Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment

Size: px
Start display at page:

Download "Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment"

Transcription

1 ANSI/AHRI Standard 210/240 with Addenda 1 and 2 (formerly ARI Standard 210/240) 2008 Standard for Performane Rating of Unitary Air-Conditioning & Air-Soure Heat Pump Equipment Approved by ANSI in Deember 2012

2 ANSI/AHRI STANDARD 210/ WITH ADDENDUM 2 Performane Rating of Unitary Air-Conditioning & Air-Soure Heat Pump Equipment Marh 2012 Addendum 2 of ANSI/AHRI Standard 210/ , is provided as follows. The following hanges have been inorporated (additions are shown with highlights; deletions are shown by strikethroughs) into the already published 2008 version of ANSI/AHRI Standard 210/240 with Addendum 1 to avoid onfusion: The Integrated Energy Effiieny Ratio (IEER) methodology has been added to the standard for water-ooled and evaporatively-ooled produts. It is not intended for air-ooled produts whih should be rated with SEER. This inludes: 1. The addition of definition of IEER (page 2) 2. The addition of and in multiples of 0.1 for IEER to Setion (page 5). 3. The addition of Part-Load IEER Conditions to Test Conditions to Table 12 (page 21) 4. The reinstatement of Note 2 in Table 12 (page 21) 5. New Setion 6.2 Part Load Ratings (pages 22-26). This new Setion 6.2 is dupliated from Setion 6.2 from AHRI Standard 340/ with addenda 1 and The addition of plus the IEER (where appliable), to Setion 6.4 (page 26) 7. The addition of exept IEER whih shall not be less than 90% of Published Ratings. to Setion 6.5 (page 26) 8. The addition of 3. Integrated Energy Effiieny Ratio, IEER, to Setion 7.1.b (page 27)

3 ANSI/AHRI STANDARD 210/ WITH ADDENDUM 1 Performane Rating of Unitary Air-Conditioning & Air-Soure Heat Pump Equipment June 2011 Addendum 1 of ANSI/AHRI Standard 210/ , is provided as follows. The following hanges have been inorporated (deletions are shown by strikethroughs) into the already published 2008 version of ANSI/AHRI Standard 210/240 to avoid onfusion: The Integrated Part-Load Values (IPLV) methodology has been removed from the standard. This inludes the deletion of: 9. Setion 3.6 Integrated Part Load Value (IPLV) Definition (page 2) 10. and in multiples of 0.1 for IPLV from Setion (page 5) 11. The Part Load Conditions line and Note 2 of Table 12 (page 21) 12. Setion 6.2 Part Load Ratings (pages 21-22) 13. plus the IPLV (where appliable) from Setion 6.4 (page 22) 14. Appendix E. The orresponding Table E1 has also been removed (pages )

4 IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not ertify or guarantee the safety of any produts, omponents or systems designed, tested, rated, installed or operated in aordane with this standard/guideline. It is strongly reommended that produts be designed, onstruted, assembled, installed and operated in aordane with nationally reognized safety standards and ode requirements appropriate for produts overed by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and aepted industry praties. AHRI does not ertify or guarantee that any tests onduted under its standards/guidelines will be non-hazardous or free from risk. AHRI CERTIFICATION PROGRAM PROVISIONS Sope of the Certifiation Program The Certifiation Program inludes all Unitary Air-Conditioning and Air-Soure Unitary Heat Pump equipment rated below 65,000 Btu/h [19,000 W] at AHRI Standard Rating Conditions (Cooling). Certified Ratings The following Certifiation Program ratings are verified by test: Unitary Air-Conditioners A. Air-ooled under 65,000 Btu/h [19,000 W] 1. AHRI Standard Rating Cooling Capaity, Btu/h [W] 2. Seasonal Energy Effiieny Ratio, SEER, Btu/(W h) B. Water-ooled and evaporatively-ooled under 65,000 Btu/h [19,000 W] 1. AHRI Standard Rating Cooling Capaity, Btu/h [W] 2. Energy Effiieny Ratio, EER, Btu/(W h) 3. Integrated Energy Effiieny Ratio, IEER, Btu/(W h) Air-Soure Unitary Heat Pumps Air-ooled under 65,000 Btu/h [19,000 W] 1. AHRI Standard Rating Cooling Capaity, Btu/h [W] 2. Seasonal Energy Effiieny Ratio, SEER, Btu/(W h) 3. High Temperature Heating Standard Rating Capaity, Btu/h [W] 4. Region IV Heating Seasonal Performane Fator, HSPF, Minimum Design Heating Requirement, Btu/(W h) Conformane to the requirements of the Maximum Operating Conditions Test, Voltage Tolerane Test, Low- Temperature Operation Test (Cooling), Insulation Effetiveness Test (Cooling), and Condensate Disposal Test (Cooling), as outlined in Setion 8, are also verified by test. Note: This standard supersedes ARI Standard 210/

5 TABLE OF CONTENTS SECTION PAGE Setion 1. Purpose... 1 Setion 2. Sope... 1 Setion 3. Definitions... 1 Setion 4. Classifiations... 4 Setion 5. Test Requirements... 4 Setion 6. Rating Requirements... 4 Setion 7. Minimum Data Requirements for Published Ratings Setion 8. Operating Requirements Setion 9. Marking and Nameplate Data Setion 10. Conformane Conditions TABLES Table 1. Classifiation of Unitary Air-Conditioners... 6 Table 2. Classifiation of Air-Soure Unitary Heat Pumps... 7 Table 3. Table 4. Table 5. Table 6. Cooling Mode Test Conditions for Units Having a Single-Speed Compressor and a Fixed-Speed Indoor Fan, a Constant Air Volume Rate Indoor Fan, or No Indoor Fan Heating Mode Test Conditions for Units Having a Single-Speed Compressor and a Fixed-Speed Indoor Fan, a Constant Air Volume Rate Indoor Fan, or No Indoor Fan Cooling Mode Test Conditions for Units Having a Single-Speed Compressor and a Variable Air Volume Rate Indoor Fan that Correlates with the Outdoor Dry Bulb Temperature (Setion ) Heating Mode Test Conditions for Units Having a Single-Speed Compressor and a Variable Air Volume Rate Indoor Fan... 16

6 TABLES (Cont d) Table 7. Table 8. Table 9. Table 10. Table 11. Table 12. Cooling Mode Test Conditions for Units Having a Two-Capaity Compressor Heating Mode Test Conditions for Units Having a Two-Capaity Compressor Cooling Mode Test Conditions for Units Having a Variable-Speed Compressor Heating Mode Test Conditions for Units Having a Variable-Speed Compressor Minimum External Stati Pressure for Duted Systems Tested with an Indoor Fan Installed Conditions for Standard Rating Tests and Operating Requirement Tests for Water-ooled and Evaporatively-ooled Equipment Using ASHRAE Standard Table 12A. IEER Part-Load Rating Conditions Table 13. Conditions for Operating Requirement Tests for Air-ooled Equipment FIGURE Figure 1. Part-Load Fator Curve APPENDICES Appendix A. Referenes Normative Appendix B. Referenes Informative Appendix C. Uniform Test Method for Measuring the Energy Consumption of Central Air Conditioners and Heat Pumps Normative Appendix D. Presriptive Methodology for the Cyli Testing of Duted Systems Normative Appendix E. Example of Calulating Integrated Part-Load Values (IPLV) Normative

7 TABLE FOR APPENDICES Table E1. Example IPLV Calulation FIGURES FOR APPENDICES Figure D1. Tunnel Air Enthalpy Test Method Arrangement Figure D2. Loop Air Enthalpy Test Method Arrangement Figure D3. Calorimeter Air Enthalpy Test Method Arrangement Figure D4. Room Air Enthalpy Test Method Arrangement

8 ANSI/AHRI STANDARD 210/ PERFORMANCE RATING OF UNITARY AIR- CONDITIONING AND AIR-SOURCE HEAT PUMP EQUIPMENT Setion 1. Purpose 1.1 Purpose. The purpose of this standard is to establish, for Unitary Air-Conditioners and Air-Soure Unitary Heat Pumps: definitions; lassifiations; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data; and onformane onditions Intent. This standard is intended for the guidane of the industry, inluding manufaturers, engineers, installers, ontrators and users Review and Amendment. This standard is subjet to review and amendment as tehnology advanes. Setion 2. Sope 2.1 Sope. This standard applies to fatory-made Unitary Air-Conditioners and Air-Soure Unitary Heat Pumps as defined in Setion Energy Soure. This standard applies only to eletrially operated, vapor ompression refrigeration systems. 2.2 Exlusions This standard does not apply to the rating and testing of individual assemblies, suh as ondensing units or oils, for separate use This standard does not apply to heat operated air-onditioning/heat pump equipment, or to pakaged terminal air-onditioners/heat pumps, or to room air-onditioners/heat pumps This standard does not apply to Unitary Air-Conditioners as defined in AHRI Standard 340/360 with apaities of 65,000 Btu/h [19,000 W] or greater This standard does not apply to Air-Soure Unitary Heat Pumps as defined in AHRI Standard 340/360 with ooling apaities of 65,000 Btu/h [19,000 W] or greater, or to water-soure heat pumps, to ground water-soure heat pumps, and to ground soure losed-loop heat pumps This standard does not inlude water heating heat pumps This standard does not apply to rating units equipped with desuperheater/water heating devies in operation. Setion 3. Definitions All terms in this doument shall follow the standard industry definitions in the urrent edition of ASHRAE Terminology of Heating, Ventilation, Air- Conditioning and Refrigeration, unless otherwise defined in this setion. Note: Definitions for Small-dut, High-veloity Systems, Spae Constrained Produts, and Through-the-wall Air Conditioners and Heat Pumps are taken from Title 10, Code of Federal Regulations, Part 430, Subparts and (). See Appendix C for definitions that apply to the testing and alulation proedures required by Appendix C. 1

