SIRIUS SIMOCODE pro V: Prevention of Pump Blockages by Changing the Direction of Rotation

Size: px
Start display at page:

Download "SIRIUS SIMOCODE pro V: Prevention of Pump Blockages by Changing the Direction of Rotation"

Transcription

1 Application Example 08/2015 SIRIUS SIMOCODE pro V: Prevention of Pump Blockages by Changing the Direction of Rotation SIRIUS SIMOCODE pro V

2 Warranty and Liability Warranty and Liability Note The Application Examples are not binding and do not claim to be complete regarding the circuits shown, equipping and any eventuality. The Application Examples do not represent customer-specific solutions. They are only intended to provide support for typical applications. You are responsible for ensuring that the described products are used correctly. These Application Examples do not relieve you of the responsibility to use safe practices in application, installation, operation and maintenance. When using these Application Examples, you recognize that we cannot be made liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these Application Examples at any time without prior notice. If there are any deviations between the recommendations provided in these Application Examples and other Siemens publications e.g. Catalogs the contents of the other documents have priority. We do not accept any liability for the information contained in this document. Any claims against us based on whatever legal reason resulting from the use of the examples, information, programs, engineering and performance data etc., described in this Application Example shall be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German Product Liability Act ( Produkthaftungsgesetz ), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition which goes to the root of the contract ( wesentliche Vertragspflichten ). The damages for a breach of a substantial contractual obligation are, however, limited to the foreseeable damage, typical for the type of contract, except in the event of intent or gross negligence or injury to life, body or health. The above provisions do not imply a change of the burden of proof to your detriment. Any form of duplication or distribution of these Application Examples or excerpts hereof is prohibited without the expressed consent of Siemens AG. Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens' products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. For more information about industrial security, visit To stay informed about product updates as they occur, sign up for a productspecific newsletter. For more information, visit Entry ID: , V1.0, 08/2015 2

3 Table of Contents Table of Contents Warranty and Liability Task Solution Overview Hardware and software components Validity Components used Mode of Operation Logic blocks used Explanation of the logic Embedding Detecting faults in the conveying flow Switching on via the control station Switching on in the conveying direction (ON>) Switching on in the opposite direction (ON<) Switching off via the control station or in the event of a fault Revoking the ON> command Revoking the ON< command Manual reversal in the other direction of rotation Reversal in the opposite direction when a conveying fault has been detected Fault shutdown after n reversals Drive start after fault shutdown Resetting the fault counter during operation Blockage in the opposite direction Cyclic communication with the controller Cyclic receive Cyclic send Configuration and Project Engineering Requirement Default values Configuring the SIMOCODE pro V Parameterizing the SIMOCODE pro V Installation and Commissioning Installing the hardware Installing the software (download) Commissioning Operation of the Application General information on operator control and monitoring Control stations list Control stations selection Online monitoring options in TIA Portal Scenarios Scenario 1: Blockage is not cleared Scenario 2: Blockage is cleared Scenario 3: Blockage in the opposite direction Timestamping Configuring time synchronization and parameterizing timestamping 51 Entry ID: , V1.0, 08/2015 3

4 Table of Contents 8 References History Entry ID: , V1.0, 08/2015 4

5 1 Task 1 Task Figure 1-1: Schematic representation Blockages of pumps, sieves or screens caused by solids are a major problem in conveying wastewater. In the worst-case scenario, this can result in flooded tanks, unwanted water leakage or motor failures. What is at least required is unscheduled work to manually clear the blockages. In many cases, blockages in the conveying flow can be cleared by short-term reversal of the conveying direction if necessary multiple times. To initiate this, imminent blockages must be detected. Suitable criteria for this can be derived from the electrical power supply of the pump drive. Entry ID: , V1.0, 08/2015 5

6 2 Solution 2.1 Overview 2 Solution 2.1 Overview Diagrammatic representation The task is solved using the flexible, modular SIMOCODE pro motor management system for motors in the low-voltage range. Figure 2-1: Components and wiring (diagram) PLC 7 PROFIBUS DP, PROFINET IE, MODBUS RTU SIMOCODE System wiring SIRIUS SIMOCODE pro V Basic Unit SIRIUS Digital module SIRIUS Operator panel SIRIUS Molded case circuit breaker SIRIUS Current / voltage measuring module SIRIUS Reversing contactor combination PG/PC Basic unit (BU) A SIMOCODE pro V motor control unit with PROFIBUS interface is installed in the application example. However, you can also use basic units with PROFINET IE or MODBUS RTU. The basic parameterization corresponds to a reversing starter. Identifying irregularities in the conveying flow In this application example, the SIMOCODE basic unit uses the motor current i max and the power factor cos φ to identify irregularities in the pump s conveying flow. To this end, the associated current/voltage measuring module picks off the three-phase motor voltage and the three-phase motor current at the feeder. Entry ID: , V1.0, 08/2015 6

7 2 Solution 2.1 Overview Clearing blockages in the conveying flow Digital module (DM1) Operator panel (OP) Thanks to a comprehensive selection of logic modules implemented in the basic unit such as truth tables, counters and timers that can be interconnected as desired, a logic was implemented that, in the case of an identified irregularity in the conveying flow, briefly reverses the pump drive up to three times. This gives the drive the chance to successfully move to a normal travel range. If it succeeds, this prevents the imminent forced shutdown. In this example, the status feedback, ON<, OFF and ON>, is output to indicator lights. As the SIMOCODE pro V basic unit can only provide one relay output for ON< for this purpose, two relay outputs of the digital module are used for OFF and ON>. In the example, the motor feeder can also be controlled using the operator panel as the control station. In addition, current measured values, operating data and diagnostic data or status information can be displayed on the operator panel. Communication with a PLC The application example can be run without communication with a PLC. For the cyclic send and receive data, however, the Standard interconnections of the reversing starter (see chapter in \3\) apply so that the drive can be operator controlled and monitored provided that the communication is parameterized accordingly. Chapter describes additional application-specific data exchange with a controller. The fieldbus interface of the SIMOCODE pro V PROFIBUS version used in the sample project corresponds to the default parameterization and has PROFIBUS address 2. Advantages Using SIMOCODE pro, you can prevent faults in automated processes and costly plant downtimes and ensure optimum motor load. SIMOCODE pro allows you to avoid faults in your system and detect pending errors at an early stage. This application example helps you minimize maintenance work. For the benefits the SIMOCODE pro motor management system offers compared to a conventionally designed motor feeder, please refer to or, for example, the SIMOCODE pro manuals (\3\, \4\, \5\) which provide specific information. Scope This application example does not contain a general description of... the hardware components listed in Table 2-1. It provides references to the relevant manuals and system descriptions. See the References in chapter TIA Portal. the SIMOCODE ES configuration software. Basic knowledge of these topics is required. Required knowledge Understanding the application example requires general knowledge of low-voltage controls and distribution, digital circuit engineering and automation technology. You also need basic knowledge of SIMOCODE pro. Being able to handle the SIMOCODE ES option package in TIA Portal is an advantage. Entry ID: , V1.0, 08/2015 7

8 2 Solution 2.2 Hardware and software components 2.2 Hardware and software components Validity This application example can be implemented with... SIMOCODE pro V basic units (PROFIBUS DP, PROFINET IO, MODBUS RTU) SIMOCODE ES software (2007, V13) Components used The example was created with the following components: Hardware components Table 2-1: Hardware components Component Article number Note SIMOCODE pro V basic unit (PROFIBUS version) SIRIUS current/voltage measuring module 2 1 Connection cable to the measuring module (length: 30cm) 1 3UF7010-1AB V DC 1 3UF7010-1AU00-0 3UF711x-1yA00-0 (with x=0) 1 3UF7935-0AA00-0 SIRIUS digital module 1 3UF7300-1AB00-0 Connection cable to the basic unit (length: 2.5cm) SIRIUS operator panel with display Connection cable to the operator panel (length: 50cm) 1 3UF7930-0AA UF7210-1AA UF7932-0AA00-0 Also possible: V AC/DC x=0,1,2,3,4 (depending on the required connected loads of the motor) y=a,b (depending on the type: straight-through current transformer or busbar connection)... other length can also be used optional 3 (if you want to connect, for example, indicator lights for status feedback to the Protection/Control function block)... other length can also be used optional 4 1 In addition, you require a 24V DC power supply. 2 If your application does not require the evaluation of the power factor cos φ (see chapter 3.2.2), you can also use a pure current measuring module 3UF710x-1yA00-0. However, in this case, you have to replace the measuring module in the device configuration in the configuration of the supplied example (see 2 in Table 4-1). 3 When the digital module is not used, it has to be deleted from the device configuration in the configuration of the supplied example (see 2 in Table 4-1). 4 When the operator panel is not used, it has to be deleted from the device configuration in the configuration of the supplied example (see 2 in Table 4-1). Entry ID: , V1.0, 08/2015 8

