Data Centres. Special Working Group Spin I A Guide to Energy Savings in Data Centres

Size: px
Start display at page:

Download "Data Centres. Special Working Group Spin I A Guide to Energy Savings in Data Centres"

Transcription

1 Data Centres Special Working Group Spin I

2 Table of Contents 1. Introduction Systems Covered 1 2. Design Flaws 4 3. Savings Initiatives The Actual Demand Recommendations 5 4. Quantifying the Impact of Savings Reduce bypass and mixing of cold supply air: impact on temperature demand Cold supply air temperature demand: impact on COP Cold supply air flow demand: impact on energy consumption Free cooling of chilled water: impact on energy consumption Free cooling with outside air, HVAC-style: humidification impact on energy consumption References 15

3 1. Introduction This study covers traditional air-cooled data centres and two of the most common free-cooling methods. It describes the most common design flaws and their impact on energy consumption, and outlines the impact that various savings initiatives can have on energy consumption. Finally, it quantifies the impact of selected savings initiatives in tables and diagrams. 1.1 Systems Covered This report covers traditional air-cooled data centres (or rooms with electronic equipment in general) with at least one row of racks; air is recirculated and conditioned to temperature and humidity, and fresh-air supply is minimal. It does not deal with small rooms with a few PC-servers and a split cooling unit, or with energy savings from virtualisation, new semiconductor or software technology. Glossary of terms 1. Module (electronic): could be a blade server, a switch, communication module, a power supply, or a disk module, etc, usually mounted vertically together with several other modules in a crate. 2. Crate: contains several modules. The crate is sometimes also called a rack or a bin. The mounting brackets of a crate are usually 19 ins apart. 3. Units are just bigger modules that are mounted directly into the rack, often 19 ins wide (e.g. non-blade -computers, power supplies, fan-units). 4. Rack contains several crates or units. The racks are often much wider than the crates/units to provide for cables and air in the sides. Some racks are open (or with a grid door) front and back to provide for horizontal airflow. Others are closed with doors to provide for confined vertical airflow. 5. Aisle is the space between two rows of racks (or one row and a wall). 6. Cold air supply is the air produced by the CRAC (see below). 7. Cold air supply temperature and relative humidity (RH) is the air condition right after leaving the cooling coil and humidifier in the CRAC. 8. CRAC: Computer Room Air Conditioner 9. DX is a CRAC using direct expansion on the cooling coil, usually a standalone unit with builtin compressor. 10. Cooling air is the air going into the various modules and units to cool the electronic components. 11. Cooling air temperature and relative humidity (RH) is the condition of the air just before it enters the various modules and units. 12. Heated air is what comes out of the modules and units. 13. Hot return air is the mix of air that is returned to the CRAC for cooling. 14. Elevated floors contain cables and most often also provide the duct for cold air supply. 15. Cold aisle is an aisle where an attempt is made to keep the cold supply air confined, so that it will not mix with the heated air, in order to obtain the coldest possible cooling air for the modules and units. 16. Room temperature is a very questionable issue, but often refers to the temperature of the hot return air. 1

4 Figure 1: Data centre air-cooling components The most common types of free-cooling systems There are several options for free cooling. Five of the most common methods are described below: 1. Cooling Tower. In systems with chilled water cooled CRAC units, a cooling tower (dry or wet) is often cut into the chilled water loop over a bypass valve, and, when the outside temperature is low, the compressors are stopped and the tower valve is opened. In DX units, the free cooling is often established with an extra (water) cooling coil inside the DX. This coil is connected to the same outside cooling tower that also cools the condenser. Note that different types of towers exist: open, spray, dry, etc, and that they all have different advantages and disadvantages (e.g. water cost, noise). Evaporator Compressor Pump Expansion valve Condenser CRAC units Cooling tower for free-cooling Figure 2: Chilled water system with cooling tower 2. Free Cooling with Direct Supply of Outside Air is also an option. One method is to build a balanced HVAC system that can modulate from full fresh air to full recirculation. Duct work is needed together with good filters, cooling coil, dehumidifier, humidifier, dampers, and 2