9 ANSI/AHRI STANDARD 210/ Air-Soure Unitary Heat Pump. One or more fatory-made assemblies whih normally inlude an indoor onditioning oil(s), ompressor(s), and outdoor oil(s), inluding means to provide a heating funtion. When suh equipment is provided in more than one assembly, the separated assemblies shall be designed to be used together, and the requirements of rating outlined in the standard are based upon the use of mathed assemblies Funtions. They shall provide the funtion of air heating with ontrolled temperature, and may inlude the funtions of air-ooling, air-irulating, air-leaning, dehumidifying or humidifying. 3.2 Degradation Coeffiient (C D ). The measure of the effiieny loss due to the yling of the units as determined in Appendies C and D. 3.3 Design Heating Requirement (DHR). This is the amount of heating required to maintain a given indoor temperature at a partiular outdoor design temperature. 3.4 Energy Effiieny Ratio (EER). A ratio of the ooling apaity in Btu/h to the power input value in watts at any given set of Rating Conditions expressed in Btu/(W h) Standard Energy Effiieny Ratio. A ratio of the apaity to power input value obtained at Standard Rating Conditions Integrated Energy Effiieny Ratio (IEER). A single number ooling part-load effiieny figure of merit alulated per the method desribed in Setion expressed in Btu/(W h). 3.5 Heating Seasonal Performane Fator (HSPF). The total spae heating required during the spae heating season, expressed in Btu s, divided by the total eletrial energy onsumed by the heat pump system during the same season, expressed in watt-hours. 3.6 Integrated Part-Load Value (IPLV). A single number part-load effiieny figure of merit alulated per the method desribed in this standard. 3.7 Published Rating. A statement of the assigned values of those performane harateristis, under stated Rating Conditions, by whih a unit may be hosen to fit its appliation. These values apply to all units of like nominal apaity and type (identifiation) produed by the same manufaturer. As used herein, the term Published Rating inludes the rating of all performane harateristis shown on the unit or published in speifiations, advertising, or other literature ontrolled by the manufaturer, at stated Rating Conditions Appliation Rating. A rating based on tests performed at Appliation Rating Conditions (other than Standard Rating Conditions) Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.8 Rating Conditions. Any set of operating onditions under whih a single level of performane results and whih auses only that level of performane to our Standard Rating Conditions. Rating Conditions used as the basis of omparison for performane harateristis. 3.9 Seasonal Energy Effiieny Ratio (SEER). The total heat removed from the onditioned spae during the annual ooling season, expressed in Btu s, divided by the total eletrial energy onsumed by the air onditioner or heat pump during the same season, expressed in watt-hours "Shall" or "Should". "Shall" or "should" shall be interpreted as follows: Shall. Where "shall" or "shall not" is used for a provision speified, that provision is mandatory if ompliane with the standard is laimed Should. "Should" is used to indiate provisions whih are not mandatory but whih are desirable as good pratie. 2

10 ANSI/AHRI STANDARD 210/ Small-dut, High-veloity System. A heating and/or ooling produt that ontains a blower and indoor oil ombination that is designed for, and produes, at least 1.2 in H 2 O [300 Pa] of external stati pressure when operated at the ertified air volume rate of fm [ m 3 /s] per rated ton [12,000 Btu/h] of ooling. When applied in the field, small-dut produts use high-veloity room outlets (i.e., generally greater than 1,000 fpm [5 m/s]) having less than 6.0 in 2 [3,900 mm 2 ] of free area Spae Constrained Produt. A entral air onditioner or heat pump: a. that has rated ooling apaities no greater than 30,000 Btu/h [8,800 W]; b. that has an outdoor or indoor unit having at least two overall exterior dimensions or an overall displaement that: 1. is substantially smaller than those of other units that are: a. urrently usually installed in site built single family homes; and b. of a similar ooling, and, if a heat pump, heating apaity; and 2. if inreased, would ertainly result in a onsiderable inrease in the usual ost of installation or would ertainly result in a signifiant loss in the utility of the produt to the onsumer; and. of a produt type that was available for purhase in the United States as of Deember 1, Standard Air. Air weighing lb/ft 3 [1.2 kg/m 3 ] whih approximates dry air at 70 F [21 C] and at a barometri pressure of in Hg [101.3 kpa] Tested Combination for Multiple-split air onditioners and heat pumps Tested ombination means a multi-split system with multiple indoor oils having the following features: The basi model of a system used as a tested ombination shall onsist of one outdoor unit, with one or more ompressors, that is mathed with between 2 and 5 indoor units; for multi-split systems, eah of these indoor units shall be designed for individual operation The indoor units shall: Represent the highest sales model family, or another indoor model family if the highest sales model family does not provide suffiient apaity (see ); Together, have a nominal ooling apaity that is between 95% and 105% of the nominal ooling apaity of the outdoor unit; Not, individually, have a apaity that is greater than 50% of the nominal apaity of the outdoor unit; Operate at fan speeds that are onsistent with the manufaturer's speifiations; and All be subjet to the same minimum external stati pressure requirement (i.e., 0 in H 2 O [0 Pa]) for non-duted, see Table 2 in Appendix M to Subpart B of this part for duted indoor units) while being onfigurable to produe the same stati pressure at the exit of eah outlet plenum when manifolded as per setion of Appendix M to Subpart B of Part 430 Uniform Test Method for Measuring the Energy Consumption of Central Air Conditioners and Heat Pumps Through-the-wall Air Conditioner and Heat Pump. A entral air onditioner or heat pump that is designed to be installed totally or partially within a fixed-size opening in an exterior wall, and: a. is manufatured prior to January 23, 2010; b. is not weatherized;. is learly and permanently marked for installation only through an exterior wall; d. has a rated ooling apaity no greater than 30,000 Btu/h [8,800 W]; e. exhanges all of its outdoor air aross a single surfae of the equipment abinet; and f. has a ombined outdoor air exhange area of less than 800 in 2 [0.516 m 2 ] (split systems) or less than 1,210 in 2 [ m 2 ] (single pakaged systems) as measured on the surfae desribed in 3.14.e. 3

11 ANSI/AHRI STANDARD 210/ Two-apaity (or Two-stage) Compressor. An air onditioner or heat pump that has one of the following: a. A two-speed ompressor, b. Two ompressors where only one ompressor ever operates at a time,. Two ompressors where one ompressor (Compressor #1) operates at low loads and both ompressors (Compressors #1 and #2) operate at high loads but Compressor #2 never operates alone, or d. A ompressor that is apable of ylinder or sroll unloading. For suh systems, low apaity means: a. Operating at low ompressor speed, b. Operating the lower apaity ompressor,. Operating Compressor #1, or d. Operating with the ompressor unloading (e.g., operating one piston of a two-piston reiproating ompressor, using a fixed frational volume of the full sroll, et.). For suh systems, high apaity means: a. Operating at high ompressor speed, b. Operating the higher apaity ompressor,. Operating Compressors #1 and #2, or d. Operating with the ompressor loaded (e.g., operating both pistons of a two-piston reiproating ompressor, using the full volume of the sroll) Unitary Air-Conditioner. One or more fatory-made assemblies whih normally inlude an evaporator or ooling oil(s), ompressor(s), and ondenser(s). Where suh equipment is provided in more than one assembly, the separated assemblies are to be designed to be used together, and the requirements of rating outlined in this standard are based upon the use of these assemblies in operation together Funtions. Either alone or in ombination with a heating plant, the funtions are to provide air-irulation, air leaning, ooling with ontrolled temperature and dehumidifiation, and may optionally inlude the funtion of heating and/or humidifying. Setion 4. Classifiations Equipment overed within the sope of this standard shall be lassified as shown in Tables 1 and 2. Setion 5. Test Requirements All Standard Ratings shall be verified by tests onduted in aordane with the test methods and proedures as desribed in this standard and its appendies. Air-ooled units shall be tested in aordane with ANSI/ASHRAE Standard 37 and with Appendies C and D. Water-ooled and evaporatively-ooled units shall be tested in aordane with ANSI/ASHRAE Standard 37. Setion 6. Rating Requirements 6.1 Standard Ratings. Standard Ratings shall be established at the Standard Rating Conditions speified in Air-ooled units shall be rated at onditions speified in Tables Water-ooled and evaporatively-ooled units shall be rated at onditions speified in Table 12. Standard Ratings relating to ooling or heating apaities shall be net values, inluding the effets of irulating-fan heat, but not inluding supplementary heat. Power input shall be the total power input to the ompressor(s) and fan(s), plus ontrols and other items required as part of the system for normal operation. Standard Ratings of units whih do not have indoor air-irulating fans furnished as part of the model, i.e., split systems with indoor oil alone, shall be established by subtrating from the total ooling apaity 1,250 Btu/h per 1,000 fm [775 W/m 3 /s], and by adding the same 4

12 ANSI/AHRI STANDARD 210/ amount to the heating apaity. Total power input for both heating and ooling shall be inreased by 365 W per 1,000 fm [226 W/m 3 /s] of indoor air irulated. Standard Ratings of water-ooled units shall inlude a total allowane for ooling tower fan motor and irulating water pump motor power inputs to be added in the amount of 10.0 W per 1,000 Btu/h [34.1 W per 1,000 W] ooling apaity Values of Standard Capaity Ratings. These ratings shall be expressed only in terms of Btu/h [W] as shown: Capaity Ratings, Multiples, Btu/h [W] Btu/h [W] < 20,000 [5,900] 100 [30] 20,000 and < 38,000 [5,900 up to 11,000] 200 [60] 38,000 and < 65, [150] [11,000 up to 19,000] Values of Measures of Energy Effiieny. Standard measures of energy effiieny, whenever published, shall be expressed in multiples of the nearest 0.05 Btu/(W h) for EER, SEER and HSPF, and in multiples of 0.1 for IEER. and in multiples of 0.1 for IPLV Standard Rating Tests. Tables 3-10 and 12 indiate the test and test onditions whih are required to determine values of standard apaity ratings and values of measures of energy effiieny. 5

