Guidance Note on the Avoidance of Water Damage on Construction Sites
|
|
- Reynard Adams
- 8 years ago
- Views:
Transcription
1 Guidance Note on the Avoidance of Water Damage on Construction Sites Introduction Over recent years the incidence and magnitude of water damage claims in the construction industry, arising from internal water services, has been on the increase. The reasons for this increase are many and varied and the causes not always simple to tackle. Unfortunately, to date, the industry has failed to attempt any co-ordinated response to address the problem. The purpose of this document is to outline some of the ways in which the industry can attempt to tackle the root causes of the problem and also to suggest ways in which organisations and individuals can mitigate the effects of an incident should a loss occur. Contents 1.0 Project Management 2.0 Sub-Contractor Appointment 3.0 Quality Control 4.0 Mitigation Appendix: Risk Assessment Template This Guidance Note is intended for Projects during their Design & Construction Stage and also for On-going Construction Projects. It is acknowledged that whilst on-going projects would not necessarily have the immediate benefit of all the Risk Management measures proposed, it should nevertheless be used as a practical guide and a Best Practice reference point as the project develops. The guide is not intended to be applied to the construction of individual dwellings (though some of the recommendations may be applicable). 3rd Edition 1 4 th May 2010
2 1.0 Project Management 1.1 The Design Team should be tasked with designing out features that are known to exacerbate water damage losses and include those that may mitigate a loss should an escape of water occur. Examples of unfavourable features include: combined service risers inappropriate or concealed pipework routes positioning of water tanks open risers porous cabling electrical cables laid directly onto floor slabs. The design should allow for: additional isolation valves; riser upstands; full and easy access to pipes; and temporary drainage points from the floor plates to help mitigate the effects of escaped water. 1.2 The selection of the water distribution system(s) should be based on a comprehensive risk assessment which should take into account the following factors: the loss history associated with various types of plumbing system the building occupancy the building s susceptibility to water damage (type and quality of finishing to be employed) the height of the building the presence of drainage points the sub-contractor appointment process design input & supervision testing/certification procedures the presence (or absence) of mitigation features (e.g. water management devices, bunding and leak detection) the presence of in-built system safeguards. the potential for damage being caused by pressure surges If the design and system selection is already complete then the adoption of other measures detailed in this document remain valid for effective risk control and mitigation. 1.3 The Principal Contractor or Employer should be responsible for the management of the water damage risk and it is strongly recommended that they nominate an experienced individual to accept responsibility for managing / overseeing this exposure. This individual should ensure: the selection and appointment of skilled sub-contractors and labour (in accordance with section 2) incorporation of written procedures (with respect to installation, testing and commissioning) into contractual terms verification of installation standards and adherence to codes as detailed below that independent site checks and quality control are carried out pressure testing and commissioning procedures are completed full certification of work with audited records verifying compliance with all requirements written quality systems and document control are maintained 1.4 A Water Management Plan should be drawn up detailing responsibilities, procedures and specific actions required to manage all the aspects detailed within this document (both pre and post loss). 1.5 The works should be phased to reduce the likelihood (and severity) of damage from burst pipes or weather-related incidents. Roof and cladding should, ideally, be complete and the envelope made water-tight before internal works of any description are carried out. Where the phasing of the 3rd Edition 2 4 th May 2010
3 works makes this unachievable, the nature and extent of the fit-out works undertaken prior to weather tightness should be subject to a damage risk assessment. 1.6 Permanent drainage should be installed early with full functionality or, alternatively, specific measures put in place to manage the discharge of water from the building. These measures should be detailed in the Water Management Plan. 1.7 Ensure bunding is complete and drainage from plant rooms connected before tanks are filled. Aim to achieve early commissioning of sump pump alarms, leak detection, water management devices and also enabling of the facility to monitor these (often the Building Management System). Any alert system should be routinely checked or remotely monitored. 1.8 Pipework and valves to be identified and labelled as works proceed, not at completion of the project. Valve location and function should be included in the emergency procedures. When working on existing systems, the location and function of all valves should be established, and effectively communicated, prior to work commencing. The template appended to this document can be used to facilitate the risk assessment process and can also be used to form the basis of the Water Management Plan 3rd Edition 3 4 th May 2010
