1 REPAIRING ALUMINUM WIRING U.S. Consumer Product Safety Commission Bethesda, MD Publication 516
2
3 ALUMINUM WIRING The U.S. Consumer Product Safety Commission (CPSC) staff and other government officials have investigated numerous hazardous incidents and fires throughout the nation involving aluminum branch circuit wiring. A national survey conducted by Franklin Research Institute for CPSC showed that homes built before 1972, and wired with aluminum, are 55 times more likely to have one or more wire connections at outlets reach Fire Hazard Conditions 1 than homes wired with copper. That survey encompassed only the wire connections at outlets. It did not address other types of aluminum wire connections and splices in homes that are also prone to fail. No information was developed for aluminum-wired homes built after The fire hazard investigated by CPSC occurs at connections with aluminum wire, including receptacles or switches and junction boxes; or the hazards occur with major appliances, including dishwashers or furnaces, for example. There are several deterioration processes in aluminum wire connections that cause increased resistance to the flow of electric current, resulting in damage that is cumulative in effect. That increased resistance causes overheating, sometimes at hazardous levels, when current is flowing in the circuit. A shortage of copper in the mid 1960s caused builders to increase the use of aluminum wire in residential electrical distribution systems from the few large-power circuits (i.e., for electric clothes dryers and ranges), to general purpose 15- and 20-ampere-rated circuits. Homes built before 1965 are unlikely to have aluminum branch circuit wiring. Electrical cables installed between 1965 and the mid 1970s in new homes, in additions, and as part of rewired/new circuits may contain aluminum wiring. On April 28, 1974, two people died in a home in Hampton Bays, N.Y. Fire officials determined that the fire was caused by an overheating aluminum wire connection at a wall receptacle. 1 The survey conducted by the Franklin Research Institute defined Fire Hazard Conditions to occur when receptacle cover plate mounting screws reached 149 C (300 F), or sparks were emitted from the receptacle, or materials around the receptacle were charred. Publication June 2011
4 TROUBLE SIGNS Unfortunately, failing aluminum-wired connections seldom provide easily detected warning signs. Aluminum-wired connections and splices have been reported to fail and overheat without any prior indications or problems. If you notice any signs of a problem, have a qualified electrician determine the cause. DO NOT TRY TO DO IT YOURSELF. You could be electrocuted, or you could make the problem worse. Signs of electrical system problems include hot-to-the touch face plates on receptacles or switches; flickering lights; circuits that don t work; or the smell of burning plastic at outlets or switches. IDENTIFYING ALUMINUM WIRING Virtually all of the aluminum wiring was installed as plastic-sheathed cable (type NM, often called Romex ) with no readily discernable distinction from a cable with copper conductors. Look at the printed or embossed markings on the outer jacket of the electric cables, which are visible in unfinished basements, attics, or garages. If necessary, use a flashlight shining on the surface at a low angle to help make the embossed markings readable. Cable with aluminum conductors will have Al or Aluminum and other information marked on one side of the cable jacket every few feet along its length. (Note: be sure to read as much of the marking as possible because the marking CU-clad or Copper-clad, in addition to the Al or Aluminum, means that the cable uses copper-coated aluminum wire and is not covered by the repair recommendations outlined in this publication). 2,3 If you are unable to identify the type of wire in your home by this method, but you suspect that you have aluminum wire, have a qualified electrician make the determination. If your home has aluminum wiring that has not been remediated, CPSC recommends a permanent repair of the connections, as described in the following sections. FIXING THE PROBLEM Aluminum wiring can be replaced or repaired to effectively and permanently reduce the possibility of fire and injury due to failing (overheating) wire connections and splices. It is highly recommended that you hire a qualified electrician to perform this remediation. Other than complete replacement of aluminum wire with copper wire, there may 2 Aluminum and copper-clad aluminum cables are sized at No.10 and No.12 AWG for 20-ampere and 15-ampere rated circuits, respectively, as opposed to No.12 and No.14 AWG for copper conductors. 3 The repairs outlined in this publication do not apply to larger gauge aluminum wire circuits and connections used for service entrance cables, electric clothes dryers, and cooking ranges. 2