9 Alternative Siemens AG 2015 All rights reserved 2 Solution 2.2 Hardware and software components Component Article number Note SIRIUS PC cable 1 3UF7941-0AA00-0 SIRIUS circuit-breaker 1 3RV2311-0AC10 SIRIUS contactor 2 3RT2015-1FB42 SIRIUS wiring module top SIRIUS wiring module bottom Motor 1 - Bus connector for PROFIBUS PROFIBUS bus cable 1 3RA1913-3D 1 3RA1913-3E 1 Sold by the meter 6ES7972-0BA52-0XA0 (without PG socket) or 6ES7972-0BB52-0XA0 (with PG socket) 6XV1830-0JH10 to connect the basic unit to the development system or other circuit-breaker, depending on the required connected loads of the motor and the user wishes regarding the design. or other contactors, depending on the required connected loads of the motor and the user wishes regarding the design. for reversing starters, for S00 contactor assemblies depending on customer requirement optional; or other PROFIBUS connector type with switchable terminating resistor optional; or other PROFIBUS bus cable Other small accessories are not included in the above list. Software components Table 2-2: Software components Component Article number Note SIMOCODE ES V13 Standard Floating License (on DVD) SIMOCODE ES V13 Standard Floating License (as a download) 3ZS1322-5CC11-0YA5 3ZS1322-5CE11-0YB5 You can also use the text-based Basic version or the Premium version with parameterization and diagnostics via PROFIBUS/PROFINET. Hardware Support Packages Entry ID (free download: \6\) optional for... SIMOCODE pro V MR SIMOCODE pro V PN, FW V1.2 Driver for SIRIUS USB PC cable 3UF7941-0AA00-0 Entry ID (free download: \7\) Including installation guide Entry ID: , V1.0, 08/2015 9

10 2 Solution 2.2 Hardware and software components Sample files and projects The following list contains the files and projects that are used in this example. They can be downloaded from the appropriate Industry Online Support page. Table 2-3: Sample files and projects Documents _SIMOCODEproV_PumpBlockagePrevention_V1d0_en.pdf _SIMOCODEproV_PumpBlockagePrevention_CODE_V1d0.zip Note... this document TIA project Entry ID: , V1.0, 08/

11 3 Mode of Operation 3 Mode of Operation Figure 3-1: Blockage prevention function diagram Entry ID: , V1.0, 08/

12 3 Mode of Operation 3.1 Logic blocks used The function diagram in Figure 3-1 to which the following explanations refer only shows the additional blockage prevention logic (in the following referred to as logic ). Figure 3-1 does not include the standard interconnections of the reversing starter that forms the basis. 3.1 Logic blocks used The pump blockage prevention logic implemented in the SIMOCODE pro V uses the following blocks that can be freely interconnected: Table 3-1: Logic blocks used Symbol & & TT 4 Explanation Truth table A truth table allows you to implement a logic operation of digital signals. For purposes of illustration, Figure 3-1 shows the truth tables as gates or a combination of gates. Truth tables with the following input/output quantity frameworks are available: 3I/1Q, 2I/1Q and 5I/2Q. For details, please see chapters 12.3, 12.4 and 12.5 of the system manual \3\. Counter 1 + Q 4 R Valu Timer 1 R 30s with opening Signal conditioning 1 R IN Signal conditioning 2 R 1 IN Counter Each positive edge at one of the counter inputs (+/-) increments/decrements the count. The application example uses only the + counter inputs. When the defined limit is reached ( 4 in the left-hand figure), the output (Q) is set to true. The reset input (R) is used to reset the counter to 0. The count is available as an output. For details, please refer to chapter 12.6 of the system manual \3\. Timer In the example, it is parameterized with closing delay or with opening delay. Runtime and output can be reset via a reset input (R). For the exact output response, please refer to the respective timing diagrams in chapter 12.7 of the system manual \3\. Signal conditioning In the example, signal conditioning is parameterized as... edge rising with memory. The signal is only reset by true at the reset input (R). Negation For details, please refer to chapter 12.8 of the system manual \3\. Entry ID: , V1.0, 08/

13 3 Mode of Operation 3.2 Explanation of the logic i max Symbol Limit monitor 1 Explanation Limit monitors In the example, the limit monitors are used to monitor the motor current for undershooting or overshooting of limits and the power factor is monitored for undershooting of a limit. When the relevant limit is reached, the digital output changes to true. When parameterizing the limit monitor, you can define in which motor operating state it will be evaluated. For all limit monitors in the example, the default setting (0.5s) for a configurable delay of the signaling output was not changed. For details, please refer to chapter in the system manual \3\. 3.2 Explanation of the logic Embedding When you configure the preconfigured reversing starter application (Parameters > Device configuration in the project tree), the Control Stations and Protection/Control function blocks are interconnected according to Figure 3-2 by default. Figure 3-2: Reversing starter, standard interconnection To embed the blockage prevention logic, the interconnection of the ON commands is separated. The enabled control commands ON<, ON> and OFF from Control Stations are supplied to the logic as inputs (shown in green in Figure 3-1 and Figure 3-3). The logic outputs are interconnected with the ON plug of Protection/Control (shown in red in Figure 3-1 and Figure 3-3). The enabled control command OFF from Control Stations remains connected to the OFF plug of Protection/Control. Entry ID: , V1.0, 08/

14 3 Mode of Operation 3.2 Explanation of the logic Figure 3-3: Reversing starter with blockage prevention logic embedded Detecting faults in the conveying flow In normal operation, the pump motor operates in a nominal range with regard to its torque. Depending on the type of the specific application in the process, a conveying fault can manifest itself both as a value above and below the nominal range. Both a significant overload with in the worst case total blocking of the motor and a considerable load off the motor up to no-load operation can be interpreted as a fault. To detect this, the application example measures the following parameters: motor current and voltage. The SIMOCODE pro V basic unit calculates the power factor from the phase displacement. An analysis of the motor current and power factor limits eventually indicates a fault in the conveying flow. In the overload range, there is a disproportionately significant increase in the motor current so that, due to its steep characteristic, it is well suited to be used as a trip criterion. In the underload range, however, the power factor has a steep characteristic and, in this range, is better suited as a trip criterion than the motor current. The logic in the SIMOCODE pro V basic unit detects a fault in the conveying flow when the value of the motor current is outside a defined nominal range defined by limit monitor 2 (below nominal range) and 3 (above nominal range) (inputs 1 and 2 of truth table TT9)... or the value of the power factor is below a defined limit defined by limit monitor 4 (input 3 of truth table TT9). The three limit monitors are parameterized such that they respond only when... the motor is running. the start operation has completed (i.e., not before the Class time you set when parameterizing overload protection in Parameters > Motor protection has elapsed; for the trip class, please see CLASS in the glossary of \3\). there is no test position (TPF) (see chapter 11.4 in \3\). Entry ID: , V1.0, 08/

15 3 Mode of Operation 3.2 Explanation of the logic The fault will only be evaluated if the drive is running in the conveying direction, i.e., if the QE1 socket of the Protection/Control function block is true (input 5 of truth table TT9). In Local 2 mode ( local operation or using operator panel), you can activate/deactivate processing of the fault using button 1 of the operator panel. In Remote mode, fault processing is activated via bit 0 of the Cyclic receive byte 1 interface. The interconnection of counter 2, signal conditioning 3 and truth table TT4 is used for this purpose. At output 1 of truth table TT9, the fault signal is available for further processing Switching on via the control station It is assumed that the non-maintained command mode is not checked. This is the default configuration (see the Parameters>Motor control>control function>operating mode menu). Figure 3-4: Default parameterisation: no non-maintained command mode With this setting, the SIMOCODE device, according to the locking of contactors, saves the ON> or ON< command without requiring the user to interconnect appropriate logic blocks. Therefore, an ON command is triggered by a pulse (locally, for example, by a pushbutton) at the respective control station. Switching on in the conveying direction (ON>) Signal conditioning 1 remembers the enabled control command ON> provided by the Control Stations function block. Although, with the no non-maintained command mode default configuration, the ON commands are maintained commands, the ON> command must be additionally saved via signal conditioning 1 to ensure that the fault logic can switch the drive back on in the conveying direction after automatic reversal. Via input 1 of truth table TT2, the ON> command is switched through to the Protection/Control function block provided that input 2 is false, which corresponds to normal, faultless operation. Switching on in the opposite direction (ON<) Moving in the opposite direction can be initiated by the active control station; however, this is not part of normal operation. Via input 2 of truth table TT7, the ON< command provided by the Control Stations function block is switched through to the Protection/Control function block. The control command is saved due to the no non-maintained command mode default configuration. Entry ID: , V1.0, 08/

16 3 Mode of Operation 3.2 Explanation of the logic Switching off via the control station or in the event of a fault Switching off the drive via the active control station is implemented by the fact that the enabled control command OFF of the Control Stations function block is interconnected with the OFF plug of the Protection/Control function block. This connection is created by default when you configure a reversing starter. The blockage prevention logic is only used for reversal operations, it is not used for switching-off via the OFF plug of Protection/Control. Shutting down the drive in the event of a fault is performed by the Protection/Control function block according to the parameterization of the SIMOCODE device. To ensure that the drive does not automatically switch back on after an OFF command, it must be ensured that the ON commands of the logic to the Protection/Control function block are revoked when switching off the motor. Revoking the ON> command In the logic, the ON> command to Protection/Control is revoked by resetting signal conditioning 1: The commands OFF and ON< from the Control Stations function block and the general fault from the Status General fault function block are ORed via truth table TT1 and supplied to signal conditioning 1. Revoking the ON< command It is assumed that the enabled control command ON< from Control Stations is no longer true when the drive is being shut down. If the ON< command is triggered, for example, by a pushbutton, this is the case. As the ON< command is not saved in the logic, resetting the ON< command to Protection/Control is not necessary provided that the reverse motion command was given manually via the active control station. If, however, the ON< command is present due to the automatic reversing operation caused by a forward blocking, the drive is switched off by resetting timer 1. For this purpose, the enabled OFF command at the output of the Control Stations function block is interconnected with the reset input of timer 1 via the truth tables TT5 and TT Manual reversal in the other direction of rotation Motor control is parameterized such that direct reversal via the active control station is possible without requiring the user to give the stop command (see Table 4-2, step 6). As the ON> command is saved via signal conditioning 1, it must be additionally deleted in the logic by resetting the signal conditioning when reversing in the opposite direction. For this purpose, the ON< command from the Control Stations function block is interconnected with the reset input of signal conditioning 1 via truth table TT1. As the ON< command is not separately saved in the logic, direct reversal back to the conveying direction is implemented without additional logical interconnections provided that the motion in the opposite direction is based on a manual command. If, however, the ON< command is present due to the automatic reversing operation caused by a forward blocking, manual direct reversal back to the conveying direction is implemented by resetting timer 1. For this purpose, the enabled ON> command at the output of the Control Stations function block is interconnected with the reset input of timer 1 via the truth tables TT5 and TT8. Entry ID: , V1.0, 08/