4 2.0 Sub-Contractor Appointment 2.1 Only qualified plumbers with appropriate skill sets should be permitted to work on water distribution systems. It is strongly recommended that persons employed to work upon water distribution systems have, as a minimum, a NVQ level 3 (or equivalent) and are affiliated to an industry body such as the IPHE or IP (see below). Apprentices and trainees should be under the direct supervision of qualified plumbers. Unqualified operatives should never be engaged to work on water services unsupervised. 2.2 Where new systems are employed using different techniques or bespoke machinery, all operatives should be fully trained by the manufacturer supplying the system and training records kept to verify this training has been completed. As a minimum, operatives should have received verified training on the proposed system within the last 12 months. 2.3 The Principal Contractor or Employer should ensure the on-site inspection and certification of the trade contractor s work throughout the process. This task can be delegated to a suitably qualified, independent third party. 2.4 Individuals engaged to work on plumbing installations should be affiliated to an industry body such as the Institute of Plumbing and Heating Engineers (IPHE) or the Institute of Plumbing (IP). 2.5 Plumbing and HV companies should be members of recognised industry associations such as the Association of Plumbing and Heating Contractors (APHC) or the Heating and Ventilation Contractors Association (HVCA). 2.6 Membership of Approved Contractor Schemes (ACS) is a further indication of quality e.g. the IPHE Approved Contractor Scheme and the Water Industry Approval Scheme (WIAPS). Similar schemes are also run by some of the larger Water Authorities and are generally considered to be of equal status. 2.7 All operatives should be required to produce evidence of association membership at induction. Records should be maintained by the Principal Contractor. 3rd Edition 4 4 th May 2010
5 3.0 Quality Control 3.1 The Principal Contractor or Employer should implement a procedure for independent certification of work carried out throughout the installation, testing and commissioning. This procedure may be undertaken by the Principal Contractor and should be documented and auditable. Self-certification by the installing trade contractor is not acceptable. 3.2 All contractors should be required to work to industry recognised codes which should be clearly defined in all work specifications and contractual documents. The main applicable documents are: Water Supply (Water Fittings) Regulations 2000; BS6700:2006 Design, installation, testing and maintenance of services supplying water for domestic use within buildings and their curtilages : specification; HVCA Good Practice Guides; and CIBSE (Chartered Institute of Building Services Engineers) standards. 3.3 Ensure strict compliance with design guidelines and manufacturer s installation manuals. Any operatives working on a system should have received on-site training by the system supplier. Training records should be maintained by the Principal Contractor. No matter what the nature of the system, installation work must only be carried out by qualified, trained personnel or supervised apprentices. 3.4 All joints should be subject to a visual inspection as part of commissioning and for a period not less than 2 weeks thereafter. In areas where access is not possible for visual inspection, consideration should be given to leak detection at strategic points e.g. at the feet of service risers. This should form part of a formal, documented procedure which should also include testing of the pipework, commissioning and certification. 3.5 All pipework should be subjected to a clearly defined Pressure Testing regime in accordance with the manufacturer s guidelines (which will be specific to the system employed). Failure to test an installation to the correct pressure for the required duration may nullify the manufacturer s warranty (this applies to pressures and duration being too low as well as too high). 3.6 In most circumstances, unless otherwise directed by the system supplier, pipework should be subject to an initial air test followed by sectional hydraulic testing at a minimum of 1.5 times the working pressure for a minimum duration of 2 hours. Account needs to be taken of the daily variation in mains pressures when determining the normal working pressures. 3.7 Pressure testing should be witnessed by the Principal Contractor or independent third party, such as a commissioning manager, and should never be conducted unattended. 3.8 All sections of pipework should be certified to have met the test standard and certificates should be issued for each section of pipework tested. The Principal Contractor should be responsible for auditing this paperwork. 3.9 Industry-recognised guidance documents should be regarded as the default position if manufacturer s guidance is not forthcoming e.g. The Guide to Good Practice Site Pressure Testing of Pipework produced by the HVCA and also BS Following sectional testing, full pressure tests should be carried out on systems in their entirety, including all equipment and fittings at their working pressure, in line with equipment supplier s guidelines. A minimum commissioning period of 8 hours is recommended which should be attended for its full duration by an operative familiar with the installation. 3rd Edition 5 4 th May 2010
6 3.11 It is advised that water management devices are installed with audible signalling to provide a warning of failure in any part of the system There should be a full audit trail of all components used, the testing regime, commissioning procedures and approval certificates The Water Authority will inspect all new-builds and issue a certificate of compliance which should be made available for third party audit. This certificate is not a guarantee of workmanship, only confirmation that appropriate fittings have been used in the installation. 3rd Edition 6 4 th May 2010
