Experimental study on frost growth and dynamic performance of air source heat pump system

Size: px
Start display at page:

Download "Experimental study on frost growth and dynamic performance of air source heat pump system"

Transcription

1 Available online at Applied Thermal Engineering 28 (2008) Experimental study on frost growth and dynamic performance of air source heat pump system Xian-Min Guo a,b, *, Yi-Guang Chen b, Wei-Hua Wang b, Chun-Zheng Chen a a Energy and Power Engineering, Xi an Jiaotong University, Xi an , PR China b School of Mechanical Engineering, Tianjin University of Commerce, Tianjin , PR China Received 11 April 2007; accepted 6 January 2008 Available online 18 January 2008 Abstract The effect of the frost growth and frost morphology on the performance of an air source heat pump was investigated experimentally. The frost thickness, frost accumulation and the dynamic performance of the heat pump were measured. It is found that the frost growth can be divided into three stages according to the frost morphology. In the initial stage, condensed water freezes and forms a transparent thin ice layer on the fins and tubes firstly, then the granular ices appear and grow gradually on the ice layer, and the column-shaped ice crystals are formed at last. The growth rate of the frost thickness, the heating capacity and COP of the heat pump increase with the frosting time significantly until the column-shaped frost layer is formed. In the second stage, the column-shaped ice crystals grow in its radius rather than in its length, and the frost thickness growth rate decreases or remains to be constant. However, the heating capacity and COP of the heat pump are only slightly affected by frosting on the outdoor coils. In the third stage, the ice crystals mainly grow in its length, and become gradually of an acerose-shaped one, finally a fluffy frost layer is formed. The frost thickness growth rate is about 2 4 times of that in the second stage. The drops per minute in the heating capacity and COP are increased by several times of those in the second stage. In addition, it is found that the frost growth rate and the drop in the performance of the heat pump are highest when the outdoor air temperature is about 0 C with various relative humidity. The experimental results are in agreement with the corresponding simulation data except in the third frosting stage. Ó 2008 Elsevier Ltd. All rights reserved. Keywords: Air source heat pump; Frosting; Dynamic performance; Frost growth; Frost thickness; Experiment 1. Introduction Frost formation on the outdoor heat exchanger of an air source heat pump (ASHP) unit occurs when the surface temperature is both below the dew point of the moist air and the freezing point. Frost accumulation on the surface of the evaporator results in a performance degradation of the ASHP system because the frost layer leads to an increase in thermal resistance and air flow pressure drop across the heat exchanger, hence, causes a decrease in the air flow rate for a fan-driven heat exchanger. When the * Corresponding author. Address: Energy and Power Engineering, Xi an Jiaotong University, Xi an , PR China. Tel./fax: address: xmguo@tjcu.edu.cn (X.-M. Guo). evaporator heat transfer rate is reduced, the evaporation temperature, the suction pressure and the system capacity drop accordingly. The lower evaporation temperature may create mechanical problems in the system such as liquid refrigerant flood back to the compressor and periodic defrost is required. Therefore, it is important to investigate the frosting process and its effects for improving the performance and operational reliability of the ASHP system under frosting conditions. A number of theoretical and experimental studies [1 10] on the performance of heat exchangers under frosting conditions were reported, and the effects of ambient and geometry parameters on the performance of the heat exchangers were discussed comprehensively. In most of these experimental [1 4,7] and numerical [5,6] studies the air flow rate /$ - see front matter Ó 2008 Elsevier Ltd. All rights reserved. doi: /j.applthermaleng

2 2268 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) Nomenclature A face area, m 2 d absolute humidity, kg/kg dry air h air specific enthalpy, J/kg M fr frost accumulation mass, kg q a air volume flow rate, m 3 /s p pressure, N/m 2 P consumption power, W Q h heating capacity, W COP coefficient of performance RH relative humidity T temperature, C t time, s V velocity, m/s d fr frost thickness, m q a air density, kg/m 3 Subscripts i inlet o outlet av average a air c condenser e evaporator fr frost p pipe wall 1 6 state point number and refrigerant temperature were assumed as constant during the frosting process, the changes inside a practical evaporator, such as the variation of the evaporation temperature and refrigerant liquid dry out position, was not taken into account, and only in a few of the studies [8 10] the decrease in the air flow rate due to frost accumulation was considered. However, the constant flow rate constraint is unlikely for a fan-driven heat exchanger used in ASHP unit. Tso et al. [11,12] developed a general distributed model with two-phase flow for refrigerant coupled with a frost model for studying the dynamic behavior of an evaporator validated experimentally. In fact, frost growth will cause the changes of cycle parameters of the ASHP system, such as the evaporating and condensing temperatures, which will in turn affect frost formation. Therefore, it is necessary to investigate the performance of ASHP unit by coupling the frosting process with the operating process of ASHP system. In despite of a large amount of studies on the performance of the heat exchangers under frosting conditions, the published literatures for study on the performance of ASHP system under frosting conditions are limited. Senshu et al. [13] and Yasuda et al. [14] studied the performance of a heat pump air conditioner under JIS frosting conditions numerically and experimentally. Miller [15] tested an airto-air split-system residential heat pump under variable frosting conditions. The experimental results suggested that the performance of the heat pump was slightly affected by frosting. The present authors [16,17] developed a model, which coupled the frost growth model with the refrigerant-side parameters variation of ASHP system due to the frost formation, to predict the performance of ASHP unit under frosting conditions. The simulated results were compared with the experimental data, but in that work the frost thickness was not measured. The purpose of this paper is to observe the frost growth process and investigate its corresponding effect on the performance of ASHP system. An ASHP unit with 11.2 kw rated refrigeration capacity was tested under various frosting conditions, and the transient performance of the heat pump, frost accumulation mass, and frost thickness were measured. 2. Experimental apparatus and prototype The experiments were conducted in two psychrometric rooms, in which the air temperature and relative humidity could be controlled respectively to be the desired values. The experimental prototype was a split-type heat pump air conditioner with 11.2 kw rated refrigeration capacity. The test outdoor and indoor units were connected by a pair of 5 m long well insulated pipes. The indoor unit was located in the indoor psychrometric room and its discharge air was fed into a chamber, in which the discharge air was adequately mixed and the pressure and temperature were measured. To determine the air flow rate through the indoor heat exchanger, the discharge air was exhausted into the room through the nozzles by a variable speed fan. The outdoor unit was located in the outdoor psychrometric room. The schematic diagrams of the experimental apparatus and the test ASHP system with measuring points are shown in Figs. 1 and 2, respectively Psychrometric rooms As shown in Fig. 1, to obtain the air temperature and relative humidity in the rooms, the air dry/wet bulb temperatures in both of the psychrometric rooms were measured by using Pt 100 X RTD sensors (±0.1 C) in the sampling ducts, in which the velocity was about 5 m/s. The air temperature and relative humidity in the outdoor and indoor rooms were adjusted by two sets of air handling units (AHU). Each AHU contained a cooling coil, an electrical heater, and a steam humidifier, which were controlled by a computer program using PID control algorithm to keep the ambient air parameters at the desired values. The air flow rate through the indoor exchanger was measured by the multiple nozzles, across which the pressure drop was