13 ANSI/AHRI STANDARD 210/ Table 1. Classifiation of Unitary Air-Conditioners Types of Unitary Air-Conditioners Designation AHRI Type 1,2 Arrangement Single Pakage SP-A SP-E SP-W FAN EVAP COMP COND Year-Round Single Pakage SPY-A SPY-E SPY-W FAN HEAT EVAP COMP COND Remote Condenser RC-A RC-E RC-W FAN EVAP COND Year-Round Remote Condenser RCY-A RCY-E RCY-W FAN EVAP HEAT COND Condensing Unit, Coil Alone RCU-A-C RCU-E-C RCU-W-C EVAP COND COMP Condensing Unit, Coil And Blower RCU-A-CB RCU-E-CB RCU-W-CB FAN EVAP COND COMP Year-Round Condensing Unit, Coil and Blower Through-the-wall Air Conditioner Spae Constrained Produts Small-dut, High-veloity System Notes: RCUY-A-CB RCUY-E-CB RCUY-W-CB TTW-SP-A,E,W TTW-SPY-A,E,W TTW-RCU-A,E,W-C TTW-RCU-A,E,W-CB TTW-RCUY-A,E,W-CB SCP-SP-A,E,W SCP-SPY-A,E,W SCP-RCU-A,E,W-C SCP-RCU-A,E,W-CB SCP-RCUY-A,E,W-CB SDHV-SP-A,E,W SDHV-SPY-A,E,W SDHV-RCU-A,E,W-C SDHV-RCU-A,E,W-CB SDHV-RCUY-A,E,W-CB FAN EVAP COND HEAT COMP FAN COMP EVAP COND or FAN COMP EVAP COND or FAN COMP EVAP COND or FAN EVAP FAN EVAP FAN EVAP COND COMP COND COMP COND COMP 1 2 A suffix of "-O" following any of the above lassifiations indiates equipment not intended for use with field-installed dut systems ( ). A suffix of "-A" indiates air-ooled ondenser, "-E" indiates evaporatively-ooled ondenser and "-W" indiates water-ooled ondenser. 6

14 ANSI/AHRI STANDARD 210/ Table 2. Classifiation of Air-Soure Unitary Heat Pumps Types of Air-Soure Unitary Heat Pumps Designation AHRI Type 1 Arrangement Heating and Cooling Heating Only Single Pakage HSP-A HOSP-A FAN INDOOR COIL COMP OUTDOOR COIL Remote Outdoor Coil HRC-A-CB HORC-A-CB FAN INDOOR COIL COMP OUTDOOR COIL Remote Outdoor Coil With No Indoor Fan HRC-A-C HORC-A-C INDOOR COIL COMP OUTDOOR COIL Split System HRCU-A-CB HORCU-A-CB FAN COMP INDOOR COIL OUTDOOR COIL Split System With No Indoor Fan HRCU-A-C HORCU-A-C COMP INDOOR COIL OUTDOOR COIL Through-the-wall Heat Pump TTW-HSP-A TTW-HRCU-A-C TTW-HRCU-A-CB TTW-HOSP-A TTW-HORCU-A-C TTW-HORCU-A-CB FAN INDOOR COIL COMP OUTDOOR COIL or FAN INDOOR COIL COMP OUTDOOR COIL Spae Constrained Produts SCP-HSP-A SCP-HRCU-A-C SCP-HRCU-A-CB SCP-HOSP-A SCP-HORCU-A-C SCP-HORCU-A-CB FAN INDOOR COIL COMP OUTDOOR COIL or FAN INDOOR COIL COMP OUTDOOR COIL Small-dut, Highveloity System SDHV-HSP-A SDHV-HRCU-A-C SDHV-HRCU-A-CB SDHV-HOSP-A SDHV-HORCU-A-C SDHV-HORCU-A-CB FAN INDOOR COIL COMP OUTDOOR COIL or FAN INDOOR COIL COMP OUTDOOR COIL Note: 1 A suffix of "-O" following any of the above lassifiations indiates equipment not intended for use with field-installed dut systems ( ) Assigned Degradation Fator. In lieu of onduting C and D tests or the heating yling test, an assigned value of 0.25 may be used for either the ooling or heating Degradation Coeffiient, C D, or both. For units with two ompressor speeds, two ompressors or ylinder unloading, if the assigned C D is used for one ooling mode, it must be used for both ooling modes. If the assigned C D is used for one heating mode, it must be used for both heating modes Eletrial Conditions. Standard Rating tests shall be performed at the nameplate rated voltage(s) and frequeny. For air-ooled equipment whih is rated with V dual nameplate voltages, Standard Rating tests shall be performed at 230 V. For all other dual nameplate voltage equipment overed by this standard, the Standard Rating tests shall be performed at both voltages or at the lower of the two voltages if only a single Standard Rating is to be published. 7

15 ANSI/AHRI STANDARD 210/ Airflow Through The Indoor Coil Cooling Full-load Air Volume Rate Cooling Full-load Air Volume Rate for Duted Units. The manufaturer must speify the Cooling Full-load Air Volume Rate. Use this value as long as the following two requirements are satisfied. First, when onduting the A or A 2 test (exlusively), the measured air volume rate, when divided by the measured indoor air-side total ooling apaity, must not exeed 37.5 sfm per 1,000 Btu/h [0.06 m 3 /s per 1,000 W]. If this ratio is exeeded, redue the air volume rate until this ratio is equaled. Use this redued air volume rate for all tests that all for using the Cooling Full-load Air Volume Rate. The seond requirement is as follows: a. For all duted units tested with an indoor fan installed, exept those having a variablespeed, onstant-air-volume-rate indoor fan. The seond requirement applies exlusively to the A or A 2 Test and is met as follows. 1. Ahieve the Cooling Full-load Air Volume Rate, determined in aordane with the previous paragraph; 2. Measure the external stati pressure; 3. If this pressure is equal to or greater than the appliable minimum external stati pressure ited in Table 11, this seond requirement is satisfied. Use the urrent air volume rate for all tests that require the Cooling Full-load Air Volume Rate. 4. If the Table 11 minimum is not equaled or exeeded, 4a. redue the air volume rate until the appliable Table 11 minimum is equaled or 4b. until the measured air volume rate equals 95 perent of the air volume rate from step 1, whihever ours first. 5. If the onditions of step 4a our first, this seond requirement is satisfied. Use the step 4a redued air volume rate for all tests that require the Cooling Full-load Air Volume Rate. 6. If the onditions of step 4b our first, make an inremental hange to the set-up of the indoor fan (e.g., next highest fan motor pin setting, next highest fan motor speed) and repeat the evaluation proess beginning at above step 1. If the indoor fan set-up annot be further hanged, redue the air volume rate until the appliable Table 11 minimum is equaled. Use this redued air volume rate for all tests that require the Cooling Full-load Air Volume Rate. b. For duted units that are tested with a variable-speed, onstant-air-volume-rate indoor fan installed. For all tests that speify the ooling full-load air volume rate, obtain an external stati pressure as lose to (but not less than) the appliable Table 11 value that does not ause instability or an automati shutdown of the indoor blower.. For duted units that are tested without an indoor fan installed. For the A or A 2 test, (exlusively), the pressure drop aross the indoor oil assembly must not exeed 0.30 in H 2 O [75 Pa]. If this pressure drop is exeeded, redue the air volume rate until the measured pressure drop equals the speified maximum. Use this redued air volume rate for all tests that require the ooling full-load air volume rate Cooling Full-load Air Volume Rate for Non-duted Units. For non-duted units, the ooling full-load air volume rate is the air volume rate that results during eah test when the unit is operated at an external stati pressure of zero in H 2 O [0 Pa]. 8

16 ANSI/AHRI STANDARD 210/ Cooling Minimum Air Volume Rate. a. For duted units that regulate the speed (as opposed to the fm) of the indoor fan, Cooling Minimum Air Vol. Rate = Cooling Minimum Fan Speed Cooling Full - load Air Vol. Rate A Test Fan Speed 2 where ooling minimum fan speed orresponds to the fan speed used when operating at low ompressor apaity (two-apaity system), the fan speed used when operating at the minimum ompressor speed (variable-speed system), or the lowest fan speed used when ooling (single-speed ompressor and a variable-speed variable-air-volume-rate indoor fan). For suh systems, obtain the ooling minimum air volume rate regardless of the external stati pressure. b. For duted units that regulate the air volume rate provided by the indoor fan, the manufaturer must speify the ooling minimum air volume rate. For suh systems, ondut all tests that speify the ooling minimum air volume rate (i.e., the A 1, B 1, C 1, F 1, and G 1 tests) at an external stati pressure that does not ause instability or an automati shutdown of the indoor blower while being as lose to, but not less than, A, B, C, F, and G Test ΔP st st,a 2 Cooling Minimum Air Volume Rate = ΔP Cooling Full load Air Volume Rate 2 where ΔP is the appliable Table 11 minimum external stati pressure that was targeted during the A 2 st,a 2 (and B 2 ) test.. For duted two-apaity units that are tested without an indoor fan installed, the ooling minimum air volume rate is the higher of (1) the rate speified by the manufaturer or (2) 75 perent of the ooling fullload air volume rate. During the laboratory tests on a oil-only (fanless) unit, obtain this ooling minimum air volume rate regardless of the pressure drop aross the indoor oil assembly. d. For non-duted units, the ooling minimum air volume rate is the air volume rate that results during eah test when the unit operates at an external stati pressure of zero in H 2 O [0 Pa] and at the indoor fan setting used at low ompressor apaity (two-apaity system) or minimum ompressor speed (variable-speed system). For units having a single-speed ompressor and a variable-speed variable-air-volume-rate indoor fan, use the lowest fan setting allowed for ooling Cooling Intermediate Air Volume Rate. a. For duted units that regulate the speed of the indoor fan, E Test Fan Speed V Cooling Intermediate Air Volume Rate = Cooling Full load Air Volume Rate A Test Fan Speed For suh units, obtain the ooling intermediate air volume rate regardless of the external stati pressure. b. For duted units that regulate the air volume rate provided by the indoor fan, the manufaturer must speify the ooling intermediate air volume rate. For suh systems, ondut the E V test at an external stati pressure that does not ause instability or an automati shutdown of the indoor blower while being as lose to, but not less than, 2 E V Test ΔP st,a 2 Cooling Intermediate Air Volume Rate Cooling Full load Air Volume Rate 2 9

