Kilsen KFP-CF Series Operation Manual

Size: px
Start display at page:

Download "Kilsen KFP-CF Series Operation Manual"

Transcription

1 GE Security Kilsen KFP-CF Series Operation Manual P/N REV 1.0 ISS 01MAY09

2 Copyright 2009 GE Security, Inc. This document may not be copied in whole or in part or otherwise reproduced without prior written consent from GE Security, Inc., except where specifically permitted under US and international copyright law. Disclaimer The information in this document is subject to change without notice. GE Security, Inc. ( GE Security ) assumes no responsibility for inaccuracies or omissions and specifically disclaims any liabilities, losses, or risks, personal or otherwise, incurred as a consequence, directly or indirectly, of the use or application of any of the contents of this document. For the latest documentation, contact your local supplier or visit us online at This publication may contain examples of screen captures and reports used in daily operations. Examples may include fictitious names of individuals and companies. Any similarity to names and addresses of actual businesses or persons is entirely coincidental. Trademarks and patents GE and the GE monogram are trademarks of General Electric Company. CleanMe and the Kilsen KFP-CF Series name and logo are trademarks of GE Security. Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products. Intended use Use this product only for the purpose it was designed for; refer to the data sheet and user documentation for details. For the latest product information, contact your local supplier or visit us online at Certification and compliance European Union directives 2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: /108/EC (EMC directive): Non-European manufacturers must designate an authorized representative in the Community. Our authorized manufacturing representative is: GE Security B.V., Kelvinstraat 7, 6003 DH Weert, The Netherlands. 2006/66/EC (battery directive): This product contains a battery that cannot be disposed of as unsorted municipal waste in the European Union. See the product documentation for specific battery information. The battery is marked with this symbol, which may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). For proper recycling, return the battery to your supplier or to a designated collection point. For more information see: Contact information For contact information see our Web site:

3 Content Introduction 1 Product range 1 Operating modes 1 Sounder and fire routing delays 2 Control panel overview 3 User interface for two- and four-zone control panels 3 User interface for eight-zone control panels 4 Operator controls and indicators 5 Acoustic indicators 7 Summary of status indications 7 Control panel operation 10 Access levels 10 Basic operation 11 Advanced operation 13 Maintenance 17 Fire alarm system maintenance 17 Battery maintenance 18 Product compliance 19 Kilsen KFP-CF Series Operation Manual I

4 II Kilsen KFP-CF Series Operation Manual

5 Introduction This is the access level 1 and access level 2 operation manual for the Kilsen KFP-CF series fire alarm control panels. Read these instructions and all related documentation entirely before operating this product. Product range The KFP-CF series includes the models shown below. Model KFP-CF2 KFP-CF4 KFP-CF8 Description Two-zone fire alarm control panel Four-zone fire alarm control panel with fire routing Eight-zone fire alarm control panel with fire routing Fire routing on the four- and eight-zone models is not available for all operating modes. See Sounder and fire routing delays on page 2. Operating modes Supported operating modes are shown in the table below. The default operating mode is EN Table 1: Operating modes Operating mode EN 54-2 (default) EN 54-2 Evacuation EN 54-2 Scandinavia BS NBN S NEN 2535 Region European Union European Union (Spain) European Union (Scandinavia) United Kingdom Belgium The Netherlands The choice of operating mode used depends on your location and the specific regional requirements of your fire alarm system. As there is no visual indication of the active operating mode, your installation or maintenance contractor should provide full details of your configuration. Kilsen KFP-CF Series Operation Manual 1

6 Sounder and fire routing delays Sounder and fire routing delays are not available for all operating modes. The table below shows delay availability for each operating mode. Table 2: Sounder and fire routing delays Operating mode Sounder delay Fire routing delay Extended fire routing delay EN 54-2 Yes Yes No EN 54-2 Evacuation Yes No No EN 54-2 Scandinavia Yes Yes Yes BS Yes No No NBN S Yes No No NEN 2535 No Yes Yes Note: Fire routing is not available on any two-zone control panel. 2 Kilsen KFP-CF Series Operation Manual

7 Control panel overview This topic provides an introduction to the control panel interface, operator controls, and indicators. User interface for two- and four-zone control panels Figure 1: User interface for two- and four-zone control panels 1. Zone buttons and LEDs (Z1, Z2, etc.) 2. Supply LED 3. General Fault LED 4. General Fire Alarm LEDs 5. Sounder Fault/Disable/Test button and LED 6. Sounder Delay button and LED 7. Network Fault LED 8. Service Detector LED 9. Expansion I/O Fault/Disabled LED 10. General Disable button and LED 11. General Test button and LED 12. Configuration controls 13. Reset button and LED 14. Panel Silence button and LED 15. Sounder Start/Stop button and LED 16. System Fault LED 17. Out of Service LED 18. Earth Fault LED 19. Supply Fault LED 20. Fire Routing Delay button and LED 21. Fire Routing Start and Fault/Disable/Test button and LEDs Note: Two-zone control panels do not include fire routing. Kilsen KFP-CF Series Operation Manual 3

8 User interface for eight-zone control panels Figure 2: User interface for eight-zone control panels 1. Zone buttons and LEDs (Z1, Z2, etc.) 2. Supply LED 3. General Fault LED 4. General Fire Alarm LEDs 5. Sounder Fault/Disable/Test button and LED 6. Sounder Delay button and LED 7. Network Fault LED 8. Service Detector LED 9. Expansion I/O Fault/Disabled LED 10. General Disable button and LED 11. General Test button and LED 12. Configuration controls 13. Reset button and LED 14. Panel Silence button and LED 15. Sounder Start/Stop button and LED 16. System Fault LED 17. Out of Service LED 18. Earth Fault LED 19. Supply Fault LED 20. Fire Routing Delay button and LED 21. Fire Routing Start and Fault/Disable/Test button and LEDs 4 Kilsen KFP-CF Series Operation Manual

9 Operator controls and indicators The following table gives an overview of the control panel operator controls and indicators. Item numbers refer to Figure 1 on page 3 and Figure 2 on page 4. Operational features described here may not be available to all users. Further information on control panel operation and access restrictions can be found in the topic Control panel operation on page 10. Table 3: Operator controls and LED indicators Item Control/LED LED colour Description 1 Zone button and LEDs Red/Yellow Disables or tests a zone (when pressed together with the general Disable or general Test button). The red LED indicates an alarm in the corresponding zone. A flashing red LED indicates that the fire alarm was activated by a detector. A steady red LED indicates that the fire alarm was activated by a manual call point. The yellow LED indicates a fault, test, or disablement in the corresponding zone. A flashing yellow LED indicates a fault. A steady yellow LED indicates that the zone is disabled or is being tested. 2 Supply LED Green Indicates that the system is powered up correctly. 3 General Fault LED Yellow Indicates a fault. The corresponding zone, device, or function fault LED also flashes. 4 General Fire Alarm LEDs 5 Sounder Fault/Disable/ Test button and LED 6 Sounder Delay button and LED Red Yellow Yellow Indicates a fire alarm. Flashing LEDs indicate that the fire alarm was activated by a detector. Steady LEDs indicate that the fire alarm was activated by a manual call point. The corresponding zone alarm LED indicates the source of fire alarm. 7 Network Fault LED Yellow Indicates a network fault. Disables or tests sounders (when pressed with the general Disable or general Test button). A flashing LED indicates a fault with the sounders. A steady LED indicates that the sounders are disabled or are being tested. Enables or disables a previously configured sounder delay. A steady LED indicates that a sounder delay is configured and enabled. 8 Service Detector LED Yellow Indicates that a detector requires servicing (CleanMe compatible detectors only). 9 Expansion I/O Fault/Disabled LED Yellow Indicates that an installed expansion module has a fault or is disabled. A flashing LED indicates a fault with an expansion module. A steady LED indicates that an expansion module is disabled. Kilsen KFP-CF Series Operation Manual 5

