JUMO Wtrans RF-Series Receiver unit T01 for wireless temperature probes
|
|
- Ashley Long
- 7 years ago
- Views:
Transcription
1 Data Sheet Page 1/7 JUMO Wtrans RF-Series Receiver unit T01 for wireless temperature probes k For temperature measurements of -30 to +260 C k Interface RS485 with Modbus protocol k Wireless reception of measured values k Low wiring cost thanks to modern RF-technology k For a maximum of 16 probes per receiver In connection with suitable Wtrans probes, the Wtrans receiver is used for the mobile and stationary measurement of temperatures. The use of radio frequency (RF) technology (ISM band MHz or 915 MHz) reduces installation costs significantly. Cables are no longer necessary and the radio-based temperature sensor technology also works in rough industrial environments. The supplied lambda/4 antenna with an impedance of 50Ω can be screwed on directly or mounted externally. If the recommended antenna wall mounting is used, the maximum open air range is 300m. The measured values are converted within the receiver and made available directly at the terminals as analog and temperature-linear current or voltage signals (0(4) to 20mA, 0 to 10V). All outputs of the receiver are electrically isolated. A connection to superordinate systems, e. g. the plant visualization software JUMO SVS3000 or the Modbusmaster-capable paperless recorder JUMO LOGOSCREEN nt, is possible via the RS485 interface in the Modbus protocol. Operation and configuration are possible via the keyboard and a two-line LCD or, more comfortable, via a setup program. Thus it is possible to configure parameters such as filter constants, offset, alarms as well as peak-reading-pointer (minimum and maximum value storage) separately for each channel. For this purpose, there is an interface at the front to connect the receiver with a PC, using a TTL/RS232 or USB/TTL converter. The receiver is designed for mounting on DIN rail 35mm x 7.5mm to EN The screw terminals for the electric connection are arranged on different levels. Type /10... Block structure Suitable Wtrans probes Reception unit Keyboard Reception frequency 868,4 MHz or 915 MHz 4 keys for operation and configuration Wtrans receiver Outputs 4x 0(4) to 20mA or 0 to 10V Display 2-line LCD for the visualisation of measured values and configuration as well as 2 LED as status indicators k Max. 16 Wtrans probes per Wtrans receiver k For mobile or stationary temperature measurements k Open-air range approx. 300m k Radio frequency MHz or 915 MHz; within the frequency band 915 MHz, ten frequencies can be configured k Different thermowell lengths k Voltage supply via lithium-battery 3.6V, 2.1Ah k Oil and acid resistant housing k Protection class IP67 Voltage supply Interfaces AC 110 to 240 V +10/-15 % 48 to 63 Hz 1x RS485 1x Setup More information see data sheet
2 Data Sheet Page 2/7 Technical data Input Number of probes Reception frequency Open-air range Measurement range limits Configuration Unit A maximum number of 16 probes can be supported per receiver MHz (Europe), 915 MHz (America, Australia, Canada and New Zealand); within the frequency band, ten frequencies can be configured max. 300m if the antenna wall mounting with 3m antenna cable is used -30 to +260 C via the keys at the unit or via setup program C ( F); can be set at the unit or with setup program Analog outputs Number 4 Analog outputs Output signal: - Current - Voltage can be set via the keys at the unit or with the setup program proportional DC current 0 to 20mA or 4 to 20mA DC voltage 0 to 10V Transmission behaviour temperature-linear, freely scalable working resistance (at current output) 500 ohms Load (at voltage output) 10k ohms Setting time during temperature change The setting time depends on the sending interval set in the probe Setting time after switch-on or reset 5s Calibration conditions AC 230V/22 C (±3K) Accuracy ±0.1% 1 (accuracy includes calibration linearization, influence of working resistance, load and voltage supply) Ripple ±0.2% 1 Galvanic isolation Galvanic isolation voltage The outputs are isolated from each other as well as from the interfaces 50V Measuring circuit monitoring of the analog outputs Measuring range undercut: - Current output 4 to 20mA - Current output 0 to 20mA - Voltage output 0 to 10V Measuring range exceedance: - Current output 4 to 20mA - Current output 0 to 20mA - Voltage output 0 to 10V Sensor short circuit or sensor and cable break and alarms: - Current output 4 to 20mA - Current output 0 to 20mA - Voltage output 0 to 10V Output behaviour declining until 3.8mA, then jump to configured signalling declining until -0.1mA, then jump to configured signalling declining until -0.1V, then jump to configured signalling rising until 20.5mA, then jump to configured signalling rising until 20.5mA, then jump to configured signalling rising until 10.25V, then jump to configured signalling positive signalling: > 21mA negative signalling: < 3.6mA positive signalling: > 21mA negative signalling: < -0.1mA positive signalling: > 10.5V negative signalling: < -0.1V The output behaviour (pos. or neg. signalling) can be configured. 1 All accuracy details in % from the measuring range end value 20mA or 10V.