5 be numerous potential solutions for the permanent repair of hazardous aluminum wire connections and splices. However, CPSC can recommend repair methods or products only where there is satisfactory, documented evidence that the methods or products meet the following criteria: Safe. The method or product must be safe and not increase the risk of fire or other hazards. Effective. The method or product must be effective and successfully eliminate or substantially mitigate the fire hazard. Permanent. The method or product must affect a permanent repair. Methods or products designed to address temporary or emergency repair situations, but which may fail over time, are not considered permanent. Based on these standards, as of the date of this publication, CPSC approves of only three methods for a permanent repair. 4 1) Complete Replacement of Copper Cable 2) COPALUM Method of Repair 3) Acceptable Alternative Repair Method/ AlumiConn Connector 1) Complete Replacement with Copper Cable Replacement of the aluminum branch circuit conductors with copper wire eliminates the primary cause of the potential hazards, the aluminum wire itself. Depending on the architectural style of your home and the number and locations of unfinished spaces (e.g., basements and attics), it may be relatively easy for a qualified electrician to rewire your home. A new copper wire branch circuit system would be installed, and the existing aluminum wire could be abandoned inside the walls. This is the best method available; but for many homes, rewiring with copper is impractical and/or prohibitively expensive. 4 Any individual or company that develops a method or product that meets these CPSC standards for a safe, effective, and permanent repair of aluminum wire connections and splices and desires that the CPSC consider recommending the method or product may submit documentation of compliance with such standards to: CPSC, 4330 East West Highway, Bethesda, MD Recommendation of products or methods is rare and is solely within the discretion of the CPSC. The burden and costs of establishing compliance with such standards is the responsibility of the requestor. Consideration of a product or method is not intended and does not create any right or benefit, substantive or procedural, enforceable at law or in equity, by any party against the U.S. Consumer Product Safety Commission or the United States, its officers, employees, or agents, or any other person. 3
6 2) COPALUM Method of Repair As an alternate to rewiring with copper, CPSC recommends attaching a short section of copper wire to the ends of the aluminum wire at connection points (a technique commonly referred to as pigtailing ), using a special connector named COPALUM to join the wires. CPSC staff considers pigtailing with a COPALUM connector to be a safe and permanent repair of the existing aluminum wiring. The repair should include every connection or splice involving aluminum wire in the home, including outlets, dimmers, switches, fixtures, appliances, and junction boxes. The repaired system, with short copper wire extensions at every termination throughout the home, permits the use of standard wiring devices, including receptacles and switches. The COPALUM repair method is recommended by CPSC on the basis of CPSCsponsored research, laboratory tests, and demonstration projects. This repair method has been thoroughly proven by more than a quarter of a century of field experience to provide a permanent, low-resistance electrical connection to aluminum wire. The COPALUM repair method eliminates the aluminum connection failure problems and still uses the existing, installed aluminum wire. The COPALUM repair method has been shown to be practical for installation in an occupied and furnished home. Every connection of aluminum-to-aluminum or aluminum-to-copper wire should be repaired in order to obtain the maximum benefit from such repair work. All appliances connected directly to No.12 or No.10 AWG aluminum branch circuit wiring (e.g., dishwashers, cooling equipment, heaters, air conditioners, and light fixtures) must be repaired in addition to wall outlets, switches, junction boxes, and panel boxes. The COPALUM connector is a specially designed system that includes a metal sleeve intended to be installed only with a dedicated power tool and crimping die to make a permanent connection, that is, in effect, a cold weld (the precision dies in the CO- PALUM tool compress the connector and wires using upwards of 10,000 pounds of force, as required to make the permanent aluminum wire connection). 4