10 Item Control/LED LED colour Description 10 General Disable button and LED 11 General Test button and LED 12 Numeric keypad and Enter button Yellow Yellow N/A Disables a zone, sounders, fire routing, or expansion I/O module (when pressed with the corresponding button). A steady general Disable LED and the corresponding zone, sounders, or fire routing Fault/Disable/Test LED indicates a disablement. Tests a zone, sounders, or fire routing (when pressed with the corresponding button). A steady general Test LED and the corresponding zone, sounders, or fire routing Fault/Disable/Test LED indicates a test. Used to enter the access level 2 password. The Enter button is also used to disable expansion I/O modules (when pressed with the general Disable button). 13 Reset button Yellow Resets the control panel and clears all current system events (except expansion I/O module fault communication). A steady LED indicates that access level 2 is active (see Access levels on page 10). 14 Panel Silence button and LED 15 Sounder Start/Stop button and LED Yellow Red Silences the internal buzzer and acknowledges all current events. A steady LED indicates that all current events were acknowledged. Stops (silences) all active sounders. Pressing the button again restarts them. A flashing LED indicates that sounders activate when a configured delay elapses. A steady LED indicates that the sounders are active (sounding). 16 System Fault LED Yellow Indicates a control panel CPU failure. 17 Out of Service LED Yellow Indicates that the control panel is not operational. 18 Earth Fault LED Yellow Indicates an earth fault. 19 Supply Fault LED Yellow Indicates a fault with the power supply. 20 Fire Routing Delay button and LED 21 Fire Routing Start button and LED Yellow Red A flashing LED indicates a battery or battery fuse fault. A steady LED indicates a mains or mains fuse fault. Enables or disables a previously configured fire routing delay. A steady LED indicates that a fire routing delay is configured and enabled. Cancels a previously configured delay and activates fire routing. A flashing LED indicates that fire routing activates when the configured delay elapses. A steady LED indicates that fire routing is active. 6 Kilsen KFP-CF Series Operation Manual

11 Item Control/LED LED colour Description 21 Fire Routing Fault/Disable/Test button and LED Yellow Indicates that fire routing is in a fault condition, is disabled, or is being tested. A flashing LED indicates a fault. A steady LED indicates that the function is disabled or is being tested. Acoustic indicators The control panel uses the following acoustic indicators to highlight system events. Indication The internal buzzer sounds constantly The internal buzzer sounds intermittently Description Indicates a fire alarm or a system fault Indicates all other faults Summary of status indications This section includes a summary of the control panel status indications. Standby (normal status) Standby, or normal status, is indicated as follows: The Supply LED is steady. If a sounder delay was enabled, the Sounder Delay LED is steady. If a fire routing delay was enabled, the Fire Routing Delay LED is steady. There are no acoustic indications. Fire alarm Fire alarm status is indicated as follows: The general Fire Alarm LEDs are flashing if the alarm was activated by a detector or steady if the alarm was activated by a manual call point. The corresponding zone alarm LEDs are flashing if the alarm was activated by a detector or steady if the alarm was activated by a manual call point. If a sounder delay was enabled, the Sounder Delay LED is steady. The Sounder Start/Stop LED flashes while the delay is active. When the sounders are active (sounding), the LED is steady. If a fire routing delay was enabled, the Fire Routing Delay LED is steady. The Fire Routing Start LED flashes while the delay is active. When fire routing is active, the LED is steady. The internal buzzer sounds constantly. Alarms activated by a manual call point always take priority over alarms activated by a detector. If an alarm is activated by both devices, the Fire Alarm LEDs and zone alarm LEDs are steady. Kilsen KFP-CF Series Operation Manual 7

12 Fault Fault status is indicated as follows: General faults are indicated by the general Fault LED and the corresponding zone, function, or device fault LED indicator flashing. Mains power faults and mains fuse faults are indicated by a flashing general Fault LED and a steady Supply Fault LED. Battery power and battery fuse faults are indicated by a flashing general Fault LED and a flashing Supply Fault LED. Earth faults are indicated by a flashing general Fault LED and a steady Earth Fault LED. The internal buzzer sounds intermittently. WARNING: Contact your installation or maintenance contractor to investigate the cause of all reported faults. Disabled Disabled zones are indicated as follows: The general Disable LED and the corresponding zone Fault/Disable/Test LEDs are steady. There is no acoustic indicator. Disabled sounders are indicated as follows: The general Disable LED and the Sounder Fault/Disable/Test LEDs are steady. There is no acoustic indicator. Disabled fire routing is indicated as follows: The general Disable LED and the Fire Routing Fault/Disable/Test LEDs are steady. There is no acoustic indicator. Disabled expansion modules are indicated as follows: The general Disable LED and the I/O Fault/Disabled LEDs are steady. There is no acoustic indicator. Test A zone test is indicated as follows: The general Test and the corresponding zone Fault/Disable/Test LEDs are steady. There is no acoustic indicator. A sounder test is indicated as follows: The general Test and the Sounder Fault/Disable/Test LEDs are steady. There is no acoustic indicator. A fire routing test is indicated as follows: The general Test and the Fire Routing Start Fault/Disable/Test LEDs are steady. There is no acoustic indicator. 8 Kilsen KFP-CF Series Operation Manual

13 Out of service WARNING: When the control panel indicates Out of Service, your fire alarm system is inactive and your site is not protected. Contact your installation or maintenance contractor immediately to investigate the problem. The control panel is out of service when there is insufficient or no mains and/or battery power. In this state there is no further fire alarm or fault warning and all panel operation stops. Out of service is indicated as follows: The Supply LED flashes if there is no mains power and the battery voltage is insufficient. The Supply LED is steady if the mains power is insufficient and no battery power is detected. The Out of Service LED is steady. The internal buzzer sounds intermittently. When power is re-established the control panel returns to its former status. Caution: To avoid damage to batteries, we recommended that you disconnect them when the control panel is out of service. Kilsen KFP-CF Series Operation Manual 9