17 ANSI/AHRI STANDARD 210/ where ΔP is the appliable Table 11 minimum external stati pressure that was targeted during the A 2 st,a 2 (and B 2 ) test.. For non-duted units, the ooling intermediate air volume rate is the air volume rate that results when the unit operates at an external stati pressure of zero in H 2 O [0 Pa] and at the fan speed seleted by the ontrols of the unit for the E V test onditions Heating Full-load Air Volume Rate Duted Heat Pumps Where the Heating and Cooling Full-load Air Volume Rates Are the Same. a. Use the ooling full-load air volume rate as the heating full-load air volume rate for: 1. Duted heat pumps that operate at the same indoor fan speed during both the A (or A 2 ) and the H1 (or H1 2 ) tests; 2. Duted heat pumps that regulate fan speed to deliver the same onstant air volume rate during both the A (or A 2 ) and the H1 (or H1 2 ) tests; and 3. Duted heat pumps that are tested without an indoor fan installed (exept two-apaity northern heat pumps that are tested only at low apaity ooling - see ). b. For heat pumps that meet the above riteria 1 and 3, no minimum requirements apply to the measured external or internal, respetively, stati pressure. For heat pumps that meet the above riterion 2, test at an external stati pressure that does not ause instability or an automati shutdown of the indoor blower while being as lose to, but not less than, the same Table 11 minimum external stati pressure as was speified for the A (or A 2 ) ooling mode test Duted Heat Pumps Where the Heating and Cooling Full-load Air Volume Rates Are Different Due To Indoor Fan Operation. a. For duted heat pumps that regulate the speed (as opposed to the fm) of the indoor fan, Heating Full load Air Volume Rate = H1 or H1 Test Fan Speed 2 Cooling Full load Air Volume Rate A or A Test Fan Speed 2 For suh heat pumps, obtain the heating full-load air volume rate without regard to the external stati pressure. b. For duted heat pumps that regulate the air volume rate delivered by the indoor fan, the manufaturer must speify the heating full-load air volume rate. For suh heat pumps, ondut all tests that speify the heating full-load air volume rate at an external stati pressure that does not ause instability or an automati shutdown of the indoor blower while being as lose to, but not less than, Heating Air Volume Rate Heating Full load ΔP = Cooling Full Load ΔP st st Cooling Air Volume Rate where the ooling full-load ΔP st,h1 2 is the appliable Table 11 minimum external stati pressure that was speified for the A or A 2 test When testing duted, two-apaity northern heat pumps (see Definition 1.46 of Appendix C), use the appropriate approah of the above two ases for units that are tested with an indoor fan installed. For oil-only (fanless) northern heat pumps, the heating full-load air volume rate is

18 ANSI/AHRI STANDARD 210/ the lesser of the rate speified by the manufaturer or 133 perent of the ooling full-load air volume rate. For this latter ase, obtain the heating full-load air volume rate regardless of the pressure drop aross the indoor oil assembly Duted Heating-Only Heat Pumps. The manufaturer must speify the heating full-load air volume rate. a. For all duted heating-only heat pumps tested with an indoor fan installed, exept those having a variable-speed, onstant-air-volume-rate indoor fan. Condut the following steps only during the first test, the H1 or H1 2 Test. 1. Ahieve the Heating Full-load Air Volume Rate. 2. Measure the external stati pressure. 3. If this pressure is equal to or greater than the Table 11 minimum external stati pressure that applies given the heating-only heat pump s rated heating apaity, use the urrent air volume rate for all tests that require the Heating Full-load Air Volume Rate. 4. If the Table 11 minimum is not equaled or exeeded, 4a. redue the air volume rate until the appliable Table11 minimum is equaled or 4b. until the measured air volume rate equals 95 perent of the manufaturer-speified Fullload Air Volume Rate, whihever ours first. 5. If the onditions of step 4a ours first, use the step 4a redued air volume rate for all tests that require the Heating Full-load Air Volume Rate. 6. If the onditions of step 4b our first, make an inremental hange to the set-up of the indoor fan (e.g., next highest fan motor pin setting, next highest fan motor speed) and repeat the evaluation proess beginning at above step 1. If the indoor fan set-up annot be further hanged, redue the air volume rate until the appliable Table 11 minimum is equaled. Use this redued air volume rate for all tests that require the Heating Full-load Air Volume Rate. b. For duted heating-only heat pumps that are tested with a variable-speed, onstant-air-volumerate indoor fan installed. For all tests that speify the heating full load air volume rate, obtain an external stati pressure that does not ause instability or an automati shutdown of the indoor blower while being as lose to, but not less than, the appliable Table 11 minimum.. For duted heating-only heat pumps that are tested without an indoor fan installed. For the H1 or H1 2 test, (exlusively), the pressure drop aross the indoor oil assembly must not exeed 0.30 in H 2 O [75 Pa]. If this pressure drop is exeeded, redue the air volume rate until the measured pressure drop equals the speified maximum. Use this redued air volume rate for all tests that require the heating full-load air volume rate Non-duted Heat Pumps, Inluding Non-duted Heating-only Heat Pumps. For non-duted heat pumps, the heating full-load air volume rate is the air volume rate that results during eah test when the unit operates at an external stati pressure of 0 in H 2 O [0 Pa] Heating Minimum Air Volume Rate. a. For duted heat pumps that regulate the speed (as opposed to the airflow) of the indoor fan, 11

19 ANSI/AHRI STANDARD 210/ Heating Minimum Air Volume Rate = Heating Minimum Fan Speed Heating Full load Air Volume Rate H1 Test Fan Speed 2 where heating minimum fan speed orresponds to the fan speed used when operating at low ompressor apaity (two-apaity system), the lowest fan speed used at any time when operating at the minimum ompressor speed (variable-speed system), or the lowest fan speed used when heating (single-speed ompressor and a variable-speed variable-air-volume-rate indoor fan). For suh heat pumps, obtain the heating minimum air volume rate without regard to the external stati pressure. b. For duted heat pumps that regulate the air volume rate delivered by the indoor fan, the manufaturer must speify the heating minimum air volume rate. For suh heat pumps, ondut all tests that speify the heating minimum air volume rate (i.e., the H0 1, H1 1, H2 1, and H3 1 tests) at an external stati pressure that does not ause instability or an automati shutdown of the indoor blower while being as lose to, but not less than, Heating Minimum Air Volume Rate H0,H1,H2,H3 Test P st,h1 2 Heating Full load Air Volume Rate 2 where ΔP is the minimum external stati pressure that was targeted during the H1 2 test. st,h1 2. For duted two-apaity northern heat pumps that are tested with an indoor fan installed, use the appropriate approah of the above two ases. d. For duted two-apaity heat pumps that are tested without an indoor fan installed, use the ooling minimum air volume rate as the heating minimum air volume rate. For duted twoapaity northern heat pumps that are tested without an indoor fan installed, use the ooling fullload air volume rate as the heating minimum air volume rate. For duted two-apaity heatingonly heat pumps that are tested without an indoor fan installed, the heating minimum air volume rate is the higher of the rate speified by the manufaturer or 75 perent of the heating full-load air volume rate. During the laboratory tests on a oil-only (fanless) unit, obtain the heating minimum air volume rate without regard to the pressure drop aross the indoor oil assembly. e. For non-duted heat pumps, the heating minimum air volume rate is the air volume rate that results during eah test when the unit operates at an external stati pressure of 0 in H 2 O [0 Pa] and at the indoor fan setting used at low ompressor apaity (two-apaity system) or minimum ompressor speed (variable-speed system). For units having a single-speed ompressor and a variable-speed, variable-air-volume-rate indoor fan, use the lowest fan setting allowed for heating Heating Intermediate Air Volume Rate. a. For duted heat pumps that regulate the speed of the indoor fan, Heating Intermediate Air Volume Rate = Heating Full load H2 Test Fan Speed V Air Volume Rate H1 Test Fan Speed 2 For suh heat pumps, obtain the heating intermediate air volume rate without regard to the external stati pressure. 12 b. For duted heat pumps that regulate the air volume rate delivered by the indoor fan, the manufaturer must speify the heating intermediate air volume rate. For suh heat pumps, ondut the H2 V test at an external stati pressure that does not ause instability or an automati

20 ANSI/AHRI STANDARD 210/ shutdown of the indoor blower while being as lose to, but not less than, H2 Test ΔP = V st, H1 2 Heating Intermediate Air Volume Rate Heating Full load Air Volume Rate 2 where ΔP is the minimum external stati pressure that was speified for the H1 2 test. st, H1 2. For non-duted heat pumps, the heating intermediate air volume rate is the air volume rate that results when the heat pump operates at an external stati pressure of zero in H 2 O [0 Pa] and at the fan speed seleted by the ontrols of the unit for the H2 V test onditions Heating Nominal Air Volume Rate. Exept for the noted hanges, determine the heating nominal air volume rate using the approah desribed in setion Required hanges inlude substituting H1 N test for H2 V test within the first setion equation, substituting H1 N test ΔP st for H2 V test ΔP st in the seond setion equation, substituting H1 N test for eah H2 V test, and substituting heating nominal air volume rate for eah heating intermediate air volume rate. Heating Nominal Air Volume Rate = H1 Test Fan Speed N Heating Air Volume Rate H1 Test Fan Speed 2 H1 Test ΔP = ΔP N st st,h1 2 Heating Nominal Air Volume Rate Heating Full load Air Volume Rate Outdoor-Coil Airflow Rate. All Standard Ratings shall be determined at the outdoor-oil airflow rate speified by the manufaturer where the fan drive is adjustable. Where the fan drive is non-adjustable, they shall be determined at the outdoor-oil airflow rate inherent in the equipment when operated with all of the resistane elements assoiated with inlets, louvers, and any dutwork and attahments onsidered by the manufaturer as normal installation pratie. One established, the outdoor oil air iruit of the equipment shall remain unhanged throughout all tests presribed herein Requirements For Separated Assemblies. All Standard Ratings for equipment in whih the outdoor setion is separated from the indoor setion, as in Types RC, RCY, RCU, RCUY, HRC, HORC, HRCU and HORCU (shown in Setion 4), shall be determined with at least 25 ft [7.6 m] of interonnetion tubing on eah line of the size reommended by the manufaturer. Suh equipment in whih the interonnetion tubing is furnished as an integral part of the mahine not reommended for utting to length shall be tested with the omplete length of tubing furnished, or with 25 ft [7.6 m] of tubing, whihever is greater. At least 10 ft [3.0 m] of the interonnetion tubing shall be exposed to the outside onditions. The line sizes, insulation, and details of installation shall be in aordane with the manufaturer s published reommendation Conditions For Standard Rating Tests Cooling Mode Tests For A Unit Having A Single-speed Compressor That Is Tested With A Fixedspeed Indoor Fan Installed, With A Constant-air-volume-rate Indoor Fan Installed, Or With No Indoor Fan Installed. Condut two steady-state wet oil tests, the A and B tests. Use the two optional dry-oil tests, the steady-state C test and the yli D test, to determine the ooling mode yli degradation oeffiient, C. If the two optional tests are not onduted, assign C the D default value of Table 3 speifies test onditions for these four tests. D 13

