EVACUATION & LIFE SAFETY STRATEGIES FOR SUPER HIGH RISE BUILDINGS. Sam Aloi, Grad. Dip. (Fire Safety & Risk Eng.)VUT Melb, BE (Building) VUT Melb.

Size: px
Start display at page:

Download "EVACUATION & LIFE SAFETY STRATEGIES FOR SUPER HIGH RISE BUILDINGS. Sam Aloi, Grad. Dip. (Fire Safety & Risk Eng.)VUT Melb, BE (Building) VUT Melb."

Transcription

1 EVACUATION & LIFE SAFETY STRATEGIES FOR SUPER HIGH RISE BUILDINGS By Sam Aloi, Grad. Dip. (Fire Safety & Risk Eng.)VUT Melb, BE (Building) VUT Melb. & Jason Rogers, Grad. Dip. (Fire Safety & Risk Eng.)VUT Melb, Ass. Dip. (App. Sci.) SU. Norman Disney & Young Level 6, 5 Queens Road, Melbourne, Victoria, 3004, Australia s.aloi@ndy.com, FACSIMILE , TELEPHONE ABSTRACT The paper will discuss strategies implemented for ensuring safety of occupants in tall buildings under fire conditions. The life safety strategy must integrate key fire safety systems with building features. The possible use of vertical transportation for phased evacuation requires a combination of safe havens, innovative smoke management and sophisticated communication systems to ensure occupants under threat from fire are moved to safe locations within the building. Application of smoke analysis to confirm the effectiveness of designs will be considered. Theoretical design will be supported by practical examples currently being implemented on the 88 level Eureka Tower in Melbourne, Australia. The Eureka Tower project is being developed by a joint venture made up of the Grocon Group, the architect Nation Fender Katsalidis and Tab Fried. The Builder is Grocon Constructors Pty Ltd.

2 INTRODUCTION The height of very tall buildings places great demand on time for occupant evacuation, fire fighting, search and rescue and preservation of the building. In considering fire protection measures for tall buildings, it has become evident that the safety of occupants and fire fighting personnel depends on the design of the building as a whole. A fire engineered approach was used in the design of Eureka Tower in Melbourne, Australia for compliance with the performance requirements of the Building Codes. Eureka Tower is primarily a residential building comprising 88 storeys at a total height of approximately 300 metres. The development is to be the world s tallest residential skyscraper. Eureka Tower sits above a 10 storey podium which incorporates car parking, health centre and gymnasium, shopping, retail outlets, restaurants and cafes. In addition to this, the top four storeys include professional and recreational facilities as well as designated areas that will be freely accessible by the public, namely the observation deck. Fig. 1 The focus of the life safety strategy was to protect people in place. High rise building occupants near the fire would evacuate using the vertical transportation system; whilst occupants remote from the fire would remain protected within the structure. To facilitate this strategy, the fire must be kept small and the persons in the area of fire origin must be permitted to move safely within the structure. The key to the strategy was the design of an integrated fire safety system, with consideration to unique building features that influence fire and smoke spread throughout the building. Blindly following the prescriptive requirements of the Building Codes would not address these issues. A fire engineered approach assesses the level of fire safety and establishes innovative fire safety solutions to suit the specific risk.

3 FIRE DEVELOPMENT & SMOKE SPREAD The fire scenarios used within the quantitative fire and smoke analysis for the building were determined via a hazard analysis. Various fire scenarios were considered within the residential, office and public areas of the building to determine the fire risk based on ignition potential, frequency and consequence. The combustible fuel load throughout the building is expected to vary in content and location. Therefore representative design fires we developed utilising a combination of the anticipated fuel loads, fire test data and statistical information. The considered design fires can be categorized into three main groups being smouldering fires, flaming fires and flashover fires. Smouldering fires are generally a poorly ventilated fire producing very little heat and thus not expected to spread beyond the object of fire origin. The HAZARD I zone computational model, as developed by the United States Department of Commerce- building & Fire Research Laboratory, was used for the quantitative analysis of fire spread from typical apartments to egress paths. Time to untenable conditions were then compared with egress and people movement. EGRESS & PEOPLE MOVEMENT As buildings reach for the heavens, we can not expect building occupants to evacuate using traditional means of egress via hundreds of flights of stairs. Egress down multiple flights of stairs is expected to slow down occupant evacuation, create queuing and bottle necks and cause injury. Studies suggest that it is often the journey to the outside that leads to injury or fatality, with the risk of injury increasing with the number of floors traveled.