14 Control panel operation Access levels For your safety, operation of some features of this product are restricted by access level. Access level 1 Access level 1 is the default access level and allows basic operational access only, such as responding to a fire alarm or fault warning at the control panel. The tasks you can perform at this access level are detailed in the topic Basic operation on page 11. Access level 2 Access level 2 allows advanced operational access. It is reserved for authorized users who have been trained to operate the control panel. The default access level 2 password is The tasks you can perform at this access level are detailed in the topic Advanced operation on page 13. Entering access level 2 To enter access level 2: 1. Enter the access level 2 password using the numeric keypad. 2. Press Enter. A long beep and a steady Reset LED indicate that the correct password was entered and access level 2 is active. Note: Three short beeps accompanied by a flashing general Fault LED indicate that an incorrect password was entered. Exiting from access level 2 The control panel automatically exits from access level 2 and reverts to access level 1 after five minutes if no button is pressed. 10 Kilsen KFP-CF Series Operation Manual

15 Basic operation Basic operation includes those tasks that can be performed when the control panel is in access level 1, the default access level. Basic operation in access level 1 lets you: Acknowledge a system event and silence the internal buzzer Cancel an active sounder delay Cancel an active fire routing delay Perform a control panel LED and internal buzzer test No other system controls are available at access level 1. Acknowledging a system event and silencing the internal buzzer To acknowledge a system event and silence the internal buzzer, press the Panel Silence button. A steady Panel Silence LED indicates that the internal buzzer was silenced and that all current events were acknowledged. Cancelling an active sounder delay If a sounder delay is enabled and active, press the Sounder Start/Stop button to cancel the delay and activate sounders immediately. A sounder delay is indicated as follows: A steady Sounder Delay LED indicates that a delay is enabled. A flashing Sounder Start/Stop LED during a fire alarm indicates that the configured delay is active (sounders are activated when the configured delay elapses or when the delay is cancelled). A fire alarm activated by a manual call point overrides any configured delay and activates sounders immediately. Cancelling an active fire routing delay If a fire routing delay is enabled and active, press the Fire Routing Start button to cancel the delay and activate fire routing immediately. A fire routing delay is indicated as follows: A steady Fire Routing Delay LED indicates that a delay is enabled. A flashing Fire Routing Start LED during a fire alarm indicates that the configured delay is active (fire routing is activated when the configured delay elapses or when the delay is cancelled). A fire alarm activated by a manual call point overrides any configured delay and activates fire routing immediately. Kilsen KFP-CF Series Operation Manual 11

16 Performing a control panel LED indicator and internal buzzer test To perform a control panel LED indicator and internal buzzer test, press and hold the Test button for three seconds or more. The test is indicated as follows: The general Fault and System Fault LEDs flash. All other LEDs are steady. The internal buzzer sounds constantly. The test continues for as long as the Test button remains pressed (with an automatic timeout of twelve seconds). When the test is completed the control panel returns to its former state. 12 Kilsen KFP-CF Series Operation Manual

17 Advanced operation Advanced operation includes those tasks that can be performed when the control panel is in access level 2. This access level is password-protected and is reserved for authorized users who have been trained to operate the control panel. The default access level 2 password is Those tasks included in the topic Basic operation on page 11 are also available at access level 2. Resetting the control panel To reset the control panel and clear all current system events, press the Reset button. System events that have not been resolved continue to be highlighted when the reset process ends. Caution: Investigate all fire alarms and system faults before resetting the control panel. Stopping sounders or restarting stopped sounders To stop sounders, press the Sounder Start/Stop button. To restart stopped sounders, press the button again. A steady Sounder Start/Stop LED indicates that the sounders are active (sounding). A flashing Sounder Start/Stop LED indicates that a configured sounder delay is active (to cancel an active sounder delay, see Cancelling an active sounder delay on page 11). Note: Sounder functionality is defined by your system configuration settings and stopped sounders may restart automatically if another alarm event is detected. Contact your fire system installation or maintenance contractor to confirm your configuration details. Enabling or disabling a configured sounder delay To enable a configured sounder delay, press the Sounder Delay button. To disable the delay, press the button again. Note: Availability of this feature is subject to configuration and its functionality may vary for each zone. Contact your fire system installation or maintenance contractor to confirm your configuration details. Enabling or disabling a configured fire routing delay To enable a configured fire routing delay, press the Fire Routing Delay button. To disable the delay, press the button again. Note: Availability of this feature is subject to configuration and its functionality may vary for each zone. Contact your fire system installation or maintenance contractor to confirm your configuration details. Kilsen KFP-CF Series Operation Manual 13

18 Enabling or disabling a configured extended fire routing delay If configured, the extended fire routing delay is enabled or disabled at the same time as the standard fire routing delay. In NEN 2535 operating mode, the extended fire routing delay becomes the active delay when sounders are stopped (by pressing the Sounder Start/Stop button) and remain stopped when the standard fire routing delay time has elapsed. In EN 54-2 Scandinavia operating mode, the extended fire routing delay becomes the active delay when an extended fire routing delay switch is activated while the standard fire routing delay elapses. Testing a zone To test a zone, press the general Test button, and then press the corresponding Zone button. The maximum number of zones that may be tested at the same time is four. A zone in test is indicated as follows: The general Test LED is steady. The Zone Fault/Disable/Test LED is steady. When an alarm is activated in a zone in test: The general Fire Alarm LEDs and Zone alarm LED are steady or flashing, depending on the source of the alarm. Fire routing and other zone-dependent functions are not activated. Unless configured otherwise, the sounders are activated for five seconds and the Sounder Start/Stop LED is steady (see note). Unless configured otherwise, the internal buzzer sounds constantly (see note). The control panel will reset automatically after five seconds and clear alarms for the zone in test. To end the test, press the Test button, and then press the Zone button again. If there is a fire alarm in another zone not in test, the control panel responds to the alarm event as configured. Note: The internal buzzer and sounders may be configured not to sound when an alarm is activated in a zone being tested. Contact your fire system installation or maintenance contractor to confirm your configuration details. Disabling a zone or enabling a disabled zone To disable a zone, press the general Disable button, and then press the corresponding Zone button. A disabled zone is indicated as follows: The general Disable LED is steady. The zone Fault/Disable/Test LED is steady. To enable the zone, press the general Disable button, and then press the Zone button again. 14 Kilsen KFP-CF Series Operation Manual

19 WARNING: No fire alarm or faults are indicated for disabled zones. Testing sounders To test sounders, press the general Test button, and then press the Sounder Fault/Disable/Test button. Sounders can only be tested when the control panel is in standby. The test is indicated as follows: The general Test LED is steady. The Sounder Fault/Disable/Test LED is steady. The sounders emit the audible test signal (three seconds on, five seconds off) for the duration of the test, without any configured delay. To end the test, press the general Test button, and then press the Sounder Start/Stop button again. If there is a fire alarm the fire panel will exit the test immediately and respond to the alarm as configured. Disabling sounders or enabling disabled sounders To disable sounders, press the general Disable button, and then press the Sounder Fault/Disable/Test button. Sounders can only be disabled when the control panel is in standby. Disabled sounders are indicated as follows: The general Disable LED is steady. The Sounder Fault/Disable/Test LED is steady. To enable the sounders, press the general Disable button, and then press the Sounder Fault/Disable/Test button again. WARNING: Disabled sounders do not indicate a fault or operate if there is a fire alarm. Testing fire routing Caution: Always notify the fire brigade of any planned fire routing tests. To test fire routing, press the general Test button, and then press the Fire Routing Start button. The test is indicated as follows: The general Test LED is steady. The Fire Routing Fault/Disable/Test LED is steady. The Fire Routing Start LED flashes and the test signal (three seconds on/five seconds off) is activated without any configured delay for the duration of the test. To end the test, press the general Test button, and then press the Fire Routing Start button again. Kilsen KFP-CF Series Operation Manual 15