17 3 Mode of Operation 3.2 Explanation of the logic Reversal in the opposite direction when a conveying fault has been detected The value true at output 1 of truth table TT9 supplied to the input plug of timer 1 sets the timer output. The timer is parameterized with opening delay. The delay time to be set depends on the application and corresponds to the time you want the drive to move in the opposite direction. For this purpose, the timer output is connected to the ON< plug of the Protection/Control function block via truth table TT7. At the same time, the motion command in the conveying direction is revoked via truth table TT2; this has the effect that also the fault signal at the output of truth table TT9 and therefore the timer input change back to false. Now the motor continues to rotate in the opposite direction until the timer expires provided that it is not prematurely reset via its reset plug. When the timer has expired, its output changes back to false, which revokes the ON< command via TT7 and gives the ON> command via TT2. For this logic to work, Save change-over command must be parameterized (see Table 4-2, step 6) Fault shutdown after n reversals Each positive edge of the fault signal at output 1 of truth table TT9 increments counter 1. This means it counts the runs in the opposite direction. When the counter reaches its parameterized limit n (in the application example: n=4), which means that the drive has already made n-1 reversing runs, the counter output is set to true and, via the External fault 1 function block, it initiates that no other reversing attempts are made, the drive is switched off and an appropriate fault message with a resulting general fault is generated Drive start after fault shutdown Like any fault, the fault message detected by the logic and generated via the External fault 1 function block requires acknowledgment. Therefore, the drive cannot be restarted before the fault has been acknowledged. It cannot be acknowledged before counter 1 has been reset. This is done via the truth tables TT3 and TT6 when one of the following actions is performed: The Test/Reset button on the SIMOCODE basic unit is pressed ( Test/Reset button socket of the BU inputs function block) The Test/Reset button on the SIMOCODE operator panel is pressed ( Test/Reset button socket of the OP buttons function block) Acknowledgment via a PLC (socket for bit 6 of the Cyclic receive byte 0 function block) Resetting the fault counter during operation Counter 1 defines the maximum number of reversing attempts to be made when conveying is blocked. If a blockage is cleared with fewer than the maximum number of parameterized reversing operations, the counter retains its current count. In this case, only the remaining number of reversals is available for another blockage clearing before fault shutdown would be performed. Therefore, the logic prematurely resets counter 1 in the following cases to ensure that the total number of parameterized reversing attempts is always available for future automatic reversing attempts: Entry ID: , V1.0, 08/

18 3 Mode of Operation 3.2 Explanation of the logic Manual motion in the opposite direction. For this purpose, the ON< socket of the Control Stations function block is connected to input 3 of truth table TT6. If no blockage is detected within a specific time interval (in the application example: 1h). For this purpose, timer 2 parameterized with closing delay is interconnected via signal conditioning 2 parameterized as a negation in such a way that it deletes counter 1 via Input 2 of truth table TT6 every hour by a pulse. However, each reversing run triggered by the logic resets timer 2 so that it does not fully expire and the fault counter is not deleted Blockage in the opposite direction If the drive also blocks in the opposite direction, which is detected by limit monitor 1 that responds to a current maximum in reverse motion, the logic initiates immediate reversal back to the conveying direction. For this purpose, the relevant limit monitor resets timer 1 via the truth tables TT5 and TT8 (QE2 socket of Protection/Control) when a reverse motion is detected. According to the current count of counter 1, this is followed by more reversing attempts or fault shutdown of the drive, if necessary Cyclic communication with the controller Cyclic receive In addition to the cyclic receive data that has already been predefined for the reversing starter, the following interconnections have been created: Reset fault The socket for bit 6 of the Cyclic receive byte 0 function block is interconnected with input 3 of truth table TT3. If the SIMOCODE device is reset via communication after a fault, the fault counter counter 1 is interconnected via this interconnection (see also chap ). Deactivate blockage prevention logic The socket for bit 0 of the Cyclic receive byte 1 function block is interconnected with input 4 of truth table TT9. If the PLC transfers false or if no PLC is connected, the blockage prevention logic is active. If true, the limit monitors 2, 3 and 4 are not evaluated (see also chap ). Cyclic send In addition to the cyclic send data that has already been predefined for the reversing starter, the following interconnections have been created: Status device o.k. The socket of the Status device o.k. binary connection block is interconnected with the plug for bit 0 of the Cyclic send byte 1 function block. If the SIMOCODE device operates correctly, the controller receives true. Blockage message The socket of the External fault 1 function block is interconnected with the plug for bit 1 of the Cyclic send byte 1 function block. Therefore, the PLC receives true if a blockage in the conveying flow could not be automatically cleared and the drive is stopped (see also chap ). Fault counter counter 1 The analog output of counter 1 is interconnected with input 1 of the Cyclic send byte 4/9 function block. This ensures that the current number of reversals Entry ID: , V1.0, 08/

19 3 Mode of Operation 3.2 Explanation of the logic performed until fault shutdown (see also chap ) or resetting of the value (see also chap ) is transferred to the PLC. Fault counter counter 2 The analog output of counter 2 is interconnected with input 2 of the Cyclic send byte 4/9 function block. Counter 2 counts all automatic reversals initiated by the logic. The count is transferred to the controller for statistical evaluation. For this purpose, the output of timer 1 at which a positive edge is recorded each time a fault is detected in the conveying flow is interconnected with the + plug of counter 2 (see also chap ). After an overflow (>65535), the counter restarts at 0. Entry ID: , V1.0, 08/

20 4 Configuration and Project Engineering 4 Configuration and Project Engineering Requirement Default values This chapter describes the configuration steps necessary for you to create the sample project. You will find helpful project engineering support, in particular if your required configuration differs from the supplied application example in terms of hardware and component parameterization. The software components listed in Table 2-2 are installed on your development system and you have opened a new software project or a project you want to extend/modify in TIA Portal. When you add a device from the hardware catalog to the project in TIA Portal, a default parameterization will be created. This default parameterization will be used as a basis in the following step tables. Parameters and settings in this application example that do not have to be changed regarding the default values will not be mentioned in the following sections. Note The configuration in TIA Portal offers various options. The following configuration steps represent one possible solution. Steps deviating from this approach to a greater or lesser extent can also lead to the same goal. To also meet the requirements of users using the text-based Basic version of SIMOCODE ES V13, all parameterizations were described without using diagrams. However, when installing the standard or premium version of SIMOCODE ES V13, the function diagram is displayed in the graphic editor where it can be edited. Entry ID: , V1.0, 08/

21 4 Configuration and Project Engineering 4.1 Configuring the SIMOCODE pro V 4.1 Configuring the SIMOCODE pro V Table 4-1: Table for configuring the SIMOCODE pro V In the project tree, go to Devices & networks. 2. Select the Network view. 3. Locate the SIMOCODE pro V in the version you are using and use drag and drop to move it from the Hardware catalog task card to the graphic area of the Network view. In the graphic area of the Network view and in the project tree, the SIMOCODE device is created as Control device_1 (name can be changed). Entry ID: , V1.0, 08/

22 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V In the graphic area, select the SIMOCODE device and go to the Device view. 2. Locate the IUM 0.3 3A current/voltage measuring module, the DM mono digital module and the OPD operator panel and drag these components from the Hardware catalog task card to the appropriate slots in the graphic area of the Network view. 4.2 Parameterizing the SIMOCODE pro V Table 4-2: Table for parameterizing the SIMOCODE pro V 1. In the project tree, select Parameters. Entry ID: , V1.0, 08/

23 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V Go to the fieldbus interface. 2. Enter the communication parameters required for your project. 3. To be able to transfer all the send data described in chapter to the controller, select Basic type 1. Note The STEP 7 project does not contain a controller *) as it is not part of the core content of the example. The user is responsible for integrating and networking a controller in this project. At this point, it is worth noting that the blockage prevention logic can also be used with SIMOCODE pro V PN or MR independently of the bus system used. *) As the SIMOCODE device is not networked with a controller, it additionally appears in Unassigned devices in the project tree and is labeled as Not assigned in the Network view Go to Device configuration. 2. Make sure that the default setting for the SIMOCODE device is Reversing starter. Entry ID: , V1.0, 08/

24 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V Go to Motor protection > Overload/Unbalance/Stalled rotor. 2. Set Set current Ie 1 (rated motor current of the connected motor). In the application example, it was set to 0.5 A. 3. The Class (trip class) influences the limit monitors 2, 3 and 4 (see chapter 3.2.2). They are parameterized such that they do not become active before the motor start is complete. When Class 10 (= default setting), the value defined for the start operation is 10 s. 4. Make sure that the stalled rotor response is deactivated (= default setting). Entry ID: , V1.0, 08/

