techniques for Effective Power Provisioning in Data Centers

Statistical Profiling-based Techniques for Effective Power Provisioning in Data Centers Statistical Profiling-based Techniques for Effective Power Provisioning in Data Centers Sriram Govindan, Jeonghwan Choi, Bhuvan Urgaonkar, Anand Sivasubramaniam, Andrea Baldini Penn State, KAIST, Tata

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

RiMatrix S Make easy.

RiMatrix S Make easy. RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power

More information

Power to the adaptable data center

Power to the adaptable data center Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.

More information

How To Manage Energy At An Energy Efficient Cost

How To Manage Energy At An Energy Efficient Cost Hans-Dieter Wehle, IBM Distinguished IT Specialist Virtualization and Green IT Energy Management in a Cloud Computing Environment Smarter Data Center Agenda Green IT Overview Energy Management Solutions

More information

Energy Management in a Cloud Computing Environment

Energy Management in a Cloud Computing Environment Hans-Dieter Wehle, IBM Distinguished IT Specialist Virtualization and Green IT Energy Management in a Cloud Computing Environment Smarter Data Center Agenda Green IT Overview Energy Management Solutions

More information

Power Efficiency Comparison: Cisco UCS 5108 Blade Server Chassis and Dell PowerEdge M1000e Blade Enclosure

Power Efficiency Comparison: Cisco UCS 5108 Blade Server Chassis and Dell PowerEdge M1000e Blade Enclosure White Paper Power Efficiency Comparison: Cisco UCS 5108 Blade Server Chassis and Dell PowerEdge M1000e Blade Enclosure White Paper March 2014 2014 Cisco and/or its affiliates. All rights reserved. This

More information

GRIDCENTRIC VMS TECHNOLOGY VDI PERFORMANCE STUDY

GRIDCENTRIC VMS TECHNOLOGY VDI PERFORMANCE STUDY GRIDCENTRIC VMS TECHNOLOGY VDI PERFORMANCE STUDY TECHNICAL WHITE PAPER MAY 1 ST, 2012 GRIDCENTRIC S VIRTUAL MEMORY STREAMING (VMS) TECHNOLOGY SIGNIFICANTLY IMPROVES THE COST OF THE CLASSIC VIRTUAL MACHINE

More information

USING VIRTUALIZATION TO IMPROVE DATA CENTER EFFICIENCY

USING VIRTUALIZATION TO IMPROVE DATA CENTER EFFICIENCY WHITE PAPER #19 USING VIRTUALIZATION TO IMPROVE DATA CENTER EFFICIENCY EDITOR: RICHARD TALABER, VMWARE CONTRIBUTORS: TOM BREY, IBM LARRY LAMERS, VMWARE PAGE 2 ABSTRACT This paper outlines some of the advantages,

More information

Server Technology, Inc.

Server Technology, Inc. Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,

More information

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published

More information

Power Efficiency and Storage Arrays Technology Concepts and Business Considerations

Power Efficiency and Storage Arrays Technology Concepts and Business Considerations Technology Concepts and Business Considerations Abstract Factors like cost and availability of energy for the data center are rapidly gaining in importance as both usage and costs increase. This white

More information

ASHRAE DATACOM BOOK SERIES

ASHRAE DATACOM BOOK SERIES WHITE PAPER #18 ASHRAE DATACOM BOOK SERIES EDITORS: DR. MICHAEL PATTERSON, INTEL RICH JONES, CHATSWORTH PRODUCTS CONTRIBUTORS: JOHN BEAN, APC ROBB JONES, CHATSWORTH PRODUCTS JOHN WALLERICH, DELL ROD BEDNAR,

More information

ASSESSMENT OF EPA MID-TIER DATA CENTER AT POTOMAC YARD

ASSESSMENT OF EPA MID-TIER DATA CENTER AT POTOMAC YARD ASSESSMENT OF EPA MID-TIER DATA CENTER AT POTOMAC YARD CONTRIBUTORS BRUCE LONG, APC BY SCHNEIDER ELECTRIC JAMES FREEMAN, EPA DR. MICHAEL PATTERSON, INTEL PAGE 2 EXECUTIVE SUMMARY In April of 2008, The

More information

HP power and cooling technologies for the data center

HP power and cooling technologies for the data center HP power and cooling technologies for the data center Technology brief, 2 nd edition Introduction... 2 ProLiant server efficiency... 2 High-efficiency features... 2 Power monitoring and reporting tools...