20 If there is a fire alarm the fire panel will exit the test and respond to the alarm as configured. Disabling fire routing or enabling disabled fire routing To disable fire routing, press the general Disable button, and then press the Fire Routing Start button. Disabled fire routing is indicated as follows: The general Disable LED is steady. The Fire Routing Fault/Disable/Test LED is steady. To enable fire routing, press the general Disable button, and then press the Fire Routing Start button again. WARNING: Disabled fire routing does not indicate a fault or operate if there is a fire alarm. Disabling expansion modules or enabling disabled expansion modules To disable expansion modules, press the general Disable button, and then press Enter. Disabled expansion modules are indicated as follows: The general Disable LED is steady. The Expansion I/O Fault/Disabled LED is steady. To enable the expansion modules, press the general Disable button, and then press Enter again. WARNING: Disabled expansion modules do not indicate a fault or operate if there is a fire alarm. 16 Kilsen KFP-CF Series Operation Manual

21 Maintenance Fire alarm system maintenance Perform the following maintenance tasks to ensure that your fire alarm system works correctly and complies with all required European regulations. Caution: Before performing any tests, ensure that fire routing (if configured) is disabled or that the fire brigade has been notified. Daily maintenance Check that the control panel is in standby. If it is not, investigate all system events and/or contact your installation or maintenance contractor to fix any reported faults. Weekly maintenance Activate an alarm from at least one detector or manual call point in your fire alarm system and verify that the control panel responds correctly to the alarm. If it does not, investigate all system events and/or contact your installation or maintenance contractor to fix any reported faults. Caution: Perform this test from a different detector or manual call point each time. Quarterly maintenance Contact your installation or maintenance contractor to carry out a quarterly inspection of the fire alarm system. This inspection must test at least one device per zone and verify that the control panel responds to all fault and alarm events. The control panel power supply and battery voltage should be checked. Batteries with low voltage must be replaced (for more information see Battery maintenance on page 18). Annual maintenance Contact your installation or maintenance contractor to carry out an annual inspection of the fire alarm system. This inspection must test all system devices and verify that the control panel responds to all fault and alarm events. All electrical connections must be visually inspected to make sure that they are securely fastened, that they have not been damaged, and that they are appropriately protected. Cleaning Keep the outside and inside of the control panel clean. Carry out periodic cleaning using a damp cloth for the outside. Do not use products containing solvents to clean the unit. Do not clean the inside of the cabinet with liquid products. Kilsen KFP-CF Series Operation Manual 17

22 Battery maintenance The control panel requires two 12 V, 7.2 or 12 Ah rechargeable sealed lead-acid batteries. Compatible batteries for this product are shown in Table 4 below. Batteries are installed inside the control panel cabinet and must be installed in series, using the leads and bridge provided. Polarity must be observed. Connect batteries to the BATT connector on the control panel PCB. Table 4: Compatible batteries Control panel Battery type Recommended batteries Two- and four-zone control panels 12 V, 7.2 Ah GE BS127N Fiamm FG20721/2 Yuasa NP7-12 Eight-zone control panel 12 V, 7.2 Ah or 12 V, 12 Ah GE BS127N (7.2 Ah) GE BS130N (12 Ah) Fiamm FG20721/2 (7.2 Ah) Fiamm FG21201/2 (12 Ah) Yuasa NP7-12 (7 Ah) Yuasa NP12-12 (12 Ah) Low battery indication Battery supply and battery fuse faults are indicated by a flashing Supply Fault LED. If this LED flashes, check the following: That the battery cables are in good condition That the battery cables are connected securely and correctly at the battery and at the control panel PCB That the battery voltage is greater than 19.6 V If the cables are in good condition and all connections are correct, then the batteries should be replaced immediately. Replacing batteries Batteries must be replaced periodically as recommended by the manufacturer. The useful life of the battery is approximately four years. Avoid the total discharge of the batteries. Always use the recommended replacement batteries. To replace the batteries: 1. Disconnect and remove the existing batteries from the cabinet. 2. Install and connect the replacement batteries using the bridge provided. Observe correct polarity. 3. Dispose of the batteries as required by local or regional regulations. 18 Kilsen KFP-CF Series Operation Manual

23 Product compliance European standards for fire control and indicating equipment These control panels have been designed in accordance with European EN 54-2, EN 54-4, BS , NBN S21-100, and NEN 2535 standards. In addition, all models comply with the following EN 54-2 optional requirements: Option Description 7.8 Output to fire alarm devices Output to fire alarm routing equipment [1] 7.11 Delays to outputs 7.13 Alarm counter [2] 8.4 Total loss of the power supply 10 Test condition 11 Standardised input/output interface [1] Excluding two-zone models. [2] Dutch models only. European standards for electrical safety and electromagnetic compatibility These control panels have been designed in accordance with the following European standards for electrical safety and electromagnetic compatibility: EN EN EN EN EN Kilsen KFP-CF Series Operation Manual 19

24 20 Kilsen KFP-CF Series Operation Manual

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

Control and Indicating Equipment

Control and Indicating Equipment VdS Guidelines for Fire Detection and Fire Alarm Systems VdS 2540en Control and Indicating Equipment Requirements and Test Methods VdS 2540en : 2010-12 (02) Publishing house: VdS Schadenverhütung GmbH

More information

TruVision Bullet IR Camera Pocket Guide

TruVision Bullet IR Camera Pocket Guide GE Security TruVision Bullet IR Camera Pocket Guide g 1065693A Copyright Disclaimer Trademarks and patents Intended use Copyright 2008 GE Security. All rights reserved. This document may not be copied

More information

IFS SP-PoE Splitter User Manual

IFS SP-PoE Splitter User Manual IFS SP-PoE Splitter User Manual P/N 1069176-EN REV 1.01 ISS 01JUL10 2011 UTC Fire & Security. All rights reserved. Content Overview 2 Package contents 2 Introduction 3 Product Specifications 3 Hardware

More information

KeyAdvantage System DMS Integration. Software User Manual

KeyAdvantage System DMS Integration. Software User Manual KeyAdvantage System DMS Integration Software User Manual ii Copyright Disclaimer Trademarks and patents Intended use EMC Directive Regulatory 2013 United Technologies Corporation. All rights reserved.