7 The tool is shown in the illustration below. An insulating sleeve is placed around the crimp connector to complete the repair. The copper wire pigtail is then connected to the switch, receptacle, or other termination device. An example of a repaired receptacle outlet is also illustrated below. Only electricians who are trained by the manufacturer to use the tool properly are authorized to install COPALUM connectors. CPSC staff emphasizes that this training is necessary to ensure that the electrician uses the careful, professional workmanship and thoroughness required to make the crimp connector repair safe and permanent. COPALUM Crimp Connector and its Specialized Installation Tooling Recommended COPALUM Connector Repair 5
8 To determine if there is a COPALUM installer in your region, visit: tycoelectronics.com/copalum/copalum_ home.asp, or contact the manufacturer at (800) or at the following address: TE Connectivity Attn: COPALUM Aluminum Wire Repair Program P.O. Box 3608 Harrisburg, Pa ) Acceptable Alternative Repair Method CPSC staff recognizes that copper replacement may be cost prohibitive and that the COPALUM repair may be unavailable in a locality. Based upon an evaluation that was, in part, CPSC supported, 5 consumers are advised that, if the COPALUM repair is not available, the AlumiConn connector may be considered the next best alternative for a permanent repair. This repair method involves pigtailing using a setscrew type connector instead of the COPALUM crimp connector in the repaired connections. The AlumiConn connector has performed well in initial tests, but is too new to have developed a significant long-term safe performance history as the COPALUM repair. The repair should be conducted by a qualified electrician because careful, professional workmanship and thoroughness are required to make the AlumiConn connector repair safe and permanent. The AlumiConn Connector For additional information on the AlumiConn connector, visit: alumiconn, or contact the manufacturer at (800) , or write to the firm at the following address: King Innovation 42 N. Central Drive O Fallon, Mo RECOMMENDATIONS AGAINST USING OTHER REPAIR METHODS Non-COPALUM Crimp Connectors There are many other brands and types of crimp connectors including those intended to be installed with a pliers-type of handtool which are readily available to consumers at common retailers. No other crimp connectors have been evaluated for connecting copper and aluminum conductors. CPSC staff strongly recommends against their use as a repair method. 5 CPSC s contractor self-funded the fundamental part of this research. The CPSC contract provided funds for additional longer term testing and recommendations requested in the CPSC contract. 6
9 of twist-on connectors with aluminum wire. It is possible that some pigtailing repairs made with twist-on connectors may be prone to even more failures than the original aluminum wire connectors. Accordingly, CPSC staff believes that this method of repair does not solve the problem of overheating present in aluminum-wired branch circuits. Do Not Use Common Hand-Crimped Connectors with Aluminum Wire Two other repair methods described below are often recommended by some electricians because they are substantially less expensive than COPALUM crimp connectors. CPSC staff does not consider either of these repairs an acceptable permanent repair. Twist-on Connectors The first temporary repair involves pigtailing with a twist-on connector. The effectiveness of pigtailing using twist-on connectors has been evaluated by CPSC staff. In CPSC-sponsored laboratory testing and life tests, substantial numbers of these connectors overheated severely. Surveys of and statements made by electricians and electrical inspectors confirm the highly variable and often poor performance Pigtailing with Twist-on Connectors Is Not a Recommended Repair CO/ALR Switches and Receptacles The other repair recommended by the industry is to use switches and receptacles labeled CO/ALR. These devices are intended for direct connection to aluminum wire, although they can be used with copper or copper-clad wire. CO/ALR devices perform better with aluminum wire than non-co/alr devices when 7
10 installed carefully and according to best electrical practices. However, CO/ALR wiring devices have failed in laboratory tests when connected to aluminum wire typical of that installed in existing homes. The test conditions simulated actual use conditions; no overstress type of testing was used. Further, CO/ALR connectors are not available for all parts of the wiring system (e.g., for the permanently wired appliances and ceiling mounted light fixtures). In the opinion of CPSC staff, CO/ALR devices must be considered, at best, an incomplete repair. Recommendations on Temporary Repairs AL/CU twist-on connector pigtails or CO/ALR devices may be used as an emergency, temporary repair for a failed aluminum termination. Should such a repair be performed, CPSC staff recommends that a complete repair of the aluminum-wired system be performed using the CPSCrecommended methods as soon as possible. CODE COMPLIANCE AND INSPECTION All modifications and additions to installed wiring should be performed and inspected in accordance with local regulations. 8