3 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) Fig. 1. Schematic diagram of experimental apparatus. Fig. 2. Schematic diagram of test ASHP system and measuring points. detected in terms of a precision difference pressure transducer (±0.08%). The air flow rate was controlled to be a fixed value over all the experiments by adjusting the rotation speed of the variable speed centrifugal fan. The outlet air dry/wet bulb temperatures of the indoor heat exchanger were measured by using Pt 100 X RTD sensors (±0.1 C). The power consumption of the test heat pump was measured in terms of a precision power transducer (±0.5%). From the measured inlet and outlet parameters of the indoor heat exchanger, the heating capacity and COP of the ASHP unit was estimated from Q h ¼ q a;c q a;c ðh c;o h c;i Þ for condenser side ð1þ COP ¼ Q h =P ð2þ where the air density and the air specific enthalpy were obtained from the psychrometric chard according to the measured dry/wet bulb temperatures Parameters measurement of the outdoor heat exchanger and HP system The entering air velocity, dry-bulb temperature and relative humidity were measured with twelve velocity sensors (±0.5%) and twelve dry-bulb temperature/relative humidity multi-sensors (±0.1 C, 2%RH), which were located on the 4 by 3 sensor grid in the upstream of the outdoor heat exchanger. Four dry-bulb temperature/relative humidity multi-sensors (±0.1 C, 2%RH) were located in the downstream of the outdoor coil to measure the outlet air temperature and relative humidity. The airflow rate through the outdoor heat exchanger (evaporator), the frost accumulation mass, and the average inlet and outlet air enthalpies were determined from the average measured parameters. The frost accumulation mass in the period of Dt was calculated from

4 2270 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) DM fr ¼ q a;e A e V av Dt ðd e;i d e;o ÞðkgÞ ð1 þ d e;i Þ The heating capacity of the ASHP unit was estimated from energy balance of the ASHP system as Eq. (4) Q h ¼ q a;e A e V av ðh e;i h e;o Þ þ P for evaporator side ð4þ where the air density, the absolute humidity, and the air specific enthalpy were obtained from the psychrometric chard according to the measured dry/wet bulb temperatures. During the experiments the error between the calculated heating capacities from Eqs. (1) and (4) was maintained within 5%. The pipe wall temperatures of the outdoor heat exchanger were measured in terms of forty pre-calibrated T-type Table 1 Component parameters of test ASHP unit Parameters Values Heat exchangers Indoor Outdoor Tube length (mm) Number of columns Number of rows 4 2 Air flow rate (m 3 /h) Fin type Wavy fin Wavy fin Out tube diameter (mm) Fin thickness (mm) Fin pitch (mm) Tube spacing (mm) Scroll compressor Refrigeration capacity (kw) Input power (kw) 4.28 Capillary tube Diameter (mm) 2.96 Length (mm) 700 ð3þ copper-constantan thermocouples (±0.1 C) which were stuck on the copper elbows of the evaporator. The refrigerant-side pressures and temperatures were measured in terms of precision pressure transducers (±0.08%) and Pt 100 X RTD sensors (±0.1 C), respectively. The measuring points are shown in Fig. 2. The frost on the fins was observed and recorded by a microscope and a CCD camera every 5 min. The frost thickness was obtained from processing the images captured with the CCD camera through a microscope with a magnification of 90 times on a front view of the outdoor heat exchanger Component parameters of the prototype and experimental procedure The schematic diagram of the test ASHP system with measuring points is shown in Fig. 2. The component parameters of the test ASHP unit are shown in Table 1. There are eight and six refrigerant circuits in the outdoor and indoor heat exchanger, respectively. The tube arrangements are shown in Fig. 3. In this work the air temperature and the relative humidity in the outdoor environmental room were controlled in the ranges of 15 to 5 C and 55 90%, respectively. It was found that the frost formation did not occur or was of no significance on the cold surfaces under the conditions of 55% outdoor air relative humidity. The air temperature and the relative humidity in the indoor environmental room were controlled to be 20 C and 60%, respectively, and the air flow rate across the indoor heat exchanger was kept at 2500 m 3 /h over all the experiments. Before performing the experiments, the AHUs were operated to adjust the indoor and outdoor air parameters. When the air conditions in the rooms reached to the steady state, the frosting experiments were started by running the Fig. 3. Schematic diagram of heat exchangers of test ASHP unit.