More information

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual CONTENTS Installation Precautions... 1 EN 54 Information... 2 Chapter 1 Product Overview... 3 1.1 Features... 3 1.2 Technical Specifications... 3 1.2.1 Operating Voltage... 3 1.2.2 Batteries... 4 1.2.3

More information

500r+ Installation and User Guide

500r+ Installation and User Guide 500r+ Installation and User Guide Compatible Equipment 502rUK-50 Watch/Pendant PA. 509rUK-50 Smoke Detector 515rUK-00 10 metre passive infra red movement detector. 525rUK-00 Remote Set/Unset (Full and

More information

Installation guide H-5500-8554-03-A. HSI hardwired system interface

Installation guide H-5500-8554-03-A. HSI hardwired system interface Installation guide H-5500-8554-03-A HSI hardwired system interface 2008-2011 Renishaw plc. All rights reserved. This document may not be copied or reproduced in whole or in part, or transferred to any

More information

Using your LED Plus keypad

Using your LED Plus keypad Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced

More information

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 1.52 & LOOP CARD 2.0 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK #Doc No. GLT.MAN-135 TABLE OF CONTENTS WHAT TO DO IF THE

More information

Product Data Sheet. User Manual. User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels

Product Data Sheet. User Manual. User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels User Manual Product Data Sheet User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

CONTENTS 4. HOW TO UNSET THE PANEL...7

CONTENTS 4. HOW TO UNSET THE PANEL...7 Pi-8 USER MANUAL CONTENTS 1. THE KEYPAD AND ITS OPERATION...3 1.1 DESCRIPTION OF THE KEYPAD LEDS... 3 1.1.1 READY LED (RED)...3 1.1.2 TAMPER LED (RED)...3 1.1.3 POWER LED (GREEN)...3 1.1.4 CIRCUIT LEDs

More information

9452/9453 Installation and User Guide

9452/9453 Installation and User Guide 9452/9453 Installation and User Guide Compatible Equipment 9425 Remote Keypad 9040 Internal Sounder 660 Speech Communicator 8440 4-Channel Minicom 496330 Issue 1 1 of 10 9452/3 Introduction The 9452 and

More information

CS848E Receiver for 868GEN2 Devices Installation Sheet

CS848E Receiver for 868GEN2 Devices Installation Sheet CS848E Receiver for 868GEN2 Devices Installation Sheet EN 1 2 1 3 4 2 3 EN: Installation Sheet Description The CS848E Receiver adds wireless capabilities to the CS line of control panels. The CS848E allows

More information

Fire Alarm Control Panel. Family. Operating Manual

Fire Alarm Control Panel. Family. Operating Manual Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...

More information

GST301. (Single Protection Zone) Operation Manual

GST301. (Single Protection Zone) Operation Manual GST301 Gas Extinguishing Control Panel (Single Protection Zone) Operation Manual 2 of 19 CONTENTS 1 OVERVIEW... 4 2 TECHNICAL DATA... 4 3 STRUCTURES... 5 3.1 FRONT SURFACE DESCRIPTION... 5 3.1.1 Indicators...

More information

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

MIC-WKT and MIC-WKT-IR

MIC-WKT and MIC-WKT-IR MIC-WKT and MIC-WKT-IR Installation Manual Bosch Security Systems EN Installation and Operation Manual MIC-WKTI and MIC-WKT-IR Installation Manual EN 2 MIC-WKT and MIC-WKT-IR Washer Pump Drive Card Kits

More information

MIC-BP4 Bi-Phase Converter Card For the MIC400 series camera

MIC-BP4 Bi-Phase Converter Card For the MIC400 series camera MIC-BP4 Bi-Phase Converter Card for the MIC400 PTZ Camera Series Bosch Security Systems EN Installation and Operation Manual BP4 Bi-phase card Installation and Operation Manual AAAEN 2 MIC-BP4 Bi-Phase

More information

CB200W Water Leak Detection Panel Application Guide

CB200W Water Leak Detection Panel Application Guide Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical

More information

aseries A13B Mini Bullet Camera User Manual

aseries A13B Mini Bullet Camera User Manual aseries A13B Mini Bullet Camera User Manual Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to the MicroView

More information

NetworX Series. NX- 4/8 Code Pad. User Manual (Australian Version)

NetworX Series. NX- 4/8 Code Pad. User Manual (Australian Version) NetworX Series NX- 4/8 Code Pad User Manual (Australian Version) Table Of Contents Code Pad Diagram... Inside Front Glossary of Terms...2 Understanding the Code Pad lights...3 Code Pad Tones...4 Fully

More information

Diamond II v2.3 Service Pack 4 Installation Manual

Diamond II v2.3 Service Pack 4 Installation Manual Diamond II v2.3 Service Pack 4 Installation Manual P/N 460987001B ISS 26APR11 Copyright Disclaimer Trademarks and patents Intended use Software license agreement FCC compliance Certification and compliance

More information

FIREDEX 2200. Conventional Fire Panels

FIREDEX 2200. Conventional Fire Panels 68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class

More information

SECURIT 800L+ CONTROL PANEL

SECURIT 800L+ CONTROL PANEL USER MANUAL SECURIT 800L+ CONTROL PANEL COMPANY PROFILE IntelliSense have been successfully making security products for over 20 years and lead the security industry throughout the world with many innovative

More information

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual. i800 AC Current Clamp Instruction Sheet Introduction The i800 AC Current Clamp, the Clamp, has been designed for use with multimeters, recorders, power analyzers, safety testers, etc., for accurate non-intrusive

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

ACTIVE 5 ENGINEERING MANUAL

ACTIVE 5 ENGINEERING MANUAL ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features

More information

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.:

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.: Documento: M-010.1-MGAS-ENG Edizione: 01/1997 Rev.: A.1 a Division of Pittway Corporation FRONT PANEL & VISUAL INDICATIONS GENERAL TROUBLE GENERAL PROGRAMMING IN PROGRESS ENABLE/ALARM/TROUBLE (ZONE 1 ALARM

More information

How To Set A Timer On A Gg System

How To Set A Timer On A Gg System ZONE ZONE 2 ZONE ZONE ZONE 5 ZONE 6 ZONE 7 ZONE Power PA XR2/ XR2+ Intruder alarm system Operating Instructions ZONE ZONE 2 ZONE ZONE ZONE 5 ZONE 6 ZONE 7 ZONE 0 2 5 6 7 9 Omit Prog Remote LED keypad 0

More information

ICP-CP500. User's Guide ICP-CP500 Codepads

ICP-CP500. User's Guide ICP-CP500 Codepads ICP-CP500 EN User's Guide ICP-CP500 Codepads ICP-CP500 User's Guide 1.0 ICP-CP500 Series Codepads Overview EN 2 1.0 ICP-CP500 Series Codepads Overview The codepad is the communications interface between

More information

AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810

AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810 AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810 This Manual and the information contained therein is the property of AMI Marine (UK) Ltd. It must not be reproduced

More information

User s manual FLIR VP50/VP52 Non-contact AC voltage detector

User s manual FLIR VP50/VP52 Non-contact AC voltage detector User s manual FLIR VP50/VP52 Non-contact AC voltage detector User s manual FLIR VP50/VP52 #T559851; r. AD/ 9134/9134; en-us Table of contents 1 Disclaimers... 1 1.1 Copyright... 1 1.2 Quality assurance...