7 4.0 Mitigation 4.1 Switch off temporary water supply(s) outside working hours. It is recommended that a master valve is located in an accessible location and a designated person nominated to perform the task. Where a boosted supply is installed and is operational, some thought should be given to whether it is possible to isolate these without causing damage to the installation (consideration needs to be given to the effects of thrust pressure when these are turned back on). 4.2 Install a water management device on the incoming riser and programme it to shut down the water supply when water flows exceed pre-determined parameters; these parameters should be set in relation to normal water usage. The device should be set to shut off water supplies outside working hours when very small flows are detected. The device should have the facility to monitor normal water usage over a time period so it can then be programmed to allow water to be shut-off at a very precise, pre-determined flow rate outside of the normal usage parameters. 4.3 The water management device should have an integral battery back-up to ensure that it is effective during the testing and commissioning stage when power is often isolated for long periods. On unmanned sites such a device should be configured for remote monitoring. 4.4 Dependent upon the configuration of the HVAC system, consideration should also be given to installing water management devices on header tanks of enclosed systems. In a residential development, if fitted to individual flats, they can provide protection for finished units prior to occupation. 4.5 Install and commission leak detection, with temporary alarms, in areas such as bunds, the bottoms of risers, equipment rooms, around AC units and in vulnerable cable trays. In an unattended building, alarms should be linked to pagers, or other form of remote monitoring, and an emergency response procedure put in place. 4.6 Security guards, where present, should be trained to provide an early emergency response and to manually shut down systems, where appropriate. Un-manned sites should have personnel cover for emergency out of hours call out to respond to remote monitoring of leak and flow detection. On larger, high value or complex projects consideration should be given to a full time attendance by an engineer with intimate knowledge of the system. 4.7 Guards duties should be extended to routine patrols to check for escape of water where wet services are live. They should be trained in how to respond when discovering an incident. Similar emergency response duties to be allocated to nominated individuals where security is not employed or not present during the day. 4.8 Emergency procedures should be clearly defined within the Water Management Plan including a call out list and knowledge of, and access to, isolation valves. Spill kits and pumps should be made available. A method statement for water isolation to be produced and updated during construction works so that is clear how isolation can be achieved. This isolation procedure should be tested at intervals throughout the construction process. 4.9 Within the Water Management Plan establish the means for bringing in, handling and discharging temporary and permanent water supplies in the buildings under construction. This should include designated water discharge points/routes, and should include supply/discharge of water from roof drainage systems, sprinklers, HVAC systems and temporary welfare & accommodation facilities, where set up inside the building. 3rd Edition 7 4 th May 2010
8 4.10 Temporary rising mains for use of wet trades should be tightly controlled with lockable discharge points. Water butts can be used to ensure only limited quantities of water are available inside the building. Externally routed temporary pipes should be insulated and/or heated to prevent freezing Wherever possible, a permanent supply should be installed in preference to a less reliable temporary mains e.g. through utilising a fire fighting water supply. Temporary water discharge pipes must not be placed in electrical (or other water-susceptible) service risers All incidents of water escape or water damage should be fully investigated and documented. This information should be shared with the Insurance Company and, where possible, remedial measures put in place to prevent a reoccurrence. This guidance is endorsed by the membership of the UK CAR Underwriters Group and the Construction Insurance Risk Engineers Group (CIREG) The UK CAR Underwriters Group CIREG ACE Endurance RSA ACE Allianz Cornhill Eng FM Global SCOR Allianz Global Corporate Allianz Global Corporate General Re Swiss Re Chubb Aspen Re HD- Gerling Tokio Marine Global Axa Corporate Solutions Houston Casualty WR Berkley Beazley Liberty XL Insurance Catlin Mitsui Sumitomo Zurich Global HDI-Gerling Liberty Mitig8 Mitsui Sumitomo Chaucer Chubb Munich Re Norwich Union Risk Engineering Solutions Zurich Global UK CAR Underwriters Group/CIREG Water Damage Co-ordinator and Technical Contact - M Redding Mitsui Sumitomo mredding@msilm.com or contact other member of the sub-committee I Lushington Allianz Global Ian.Lushington@Allianzglobalrisks.co.uk C Rose Beazley Colin.Rose@beazley.com D Huggins Mitsui Sumitomo dhuggins@msilm.com C Jones Zurich Global caroline.z.jones@zurich.com 3rd Edition issued on the 4 th May 2010 Disclaimer The guidance in this document is considered best practice loss control advice. Adoption of the provisions contained herein does not imply compliance with industry / statutory codes or guidelines nor does it guarantee that water related losses will not occur. 3rd Edition 8 4 th May 2010
9 Appendix: Risk Assessment Template Project Address Principal Contractor Plan Owner Date of Plan Next Revision Water Damage Risk Assessment Aspect No. Hazard Mitigation CIREG reference Owner 1. Design 1.1 No consideration has been given to designing-out features likely to increase the likelihood of damage or exacerbate the extent of damage should an incident occur 1.2 The selection of materials and systems is not subject to a full risk assessment taking into account the nature, height and future use of the building Temporary Supplies 2.1 The temporary supply is brought into the building without due consideration of how water will be safely discharged from the structure without damaging any building elements 2.2 The temporary supply is left live when the building is unattended 4.1; 4.9: 4.10; ; 4.6; 4.7 3rd Edition 9 4 th May 2010