25 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V Go to Motor control > Control station. 2. Define the three control stations Local control (inputs 1 3 of the SIMOCODE basic unit (BU inputs)) PLC/PCS (bits of the cyclic communication (Cyclic receive byte 0) Operator panel (buttons 2 4 (OP buttons)) for the ON>, OFF and ON< commands according to the figure above. Local control Operator panel Conveying direction ON> (button 2) Opposite direction ON< (input 1) OFF (input 2) Conveying direction ON> (input 3) Opposite direction ON< (button 3) OFF (button 4) Entry ID: , V1.0, 08/

26 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V Go to Motor control > Control function. 2. Check Save change-over command to select this mode. 3. Interconnect the ON< and ON> control commands with the outputs of the appropriate truth tables, as shown in the figure. 4. In Timers, set the interlocking time required for your application. With the 2 s parameterized in the example, the switch-on interlocking of a reversing operation can be monitored well Open Outputs > Basic unit. 2. As shown in the figure, interconnect outputs 1-3 of the basic unit (BU outputs) with plugs 1 QE1, 2 QE2 and QLE< (ON<) of the Protection/Control function block. Entry ID: , V1.0, 08/

27 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V Open Outputs > Operator panel LEDs. 2. Assign LED 1 of the operator panel (OP LED) to the Status remote mode binary connection block. 3. Interconnect LEDs 2-4 with plugs QLE> (ON>), QLE< (ON<) and QLA (OFF) of the Protection/Control function block, as shown in the figure Open Outputs > Digital module Interconnect outputs 1 and 2 of the digital module (DM1 outputs) with plugs QLA (OFF) and QLE> (ON>) of the Protection/Control function block, as shown in the figure. Entry ID: , V1.0, 08/

28 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V Open Outputs > Cyclic send data. 2. In addition to the standard interconnections of the reversing starter, assign the Device o.k. signal of the Status device o.k. binary connection block and the output signal of the External fault 1 function block to bits 0 and 1 of the Cyclic send byte 1 interface. 3. Interconnect the values of counters 1 and 2 used in the logic with inputs 1 and 2 of Cyclic send byte 4/9. Entry ID: , V1.0, 08/

29 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V Go to Standard functions > External fault > External fault Assign the binary output of counter 1 a to the input of the External fault 1 function. 3. In Response, select Trip. 4. Select the marking to be displayed, for example, on the operator panel with display in the event of a fault. Entry ID: , V1.0, 08/

30 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 12. In Logic modules > Truth table 3I/1Q > Truth table 1, define the signals and logic of truth table 1 (TT1 in Figure 3-1). The logic corresponds to an OR operation with three inputs. I1 I2 I3 13. In Logic modules > Truth table 3I/1Q > Truth table 2, define the signals and logic of truth table 2 (TT2 in Figure 3-1). By default, the unused input 3 is false. I1 I2 & I3 (false) Entry ID: , V1.0, 08/

31 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 14. In Logic modules > Truth table 3I/1Q > Truth table 3, define the signals and logic of truth table 3 (TT3 in Figure 3-1). I1 I2 I3 15. In Logic modules > Truth table 3I/1Q > Truth table 4, define the signals and logic of truth table 4 (TT4 in Figure 3-1). I1 I2 I3 & & & Entry ID: , V1.0, 08/

32 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 16. In Logic modules > Truth table 3I/1Q > Truth table 5, define the signals and logic of truth table 5 (TT5 in Figure 3-1). I1 I2 I3 17. In Logic modules > Truth table 3I/1Q > Truth table 6, define the signals and logic of truth table 6 (TT6 in Figure 3-1). I1 I2 I3 Entry ID: , V1.0, 08/

33 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 18. In Logic modules > Truth table 2I/1Q > Truth table 7, define the signals and logic of truth table 7 (TT7 in Figure 3-1). The logic corresponds to an OR operation with two inputs. I1 I2 19. In Logic modules > Truth table 2I/1Q > Truth table 8, define the signals and logic of truth table 8 (TT8 in Figure 3-1). I1 I2 & - Entry ID: , V1.0, 08/

34 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 20. In Logic modules > Truth table 5I/2Q > Truth table 9, define the signals and logic of truth table 9 (TT9 in Figure 3-1). Only output 1 of the truth table is combined. I1 I4 I2 & Q1 I3 I5 Entry ID: , V1.0, 08/

35 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 21. In Logic modules > Counter > Counter 1, select input + (increment), reset and the limit value for counter In Logic modules > Counter > Counter 2, select input + (increment), reset and the limit value for counter In Logic modules > Counter > Counter 3, select input + (increment), reset and the limit value for counter 3. Entry ID: , V1.0, 08/

36 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 24. In Logic modules > Timer > Timer 1, select input, reset, the with opening delay type and the limit value for timer In Logic modules > Timer > Timer 2, select input, reset, the with closing delay type and the limit value for timer In Logic modules > Signal conditioning > Signal conditioning 1, select input, reset and the edge rising with memory type. Entry ID: , V1.0, 08/

37 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 27. In Logic modules > Signal conditioning > Signal conditioning 2, select input and the type inverting. 28. In Logic modules > Signal conditioning > Signal conditioning 3, select input, reset and the edge rising with memory type. 29. In Logic modules > Limit monitor > Limit monitor 1, parameterize the Limit value function block for the upper current limit in reverse motion. In Active status, select always on. Specify the limit in %, referring to the motor current on the input plug. If necessary, select a marking. Entry ID: , V1.0, 08/

38 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 30. In Logic modules > Limit monitor > Limit monitor 2, parameterize the Limit value function block for the lower current limit in the conveying direction. The limit monitor should only be active when the motor is running and after the start operation has completed (if the motor is running, except TPF, with startup override (run+)). Specify the limit in %, referring to the motor current on the input plug. If necessary, select a marking. 31. In Logic modules > Limit monitor > Limit monitor 3, parameterize the Limit value function block for the upper current limit in the conveying direction. The limit monitor should only be active when the motor is running and after the start operation has completed (if the motor is running, except TPF, with startup override (run+)). Specify the limit in %, referring to the motor current on the input plug. If necessary, select a marking. Entry ID: , V1.0, 08/

39 4 Configuration and Project Engineering 4.2 Parameterizing the SIMOCODE pro V 32. In Logic modules > Limit monitor > Limit monitor 4, parameterize the Limit value function block for the cos φ lower limit in the conveying direction. The limit monitor should only be active when the motor is running and after the start operation has completed (if the motor is running, except TPF, with startup override (run+)). Specify the limit in %, referring to the motor current on the input plug. If necessary, select a marking. 33. Compile Control device_1 to identify any errors and save its parameterization If necessary, complete your configuration by networking the SIMOCODE pro V as a PROFIBUS slave with a controller that has also been configured in TIA Portal (PROFIBUS master). This allows read and write control access to the interconnected cyclic send and receive data. Entry ID: , V1.0, 08/

40 5 Installation and Commissioning 5.1 Installing the hardware 5 Installation and Commissioning 5.1 Installing the hardware Note Always follow the installation, mounting and wiring guidelines for the individual components provided in the appropriate manuals and accompanying notes. Table 5-1: Table for installing and wiring the hardware 1. Mechanically install the components shown in Figure Establish the power wiring as indicated in Figure phase infeed SIRIUS circuit-breaker SIRIUS current/voltage measuring module SIRIUS reversing contactor assembly Motor 3. Follow the short instructions given in \3\ to wire the SIRIUS SIMOCODE pro V basic unit as a reversing starter. If as intended in the application example you want to indicate the ON<, OFF and ON> states in local control by indicator lights or illuminated pushbuttons, use output OUT3 (terminal 7) of the basic unit to signal counterclockwise rotation ON<. Apply the 24V contact supply to terminal If as intended in the application example you want to indicate the ON<, OFF and ON> states in local control by indicator lights or illuminated pushbuttons, use output Out1 (terminal 21) of the digital module to signal the OFF stop state and output Out2 (terminal 22) to signal clockwise rotation ON>. Apply the 24V contact supply to terminal 20. If you do not need state signaling in local control, you can remove the digital module from the configuration (see step 2 in Table 4-1): In the Device configuration of Control device_1, right-click the digital module and in the context menu, left-click Delete. 5. As indicated in Figure 2-1, establish the SIMOCODE system wiring between the following components: SIRIUS SIMOCODE pro V basic unit SIRIUS current/voltage measuring module SIRIUS digital module SIRIUS operator panel For the respective cables, please refer to Table 2-1. Furthermore, please refer to chapter 14.5 System interfaces in \3\. 6. Use the SIRIUS USB PC cable to connect your development system to an available SIMOCODE system interface. In the application example, this interface is on the operator panel. 7. Physically establish the PROFIBUS connection to any controller (PROFIBUS master). Entry ID: , V1.0, 08/

41 5 Installation and Commissioning 5.2 Installing the software (download) 5.2 Installing the software (download) Table 5-2: Installing the software (download) 1. To enable your development system (PG/PC) to communicate with the SIMOCODE device via the USB PC cable, install the associated driver. SIEMENS Industry Online Support provides the download and an installation guide (\7\). 2. Make sure that... the hardware has been completely installed and wired (see chapter 5.1). the 3-phase power circuit is de-energized or has been disconnected using the SIRIUS circuit-breaker. the power supply of all components is on. 3. If you are using the supplied _SIMOCODEproV_PumpBlockagePrevention_CODE_V1d0.zip archive, extract it to a directory on the hard drive of your development system. 4. In TIA Portal, open the project you have just extracted, SIMOCODEproV_PumpBlockagePrevention, or your own project that has already been modified. 5. Download Control device_1 to the SIMOCODE basic unit. Entry ID: , V1.0, 08/