More information

USER GUIDE SERIES 4250 AUDIO ALARM CONFIRMATION SYSTEM CONTROL UNIT

USER GUIDE SERIES 4250 AUDIO ALARM CONFIRMATION SYSTEM CONTROL UNIT USER GUIDE SERIES 4250 AUDIO ALARM CONFIRMATION SYSTEM CONTROL UNIT CONTENTS Page INTRODUCTION... 2 Security conditions... 3 Full Set (Fully armed)... 3 Part Set (Partially armed)... 3 Unset (Disarmed)...

More information

9448 Installation and User Guide

9448 Installation and User Guide 9448 Installation and User Guide Compatible Equipment 9040 Internal Sounder 660 Speech communicator 496327 Issue 1 1 of 6 9448 INTRODUCTION The 9448 is a 3 zone control panel with separate Entry/Exit and

More information

Interactive Fire Alarm System. User Guide. Loop viewer tool, LoopViewer. Protecting life, environment and property... P-ASAFE-LV/FE, Rev.

Interactive Fire Alarm System. User Guide. Loop viewer tool, LoopViewer. Protecting life, environment and property... P-ASAFE-LV/FE, Rev. Interactive Fire Alarm System User Guide Loop viewer tool, LoopViewer Protecting life, environment and property... P-ASAFE-LV/FE, Rev. A, 033105 COPYRIGHT This publication, or parts thereof, may not be

More information

616, 626, 636 & 646 Keypads

616, 626, 636 & 646 Keypads 616, 626, 636 & 646 Keypads User s Manual TABLE OF CONTENTS 1.0 BASIC OPERATION...2 2.0 ACCESS CODES...4 3.0 ARMING & DISARMING...6 4.0 PANIC ZONES...13 5.0 KEY ACCESS PROGRAMMING.14 6.0 ADDITIONAL FEATURES...15

More information

User s Information Guide R1A

User s Information Guide R1A HSC505-R Home Security Controller - User Manual Release R1a Pi HSC505 and Pi HSC505R Home Security Controller User s Information Guide R1A Page 1 QD Dynamics (Pty) Ltd reserves the right to make changes

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

PC Tab Security System INSTRUCTION MANUAL

PC Tab Security System INSTRUCTION MANUAL PC Tab Security System INSTRUCTION MANUAL This manual is intended as a Quick Start manual covering the basic functions that have been enabled on the alarm panel. The alarm panel is capable of extensive

More information

XR1. Intruder alarm system Operating Instructions. Unset system indications. Set System indication

XR1. Intruder alarm system Operating Instructions. Unset system indications. Set System indication h m mi R s t P o S t A XR EP 9 XR G panel with built-in keypad 2 5 6 7 Power A tack 0 2 5 6 7 9 Intruder alarm system Operating Instructions These operating instructions cover the following intruder system:

More information

User Guide. RX-406 LED Keypad For CAPTAIN-I Ver.5.5 & up

User Guide. RX-406 LED Keypad For CAPTAIN-I Ver.5.5 & up RX-406 LED Keypad For CAPTAIN-I Ver.5.5 & up User Guide PIMA Electronic Systems Ltd. 5 Hatzoref Street, Holon 58856, Israel +972-3-6506444 +972-3-5500442 support@pima-alarms.com http://www.pima-alarms.com

More information

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18

IDS. Users Guide to Keypad Functions S E C U R I T Y MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18 INHEP DIGITAL IDS S E C U R I T Y Users Guide to Keypad Functions MANUAL NO. 700-171-01B ISSUED AUG 2002 VERSION 1.18 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Away Arm Stay

More information

MONITOR ISM / AFx Multi-Tenant Security System User Guide V1.3

MONITOR ISM / AFx Multi-Tenant Security System User Guide V1.3 MONITOR ISM / AFx Multi-Tenant Security System User Guide V.3 Multi-Tenant Security System User Guide Welcome New Users! There are two types of suite security keypads. Follow the instructions in the proceeding

More information

Advisor Master Programming Guide

Advisor Master Programming Guide Advisor Master Programming Guide P/N 000000 REV 00.04 ISS 15SEP10 Copyright Trademarks and patents Manufacturer 2010 UTC Fire & Security. All rights reserved. The Advisor Master name and logo are trademarks

More information

Users Guide to Keypad Functions

Users Guide to Keypad Functions Users Guide to Keypad Functions MANUAL NO. 700-175-01J ISSUED JAN 2002 VERSION 1.41 Summary of Operation A rm/ disarm [#] + [USER CODE] Quick Quick Quick Panic Fire Medical Away Arm Stay Arm Stay Arm &

More information

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM Page 0 Table of Contents Introduction 1 System Basics.. 1 Burglary Protection.. 1 Fire Protection.. 1 Security Codes. 1 Zones and Partitions

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

Model 940 Proximity Reader. Installation Manual

Model 940 Proximity Reader. Installation Manual Model 940 Proximity Reader Installation Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2008, GE Security Inc. All rights reserved. This document may not be copied

More information

Installation Manual Premier Elite ComIP

Installation Manual Premier Elite ComIP Installation Manual Premier Elite ComIP INS273-5 Overview Introduction The ComIP module allows the Premier & Premier Elite control panels to be connected to either a Local Area Network (LAN) or Wide Area

More information

Personal VoIP Gateway SKG-300 User Manual

Personal VoIP Gateway SKG-300 User Manual Personal VoIP Gateway SKG-300 User Manual 1 Copyright Copyright (C) 2005 PLANET Technology Corp. All rights reserved. The products and programs described in this User s Manual are licensed products of

More information

Installation Handbook. Interactive Fire Alarm System Release 3. Repeater Panel BU-320 / Information Panel BV-320

Installation Handbook. Interactive Fire Alarm System Release 3. Repeater Panel BU-320 / Information Panel BV-320 Interactive Fire Alarm System Release 3 Installation Handbook Repeater Panel BU-320 / Information Panel BV-320 Protecting life, environment and property... P-ASAFE/RI/DE Rev. A, 010531 COPYRIGHT This publication,

More information

2 4PI175 issue 1_6/01. How to unset system in alarm. Programs 1, 2 and 3. Access codes. How to operate Personal Attack

2 4PI175 issue 1_6/01. How to unset system in alarm. Programs 1, 2 and 3. Access codes. How to operate Personal Attack Access codes Contents Unset system indications - - - - - - - - - - - System indication - - - - - - - - - - - - Access codes - - - - - - - - - - - - - - - - How to operate Personal - - - - - - How to unset

More information

Facility Commander 2.2 with VisioWave Setup Guide

Facility Commander 2.2 with VisioWave Setup Guide GE Security Facility Commander 2.2 with VisioWave Setup Guide P/N 460702001B 19APR09 Copyright Copyright 2009 GE Security, Inc. All rights reserved. This document may not be copied in whole or in part