21 ANSI/AHRI STANDARD 210/ Table 3. Cooling Mode Test Conditions for Units Having a Single-Speed Compressor and a Fixed-Speed Indoor Fan, a Constant Air Volume Rate Indoor Fan, or No Indoor Fan Test Desription A Test required (steady, wet oil) B Test required (steady, wet oil) C Test optional (steady, dry oil) D Test optional (yli, dry oil) Notes: Air Entering Indoor Unit Temperature Dry-Bulb Wet-Bulb F C F C Air Entering Outdoor Unit Temperature Dry-Bulb Wet-Bulb F C F C Cooling Air Volume Rate (1) 23.9 (1) Cooling Fullload (2) (1) 18.3 (1) Cooling Fullload (2) (3) (3) Cooling Fullload (2) (4) (1) (2) (3) (4) The speified test ondition only applies if the unit rejets ondensate to the outdoor oil. Defined in setion The entering air must have a low enough moisture ontent so no ondensate forms on the indoor oil. (It is reommended that an indoor wet-bulb temperature of 57.0 F [13.9 C] or less be used.) Maintain the airflow nozzles stati pressure differene or veloity pressure during the ON period at the same pressure differene or veloity pressure as measured during the C Test Heating Mode Tests For A Heat Pump Having A Single-speed Compressor That Is Tested With A Fixed Speed Indoor Fan Installed, With A Constant-air-volume-rate Indoor Fan Installed, Or With No Indoor Fan Installed. Condut three tests: the high temperature (H1) test, the frost aumulation (H2) test, and the low temperature (H3) test. Condut the optional high temperature yli (H1C) test to determine h h the heating mode yli degradation oeffiient, C. If this optional test is not onduted, assign C the D D default value of Test onditions for these four tests are speified in Table 4. Table 4. Heating Mode Test Conditions for Units Having a Single-Speed Compressor and a Fixed-Speed Indoor Fan, a Constant Air Volume Rate Indoor Fan, or No Indoor Fan Test Desription H1 Test (required, steady) H1C Test (optional, yli) H2 Test (required) H3 Test (required, steady) Notes: Air Entering Indoor Unit Temperature Dry-Bulb Wet-Bulb F C F C Air Entering Outdoor Unit Temperature Dry-Bulb Wet-Bulb F C F C (max) 15.6 (max) (max) 15.6 (max) (max) 15.6 (max) (max) 15.6 (max) Heating Air Volume Rate Heating Fullload (1) (2) Heating Fullload (1) Heating Fullload (1) (1) (2) Defined in setion Maintain the airflow nozzles stati pressure differene or veloity pressure during the ON period at the same pressure differene or veloity pressure as measured during the H1 Test. 14

22 ANSI/AHRI STANDARD 210/ Cooling Mode Tests For A Unit Having A Single-speed Compressor And A Variable-speed Variable-air-volume-rate Indoor Fan Installed Indoor Fan Capaity Modulation That Correlates With The Outdoor Dry Bulb Temperature. Condut four steady-state wet oil tests: the A 2, A 1, B 2, and B 1 tests. Use the two optional dry-oil tests, the steady-state C 1 test and the yli D 1 test, to determine the ooling mode yli degradation oeffiient, C. If the two optional tests are not onduted, assign C the default value of Table 5 speifies test onditions for these six tests. D Indoor Fan Capaity Modulation Based On Adjusting The Sensible To Total (S/T) Cooling Capaity Ratio. The testing requirements are the same as speified in setion and Table 3. Use a ooling air volume rate that represents a normal residential installation. If performed, ondut the steady-state C test and the yli D test with the unit operating in the same S/T apaity ontrol mode as used for the B test. D Table 5. Cooling Mode Test Conditions for Units Having a Single-Speed Compressor and a Variable Air Volume Rate Indoor Fan that Correlates with the Outdoor Dry Bulb Temperature (Setion ) Test Desription A 2 Test - required (steady, wet oil) A 1 Test - required (steady, wet oil) B 2 Test - required (steady, wet oil) B 1 Test - required (steady, wet oil) C 1 Test (4) - optional (steady, dry oil) D 1 Test (4) - optional (yli, dry oil) Notes: Air Entering Indoor Unit Temperature Air Entering Outdoor Unit Temperature Cooling Air Dry-Bulb Wet-Bulb Dry-Bulb Wet-Bulb Volume Rate F C F C F C F C (1) 23.9 (1) Cooling Fullload (1) 23.9 (1) Cooling Minimum (3) (1) 18.3 (1) Cooling Fullload (2) (1) 18.3 (1) Cooling Minimum (3) (4) Cooling Minimum (3) (4) (5) (1) (2) (3) (4) (5) The speified test ondition only applies if the unit rejets ondensate to the outdoor oil. Defined in setion Defined in setion The entering air must have a low enough moisture ontent so no ondensate forms on the indoor oil. (It is reommended that an indoor wet-bulb temperature of 57.0 F [13.9 C] or less be used.) Maintain the airflow nozzles stati pressure differene or veloity pressure during the ON period at the same pressure differene or veloity pressure as measured during the C 1 Test Heating Mode Tests For A Heat Pump Having A Single-speed Compressor And A Variable-speed, Variable-air-volume-rate Indoor Fan: Capaity Modulation Correlates With Outdoor Dry Bulb Temperature. Condut five tests: two high temperature tests (H1 2 and H1 1 ), one frost aumulation test (H2 2 ), and two low temperature tests (H3 2 and H3 1 ). Conduting an additional frost aumulation test (H2 1 ) is optional. Condut the optional high temperature yli (H1C 1 ) test to determine the heating mode h h yli degradation oeffiient, C. If this optional test is not onduted, assign C the default value of D Table 6 speifies test onditions for these seven tests. If the optional H2 1 test is not done, use the equations in setion of Appendix C to approximate the apaity and eletrial power of the heat pump at the H2 1 test onditions: D 15

23 ANSI/AHRI STANDARD 210/ Test Desription H1 2 Test (required, steady) H1 1 Test (required, steady) H1C 1 Test (optional, yli) H2 2 Test (required) H2 1 Test (optional) H3 2 Test (required, steady) H3 1 Test (required, steady) Notes: Table 6. Heating Mode Test Conditions for Units Having a Single-Speed Compressor and a Variable Air Volume Rate Indoor Fan Air Entering Indoor Unit Temperature Dry-Bulb Wet-Bulb F C F C Air Entering Outdoor Unit Temperature Dry-Bulb Wet-Bulb F C F C (max) 15.6 (max) (max) 15.6 (max) (max) 15.6 (max) (max) 15.6 (max) (max) 15.6 (max) (max) 15.6 (max) (max) 15.6 (max) Heating Air Volume Rate Heating Fullload (1) Heating Minimum (2) (3) Heating Fullload (1) Heating Minimum (2) Heating Fullload (1) Heating Minimum (2) (1) (2) (3) Defined in setion Defined in setion Maintain the airflow nozzles stati pressure differene or veloity pressure during the ON period at the same pressure differene or veloity pressure as measured during the H1 1 Test Cooling Mode Tests For A Unit Having A Two-apaity Compressor. (See Definition 1.45 in Appendix C.) a. Condut four steady-state wet oil tests: the A 2, F 1, B 2, and B 1 tests. Use the two optional dry-oil tests, the steady-state C 1 test and the yli D 1 test, to determine the ooling mode yli degradation oeffiient, C. If the two optional tests are not onduted, assign C the default value of Table 7 speifies test onditions for these six tests. D b. For units having a variable speed indoor fan that is modulated to adjust the sensible to total (S/T) ooling apaity ratio, use ooling and ooling minimum air volume rates that represent a normal residential installation. Additionally, if onduting the optional dryoil tests, operate the unit in the same S/T apaity ontrol mode as used for the B 1 test.. Test two-apaity, northern heat pumps (see Definition 1.46 of Appendix C) in the same way as a single speed heat pump with the unit operating exlusively at low ompressor apaity (see setion and Table 3). d. If a two-apaity air onditioner or heat pump loks out low apaity operation at outdoor temperatures that are less than 95.0 F [35.0 C], ondut the F 1 test using the outdoor temperature onditions listed for the F 1 test in Table 9 rather than using the outdoor temperature onditions listed in Table 7 for the F 1 test. D 16

2007 Standard for Performance Rating of Commercial and Industrial Unitary Air- Conditioning and Heat Pump Equipment

2007 Standard for Performance Rating of Commercial and Industrial Unitary Air- Conditioning and Heat Pump Equipment ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2 (Formerly ARI Standard 340/360-2007) 2007 Standard for Performance Rating of Commercial and Industrial Unitary Air- Conditioning and Heat Pump Equipment

More information

Computational Analysis of Two Arrangements of a Central Ground-Source Heat Pump System for Residential Buildings

Computational Analysis of Two Arrangements of a Central Ground-Source Heat Pump System for Residential Buildings Computational Analysis of Two Arrangements of a Central Ground-Soure Heat Pump System for Residential Buildings Abstrat Ehab Foda, Ala Hasan, Kai Sirén Helsinki University of Tehnology, HVAC Tehnology,

More information

Performance Rating of Room Fan- Coils

Performance Rating of Room Fan- Coils ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS

More information

AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps

AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled

More information

HVAC Efficiency Definitions

HVAC Efficiency Definitions HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the

More information

ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment. Partner Commitments.

ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment. Partner Commitments. ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment Partner Commitments Commitment The following are the terms of the ENERGY STAR Partnership

More information

protection p1ann1ng report

protection p1ann1ng report f1re~~ protetion p1ann1ng report BUILDING CONSTRUCTION INFORMATION FROM THE CONCRETE AND MASONRY INDUSTRIES Signifiane of Fire Ratings for Building Constrution NO. 3 OF A SERIES The use of fire-resistive

More information

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units 2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not

More information

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005 KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed

More information

Technical Data Manual Model Nos. and pricing: see Price List

Technical Data Manual Model Nos. and pricing: see Price List Tehnial Data Manual Model Nos. and priing: see Prie List Vitoell 100-V CVAA and CVA Series Indiret-fired domesti hot water storage tank 42 USG to 119 USG (160 L to 450 L) apaity Indiret-fired domesti hot

More information

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not

More information

Measurement of Powder Flow Properties that relate to Gravity Flow Behaviour through Industrial Processing Lines

Measurement of Powder Flow Properties that relate to Gravity Flow Behaviour through Industrial Processing Lines Measurement of Powder Flow Properties that relate to Gravity Flow ehaviour through Industrial Proessing Lines A typial industrial powder proessing line will inlude several storage vessels (e.g. bins, bunkers,

More information

Electrician'sMathand BasicElectricalFormulas

Electrician'sMathand BasicElectricalFormulas Eletriian'sMathand BasiEletrialFormulas MikeHoltEnterprises,In. 1.888.NEC.CODE www.mikeholt.om Introdution Introdution This PDF is a free resoure from Mike Holt Enterprises, In. It s Unit 1 from the Eletrial

More information

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

More information

State of Maryland Participation Agreement for Pre-Tax and Roth Retirement Savings Accounts

State of Maryland Participation Agreement for Pre-Tax and Roth Retirement Savings Accounts State of Maryland Partiipation Agreement for Pre-Tax and Roth Retirement Savings Aounts DC-4531 (08/2015) For help, please all 1-800-966-6355 www.marylandd.om 1 Things to Remember Complete all of the setions

More information

HEAT EXCHANGERS-2. Associate Professor. IIT Delhi E-mail: prabal@mech.iitd.ac.in. P.Talukdar/ Mech-IITD

HEAT EXCHANGERS-2. Associate Professor. IIT Delhi E-mail: prabal@mech.iitd.ac.in. P.Talukdar/ Mech-IITD HEA EXHANGERS-2 Prabal alukdar Assoiate Professor Department of Mehanial Engineering II Delhi E-mail: prabal@meh.iitd.a.in Multipass and rossflow he subsripts 1 and 2 represent the inlet and outlet, respetively..

More information

Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps

Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Jon Winkler, Ph.D. September 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the

More information

INCOME TAX WITHHOLDING GUIDE FOR EMPLOYERS

INCOME TAX WITHHOLDING GUIDE FOR EMPLOYERS Virginia Department of Taxation INCOME TAX WITHHOLDING GUIDE FOR EMPLOYERS www.tax.virginia.gov 2614086 Rev. 07/14 * Table of Contents Introdution... 1 Important... 1 Where to Get Assistane... 1 Online

More information

THE PERFORMANCE OF TRANSIT TIME FLOWMETERS IN HEATED GAS MIXTURES

THE PERFORMANCE OF TRANSIT TIME FLOWMETERS IN HEATED GAS MIXTURES Proeedings of FEDSM 98 998 ASME Fluids Engineering Division Summer Meeting June 2-25, 998 Washington DC FEDSM98-529 THE PERFORMANCE OF TRANSIT TIME FLOWMETERS IN HEATED GAS MIXTURES John D. Wright Proess

More information

i e AT 8 of 1938 THE PERSONAL INJURIES (EMERGENCY PROVISIONS) ACT 1939

i e AT 8 of 1938 THE PERSONAL INJURIES (EMERGENCY PROVISIONS) ACT 1939 i e AT 8 of 1938 THE PERSONAL INJURIES (EMERGENCY PROVISIONS) ACT 1939 The Personal Injuries (Emergeny Provisions) At 1939 Index i e THE PERSONAL INJURIES (EMERGENCY PROVISIONS) ACT 1939 Index Setion

More information

INCOME TAX WITHHOLDING GUIDE FOR EMPLOYERS

INCOME TAX WITHHOLDING GUIDE FOR EMPLOYERS Virginia Department of Taxation INCOME TAX WITHHOLDING GUIDE FOR EMPLOYERS www.tax.virginia.gov 2614086 Rev. 01/16 Table of Contents Introdution... 1 Important... 1 Where to Get Assistane... 1 Online File

More information

Schedule 3(A) Room Air Conditioners

Schedule 3(A) Room Air Conditioners Schedule 3(A) Room Air Conditioners Revision : 1 Date : 21/08/15 1. Scope 1.1 This Standard specifies the energy labeling requirements for single-phase split air conditioners of the vapour compression

More information

A Three-Hybrid Treatment Method of the Compressor's Characteristic Line in Performance Prediction of Power Systems

A Three-Hybrid Treatment Method of the Compressor's Characteristic Line in Performance Prediction of Power Systems A Three-Hybrid Treatment Method of the Compressor's Charateristi Line in Performane Predition of Power Systems A Three-Hybrid Treatment Method of the Compressor's Charateristi Line in Performane Predition

More information

Table of Contents. Appendix II Application Checklist. Export Finance Program Working Capital Financing...7

Table of Contents. Appendix II Application Checklist. Export Finance Program Working Capital Financing...7 Export Finane Program Guidelines Table of Contents Setion I General...........................................................1 A. Introdution............................................................1

More information

i e AT 1 of 2012 DEBT RECOVERY AND ENFORCEMENT ACT 2012

i e AT 1 of 2012 DEBT RECOVERY AND ENFORCEMENT ACT 2012 i e AT 1 of 2012 DEBT RECOVERY AND ENFORCEMENT ACT 2012 Debt Reovery and Enforement At 2012 Index i e DEBT RECOVERY AND ENFORCEMENT ACT 2012 Index Setion Page PART 1 INTRODUCTORY 5 1 Short title... 5

More information

Disability Discrimination (Services and Premises) Regulations 2016 Index DISABILITY DISCRIMINATION (SERVICES AND PREMISES) REGULATIONS 2016

Disability Discrimination (Services and Premises) Regulations 2016 Index DISABILITY DISCRIMINATION (SERVICES AND PREMISES) REGULATIONS 2016 Disability Disrimination (Servies and Premises) Regulations 2016 Index DISABILITY DISCRIMINATION (SERVICES AND PREMISES) REGULATIONS 2016 Index Regulation Page 1 Title... 3 2 Commenement... 3 3 Interpretation...

More information

An integrated optimization model of a Closed- Loop Supply Chain under uncertainty

An integrated optimization model of a Closed- Loop Supply Chain under uncertainty ISSN 1816-6075 (Print), 1818-0523 (Online) Journal of System and Management Sienes Vol. 2 (2012) No. 3, pp. 9-17 An integrated optimization model of a Closed- Loop Supply Chain under unertainty Xiaoxia

More information

F220 Series. Installation Instructions. Photoelectric Smoke/Heat Detectors

F220 Series. Installation Instructions. Photoelectric Smoke/Heat Detectors F0 Series EN Installation Instrutions Photoeletri Smoke/Heat Detetors F0 Series Installation Instrutions.0 General Information EN.0 General Information. F0-B6 Series Bases Use with the F0 Series Heat and

More information

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS SASO XXXX:2016 (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS PERFORMANCE REQUIREMENTS AND METHODS OF TESTING 1 LARGE CAPACITY AIR CONDITIONERS

More information

A novel active mass damper for vibration control of bridges

A novel active mass damper for vibration control of bridges IABMAS 08, International Conferene on Bridge Maintenane, Safety and Management, 3-7 July 008, Seoul, Korea A novel ative mass damper for vibration ontrol of bridges U. Starossek & J. Sheller Strutural

More information

Findings and Recommendations

Findings and Recommendations Contrating Methods and Administration Findings and Reommendations Finding 9-1 ESD did not utilize a formal written pre-qualifiations proess for seleting experiened design onsultants. ESD hose onsultants

More information

Capacity at Unsignalized Two-Stage Priority Intersections

Capacity at Unsignalized Two-Stage Priority Intersections Capaity at Unsignalized Two-Stage Priority Intersetions by Werner Brilon and Ning Wu Abstrat The subjet of this paper is the apaity of minor-street traffi movements aross major divided four-lane roadways

More information

Annual Return/Report of Employee Benefit Plan

Annual Return/Report of Employee Benefit Plan Form 5500 Department of the Treasury Internal Revenue Servie Department of Labor Employee Benefits Seurity Administration Pension Benefit Guaranty Corporation Annual Return/Report of Employee Benefit Plan

More information

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory

More information

i e AT 21 of 2006 EMPLOYMENT ACT 2006

i e AT 21 of 2006 EMPLOYMENT ACT 2006 i e AT 21 of 2006 EMPLOYMENT ACT 2006 Employment At 2006 Index i e EMPLOYMENT ACT 2006 Index Setion Page PART I DISCRIMINATION AT RECRUITMENT ON TRADE UNION GROUNDS 9 1 Refusal of employment on grounds

More information

Chapter 1 Microeconomics of Consumer Theory

Chapter 1 Microeconomics of Consumer Theory Chapter 1 Miroeonomis of Consumer Theory The two broad ategories of deision-makers in an eonomy are onsumers and firms. Eah individual in eah of these groups makes its deisions in order to ahieve some

