1 Fire Engineering Seminar BS 9991:2011 Fire Safety in the Design, management and use of residential buildings Martin Davidson Jeremy Gardner Associates
2 Traditionally prescriptive Reliance on Escape routes stairs, common corridors Containment by passive means Smoke detection Smoke venting in common areas.
3 BS 5588 Part 1 Maisonettes Alternative means of escape required where a floor > 4.5m above ground Only really worked for three storey buildings Problematic with taller buildings Common balconies for alternative means of escape Security and privacy issues Dual aspect units Can t get an alternative means of escape as there is no corridor on every floor.
4 BS 5588 Part 1 Smoke venting of common corridors Guidance very limited More than 1 stair 1m 2 Openable Vent Single Stair 1.5m 2 AOV. How many corridors connect directly with external? Vertical smoke shafts 1.5m 2 Open or closed at bottom? Alternative BRE Guidance Contentious
5
6 Travel distances BS 5588 Part 1 9m within apartments with kitchen away from exit Internal protected entrance hall with 9m travel distances Distances then unlimited within accommodation 7.5m single direction of travel in common corridor 30m where there is more than one stair
7 BS 5588 Part 1 Protected entrance halls Makes apartment entrance very dark Inefficient use of space Self closing fire doors Hazard to young children Disconnected by many No maintenance Effective?
8 Fires by Location
9 Fire Deaths by Location
10 BS 9991:2011 Published 31 December 2011 Supersedes BS 5588 Part 1 with immediate effect As with BS 9999, situation in Ireland as yet unclear TGD B currently being revised Deals with all parts of Building Regulations from B1 to B5. Similar in layout to TGD B More flexible design possible.
11 BS 9991:2011 Scope includes Houses Apartments and duplexes Sheltered housing Residential blocks (e.g. Student housing) Excludes Hotels, hospitals, nursing homes, hostels, prisons or houses of multiple occupancy.
12 Dwellings No changes for single or two storey houses 3 Storey Houses Alternative means of escape from top storey; or Protected stair; or Sprinklers throughout with fire separation of the ground from the upper floors Taller houses Floors >7.5m above ground should have an alternative means of escape or A protected stairway serving all floors plus sprinklers.
13 Apartment Blocks Residential buildings > 30m in height should be sprinklered Mechanical smoke ventilation for common corridors introduced Sprinklers and/or mechanical smoke ventilation recognised as alternative solution for extended travel distances in common corridors.
14 Balcony or Deck Approach Balcony should achieve 30 minutes fire resistance and be imperforate Should be designed to encourage smoke flow out and up. If more than 2m wide then downstands requried If there are voids in the balcony and there is a single direction of travel, unless the escape route is more than 1.8m away from the elevation a smoke analysis required.
15 Balcony Escape with Voids Flat Flat Flat >1.8m Single direction
16 Balcony with Single Direction of Escape Face of building should provide at least 30 mins (excluding windows) FD30 Doors Window openings should not extend below 1.1m above balcony Balustrade should be imperforate Walls, balcony and balustrade surfaces should be Class 0
17 Common Corridor to Flats or Maisonettes Travel distances have not changed from BS 5588 Part 1 7.5m in a single direction and 30m where there is an alternative Smoke ventilation provisions have changed More flexibility on extended travel distances depending on measures provided.
18 Smoke Control Where travel distances comply, primary purpose of smoke control is to protect the stair basis of stay put evacuation strategy Where travel distances are extended, primary objective is to protect both the stair and the corridor Natural or mechanical smoke ventilation Mechanical can be extract or pressurisation
19 BS 5588 Part 1 Ventilated
20 BS 9991 Smoke Control Where escape from flats is only via a corridor 7.4(a) the travel distance between the exit doors from the dwellings and a smoke-free area should be limited, and the amount of smoke and other combustion products in the internal corridor or lobby kept to a minimum by providing either cross corridor fire doors and ventilation, or a mechanical smoke ventilation system
21
22
23 Small Buildings with Single Stair Smoke venting of lobby not required where travel distances < 4.5m Stair can continue down to basement car park provided basement is ventilated and there is a ventilated lobby. 1m 2 OV at each level in stair or a single remotely operated vent at the top.