11 This pamphlet is available on the Web at: The U.S. Consumer Product Safety Commission is charged with protecting the public from unreasonable risks of serious injury or death from thousands of types of consumer products under the agency s jurisdiction. CPSC is committed to protecting consumers and families from products that pose a fire, electrical, chemical, or mechanical hazard. CPSC s work to ensure the safety of consumer products such as toys, cribs, power tools, cigarette lighters, and household chemicals contributed significantly to the decline in the rate of deaths and injuries associated with consumer products over the past 30 years. To report a dangerous product or a product-related injury, visit: call CPSC s hotline at (800) , or CPSC s teletypewriter at (301) To join a CPSC subscription list, please go to: Consumers can obtain this release and recall information at the CPSC s website at:
12
ALUMINUM ELECTRICAL WIRING
ALUMINUM ELECTRICAL WIRING prepared by Fire Prevention and Investigation Division Denver Fire Department Department of Safety and Electrical Inspections Section Denver Building Inspection Division Community
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?
Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
HOUSING QUALITY STANDARDS (HQS)
HOUSING QUALITY STANDARDS (HQS) Series 5 Electrical Safety And INSPECTIONS 5.01 ELS Revised 8-17-06 Electricity is Dangerous All electrical repairs should be made by licensed professionals. Touching any
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
Requirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
GENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
Electrical Wiring Guide
Electrical Wiring Guide In order to wire your own home, you must comply with the requirements of the 2011 edition of the National Electrical Code (NEC). NEC code articles are indicated by brackets ([ ]),
Extension Cord Safety Policy
NATIONAL HIGH MAGNETIC FIELD LABORATORY Operated by Florida State University, University of Florida, Los Alamos National Laboratory Florida State University, 1800 East Paul Dirac Drive, Tallahassee, Florida
Service Bulletin SA-008. DATE: June 18, 2008 TO: All Service and Parts Managers SUBJECT: Flood Damaged Appliances
Service Bulletin DATE: June 18, 2008 TO: All Service and Parts Managers SUBJECT: Flood Damaged Appliances SA-008 Due to the unfortunate flooding experienced by many areas in the Midwest in recent months,
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
2 electrical. electrical. 2010 PulteGroup, Inc. All Rights Reserved.
2 12 2010 PulteGroup, Inc. All Rights Reserved. circuit breakers Circuit breakers protect your home s system from power failure. The wiring in your home is protected by circuit breakers. Circuit breakers,
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Fire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT. YOU COULD PUT YOUR FAMILY AND WORLDLY POSSESSIONS IN DANGER!!!
Residential Electrical Inspection. Checklist
443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota
REHABILITATION OF MOBILE HOMES R4 34 606
REHABILITATION OF MOBILE HOMES R4 34 606 PURPOSE The purpose of this program is to provide minimum safety standards for homes manufactured before the implementation of the HUD Manufactured Home Construction
INSIDE TELEPHONE WIRING FOR Business
Do It Yourself Guide INSIDE TELEPHONE WIRING FOR Business As of March 1, 2015 all single line business customers that have a demarcation point such as but not limited to a Network Interface Device (NID),
Four Point Insurance Inspections *A Home Inspection is NOT a 4 Point Inspection
Four Point Insurance Inspections *A Home Inspection is NOT a 4 Point Inspection Update from Citizens Insurance Effective 9/1/2012: As the leader of the Home Inspection Industry in Florida, HomeTeam Inspection
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared
in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put it into perspective: Electrocutions can be Prevented
Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, injure 1,400 people, and account
Protect your home and family with Advanced Technology from Cutler-Hammer
Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths
City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines
Western Riverside County Code Uniformity Program City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines PHONE (951) 826-5697 3900 Main Street, Riverside, CA 92522
Electric Water Heater
Electric Water Heater Operation and Installation Manual (LIMITED WARRANTY AND TANK REPLACEMENT POLICY) The following information should be noted at time of installation and retained for future reference.