10 2.4 No consideration is given as to how a leak will be detected and water flow isolated should the temporary distribution system fail / leak / burst 1.7; Section 4 3. Permanent Services 3.1 Lack of supervision, control and auditing by Principal Contractor or his appointed representative 1.3; 2.3; 3.1; There are no recognised or evident procedures for ensuring the quality of the installation work and adherence to the appropriate codes and standards 2.3; Section There are no recognised or evident procedures for ensuring the robustness of the pressure testing regime Section There are no recognised or evident procedures for ensuring the safe commissioning of the water services Section The selection of water services is not subject to a risk assessment by the mechanical services engineer The mechanical services contractor lacks the appropriate expertise to install the selected water distribution services (domestic, heating and air conditioning) Section New / innovative plumbing system to be employed with insufficient training for those involved in installation Tanks and pipework are to be filled prior to the completion of permanent bunding or drainage or the commissioning of leak detection / BMS monitoring and control 1.7; 3.9 There is no audit trail to verify the safe installation, testing and commissioning of the installations nor the use of suitable components 1.3: 2.3: 3.1; 3.8; rd Edition 10 4 th May 2010
11 3.10 There is no means for detecting and isolating the water supplies / heating systems in the event of a burst pipe, tank or fitting 3.11 There is no means for safely discharging water from a building should a leak occur 1.7; 4.2 to ; Isolation valves and pipework runs are not identified and labelled to allow the swift isolation of failed services Weather-related 4.1 The phasing of the works exposes vulnerable fixtures, fittings and finishes to wind-driven rain 1.5; 1.6; 4.7; There are no provisions (either temporary or permanent) for the removal of water from the roof of the building, to a safe place outside 1.5; 1.6; 4.7; Permanent drainage is not connected to allow for the removal of surface water or water being discharged from the incomplete building 1.5; 1.6; 4.7; 4.8 3rd Edition 11 4 th May 2010
The Avoidance of Water Damage on Construction Sites
Best Practice Guidance The Avoidance of Water Damage on Construction Sites Published by the Construction Insurance Risk Engineers Group (endorsed by the UK CAR Underwriters Group) 4 th Edition June 2015
More informationfocusfirst Construction factsheet Escape of water Things to consider
07I08 focusfirst Construction factsheet Escape of water an awareness guide for construction companies The trend of losses in the construction industry has changed significantly in recent years with statistics
More informationWater Damage on Construction Sites. A guide to loss prevention
Water Damage on Construction Sites A guide to loss prevention Water damage is the second most frequent cause of loss during building projects and represents a large percentage of Construction All Risk
More informationWASTE Application Form - Dublin Waste to Energy SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE
SECTION J ACCIDENT PREVENTION & EMERGENCY RESPONSE Describe the existing or proposed measures, including emergency procedures, to minimise the impact on the environment of an accidental emission or spillage.
More informationService Level Agreement (SLA)
Hertford College, Oxford Service Level Agreement (SLA) For Maintenance, Risk Management, and Domestic Accommodation Services At Hertford College, its residential annexes and non- residential properties
More informationINFORMATION BULLETIN BUSINESS FLOOD PLANNING AND MITIGATION GUIDE ACE GLOBAL RISK ENGINEERING. Flood risk assessment. Introduction
ACE GLOBAL RISK ENGINEERING INFORMATION BULLETIN BUSINESS FLOOD PLANNING AND MITIGATION GUIDE Introduction The most common cause of flooding is due to established water storage areas (natural and man-made)
More informationRecommendations to improve the safety of existing lifts
Recommendations to improve the safety of existing lifts Lift & Escalator Industry Association Lift Safety an introduction Lifts are amongst the very few modes of transport available for continuous unsupervised
More informationMaintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
More informationFirst Fix Leak Repair Scheme
Irish Water First Fix Leak Repair Scheme For Domestic Water Customers CER Consultation Public Submissions: Irish Water Response Submission to the CER Reg_PP_IW_FFLRS_003 31/07/15 1 Introduction This document
More informationANNEX 2 Emergency / Pollution Incident Response Plan
ANNEX 2 Emergency / Pollution Incident Response Plan Volume 5 of 5 Appendix 21.1 Annex 2 EPIRP Page 1 of 9 1 WIND FARM CONSTRUCTION ENVIRONMENTAL EMERGENCY / POLLUTION RESPONSE PLAN... 3 1.1 Policy...
More informationFIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
More informationHealth and Safety Policy
Health and Safety Policy October 2014 1 October 2014 Contents: Introduction 1. STATEMENT OF INTENT AND POLICY OBJECTIVES 2. RESPONSIBILITIES AND ACCOUNTABILITIES FOR HEALTH AND SAFETY 2.1 The Director
More informationASBESTOS CONTAINING MATERIALS POLICY
ASBESTOS CONTAINING MATERIALS POLICY Document Control Version 3 Ratified by Risk Management Sub Group Date Ratified 19 December 2012 Name of Originator/Author Head of Estates and Facilities Name of Responsible
More informationPolicy for the Management of Asbestos in the Workplace
Southwark Council Management of Asbestos in the Workplace November 2011 Page 1 of 15 CONTENTS 1. INTRODUCTION... 3 2. POLICY STATEMENT... 3 3. ASBESTOS RISK CLASSIFICATION SCHEME... 5 4. SAMPLING OF ASBESTOS
More informationFor the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression Systems
BAFE Scheme: SP203-3 Version 1: July 2008 Amendment No: 1 Fire Protection Industry Scheme, Reference SP203 Part 3 For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression
More informationRisk Guidance Note 03. Management of In-Rack Automatic Sprinklers (IRAS)
Risk Guidance Note 03 Management of In-Rack Automatic Sprinklers (IRAS) Overview In-rack automatic sprinklers (IRAS) are often a fundamental part of the fire protection solution for racked storage areas.