42 5 Installation and Commissioning 5.2 Installing the software (download) 6. When downloading for the first time, the Extended download to device window opens Select the SIRIUS PtP interface type and the number of the used COM interface. For the specific COM interface number the SIMOCODE device uses, please refer to the installation notes for the driver for the SIRIUS USB PC cable, \7\. 2. Leave Show all compatible devices checked (default setting). 3. Select Start search. 4. Check, wether the correct device has been found. 5. Start downloading and follow the instructions/information displayed on the screen. Successful download is indicated as follows: NOTICE The download is aborted with an error if the SIMOCODE device is in Remote/Automatic mode, an On command is present or the motor is running. Entry ID: , V1.0, 08/

43 5 Installation and Commissioning 5.3 Commissioning 5.3 Commissioning A specific commissioning routine is not required. Provided that you have performed the hardware and software installation described above, you only have to connect the power circuit to the 3-phase system or switch on the SIRIUS circuit-breaker. The next steps are described in the following chapter, 6 Operation of the Application. Entry ID: , V1.0, 08/

44 6 Operation of the Application 6.1 General information on operator control and monitoring 6 Operation of the Application 6.1 General information on operator control and monitoring Control stations list The configuration allows the following control stations (see step 5 in Table 4-2): Local control station, e.g. illuminated pushbutton Figure 6-1: Local control station Opposite direction ON (BU input 1) OFF (BU input 2 low active) Conveying direction ON (BU input 3) Operator panel with display Figure 6-2: Operator panel Blockage prevention On/Off (button 1) Message External fault 1 Conveying direction ON> (button 2) Opposite direction ON< (button 3) OFF (button 4) On the operator panel, blockage prevention can only be (de)activated in Local 2 mode (see Control stations selection ) using button 1. However, the LED in button 1 always indicates the correct blockage prevention status regardless of the mode (Local 2 or Remote). On the operator panel, a blockage that cannot be cleared is indicated by... the GEN LED. FAULT (flashing red), External fault 1 with the text Blocked on the display. Reset External fault 1 Entry ID: , V1.0, 08/

45 6 Operation of the Application 6.1 General information on operator control and monitoring The right one of the two softkeys is used for fault acknowledgment. PLC (via PROFIBUS) The drive is switched on and off via bits 0-2 of the Cyclic receive byte 0 interface. The relevant switching signals from the PLC must not be present permanently. The required signal behavior is the same as for pushbuttons. Bit 0 Opposite direction ON< Bit 1 OFF Bit 2 Conveying direction ON> The blockage prevention logic can also be (de)activated via PROFIBUS. This is done via bit 0 of the Cyclic receive byte 1 interface. However, this requires that Remote mode (see Control stations selection ) be selected. A blockage that cannot be cleared generates External fault 1. This fault is transferred to the PLC with bit 1 of the Cyclic send byte 1 interface. The fault is acknowledged via bit 6 of the Cyclic receive byte 0 interface. Control stations selection Two modes are available: Local 2 and Remote (see step 5 in Table 4-2). You select the mode via bit 5 of the Cyclic receive byte 0 interface. When bit 5 = true, Remote mode has been selected. Local 2 The drive is operated either locally using pushbuttons or via the operator panel. If no PLC is connected, bit 5 of the Cyclic receive byte 0 interface is always false and therefore Local 2 is automatically selected. Remote The drive is operated either using a PLC (PROFIBUS) or via the operator panel. The PLC may, but need not, be configured in the same project as the SIMOCODE device. Online monitoring options in TIA Portal When going through the following scenarios, it is useful to monitor some data and situations online in TIA Portal. To go online, perform steps 1 and 2 as shown in Figure Figure 6-3: Going online When the online connection between your PG/PC and the SIMOCODE device has been established, double-click in the project tree to go to Commissioning ( 3 in 5 It is possible that the extended go online dialog appears, which largely corresponds to the one from 6 in Table 5-2. Follow the instructions, start the search for the SIMOCODE device and eventually close the dialog using the Go online button. Entry ID: , V1.0, 08/

46 6 Operation of the Application 6.1 General information on operator control and monitoring Figure 6-3). The following menu items are relevant to the scenarios: Faults, Measured values and Service data / statistical data. Indication of the Conveying flow blocked fault (in the Faults menu item) If a blockage can t be cleared, this results in the parameterized External fault 1. Figure 6-4: Fault indication online in TIA Portal Monitoring motor current and cos φ (in the Measured values menu item) The Measured values menu item allows you to monitor the current current and power factor values to compare them to the set values of the limit monitors. Figure 6-5: Measured values online in TIA Portal Entry ID: , V1.0, 08/

47 6 Operation of the Application 6.1 General information on operator control and monitoring Monitoring counters and timers (in the Service data / statistical data menu item) The Service data / statistical data menu item allows you to monitor the current values of the timers and counters of the blockage prevention logic.figure 6-6: Timers and counters online in TIA Portal Note When using the standard or premium version of SIMOCODE ES V13, the integrated CFC-based graphic editor allows you to conveniently monitor the input and output data of all function blocks and the signal flow online. Entry ID: , V1.0, 08/

48 6 Operation of the Application 6.2 Scenarios 6.2 Scenarios The following three scenarios are only a selection of possible processes Scenario 1: Blockage is not cleared Table 6-1: Instruction for Scenario 1 1. Make sure that the blockage prevention logic is on. 2. Check whether counter 1 has the value 0. If not, perform fault acknowledgment (RESET), for example, using the TEST/RESET button on the SIMOCODE basic unit to reset counter Start the drive with ON> (conveying direction). 4. Wait until the Class 10 time has elapsed, i.e., until the start operation has completed (10s). 5. Provoke or simulate a situation that causes one of the three limit monitors 2, 3 or 4 to respond (fault situation). CAUTION Avoid overloading your motor. Think about whether you can risk a blocking of your drive. For testing, you can parameterize a set current I e1 smaller than suitable for the motor and/or less critical limits for the limit monitors. 6. The motor stops and moves in the opposite direction once the interlocking time (2s) has elapsed. Counter 1 is incremented. 7. When timer 1 (30s in the example) has expired, the motor stops again and, once the interlocking time (2s) has elapsed, rotates back to the conveying direction. 8. As the fault is still present, the motor continues its motion in the conveying direction only until the start operation has completed (= Class 10 time elapsed, 10s). 6 and 7 listed above are executed 3 x. 9. When counter 1 has reached 4, the drive stops with External fault 1. This is indicated as follows: GEN LED. FAULT on the SIMOCODE device flashes red. GEN LED. FAULT on the operator panel flashes red. In the case of an operator panel with display, the Blocked fault is indicated. In the case of PROFIBUS communication, the fault is transferred to the PLC with true via bit 1 of the Cyclic send byte 1 interface. In TIA Portal, the Online view displays External fault 1 in Commissioning > Faults. 10. Acknowledge the fault in one of the following ways: Press the TEST/RESET button on the SIMOCODE pro V basic unit. Press the right softkey on the operator panel. Via PROFIBUS, transfer true to bit 6 of the Cyclic receive byte 0 interface. Acknowledgment resets counter Clear the blocking by ensuring that each of the limit monitors 2, 3 or 4 no longer responds. Entry ID: , V1.0, 08/

49 6 Operation of the Application 6.2 Scenarios Scenario 2: Blockage is cleared Table 6-2: Instruction for Scenario 2 1. Perform steps 1-5 of Scenario The motor stops and moves in the opposite direction once the interlocking time (2s) has elapsed. Counter 1 is incremented. 3. While the drive moves in the opposite direction, clear the blocking by ensuring that each of the limit monitors 2, 3 or 4 no longer responds. 4. When timer 1 (30s) has expired, the motor stops again and, once the interlocking time (2s) has elapsed, rotates back to the conveying direction. For the time being, timer 1 retains the value 1. After an hour (timer 2 has elapsed), timer 1 is reset to 0 provided that no other blockage has occurred during this period. If other blockages occur within this hour, only two reversing runs would be left to clear them before the drive would stop with External fault Scenario 3: Blockage in the opposite direction Table 6-3: Instruction for Scenario 1 1. Perform steps 1-5 of Scenario The motor stops and moves in the opposite direction once the interlocking time (2s) has elapsed. Counter 1 is incremented. 3. While the drive moves in the opposite direction (or even before), provoke or simulate a situation that causes limit monitor 1 to respond (fault situation). 4. The drive immediately starts a reversing operation and, once the interlocking time (2s) has elapsed, rotates back to the conveying direction. 5. As a fault of one of the limit monitors 2, 3 or 4 is also present, the motor continues its motion in the conveying direction only until the start operation has completed (= Class 10 time elapsed, 10s). 2 and 4 listed above are executed 3 x. 6. Continue with 9, 10 and 11 of Scenario Clear the blockage in the opposite direction by ensuring that limit monitor 1 no longer responds. Note A blockage in the opposite direction never causes a fault message, it only results in immediate reversal in the conveying direction. Entry ID: , V1.0, 08/

50 7 Timestamping 7 Timestamping SIMOCODE pro V can provide digital signals with timestamps, recording every signal change. For statistical evaluation, for example, the... automatic reversing run (output of timer 1), lower current limit in conveying direction reached (output of limit monitor 2), upper current limit in conveying direction reached (output of limit monitor 3), cos φ lower limit in conveying direction reached (output of limit monitor 4), signals could be recorded. For the following reasons... Timestamping is not part of the core content of this application example. Timestamping is only available for the PROFIBUS version of the SIMOCODE device. Timestamping requires that the used DP master supports the functions for time synchronization via PROFIBUS (see chapter Timestamping in \3\.... the sample project does not include timestamping of the above events. However, the following table provides a brief description of its configuration and parameterization on the SIMOCODE side. Entry ID: , V1.0, 08/