5 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) test ASHP unit. The experimental data were recorded every 6 s by the data acquisition system and the computer. 3. Results and discussion 3.1. Frost growth pattern The measured frost thickness and frost growth rate under various outdoor air conditions are shown in Fig. 4. It is noted that the frost layer grows in a manner of three stages. In the initial stage, of which the duration is about min, and the frost thickness growth rate increases with the frosting time. In the second stage the frost thickness growth rate decreases with the frosting time when the outdoor air relative humidity is above 65%, and is nearly invariable when the outdoor air relative humidity is 65%. In the period of last min of the frost growth cycle, the frost thickness rises rapidly with the frosting time, and at the end of the third stage the frost thickness growth rate can reach to times of that in the second stage. For the conditions of a fixed outdoor air temperature, the durations of the initial and third stages are nearly invariable under the outdoor air relative humidity ranging from 65% to 85%, and the duration of the second stage decreases with the increase of relative humidity. For the conditions of a fixed outdoor air relative humidity, the duration of the second stage is minimum when the outdoor air temperature is about 0 C. As shown in Fig. 4, the trend of frost growth with frosting time presents the concave-up curves in the third stage over all test conditions. This frost growth pattern is different from the simulated or experimental concave-down curves reported by Yang [5], Yao [9], Tso [11,12], and Qu [18]. In some ways the present experimental results are similar to the frost thickness curve from images reported by Xia [10], but the frost thickness grows faster in the third stage. The growth pattern of the frost thickness can be explained by the morphological variation of frost, for an example, as shown in Fig. 5 for test condition of 0 C outdoor air temperature and 75% relative humidity. In Fig. 5 Fig. 4. Frost thickness and frost thickness growth rate with frosting time under different conditions.

6 2272 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) Fig. 5. Photographs of frost layer on the fins under condition of Ta,i = 0 C, RH = 75%. the photographs (a) (c), (d) (e) and (f) (i) are corresponded to the initial stage, the second stage, and the third stage, respectively. It can be seen that in the initial stage the condensed water freezes and a transparent thin ice layer is formed on the fins firstly (Fig. 4a), after about 6 min from the beginning of frosting the granular ices appear and grow gradually on the surface (Fig. 4b), and then the columnshaped crystals are formed (Fig. 4c). In this stage the frost thickness growth rate increase with time until the columnshaped ice is formed. In the second stage, some melted water droplets seemed to be visible on the top of the ice columns, so the column-shaped crystals grow in its radius rather than in its length (Fig. 4d f). As a result, the frost thickness rises slowly. In the last about 20 min of the frost growth cycle, the column-shaped ice crystals grow mainly in its length, and the ice crystals become gradually of an acerose-shaped one (Fig. 4g i), finally a fluffy frost layer through which air can still pass across the coil is formed, so in the period the frost thickness grows very rapidly. Therefore, the three stage patterns of frost growth may be mainly attributed to the morphological variation of the frost crystals. Qu [18] reported that the frost layer thickness increased stepwise during the frost formation process on a cold plate,

7 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) and the phenomena was attributed to the column-shaped ice crystals growing alternately in its length and radius. In this work, we found the similar stepwise growth phenomena of the frost thickness, but the alternateness of slow and rapid increasing in the frost thickness occurred only once in the second and third stages. This is different from the multi-cycle pattern reported by Qu [18]. However, it is considered that the morphological variation of frost in the third stage is caused by the rapid decrease in the wall temperature and air flow rate as shown in Figs. 6 and 7. It is seen that the wall temperature and air flow rate in the third stage is significantly reduced due to the insulating and blocking effects of the frost layer, and the drops will in turn affect the frosting process. As a result, a vicious spiral of the frost growth and the decrease in the wall temperature and the air flow rate is formed. Hence the frost thickness increased rapidly in the third stage Effects of frosting on dynamic performance of ASHP system Figs. 8 and 9 show the heating capacity and COP, and the evaporating and condensing pressures of the test ASHP system as a function of the frosting time under conditions of a fixed outdoor air temperature with various relative humidity. It can be seen from Fig. 8 that the effects of the frost formation on the performance of the ASHP unit are different Fig. 6. Dynamic wall temperature of evaporator in frost growth cycle. Fig. 7. Dynamic face velocity of evaporator in frost growth cycle.

8 2274 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) in the three stages. In the initial stage the heating capacities of the ASHP unit increase with the frosting time, and reach to the peak point by the end of the initial stage. The COP curves present a similar trend with the heating capacity. The improvement in performance of the ASHP unit may be caused by two factors. Firstly, the change of the air-side conditions of the evaporator from dry to wet improves the performance. Secondly, the initial frost deposition makes the surface roughly (Fig. 5b), but its effect on the air flow rate is of no significance (Fig. 7), so the heat transfer coefficient on air-side of the evaporator is increased. Furthermore, the thermal resistance of the frost layer can be ignored due to its very small thickness. As a result, the performance of the ASHP unit is improved in the initial stage. In the second stage, the evaporating pressure and the air flow rate are slightly reduced due to the slow increasing in frost layer (Figs. 9 and 7). Therefore, the heating capacity and COP of the ASHP unit are slightly affected by frosting in this stage. As showing in Fig. 8, in the third stage, just corresponding to the rapid increase in frost thickness, the heating capacity and COP of the ASHP unit reduce rapidly. The drops per minute of the heating capacity and COP can reach to several times of these in the second stage respectively. The fact can be explained as follows. The frost morphological variation in the third stage causes the rapid increase in the frost thickness as showing above, and results in a decrease in outdoor air flow rate and a rapid increase in thermal resistance between moist air Fig. 8. Dynamic heating capacity and COP in frost growth cycle. Fig. 9. Dynamic evaporating and condensing pressures in frost growth cycle.

9 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) and cold surface. As a result, the evaporating pressure and the wall temperature decrease rapidly. The lower wall temperature will in turn result in a faster increase in the frost thickness. In this way a vicious spiral is formed. Thus the performance of the ASHP unit degrades rapidly. Miller s experimental data [15] showed that the performance of the ASHP unit decreased only marginally despite the frost accumulation on the outdoor heat exchanger. However, in our experiments it was not found that the outdoor fans operated through the surging or stalling region as observed in experiments by Miller [15]. Therefore, it is suggested that the frost morphological variation mainly caused the rapid performance degradation in the third stage Effects of outdoor air parameters on frost growth Fig. 10 presents the frost thickness and frost accumulation mass after 35 min from the beginning of the frost-cycle under various test conditions. It is found that the frost thickness and the frost accumulation mass is maximized when the outdoor air temperature is about 0 C with a fixed relative humidity. Further more, the maximum frost thickness and the frost accumulation mass are formed at the same outdoor temperature for different outdoor air relative humidity. In other words, there is a peak frosting outdoor air temperature, under which the frost growth rate is maximum. The experimental peak frosting outdoor air temperature for the test ASHP unit is about 0 C at all outdoor air relative humidity level. The phenomena can be explained as follows. When the outdoor air temperature is increased with a fixed relative humidity, both of the air absolute humidity and the wall temperature of the evaporator will increase correspondingly. The increase in the air absolute humidity is benefit to frost formation on the cold surface, but the increase in the wall temperature makes against frost formation. Therefore, there is a most favorable condition for frost formation. Fig. 10. Comparison of frost accumulation mass and frost thickness after 35 min operating.

10 2276 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) Comparison of experimental data with simulated results The present authors developed a quasi-steady model to predict the dynamic performance of a heat pump system under frosting conditions [16,17]. The two-phase flow distributed model was used for the analysis of refrigerant flow in heat exchangers, and was coupled with a frost model for studying the dynamic behavior of the evaporator. The flow in the capillary tube was considered as homogeneous, and the delay of flash point was included quantitatively. The fitted performance curves of the compressor and the outdoor heat exchanger fans were used in the model to determine the refrigerating capacity, the power consumption, the refrigerant mass flow rate of the compressor, and the air flow rate of the fans, respectively. The model and simulation method were described in detail by Chen et al. [16] and Guo et al. [17]. In this paper the dynamic performance of the test ASHP unit under frosting conditions was predicted by using the presented model. The simulated results under the condition of 0 C outdoor air temperature and 75% relative humidity were compared with the experimental results as shown in Figs. 11 and 12. Fig. 11 presents a comparison between the experimental and simulated frost accumulation mass and frost thickness. It is noted that the simulated frost accumulation mass increases linearly with the frosting time, and is in agreement with the experimental data. The experimental frost accumulation mass increases faster within the prior Fig. 11. Comparison of experimental frost accumulation mass and frost thickness with simulated results under condition of T a,i =0 C, RH = 75%. Fig. 12. Comparison of experimental heating capacity and COP with simulated results under condition of T a,i =0 C, RH = 75%.

11 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) min and then slower than simulated data. The simulated frost thickness grows linearly with the frosting time before its rapidly increasing at about 57 min. It is found that the experimental frost growth rate in the first and third stages is greater than the simulated one, especially in the third stage, the experimental frost growth rate is about 2 3 times of the simulated one. As described above, in the third frosting stage the ice crystals on the fins and pipes changes gradually to an acerose-shaped, finally a fluffy frost layer, therefore the frost thickness grows rapidly. However, the morphological variation of the frost crystals is not taken into account in the simulation model. As a result, the maximum error between the simulated and experimental frost thickness reaches to about 25% in the third frosting stage. It is found from Fig. 12 that the trend of the simulated dynamic performance of ASHP unit is consistent with the experimental results. The error between the experimental data and simulated results is within 8%. In the initial frosting stage, the experimental heating capacity and COP increase faster than simulated one. The causes may be that in the simulation model the frost growth is assumed in a fully developed period and the frost formation starts from the steady state of the system. In the experiments frost formation occurs before its reaching to the steady state of the test HP system. In the third stage the experimental performance of the ASHP unit decline faster than simulated results, the decreasing rate of the experimental heating capacity is about two times of that of the simulated data. As mentioned above, the rapid falling in the performance of ASHP unit can be attributed to the rapid frost growth caused by the variation of frost morphology. 5. Conclusions The frost growth on the outdoor heat exchanger and the dynamic performance of an ASHP unit under frosting conditions was experimentally investigated with consideration of the fan performance curves and the variable refrigerantside parameters of the system. The effects of the outdoor air parameters on the frost growth as well as the performance of the ASHP unit are discussed. The experimental results are compared with the simulated data. (1) The frost layer on the outdoor heat exchanger grows in a manner of three stages. In the initial stage, the frost layer goes through a transparent thin ice layer and a granular ice layer, at last form a columnshaped ice crystal layer. The frost thickness growth rate increase with the frosting time in this stage. The performance of the ASHP unit is improved due to the rough surface formed by the initial frost layer. After the first stage, the column-shaped ice crystals on the frost surface grow in its radius rather than in its length, therefore, the frost thickness growth rate decreases or keeps nearly at a constant value with the frosting time. The heating capacity and COP of the test ASHP unit are only slightly affected by frosting on the outdoor coils due to a slow frost thickness growth. In the third stage the column-shaped ice crystals on the frost surface grow in its length rather than in its radius, thus the acerose-shaped ice crystals on the frost layer are formed, and the frost thickness growth rate increases rapidly to about times of that in the second stage. The performance of the ASHP unit decays rapidly, and the decreasing rates of the heating capacity and COP can reach to a level of several times of these in the second stage. The experimental results suggested that the rapid performance degradation is mainly caused by the morphological variation of the frost layer in the third stage. (2) The duration of the initial and the third stages are nearly a constant value under conditions of variable outdoor air relative humidity, but the duration of the second stage is longer with lower outdoor air relative humidity. (3) The experimental results indicate that there is a peak frosting outdoor air temperature, under which the frost growth rate is maximized under variable outdoor air relative humidity conditions. For the test ASHP unit the peak frosting outdoor air temperature is about 0 C at all outdoor air relative humidity level. (4) Experimental results are in agreement with the corresponding simulation data except in the third frosting stage. Acknowledgement The financial support of this work by Tianjin Municipal Science and Technology Commission, China, under Grant No. 06YFJMJC05500 is gratefully acknowledged. References [1] S.N. Kondepudi, D.L. O Neal, Effect of frost growth on the performance of louvered finned tube heat exchangers, Int. J. Refrig. 12 (1989) [2] S.N. Kondepudi, D.L. O Neal, Performance of finned-tube heat exchangers under frosting conditions: II. Comparison of experimental data with model, Int. J. Refrig. 16 (1993) [3] D.Q. Deng, L. Xu, S.Q. Xu, Experimental investigation on the performance of air cooler under frosting conditions, Appl. Therm. Eng. (23) (2003) [4] W.M. Yan, H.Y. Li, Y.J. Wu, et al., Performance of finned tube heat exchangers operating under frosting conditions, Int. J. Heat Mass Transfer (46) (2003) [5] D.K. Yang, K.S. Lee, S. Song, Modeling for predicting frosting behavior of a fin tube heat exchanger, Int. J. Heat Mass Transfer 49 (2006) [6] D. Seker, H. Karatas, N. Egrican, Frost formation on fin-and-tube heat exchanges. Part I: Modeling of frost formation on fin-and-tube heat exchangers, Int. J. Refrig. 27 (2004) [7] D. Seker, H. Karatas, N. Egrican, Frost formation on fin-and-tube heat exchanges. Part II: Experimental investigation of frost formation on fin-and-tube heat exchangers, Int. J. Refrig. 27 (2004)

12 2278 X.-M. Guo et al. / Applied Thermal Engineering 28 (2008) [8] H. Chen, L. Thomas, R.W. Besant, Fan supplied heat exchanger fin performance under frosting conditions, Int. J. Refrig. 26 (2003) [9] Y. Yao, Y.Q. Jiang, S.M. Deng, A study on the performance of the airside heat exchanger under frosting in a air source heat pump water heater/chiller unit, Int. J. Heat Mass Transfer (47) (2004) [10] Y. Xia, Y. Zhong, P.S. Hrnjak, et al., Frost, defrost, and refrost and its impact on the air-side thermal-hydraulic performance of louveredfin, flat-tube heat exchangers, Int. J. Refrig. 29 (2006) [11] C.P. Tso, Y.C. Cheng, A.C.K. Lai, Dynamic behavior of a direct expansion evaporator under frosting condition. Part I. Distributed model, Int. J. Refrig. 29 (2006) [12] C.P. Tso, Y.C. Cheng, A.C.K. Lai, Dynamic behavior of a direct expansion evaporator under frosting condition. Part II. Field investigation on a shipping container, Int. J. Refrig. 29 (2006) [13] T. Senshu, H. Yasuda, S. Kuroda, et al., Heat pump performance under frosting conditions: Part I Heat and mass transfer on crossfinned tube heat exchangers under frosting conditions, ASHRAE Trans. 96 (1990) [14] H. Yasuda, T. Senshu, S. Kuroda, et al., Heat pump performance under frosting conditions: Part II Simulation of heat pump cycle characteristics under frosting conditions, ASHRAE Trans. 96 (1990) [15] W.A. Miller, Laboratory examination and seasonal analysis of frosting and defrosting for an air-to-air heat pump, ASHRAE Trans. 93 (1987) [16] Y.G. Chen, X.M. Guo, Numerical simulation on the performance of heat pumps under frost conditions, Proceedings of 5th International Conference on Compressor and Refrigeration, vol. 8, Dalian, China, 2005, pp [17] X.M. Guo, C.S. Wang, W.H. Wang, et al., Numerical simulation and experimental verification on dynamic performance of air source heat pump under frosting conditions, J. Xi an Jiaotong Univ. 40 (2006) [18] K.Y. Qu, S. Komori, Y. Jiang, Local variation of frost layer thickness and morphology, Int. J. Therm. Sci. 45 (2006)

Experimental Evaluation Of The Frost Formation

Experimental Evaluation Of The Frost Formation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Evaluation Of The Frost Formation Yusuke Tashiro Mitsubishi

More information

The Development of a Frost-Less Heat Pump

The Development of a Frost-Less Heat Pump The Development of a Frost-Less Heat Pump V. C. Mei, R. E. Domitrovic, and F. C. Chen, Oak Ridge National Laboratory J. K. Kilpatrick, Tennessee Valley Authority ABSTRACT There are two major concerns associated

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

Frost. On Air-Cooling Evaporators. refrigeration applications at temperatures below freezing. These heat exchangers

Frost. On Air-Cooling Evaporators. refrigeration applications at temperatures below freezing. These heat exchangers The following article was published in ASHRAE Journal, February 2009. Copyright 2009 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Research on the Air Conditioning Water Heater System

Research on the Air Conditioning Water Heater System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

Testing methods applicable to refrigeration components and systems

Testing methods applicable to refrigeration components and systems Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University

More information

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)

More information

Experimental Study of Frost Accumulation on Fan- Supplied Tube-Fin Evaporators

Experimental Study of Frost Accumulation on Fan- Supplied Tube-Fin Evaporators Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Experimental Study of Frost Accumulation on Fan- Supplied Tube-Fin Evaporators

More information

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under

More information

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005 KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed

More information

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

More information

Performance Test of Solar Assisted Solid Desiccant Dryer

Performance Test of Solar Assisted Solid Desiccant Dryer Performance Test of Solar Assisted Solid Desiccant Dryer S. MISHA 1,2,*, S. MAT 1, M. H. RUSLAN 1, K. SOPIAN 1, E. SALLEH 1, M. A. M. ROSLI 1 1 Solar Energy Research Institute, Universiti Kebangsaan Malaysia,

More information

Development and testing of a multi-type air conditioner without using AC inverters

Development and testing of a multi-type air conditioner without using AC inverters Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

Experimental test preparation, performance and data processing

Experimental test preparation, performance and data processing Chapter 4 Experimental test preparation, performance and data processing 4.1 Introduction This chapter is dedicated to the experimental test preparation, performance, and data processing and analysis.

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment

More information

Waste Heat Recovery through Air Conditioning System

Waste Heat Recovery through Air Conditioning System International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn : 2278-800X, www.ijerd.com Volume 5, Issue 3 (December 2012), PP. 87-92 Waste Heat Recovery through Air Conditioning

More information

Energy and Buildings

Energy and Buildings Energy and Buildings 42 (2010) 1833 1840 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild Membrane heat exchanger in HVAC energy recovery

More information

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning

More information

Investigation into the energy consumption of a data center with a thermosyphon heat exchanger

Investigation into the energy consumption of a data center with a thermosyphon heat exchanger Article Mechanical Engineering July 2011 Vol.56 No.20: 2185 2190 doi: 10.1007/s11434-011-4500-5 SPECIAL TOPICS: Investigation into the energy consumption of a data center with a thermosyphon heat exchanger

More information

FROST PREDICTION ON EVAPORATOR COILS OF SUPERMARKET DISPLAY CABINETS USING ARTIFICIAL NEURAL NETWORKS

FROST PREDICTION ON EVAPORATOR COILS OF SUPERMARKET DISPLAY CABINETS USING ARTIFICIAL NEURAL NETWORKS FROST PREDICTION ON EVAPORATOR COILS OF SUPERMARKET DISPLAY CABINETS USING ARTIFICIAL NEURAL NETWORKS D. Datta and S. A. Tassou Department of Mechanical Engineering, Brunel University Uxbridge, Middlesex

More information

New Trends in the Field of Automobile Air Conditioning

New Trends in the Field of Automobile Air Conditioning New Trends in the Field of Automobile Air Conditioning E. Janotkova and M. Pavelek Department of Thermomechanics and Environmental Engineering Brno University of Technology, 61669 Brno, Czech Republic

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

HAIL EFFECTS ON AIR-CONDITIONER PERFORMANCE

HAIL EFFECTS ON AIR-CONDITIONER PERFORMANCE Proceedings of IMECE 2007 2007 ASME International Mechanical Engineering Congress and Eposition November 11-15, 2007, Seattle, Washington, United States IMECE2007-41518 HAIL EFFECTS ON AIR-CONDITIONER

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

P. A. Hilton Ltd REFRIGERATION & AIR CONDITIONING VAPOUR COMPRESSION HEAT PUMPS VENTILATION VOCATIONAL

P. A. Hilton Ltd REFRIGERATION & AIR CONDITIONING VAPOUR COMPRESSION HEAT PUMPS VENTILATION VOCATIONAL REFRIGERATION & AIR CONDITIONING Refrigeration and air conditioning is an aspect of modern life that is accepted almost without thought. Food storage, the long distance transport of foodstuffs, stockpiling

More information

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT

More information

Experimental Study on Super-heated Steam Drying of Lignite

Experimental Study on Super-heated Steam Drying of Lignite Advanced Materials Research Vols. 347-353 (2012) pp 3077-3082 Online available since 2011/Oct/07 at www.scientific.net (2012) Trans Tech Publications, Switzerland doi:10.4028/www.scientific.net/amr.347-353.3077

More information

Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps

Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Jon Winkler, Ph.D. September 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the

More information

DEVELOPMENT OF HIGH SPEED RESPONSE LAMINAR FLOW METER FOR AIR CONDITIONING

DEVELOPMENT OF HIGH SPEED RESPONSE LAMINAR FLOW METER FOR AIR CONDITIONING DEVELOPMENT OF HIGH SPEED RESPONSE LAMINAR FLOW METER FOR AIR CONDITIONING Toshiharu Kagawa 1, Yukako Saisu 2, Riki Nishimura 3 and Chongho Youn 4 ABSTRACT In this paper, we developed a new laminar flow

More information

Comparison of fin-and-tube interlaced and face split evaporators with flow maldistribution

Comparison of fin-and-tube interlaced and face split evaporators with flow maldistribution Downloaded from orbit.dtu.dk on: Nov 06, 2015 Comparison of fin-and-tube interlaced and face split evaporators with flow maldistribution and compensation Kærn, Martin Ryhl; Elmegaard, Brian; Larsen, L.F.S.