24 Section 26 Smoke Vent Single Stair > 11m Requirements 1.5m 2 AOV on the external elevation directly adjacent to the stair as high as possible and a 1m 2 AOV at the top of the stair; or 1.5m 2 vertical shaft directly adjacent to the stair as high as possible and a 1m 2 AOV at the top of the stair (fire fighting cores limited to 30m) ; or Mechanical extraction directly adjacent to the stair as high as possible and a 1m 2 AOV at the top of the stair
25 Mechanical Smoke Ventilation Usually incorporates a fan and a vertical shaft Where travel distance comply inlet via vent at top of stair Extended travel distances require inlet air provisions at each level Should shown better or equivalent conditions to the natural system using CFD analysis
26 Internal Layout of Flats Previous guidance retained Travel distances < 9m with no escape towards cooking areas Protected entrance hall with 9m travel distance Open plan flats permitted Sprinklers Size of flat < 16m x 12m Open plan flat should be single storey.
27 Internal Layout of Flats Open plan flats Ceiling height minimum 2.25m Where flat > 10m x 8m kitchen should be enclosed Where flat < 10m x 8m, kitchen can be open but located away from exit Open plan not permitted in sheltered housing.
28 Maisonettes Maisonettes < 4.5m above ground are the same as dwellings Maisonettes > 4.5m above ground have four options An alternative exit from any habitable room not on the entrance level A protected stair serving all rooms on upper level and 1 alternative exit A protected stair and LD1 detection if no floor >7.5m above or below entrance level A protected stair and sprinklers.
29 Variations Concept consistent with BS 9999 Where sprinklers fitted in flats travel distances can be increased In one direction from 7.5m to 15m More than one direction from 30m to 60m Extended travel distances can be addressed using mechanical ventilation.
30
31 Fire Fighting Facilities Buildings not fitted with fire mains Houses should have access to all areas to within 45m from appliance along route suitable for hose Flats should have vehicle access for a fire appliance not more than 45m from all points within each dwelling If sprinklers and no floor greater than 4.5m then distance can be increased to 90m in houses and 75m in flats provided fire brigade attendance time is less than 10m
32 Fire Fighting Facilities Fire fighting shaft required in buildings with floor greater than 18m (TGD B 20m) Sufficient number of fire fighting shafts should provided to meet hose coverage distances (60m) and at least two fire fighting shafts in a building with an area of more than 900m 2.
33 Fire Resistance Periods Error Why else would you bother?
34 Sprinklers Can be to BS 9251 if using table 3 ADB advises that limitations on the use of BS 9251 for buildings greater than 20m can be ignored If using table 4 then BS EN sprinkler system Tanks, pumps etc Any reductions in cost due to reduced fire resistance maybe cancelled out due to higher sprinkler system requirements.
35 Other Considerations Self-closing devices not required on fire doors within dwellings, flats or maisonettes except for door to communal areas Single stair building >11m stair should not continue down to basement unless it is sprinklered.
36 Other Considerations Lobby should have a falling dry main and be ventilated where it s a basement car park lobby vent should be 1m 2 AOV Currently current practice in Ireland is to provide double lobby protection in basement with one lobby ventilated with 0.4m 2 permanently open vent
37 London Edinburgh Dublin Belfast Galway
SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS
Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses
More informationFire Safety In High Rise Building
Fire Safety In High Rise Building CLASSIFICATION OF BUILDINGS AS PER NATIONAL BUILDING CODE 1. GROUPING. Group A - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group B Group C - Educational
More informationIntroduction. CE marked construction products
Introduction This Technical Booklet has been prepared by the Department of Finance and Personnel and provides for certain methods and standards of building which, if followed, will satisfy the requirements
More informationNorthern Ireland Housing Executive: HMO Fire Safety Guide
Northern Ireland Housing Executive: HMO Fire Safety Guide Contents Equality Statement 5 Houses in Multiple Occupation (HMOs) means of escape in case of fire and other fire precautions 6 1.0 Introduction
More information- 5 - Table1. Maximum Compartment Volumes
- 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,
More informationFire precautions in dwellings. Private sector housing Providing homes building communities
Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared
More informationHOUSES IN MULTIPLE OCCUPATION STANDARDS. Housing Executive
HOUSES IN MULTIPLE OCCUPATION STANDARDS Housing Executive Contents 1.0 Introduction 3 2.0 Standards 4 3.0 Method of Measurement 6 4.0 Overcrowding 7 5.0 Over Occupation 8 6.0 Facilities for Storage, Preparation
More informationRESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
More informationGuidance on loft conversions in two-storey houses
Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for
More informationRESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
More informationErrata has been identified as follows:
2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page
More informationContents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4
Contents 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 2. Scope and Application 2.1 Scope of the Guide 5 2.2 Premises to which the
More informationRESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK PERRONET HOUSE PRINCESS STREET LONDON SE1 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
More informationFire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
More informationIFE Level 4 Certificate in Fire Science and Fire Safety (HL)
IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and
More informationI.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
More informationWe hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.