Residential Electrical Inspection Checklist
Residential Electrical Inspection Checklist Based on the 2008 National Electrical Code Generally, Minnesota law requires all electrical work to be performed by licensed, bonded and insured electrical contractors
Residential Electrical Inspection. Checklist
Electrical Licensing and Inspection 443 Lafayette Road North St. Paul, Minnesota 55155-4342 www.doli.state.mn.us 651-284-5064 Fax: 651-284-5743 TTY: 651-297-4198 1-800-DIAL-DLI Residential Electrical Inspection
Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)
Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations
Homeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
Questions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
COMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
WISCONSIN DEPARTMENT OF SAFETY & PROFESSIONAL SERVICES
Scott Walker Governor David Ross Secretary WISCONSIN DEPARTMENT OF SAFETY & PROFESSIONAL SERVICES 1400 E Washington Ave PO Box 8935 Madison WI 53708-8935 Email: [email protected] Voice: 608-266-2112 FAX:
Home Inspection Report
4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 [email protected] Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
Article 10 - ADMINISTRATIVE SECTION
Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the
MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850
Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
Electrical Hazards. Power Tools. Extension Cords
Electrical Hazards Electrical hazards can be found in nearly every roofing work site. Whether the hazard is posed by worn or damaged power tools or cords, improperly grounded tools or equipment, or the
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
4-Point Inspection Personal Lines (Edition 9/2012)
(Edition 9/2012) INSURED/APPLICANT NAME: Mr. and Mrs. America APPLICATION/POLICY #: ADDRESS INSPECTED: 1234 Surfing Villa Way, Riverview, FL 33569 ACTUAL YEAR BUILT: 1987 DATE OF INSPECTION: 5/09/2014
Vision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
Residential Electrical System Aging Research Project. Dave Dini Sr. Research Engineer Underwriters Laboratories
Residential Electrical System Aging Research Project Dave Dini Sr. Research Engineer Underwriters Laboratories Aging Residential Electrical Systems Research Project Sponsors Fire Protection Research Foundation
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
HOME ELECTRICAL Safety Checklist
Keeping You and Your Family Safe, Room-by-Room U.S. Consumer Product Commission 4330 East West Highway Bethesda, MD 20814 Pub 513 July 2008 This document was prepared by CPSC staff, has not been reviewed
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
Ducoterra Radiant Heating Panel Installation Manual
Ducoterra Radiant Heating Panel Installation Manual 1. Introduction Your new radiant heating panels are designed to heat living and working spaces rapidly and efficiently by radiant heating. Like the sun,
in the United States Home fires are a major problem Older Homes Pose an Even Greater Threat Put Into Perspective Electrocutions Can Be Prevented
Home fires are a major problem in the United States Each year, home electrical problems alone account for an estimated 53,600 fires. These fires cause more than 500 deaths, 1,400 injuries, and $1.4 billion
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022.
The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022. Train now for affordable Electrician careers and get wired for success. Residential Electrician Diploma Program
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
Electrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
PROPERTY INSPECTION REPORT
Whisper Computer Solutions, Inc. P.O. Box 690502 San Antonio, TX 78269-0502 Phone: (210)681-6325 Fax: (210)681-6325 Email: [email protected] PROPERTY INSPECTION REPORT Prepared For: Concerning:,
A guide to understanding and maintaining your home s electrical system. A publication presented by the Electrical Safety Foundation International
A guide to understanding and maintaining your home s electrical system A publication presented by the Electrical Safety Foundation International What s Inside? Everything you need to know Should You Do-It-Yourself?