More informationProtection of unoccupied or void properties
Real Estate Issue one Protection of unoccupied or void properties Introduction The current economic downturn has lead to a greatly increased number of vacant properties. In some countries rates of unoccupancy
More informationInformation security controls. Briefing for clients on Experian information security controls
Information security controls Briefing for clients on Experian information security controls Introduction Security sits at the core of Experian s operations. The vast majority of modern organisations face
More informationGuidance to Prevent Slips, Trips & Falls
Guidance to Prevent Slips, Trips & Falls Published June 2005 CONTENTS 1. Scope of this guidance 2. New plant/ installations 3. Maintenance 4. Housekeeping 1. Scope of this guidance Slips, trips and falls
More informationFire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
More informationlater damage - Loss ControL
later damage - Loss ControL axisinsurance.ca Table of Contents EXECUTIVE SUMMARY... 1 FACILITY SYSTEMS WATER DAMAGE... 2 Frozen Pipes.....................................................................................
More informationISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
More information1.1.4 The findings from Fire Risk Assessment must be incorporated into the FRAMS Action Plan to manage fire safety at each premise.
Fire Safety Policy 1.1 Policy Statement of Intent 1.1.1 Under the current UK Legislation (In England and Wales, the Regulatory Reform (Fire Safety) Order 2005, Fire (Scotland) Act 2005, Fire and Rescue
More informationAsbestos Management Policy
Asbestos Management Policy Originator: Approval date: Policy and Strategy Team Sovini Board PCHA Board OVH Board/EMT 3 rd December 2012 22 nd November 2012 25 th September 2012 Review date: December 2013
More informationPOLICY ON HEALTH AND SAFETY (GENERAL)
POLICY ON HEALTH AND SAFETY (GENERAL) General Statement It is the policy of Serenity Homecare Limited to ensure, so far as is reasonably practicable, the health, safety and welfare of its employees and
More informationRisk Management Guidelines
Water Damage Risks Introduction Each year there are numerous insurance claims for damage to Buildings, Contents/Stock and Machinery caused by water. This Risk Management Guideline is intended to demonstrate
More informationEnvironmental Policy. JRI Orthopaedics Limited
JRI Orthopaedics Limited October 2014 Contents Clause 1. Policy Statement 1 2. Who is covered by the policy? 2 3. Organisation and Responsibilities 2 4. Training and Communication 3 5. Suppliers and Customers
More informationCorporate Health and Safety Policy
Corporate Health and Safety Policy November 2013 Ref: HSP/V01/13 EALING COUNCIL Table of Contents PART 1: POLICY STATEMENT... 3 PART 2: ORGANISATION... 4 2.1 THE COUNCIL:... 4 2.2 ALLOCATION OF RESPONSIBILITY...
More informationCONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
More informationProtecting Your School from Fire and Weather Related Losses
Protecting Your School from Fire and Weather Related Losses Allianz Ireland s Leading School Insurer Protecting Schools since 1902 Our Policyi The most complete and appropriate insurance arrangement for
More informationCall reduction guidance for false alarm/ unwanted fire signals
Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately
More informationASBESTOS MANAGEMENT POLICY
ASBESTOS MANAGEMENT POLICY Published : 4th Revision December 2014 1 Table of Contents INTRODUCTION... 3 DUTY TO MANAGE ASBESTOS... 3 DUTIES OF CAMPUS SERVICES... 3 1.0 POLICY OBJECTIVES... 5 2.0 RESPONSIBILITIES...
More informationHow To Comply With The Loss Prevention Certification Board
Loss Prevention Standard LPS 1014: Issue 5.3 This Loss Prevention Standard is the property of BRE Global Ltd. and is made publicly available for information purposes only. Its use for testing, assessment,
More informationEnvironmental Management System Procedures
Environmental Management System s Plan Title Oils and Oil Contaminated Items Delivery, Storage, Use and Disposal Ref No Op-Proc-71 Related Documents EMS-Plan-7 Op-Proc-72 EMS-F-71 EMS-F-72 Record of Revisions
More informationWater Damage During Construction
Allianz Global Corporate & Specialty Americas Water Damage During Construction May 2012 A Contractor s Loss Prevention Guide Water damage losses are a major cause of loss during construction and represent