5 control equipment. One has to consider the extra power needed for humidification and dehumidification, and filter maintenance will be an extra cost. The higher complexity and need for extra space must also be considered. VSD G3 F7 Ventilated rooms VSD F7 Figure 3: A balanced HVAC system 3. Free Air Cooling. A very simple free air cooling option in this system fresh air is only used when the outside temperature and humidity is within the acceptable limits. If not, it is shut off and the conventional CRAC takes over. Filters and control system is still needed, but the complexity is much lower than with a balanced HVAC system. 4. Evaporative Cooling. In the last few years a new type of free cooling has been installed in the US (and at least one in Denmark). The principle is called evaporative cooling, and is based on cooling with water without the aid of compressors. Outside air is drawn over a big water-filled sponge or through a water curtain, and in this way cooled by the water vaporisation. At the same time the air is humidified and to some extent particles are also caught by the water. This principle has been known for many years and used in many industries. The drawbacks are water consumption, possible infections (e.g. Legionella) and rather bulky installations. The obvious benefits are very low electrical power consumption covering only fans, pumps and water treatment plant. Note that this principle is useful for a few degrees of cooling only, and that another form of cooling will usually be necessary (chilled water, DX, etc). 5. Liquid Cooling. The last method worth mentioning is liquid cooling. Computers and other electronic equipment with liquid cooling have existed for many years (e.g. CDC and other vintage super-computers). Heat pipes to transport the heat out from a closed module were seen many years ago in fighter-aircraft radios. A mix of these technologies could result in very energy-efficient server cooling, using direct wet tower free cooling most of the year. The high-power density in future servers will probably revive these systems. With these systems the issues of cooling temperature are the same, and the possibilities for free cooling should still be used. There is a move back to this technology already. IBM s latest High Performance Computer has liquid cooling directly to the heat-producing chips. It is worth noting that water has far superior heat-removal capacities than air (approx. 3,500 times greater), hence the move back to this technology. Establishing free cooling only gives savings on the energy bill. Capital investment will always be larger, since the compressors must still be installed to cater for the increased cooling demand when free cooling is not possible on days with very warm weather. 3

6 2. Design Flaws There are many reasons why data centres are not designed with efficient cooling systems. The most common reasons, mainly relating to the cold air supply, are listed below: Cold supply air passes direct to the return without ever reaching cabinets. Further reading in section 3; recommendation 5 Cold supply air is mixed with heated air around cabinets. In order for all units to receive the demanded cooling air temperature, the supply air temperature is set very low. Further reading in section 3; recommendation 5 Hot and cold aisles are not functioning correctly; grids in the floor are covered, racks are not the same height, cable holes are too large, obstructions in the ceiling causing turbulence, uneven air distribution, etc. Further reading in section 3; recommendation 5 Cold supply air passes through holes in cabinets without getting heated. A big part of the cold air supply never reaches the server units. A lot of air is pumped around for no reason, and excess fan power is added to the room load, as well as to the total electricity consumption. Further reading in section 3; recommendation 7 Air passes though several units, getting hotter and hotter, so the cooling air temperature for these units must be very low to provide the last unit with acceptable temperature. Further reading in section 3; recommendation 5 Cold air supply temperature is dictated by only a few units (see above), where the rest could have operated at a higher temperature. Further reading in section 3; recommendations 1 to 3 Actual demands from unit suppliers are not followed/questioned. Often suppliers specify wider span for cooling air going into the unit than they do for the not very well defined room temperature. Further reading in section 3; recommendations 1 to 3 Uneven distribution of cold supply air (several issues) under the elevated floor results in some units getting too little cooling air. Airflow is increased and temperature decreased, both leading to excess energy consumption. Further reading in section 3; recommendations 5 and 6 Demand for latency in the cooling system. If cooling fails, operators must have time to shut down in a controlled manner. Since air is not good storage for cooling, this leads to excess low cold supply air temperatures and large room volumes in order to get just a few minutes latency. Further reading in section 3; recommendation 14 Room and cooling are designed for other purposes. Excess low chiller coil temperature is dictated by other demands not related to the server room, e.g. office ventilation, process cooling. Further reading in section 3; recommendation 5 Excess low coil temperatures in CRAC units. Further reading in section 3; recommendation 10 Room temperature is not uniform. If recirculation is very high, the mixing of air with different temperatures in the room will become more efficient, and thus the temperature uniform. In this case one can talk about a single room temperature. With low air change rates, many different temperatures can be measured. This is probably reminiscent of a time where all sorts of odd boxes with different shapes were put together in a room. Further reading in section 3; recommendation 1 Room humidity is not well defined. Unnecessary power load on room. Further reading in section 3; recommendation 9 Poor coefficiency of performance (COP) for built-in compressors in DX units (several issues). Further reading in section 3; recommendation 5 4

7 Poor COP for chilled water systems (several issues). All the usual issues with cooling systems: poor maintenance of condensers, filters, etc. Low focus on energy in the design phase. Poor control system and lack of monitoring of energy. Further reading in section 3; recommendations 12 and 13 Energy consumption is not an issue at all; lack of meters and energy management. 3. Savings Initiatives 3.1 The Actual Demand A common argument is that little can to be done to reduce cooling energy consumption i.e. the energy that goes into all the electronics modules in a given installation must be transported out again (balance) in order to maintain temperature equilibrium at a certain level, and this temperature equilibrium is of less importance if the room is fairly well isolated. This argument is correct regarding the energy balance, but the savings potential lies more in how we provide the cooling, and in this context the temperature and airflow are of considerable importance. If good data about the actual demand can be provided, the safety margins outlined in the previous chapter can be minimised. As in all work with energy savings, it is important to identify the actual demand. To do this, one has to look at the individual modules that need cooling. Inside every unit, power is dissipated from one or more hot components (usually CPUs) by convection from cooling fins to the surrounding air. The unit will burn if this air is not removed, and in most cases small fans are installed to ensure the correct airflow. In some (older) units with low power dissipation, the air is designed to move by natural flow without fans. As the air passes through the unit, it gets hotter for each component it meets, and the optimum airflow and cooling air temperature for the incoming air is in principle determined by the demand from the last and hottest component in the unit. Increased airflow can, to a certain extent, compensate for increased temperatures in general. Electronics designers have focused a lot on these matters, because, from the early days of the transistor age, the electronics industry has combatted heating problems. For each unit found in a server room it should be possible to find precise data for the airflow and temperature necessary to keep the unit operational for the guaranteed period. With a population of several different types of units, the ideal common air cooling demand should be: Cold air supply temperature equal to the lowest cooling air temperature demanded by any unit Cold air supply flow equal to the sum of all unit demands Since no cooling installation is ideal, both demands must include a safety margin, mainly because some of the airflow will shortcircuit and never reach the units, and some of the cold air will be heated in advance, from mixing with heated air or by passing from one unit to another. Another common reason for adding a safety margin is the need for a response time if the cooling fails. A further safety margin must also be considered to deal with the situation where the doors are left open for longer periods (e.g. unintentionally, for service or rebuilding). The main question is how big all these safety margins have to be. The energy consumption can be kept at a minimum if the margins can be kept low. 3.2 Recommendations To establish an energy-efficient server room, the actions listed below are recommended, in the following order: 5

8 1. Find the actual cooling air temperature demand. Cold air supply temperature should equal the lowest cooling air temperature demand set by any module/unit (+ any safety margin). 2. Challenge the cooling air temperature demand. Do not accept a vague temperature demand such as room temperature. Suppliers of any electronic module must know and specify what the temperature of the cooling air going into the module must be, and how much is needed. o There should be a greater emphasis on measuring and monitoring the temperature of air onto the server, rather than the prevailing situation of monitoring the temperature of the return air. 3. Disk drives temperature should be challenged. See Google s reference paper on reliability, which indicates much less sensitivity to heat than normally assumed. 4. Find the actual cooling airflow demand. Cold air supply flow should equal the sum of cooling airflow demands from all modules (+ any safety margin). Suppliers of any electronic module must know and specify what the flow of the cooling air going into the module must be. 5. Direct all cold supply air to racks (several solutions). Make sure that all cold air supply goes directly, and only, to all the individual modules/units, without being preheated or mixed with heated air. This can be done in many ways, but commonly by establishing closed cold aisles, with roof and doors, or by ducting the air directly to the racks. Closed cold aisles should, together with the space under the elevated floor, form a plenum for the cold supply air where temperature is almost even, and with sufficient pressure everywhere. o o Closed cold aisles (with roof and doors) can be difficult to establish if racks are of different heights. Empty dummy racks, boxes or panels could cover the space from the rack to the roof of the aisle. The underfloor void should be at least 600 mm in height and be free from cabling infrastructure and other potential obstacles to the movement of air. 6. Minimise pressure drop in supply- and return-air paths (several solutions). Establish an even cold supply air distribution under the elevated floor, and adjust pressure drop across inlet grids in the floor according to the demand. Make sure that cables or building details do not block the airflow. 7. Stop any bypass of supply air to return air (several solutions). Make sure that no cold supply air escapes through unused module slots, missing crates or units, cable holes and spaces between rack side panels and crate/unit fixture rails. Use blind panels, sheet metal/plastic, cardboard, foam, etc to fill the holes. 8. Take precautions concerning operating and maintenance errors (several solutions). With closed cold aisles, precautions must be taken to deal with the situation where the doors are left open unintentionally for longer periods. An alarm system on the doors should be part of the solution, rather than building in a safety margin on temperature and flow. 9. Remove any unnecessary power load from the room (several solutions). Remove any unnecessary power load from the room, by shutting down unused equipment (e.g. displays, service computers, lights), and by removing equipment that is not sensitive to heat into other non-air-conditioned rooms (e.g. UPS electronics, DX compressors, fan motors and drives, switchboards). A few ideas are listed below: o Keep UPS batteries in the server room 1 and remove the UPS. Under normal conditions batteries do not produce any heat, but their lifetime and performance are improved when they re kept at a constant moderate temperature. The UPS itself 1 This is a trade-off as server room is sellable footprint. 6

9 o o is often not sensitive to heat, and can be put in an adjacent room with free air cooling (at least in northern countries) together with switchboards, etc. The power delivered to the fan itself will always be an extra load to the room, but the smaller fraction (10 to 15%) that is dissipated from the motor and VSD could be avoided if these were placed outside the room, or isolated from the airstream in the CRAC and ventilated from an adjacent room. Using filters and coils with lowpressure drop can reduce the fan power by a few percent. Most often in standalone DX units, the compressor is placed inside the cabinet in the air-stream, giving an extra load to the room. If the compressor is placed outside it could be naturally cooled most of the year. 10. Increase cold air supply temperature as a result of the other solutions. When all the above actions have been taken, the cold air supply temperature can (hopefully!) be increased. Cooling coil temperature must now also be increased according to the new limits, and a better COP can be obtained together with increased possibilities for free cooling. With chilled water systems, make sure that chiller coil temperature is not dictated by other nonrelevant demands such as office ventilation and process cooling. 11. Decrease cold air supply flow as a result of the other solutions. When all the above actions have been taken, the cold air supply flow can (hopefully!) be decreased, resulting in lower fan power consumption together with lower cooling power to cool the fan power. 12. Improve chilled water COP (a rather big issue with several solutions). Chilled water systems and DX units must be checked for acceptable COP, and maintained, repaired or changed until a good COP is reached. This involves a broad field of skills and knowledge, and is best performed by a cooling or energy specialist. 13. Use free cooling (a rather big issue with several solutions). Free cooling should be considered if the climate is suitable. See note on free cooling below. 14. Establish a cooling buffer. If the demand for a cooling buffer in case of cooling shutdown imposes a very high safety margin on the temperature, other solutions should be considered: higher reliability or redundancy on the cooling systems, emergency fans for outside air, higher thermal capacity in the building, or liquid nitrogen as used in the food industry. Please note that the cooling buffer in the recirculated air itself is not influenced by increasing the cold supply air temperature, if the average temperature going to the servers is kept the same, as obtained with improved air distribution. 15. Regularly clean the chiller coils. Where permissible, chiller coils should be power-washed every 6 months to prevent a build-up of dirt, which reduces their efficiency. 7

10 4. Quantifying the Impact of Savings This study provides server-room users with tools to calculate possible savings from implementing the initiatives described. These tools are in the form of diagrams and tables calculated for various steps in the savings process. All the following calculations are based on the following key data, so the results are scalable: Cold supply air flow of m3/sec (= 3,600 m3/hour) Cold supply air temperature 19 C Heated return air temperature 24 C (out of servers) Total power impact on air 6.1 kw Weather Dublin Airport 2008, 8760 hours The tools are divided into the following sections, each organised on a separate set of pages: 4.1 Reduce bypass and mixing of cold supply air: impact on room temperature demand 4.2 Cold supply air temperature demand: impact on COP 4.3 Cold supply air flow demand: impact on energy consumption 4.4 Free cooling of chilled water: impact on energy consumption 4.5 Free cooling with outside air, HVAC-style: humidification impact on energy consumption 8

11 4.1 Reduce bypass and mixing of cold supply air: impact on temperature demand To calculate the impact on the temperature demand, a model has been produced that in a simplified manner describes the two ways that cold supply air is wasted The input and output data for the ideal situation are shown below, together with a drawing of the model: Calculating the total supply air temperature demand Total power input kw 6,1 demand Temperature from server, unmixed C 24,0 demand Total supply-air flow m 3 /h chosen according to power Not utilized air flow Air temperature from server area C 24,0 output from mixing calculation Not utilized air flow % 0 input Not utilized air flow m 3 /h 0 calculated Utilized-air flow to server area m 3 /h calculated Temperature increase in servers C 5,0 calculated Total supply-air temperature C 19,0 calculated Total return-air temperature C 24,0 calculated Total air temperature difference C 5,0 calculated Total power output to chillers kw 6,1 calculated Mixing around servers Unwanted mixing around server % 0 input Air flow to server m 3 /h output from utilized air flow calculation Temperature increase in server C 5,0 calculated Temperature to server, mixed C 19,0 calculated Temperature to server, unmixed C 19,0 calculated Temperature from server, mixed C 24,0 calculated Power supply 6,1 kw Server room Server area 24,0 C Server 19,0 C 24,0 C Mix 19,0 C 0 % mix m 3 /h mix 0 % 0 m 3 /h Not utilized CRAC 24,0 C m 3 /h 19,0 C 6,1 kw Cooling system 9

12 Different sets of values for unwanted mixing and unused air have been put into the model; the results are shown in the following diagram: Supply air temperature C as a function of % unwanted mixing around servers. Calculated for different % of not-utilized airflow 25 Supply air temperature C % not utilized 10 % not utilized 20 % not utilized 30 % not utilized 40 % not utilized 50 % not utilized 60 % not utilized 70 % not utilized 80 % not utilized % mixing Use the diagram to visualise the effect of the non-ideal air distribution, or in a given system to read what temperature could be obtained if airflow is improved. Model for a situation with 10% unwanted mixing and 10% unused air Power supply 6,1 kw Server room Server area 24,0 C Server 18,4 C 23,4 C Mix 17,8 C 10 % mix m 3 /h mix 10 % 360 m 3 /h Not utilized CRAC 22,9 C m 3 /h 17,8 C 10 6,1 kw Cooling system