More information

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~ ID50 SYSTEM The Fire Alarm System can be activated in the following ways :~ 1. By breaking the glass in a Manual Alarm Call Point 2. By a rise in temperature activating an Automatic Heat Detector 3. By

More information

SCORPION. micron security products

SCORPION. micron security products SCORPION 4120 6020 & 8020 USER INSTRUCTIONS Thank you for purchasing a Quality Micron Security Alarm Controller. Micron product is manufactured to exacting quality standards. We understand the importance

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

Operator's Handbook Autroprime Interactive Fire Detection System

Operator's Handbook Autroprime Interactive Fire Detection System Operator's Handbook Autroprime Interactive Fire Detection System 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28 COPYRIGHT This publication, or parts thereof, may not be reproduced in any form, by any method,

More information

OCTOPLUS WARNING AND MEASUREMENT CONTROL UNIT FOR TOXIC AND FLAMMABLE GASES

OCTOPLUS WARNING AND MEASUREMENT CONTROL UNIT FOR TOXIC AND FLAMMABLE GASES OCTOPLUS WARNING AND MEASUREMENT CONTROL UNIT FOR TOXIC AND FLAMMABLE GASES USER'S MANUAL Copyright 2013 by Dalemans s.a. Article IMP00000062 Revision V2R0 of 25/11/2013 Any reproduction, whether partial

More information

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel ABC DEF GHI JKL MNO PQR STU YZ WXY FA-300 Series LCD Fire Alarm Control Panel Advanced Life Safety Solutions System Normal 10:36AM WED 2003-10-01 SYSTEM RESET A.C. ON ALARM SUPV TRBL CPU FAIL SIGNAL SILENCE

More information

astec Integrated Alarm System USER GUIDE

astec Integrated Alarm System USER GUIDE astec Integrated Alarm System USER GUIDE 020008599 CONTENTS Full Set, Part Set and Disarm 3 Instant Full Set 3 Part Set with exit time 4 Bell Test 4 Bypassing zones 4 Switch Lights on/off 4 Bypass (24

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

EST io64 and io500 Technical Reference Manual

EST io64 and io500 Technical Reference Manual GE Security EST Fire & Life Safety EST io64 and io500 Technical Reference Manual P/N 3101112 REV 2.0 ISS 30JUL08 Copyright Copyright 2008 GE Security, Inc. All rights reserved. This document may not be

More information

INSTRUCTION MANUAL PC255O

INSTRUCTION MANUAL PC255O INSTRUCTION MANUAL PC255O Canadian Department of Communications Notice NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment

More information

VEGA Analogue Addressable Control Panels

VEGA Analogue Addressable Control Panels Analogue Addressable Control Panels Representing the future of fire alarm control technology, Vega's modular concept enables the tailoring of system design for the smallest to the largest system. Designed

More information

Nokia Bluetooth Headset BH-110 User Guide

Nokia Bluetooth Headset BH-110 User Guide Nokia Bluetooth Headset BH-110 User Guide Issue 1.0 2 Introduction About your headset With the Nokia Bluetooth BH-110 headset, you can handle calls hands-free, even when you are using two phones at the

More information

HILLS Series LED Code Pad User Manual

HILLS Series LED Code Pad User Manual HILLS Series LED Code Pad User Manual Not all features may be available on your system Check with your installer to find out which features are programmed Page 2 TABLE OF CONTENTS Code Pad Diagrams...2

More information

SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES

SECURITY SYSTEM NOTES SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES SECURITY SYSTEM NOTES Installing/Service Company For Service Call SPECIAL CODES "Chime" Digit 1 "Partial Arm" Digit 2 "Quick Arm" Digit 3 ENTRY / EXIT DELAY TIMES Exit Delay Time Entry Delay Time Secondary

More information

Accenta/Optima. User Guide. Servicing Organisation (Installer) name: Telephone Number: Date of Installation: Account Number: Honeywell Security

Accenta/Optima. User Guide. Servicing Organisation (Installer) name: Telephone Number: Date of Installation: Account Number: Honeywell Security Accenta/Optima User Guide ZONE 1 2 3 4 5 6 7 8 9 Chime Omit Prog PA 0 1 2 3 4 5 6 7 8 9 CHIME OMIT RESET PROG SET Accenta + TA PA DAY POWER PA! " # $ % & 0 1 2 3 5 6 7 8 Chime Omit Reset Prog 4 9 Set PA

More information

HILLS Series LED Code Pad User Manual

HILLS Series LED Code Pad User Manual HILLS Series LED Code Pad User Manual Not all features may be available on your system Check with your installer to find out which features are programmed Page 2 TABLE OF CONTENTS Code Pad Diagrams...2

More information

SYSTEM 7000 IRIS+ USER MANUAL

SYSTEM 7000 IRIS+ USER MANUAL SYSTEM 7000 IRIS+ USER MANUAL Table of Contents Section Page No 1. INTRODUCTION... 3 2. THE DISPLAY... 3 3. TRANSMITTERS... 6 4. MESSAGE PAGER SYSTEM... 7 2 1. Introduction 1.1 The IRIS+ is a radio based

More information

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual. INTRODUCTION The information provided herein covers the range of products known as the 'Sensor 901' series. The range of equipment is designed to meet the requirements of BS 5839 parts 1 & 4 1988. The

More information

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1

CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL. user manual & log book. Approved Document No. DFU7001020 Rev 1 CFP 2/4/8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL user manual & log book Approved Document No. DFU7001020 Rev 1 CONTENTS Safety...3 Important information regarding the safe use of this fire alarm panel

More information

GE Security. ZP3 Fire Control Panel User Guide

GE Security. ZP3 Fire Control Panel User Guide GE Security ZP3 Fire Control Panel User Guide Copyright Disclaimer Trademarks and patents Intended use Regulatory Copyright 2008, GE Security, Inc. This document may not be copied in whole or in part or

More information

Installation and Operation Manual

Installation and Operation Manual GST102 GST104 Conventional Alarm Control Panel nstallation and peration Manual (ssue3.03, November 2005) nstallation and peration Manual The ntelligent Solution CNTENTS 1 General... 1 2 Technical Specifications...

More information

HDTV Anywhere USER MANUAL 3. 20672/ 20140710 HDTV Anywhere ALL RIGHTS RESERVED MARMITEK

HDTV Anywhere USER MANUAL 3. 20672/ 20140710 HDTV Anywhere ALL RIGHTS RESERVED MARMITEK HDTV Anywhere USER MANUAL 3 20672/ 20140710 HDTV Anywhere ALL RIGHTS RESERVED MARMITEK 2 MARMITEK SAFETY WARNINGS To prevent short circuits, this product should only be used inside and only in dry spaces.