More information

ANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals

ANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals ANSI/AHRI Standard 880 (I-P) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:

More information

Neural network-based Load Balancing and Reactive Power Control by Static VAR Compensator

Neural network-based Load Balancing and Reactive Power Control by Static VAR Compensator nternational Journal of Computer and Eletrial Engineering, Vol. 1, No. 1, April 2009 Neural network-based Load Balaning and Reative Power Control by Stati VAR Compensator smail K. Said and Marouf Pirouti

More information

Deadline-based Escalation in Process-Aware Information Systems

Deadline-based Escalation in Process-Aware Information Systems Deadline-based Esalation in Proess-Aware Information Systems Wil M.P. van der Aalst 1,2, Mihael Rosemann 2, Marlon Dumas 2 1 Department of Tehnology Management Eindhoven University of Tehnology, The Netherlands

More information

A Keyword Filters Method for Spam via Maximum Independent Sets

A Keyword Filters Method for Spam via Maximum Independent Sets Vol. 7, No. 3, May, 213 A Keyword Filters Method for Spam via Maximum Independent Sets HaiLong Wang 1, FanJun Meng 1, HaiPeng Jia 2, JinHong Cheng 3 and Jiong Xie 3 1 Inner Mongolia Normal University 2

More information

In order to be able to design beams, we need both moments and shears. 1. Moment a) From direct design method or equivalent frame method

In order to be able to design beams, we need both moments and shears. 1. Moment a) From direct design method or equivalent frame method BEAM DESIGN In order to be able to design beams, we need both moments and shears. 1. Moment a) From diret design method or equivalent frame method b) From loads applied diretly to beams inluding beam weight

More information

' R ATIONAL. :::~i:. :'.:::::: RETENTION ':: Compliance with the way you work PRODUCT BRIEF

' R ATIONAL. :::~i:. :'.:::::: RETENTION ':: Compliance with the way you work PRODUCT BRIEF ' R :::i:. ATIONAL :'.:::::: RETENTION ':: Compliane with the way you work, PRODUCT BRIEF In-plae Management of Unstrutured Data The explosion of unstrutured data ombined with new laws and regulations

More information

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16. The following exerpt are pages from the North Amerian Produt Tehnial Guide, Volume 2: Anhor Fastening, Edition 16. Please refer to the publiation in its entirety for omplete details on this produt inluding

More information

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,

More information

HEAT CONDUCTION. q A q T

HEAT CONDUCTION. q A q T HEAT CONDUCTION When a temperature gradient eist in a material, heat flows from the high temperature region to the low temperature region. The heat transfer mehanism is referred to as ondution and the

More information

i e SD No. 2016/0058 HARBOUR DUES (MERCHANT VESSELS) REGULATIONS 2016

i e SD No. 2016/0058 HARBOUR DUES (MERCHANT VESSELS) REGULATIONS 2016 i e SD No. 2016/0058 HARBOUR DUES (MERCHANT VESSELS) REGULATIONS 2016 Harbour Dues (Merhant Vessels) Regulations 2016 Index HARBOUR DUES (MERCHANT VESSELS) REGULATIONS 2016 Index Regulation Page 1 Title...

More information

WATER CLOSET SUPPORTS TECHNICAL DATA

WATER CLOSET SUPPORTS TECHNICAL DATA WATER CLOSET SUPPORTS TECHNICAL DATA Smith engineers have developed an unusually omplete line of fixture supports for mounting all types of "off the floor" fixtures. Supports have been designed for water

More information

Open and Extensible Business Process Simulator

Open and Extensible Business Process Simulator UNIVERSITY OF TARTU FACULTY OF MATHEMATICS AND COMPUTER SCIENCE Institute of Computer Siene Karl Blum Open and Extensible Business Proess Simulator Master Thesis (30 EAP) Supervisors: Luiano Garía-Bañuelos,

More information

FOOD FOR THOUGHT Topical Insights from our Subject Matter Experts

FOOD FOR THOUGHT Topical Insights from our Subject Matter Experts FOOD FOR THOUGHT Topial Insights from our Sujet Matter Experts DEGREE OF DIFFERENCE TESTING: AN ALTERNATIVE TO TRADITIONAL APPROACHES The NFL White Paper Series Volume 14, June 2014 Overview Differene

More information

Supply chain coordination; A Game Theory approach

Supply chain coordination; A Game Theory approach aepted for publiation in the journal "Engineering Appliations of Artifiial Intelligene" 2008 upply hain oordination; A Game Theory approah Jean-Claude Hennet x and Yasemin Arda xx x LI CNR-UMR 668 Université

More information

Hierarchical Clustering and Sampling Techniques for Network Monitoring

Hierarchical Clustering and Sampling Techniques for Network Monitoring S. Sindhuja Hierarhial Clustering and Sampling Tehniques for etwork Monitoring S. Sindhuja ME ABSTRACT: etwork monitoring appliations are used to monitor network traffi flows. Clustering tehniques are

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

A Holistic Method for Selecting Web Services in Design of Composite Applications

A Holistic Method for Selecting Web Services in Design of Composite Applications A Holisti Method for Seleting Web Servies in Design of Composite Appliations Mārtiņš Bonders, Jānis Grabis Institute of Information Tehnology, Riga Tehnial University, 1 Kalu Street, Riga, LV 1658, Latvia,

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

SCHEME FOR FINANCING SCHOOLS

SCHEME FOR FINANCING SCHOOLS SCHEME FOR FINANCING SCHOOLS UNDER SECTION 48 OF THE SCHOOL STANDARDS AND FRAMEWORK ACT 1998 DfE Approved - Marh 1999 With amendments Marh 2001, Marh 2002, April 2003, July 2004, Marh 2005, February 2007,

More information

NASDAQ Commodity Index Methodology

NASDAQ Commodity Index Methodology NASDAQ Commodity Index Methodology January 2016 1 P a g e 1. Introdution... 5 1.1 Index Types... 5 1.2 Index History... 5 1.3 Index Curreny... 5 1.4 Index Family... 6 1.5 NQCI Index Setors... 6 2. Definitions...

More information

Static Fairness Criteria in Telecommunications

Static Fairness Criteria in Telecommunications Teknillinen Korkeakoulu ERIKOISTYÖ Teknillisen fysiikan koulutusohjelma 92002 Mat-208 Sovelletun matematiikan erikoistyöt Stati Fairness Criteria in Teleommuniations Vesa Timonen, e-mail: vesatimonen@hutfi

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

Understanding Heating Seasonal Performance Factors for Heat Pumps

Understanding Heating Seasonal Performance Factors for Heat Pumps Understanding Heating Seasonal Performance Factors for Heat Pumps Paul W. Francisco, University of Illinois, Building Research Council Larry Palmiter and David Baylon, Ecotope, Inc. ABSTRACT The heating

More information

OpenScape 4000 CSTA V7 Connectivity Adapter - CSTA III, Part 2, Version 4.1. Developer s Guide A31003-G9310-I200-1-76D1

OpenScape 4000 CSTA V7 Connectivity Adapter - CSTA III, Part 2, Version 4.1. Developer s Guide A31003-G9310-I200-1-76D1 OpenSape 4000 CSTA V7 Connetivity Adapter - CSTA III, Part 2, Version 4.1 Developer s Guide A31003-G9310-I200-1-76 Our Quality and Environmental Management Systems are implemented aording to the requirements

More information

BENEFICIARY CHANGE REQUEST

BENEFICIARY CHANGE REQUEST Poliy/Certifiate Number(s) BENEFICIARY CHANGE REQUEST *L2402* *L2402* Setion 1: Insured First Name Middle Name Last Name Permanent Address: City, State, Zip Code Please hek if you would like the address

More information

Account Contract for Card Acceptance

Account Contract for Card Acceptance Aount Contrat for Card Aeptane This is an Aount Contrat for the aeptane of debit ards and redit ards via payment terminals, on the website and/or by telephone, mail or fax. You enter into this ontrat with

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

Effects of Inter-Coaching Spacing on Aerodynamic Noise Generation Inside High-speed Trains

Effects of Inter-Coaching Spacing on Aerodynamic Noise Generation Inside High-speed Trains Effets of Inter-Coahing Spaing on Aerodynami Noise Generation Inside High-speed Trains 1 J. Ryu, 1 J. Park*, 2 C. Choi, 1 S. Song Hanyang University, Seoul, South Korea 1 ; Korea Railroad Researh Institute,

More information

Weighting Methods in Survey Sampling

Weighting Methods in Survey Sampling Setion on Survey Researh Methods JSM 01 Weighting Methods in Survey Sampling Chiao-hih Chang Ferry Butar Butar Abstrat It is said that a well-designed survey an best prevent nonresponse. However, no matter

More information

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged

More information

Parametric model of IP-networks in the form of colored Petri net

Parametric model of IP-networks in the form of colored Petri net Parametri model of IP-networks in the form of olored Petri net Shmeleva T.R. Abstrat A parametri model of IP-networks in the form of olored Petri net was developed; it onsists of a fixed number of Petri

More information

) ( )( ) ( ) ( )( ) ( ) ( ) (1)

) ( )( ) ( ) ( )( ) ( ) ( ) (1) OPEN CHANNEL FLOW Open hannel flow is haraterized by a surfae in ontat with a gas phase, allowing the fluid to take on shapes and undergo behavior that is impossible in a pipe or other filled onduit. Examples

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

Customer Efficiency, Channel Usage and Firm Performance in Retail Banking

Customer Efficiency, Channel Usage and Firm Performance in Retail Banking Customer Effiieny, Channel Usage and Firm Performane in Retail Banking Mei Xue Operations and Strategi Management Department The Wallae E. Carroll Shool of Management Boston College 350 Fulton Hall, 140

More information

BUILDING CODE SUMMARY GENERAL NOTES DESIGN BUILD ELECTRICAL DESIGN BUILD MECHANICAL & PLUMBING GENERAL NOTES GENERAL NOTES G101

BUILDING CODE SUMMARY GENERAL NOTES DESIGN BUILD ELECTRICAL DESIGN BUILD MECHANICAL & PLUMBING GENERAL NOTES GENERAL NOTES G101 D D BUILDING CODE SUMMARY GENERAL NOTES PROJECT DESCRIPTION: THIS PROJECT IS THE MINOR RENOVATION OF AN EXISTING OUTPATIENT CLINIC. SCOPE CONSISTS OF PAINT, CARPET, TILE, AND UPGRADE TO DIGITAL X-RAY BUILDING

More information

Previously Published Works UC Berkeley

Previously Published Works UC Berkeley Previously Published Works UC Berkeley A University of California author or department has made this artile openly available. Thanks to the Aademi Senate s Open Aess Poliy, a great many UC-authored sholarly

More information

i e AT 6 of 2001 REHABILITATION OF OFFENDERS ACT 2001

i e AT 6 of 2001 REHABILITATION OF OFFENDERS ACT 2001 i e AT 6 of 2001 REHABILITATION OF OFFENDERS ACT 2001 Rehabilitation of Offenders At 2001 Index i e REHABILITATION OF OFFENDERS ACT 2001 Index Setion Page 1 Rehabilitated persons and spent onvitions...