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

Strategies for Deploying Blade Servers in Existing Data Centers

Strategies for Deploying Blade Servers in Existing Data Centers Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling

More information

How to Measure Energy Consumption in Your Data Center

How to Measure Energy Consumption in Your Data Center How to Measure Energy Consumption in Your Data Center Gartner RAS Core Research Note G00205428, Rakesh Kumar, 8 September 2010, R3506 02112011 This research outlines a pragmatic approach that should be

More information

Power Management in the Cisco Unified Computing System: An Integrated Approach

Power Management in the Cisco Unified Computing System: An Integrated Approach Power Management in the Cisco Unified Computing System: An Integrated Approach What You Will Learn During the past decade, power and cooling have gone from being afterthoughts to core concerns in data

More information

How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring

How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring Brian Rehnke e-pdu Business Development Manager November, 2011 The Problems Energy Usage in most data centers

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

SERVER POWER CALCULATOR ANALYSIS: CISCO UCS POWER CALCULATOR AND HP POWER ADVISOR

SERVER POWER CALCULATOR ANALYSIS: CISCO UCS POWER CALCULATOR AND HP POWER ADVISOR SERVER POWER CALCULATOR ANALYSIS: CISCO UCS POWER CALCULATOR AND HP POWER ADVISOR OVERVIEW 20% 15% 10% Power estimation is an important part of data center planning. Historically, data center power circuits

More information

Types of Electrical Meters in Data Centers

Types of Electrical Meters in Data Centers Types of Electrical Meters in Data Centers White Paper 172 Revision 1 by David Kidd and Wendy Torell > Executive summary There are several different types of meters that can be designed into a data center,

More information

BCS Intermediate Certificate in Energy and Cost Management in the Data Centre Syllabus

BCS Intermediate Certificate in Energy and Cost Management in the Data Centre Syllabus BCS Intermediate Certificate in Energy and Cost Management in the Data Centre Syllabus Version 2.2 March 2015 Change History Any changes made to the syllabus shall be clearly documented with a change history

More information

System and Storage Virtualization For ios (AS/400) Environment

System and Storage Virtualization For ios (AS/400) Environment Date: March 10, 2011 System and Storage Virtualization For ios (AS/400) Environment How to take advantage of today s cost-saving technologies for legacy applications Copyright 2010 INFINITE Corporation.

More information

Data Center Power and Cooling

Data Center Power and Cooling White Paper Data Center Power and Cooling White Paper August, 2011 Introduction and Scope... 3 Data Center Thermal Considerations... 3 Data Center Temperature and Humidity Guidelines... 3 Best Practices...

More information

ENERGY STAR Servers Server Energy Use Evaluation Resources February 23, 2011. 1 Introduction

ENERGY STAR Servers Server Energy Use Evaluation Resources February 23, 2011. 1 Introduction ENERGY STAR Servers Server Energy Use Evaluation Resources February 23, 2011 1 Introduction 2 This document provides program updates as a foundation for EPA s assembly of a dataset for all servers 3 with

More information

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

AbSTRACT INTRODUCTION background

AbSTRACT INTRODUCTION background february 20, 2007 GREEN GRID METRICS: Describing Datacenter Power Efficiency Technical Committee White Paper white paper 1 Abstract The Green Grid is an association of IT professionals seeking to dramatically

More information

To Cloud or Not? Fri, 08/31/2012-12:28pm Don Lyman, CEO, Docassist cloud document managment

To Cloud or Not? Fri, 08/31/2012-12:28pm Don Lyman, CEO, Docassist cloud document managment This article was originally published on http://www.mbtmag.com To Cloud or Not? Fri, 08/31/2012-12:28pm Don Lyman, CEO, Docassist cloud document managment For a manufacturer considering a move to the cloud,

More information

Guidelines for Specification of Data Center Power Density

Guidelines for Specification of Data Center Power Density Guidelines for Specification of Data Center Power Density White Paper 120 Revision 1 by Neil Rasmussen > Executive summary Conventional methods for specifying data center density are ambiguous and misleading.

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations

More information

Avoiding Costs from Oversizing Data Center and Network Room Infrastructure

Avoiding Costs from Oversizing Data Center and Network Room Infrastructure Avoiding Costs from Oversizing Data Center and Network Room Infrastructure White Paper 37 Revision 7 by Neil Rasmussen > Executive summary The physical infrastructure of data centers and network rooms

More information

Applying Data Center Infrastructure Management in Collocation Data Centers

Applying Data Center Infrastructure Management in Collocation Data Centers Applying Data Center Infrastructure Management in Collocation Data Centers Infrastructure Management & Monitoring for Business-Critical Continuity TM Applying Data Center Infrastructure Management (DCIM)

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

Server Migration from UNIX/RISC to Red Hat Enterprise Linux on Intel Xeon Processors:

Server Migration from UNIX/RISC to Red Hat Enterprise Linux on Intel Xeon Processors: Server Migration from UNIX/RISC to Red Hat Enterprise Linux on Intel Xeon Processors: Lowering Total Cost of Ownership A Case Study Published by: Alinean, Inc. 201 S. Orange Ave Suite 1210 Orlando, FL

More information