More information

SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS

SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS SECURITY SYSTEM NOTES Installing/Service Company For Service Call Area 1 Area 2 Area 3 AREA LISTINGS SPECIAL CODES "Quick Arm" Digit "Partial Arm" Digit "Chime" Digit ENTRY / EXIT DELAY TIMES Exit Delay

More information

HARDWIRED CONTROL PANELS

HARDWIRED CONTROL PANELS USER GUIDE 9651 HARDWIRED CONTROL PANELS Contents 1. Introduction...3 The Alarm System...3 The Keypad...3 About This Guide...5 2. Everyday Operation...6 How Do I Know if the System is Working?...6 Setting

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-8 Control/Communicator Installation Manual Page General Description... 2 Ordering Information... 2 Option Definitions... 2 Programming the LED Code Pads... 4 Programming the NX-8... 8 Types

More information

TMS TANK MANAGEMENT SYSTEM

TMS TANK MANAGEMENT SYSTEM TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS

More information

CAPTAIN 6. USER GUIDE System ver. 6.0. 6 Zones Intruder Alarm System. PIMA Electronic Systems Ltd. www.pima-alarms.com

CAPTAIN 6. USER GUIDE System ver. 6.0. 6 Zones Intruder Alarm System. PIMA Electronic Systems Ltd. www.pima-alarms.com CAPTAIN 6 6 Zones Intruder Alarm System USER GUIDE System ver. 6.0 PIMA Electronic Systems Ltd. www.pima-alarms.com P/N 4410049, G2 XX en, Jan. 2010 2 CAPTAIN 6 User Guide SAFETY INSTRUCTIONS Your CAPTAIN-i

More information

510 / 511 Cardiorespiratory Monitor Preventative Maintenance Test Procedure

510 / 511 Cardiorespiratory Monitor Preventative Maintenance Test Procedure CAS MEDICAL SYSTEMS, INC. 510 / 511 Cardiorespiratory Monitor Preventative Maintenance Test Procedure using the 2301Multi-Function Tester 44 East Industrial Road Branford, CT 06405 USA www.techsrv@casmed.com

More information

CA60 Plus Software Version 3.1 User Manual May 2000

CA60 Plus Software Version 3.1 User Manual May 2000 TeleT eletek ek CA60 Plus Software Version 3.1 User Manual May 2000 CONTENTS 1. CA60Plus Keypad... 3 1.1. LED display... 3 1.2. Keys... 4 1.3. Combinations of Keys... 4 1.4. Audible Indication... 4 2.

More information

USER MANUAL OPERATION AND USE OF CAR WITH. Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM

USER MANUAL OPERATION AND USE OF CAR WITH. Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM USER MANUAL OPERATION AND USE OF CAR WITH Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM Page 2 z 7 Table of contents 1. STARTING THE ENGINE... 3 2. CONTROL PANEL... 3 2.1 Indication of the current level

More information

SmartLine. Conventional Fire Detection Control Panel. Extinguishant system Control Panel. User's Manual. GameOver

SmartLine. Conventional Fire Detection Control Panel. Extinguishant system Control Panel. User's Manual. GameOver SmartLine Conventional Fire Detection Control Panel Extinguishant system Control Panel User's Manual GameOver Chapter 1 Description of the Control panel 1.1 Manufacturer's name and address INIM Electronics

More information

Matrix 424/832/832+ ICON & LCD User Manual. Software Version 5 RINS915-2. EN50131-1 Security Grade 2 Environmental Class 2

Matrix 424/832/832+ ICON & LCD User Manual. Software Version 5 RINS915-2. EN50131-1 Security Grade 2 Environmental Class 2 Matrix 424/832/832+ ICON & LCD User Manual Software Version 5 RINS915-2 EN50131-1 Security Grade 2 Environmental Class 2 CONTENTS CHAPTER 1: INTRODUCTION... 1 CHAPTER 2: REPLACING THE BATTERIES... 2 CHAPTER

More information

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT-201-7-1 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3 ABOUT THE INFINITY FIRE ALARM CONTROL PANEL

More information

SPECIAL CODES AUXILIARY CODES SYSTEM NOTES

SPECIAL CODES AUXILIARY CODES SYSTEM NOTES Installing/Service Company Monitoring Center SPECIAL CODES Master Code Duress Code AUXILIARY CODES "Quick Arm" " Chime" 08 02 09 03 10 04 11 05 12 06 13 07 14 SYSTEM NOTES Exit Delay Time Entry Delay Time

More information

CS450. User Manual 143163999-2

CS450. User Manual 143163999-2 CS450 User Manual 143163999-2 COPYRIGHT SLC BV 1997. All rights reserved. No part of this publication may be reproduced, transmitted, stored in a retrieval system, or transmitted in any form, or by any

More information

FTP-1000 Touchpad/Display. Installation Manual. Stay. Away. Disarm. Quick Exit

FTP-1000 Touchpad/Display. Installation Manual. Stay. Away. Disarm. Quick Exit FTP-1000 Touchpad/Display Installation Manual A B 1 2 3 4 5 6 7 8 9 0 * # Stay Away Disarm Quick Exit C D Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security

More information

How To Use A Power Supply Unit (Upu)

How To Use A Power Supply Unit (Upu) BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.

More information

Kvaser Mini PCI Express User s Guide

Kvaser Mini PCI Express User s Guide Kvaser Mini PCI Express User s Guide Copyright 2013-2014 Kvaser AB, Mölndal, Sweden http://www.kvaser.com Printed Sunday 28 th September, 2014 We believe that the information contained herein was accurate

More information

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide PIMA Electronic Systems Ltd. 5 Hatzoref Street, Holon 58856, Israel +972-3-5587722 +972-3-5500442 support@pima-alarms.com http://www.pima-alarms.com

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

EPGM1 HARDWIRED ZONE & PGM OUTPUT EXPANSION MODULE

EPGM1 HARDWIRED ZONE & PGM OUTPUT EXPANSION MODULE EPGM1 HARDWIRED ZONE & PGM OUTPUT EXPANSION MODULE User manual v1.5 Compatible with: ESIM264 v7.09.02 and up. ESIM364 all versions. Main features: Hardwired zone expansion adding 16 additional zones per

More information

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS + Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,

More information

Communication bridge Xcom-MS User Manual

Communication bridge Xcom-MS User Manual Communication bridge User Manual Copyright 2011 Studer Innotec SA - V1.0.1 Communication bridge : User Manual V1.0.1 Copyright 2011 Studer Innotec SA About the software This document applies to the software

More information

D24 ALARM CONTROL PANEL USER S MANUAL REVISION 1.1 A$12.00 INC GST

D24 ALARM CONTROL PANEL USER S MANUAL REVISION 1.1 A$12.00 INC GST D24 ALARM CONTROL PANEL USER S MANUAL REVISION 1.1 A$12.00 INC GST Ness Security Products Pty Ltd Quality Endorsed Company ISO9001 LIC.No. QEC2074 NSW Head Office only WWW.NESS.COM.AU Australia s largest

More information

Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6. User s manual

Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6. User s manual Uninterruptible Power Supply ERA LED 1.5 ERA LED 2.0 ERA LED 2.6 User s manual Index Safety Warnings... 2 1 Introduction... 3 2 General Characteristics... 4 3 Receipt and site selection... 4 4 EXTERNAL

More information