September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify
More informationFIRE SAFETY RISK ASSESSMENT
FIRE SAFETY RISK ASSESSMENT For small single occupancy premises Premises Hertco Ltd ACME House, Old London Road, Hertford SG17 7LD Fire Safety Risk Assessment for Small Premises Introduction Regulatory
More informationDesign Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
More informationI.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
More informationGENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)
GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) Chapter 1 : Definitions clause 1.2.10 : circulation space OLD CLAUSE A space mainly used as means of access between a room or protected shaft
More informationCh. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM
More informationBuilding Control Guidance Note
Issued 01/10/10 Rev Page 1 A new updated version of Approved Document B comes into force from the 6 th April 2007. This revised guidance is split into two separate documents:- Volume 1 Dwelling Houses
More informationHOUSING STANDARDS POLICY TRANSITION STATEMENT IMPLEMENTATION: OCTOBER 2015. May 2015
HOUSING STANDARDS POLICY TRANSITION STATEMENT IMPLEMENTATION: OCTOBER 2015 May 2015 MAYOR OF LONDON Housing Standards: Transition Policy Statement. On 25 March 2015 through a written ministerial statement,
More informationON MOST schemes, the architectural design of. Flexible strategy. Case study. The Forum
Flexible strategy ON MOST schemes, the architectural design of a building is influenced by fire engineering strategy. This could be in the form of visual, physical elements such as fire doors, fire curtains,
More informationFire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
More informationMINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
More informationBUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
More informationUsing Sprinkler Systems in Buildings and Structures Compliance with current fire safety guidance
Technical Guidance Note No 2 Issue No 1: October 2011 ISBN 0-9552628-8-7 Using Sprinkler Systems in Buildings and Structures Compliance with current fire safety guidance In this Technical Guidance Note
More informationBuilding Control Guidance Note
Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you
More informationOverview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
More informationWhat you need to know about. Smoke alarms for residential buildings
What you need to know about Smoke alarms for residential buildings Are s compulsory? Smoke alarms are compulsory and must be installed in residential buildings on or near the ceiling of every storey. What
More informationChapter 2 MEANS OF ESCAPE
Chapter 2 MEANS OF ESCAPE 2.1 General 2.1.1 The provisions of this chapter of the Code shall serve to express the intentions for determining the design, construction, protection, location, arrangement
More informationFIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
More informationFire Strategy. Oak Park Care Home and Extra Care Block. 21 July 2015
21 July 2015 Revision History Version Date Author Comments 1 21/07/2015 Anthony Robson First Issue Contents EXECUTIVE SUMMARY 1 1 INTRODUCTION 1 2 PROJECT INFORMATION 2 3 MEANS OF ESCAPE 3 Document Reference
More informationREVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS
, Volume 3, Number 1, p.25-51, 2001 REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS W.Y. Hung and W.K. Chow Department of Building
More informationJames R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc.
AT THE STRATOSPHERE TOWER, LAS VEGAS NEVADA By: James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc. INTRODUCTION This paper discusses the performance based approach to fire protection
More informationAppraisal of Passive and Active Fire Protection Systems in Student s Accommodation
MATEC Web of Conferences 10, 06002 (2014) DOI: 10.1051/ matecconf/ 20141006002 C Owned by the authors, published by EDP Sciences, 2014 Appraisal of Passive and Active Fire Protection Systems in Student
More informationSchedule B to By-law 33-2009 Part A Fees Payable for Permits
Floor Area Calculation Floor area shall: Part A Fees Payable for Permits (Effective January 1, 2015) a) be calculated by measuring to the outer face of exterior walls and to the centre of party walls or
More informationCHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
More information3.In making the following determination, the Secretary of State has not considered whether the plans conform to any other relevant requirements.