4 To minimise occupant travel distance within the stairways, the Eureka Tower was separated into Evacuation Zones according to the proposed lifting arrangement of the building. (three vertical transportation system zones) Fig. 2 The evacuation process and fire safety systems can be best explained as follows: 1. The occupants in the EVACUATION ZONE FLOOR OF FIRE ORIGIN ONLY via the fire isolated stairs which discharge to Transfer Levels. 2. At the Transfer Level, occupants are transferred to express lifts (located in separate shafts to avoid smoke/water damage and provide unimpeded Brigade access to the fire floors via goods lifts) and shuttled to ground floor for direct egress. To permit orderly evacuation, it is proposed to evacuate only the Floor of Fire Origin (FFO) in the first instance. Occupants in Evacuation Zones and Floors of Non-Fire Origin remain in place. Alert and evacuation information in the form of pre-recorded messages is communicated to these floors as required. Occupants are also provided with the option for building evacuation via the fire isolated stairways if required. Table 1 provides a summary of the number of occupants evacuated and evacuation times for the respective evacuation zones. Evacuation Zone Levels Served No. Lifts Serving Evacuation Area No. Occupants Transfer Floor Area Total Zone Evacuation Time Evacuation of Four Floors 2 L24 to L51 2 x 17 passenger 970 persons Lobby 1 hr 6 mins 16.5 mins Area 3 L52 to L88 3 x 17 passenger 1303 persons hr 10 mins 33 mins Table 1. Egress & People Movement Elevators are being considered to be the primary mode of evacuation from high rise buildings in Australia, with some buildings proposing to evacuate the FLOOR OF FIRE ORIGIN using the lift which awaits them, called by the smoke detection system and protected by lobby and air pressurised system.

5 EMERGENCY EGRESS USING VERTICAL TRANSPORTATION SYSTEMS Emergency egress using vertical transportation has been acknowledged as a priority in Australia. Currently Australian regulations and standards do not permit the use of vertical transportation for egress in case of fire. British Standard BS5588 allows fire fighting personnel or people with disabilities to use the lifts in the event of fire, provided the evacuation is managed and elevator system is suitably designed and protected by the building. European Normalised Standards EN 81-72: Fire Fighting Lifts and EN 81-6: Evacuation Lifts have adopted the British approach for emergency egress in multistory buildings. Given this international experience, it was considered reasonable to use the vertical transportation system for evacuation of building occupants in the event of fire, provided the building architecture, lifts, mechanical services, fire safety and electrical systems were correctly designed, installed, commissioned, maintained and managed. The zoned evacuation strategy, utilising the vertical transportation system at Eureka Place Tower, required the development of an alternative solution to the prescriptive (deemed to satisfy) provisions for approval by the Australian Authorities having jurisdiction. The adopted strategy required liaison between the design team and local Authority for identification of risks that could lead to the failure of the lifts. Once identified, systems were put in place to mitigate the risk to satisfy the life safety of the regulations. The following hazards associated with the vertical transportation system were identified: The lift shafts which connect all levels presented a major path for fire and smoke spread The piston effect generated by the movement of the lifts may increase smoke spread Lifts may be called to the floor of fire origin due to adverse effects on controls due to fire