Electric Vehicle Charging Station Installation Guidelines: Residential and Commercial Locations
Electric Vehicle Charging Station Installation Guidelines: Residential and Commercial Locations Streamlining Permitting and Inspection of Residential and Commercial Electric Vehicle Charging Station Installations
Inspecton Report. Property Address:
Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 [email protected] www.nationalhomeservices.com Property Address: 873
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
Electrical Safety In and Around the Home
In and Around the Home Electrical Safety In and Around the Home Developed by: American Burn Association Burn Prevention Committee Funded by: United States Fire Administration/ Federal Emergency Management
Smoke & Carbon Monoxide
A Guide to the Massachusetts Smoke & Carbon Monoxide Requirements when Selling a Oneor Two-Family Residence FIRE SERVICES Department of Fire Services PO Box 1025 Stow, MA 01775 978-567-3300 www.mass.gov/dfs
Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
Candle Ring Recalled by Yankee Candle Due to Fire Hazard
U.S. Consumer Product Safety Commission Recall w/health Canada Recall Date: December 20, 2013 Recall Number: 14-FOR CLEARANCE Candle Ring Recalled by Yankee Candle Due to Fire Hazard WASHINGTON, D.C. -
Inspection Tech. (330) 310-6559 http://www.inspectiontech.us [email protected] Inspected By: Aaron Westerburg
Inspection Tech (330) 310-6559 http://www.inspectiontech.us [email protected] Inspected By: Aaron Westerburg Inspection Tech Home Inspection Report Prepared For: Mr. & Mrs. Homebuyer Property
HomeOwner Wiring. Please remember you are required to contact your inspector for inspections
HomeOwner Wiring Please remember you are required to contact your inspector for inspections South Dakota Electrical Commission 308 S. Pierre St. Pierre, SD 57501 1-800-233-7765 or (605) 773-3573 www.electrical.sd.gov
BATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716
BATHROOM HEATER User's Manual Page 2...A515 Page 9...A716 BATHROOM HEATER User's Manual A515 SAVE THESE INSTRUCTIONS AND READ ALL INSTRUCTIONS BEFORE USING THE HEATER. Dear customers, Thank you for selecting
SITE INSPECTION CHECKLIST
SITE INSPECTION CHECKLIST Numerous steps are required in determining that a site is suitable for the installation of a solar system. The inspection procedures and their proper chronology are outlined below.
Electrical Extension Cords & Relocatable Power Taps: (RPT s)
Electrical Extension Cords & Relocatable Power Taps: (RPT s) If either device is not use correctly, a fire can happen The new FDNY Fire Code (eff. 7.08) addresses these issues in 605.4 and 605.5 A recent
Home Electrical Safety Challenge
Home Electrical Safety Challenge Home Electrical Safety Challenge Why is there a different kind of outlet in my bathroom? What does that TEST button do? Why does the circuit breaker trip every time my
INSPECTION REPORT. LOCATION OF PROPERTY 1234 Sample Street Tucson, AZ 85701. CLIENT Mr. & Mrs. John Q. Sample c/o Agent DATE OF INSPECTION 1/30/2008
INSPECTION REPORT LOCATION OF PROPERTY 1234 Sample Street CLIENT Mr. & Mrs. John Q. Sample c/o Agent DATE OF INSPECTION 1/30/2008 INSPECTOR Dave Woityra FILE CODE: 0100114.SAM AGENT Sample Q. Jones A.B.C.