Date: 06/09/99 Ref: 45/1/166 Note: The following letter was issued by our former department, the Department for Environment, Transport and the Regions (DETR). DETR is now Communities and Local Government
More informationSchedule B to By-law 33-2009
Amended by By-law 8-2016 Note: This consolidation is prepared for convenience only. For accurate reference the original by-laws should be reviewed. Floor Area Calculation Floor area shall: Schedule B to
More informationFURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS
Fire Safety Technical Guide FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS 1.0. Introduction 1.1. Furniture and furnishings may significantly increase fire spread in rooms and those circulation spaces,
More informationFIRE ESCAPE SIGNS Guidance on compliance
FIRE ESCAPE SIGNS Guidance on compliance Document control information Published document name: escapesigns-gn.pdf, Date issued: January 2011 Version: 2.0 Previous review dates: 2011 Next review date: Related
More informationBuilding Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
More informationA study of the nature of fire risks in tall buildings
A study of the nature of fire risks in tall buildings David Charters and Carl Sherwood BRE Global 12 th March 2013 Part of the BRE Trust Overview 1. Introduction 2. Challenges of tall buildings 3. Analysis
More informationFire Safety Risk Assessment
1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept
More informationPage 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.
Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable
More informationProposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
More informationPollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2
Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,
More informationProposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed
More informationSCHEDULE A BY-LAW B-6 CLASSES OF PERMITS AND FEES
1. CALCULATION OF PERMIT FEES SCHEDULE A BY-LAW B-6 CLASSES OF PERMITS AND FEES Permit fees shall be calculated based on the formula given below, unless otherwise specified in this schedule: Permit Fee
More informationIf you require any assistance with smoke control systems we can be contacted as follows:
This document provides guidance relating to the design, installation and commissioning of smoke ventilation systems within the common escape routes in apartment buildings. Although the prevention of smoke
More informationCITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.
More informationBUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010
Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
More informationFIRE RISK ASSESSMENT WORKED EXAMPLE
FIRE RISK ASSESSMENT WORKED EXAMPLE 1 PREMISES PARTICULARS BE-INT05 Premises Name S M Enterprises Address Small Place Medium Road Anywhere Tel no: 01234 567890 Date of Risk Assessment 1 st July 2011 Use
More informationArea of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
More informationUPP Residential Services Fire Risk Assessment
UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This
More informationBuilding Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
More informationGrasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment
Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS
More informationFire safety advice for landlords
YOU CAN PREVENT IT Fire safety advice for landlords Introduction Each year there are over 50,000 fires in dwellings in the UK. These result in around 300 hundred fatalities and several thousand serious
More informationHow To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
More informationPractice Note 2006-27
Practice Note Self-Contained smoke alarms to existing buildings This updates the previous Practice Note 2005-27 issued May 2005. Reference to the BCA in this Practice Note means Volume One and Volume Two
More informationSt. John s University
St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica
More informationFire Safety in High Rise Residential Blocks
Fire Safety in High Rise Residential Blocks What can we learn from Lakanal House? www.labc.co.uk This information paper has been prepared to focus on the lessons learned from the Lakanal House enquiry.
More informationLONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough
More informationFIRE SAFETY PRINCIPLES FOR RESIDENTIAL ACCOMMODATION
FIRE SAFETY PRINCIPLES FOR RESIDENTIAL ACCOMMODATION HOUSING REGULATION TEAM HOUSING SERVICES 25 th July 2011 Foreword This document has been produced by Leeds City Council, in consultation with the West
More informationFire Safety Requirements for Child Care Centre
Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
More informationFor use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
More informationTechnical Bulletin 005(A) Developed with Communities and Local Government
Technical Bulletin 005(A) Developed with Communities and Local Government Title: Gas cookers in internal kitchens - Ventilation requirements as applied to England, Wales, the le of Man and Guernsey Date
More informationEVACUATION & LIFE SAFETY STRATEGIES FOR SUPER HIGH RISE BUILDINGS. Sam Aloi, Grad. Dip. (Fire Safety & Risk Eng.)VUT Melb, BE (Building) VUT Melb.