51 7 Timestamping Configuring time synchronization and parameterizing timestamping Table 7-1: Configuring and parameterizing time synchronization 1. In the project tree, select Parameters Open Standard functions > Time stamping. 2. To timestamp the events suggested above, make the entries as shown in the figure 3. Check Time stamping active. 4. Open the Properties of Control device_1 and in General, check Time synchronization. The Interval must match the configuration of the time master. Entry ID: , V1.0, 08/

Application example and brief instruction 04/2015. LOGO! App V3.0. LOGO! 8 and LOGO! 7

Application example and brief instruction 04/2015. LOGO! App V3.0. LOGO! 8 and LOGO! 7 Application example and brief instruction 04/2015 LOGO! App V3.0 LOGO! 8 and LOGO! 7 Warranty and Liability Warranty and Liability Note The Application Examples are not binding and do not claim to be complete

More information

Applications & Tools. Configuration of Messages and Alarms in WinCC (TIA Portal) WinCC (TIA Portal) Application description December 2012

Applications & Tools. Configuration of Messages and Alarms in WinCC (TIA Portal) WinCC (TIA Portal) Application description December 2012 Cover Configuration of Messages and Alarms in WinCC (TIA Portal) WinCC (TIA Portal) Application description December 2012 Applications & Tools Answers for industry. Siemens Industry Online Support This

More information

How To Use An American Zw.Com V20-20 (V20) V20 (Veu) V2.20 (Femalese) V1.2.2 (V2.1) V3.

How To Use An American Zw.Com V20-20 (V20) V20 (Veu) V2.20 (Femalese) V1.2.2 (V2.1) V3. Cover SINAMICS V: Speed Control of a V20 with S7-1200 via USS Protocol in TIA Portal SINAMICS V20, SIMATIC S7-1200 Short Documentation November 2012 Applications & Tools Answers for industry. Siemens Industry

More information

SIMOCODE ES Online Help. SIMOCODE pro. SIMOCODE ES V12 Online Help. Tooltips SIRIUS + SIMOCODE. General information. Device configuration

SIMOCODE ES Online Help. SIMOCODE pro. SIMOCODE ES V12 Online Help. Tooltips SIRIUS + SIMOCODE. General information. Device configuration SIMOCODE ES Online Help Tooltips SIRIUS + SIMOCODE 1 General information 2 SIMOCODE pro Programming and Operating Manual Device configuration 3 Diagnostics & Online 4 Parameterization of the modules 5

More information

RAID systems within Industry

RAID systems within Industry White Paper 01/2014 RAID systems within Industry Functioning, variants and fields of application of RAID systems. A white paper issued by: Siemens. Siemens AG 2014. All rights reserved Warranty and liability

More information

Applications & Tools. Migration to TIA Portal. WinCC Basic / Comfort / Advanced STEP 7 V5.x / WinCC flexible 2008 SP3. Migration Guide September 2013

Applications & Tools. Migration to TIA Portal. WinCC Basic / Comfort / Advanced STEP 7 V5.x / WinCC flexible 2008 SP3. Migration Guide September 2013 Migration to TIA Portal WinCC Basic / Comfort / Advanced STEP 7 V5.x / WinCC flexible 2008 SP3 Migration Guide September 2013 Applications & Tools Answers for industry. Siemens Industry Online Support

More information

Application about Communication

Application about Communication Application about Communication Integration of ET200S PROFIBUS I/O in a Rockwell CompactLogix Controller Configuration Example Warranty, liability and support Note The application examples are not binding

More information

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE T I A Training Document Page 1 of 25 Module This document has been written by Siemens AG for training

More information

Tool for Control Technology

Tool for Control Technology Tool for Control Technology Tools Collection of Functions for Programming Tasks Tools Collection of Functional Examples for Date and Time Warranty, Liability and Support Note The application examples and

More information

Application on Control Technology

Application on Control Technology Application on Control Technology Programming Example in Ladder Logic Getting the Status for the CPU LED Indicators Note The application examples are not binding and do not claim to be complete regarding

More information

EXPERIMENT 2 TRAFFIC LIGHT CONTROL SYSTEM FOR AN INTERSECTION USING S7-300 PLC

EXPERIMENT 2 TRAFFIC LIGHT CONTROL SYSTEM FOR AN INTERSECTION USING S7-300 PLC YEDITEPE UNIVERSITY ENGINEERING & ARCHITECTURE FACULTY INDUSTRIAL ELECTRONICS LABORATORY EE 432 INDUSTRIAL ELECTRONICS EXPERIMENT 2 TRAFFIC LIGHT CONTROL SYSTEM FOR AN INTERSECTION USING S7-300 PLC Introduction:

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

Getting Started - SINAMICS Startdrive. Startdrive. SINAMICS Getting Started - SINAMICS Startdrive. Introduction 1

Getting Started - SINAMICS Startdrive. Startdrive. SINAMICS Getting Started - SINAMICS Startdrive. Introduction 1 Introduction 1 Connecting the drive unit to the PC 2 Startdrive SINAMICS Getting Started - SINAMICS Startdrive Getting Started Creating a project 3 Going online and incorporating devices 4 Commissioning

More information

1 Application Description... 3. 1.1 Objective... 3 1.2 Goals... 3

1 Application Description... 3. 1.1 Objective... 3 1.2 Goals... 3 Contents Moxa Technical Support Team support@moxa.com 1 Application Description... 3 1.1 Objective... 3 1.2 Goals... 3 2 System Topology... 3 3 Hardware and Software Requirements... 4 4 Configuration...

More information

SIMATIC HMI. WinCC flexible 2008 Getting Started - First-Time Users Getting Started. Printout of the Online Help 06/2008 A5E00279548-04

SIMATIC HMI. WinCC flexible 2008 Getting Started - First-Time Users Getting Started. Printout of the Online Help 06/2008 A5E00279548-04 SIMATIC HMI WinCC flexible 2008 Getting Started - First-Time Users Getting Started Printout of the Online Help 06/2008 A5E00279548-04 Safety Guidelines This manual contains notices you have to observe

More information

Programming A PLC. Standard Instructions

Programming A PLC. Standard Instructions Programming A PLC STEP 7-Micro/WIN32 is the program software used with the S7-2 PLC to create the PLC operating program. STEP 7 consists of a number of instructions that must be arranged in a logical order

More information

Applications & Tools. Master Slave Communication via a CM PtP using the Modbus RTU Protocol. S7-1500 CM PtP RS422/485 HF, ET 200SP CM PtP

Applications & Tools. Master Slave Communication via a CM PtP using the Modbus RTU Protocol. S7-1500 CM PtP RS422/485 HF, ET 200SP CM PtP Cover Master Slave Communication via a CM PtP using the Modbus RTU Protocol S7-1500 CM PtP RS422/485 HF, ET 200SP CM PtP Application Description March 2013 Applications & Tools Answers for industry. Siemens

More information

How to read this guide

How to read this guide How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information

More information

Parameterization, Configuration and Visualization with SIRIUS

Parameterization, Configuration and Visualization with SIRIUS Parameterization, Configuration and Visualization with SIRIUS Price groups 200, 346, 42B, 42C, 42D, 42H, 42J, 4N1 /2 Introduction /5 Soft Starter ES /9 SIRIUS 3RW44 soft starter block library for SIMATIC

More information

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library. Deleting program block Main [OB1] Copying program blocks

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library. Deleting program block Main [OB1] Copying program blocks Loading the block library 1 Deleting program block Main [OB1] 2 TIA Portal SIMATIC Getting Started Copying program blocks 3 Cyclic interrupt OB 4 Copying tag tables 5 Compiling a project 6 Load project

More information

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL E04

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL E04 Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL PROFINET with IO Controller CPU 315F-2 PN/DP and IO Device ET 200S T I A Training Document Page 1 of

More information

PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL

PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL Rev. D PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL 10 BORIGHT AVENUE, KENILWORTH NEW JERSEY 07033 TELEPHONE: 800-524-0273 FAX: 908-686-9317 TABLE OF CONTENTS Page

More information

SIMATIC S7-300. Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01

SIMATIC S7-300. Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01 SIMATIC S7-300 Getting Started for First Time Users Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01 Safety Guidelines This manual contains notices you have to observe in order to ensure your personal

More information

FAQ about Drive Technology

FAQ about Drive Technology FAQ about Drive Technology Technology CPU FAQ Operation of SINAMICS S120 (Firmware V2.2) with the Technology CPU (S7 Technology V2.0 SP1) SINAMICS S120 at Technology CPU Entry ID: 21767896 Table of Contents

More information

SIMATIC HMI. WinCC flexible Getting Started First Time User. Order number 6ZB5370-1CL02-0BA2. Edition 04/2006 A5E00279548-03

SIMATIC HMI. WinCC flexible Getting Started First Time User. Order number 6ZB5370-1CL02-0BA2. Edition 04/2006 A5E00279548-03 SIMATIC HMI WinCC flexible Getting Started First Time User Order number 6ZB5370-1CL02-0BA2 Edition 04/2006 A5E00279548-03 Safety Guidelines This manual contains notices which you should observe to ensure

More information

DeviceNet Bus Software Help for Programming an Allen Bradley Control System

DeviceNet Bus Software Help for Programming an Allen Bradley Control System FBP FieldBusPlug V7 DeviceNet Bus Software Help for Programming an Allen Bradley Control System DeviceNet Software Help for Programming an Allen Bradley Control System Contents Page General Purpose...