6 Lift doors may not close if opened on the fire floor, due to smoke interfering with closure mechanisms; door distortion due to the heat of the fire; or pressure differentials at lift doors The potential effects of water from issuing fire hose steams or sprinkler discharge on electrical lift equipment Loss of power to the lifts Lift over loading in panic situations VERTICAL TRANSPORTATION & EGRESS SAFETY General The strategy implemented for ensuring safety of occupants combined the use of safe havens, innovative smoke control systems and sophisticated fire detection, alarm and communication systems. Smoke spread and heat damage must be limited to the fire floor by fast response sprinklers and compartmentation. The population must be able to leave the fire affected area to a place of safety and fire fighting personnel must be able to operate safely and efficiently. The vertical transportation system at Eureka Place Tower was protected against smoke and water, as follows: Lift and stairway shafts were air pressurised Lift lobbies were enclosed in smoke resistant construction and pressurised via lift shaft and stair pressurisation leakage Lobbies were protected by intelligent smoke detectors and floor sprinkler flow switches interfaced with lift control for recall in the event of smoke or water flow Lifts used for staged occupant evacuation were located in separate shafts from those located in the Evacuation Zone of fire origin and as such not subject to water damage Sump pumps were located in lift over run pits to drain water at the bottom of lift shafts

7 Lifts were capable of being operated from an emergency power generator Smoke Resistant Lift Lobbies The provision of smoke resistant lift lobbies mitigate smoke spread via lift shafts which connect multiple compartments. Reducing the fire and smoke hazard allows occupants on floors remote from the fire to stay in place. The lobby also provides a safe haven for occupants and fire fighting personnel using lifts during the evacuation of the fire floor. The lobby needs to be of sufficient size to accommodate all people who may use the lifts in a fire emergency with the doors closed to prevent smoke. According to Australian Building Codes, horizontal exits for commercial buildings must have a clear area of not less than 0.5 m 2 per person to accommodate the total number of persons from both parts of the storey. Hence 0.5 m 2 per person was used at Eureka Tower in the calculation for the lobby & transfer area. The lobby also needs to resist the spread of smoke and fire from the floor or lift shaft to maintain tenable conditions for the time required for evacuation or fire fighting search and rescue. Given Eureka Place Tower is fully sprinkler protected, the lobbies were designed to withstand a temperature of 200 C, which was considered appropriate for a smoldering or shielded sprinkler fire. The smoke lobbies at Eureka Tower generally comprised the bounding wall construction of apartments complete with self closing 38mm solid core doors fitted with medium temperature smoke seals. Air Pressurization Systems The effectiveness of a smoke lobby to provide a tenable environment can be enhanced by the use of air pressurisation systems. It is important that smoke does not spread into the lift shafts via the lobby because the piston effect of elevators can distribute smoke throughout the

8 building. Spurious alarms caused by smoke spread may also cause the building pressurisation systems to operate in other adverse modes. Each fire isolated stairway, lift shaft and Transfer Level at Eureka Tower were provided with an air pressurisation system, with lobbies pressurised via leakage. All systems activated simultaneously upon receipt of any general fire alarm in the building for simplicity. The system minimised smoke intrusion by pressurisation with outside air. The system was carefully designed to ensure that positive pressures are maintained and that stack effect, piston effect wind and excessive pressure did not interfere with the door operation. Suitably sized pressure relief was provided in the lift lobbies on all levels to address these issues. Detailed fluid dynamic calculations and modeling were carried out determine pressure and flow throughout out the building for air balancing. Intelligent Smoke Detection & Alarm Systems Information is critical during a fire emergency. Data from equipment such as detectors, remote field devices and television or security cameras in lobbies would be a valuable additional source of information to be used in a fire emergency. Analogue addressable smoke detection technology was used in Eureka Tower to quickly locate the fire and transmit coded signals to various building automation system for phased evacuation. High sensitivity smoke detectors were located below ceiling in all public spaces and lift lobbies. Computer programs set priorities and determine which floors should evacuate using the lifts and which floors remain in place. Lift control panels send elevators to the appropriate floor and recall to home in the event smoke is detected in a lift lobby. Occupant evacuation within the Evacuation Zone is intended to be cascading subject to the severity of the fire incident.

9 Upon fire alarm, it is proposed to evacuate the Floor of Fire Origin (FFO) in the first instance, with the subsequent evacuation of occupants on the floors above and below depending on smoke detection or Fire Brigade intervention. Informative voice alert and evacuation information to building occupants is communicated automatically by the building Emergency Warning And Intercommunication System. The strategy at Eureka Tower is proposed to be managed by responsible fire wardens on each floor; or an Emergency Response Team consisting of security staff, office and retail staff; thus the importance of implementing and maintaining detailed emergency procedures. A fire control room is provided for the exclusive purpose of directing emergency operations. Hard wired emergency phones or Fire Brigade Intercom points are proposed in lift lobbies, elevator cars and transfer levels to communicate between those using the elevator evacuation system and the fire control room. Commissioning, Testing & Maintenance The use of lifts in a fire requires a large number of systems and components to work together. Such systems are inherently unreliable and require periodic routine inspection, testing and maintenance. It is strongly recommended that an overall fire safety system approach is adopted for testing rather than individual components. The performance based design approach relies on the integration between various sub systems; therefore each interface and effect should be tested and maintained for correct operation. TRANSFER LEVELS General Open space public areas such as sky lobbies, observation lounges and panorama decks may be used as transfer levels where people assemble until an emergency is over or be evacuated via the lifts servicing the level.

10 The following levels were nominated as Transfer Levels at Eureka Tower for the evacuation of building occupants : Level 52 (minimum Occupant Area of 455m 2 ) Level 24 (minimum Occupant Area - lobby/corridor) The transfer levels were fire separated from the remainder of the building and serviced with essential services equipment. The construction materials and contents within the transfer levels were selected with consideration to smoke developed and flame spread indices; and consistent with those nominated within regulations for public corridors leading to a fire rated exit. The minimum Occupant Area was determined with consideration to a maximum four levels evacuating at any point in time. This philosophy is consistent with a cascading Emergency Warning System as detailed within Australian Standard AS 2220, which provides warning to the fire level, two levels above and one level below. Transfer Level Area The required Transfer Level area at Eureka Tower was calculated using an inflow and outflow methodology. Project specific first principle evacuation spreadsheets were developed for the calculation of the occupant inflow. These were based on studies by Proulx, Nelson, MacLennan and Pauls. Occupant outflow from the Transfer levels was calculated from data obtained from the ELVAC computational model by Klote et al.

11 NON - FIRE EMERGENCY EVACUATION The evacuation strategy adopted for the Eureka Tower also caters for non-fire related emergencies. The fact that the evacuation zones may be evacuated independently without relying on common equipment, is one of the primary design initiatives adopted which adds to the versatility of the evacuation system. Other design initiatives which were adopted removed the critical single points of failure, which included: Distributed exit stairways which traverse the entire building and discharge at ground level. Distributed lift banks with independent lift motor rooms. Generator or battery back-up power located on a separate floor to the building sub-station for essential fire & life safety services including lifts. Distributed fire detection and alarm system with return path of communication loop cabling located with separate services rated shafts. Networked Fire Indicator and Master Evacuation Control panels located in separate zones where each panel can maintain status and control of its own dedicated circuits and control activity at other locations should a panel fail. Ringed gravity fed fire services water supply, complete with fire brigade booster facilities. The evacuation of the building during non-fire related emergencies requires the building structure to remain in place for the time required to safely evacuate the building. CONCLUSION Tall buildings represent man s very nature to continue to reach for the heavens, creating lasting monuments to their own ingenuity and courage. Performance-Based Codes and Fire Safety Design Methods provide the vehicle in delivering these monuments that we can all be proud of.

12 REFERENCES 1. Australian Building Codes Board, 1996 BUILDING CODE OF AUSTRALIA, Amdt. No Hui, M.C., Nov. 9, 2000 LOBBY PROTECTION, Proceedings From IEAust. Conference, The Use Of Vertical Transportation In an Emergency. 3. Johncock, Alan, Nov. 9, 2000 EMERGENCY EGRESS USING VERTICAL TRANSPORTATION SYSTEMS, Proceedings From IEAust. Conference, The Use Of Vertical Transportation In an Emergency. 4. Klote J., Alvord D. M. and Deal S., November 1991 ROUTINE FOR ANALYSIS OF THE PEOPLE MOVEMENT TIME FOR ELEVATOR EVACUATION, NISTIR Levin, Bernard M. & Groner, Norman E., September, 1997 SOME CONTROL AND COMMUNICATION CONSIDERATIONS IN DESIGNING AN ELEVATOR EVACUATION SYSTEM, Elevator World pp Nelson, H.E. and MacLennan, H.A., June 1995 EMERGENCY MOVEMENT The SFPE Handbook of Fire Protection Engineering, Society of Fire Protection Engineering, 2nd Ed. 7. Proulx, G. EVACUATION TIME AND MOVEMENT IN APARTMENT BUILDINGS, Fire Safety Journal, Vol. 24, 1995, pp Pauls, J.L., 1980 FIRES AND HUMAN BEHAVIOUR, John Wiley and Sons, New York.

2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings

2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings 2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings Richard W. Bukowski, P.E., FSFPE NIST Building and Fire Research Laboratory The events of September 11, 2001 have generated

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

Appraisal of Passive and Active Fire Protection Systems in Student s Accommodation

Appraisal of Passive and Active Fire Protection Systems in Student s Accommodation MATEC Web of Conferences 10, 06002 (2014) DOI: 10.1051/ matecconf/ 20141006002 C Owned by the authors, published by EDP Sciences, 2014 Appraisal of Passive and Active Fire Protection Systems in Student

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company

Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing

More information

GENERAL FIRE SAFETY TERMS & DEFINITIONS

GENERAL FIRE SAFETY TERMS & DEFINITIONS UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:

More information

Fire Alarm system Installation Guide

Fire Alarm system Installation Guide Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

3.In making the following determination, the Secretary of State has not considered whether the plans conform to any other relevant requirements.

3.In making the following determination, the Secretary of State has not considered whether the plans conform to any other relevant requirements. Date: 06/09/99 Ref: 45/1/166 Note: The following letter was issued by our former department, the Department for Environment, Transport and the Regions (DETR). DETR is now Communities and Local Government

More information

ON MOST schemes, the architectural design of. Flexible strategy. Case study. The Forum

ON MOST schemes, the architectural design of. Flexible strategy. Case study. The Forum Flexible strategy ON MOST schemes, the architectural design of a building is influenced by fire engineering strategy. This could be in the form of visual, physical elements such as fire doors, fire curtains,

More information

Introduction. CE marked construction products

Introduction. CE marked construction products Introduction This Technical Booklet has been prepared by the Department of Finance and Personnel and provides for certain methods and standards of building which, if followed, will satisfy the requirements

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

Area of Rescue Assistance Communication System ADA Code Applicable excerpts: Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment

More information

Indiana Building Rehabilitation Standard

Indiana Building Rehabilitation Standard Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC

More information

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the

More information

Australian/New Zealand Standard

Australian/New Zealand Standard Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The

More information

Interfacing Elevators with Fire Alarm and Sprinklers

Interfacing Elevators with Fire Alarm and Sprinklers Interfacing Elevators with Fire Alarm and Sprinklers IEEE Atlanta Chapter May 15, 2006 Brian K Fabel, PE Agenda Today s Codes NFPA, ASME, IBC/IFC Conflicts/Issues Tomorrow s Codes? Applicable Codes NFPA

More information

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.

More information

Fire Safety In High Rise Building

Fire Safety In High Rise Building Fire Safety In High Rise Building CLASSIFICATION OF BUILDINGS AS PER NATIONAL BUILDING CODE 1. GROUPING. Group A - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group B Group C - Educational

More information

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

2012 Ontario Building Code Changes Affecting Fire Alarm Systems 2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development

More information

Capital Development Guideline. 7. 6 Fire risk management for hospitals

Capital Development Guideline. 7. 6 Fire risk management for hospitals Capital Development Guideline 7. 6 Fire risk management for hospitals Department of Human Services Capital Management Branch 2008 Acknowledgments Copyright State of Victoria 2008. Published by the Capital

More information

FIRE SAFETY ONLINE TRAINING

FIRE SAFETY ONLINE TRAINING INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

Fire precautions in dwellings. Private sector housing Providing homes building communities

Fire precautions in dwellings. Private sector housing Providing homes building communities Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared

More information

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:

More information

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern

More information

Life Safety Code Enabling References

Life Safety Code Enabling References SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety

More information

Fire Safety Risk Assessment Checklist for Residential Care Premises

Fire Safety Risk Assessment Checklist for Residential Care Premises Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or

More information

A study of the nature of fire risks in tall buildings

A study of the nature of fire risks in tall buildings A study of the nature of fire risks in tall buildings David Charters and Carl Sherwood BRE Global 12 th March 2013 Part of the BRE Trust Overview 1. Introduction 2. Challenges of tall buildings 3. Analysis

More information

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE

More information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed

More information

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

Learn how all this can be achieved. architecture AND save money. exceptional. with the SALT LAKE CITY, UT PERMIT # US POSTAGE PAID FIRST CLASS

Learn how all this can be achieved. architecture AND save money. exceptional. with the SALT LAKE CITY, UT PERMIT # US POSTAGE PAID FIRST CLASS The ONLY horizontal sliding fire-door with these unique features: Spans unlimited widths, heights up to 23 feet Meets fire codes without being seen Approved for egress applications Automatic closing and

More information

St. John s University

St. John s University St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica

More information

How To Write A Fire Risk Assessment

How To Write A Fire Risk Assessment Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes

More information

IFE Level 4 Certificate in Fire Science and Fire Safety (HL)

IFE Level 4 Certificate in Fire Science and Fire Safety (HL) IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and

More information

Decree of the Ministry of the Environment. on fire safety of garages

Decree of the Ministry of the Environment. on fire safety of garages E4 THE NATIONAL BUILDING CODE OF FINLAND Fire safety of garages Guidelines 2005 Decree of the Ministry of the Environment on fire safety of garages Adopted in Helsinki, 22 March 2005 Pursuant to the Decision

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

CBD-233. Fire Alarm and Detection Systems

CBD-233. Fire Alarm and Detection Systems Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually

More information

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this

More information

Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.

Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable

More information

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

Building Codes Update: The 2009 International Fire Code and the Apartment Industry ! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM

More information

Wyoming State Capitol Building Restoration and Modernization

Wyoming State Capitol Building Restoration and Modernization Wyoming State Capitol Building Restoration and Modernization Level I / II Life Safety and Fire Protection Assessment 25 September 2013 Presentation Overview Project Overview Applicable Codes Non-Conformance

More information

REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS

REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS , Volume 3, Number 1, p.25-51, 2001 REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS W.Y. Hung and W.K. Chow Department of Building

More information

What you need to know about. Smoke alarms for residential buildings

What you need to know about. Smoke alarms for residential buildings What you need to know about Smoke alarms for residential buildings Are s compulsory? Smoke alarms are compulsory and must be installed in residential buildings on or near the ceiling of every storey. What

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc.

James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc. AT THE STRATOSPHERE TOWER, LAS VEGAS NEVADA By: James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc. INTRODUCTION This paper discusses the performance based approach to fire protection

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) Chapter 1 : Definitions clause 1.2.10 : circulation space OLD CLAUSE A space mainly used as means of access between a room or protected shaft

More information

DOMESTIC SMOKE ALARMS

DOMESTIC SMOKE ALARMS SOUTH AUSTRALIAN METROPOLITAN FIRE SERVICE HOME FIRE SAFETY INFORMATION For further advice contact the Community Safety Department South Australian Metropolitan Fire Service on 8204 3611 DOMESTIC SMOKE

More information

The Mission Critical Fire Protection Experts

The Mission Critical Fire Protection Experts The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure

More information

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager FIRE RATED WIRING What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager INTRODUCTION OBC requirements for emergency power OBC requirements for emergency power for fire alarm systems and other building

More information

Fire Standards & Regulations Are you confused?

Fire Standards & Regulations Are you confused? Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm

More information

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2 Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,

More information

- 5 - Table1. Maximum Compartment Volumes

- 5 - Table1. Maximum Compartment Volumes - 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,

More information

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010

BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Page 1 of 7 PURPOSE: This Guidance

More information

Decree of the Ministry of the Environment on fire safety of ventilation systems

Decree of the Ministry of the Environment on fire safety of ventilation systems THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18

More information

FLA S FIRE SAFETY INITIATIVE

FLA S FIRE SAFETY INITIATIVE Improving Workers Lives Worldwide FLA S FIRE SAFETY INITIATIVE Preventing fires and saving lives by empowering workers and factory managers SCENARIO 1 OCCURS AT FACTORY ABC, WHICH HAS NOT IMPLEMENTED NECESSARY

More information

Contents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4

Contents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 Contents 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 2. Scope and Application 2.1 Scope of the Guide 5 2.2 Premises to which the

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/10/10 Rev Page 1 A new updated version of Approved Document B comes into force from the 6 th April 2007. This revised guidance is split into two separate documents:- Volume 1 Dwelling Houses

More information

Practice Note 2006-27

Practice Note 2006-27 Practice Note Self-Contained smoke alarms to existing buildings This updates the previous Practice Note 2005-27 issued May 2005. Reference to the BCA in this Practice Note means Volume One and Volume Two

More information

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS

1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS Fire Risk assessment 1.0 APPOINTMENTS 1.1 Responsible Person. In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO) the School s Head, Mrs J M Miles is appointed as the Responsible Person

More information

Emergency Lighting Practices in the UAE. Richard Caple MSc MSLL Lighting Applications Manager SLL Vice President

Emergency Lighting Practices in the UAE. Richard Caple MSc MSLL Lighting Applications Manager SLL Vice President Emergency Lighting Practices in the UAE Richard Caple MSc MSLL Lighting Applications Manager SLL Vice President Agenda UAE emergency lighting requirements Emergency systems and luminaires Emergency lighting

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

720r Addendum: Siting the 720r

720r Addendum: Siting the 720r 720r Addendum: Siting the 720r UK 1 Cooper Security Limited 2013 Every effort has been made to ensure that the contents of this leaflet are correct. However, neither the authors nor Cooper Security Limited

More information

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use. Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent

More information

CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY

CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY This policy was written in July 2014 and will be agreed by the Board of Governors in October 2014. To be reviewed by June

More information

A. OCCUPANT FIRE PROCEDURES... 3 B. THE TENANT FIRE SAFETY TEAM... 6 C. SENIOR FIRE WARDEN... 7 D. DEPUTY FIRE WARDEN... 8

A. OCCUPANT FIRE PROCEDURES... 3 B. THE TENANT FIRE SAFETY TEAM... 6 C. SENIOR FIRE WARDEN... 7 D. DEPUTY FIRE WARDEN... 8 Brookfield Place BROOKFIELD PLACE Page 2 of 12 OCTOBER 2006 TABLE OF CONTENTS A. OCCUPANT FIRE PROCEDURES... 3 B. THE TENANT FIRE SAFETY TEAM... 6 C. SENIOR FIRE WARDEN... 7 D. DEPUTY FIRE WARDEN... 8

More information

Fire Safety Risk Assessment

Fire Safety Risk Assessment 1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept

More information

NY Fire Safety Institute

NY Fire Safety Institute NY Fire Safety Institute Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness F-80 Definitions and Terminology Established 1995 Preparing

More information

EVALUATION OF THE PERFORMANCE OF FIRE DETECTION SYSTEM IN AN INSTITUTIONAL BUILDING

EVALUATION OF THE PERFORMANCE OF FIRE DETECTION SYSTEM IN AN INSTITUTIONAL BUILDING , Volume 6, Number 4, p.333-343, 2004 EVALUATION OF THE PERFORMANCE OF FIRE DETECTION SYSTEM IN AN INSTITUTIONAL BUILDING C.M. Tse Department of Building Services Engineering, The Hong Kong Polytechnic

More information

Current as of 11/10/08 1 of 1

Current as of 11/10/08 1 of 1 BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that

More information

FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES

FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES P.L. Senez*, K.D. Calder, Hsing H (Isabella) Li Sereca Fire Consulting Ltd., Canada INTRODUCTION

More information

FIRE RISK ASSESSMENT WORKED EXAMPLE

FIRE RISK ASSESSMENT WORKED EXAMPLE FIRE RISK ASSESSMENT WORKED EXAMPLE 1 PREMISES PARTICULARS BE-INT05 Premises Name S M Enterprises Address Small Place Medium Road Anywhere Tel no: 01234 567890 Date of Risk Assessment 1 st July 2011 Use

More information

Underwriting Guidelines for Condominium Pac and Condominium Pac Plus

Underwriting Guidelines for Condominium Pac and Condominium Pac Plus UNDERWRITING GUIDELINES FOR CONDOMINIUMS SEGMENT Local exceptions to these underwriting guidelines may apply. Please consult with your underwriter or sales executive for details and to discuss risks which

More information

CHAPTER 9 FIRE PROTECTION SYSTEMS

CHAPTER 9 FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes

More information

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.

More information

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

Smoke Alarms. New smoke alarm requirements for existing buildings from 1 May 2006. Introduction. Advisory note March 2006

Smoke Alarms. New smoke alarm requirements for existing buildings from 1 May 2006. Introduction. Advisory note March 2006 New smoke alarm requirements for existing buildings from 1 May 2006 Advisory note March 2006 Introduction To enhance safety and minimise loss-of-life in building fires, the NSW Parliament, in July last

More information

FIRE RISK ASSESSMENT SW13 0HA

FIRE RISK ASSESSMENT SW13 0HA FIRE RISK ASSESSMENT at Carmichael Court Grove Road London SW13 0HA ON BEHALF OF Farrar Property Management Date of assessment: 14/01/2013 Recommended review date: January 2015 CONTENTS 1.0 INTRODUCTION

More information

Appendix G. Security management plan

Appendix G. Security management plan Appendix G Security management plan Security Management Plan Prepared by: Kann Finch Group Project Energy Australia Belmore Park Zone 1- Sub-station component General Design Requirements The perimeter

More information

Voice alarm system E100 the new standard for safe evacuation

Voice alarm system E100 the new standard for safe evacuation Voice alarm system E100 the new standard for safe evacuation Clear announcements and future-proof protection in case of fire Answers for infrastructure. E100 from Siemens so everyone knows what to do when

More information

Hotel Fire Safety for staff

Hotel Fire Safety for staff Teaching Guide Hotel Fire Safety for staff Seattle Fire Department Fire Prevention Division Hotel Fire Safety Instructor Outline Introduction Goals: To ensure that hotel employees are knowledgeable in

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

Fire Safety Requirements for Child Care Centre

Fire Safety Requirements for Child Care Centre Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted. NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating

More information

Walking and Working Surface Checklist:

Walking and Working Surface Checklist: Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:

More information

FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589.

FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589. FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589 Bulletin 16-12 Fire Drills This guideline was developed to assist persons

More information

Fire Safety Regulation, a comparative perspective, Ireland v Poland. Piotr Smardz

Fire Safety Regulation, a comparative perspective, Ireland v Poland. Piotr Smardz Fire Safety Regulation, a comparative perspective, Ireland v Poland Piotr Smardz Overview of the presentation Basic facts about Poland Fire statistics Fire and rescue service arrangement Building Law Regulation

More information

Guide to Fire Alarm Systems

Guide to Fire Alarm Systems Guide to Fire Alarm Systems Guide to Fire Alarm Systems INDEX Introduction Page 2 When is a Fire Alarm System Required Page 2 The Fire Precautions Act 1971 & Fire Precautions (Workplace) Regulations 1997Page

More information