EVACUATION & LIFE SAFETY STRATEGIES FOR SUPER HIGH RISE BUILDINGS By Sam Aloi, Grad. Dip. (Fire Safety & Risk Eng.)VUT Melb, BE (Building) VUT Melb. & Jason Rogers, Grad. Dip. (Fire Safety & Risk Eng.)VUT
More informationG-704-0 SPECIFICATION: GAS METER AND REGULATOR INSTALLATION REQUIREMENTS. 3 and Gas Yellow Book. REVISIONS: (See ) 1/15/14 5 Years
LAST REVIEW DATE: REVIEW CYCLE: 1/15/14 5 Years SPECIFICATION: TITLE: VOLUME: G-704-0 3 and Gas Yellow Book REVISIONS: (See ) 1) This specification is being issued for the first time. G-704-0 Gas Operations
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationLondon Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords
London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the
More informationAVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard
Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!
More informationIndiana Building Rehabilitation Standard
Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC
More informationAction required (Please tick) If you answered YES, record Action Points at STEP 4
RECORD OF FIRE SAFETY RISK ASSESSMENT Building Name & Use: Address: Postcode: Name of person(s) with fire safety duties: Name and contact details of assessor: Date of Assessment: 6 th February 2011 Laurel
More informationProperty Maintenance Check List
Property Maintenance Check List Scope These minimum conditions and responsibilities of persons for maintenance of structures, equipment and exterior property shall govern. Responsibility. Owners shall
More informationGuide to Houses in Multiple Occupation Self Contained Flats
Guide to Houses in Multiple Occupation Self Contained Flats Kitchens Bathrooms Fire Safety Room Sizes Toilets HMO self contained flat std0 Version 4 201106 INTRODUCTION GENERAL INFORMATION The Housing
More informationRochdale Building Control Guide. Approved Document F Means of ventilation
Rochdale Building Control Guide Approved Document F Means of ventilation Coming into effect 1 st October 2010 As we build homes that are more airtight it is increasingly becoming important to ensure that
More informationUCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS
Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern
More informationFor use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
More informationServices Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
More informationCompliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition
Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building
More informationWATER INDUSTRY ACT 2012. South Australian Water Heater Installation Requirements. Prepared by the Technical Regulator
WATER INDUSTRY ACT 2012 South Australian Water Heater Installation Requirements Prepared by the Technical Regulator Installation requirements for water heaters serving established Class 1A buildings, established
More informationENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III. HOUSES IN MULTIPLE OCCUPATION Space Standards
ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III HOUSES IN MULTIPLE OCCUPATION Space Standards ADOPTED HOUSING STANDARDS:CATEGORY F HOUSES Houses within this category would be of a low priority
More informationDecree of the Ministry of the Environment. on fire safety of garages
E4 THE NATIONAL BUILDING CODE OF FINLAND Fire safety of garages Guidelines 2005 Decree of the Ministry of the Environment on fire safety of garages Adopted in Helsinki, 22 March 2005 Pursuant to the Decision
More informationFire Safety Management Strategy 2015-2018
Fire Safety Management Strategy 2015-2018 Introduction This strategy is a plan and method of approach to how Medway Council Housing Services (the council) will both continue to meet our statutory obligations
More informationWhat are we discussing with you today?
What are we discussing with you today? In June we asked you what you like and don t like about your neighbourhood. We then talked to you about the types of houses you like, plus interiors and layouts.
More informationAccess to and use of buildings
The Building Regulations 2010 Access to and use of buildings APPROVED DOCUMENT M Volume 1: Dwellings M4(1) Category 1: Visitable dwellings M4(2) Category 2: Accessible and adaptable dwellings M4(3) Category
More informationBY-LAW CONCERNING THE SANITATION AND MAINTENANCE OF DWELLING UNITS
CITY OF MONTRÉAL BY-LAW 03-096 BY-LAW CONCERNING THE SANITATION AND MAINTENANCE OF DWELLING UNITS As the municipal administration seeks to ensure that all Montrealers benefit from acceptable housing conditions;
More informationImportant Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
More informationFraternity and Sorority House Fire Safety
Fraternity and Sorority House Fire Safety Buddy Dewar Director of Regional Operations National Fire Sprinkler Association 850-222-2070 How To Manage Greek Housing Fire Sprinkler Retrofit Brief Overview.
More informationFIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial
More informationCertification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
More information2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
More informationBS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
More informationExcerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
More information