Flood Risk Considerations
CHECKLIST FOR MITIGATING OR AVOIDING FLOOD DAMAGE It may not seem the case, but individuals are not powerless in influencing their potential exposure to catastrophes, such as floods. Property owners have
Electric Service Guide for Residential Construction
Electric Service Guide for Residential Construction Table of Contents Contacting KCP&L... 2 Existing Home Remodeling or Additions... 2 Changing your electric service... 2 What you need to know before you
GENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
Electrical Contractors. and the. New Jersey. Rehabilitation Code
Electrical Contractors and the New Jersey Rehabilitation Code Alan Chech Electrical Seminars 609-890-7072 www.alanchech.com Information is based on the presently adopted electrical subcode NEC 2005. Current
Acumen Enterprises, Inc.
Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter
IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.
THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to
CHAPTER 34, MUNICIPAL CODE OF THE CITY OF CEDAR RAPIDS, IOWA CEDAR RAPIDS ELECTRICAL CODE
CHAPTER 34, MUNICIPAL CODE OF THE CITY OF CEDAR RAPIDS, IOWA CEDAR RAPIDS ELECTRICAL CODE EFFECTIVE MAY 1, 2006 34.01 TITLE. This Chapter shall be known as the Cedar Rapids Electrical Code, may be so cited
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS The Language Used In This Document Does Not Create An Employment Contract Between The Employee And The Agency. This Document Does
PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS
Butte County Department of Development Services PERMIT CENTER 7 County Center Drive, Oroville, CA 95965 Main Phone (530)538-7601 Permit Center Phone (530)538-6861 Fax (530)538-7785 FORM NO DBP-71 PERMIT
October Safety Subject
October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that
Guide to Massachusetts Smoke & Carbon Monoxide Requirements
Guide to Massachusetts Smoke & Carbon Monoxide Requirements When Selling a One- or Two-Family Residence DEPARTMENT OF FIRE SERVICES Stephen D. Coan State Fire Marshal M.G.L. c 148 s. 26F - The Law Massachusetts
Arc Fault Circuit Interrupters Frequently Asked Questions
Contents My AFCI is tripping! What do I do? What is the difference between branch feeder and combination type Arc Fault Circuit Interrupters? What is new with the 2008 NEC versus the 2005 NEC with respect
Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters
Quartzone Owner s Manual File E97759 COMFORT S for INDOOR* and OUTDOOR** USE *Excluding Residences ** With Quartz Elements and when mounted Underneath an Overhang by means of brackets out of the reach
Four-Point Insurance Inspection Report
Four-Point Insurance Inspection Report Date of Inspection: Property address: Property's City, State, Zip Code: Approximate Total Square Feet: Approximate Total Living Area: Actual Year Built: Insured/Applicant
I NI NP R Inspected Items
6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and
Inspection Report Atlanta Strip Mall Commercial Building Property Address:
Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of
Wiring Around Your Home
AGRICULTURE EXTENSION 4-H-1021-W PILOT Wiring Around Your Home 4-H Electric Division V Wiring Around Your Home Welcome to Division V of the 4-H Electric Project Congratulations! You've successfully completed
Report for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 1) Tamper resistant receptacles. 2009 CEC Required in dwelling units 2012 CEC Expanded to child care facilities First introduced in the 2009
Alarms. State of Wisconsin Rules ss. 101.149(2) and (3) Comm. 62.1200 Comm.21.097
Carbon Monoxide Alarms State of Wisconsin Rules ss. 101.149(2) and (3) Comm. 62.1200 Comm.21.097 Carbon Monoxide Hazards CO, is a colorless, odorless and tasteless, yet highly toxic gas. Its molecules
COUNTY OF LOS ANGELES BUILDING AND SAFETY DIVISION ELECTRICAL CODE FEE SCHEDULE (Title 27 of the County of Los Angeles Code, Ord No.
COUNTY OF LOS ANGELES BUILDING AND SAFETY DIVISION ELECTRICAL CODE FEE SCHEDULE (Title 27 of the County of Los Angeles Code, Ord No. 2013-0049) Effective July 1, 2014, Electrical Permit Fees in the unincorporated
Model 1756 Test Lead Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you
270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer