Transcription
1 Fire Protection Equipment #SVL200 Model 373 Alarm Valves "Automatic" Sprinkler 150 Gordon Drive Exton, PA USA Tel: (610) Fax: (610)
2 TABLE OF CONTENTS Text Page General... 1 Approvals... 1 Description / Operation... 1 Variable Pressure... 1 Constant Pressure... 2 Figure 1 Operation Diagram: Model 373 Alarm Valve with Model B Retard Chamber Set Position... 2 Figure 2 Operation Diagram: Model 373 Alarm Valve with Model B Retard Chamber Operating Position... 2 Technical Data... 3 Ordering Information... 3 "Automatic" Model 373 Valve Assemblies Parts List... 4 "Automatic" Model B Retard Chamber Parts List... 5 "Automatic" 21/2 Model 373 Alarm Valve Flange/Groove Vertical/Variable Pressure Trim Setup 3732V with Retard Chamber Parts Drawing & List... 6 "Automatic" 4 Model 373 Alarm Valve Flange/Groove Vertical/Variable Pressure Trim Setup 3734V with Retard Chamber Parts Drawing & List... 7 "Automatic" 4 Model 373 Alarm Valve Flange/Groove Vertical/Constant Pressure Trim Setup 3734C Parts Drawing & List... 8 "Automatic" 6 Model 373 Alarm Valve Flange/Groove Vertical/Variable Pressure Trim Setup 3736V with Retard Chamber Parts Drawing & List... 9 "Automatic" 6 Model 373 Alarm Valve Flange/Groove Vertical/Constant Pressure Trim Setup 3736C Parts Drawing & List Testing and Maintenance Testing Testing Alarm Valve and Waterflow Alarm Devices Flow Test at Main Drain Valve (Main Drain Test) Maintenance Clapper Facing Seat Ring ByPass Check Valve Retard Chamber Alarm Line Strainer Alarm Test Valve, Main Drain Valve & Inspection Test Valve i SVL200
3 Alarm Valve and Trim Resetting of System Accessories Pressure Relief Connections General Approvals Description/Operation Installation Maintenance Availability/Ordering Information SVL200 ii
4
5 DATA SHEET #SVL200 MODEL 373 Alarm Valves General The "Automatic" Model 373 Alarm Valve is a waterflow alarm device designed for installation in the main supply to a wet pipe sprinkler system. It has a flanged inlet connection and a grooved outlet connection. Its purpose is to actuate a fire alarm when a flow of water from the system equals or exceeds that of a single sprinkler. The alarm may be accomplished in two ways: (1) mechanically by means of a water flow to a water motor alarm and/or (2) electrically via a waterpressureactuated alarm switch (circuit closer) connected to an electrically operated signaling device such as a bell or light. The Model 373 Alarm Valve, available in 2½ (63.5 mm), 4" (101.6 mm) and 6" (152.4 mm) pipe sizes for vertical installation, may be provided with either of two basic trim packages. There is one set of trim for variable supply pressure and another for constant supply pressure. Variable pressure trim is used where the water supply pressure fluctuates. A public water main is an example of such a supply. To prevent false alarms caused by surges or fluctuations in pressure, the trim set is provided with the "Automatic" Model B Retard Chamber. For installations where there is a constant supply pressure, that is, where the water pressure does not fluctuate, the retard chamber is omitted. For example, constant pressure trim may be used when the water supply is from an elevated tank or pressure tank. An excess pressure pump may be required for installtions where excessive pressure surges or extreme fluctuations in the water pressure are encountered. Approvals Underwriters Laboratories (UL) Factory Mutual (FM) Underwriters Laboratories Of Canada (ULC) The valves are listed/approved with specific trim and for installation in accordance with the applicable requirements of NFPA 25. Therefore, no substitutions or omissions, in part or in full, are allowed. Model B Retard Chambers are listed and approved for use specifically with the Model 373 Alarm Valves. All devices are listed/approved for a maximum water working pressure (WWP) of 175 psi ( kpa or 12.1 bar). Description / Operation The Model 373 Alarm Valve is the type of alarm check valve which has a grooved seat ring and an external bypass. Its operation in a wet pipe sprinkler system is as follows: When the sprinkler system is placed into service, water is allowed to flow into the system until the system pressure and the supply pressure are equal. The system pressure then causes the rubberfaced clapper of the alarm valve to close tightly on the grooved seat ring. It will remain in this closed position as long as the pressure in the system is equal to or greater than the supply pressure. See Figure 1. Variable Pressure. In service, the pressure on the system, most often, will be found to be greater than the water supply pressure. This condition exists because excess pressure from surges and fluctuations in the water supply are allowed to pass through the external checked bypass to be trapped in th esystem above the alarm valve clapper. Normally then, the clapper will remain in a closed position. At times, however, sudden surges of greater pressure may cause the clapper to open momentarily, then close. In such instances, when the clapper is open, there will be a limited flow of water through the seat ring openings and into the retard chamber. There the water can accumulate, then drain away without causing a false alarm. When a sprinkler operates, the resulting water flow relieves the system pressure. The greater supply pressure then
6 causes the alarm valve clapper to open, thereby permitting an unobstructed flow of water into the system. At the same time, water flows through the seat ring openings and via alarm line connections into the retard chamber. But now, with the system operating, the clapper remains in an open position and the volume of water flowing through the alarm line is such that the retard chamber drain cannot keep up with the incoming flow. The chamber quickly fills and the water flow continues on to sound the water motor alarm and/or operate the pressure actuated electric alarm switch. See Figure 2. Caution: All sprinkler systems contain a certain amount of confined air. It is possible that a pressure surge could compress this air and allow the alarm valve clapper to move off the seat ring. Under some conditions, this could cause false alarms. It is recommended, therefore, that the installer bleed off the confind air and fill the system with water to the fullest extent possible. Constant Pressure. Under normal conditions the system and supply pressures will be the same. Since the pressure is constant, there is no need to consider surges and fluctuations. Therefore, a retard chamber is not provided. When a sprinkler operates, the system pressure drops, allowing the alarm valve clapper to open. At the same time that water enters the system, it also flows through the seat ring openings and then via the alarm line connections directly to operate the alarm devices. 2 SVL200
7 Technical Data Available Sizes:... 2½" (63.5 mm) 4" (101.6 mm) 6" (152.4 mm) Inlet & Outlet:... Class 125 Flanged Inlet with Grooved Outlet(per ANSI/ AWWA C606) Water Working Pressure: psi ( kpa or 12.1 bar) Setup For:... Variable Pressure Constant Pressure Listings & Approvals:... UL Listed FM Approved ULC Listed Pressure Loss: For use in hydraulic calculations, the pressure loss through the alarm valve may be expressed as equivalent feet of pipe: 2½" Valve = 14 Ft 4" Valve = 9 Ft 6" Valve = 37 Ft Conversion Factors: 1 inch = 25.4 millimeters (mm) 1 psi = kilopascals (kpa) bar 1 gallon = liters (L) 2 HA I I K HA E F I E 2 = % " &! #! " #! %! & $ ' #! " E $! # %! % ' % # % 2 H A I I K H A I I + K H L A I!! $ " E $ # & '! $ E # "! % & # M E C F E! % # %! # # Ordering Information "Automatic" Model 373 Alarm Valves Flange/Groove 21/2" Valve 4" Valve 6" Valve Item/Setup Symbol Number Part Number Symbol Number Part Number Symbol Number Part Number Alarm Valve only (without trim) Trim setup for Alarm Valve: For Variable Pressure (less Retard Chamber) For Constant Pressure 3732V V 3534C V 3536C Retard Chamber Automatic Model B Note: Retard Chamber is to be ordered separately and in addition to the trim setup for variable pressure Trim Option for Alarm Switch (less Switch) 86A A A Alarm Valve, PreTrimmed For Variable Pressure, Retard Chamber included SVL200 3
8 "Automatic" Model 373 Valve Assemblies Parts List "Automatic" Model 373 Alarm Valve Assemblies Flange/Groove 21/2 Valve 4 Valve 6 Valve Item Number Valve Body Subassembly Body Seat Ring Part Name Material Symbol Number Handhole Cover Nameplate Drive Screws: #0 x ¼ 2 required Handhole Cover Gasket Hex Head Cap Screws 5/16 18 x 11/4 long 6 required 3/8 16 x 11/2 long 6 required Clapper Subassembly Clapper Clapper Facing Retaining Disc Retaining Disc Cast Iron Bronze Cast Iron Aluminum Steel Rubber Steel Steel Stainless Steel Rubber Stainless Steel Bronze Shoulder Bolt Shoulder Bolt Gasket SelfLocking Nut: 3/8 16 Brass Rubber Stainless Steel 9 Hinge Pin Stainless Steel 10 Hinge Pin Bushings (2 in Body) Bronze 11 3/8 Plug Brass Handhole cover and related items are not shown in detail. These items are not field replaceable Part Symbol Number Number S S Part Symbol Part Number Number Number S S SVL200
9 "Automatic" Model B Retard Chamber Parts List "Automatic" Model B Retard Chamber Item Number Part Name Material Symbol Number Part Number 1 Retard Chamber Body Cast Iron Outlet Plug Assembly S Outlet Plug Screen Brass Brass 3 Drain Plug Assembly S Drain Plug Screen Brass Brass 4 ORing Gasket BunaN SVL200 5
10 "Automatic" 2½" Model 373 Alarm Valve Flange/Groove Vertical/Variable Pressure Trim Setup 3732V with Retard Chamber 6 SVL200
11 "Automatic" 4" Model 373 Alarm Valve Flange/Groove Vertical/Variable Pressure Trim Setup 3734V with Retard Chamber SVL200 7
12 "Automatic" 4" Model 373 Alarm Valve Flange/Groove Vertical/Constant Pressure Trim Setup 3734C 8 SVL200
13 "Automatic" 6" Model 373 Alarm Valve Flange/Groove Vertical/Variable Pressure Trim Setup 3736V with Retard Chamber SVL200 9
14 "Automatic" 6" Model 373 Alarm Valve Flange/Groove Vertical/Constant Pressure Trim Setup 3736C 10 SVL200
15 Testing and Maintenance Reference. NFPA 25, Standard for the Inspection, Testing and Maintenance of Water Based Fire Protection Systems. Testing Before proceeding with any tests involving water flow, certain precautions need to be taken. 1. Check the location where the test connection discharges to make sure that all is clear and that there is no possibility of the water flow causing damage or injury. 2. Check the end of the test connection to make sure that it is unobstructed. To obtain a satisfactory test, there must be an unrestricted flow of water when the test valve is wide open. 3. Check for alarm connections to a central station or fire department. If such connections are found, give proper notice to the signal receiving station before proceeding with the test. Note: A main drain test will also operate local fire alarms unless they are temporarily shut off. Testing Alarm Valve and Waterflow Alarm Devices. NFPA 25 recommends that the alarm valve and its waterflow alarm devices be tested at least quarterly. The primary way to test this equipment is by opening the Inspectors Test Connection. This connection, generally located at the highest and most remote point on the system in relation to the alarm valve, consists of a test orifice and controlling globe valve. Opening of the globe valve (Inspectors Test Valve), and the subsequent discharge of water through the test orifice, simulates the operation of a sprinkler. Therefore, alarm devices should sound and/or operate when the Inspectors Test Valve is opened. An alternate means of testing waterflow alarm devices is to open the Alarm Test Valve provided as part of the alarm valve trim. It must be noted, however, that opening of this valve only tests the alarms; it does not test the operation of the alarm valve since the supply for the alarm test line is taken from a point below the alarm valve clapper (see Description/Operation). This means of testing, therefore, should only be used when weather conditions or other circumstances prohibit using the Inspectors Test Connection. Note: If alarms connect to a central station or fire department, notify the signal receiving station when all tests have been completed. Flow Test at Main Drain Valve (Main Drain Test). NFPA 25 recommends that a water flow test be made quarterly from the main drain valve at the system riser. The purpose of this test is to show whether or not the normal water supply is available to the system. By comparing static and residual pressure readings with those previously established, a main drain test can indicate the possible presence of closed valves or other obstructions in the supply piping. The procedure for conducting a Main Drain Test is as follows: 1. With the Main Drain Valve closed, note and record the reading on the lower Pressure Gage at the Alarm Valve. 2. Open the Main Drain Valve slowly until it is fully open. Then, check to make sure that a full steady flow of water is discharging from the main drain pipe. Note: If a full steady stream is not discharging, check the main drain piping further for possible obstructions. 3. Allow the water to flow until the reading on the lower Pressure Gage drops and stabilizes. Then, record this reading. Note: The first and higher pressure reading is the static pressure. The second, lower reading is the residual pressure with a given flow discharging from the main drain pipe. 4. Close the Main Drain Valve slowly. Caution: If alarms have been temporarily shut off, they must be returned to service. If alarms connect to a central station or fire department, notify the signal receiving station when the test has been completed. 5. Compare both pressure readings with previously established or normal readings. Note: If the readings compare favorably, the water supply may be considered satisfactory. If, however, the pressure readings vary to any great extent, the condition should be investigated to determine the cause. Some possible causes are: Partially or totally closed system control valves. Clogged or frozen water mains. Serious leakage at valves or mains. SVL200 11
16 Maintenance The "Automatic" Model 373 Alarm Valve and its related equipment should be examined periodically to ensure proper operation and trouble free service. Several areas to be routinely inspected are: Clapper Facing. The rubber clapper facing should be checked for wear or damage, and to determine that it is free of dirt and other foreign substances. If found to be worn or damaged (e.g., foreign matter imbedded in the surface), the facing should be replaced. If it is dirty, it should be cleaned, but compounds which could damage the rubber facing must never be used. Seat Ring. The seat ring should be checked for nicks and for stones, dirt or other foreign matter lodged in the grooves or holes. It should be cleaned thoroughly. If the seat ring is found to be severely damaged, the complete alarm valve assembly should be replaced. ByPass Check Valve. The 3/4" check valve in the external bypass should be checked for clapper and seat condition. Retard Chamber. The outlet plug and drain plug assemblies should be checked for obstructions. The screens should be cleaned thoroughly. Alarm Line Strainer. The 3/4" strainer in the alarm line of the constant pressure trim setup should be checked and cleaned thoroughly. Alarm Test Valve, Main Drain Valve & Inspection Test Valve. All controlling valves which are normally closed when the alarm valve is in the set position should be checked to be sure that they are fully closed and not leaking. Alarm Valve and Trim. The overall setup should be checked for visible leaks and possible physical damage to the valve and connections (e.g., broken gages). Resetting of System The "Automatic" Model 373 Alarm Valve is selfresetting when testing procedures are followed. When sprinklers operate, however, there are certain procedures which must be followed for restoring the system to service. 1. Close the System Control Valve (OS&Y, PIV or other). Caution: In the event of a fire, the system control valve is to be closed only after it has been determined, positively, that the fire has been extinguished. 2. Close the Alarm Control Valve. 3. Open the Main Drain Valve. Note: It is necessary to drain the system only as required to allow for sprinkler replacement. 4. Replace the sprinklers which have operated. 5. Close the Main Drain Valve. 6. Open the Inspectors Test Valve. Note: This valve is opened to permit air to be vented from the system as it is being filled with water. 7. Slowly open the System Control Valve. Caution: Open the valve only partially at the stsrt of water flow into the system. Do not open it fully at this point. To do so may cause a water hammer to occur which could either damage the piping or trap large volumes of air within the system. 8. Continue filling the system until water discharges in a continuous stream from the Inspectors Test Connection. 9. Close the Inspectors Test Connection. 10. Turn the System Control Valve to its full open position, at the same time observing the Pressure Gages. Note: The system is filled when both gages are steady and have the same pressure reading. 11. Conduct a Main Drain Test to make sure the water supply is satisfactory (see Flow Test at Main Drain Valve). 12. Open the Alarm Control Valve. 13. Conduct a test of the alarm devices (see Testing Alarm Valve and Waterflow Alarm Devices). 14. Seal, lock, or otherwise secure the System Control Valve and Alarm Control Valve in an open position (per NFPA 25). The system is now ready for service. 15. If alarms connect to a central station or fire department, notify the signal receiving station that the system has been returned to service. 12 SVL200
17 Accessories Pressure Relief Connections General A number of conditions can cause high pressure in a wet system. "Automatic" Pressure Relief Connections are designed to protect against only those that cause high pressure intermittently for example, pressure increases due to water surges in the supply main or thermal expansion within the system. If high pressure is a constant condition, then other precautions must be taken to protect the system. Pressure relief connections should be provided as original equipment when it is known at the time the system is installed that conditions warrant their use. If adverse conditions are found some time later on, however, the connections may be added to any "Automatic" alarm valve. Approvals "Automatic" Pressure Relief Connections should be provided subject to the approval of the authority having jurisdiction (AJH). While suitable for the intended service, the relief valve is not UL Listed ot FM Approved. The connections are suitable only for a normal maximum working water pressure of 175 psi. Description/Operation "Automatic" Pressure Relief Connections connect to the alarm valve at the upper water pressure gage and relieve to atmosphere through the main drain pipe. A set of connections includes a relief valve set for a normal cracking pressure of 180 psi. At this setting, the valve will open at a maximum of 185 psi (180psi ± 5 psi) to keep the system below the required 175 psi WWP. Installation When making the installation, care must be taken to be sure that all pipe and fittings are clean and free of scale and burrs. Teflon tape is recommended to seal joints. If pipe compound is used, it should be applied sparingly and only to male threads. SVL200 13
18 If the connections are installed as original equipment, the globe valve must be closed when the hydrostatic test is provided for the system. When the system is placed in service, the valve should be sealed open. Maintenance The water pressure gage on the system side of the alarm valve should be inspected frequently to be sure that the relief valve is operating properly. If the pressure is found to be in excess of 175 psi, the globe valve should be checked to see if it is open. If the valve is closed, opening it should correct the problem. If the high pressure problem exists with the globe valve open, both the globe valve and the relief valve should be checked for obstructions. If no obstructions are found and the high pressure problem continues to exist, the relief valve should be replaced with a new one. No attempt should be made to reset or repair the relief valve. Availability/Ordering Information Pressure Relief Connections are available from "Automatic" Sprinkler. To order specify: (qty) Set(s) of Pressure Relief Connections for Wet System Symbol No. 353PRC Stock Code No SVL200
19
20 This information is only a general guideline. The company reserves the right to change any portion of this information without notice. Terms and conditions of sale apply and are available on request. 2/02 Printed in USA (SLV200.P65) "Automatic" Sprinkler 150 Gordon Drive Exton, PA USA Tel: (610) Fax: (610)
3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide
", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,
More informationTECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
More informationRAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description
Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description The TYCO RAPID
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationWet System. Technical Manual for Operation, Maintenance, and Troubleshooting
Wet System Technical Manual for Operation, Maintenance, and Troubleshooting October, 2008 Form No. F_010508 Page II October 15, 2008 Table of Contents Page I. DESCRIPTION 3 II. APPLICATIONS 4 III. REQUIREMENTS
More informationWet alarm valves. Wet alarm valves. FM trim
Description Usually, a wet alarm valve station comprise: - a Rolland wet alarm valve linked to the water motor gong. - a set of valves and by pass used to test the system. - a drain valve. - a test valve
More informationFloat and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
More informationTechnical Data. Installation
Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems General Description The Figure 51 (1) Riser Manifolds
More informationTYPE E Main Valve Sizes 3 /8 through 12
SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,
More informationTD01211 PIN: NX010 201007.2 nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA
Water Motor Alarm MODEL: NX010 GENERAL DESCRIPTION TECHNICAL SPECIFICATIONS Model NX010 Working Water Pressure Range 5 to 175 psig 0.035 to 1.2 MPa (0.35 to 12 bar) Shipping Weight 11 lbs 5 kg Alarm Line
More informationDiameter 3" 4" 6" 8" Flange type PN 16 PN 16 PN 16 PN 16. Orange-red ( RAL 2002) Height (cm) 27,70 26,30 28,70 29.70
Description Usually, a wet alarm valve station comprise: a Rolland wet alarm valve linked to the water motor gong. a set of valves and by pass used to test the system. a drain valve. a test valve gauges
More informationMustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
More information1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 thru inch (DN40 thru DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical
More informationI-768 FireLock NXT Dry Valve
HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR EASY FUTURE REFERENCE WARNING WARNING Failure to follow instructions and warnings can cause product failure, resulting in serious personal injury and
More informationPRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
More informationDV-5 Deluge Valve with Remote-Resetting, Pressure-Reducing Trim 4 Inch and 6 Inch (DN100 and DN150) General Description.
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim 4 Inch and 6 Inch (DN and DN5) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water
More informationPreaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation /2 thru 8 Inch (DN thru DN200) General Description The DV5 Supervised Single
More informationPotter Electric Sprinkler Monitoring Training Manual
R Potter Electric Sprinkler Monitoring Training Manual 1 #8704200D 2 Contents Foreword... 4 Introduction... 5 Fire Alarm Signals... 6 Types Of Sprinkler Systems... 7 Wet Pipe Sprinkler Systems... 8 Straight
More informationFeatures. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)
Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0.6 bar -to- 1.9 bar) Max 3. Reset externally. Cover removal is not
More informationDARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES
SECTION 15062 STEAM AND CONDENSATE PIPING PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Comply with the provisions of the following: 1.2 DESIGN CRITERIA 1. ASME B 31.9 Building Services Piping : for
More informationInstallation and Operating Instructions Installation Instructions for SS EPE-316L Series
INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
More informationConstantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW
Installation, Operating and Maintenance Instructions 90/4.5.5 Rev. 0 Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW Table of Contents SECTION I... 2 INSTALLATION...
More informationOPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT
OPERATION AND MAINTENANCE MANUAL 5-1/4 B-84-B-5 FIRE HYDRANT INDEX AMERICAN - DARLING 5-1/4 IN. B-84-B-5 FIRE HYDRANT OPERATION AND MAINTENANCE MANUAL OPERATION AND MAINTENANCE REPAIRS Operation and Maintenance...
More informationTRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007
TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES 301.010 ANNUAL SERVICE TEST FOR FIRE HOSE EFFECTIVE: OCTOBER 2007 The Department will test all fire hose annually. The testing of fire hose determines its serviceability.
More informationSELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
More informationModel RV-1 Pressure Relief Valve 2 to 8 Inch (DN50 to DN200), 250 psi (17,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description
Technical Services 00-3-932 +-0-7-220 www.tyco-fire.com Model RV- Pressure Relief Valve 2 to Inch (DN50 to DN200), 250 psi (7,2 bar) Pilot-Operated, Globe and Angle Body Styles General Description The
More informationFIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
More informationAmerican- Darling 5¼" B-84-B-5.
-5 Sealed Lubrication Chamber Seals operating threads from water and debris which greatly reduces routine maintenance. Top Travel Stop Nut Helps prevent stem buckling and damage to bronze components which
More informationESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA
December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas
More informationNFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
More informationINSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS
INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS SETTING UP THE PRESS FOR OPERATION For shipping convenience, the gauge, pump handle, hoist crank, screw nose and base angles
More informationModel F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
More informationesfr pendent sprinkler vk510 (k25.2)
January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition
More informationMorrison Bros. Co. General Product Specifications
Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage
More informationAPCO SLOW CLOSING AIR/VACUUM VALVES
BULLETIN 1 JULY 01 APCO SLOW CLOSING AIR/VACUUM VALVES Series 1900 APCO Slow Closing Air/Vacuum s Maximum Air Flow Velocity in Good Pipeline Design The Air/Vacuum operates in the normal fashion allowing
More informationSTORAGE, INSTALLATION AND MAINTENANCE PROCEDURES
GATE VALVE O.S. & Y 1.0 Periodic Inspections 1.1 The valve stem packing should be inspected at least monthly. If the stem packing shows signs of leakage, simply tighten the adjusting nuts to compress the
More informationAIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
More informationPBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationBERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features
Pressure Relief/Sustaining Valve Prioritizing pressure zones Ensuring controlled pipeline fill-up Preventing pipeline emptying Pump overload & cavitation protection Safeguarding pump minimum flow Excessive
More information4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX
Butterfly Valves 4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com MAY 2013 L-1 BULLETIN BUTTERFLY REV. #5 GLOBE BUTTERFLY VALVE INSTALLATION
More informationFisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation
Instruction Manual 1052 Size 20 Actuator (F & G) Fisher 1052 Size 20 Diaphragm Rotary Actuator with F and G Mounting Adaptation Contents Introduction... 1 Scope of manual... 1 Description... 1 Specifications...
More informationCHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined
Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority
More informationFOAM CHAMBER MODEL - FCA & FCA-S HD FIRE PROTECT PVT. LTD. TECHNICAL DATA FEATURES APPLICATION. Carbon Steel Construction FCA-65, FCA-80 & FCA-100
MODEL - FCA & FCA-S HD FIRE PROTECT TECHNICAL DATA MODELS FCA-65, FCA-80 & FCA-100 Carbon Steel Construction FCA-S 65, FCA-S 80 & FCA-S 100 Stainless Steel Construction INLET SIZE 65, 80, 100 NB WORKING
More informationOPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS. INTRODUCTION...1 Scope...1 Description...1 Valve Identification...
OPERATING and MAINTENANCE MANUAL SERIES 2700A CONTROL VALVE CONTENTS INTRODUCTION...1 Scope...1 Description...1 Valve Identification...2 1.0 VALVE INSTALLATION...2 2.0 VALVE MAINTENANCE...3 Actuator Disassembly...3
More informationStandard Hydraulic Piping Flushing Procedure
Page 1 of 6 1.0 Scope This procedure covers the minimum technical requirements for cleaning and flushing of Hydraulic and Piping, and related accessories. 2.0 Introduction In hydraulic fluid power systems,
More informationInstruction Manual. Alfa Laval SB Membrane Sample Valve ESE02963-EN1 2015-10. www.sks-online.com www.sks-webshop.com.
Instruction Manual Alfa Laval SB Membrane Sample Valve ESE02963-EN1 2015-10 Original manual Table of contents The information herein is correct at the time of issue but may be subject to change without
More informationTECHNICAL DATA. NOTES: For use with Trim Chart on page 27 b. (open fold-out)
De cem ber 6, 1999 Trim 27 a MODEL J-1 ALARM CHECK VALVE VERTICAL TRIM Maximum 250 PSI WWP This Trim Chart is for use with the following Viking Trim Sets Valve Size Standard* Trim P/N Foam System** Trim
More informationTrash Pumps Models: 56200, 562000, 56201, 562001, 56300, 563000, 56301, 563001
Trash Pumps Models: 56200, 562000, 56201, 562001, 56300, 563000, 56301, 563001 Specifically designed pumps for heavy duty applications Handles solids with eas and simple to open and clean Standard roll
More informationSTORED PRESSURE STAINLESS STEEL
STORED PRESSURE STAINLESS STEEL WATER FIRE EXTINGUISHERS Model 240-2-1/2 Gallon OWNER'S SERVICE MANUAL NO. 05601 INSPECTION, MAINTENANCE AND RECHARGE All fire extinguishers should be installed, inspected
More informationTECHNICAL DATA. 30a. September 18, 2009 1-1/4-8 (DN32 - DN200)
September 18, 2009 30a 1. DESCRIPTION Viking EasyPac Commercial Riser Manifold Assemblies are available in sizes 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 6 and 8 for commercial systems. They are available with an
More informationAIR LINE VALVES AND GAUGES
AIR LINE VALVES AND GAUGES INGERSOLL-RAND AIR LINE VALVES AND GAUGES Maintaining consistent air pressure throughout the entire system is crucial for maximum performance and productivity. Ingersoll-Rand
More informationProduct Manual. CVS Type 67AFR Filter Regulator. Introduction. Installation. Description
Product Manual CVS Type 67AFR Filter Regulator Introduction This CVS Controls product manual includes instructions for the installation, adjustment, maintenance and parts ordering of the CVS Type 67AFR
More information5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationFire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
More informationELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
More informationInstallation, Maintenance, & Repair Series 4000B/LF4000B
Installation, Maintenance, & Repair Series 4000B/LF4000B Reduced Pressure Zone Assemblies Sizes: 1 2" 2" (15 50mm) RP/IS-A-4000B 4000B/LF4000B Size: 3 /4"! WARNING Testing Read this Manual BEFORE using
More informationINSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303
WATER MIST HAND PORTABLE FIRE EXTINGUISHERS Model B270 ¾ Gallon Model B272 2 ½ Gallon INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 6303 All fire extinguishers should be installed, inspected
More informationRisk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems
Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Introduction Fire protection systems are provided in or at a building to safeguard the lives of building
More informationDiesel Fuel Systems. Injection Nozzles
Diesel Fuel Systems Injection Nozzles Unit Terms Injection nozzle Nozzle, nozzle holder, valve, spring assembly Nozzle assembly Valve, body, and spray valve Orifice Small hole Pintle Valve which the end
More informationTrunnion-Design Ball Valves
Trunnion-Design Ball Valves 12" 20" (DN 300 500) Series 7150 12" (DN 300) Series 730S 12" 20" (DN 300 500) Series 7300 14" 24" (DN 350 600) Series 9150 14" 24" (DN 350 600) Series 9300 Installation, Maintenance
More informationALARM VALVE MODEL-H LISTED 3S38 TECHNICAL DATA OPERATION DESCRIPTION
Tel: 0000 Fax: 0000 Email: info@fireguarduk.com nd FLOOR ST.JOHNS STREET LONON EV PY UNITE KINGOM LRM VLVE MOELH TEHNIL T MOEL NOMINL SIZE MXIMUM SERVIE PRESSURE THREE OPENING ESRIPTION larm Valve is a
More informationYour safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
More informationV47 Series Temperature Actuated Modulating Water Valves
V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate
More informationAKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS
AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style
More informationInstallation Manual DIAPHRAGM WELL TANK
Installation Manual DIAPHRAGM WELL TANK IN-LINE SERIES: 2-5 & 7 GALLON VERTICAL SERIES: 14-20-25-32-36-52-65-86-96-119 GALLON HORIZONTAL SERIES: 7-14 & 20 GALLON NO LEAD NO LEAD: The weighted average of
More informationMODEL 300505 INSTALLATION INSTRUCTIONS
WWW.BURCAM.COM 2190 Boul. Dagenais West TEL: 514.337.4415 LAVAL (QUEBEC) FAX: 514.337.4029 CANADA H7L 5X9 info@burcam.com Your pump has been carefully packaged at the factory to prevent damage during shipping.
More informationAutomatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
More informationSeries 30000 Hose Reels
Operating Instructions and Parts List for Series 30000 Hose Reels - MANUAL DRIVEN - - POWER DRIVEN - SAFETY PRECAUTIONS Personal injury and/or equipment damage may result if proper safety precautions are
More informationNITROUS TRANSFER PUMP INSTRUCTIONS
NITROUS TRANSFER PUMP INSTRUCTIONS SAFETY TIPS Never directly inhale nitrous oxide. When inhaled in large quantities, nitrous oxide can cause respiratory ailments or in extreme cases, death by suffocation.
More informationDeZURIK 3-20" BAW AWWA BUTTERFLY VALVES WITH TRANSFER MOLDED SEAT
3-20" BAW AWWA BUTTERFLY VALVES WITH TRANSFER MOLDED SEAT Instruction D10386 August 2013 Instructions These instructions provide installation, operation and maintenance information for BAW Butterfly Valves.
More informationTECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
More informationFOAM CHAMBER MODEL - FC
FOAM CHAMBER MODEL - FC TECHNICAL DATA : MODEL SIZE WORKING PRESSURE FC 50, 65, 80, 100 &150 NB inlet Minimum 2.8 Kg. / sq. cm. (40 PSI) Maximum 7 Kg. / sq.cm. (100 PSI) FLANGE CONNECTION ANSI B16.5 Class
More informationI. Introduction. 10 minutes
I. Introduction 10 minutes Introduction (1 of 2) An uninterrupted water supply is: The primary weapon for extinguishment Essential for fire fighter safety Ensuring a dependable water supply is a critical
More informationSAMPLE TEST QUESTIONS STEAMFITTER/PIPEFITTER - ITA WEBSITE
1 Which tool is used to correct internal hi-low when preparing a 4-in. steel pipe for welding? A. 4-in. grinder with cutting disc. B. Mini-grinder with flapper disc. C. Pencil grinder with cone stone.
More informationFlygt Ball Check Valves
4/13 Supersedes: 6/96 The basic purpose of a check valve is to permit flow in one direction, prevent flow in the opposite direction and perform this function automatically and with minimum maintenance.
More informationINSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
More informationBOWIE PUMPS OPERATION - MAINTENANCE
BOWIE PUMPS OPERATION - MAINTENANCE PUMPING PRINCIPLE: The meshing owieeof the gears cause a slight depression, with the resulting enmeshing of the gears causing a vacuum drawing the fluid being pumped
More informationOWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
More informationWHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 gpm@gpmhydraulic.com www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS
More informationToroidal Conductivity Sensor
Instruction Sheet PN 51A-/rev.C June 2012 Toroidal Conductivity Sensor For additional information, please visit our website at www.emersonprocess.com/rosemountanalytical.com SPECIFICATIONS Wetted Materials:
More informationAWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller
January 2013 AWWA Butterfly Valve Operation and Maintenance Manual Series 511A & 510A 20 and Smaller Milliken Valve Company 190 Brodhead Avenue, Suite 100 Bethlehem, PA 18017 Phone: (610) 861-8803 Fax:
More informationTech. Services: (800) 477-8326 Fax: (800) 765-8326 Order Entry: (800) 541-1418 Fax: (800) 288-7031 Internet Address: http://www.powerteam.
ORIGINAL INSTRUCTIONS Form No.102842 5 SPX Hydraulic Technologies 5885 11th Street Rockford, IL 61109-3699 USA Tech. Services: (800) 477-8326 Fax: (800) 765-8326 Order Entry: (800) 541-1418 Fax: (800)
More informationHYDRAULIC TABLE CART 500-LB.
HYDRAULIC TABLE CART 500-LB. OWNER S MANUAL WARNING: Read carefully and understand all MACHINE ADJUSTMENT AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic
More informationHYDRAULIC LIFT TABLE CART 2200-LB.
HYDRAULIC LIFT TABLE CART 2200-LB. OWNER S MANUAL WARNING: Read carefully and understand all MACHINE ADJUSTMENT AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other
More informationPressure Limiting Driver (PLD)
Pressure Limiting Driver (PLD) Discharge Pressure Control Suction Pressure Control June 9 2009 Mark Evans Clarke Fire Protection Products Justin Strousse Clarke Fire Protection Products Overview Discharge
More informationSpill Containers. 517 Series 3 ½ Gallons AST Spill Container. 518 Series 7 ½ Gallon AST Spill Container. 515 Series AST Remote Spill Container
Spill Containers 517 Series 3 ½ Gallons AST Spill Container Installed on aboveground storage tanks for the purpose of containing small spills and drips from the fill nozzle. 3 ½ gallon capacity. Steel
More informationSunMaxx Solar Filling Station Operating Instructions
SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...
More information! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
More informationFJ2. 2 Ton Trolley Floor Jack Assembly & Operating Instructions
FJ2 2 Ton Trolley Floor Jack Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. This manual provides important information on proper operation & maintenance.
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationChapter 7 Hydraulic System Troubleshooting
Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic
More informationwith MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
More informationESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL
ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL The Viking Corporation 210 N Industrial Park Road Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:
More informationMODEL G300 BRAKE BLEEDER
MODEL G300 BRAKE BLEEDER Installation, Operation & Repair Parts Information Branick Industries, Inc. 4245 Main Avenue P.O. Box 1937 Fargo, North Dakota 58103 REV060616 P/N: 81-0035G 1 THIS PAGE INTENTIONALLY
More informationBPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap
1263050/6 IM-P126-07 ST Issue 6 BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation
More informationCYLINDER LEAKAGE CHECK (Compression)
TELEDYNE CONTINENTAL AIRCRAFT ENGINE service bulletin M84-15 SUPERSEDES M76-18 Rev.1 Technical Portions are FAA Approved 21 December 1984 TO: SUBJECT: MODELS AFFECTED: Aircraft Manufacturers, Distributors,
More information