More information

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3. Simatic. Readme. Readme

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3. Simatic. Readme. Readme Validity 1 Improvements in STEP 7 2 Simatic Improvements in WinCC 3 2012 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety,

More information

CHAPTER 11: Flip Flops

CHAPTER 11: Flip Flops CHAPTER 11: Flip Flops In this chapter, you will be building the part of the circuit that controls the command sequencing. The required circuit must operate the counter and the memory chip. When the teach

More information

Application Unit, MDRC AB/S 1.1, GH Q631 0030 R0111

Application Unit, MDRC AB/S 1.1, GH Q631 0030 R0111 , GH Q631 0030 R0111 SK 0010 B 98 The application unit is a DIN rail mounted device for insertion in the distribution board. The connection to the EIB is established via a bus connecting terminal at the

More information

Cover. WinCC/Server Virtualization. WinCC. Technical Information April 2011. Applications & Tools. Answers for Industry.

Cover. WinCC/Server Virtualization. WinCC. Technical Information April 2011. Applications & Tools. Answers for Industry. Cover / Virtualization Technical Information April 2011 Applications & Tools Answers for Industry. Industry Automation and Drive Technologies Service & Support Portal This article is taken from the Service

More information

SIMATIC S7-1200. It s the Interplay that makes the difference. Siemens AG 2010. All Rights Reserved.

SIMATIC S7-1200. It s the Interplay that makes the difference. Siemens AG 2010. All Rights Reserved. SIMATIC S7-1200 It s the Interplay that makes the difference SIMATIC S7-1200 Controller SIMATIC S7-1200 CPUs CPU 1211C 3 configurations per CPU Dimensions W x H x D (mm) CPU 1212C CPU 1214C DC/DC/DC, AC/DC/RLY,

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

The goal is to program the PLC and HMI to count with the following behaviors:

The goal is to program the PLC and HMI to count with the following behaviors: PLC and HMI Counting Lab The goal is to program the PLC and HMI to count with the following behaviors: 1. The counting should be started and stopped from buttons on the HMI 2. The direction of the count

More information

PROCESS AUTOMATION PLANNING AND INTEGRATION INFORMATION LB8106* Integration in Siemens SIMATIC PCS 7

PROCESS AUTOMATION PLANNING AND INTEGRATION INFORMATION LB8106* Integration in Siemens SIMATIC PCS 7 PROCESS AUTOMATION PLANNING AND INTEGRATION INFORMATION LB8106* Integration in Siemens SIMATIC PCS 7 With regard to the supply of products, the current issue of the following document is applicable: The

More information

Industrial Communication

Industrial Communication Industrial Communication / AS-Interface System overview /5 - Transmission technology /6 - Configuration examples /7 - Communication overview Slaves Contactors and contactor assemblies for AS-Interface

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

Applications & Tools. Control and Status Check of the digital Output of a SCALANCE W748-1 via S7 PN-CPU and SNMP Library

Applications & Tools. Control and Status Check of the digital Output of a SCALANCE W748-1 via S7 PN-CPU and SNMP Library Cover Control and Status Check of the digital Output of a SCALANCE W748-1 via S7 PN-CPU and SNMP Library SIMATIC S7 PN-CPUs, SCALANCE W700 Application Description April 2012 Applications & Tools Answers

More information

SIMATIC Safety Workshop

SIMATIC Safety Workshop Experience the fast and easy way to safe machines at highest productivity Unrestricted Siemens Industry, Inc. 2014-2015 All rights reserved. - Agenda Introduction Why Machine Safety? Why Safety PLC s?

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

Training Document for Integrated Automation Solutions Totally Integrated Automation (TIA) MODULE M1

Training Document for Integrated Automation Solutions Totally Integrated Automation (TIA) MODULE M1 Training Document for Integrated Automation Solutions Totally Integrated Automation (TIA) MODULE M1 Startup Programming of the SIMATIC S7-1200 with TIA Portal V10 T I A Ausbildungsunterlage Seite 1 von

More information

Software Manual RS232 Laser Merge Module. Document # SU-256521-09 Rev A

Software Manual RS232 Laser Merge Module. Document # SU-256521-09 Rev A Laser Merge Module Document # SU-256521-09 Rev A The information presented in this document is proprietary to Spectral Applied Research Inc. and cannot be used for any purpose other than that for which

More information

MINIMAT-EC-Servo Screwdriver Spindles

MINIMAT-EC-Servo Screwdriver Spindles Screwdriving technology Automation Air motors Air tools Screwdriver Spindles electric MINIMAT-EC-Servo Screwdriver Spindles Maximum Flexibility and process Control Straight Spindle Form - Torque range

More information

Configuration Instruction

Configuration Instruction Configuration Instruction SIMATIC PCS 7 SIMATIC IT Integration SIMATIC PCS 7 / SIMATIC IT Integration Pack 2007 Data exchange between SIMATIC IT Production Modeler/ SIMATIC IT Historian and SIMATIC PCS

More information

Remote Monitoring of Woodward easygen-3000

Remote Monitoring of Woodward easygen-3000 Remote Monitoring of Woodward easygen-3000 HMS Industrial Networks AB Page 1 (22) About this Document HMS application notes are not binding and do not claim to be complete in regard to configuration and

More information

Application about Communication

Application about Communication Application about Communication Integration of a MicroMaster Drive with Rockwell ControlLogix using DeviceNet Third-Party Integration Warranty, liability and support Note The application examples are not

More information

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4

Visualization SIMATIC. Visualization. Present sample project. HMI configuration. Insert HMI device from libraries 3. Configuring HMI connection 4 Present sample project 1 HMI configuration 2 SIMATIC Getting Started Insert HMI device from libraries 3 Configuring HMI connection 4 Configuring system diagnostics 5 Simulating an HMI device 6 05/2014

More information

Number 1 in efficiency

Number 1 in efficiency PowerXL DE1 Variable Speed Starter www.eaton.eu/de1 Number 1 in efficiency The easiest way of variable motor speed NEW Variation DE11 The new device category! The PowerXL DE1 Variable Speed Starter Why

More information

ABB i-bus EIB Logic Module LM/S 1.1

ABB i-bus EIB Logic Module LM/S 1.1 Product Manual ABB i-bus EIB Logic Module LM/S 1.1 Intelligent Installation System Contents page 1 General... 3 1.1 About this manual... 3 1.2 Product and functional overview... 3 2 Device technology...

More information

2011, The McGraw-Hill Companies, Inc. Chapter 5

2011, The McGraw-Hill Companies, Inc. Chapter 5 Chapter 5 5.1 Processor Memory Organization The memory structure for a PLC processor consists of several areas, some of these having specific roles. With rack-based memory structures addresses are derived

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves

More information

Generator Differential Relay Electrical Apparatus

Generator Differential Relay Electrical Apparatus Generator Differential Relay Electrical Apparatus MD3G Rotating Machine Differential Relay 150-3 The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor

More information

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections

More information

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030)

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) PART 1 - GENERAL SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) 1.01 SUMMARY This section describes the operation and control of a drip irrigation system. The major components

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

Install the DeviceNet Module using the following procedure:

Install the DeviceNet Module using the following procedure: Installation INSTALLATION INSTRUCTIONS: MCD DEVICENET MODULE Order Code: 175G9002 1. Installation Install the DeviceNet Module using the following procedure: 1. Remove control power and mains supply from

More information

*.ppt 11/2/2009 12:48 PM 1

*.ppt 11/2/2009 12:48 PM 1 Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Applications & Tools. Monitoring Machines and Plants with Network Cameras and SIMATIC HMI Comfort Panels. WinCC V11 Comfort

Applications & Tools. Monitoring Machines and Plants with Network Cameras and SIMATIC HMI Comfort Panels. WinCC V11 Comfort Cover Monitoring Machines and Plants with Network Cameras and SIMATIC HMI Comfort Panels WinCC V11 Comfort Application Description October 2012 Applications & Tools Answers for industry. Siemens Industry

More information

Applications & Tools. Remote Control Concept with SCALANCE S Modules over IPsec-secured VPN Tunnel SCALANCE S. Application Description February 2010

Applications & Tools. Remote Control Concept with SCALANCE S Modules over IPsec-secured VPN Tunnel SCALANCE S. Application Description February 2010 Cover Remote Control Concept with SCALANCE S Modules over IPsec-secured VPN Tunnel SCALANCE S Application Description February 2010 Applications & Tools Answers for industry. Industry Automation and Drives

More information

Siemens AG 2013. LOGO! App V1.0.0 LOGO! Edition 03/2013. Manual. Answers for industry.

Siemens AG 2013. LOGO! App V1.0.0 LOGO! Edition 03/2013. Manual. Answers for industry. LOGO! App V1.0.0 LOGO! Manual Edition 03/2013 Answers for industry. The free of charge LOGO! App enables you to monitor actual process values of your LOGO! 0BA7 application with a smart phone or a tablet

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

DC Motor control Reversing

DC Motor control Reversing January 2013 DC Motor control Reversing and a "Rotor" which is the rotating part. Basically there are three types of DC Motor available: - Brushed Motor - Brushless Motor - Stepper Motor DC motors Electrical

More information

User Manual. AS-Interface Programmer

User Manual. AS-Interface Programmer AS-Interface Programmer Notice: RESTRICTIONS THE ZMD AS-INTERFACE PROGRAMMER HARDWARE AND ZMD AS-INTERFACE PROGRAMMER SOFTWARE IS DESIGNED FOR IC EVALUATION, LABORATORY SETUP AND MODULE DEVELOPMENT ONLY.