13 4.2 Cold supply air temperature demand: impact on COP The temperature that the CRAC must produce is closely related to the obtainable chiller COP (coefficiency of performance). Higher temperature results in a higher COP. E.g. 10 C gives COP = 5.8 and 14 C gives COP = 7.5 Diagram with measured COP (ammonia, without pumps and fans) at different cooling temperatures, for the same type of system This diagram is only an example, and should only be used as a relative measure for obtainable savings with changing temperature. The condensation temperature also has an impact on the temperature. Below is shown the COP for two different size compressors (Carrier) at different chilled water and condensation temperatures: Carrier unit 30RA-010 (25 kw cooling): COP at different condensation temperatures for different chilled air temperatures 4,5 COP 4,0 3,5 3,0 2,5 2,0 1,5 Chilled water C 4,4 5,6 6,7 7,2 7,8 8,9 1,0 0,5 0, ,0 12,8 15,6 Condensation C 11

14 Carrier unit 30RA-055 (200 kw cooling): COP at different condensation temperatures for different chilled air temperatures 4,5 COP 4,0 3,5 3,0 2,5 2,0 1,5 Chilled water C 4,4 5,6 6,7 7,2 7,8 8,9 1,0 0,5 0, ,0 12,8 15,6 Condensation C 4.3 Cold supply air flow demand: impact on energy consumption Fan power is closely related to the airflow (and less to pressure). As a rule of thumb, the fan power increases with the power of 2.5 for a given system (turbulent resistance) as the flow is increased. All the fan power is dissipated in the room, thus loading the cooling even more. Diagram showing raw fan power consumption as a function of reduced airflow Power is calculated for a system with a total pressure drop of 1000 Pa at 3600 m3/h. The power shown is what the fan delivers to the air, and does not include losses in fan, transmission, motor and variable speed drive. 12

15 To calculate the total fan power, the power delivered to the air must be divided with the total efficiency. The total efficiency is the product of the individual efficiencies for fan, transmission, motor and frequency converter. Total efficiency could be as low as Be aware that the individual efficiencies vary across the entire power range for the components. Note: The overall efficiency should be calculated as shown below. The overall machine efficiency should be requested from the vendors of fans and other equipment in order to select the most efficient one. It is quite normal that suppliers will quote the efficiency point at which the fan is selected (say 70%), but if the rest of the system is inefficient then the fan selection on its own is largely meaningless. Based on the diagram above, the typical total power input for a well-designed system at 3,600 m 3 /h (= 1 m 3 /sec) could be: 0.65 kw / ( 0.7 fan * 0.95 transmission * 0.85 motor * 0.97 VSD ) = 1.19 kw The specific fan power (SFP) will in this case be 1.19 kw/(m 3 /sec), which is fairly good. 4.4 Free cooling of chilled water: impact on energy consumption The temperature that the CRAC must produce is closely related to the number of hours throughout the year where free cooling is possible. Free cooling can have COP from 30 to 50. The higher the cold supply air temperature can be set, the more hours per year free cooling can be used. Outside temperature (and humidity) data from Dublin Airport have been collected for 2007 and The data have been trimmed for errors and sorted by decreasing magnitude. A diagram has been drawn up whereby the number of free-cooling hours per year for a given temperature can be calculated e.g. 14 C in Dublin 2008 reads 1,681 hours, which means that a total of (8,760 1,681) = 7,079 hours per year can be cooled with outside air. Diagram with annual outside air temperatures for 2007 and 2008: How to read the diagram: 13

16 Read across from a given temperature to the curve. Read down to the hour s line to see the number of hours for which free cooling is NOT available. Subtract this value from 8,760 (the total number of hours in a year) to obtain the number of hours that free cooling is available. 4.5 Free cooling with outside air, HVAC-style: humidification impact on energy consumption The energy consumption for cooling and humidifying outside air has been calculated for two room air temperatures (19 C and 22 C ), each with varying degrees of humidification, from 60% RH down to 10 % RH. In the diagrams, the th (= temperature High limit) represents the highest acceptable room air temperature after it has been subjected to 6.1 kw load on the room incl kw fan power. The RHL (= Relative Humidity Low limit) represents the lowest acceptable humidity in the room at the th temperature. Other limits mentioned in the diagrams are default values without influence. Calculations for both diagrams are made at 3,600 m 3 /h (= 1 m 3 /sec), with weather profile for Dublin Airport in 2008, and with 100% fresh air (no recirculation). The pink line represents humidification energy, and the black line humidification + cooling energy. Both cooling and humidification are raw values, not including COP or any other efficiency factors. Humidification is calculated as steam humidification Server room example, Dublin, Scenarios w. Changing humidification limit, Dublin 2008 weather, at air-flow 3600 m3/h kwh/yr th=19, RHL=60, th=19, RHL=50, th=19, RHL=40, th=19, RHL=30, th=19, RHL=20, th=19, RHL=10, 14

17 System Server room example, Dublin, Input for scenarios w. Changing humidification limit, Dublin 2008 weather, at air-flow 3600 m3/h kwh/yr th=22, RHL=60, th=22, RHL=50, th=22, RHL=40, th=22, RHL=30, th=22, RHL=20, th=22, RHL=10, Note: When cooling with outside air, always remember that fan power is related to pressure drop. Therefore ductwork and fittings must be minimised, together with air velocity, in order to minimise the fan power. If this is not done properly, the result can be that free cooling requires excessive fan power that more or less outweighs the savings on the chillers. 5. References European Commission, Integrated Pollution Prevention and Control (IPPC). Reference Document on the Application of Best Available Techniques to Industrial Cooling Systems. December Pinheiro, E., Weber, W-D. & Barroso, L.A. Failure Trends in a Large Disk Drive Population. Google Inc., 1600 Amphitheatre Pkwy, Mountain View, CA Appears in the Proceedings of the 5th USENIX Conference on File and Storage Technologies (FAST 07), February 2007: disk_failures.pdf Rocky Mountain Institute (RMI). Design Recommendations for High-Performance Data Centers. Integrated Design Charrette. Conducted 2 5 February Published by Rocky Mountain Institute, 1739 Snowmass Creek Road, Snowmass, CO , USA: 15

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

Data Center Energy Profiler Questions Checklist

Data Center Energy Profiler Questions Checklist Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

White Paper #10. Energy Efficiency in Computer Data Centers

White Paper #10. Energy Efficiency in Computer Data Centers s.doty 06-2015 White Paper #10 Energy Efficiency in Computer Data Centers Computer Data Centers use a lot of electricity in a small space, commonly ten times or more energy per SF compared to a regular

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

Elements of Energy Efficiency in Data Centre Cooling Architecture

Elements of Energy Efficiency in Data Centre Cooling Architecture Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

Office of the Government Chief Information Officer. Green Data Centre Practices

Office of the Government Chief Information Officer. Green Data Centre Practices Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION 1/16 Contents: 1. Introduction: the increasing importance of energy efficiency 1.1 Power consumers in the data

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

Blade Server & Data Room Cooling Specialists

Blade Server & Data Room Cooling Specialists SURVEY I DESIGN I MANUFACTURE I INSTALL I COMMISSION I SERVICE SERVERCOOL An Eaton-Williams Group Brand Blade Server & Data Room Cooling Specialists Manufactured in the UK SERVERCOOL Cooling IT Cooling

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

EHDC. Cooling system for Data Center and server cabinets.

EHDC. Cooling system for Data Center and server cabinets. EHDC Cooling system for Data Center and server cabinets. EHDC PEN LP EHDC L is a High Density Cooling module for an pen Loop configuration. It is ideally installed with Enoc Systems cold corridor containment

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Strategies for Deploying Blade Servers in Existing Data Centers

Strategies for Deploying Blade Servers in Existing Data Centers Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling

More information

Greening Commercial Data Centres

Greening Commercial Data Centres Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200

More information

Data Centre Cooling Air Performance Metrics

Data Centre Cooling Air Performance Metrics Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption

More information

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms By Neil Rasmussen White Paper #49 Executive Summary Avoidable mistakes that are routinely made when installing cooling

More information

News in Data Center Cooling

News in Data Center Cooling News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

The Benefits of Supply Air Temperature Control in the Data Centre

The Benefits of Supply Air Temperature Control in the Data Centre Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

Energy Efficiency HOSPITALITY. www.energia.ie

Energy Efficiency HOSPITALITY. www.energia.ie Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Energy Efficiency Best Practice Guide Data Centre and IT Facilities

Energy Efficiency Best Practice Guide Data Centre and IT Facilities 2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits

More information

Benefits of Cold Aisle Containment During Cooling Failure

Benefits of Cold Aisle Containment During Cooling Failure Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Energy Efficiency. Bars & RestauRants. www.energia.ie

Energy Efficiency. Bars & RestauRants. www.energia.ie Energy Efficiency Bars & RestauRants www.energia.ie 2 Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2013

European Code of Conduct for Data Centre. Presentation of the Awards 2013 European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started

More information

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment The Intelligent Data Center Cooling Solution: Liebert CRV Trust the industry leader in Precision Cooling to deliver

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

Why Do I Need Precision Air Conditioning?

Why Do I Need Precision Air Conditioning? Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment

Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment Ten Steps to Solving Cooling Problems Caused by High- Density Server Deployment By Peter Hannaford White Paper #42 Revision 1 Executive Summary High-density servers present a significant cooling challenge.

More information

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London. Energy Efficient Data Centre at Imperial College M. Okan Kibaroglu IT Production Services Manager Imperial College London 3 March 2009 Contents Recognising the Wider Issue Role of IT / Actions at Imperial

More information

Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity

Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face

More information

In Row Cooling Options for High Density IT Applications

In Row Cooling Options for High Density IT Applications In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions

More information

RVH/BCH Data Centres Proposals for Surge Protection and Ventilation

RVH/BCH Data Centres Proposals for Surge Protection and Ventilation REPORT Proposals for Surge Protection and Ventilation BELFAST HEALTH AND SOCIAL CARE TRUST ROYAL GROUP OF HOSPITALS GROSVENOR ROAD BELFAST BT12 6BA Rev. 01 6th September 2013 Table of Contents 1.0 Ventilation

More information

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010 White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white

More information

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,

More information

White Paper Rack climate control in data centres

White Paper Rack climate control in data centres White Paper Rack climate control in data centres Contents Contents...2 List of illustrations... 3 Executive summary...4 Introduction...5 Objectives and requirements...6 Room climate control with the CRAC

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT

More information

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Data Center Power Consumption

Data Center Power Consumption Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling

More information

Driving Data Center Efficiency Through the Adoption of Best Practices

Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary

More information

Data Center Airflow Management Retrofit

Data Center Airflow Management Retrofit FEDERAL ENERGY MANAGEMENT PROGRAM Data Center Airflow Management Retrofit Technology Case Study Bulletin: September 2010 Figure 1 Figure 2 Figure 1: Data center CFD model of return airflow short circuit

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes Precision Cooling for Business-Critical Continuity Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes We re Emerson Network Power, backed by Emerson,

More information

Data Centres. Special Working Group Project Report Spin I

Data Centres. Special Working Group Project Report Spin I Data Centres Special Working Group Project Report Spin I Table of Contents Executive Summary... 1! Phased Approach... 1! Outputs... 1! Site Assessments and Special Investigations... 1! Guides/Desktop Studies...

More information

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Airflow Simulation Solves Data Centre Cooling Problem

Airflow Simulation Solves Data Centre Cooling Problem Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction

More information

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

Drives and motors. A guide to using variable-speed drives and motors in data centres

Drives and motors. A guide to using variable-speed drives and motors in data centres Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers

More information