More information

UNIVERSITY AND WORK-STUDY EMPLOYERS WEB SITE USER S GUIDE

UNIVERSITY AND WORK-STUDY EMPLOYERS WEB SITE USER S GUIDE UNIVERSITY AND WORK-STUDY EMPLOYERS WEB SITE USER S GUIDE September 8, 2009 Table of Contents 1 Home 2 University 3 Your 4 Add 5 Managing 6 How 7 Viewing 8 Closing 9 Reposting Page 1 and Work-Study Employers

More information

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012 Air Side Economizers and Energy Recovery - Improvements and New Regulations Richard Lord 09-20-2012 Introduction For commercial buildings the use of outside air for cooling and ventilation is an important

More information

Impact Simulation of Extreme Wind Generated Missiles on Radioactive Waste Storage Facilities

Impact Simulation of Extreme Wind Generated Missiles on Radioactive Waste Storage Facilities Impat Simulation of Extreme Wind Generated issiles on Radioative Waste Storage Failities G. Barbella Sogin S.p.A. Via Torino 6 00184 Rome (Italy), barbella@sogin.it Abstrat: The strutural design of temporary

More information

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.

More information

AC System Equipment Specification, Installation and Operational Options for Improved Indoor Humidity Control

AC System Equipment Specification, Installation and Operational Options for Improved Indoor Humidity Control AC System Equipment Specification, Installation and Operational Options for Improved Indoor Humidity Control Authors Don B. Shirey, III Original Publication Shirey III, D., "AC System Equipment Specification,

More information

Deduplication with Block-Level Content-Aware Chunking for Solid State Drives (SSDs)

Deduplication with Block-Level Content-Aware Chunking for Solid State Drives (SSDs) 23 IEEE International Conferene on High Performane Computing and Communiations & 23 IEEE International Conferene on Embedded and Ubiquitous Computing Dedupliation with Blok-Level Content-Aware Chunking

More information

Big Data Analysis and Reporting with Decision Tree Induction

Big Data Analysis and Reporting with Decision Tree Induction Big Data Analysis and Reporting with Deision Tree Indution PETRA PERNER Institute of Computer Vision and Applied Computer Sienes, IBaI Postbox 30 11 14, 04251 Leipzig GERMANY pperner@ibai-institut.de,

More information

VOLTAGE CONTROL WITH SHUNT CAPACITANCE ON RADIAL DISTRIBUTION LINE WITH HIGH R/X FACTOR. A Thesis by. Hong-Tuan Nguyen Vu

VOLTAGE CONTROL WITH SHUNT CAPACITANCE ON RADIAL DISTRIBUTION LINE WITH HIGH R/X FACTOR. A Thesis by. Hong-Tuan Nguyen Vu VOLTAGE CONTROL WITH SHUNT CAPACITANCE ON RADIAL DISTRIBUTION LINE WITH HIGH R/X FACTOR A Thesis by Hong-Tuan Nguyen Vu Eletrial Engineer, Polytehni University of HCMC, 1993 Submitted to the College of

More information

Comparative Analysis of Life-Cycle Costs of Geothermal Heat Pumps and Three Conventional HVAC Systems

Comparative Analysis of Life-Cycle Costs of Geothermal Heat Pumps and Three Conventional HVAC Systems AIVC #12,983 Comparative Analysis of Life-Cyle Costs of Geothermal Heat Pumps and Three Conventional HVAC Systems John A. Shonder Member ASHRAE Howard A. Mlain, Ph.D. Mihaela A. Martin, P.E. Member ASHRAE

More information

User s Guide VISFIT: a computer tool for the measurement of intrinsic viscosities

User s Guide VISFIT: a computer tool for the measurement of intrinsic viscosities File:UserVisfit_2.do User s Guide VISFIT: a omputer tool for the measurement of intrinsi visosities Version 2.a, September 2003 From: Multiple Linear Least-Squares Fits with a Common Interept: Determination

More information

How To Buy A Lennox Power System

How To Buy A Lennox Power System HVAC for Schools A Comprehensive Look at Products for a Clean, Comfortable Learning Environment Why Schools Choose Lennox Even as resources for schools continue to be constrained, education leaders and

More information

Availability, Reliability, Maintainability, and Capability

Availability, Reliability, Maintainability, and Capability Availability, Reliability, Maintainability, and Capability H. Paul Barringer, P.E. Barringer & Assoiates, In. Humble, TX Triplex Chapter Of The Vibrations Institute Hilton Hotel Beaumont, Texas February

More information

Development and testing of a multi-type air conditioner without using AC inverters

Development and testing of a multi-type air conditioner without using AC inverters Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

FIRE DETECTION USING AUTONOMOUS AERIAL VEHICLES WITH INFRARED AND VISUAL CAMERAS. J. Ramiro Martínez-de Dios, Luis Merino and Aníbal Ollero

FIRE DETECTION USING AUTONOMOUS AERIAL VEHICLES WITH INFRARED AND VISUAL CAMERAS. J. Ramiro Martínez-de Dios, Luis Merino and Aníbal Ollero FE DETECTION USING AUTONOMOUS AERIAL VEHICLES WITH INFRARED AND VISUAL CAMERAS. J. Ramiro Martínez-de Dios, Luis Merino and Aníbal Ollero Robotis, Computer Vision and Intelligent Control Group. University

More information

AUDITING COST OVERRUN CLAIMS *

AUDITING COST OVERRUN CLAIMS * AUDITING COST OVERRUN CLAIMS * David Pérez-Castrillo # University of Copenhagen & Universitat Autònoma de Barelona Niolas Riedinger ENSAE, Paris Abstrat: We onsider a ost-reimbursement or a ost-sharing

More information

Classical Electromagnetic Doppler Effect Redefined. Copyright 2014 Joseph A. Rybczyk

Classical Electromagnetic Doppler Effect Redefined. Copyright 2014 Joseph A. Rybczyk Classial Eletromagneti Doppler Effet Redefined Copyright 04 Joseph A. Rybzyk Abstrat The lassial Doppler Effet formula for eletromagneti waves is redefined to agree with the fundamental sientifi priniples

More information

Large Energy Savings Per Installation VFDs for Large Chillers

Large Energy Savings Per Installation VFDs for Large Chillers This article was published in ASHRAE Journal, June 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.tiaxllc.com.

More information

Price-based versus quantity-based approaches for stimulating the development of renewable electricity: new insights in an old debate

Price-based versus quantity-based approaches for stimulating the development of renewable electricity: new insights in an old debate Prie-based versus -based approahes for stimulating the development of renewable eletriity: new insights in an old debate uthors: Dominique FINON, Philippe MENNTEU, Marie-Laure LMY, Institut d Eonomie et

More information

Henley Business School at Univ of Reading. Pre-Experience Postgraduate Programmes Chartered Institute of Personnel and Development (CIPD)

Henley Business School at Univ of Reading. Pre-Experience Postgraduate Programmes Chartered Institute of Personnel and Development (CIPD) MS in International Human Resoure Management For students entering in 2012/3 Awarding Institution: Teahing Institution: Relevant QAA subjet Benhmarking group(s): Faulty: Programme length: Date of speifiation:

More information

protection p1ann1ng report

protection p1ann1ng report ( f1re protetion p1ann1ng report I BUILDING CONSTRUCTION INFORMATION FROM THE CONCRETE AND MASONRY INDUSTRIES NO. 15 OF A SERIES A Comparison of Insurane and Constrution Costs for Low-Rise Multifamily

More information

MEDICATION MANAGEMENT ASSESSMENT

MEDICATION MANAGEMENT ASSESSMENT MEDICATION MANAGEMENT ASSESSMENT The Mediation Management Assessment provides evidene-based reommendations/standards for Minnesota hospitals in the development of a omprehensive mediation safety program.

More information

HOW TO CALCULATE PRESSURE ANYWHERE IN A PUMP SYSTEM? Jacques Chaurette p. eng. www.lightmypump.com April 2003

HOW TO CALCULATE PRESSURE ANYWHERE IN A PUMP SYSTEM? Jacques Chaurette p. eng. www.lightmypump.com April 2003 HOW TO CALCULATE PRESSURE ANYWHERE IN A PUMP SYSTEM? Jaques Chaurette p. en. www.lihtmypump.om April 003 Synopsis Calulatin the total head of the pump is not the only task of the pump system desiner. Often

More information

Masters Thesis- Criticality Alarm System Design Guide with Accompanying Alarm System Development for the Radioisotope Production L

Masters Thesis- Criticality Alarm System Design Guide with Accompanying Alarm System Development for the Radioisotope Production L PNNL-18348 Prepared for the U.S. Department of Energy under Contrat DE-AC05-76RL01830 Masters Thesis- Critiality Alarm System Design Guide with Aompanying Alarm System Development for the Radioisotope

More information

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Optimization of Water - Cooled Chiller Cooling Tower Combinations Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator

More information