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

A heat pipe heat recovery heat exchanger for a mini-drier

A heat pipe heat recovery heat exchanger for a mini-drier A heat pipe heat recovery heat exchanger for a mini-drier A Meyer Department of Mechanical Engineering, University of Stellenbosch, Stellenbosch R T Dobson Department of Mechanical Engineering, University

More information

Frost Damage of Roof Tiles in Relatively Warm Areas in Japan

Frost Damage of Roof Tiles in Relatively Warm Areas in Japan Frost Damage of Roof Tiles in Relatively Warm Areas in Japan Influence of Surface Finish on Water Penetration Chiemi IBA Hokkaido Research Organization, Japan Shuichi HOKOI Kyoto University, Japan INTRODUCTION

More information

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling for Simultaneous Heating and Cooling F. Sustainable Energy Centre, University of South Australia Mawson Lakes Boulevard, Mawson Lakes 5095 AUSTRALIA E-mail: Frank.@UniSA.edu.au Abstract The high efficiency

More information

DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE

DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE Md Shahid Imam, Dr.M.Shameer Basha, Dr.Md.Azizuddin, Dr. K.Vijaya Kumar Reddy 4 M.Tech HVAC II Yr, Royal Institute of Technology & Science Chevella R.R Dist

More information

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory

More information

Increasing the evaporation temperature with the help of an internal heat exchanger

Increasing the evaporation temperature with the help of an internal heat exchanger Increasing the evaporation temperature with the help of an internal heat exchanger A. TAMBOVTSEV (a), H. QUACK (b) (a,b) Technische Universität Dresden, D-01062, Dresden, Germany (a) Fax: (+49351) 463-37247,

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral

More information

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li * Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting

More information

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Air-sourced 90 Hot Water Supplying Heat Pump HEM-90A Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A" Takahiro OUE *1, Kazuto OKADA *1 *1 Refrigeration System & Energy Dept., Compressor Div., Machinery Business Kobe Steel has developed an air-sourced

More information

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

More information

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

UNIT 2 REFRIGERATION CYCLE

UNIT 2 REFRIGERATION CYCLE UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression

More information

International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No.161-166, March-April 2015

International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No.161-166, March-April 2015 International Journal of Latest Research in Science and Technology Volume 4, Issue 2: Page No.161-166, March-April 2015 http://www.mnkjournals.com/ijlrst.htm ISSN (Online):2278-5299 EXPERIMENTAL STUDY

More information

Experimental Analysis of an Automotive Air Conditioning System With Two-Phase Flow Measurements

Experimental Analysis of an Automotive Air Conditioning System With Two-Phase Flow Measurements Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering Experimental Analysis of an Automotive Air Conditioning System With Two-Phase

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

Optimisation of Defrost Strategy for an Air-to-Water Heat Pump

Optimisation of Defrost Strategy for an Air-to-Water Heat Pump Optimisation of Defrost Strategy for an Air-to-Water Heat Pump Dynamic Modelling and Experimental Study of Frost Formation on Cross-Flow Heat Exchanger Surface Emil Ø. Schmidt & Mikael S. Kristensen Master

More information

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged

More information

Numerical Modeling and Experimentation on Evaporator Coils for Refrigeration in Dry and Frosting Operational Conditions

Numerical Modeling and Experimentation on Evaporator Coils for Refrigeration in Dry and Frosting Operational Conditions Numerical Modeling and Experimentation on Evaporator Coils for Refrigeration in Dry and Frosting Operational Conditions 2 Zine Aidoun, Mohamed Ouzzane and Adlane Bendaoud CanmetENERGY-Varennes Natural

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

How To Know If A Refrigeration System Is Efficient

How To Know If A Refrigeration System Is Efficient Universitatea de Ştiinţe Agricole şi Medicină Veterinară Iaşi ASSESSMENT OF E SUBCOOLING CAPABILITIES OF A ERMOELECTRIC DEVICE IN A VAPOR COMPRESSION REFRIGERATION SYSTEM R. ROŞCA 1, I. ŢENU 1, P. CÂRLESCU

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

Split units TH with hermetic compressors

Split units TH with hermetic compressors Split units TH with compressors Refrigeration units in split variant. Available with screw or solder terminal. Condensing unit with sound insulated weatherproof housing for outdoor installation. Split

More information

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in

More information

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A Jignesh K. Vaghela Assistant Professor, Mechanical Engineering Department, SVMIT, Bharuch-392001, (India) ABSTRACT

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

Dynamic Simulation of a Variable-Speed Ground-Coupled Liquid Desiccant Air-Conditioner for Use in Subtropical Regions

Dynamic Simulation of a Variable-Speed Ground-Coupled Liquid Desiccant Air-Conditioner for Use in Subtropical Regions Dynamic Simulation of a Variable-Speed Ground-Coupled Liquid Desiccant Air-Conditioner for Use in Subtropical Regions C. K. Lee and H. N. Lam Abstract The dynamic performance of a novel variable-speed

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

2B.1 Chilled-Water Return (and Supply) Temperature...119. 2B.3 Cooling-Water Supply Temperature / Flow... 124

2B.1 Chilled-Water Return (and Supply) Temperature...119. 2B.3 Cooling-Water Supply Temperature / Flow... 124 Appendix 2B: Chiller Test Results...119 2B.1 Chilled-Water Return (and Supply) Temperature...119 2B.2 Chilled-Water Flow... 122 2B.3 Cooling-Water Supply Temperature / Flow... 124 2B.4 Pressure/Temperature...

More information

18th International Congress of Mechanical Engineering

18th International Congress of Mechanical Engineering CYLINDRICAL ENCAPSULATED COLD STORAGE Juan José Milón Guzmán Universidad Católica San Pablo, Av. Salaverry, 31, Vallecito, Cercado, Arequipa, Perú milonjj@ucsp.edu.pe Sergio leal Braga Pontificia Universidade

More information

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)

More information

Comparison of R744 and R410A for Residential Heating and Cooling Applications

Comparison of R744 and R410A for Residential Heating and Cooling Applications University of Illinois at Urbana-Champaign Air Conditioning and Refrigeration Center A National Science Foundation/University Cooperative Research Center Comparison of R744 and R410A for Residential Heating

More information

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 TIME SCHEDULE MODULE TOPICS PERIODS 1 Introduction 22 Principles

More information

HEAT TRANSFER ENHANCEMENT AND FRICTION FACTOR ANALYSIS IN TUBE USING CONICAL SPRING INSERT

HEAT TRANSFER ENHANCEMENT AND FRICTION FACTOR ANALYSIS IN TUBE USING CONICAL SPRING INSERT HEAT TRANSFER ENHANCEMENT AND FRICTION FACTOR ANALYSIS IN TUBE USING CONICAL SPRING INSERT Rahul M. Gupta 1, Bhushan C. Bissa 2 1 Research Scholar, Department of Mechanical Engineering, Shri Ramdeobaba

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

A software for calculation of optimum conditions for cotton, viscose, polyester and wool based yarn bobbins in a hot-air bobbin dryer

A software for calculation of optimum conditions for cotton, viscose, polyester and wool based yarn bobbins in a hot-air bobbin dryer A software for calculation of optimum conditions for cotton, viscose, polyester and wool based yarn bobbins in a hot-air bobbin dryer H. Kuşçu, K. Kahveci, U. Akyol and A. Cihan Abstract In this study,

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

Building HVAC Load Profiling Using EnergyPlus

Building HVAC Load Profiling Using EnergyPlus Building HVAC Load Profiling Using EnergyPlus Dong Wang School of EEE Nanyang Technological University Singapore Email: wang0807@e.ntu.edu.sg Abhisek Ukil, Senior Member, IEEE School of EEE Nanyang Technological

More information

Heat Transfer Enhancement in a Heat Exchanger using Punched and V-cut Twisted Tape Inserts

Heat Transfer Enhancement in a Heat Exchanger using Punched and V-cut Twisted Tape Inserts Heat Transfer Enhancement in a Heat Exchanger using Punched and V-cut Twisted Tape Inserts Imran Quazi#1, Prof. V.R.Mohite#2 #1DPCOE-Mechanical Department, SPP University Pune, India imranqu azi198 7@gmail.com

More information

Defining Quality. Building Comfort. Heating and Cooling Coils

Defining Quality. Building Comfort. Heating and Cooling Coils Defining Quality. Building Comfort. Heating and Cooling Coils Heating and Cooling Coils Heating and Cooling Coils For over 20 years, AAON has supplied the coil needs of industrial and commercial HVAC customers.

More information

AIR REVERSING R744 AIR CONDITIONING SYSTEM

AIR REVERSING R744 AIR CONDITIONING SYSTEM AIR REVERSING R744 AIR CONDITIONING SYSTEM A.HAFNER 1 ; D.J. GARSKI 2 ; J. MANZIONE 3 1 SINTEF Energy Research, 7465 Trondheim, Norway, Armin.Hafner@sintef.no 2 MODINE, Racine, USA, D.J.Garski@na.modine.com

More information

The final numerical answer given is correct but the math shown does not give that answer.

The final numerical answer given is correct but the math shown does not give that answer. Note added to Homework set 7: The solution to Problem 16 has an error in it. The specific heat of water is listed as c 1 J/g K but should be c 4.186 J/g K The final numerical answer given is correct but

More information

Experimental and Modeling Investigation of Two Evaporator Automotive Air Conditioning Systems

Experimental and Modeling Investigation of Two Evaporator Automotive Air Conditioning Systems University of Illinois at Urbana-Champaign Air Conditioning and Refrigeration Center A National Science Foundation/University Cooperative Research Center Experimental and Modeling Investigation of Two

More information

How To Save Energy With High Pressure Control

How To Save Energy With High Pressure Control Energy savings in commercial refrigeration equipment : High Pressure Control July 2011/White paper by Christophe Borlein AFF and IIF-IIR member Make the most of your energy Summary Executive summary I

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the

Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

How To Design A Refrigeration System

How To Design A Refrigeration System AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison

More information

Comparison of Heat Transfer between a Helical and Straight Tube Heat Exchanger

Comparison of Heat Transfer between a Helical and Straight Tube Heat Exchanger International Journal of Engineering Research and Technology. ISSN 0974-3154 Volume 6, Number 1 (2013), pp. 33-40 International Research Publication House http://www.irphouse.com Comparison of Heat Transfer

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)

More information

Todd M. Rossi, Ph.D. President

Todd M. Rossi, Ph.D. President Residential Air Conditioning Fault Detection and Diagnostics (FDD) and Protocols to Support Efficient Operation DOE - Building America Program Residential Buildings Integration Meeting - July 20-22, 2010

More information

MOBILE HEAT PUMP AND A/C SYSTEM EXPERIMENTAL AND MODEL RESULTS

MOBILE HEAT PUMP AND A/C SYSTEM EXPERIMENTAL AND MODEL RESULTS TRANSCRITICAL CO 2 MOBILE HEAT PUMP AND A/C SYSTEM EXPERIMENTAL AND MODEL RESULTS C.W. Bullard, J.M. Yin, P.S. Hrnjak Air Conditioning and Refrigeration Center (ACRC) University of Illinois, 1206 W. Green

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

HVAC Efficiency Definitions

HVAC Efficiency Definitions HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents

More information