More information

SIMATIC. WinCC V7.0. Getting started. Getting started. Welcome 2. Icons 3. Creating a project 4. Configure communication 5

SIMATIC. WinCC V7.0. Getting started. Getting started. Welcome 2. Icons 3. Creating a project 4. Configure communication 5 SIMATIC WinCC V7.0 SIMATIC WinCC V7.0 Printout of the Online Help 1 Welcome 2 Icons 3 Creating a project 4 Configure communication 5 Configuring the Process Screens 6 Archiving and displaying values 7

More information

Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification

Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification Assembly 025A0215 600A0942 Rev. A May 14, 2012 025A0215 Brushless DC Motor Controller Page 1 Revision History ECN # Date Rev Description

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

Transmitter Interface Program

Transmitter Interface Program Transmitter Interface Program Operational Manual Version 3.0.4 1 Overview The transmitter interface software allows you to adjust configuration settings of your Max solid state transmitters. The following

More information

Analog Inputs and Outputs

Analog Inputs and Outputs Analog Inputs and Outputs PLCs must also work with continuous or analog signals. Typical analog signals are 0-10 VDC or 4-20 ma. Analog signals are used to represent changing values such as speed, temperature,

More information

ABB Drives. User s Manual HTL Encoder Interface FEN-31

ABB Drives. User s Manual HTL Encoder Interface FEN-31 ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions

More information

S7-1500 SIMATIC S7-1500. Welcome. Automation task. Hardware section 2. Software section 3. Security. Getting Started 05/2014 A5E03981761-AC

S7-1500 SIMATIC S7-1500. Welcome. Automation task. Hardware section 2. Software section 3. Security. Getting Started 05/2014 A5E03981761-AC Welcome Automation task 1 SIMATIC Hardware section 2 Software section 3 Security 4 Getting Started 05/2014 A5E03981761-AC Legal information Warning notice system This manual contains notices you have to

More information

Using a Modbus TCP to Profibus PA Gateway by IFAK system

Using a Modbus TCP to Profibus PA Gateway by IFAK system Using a Modbus TCP to Profibus PA Gateway by IFAK system AG012314 Objective: Learn how set up the gateway Learn how the data is mapped Equipment: Web browser Modbus TCP Client Ethernet X0 cable or Ethernet

More information

SYSTEM 45. C R H Electronics Design

SYSTEM 45. C R H Electronics Design SYSTEM 45 C R H Electronics Design SYSTEM 45 All in one modular 4 axis CNC drive board By C R Harding Specifications Main PCB & Input PCB Available with up to 4 Axis X, Y, Z, & A outputs. Independent 25

More information

PROFINET IO Diagnostics 1

PROFINET IO Diagnostics 1 PROFINET IO is a very cost effective and reliable technology. However, extensive installations can have thousands of PROFINET IO devices operating on many networks. The reliable operation of these networks

More information

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1 Softstarters Type PSTX Fieldbus communication, Built-in Modbus RTU 1SFC132089M0201 April 2015 1SFC132089M0201 1 1 Modbus RTU The Modbus protocol is a fieldbus protocol that provides full control and status

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

Inwall 4 Input / 4 Output Module

Inwall 4 Input / 4 Output Module Inwall 4 Input / 4 Output Module IO44C02KNX Product Handbook Product: Inwall 4 Input / 4 Output Module Order Code: IO44C02KNX 1/27 INDEX 1. General Introduction... 3 2. Technical data... 3 2.1 Wiring Diagram...

More information

Connecting your Victron product to a computer with VE Configure

Connecting your Victron product to a computer with VE Configure Connecting your Victron product to a computer with VE Configure www.victronenergy.com VE configure II is a program used to configure settings/options on a Multi or Quattro. It is necessary to know several

More information

RIGtalk. Revision 5. Owner s Manual 2012.

RIGtalk. Revision 5. Owner s Manual 2012. RIGtalk Revision 5 Owner s Manual 2012 www.westmountainradio.com 1020 Spring City Drive Waukesha, WI 53186 262-522-6503 sales@westmountainradio.com 2012 West Mountain Radio, All rights reserved. All trademarks

More information

PROGRAMMABLE LOGIC CONTROL

PROGRAMMABLE LOGIC CONTROL PROGRAMMABLE LOGIC CONTROL James Vernon: control systems principles.co.uk ABSTRACT: This is one of a series of white papers on systems modelling, analysis and control, prepared by Control Systems Principles.co.uk

More information

ABB i-bus EIB Universal Interfaces US/U 4.2 US/U 2.2

ABB i-bus EIB Universal Interfaces US/U 4.2 US/U 2.2 Product Manual ABB i-bus EIB US/U 4.2 US/U 2.2 Intelligent Installation Systems Intelligent and limitless Contents Page 1 General............................................. 3 1.1 Product and functional

More information

CPU 317-2 PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device

CPU 317-2 PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device SIMATIC PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device Introduction 1 Preparation 2 Learning units 3 Further Information

More information

Digital and Analog I/O

Digital and Analog I/O 70072-0127-07 TECHNICAL NOTE 02/2007 Digital and Analog I/O This document discusses the application and configuration of digital and analog inputs/outputs (I/O). Details are for both onboard I/O and external

More information

CPUs - CPU 315-2 PN/DP

CPUs - CPU 315-2 PN/DP Overview The CPU with a medium program memory and quantity framework High processing performance in binary and floating-point arithmetic Used as a central controller on production lines with central and

More information

ABB industrial drives. Quick start-up guide Drive Manager for SIMATIC

ABB industrial drives. Quick start-up guide Drive Manager for SIMATIC ABB industrial drives Quick start-up guide Drive Manager for SIMATIC List of related manuals Drive firmware manuals and guides FPBA-01 PROFIBUS DP adapter module user s manual RPBA-01 PROFIBUS DP Adapter

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

EDI Distributor Control Interface Wiring and Setup Instructions

EDI Distributor Control Interface Wiring and Setup Instructions Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls

More information

Cover sheet. Reading out the topology data of a PROFINET IO system SFB52 "RDREC" FAQ September 2009. Service & Support. Answers for industry.

Cover sheet. Reading out the topology data of a PROFINET IO system SFB52 RDREC FAQ September 2009. Service & Support. Answers for industry. Cover sheet Reading out the topology data of a PROFINET IO system FAQ September 2009 Service & Support Answers for industry. Question This entry originates from the Service&Support Portal of Siemens AG,

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01 ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions

More information

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES 204.CAxxx 204.CBxxx 204.UBxxx 204.WBxxx MP36289 1 ZP90856-GB-6 INDICE 1 SYSTEM DESCRIPTION... 4 1.1 MODES OF OPERATION... 4 2 USER INTERFACE... 6 2.1

More information

PG DRIVES TECHNOLOGY R-NET PROGRAMMER R-NET PROGRAMMING SOFTWARE - DEALER ELECTRONIC MANUAL SK78809/2 SK78809/2 1

PG DRIVES TECHNOLOGY R-NET PROGRAMMER R-NET PROGRAMMING SOFTWARE - DEALER ELECTRONIC MANUAL SK78809/2 SK78809/2 1 R-NET PROGRAMMING SOFTWARE - DEALER ELECTRONIC MANUAL SK78809/2 SK78809/2 1 PG Drives Technology 2009 All rights reserved. This manual is furnished under copyright and may only be used in accordance with

More information

SYSTEM 4C. C R H Electronics Design

SYSTEM 4C. C R H Electronics Design SYSTEM 4C C R H Electronics Design SYSTEM 4C All in one modular 4 axis CNC drive board By C R Harding Specifications Main PCB & Input PCB Available with up to 4 Axis X, Y, Z, A outputs. Independent 25

More information

Training Document for SIMIT SCE. MODULE G2 'Startup System Simulation with SIMIT SCE V7

Training Document for SIMIT SCE. MODULE G2 'Startup System Simulation with SIMIT SCE V7 Training Document for SIMIT SCE MODULE G2 Training Document for SIMIT SCE Page 1 ofn 39 Module G2 Status December 2009 Trademark SIMIT is a trademark of Siemens AG. The other names in this document may

More information

Tebis application software

Tebis application software Tebis application software Input products / ON / OFF output / RF dimmer Electrical / Mechanical characteristics: see product user manual Product reference Product designation TP device RF devices WYC81xQ

More information

DeviceNet Communication Manual

DeviceNet Communication Manual DeviceNet Communication Manual Soft-Starter Series: SSW-07/SSW-08 Language: English Document: 10000046963 / 00 03/2008 Summary ABOUT THIS MANUAL... 5 ABBREVIATIONS AND DEFINITIONS... 5 NUMERICAL REPRESENTATION...

More information

CB15/CB155. PROFIBUS Module

CB15/CB155. PROFIBUS Module CB15/CB155 PROFIBUS Module Contents Warning and Caution Notes 1. OVERVIEW 1.1 Description and Features 1.2 Application on a PROFIBUS Link 2. INSTALLATION 2.1 Installing the Module 2.1.1 CB15 Installation

More information

Installation, Operation & Service Manual

Installation, Operation & Service Manual Installation, Operation & Service Manual 0RQLWRU Pulse Monitor Software Version 1 0 1 Pulse Monitor Card Software Revision 1 4 0 Pulse Monitor Card Product Revision 0 1 0 0 February, 2007 Copyright 2007,

More information

How to connect your Victron to a computer with VE Bus Quick Configure

How to connect your Victron to a computer with VE Bus Quick Configure How to connect your Victron to a computer with VE Bus Quick Configure Before connecting your Victron to a computer the following is important: - Only identical models with VE Bus software (see sticker

More information