More informationINDEX 1.0 HEALTH, SAFETY & ENVIRONMENT 1.1 INTRODUCTION 1.2 OBJECTIVES 1.3 HEALTH, SAFETY & ENVIRONMENT STATEMENT 1.4 ENVIRONMENTAL STATEMENT
INDEX 1.0 HEALTH, SAFETY & ENVIRONMENT 1.1 INTRODUCTION 1.2 OBJECTIVES 1.3 HEALTH, SAFETY & ENVIRONMENT STATEMENT 1.4 ENVIRONMENTAL STATEMENT 2.0 HEALTH, SAFETY & ENVIRONMENT MANUAL 2.1 HAZARD MANAGEMENT
More informationInformation Security Policy September 2009 Newman University IT Services. Information Security Policy
Contents 1. Statement 1.1 Introduction 1.2 Objectives 1.3 Scope and Policy Structure 1.4 Risk Assessment and Management 1.5 Responsibilities for Information Security 2. Compliance 3. HR Security 3.1 Terms
More informationService Level Agreement/Specification
Service Level Agreement/Specification For Maintenance and Associated Risk Management Services at New College Campus and Associated properties May 2007 INDEX 1. SCOPE 2. MAINTENANCE SERVICE LEVELS a. Staffing
More informationENVIRONMENTAL POLICY & MANAGEMENT SYSTEM GUIDE
ENVIRONMENTAL POLICY & MANAGEMENT SYSTEM GUIDE 1 Statement of Intent Corps Security aims to create and maintain through staff awareness, the highest level of environmental responsibility. We regard the
More informationSt Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
St Peter s College ELECTRICAL SAFETY References: A. Peninsula Business Services Guidance Note 4-1, Electrical Safety. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
More informationCIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance
CIBSE Guide M: Maintenance engineering and management compliance legislation and guidance Types of System/Plant Action required Frequency by Type of Fire and Smoke Fire extinguishers Discharge (not CO
More informationProposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed
More informationBradlee Boilers Ltd. Instruction Manual for starting up Bradlee Hire Boiler from Cold
Bradlee Boilers Ltd Instruction Manual for starting up Bradlee Hire Boiler from Cold To be read in conjunction with Bradlee Boiler guide to Commissioning Boilers Document Ref: HM001 1. Ensure that all
More informationAsbestos Management Policy (Version 3)
Asbestos Management Policy (Version 3) Contents Page Introduction 3 College Policy Statement for Asbestos Management 3 Objectives (of this Policy and Procedure) 3 Application of Policy 4 Licensed Asbestos
More informationMAGB HEALTH, SAFETY AND ENVIRONMENT GROUP POLLUTION INCIDENT RESPONSE PLAN
MAGB HEALTH, SAFETY AND ENVIRONMENT GROUP POLLUTION INCIDENT RESPONSE PLAN SCOPE: This guidance sets out best practice for producing a Pollution Incident Response Plan to deal with an environmental incident
More informationCompliance Schedules and Building Warrant of Fitness
Compliance Schedules and Building Warrant of Fitness Purpose of this guidance information The purpose of this guidance information is to help building owners and managers of commercial, industrial or communal
More informationLook after your boiler so it can look after you
Look after your boiler so it can look after you This guide covers the steps you can take to ensure that your Vokèra boiler continues to operate efficiently and safely. No-one knows your boiler better than
More informationSafety Manual Title: Spill Prevention & Response Review Date: 6/1/2014
Operation s Purpose The purpose of this plan is to document spill prevention and response requirements. Each Elkhorn Construction, Inc. jobsite will develop a spill prevention and response plan based on
More informationUPP Residential Services Fire Risk Assessment
UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This
More informationTransformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
More informationManaging Asbestos Policy
Managing Asbestos Policy Liverpool Mutual Homes Page 1 of 16 Table of Contents 1. MANAGEMENT INFORMATION 2. POLICY STATEMENT 3. POLICY AIMS AND KEY OBJECTIVES 4. INTRODUCTION 5. DETAIL 6. LINKS TO LMH
More informationStatement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary
Installation Service Statement of Work - 1 - Cooling Start-up Service Cooling Start-up Service Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details
More informationCOLUMBUS STATE COMMUNITY COLLEGE EMPLOYEE SAFETY MANUAL
COLUMBUS STATE COMMUNITY COLLEGE EMPLOYEE SAFETY MANUAL HAZARDOUS MATERIAL MANAGEMENT Effective October 15, 1995 Page 1 of 4 Updated August, 2008 Revised August, 2009 A. Columbus State Community College
More informationcontractors, etc. and establish relationships with lease and rental companies.
The following may serve as a checklist when preparing for a Tropical Storm or Hurricane. Although Tornadoes usually provide little advance warning, locations subject to Tornadoes may apply much of the
More informationSchool or service safety advisor (SSA) role
School or service safety advisor (SSA) role Document control information Published document name: ssa-role-gn Date issued: January 2012 Version: 1.0 School or service safety advisor (SSA) role Previous
More informationA cure for water damage in real estate
A cure for water damage in real estate Presented for BC Non-Profit Housing Association by Jeff Shearman, Zurich Services Corporation 2010 Zurich Canada Focused on our customer Reduce overall risk by reducing:
More informationAsbestos Management Policy
Central Bedfordshire Council www.centralbedfordshire.gov.uk Asbestos Management Policy The Housing Service Version 1.0 Directorate Social Care Health and Housing Service Housing Service Approved by Director
More informationSafety Systems Review Facilities Management Guidance and specification Version 1 2014
Safety Systems Review Facilities Management Guidance and specification Version 1 2014 Membership Training Qualifications Audit and Consultancy Policy and Opinion Awards Contents Page Safety Systems Review
More informationHealth and Safety Policy and Procedures
Health and Safety Policy and Procedures Health & Safety Policy & Procedures Contents s REVISION AND AMENDMENT RECORD : Summary of Change Whole Policy 4.0 05 Nov 08 Complete re-issue Whole Policy 4.1 10
More informationOPTIONS. for. Replacing Boiler Plant. Sussex Lodge London W2 & 16 Stanhope Terrace London W2
OPTIONS for Replacing Boiler Plant Report to Tenants Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers Tel: 01932 873 653 13 JULY 2003. Replacing Boiler Plant... 1 1. Existing
More informationWORK HEALTH AND SAFETY
WORK HEALTH AND SAFETY SCOPE POLICY Work Health and Safety System Work Health and Safety Objectives Roles and Responsibilities Executive Responsibilities Manager Responsibilities Worker Responsibilities
More informationCivil Engineering Sector Labour-Management Health and Safety Committee
PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION SITES Civil Engineering Sector Labour-Management Health and Safety Committee July 2008 PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION
More informationHEALTH & SAFETY POLICY
HEALTH & SAFETY POLICY 1. STATEMENT OF INTENT & POLICY OBJECTIVES The Council, as the governing body of the School, recognises and accepts the responsibilities placed on it as 'Employer' by the Health
More informationAsbestos Awareness Syllabus (Category A)
Asbestos Awareness Syllabus (Category A) Introduction This syllabus sets out the guidance issued by the UK Asbestos Training Association (UKATA) for the provision of asbestos awareness training as contained
More informationAPPENDIX O. Spill Prevention and Emergency Response Plan. G3 Terminal Vancouver Port Metro Vancouver Project Permit Application APPENDIX O
APPENDIX O Spill Prevention and Emergency Response Plan APPENDIX O G3 Terminal Vancouver Port Metro Vancouver Project Permit Application G3 TERMINAL VANCOUVER: PORT METRO VANCOUVER SPILL PREVENTION AND
More informationCODE OF PRACTICE. Safety Management. Occupational Safety and Health Branch Labour Department CODE OF PRACTICE ON SAFETY MANAGEMENT 1
CODE OF PRACTICE On Safety Management Occupational Safety and Health Branch Labour Department CODE OF PRACTICE ON SAFETY MANAGEMENT 1 This Code of Practice is prepared by the Occupational Safety and Health
More informationAdditional Services Agreement. Part 3: Schedule of our requirements
Additional Services Agreement Part 3: Schedule of our requirements Schedule of our requirements Part A Water Services 1 All water services All connections to our water mains, including those used for construction
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationThis document is meant to be a starting point for any company wanting to implement the safety passport scheme for their contractors on site.
Introduction This document is meant to be a starting point for any company wanting to implement the safety passport scheme for their contractors on site. It was put together by members of the Food & Drink
More informationHealth and Safety Policy
Health and Safety Policy Status: Final Next Review Date: Apr 2014 Page 1 of 16 NHS England Health and Safety: Policy & Corporate Procedures Health and Safety Policy Policy & Corporate Procedures Issue
More informationPolicy Number: 054 Work Health and Safety July 2015
Policy Number: 054 Work Health and Safety July 2015 TRIM Ref: TD14/318 Policy Details 1. Owner Manager, Business Operations 2. Compliance is required by Staff, contractors and volunteers 3. Approved by
More informationKODAK VERSAMARK, INC.
KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF
More informationFire Alarm Systems Care and Maintenance
April 2011 Country of Origin: United Kingdom Fire Alarm Systems Care and Maintenance Introduction A fire alarm installation is designed to provide early warning of a fire condition. To ensure that the
More informationPollution Incident Response Plan
Pollution Incident Response Plan Introduction Schmidt Quarries is committed to ensuring all aspects of our quarrying activities comply with the environmental legislative requirements in NSW. This Pollution
More informationSTANDARD PLUMBING AND DRAINAGE REGULATION 2003
Queensland Subordinate Legislation 2003 No. 265 Plumbing and Drainage Act 2002 STANDARD PLUMBING AND DRAINAGE REGULATION 2003 TABLE OF PROVISIONS Section Page PART 1 PRELIMINARY Division 1 Introduction
More informationOAKPARK SECURITY SYSTEMS LIMITED. Health & Safety Policy. Requests or suggestions for amendment to this procedure
OAKPARK SECURITY SYSTEMS LIMITED Requests or suggestions for amendment to this procedure should be submitted to the owner of the process PROCESS OWNER: MANAGEMENT TEAM Current version: PREVIOUS VERSION
More informationOHS Contractor Management Procedure
The Wudinna District Council will through this procedure seek to ensure that Contractors they engage have an adequate understanding and a commitment to Occupational Health, Safety and Welfare as well as
More information1.1. EMERGENCY PROCEDURE On discovering a fire or being informed of an emergency;
Fire Action Plan FIRE ACTION PLAN SEStran aims to provide and maintain safe & healthy working conditions, equipment and systems of work for all our employees, and to provide such information, training
More informationPPG21. Pollution Prevention Guidelines. pollution incident response planning: PPG 21. 1. Introduction
PPG21 February 2004 Environmental Alliance working together Pollution Prevention Guidelines pollution incident response planning: PPG 21 These guidance notes have been drawn up to assist those developing
More informationC I T Y O F S E L M A F I R E D E P A R T M E N T
C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:
More informationGUIDELINES FOR THE CONDUCT OF OIL, GAS & PETROCHEMICAL RISK ENGINEERING SURVEYS
GUIDELINES FOR THE CONDUCT OF OIL, GAS & PETROCHEMICAL RISK ENGINEERING SURVEYS Developed by: Ron Jarvis Andy Goddard Swiss Re, London Talbot Syndicate, London Contributions made by the London market engineers
More informationSample Hazard Communications Program for Spray Polyurethane Foam Applications
Sample Hazard Communications Program for Spray Polyurethane Foam Applications Sample Hazard Communication Program for Spray Polyurethane Foam Applications Introduction This sample Hazard Communication
More informationROYAL HOLLOWAY, UNIVERSITY OF LONDON
ROYAL HOLLOWAY, UNIVERSITY OF LONDON ASBESTOS MANAGEMENT POLICY (Version 2) This Policy defines the College s arrangements for the management of asbestos and the measures to be taken for the protection
More informationProperty Policyholder Risk Improvement Report and Hurricane Survey
Risk Engineering Property Policyholder Risk Improvement Report and Hurricane Survey Zurich Services Corporation Risk Engineering 1400 American Lane Schaumburg, IL 60196-1056 847.605.6000 Fax: 847.605.7854
More informationCATERING CONTRACTORS General Code of Safety Practice
Residential & Business Services Director s Office CATERING CONTRACTORS General Code of Safety Practice CONTENTS 1 Introduction 2 2 Commencement of Work 3 3 Vehicles 3 4 Temperature control 3 5 Food hygiene
More informationB-1 Buildings & Service Maintenance
B-1 Buildings & Service Maintenance B-1 Buildings & Service Maintenance SAFETY, HEALTH AND ENVIRONMENTAL POLICY: B-1 DATE OF ISSUE: AUGUST 1994. BUILDINGS AND SERVICES MAINTENANCE 1. Introduction It is
More informationCONTRACTOR S MANAGEMENT PROCEDURE
CONTRACTOR S MANAGEMENT PROCEDURE S No Activity Responsibility 1 Pre-job meeting There shall be a pre-job meeting with contractor after award of contract in which following points shall be discussed and
More informationOPITO APPROVED STANDARD Basic H 2 S Training. OPITO Standard Code: 9014
OPITO APPROVED STANDARD OPITO Standard Code: 9014 OPITO STANDARDS OPITO is an Industry owned not for profit organisation that exists solely to service the needs of the Oil and Gas Industry. OPITO is employer
More informationClients in Construction Best Practice Guidance
Clients in Construction Best Practice Guidance Published in 2009 by the, Metropolitan Building, James Joyce Street, Dublin 1. Copyright The January 2009 Clients in Construction: Best Practice Guidance
More informationINSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
More informationOH&S Management Systems Audit Checklist (NAT, E3)
3.1.2 3.1.1 Introduction OH&S Management Systems Audit Checklist (NAT, E3) This audit checklist is based on Element 3 (Implementation) of the National Self-Insurers OHS Audit Tool. For a full copy of the
More informationFire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
More informationSLIPS, TRIPS AND FALLS POLICY
SLIPS, TRIPS AND FALLS POLICY First Issued Issue Version Purpose of issue/description of change Planned Review Date 2 Root cause analysis (RCA), RIDDOR August 2012 and inspection of communal areas referenced
More informationSAFETY and HEALTH MANAGEMENT STANDARDS
SAFETY and HEALTH STANDARDS The Verve Energy Occupational Safety and Health Management Standards have been designed to: Meet the Recognised Industry Practices & Standards and AS/NZS 4801 Table of Contents
More informationReplacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue. Photo Essay
Original HVAC Units: Replacement of Heating, Ventilation, Air Conditioning (HVAC) Units In Apartments Located at 641 Fifth Avenue Photo Essay One fan motor draws air from the lower section of the unit,
More informationHAVEBURY HOUSING PARTNERSHIP
HS028 HAVEBURY HOUSING PARTNERSHIP POLICY ASBESTOS MANAGEMENT Controlling Authority Director of Resources Policy No. HS028 Issue No. 3 Status Final Date November 2013 Review Date: November 2016 Equality
More informationSample Company SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES
SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES A. The Owner will contract separately and directly for the majority of the commissioning work
More informationSix steps to Occupational Health and Safety
Six steps to Occupational Health and Safety This booklet gives basic guidelines for workplace health and safety systems to help industry in NSW comply with the "duty of care" principle outlined in the
More informationSAFETY MANAGEMENT SYSTEM FOR MAJOR HAZARD FACILITIES - BOOKLET 3: Part 7.17
EMERGENCY PLANNING EXTRACTION FROM: SAFETY MANAGEMENT SYSTEM FOR MAJOR HAZARD FACILITIES - BOOKLET 3: Part 7.17 An extraction from: Safety Management System for Major Hazard page 1 of 14 7.17 Emergency
More informationCity of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
More information