3 Data Sheet Page 3/7 Electric data Voltage supply AC 110 to 240V +10/-15%, 48 to 63Hz Power consumption 9VA Electric connection Screw terminals up to 2.5mm 2 Electric safety EN , part 1 overvoltage class III, degree of pollution 2, for switching cabinet mounting to EN Electric isolation The voltage supply is electrically isolated from the outputs and the interfaces Test voltage 3700V Ambient factors Ambient temperature range -20 to +50 C (also in case of close-packed mounting) Storage temperature range -30 to +70 C Storage humidity relative humidity 85%, without condensation Temperature influence ±0.005% 1 /K; per K deviation from the reference temperature 22 C (±3K) Climatic conditions relative humidity 85%, without condensation to EN K3 Vibration resistance IEC , max. 1g at 10 to 55Hz EMC EN interference emission Class A - Immunity to interference Industrial requirement - radio frequency range ETSI EN , V Protection class IP20 to EN Housing Material Polyamide Flammability class UL 94 V-2 Dimensions with screwable antenna connection 22.5mm x 115.0mm x 117.8mm (WxHxD) Assembly DIN rail 35mm x 7.5mm to EN Mounting position vertical Weight approx. 200g Interfaces Setup interface - Baud rate - PC interface RS485 interface - Protocol - Baud rate - Unit address - minimum response time Galvanic isolation Galvanic isolation voltage 9600 with TTL/RS232 or USB/TTL converter Modbus 9600, 19200, to to 500ms The interfaces are electrically isolated from the analog outputs 50V LCD Top line Bottom line 4-digit, 7-segment display, 4.5mm high 5-digit, 16-segment display, 4.0mm high 1 All accuracy details in % from the measuring range end value 20mA or 10V.
4 Data Sheet Page 4/7 Operation and configuration At the receiver For the operation and configuration of the receiver, four front-sided keys suffice, having different functions depending on the respective menu chosen. The dialog is supported by a twoline LCD display. Two LEDs indicate different operating conditions. The operation as well as configuration of the parameters are organised on three different levels: - Normal display (display of values and signal quality) - Start-up level (linking channels with probe ID) - Parameter level (editing configuration parameters) The two levels can be protected from unauthorised access with the help of one code each. 1 7-segment LCD, 4.5mm, 4-digit 5 Bicolor-LED 2 16-segment LCD, 4.0mm, 5-digit 3 Setup interface 4 Function keys - green = fault-free operation - red, flashing = collection alarm (the collection alarm includes the radio timeout of the probes 1 to 16, the limit value monitoring min./max. of the channels C01 to C16, storage faults detected at switch-on and the low-battery signal of the probes 1 to 16) 6 Yellow LED, flashing shortly - Reception check for each data packet from the probe Setup program The configuration via the setup program is more comfortable than by using the keyboard. The configuration data can be stored on data carriers and printed out. All configurable parameters are described in the operating instructions. The setup program allows to overwrite modified parameters with the factory setting at any time. The connection between the receiver and the PC is established using a PC interface (USB/ TTL or TTL/RS232 converter).
5 Data Sheet Page 5/7 Allocation of probes to the receiver (linking) A receiver may be used to display and process data from a maximum of 16 probes. Each transmitter needs to be linked to the receiver. Linking is possible in three different ways: - at the unit, via a list of received, non-linked probe IDs or by direct entry of the probe ID, - using the setup program, and - via the RS485 interface through Modbus commands. The list of received, non-linked probe IDs is maintained automatically by the receiver. The probe IDs are detected, entered or deleted automatically in this list (max. 25 entries). The probe ID can be entered directly at the unit or by using the setup program. In addition, the probe ID can be configured at any time by a Modbus master (e. g. SPS) via the RS485 interface. Radio range The max. open-air range is 300m. To reach this maximum reception quality and to establish the ideal operating condition of the lambda/4 antenna, use the wall mounting, available as accessory, with the 3 meter antenna cable. Buildings, concrete floors, walls and other constructional conditions may reduce the range.
6 Data Sheet Page 6/7 Dimensions Type /10... Connection diagram Connection for Voltage supply as per type plate Terminal assignment L1 N L1 N Outputs Type /10... Analog output 1 Analog output 2 Analog output 3 Analog output 4 Voltage 0 to 10V or Current 0(4) to 20mA Digital interface RS TxD+/RxD+ 10 GND 11 TxD-/RxD- Transmission/Reception data + Earth Transmission/Reception data -
7 Data Sheet Page 7/7 Order details: JUMO Wtrans RF-Series, receiver unit for wireless temperature probes (1) Basic type JUMO Wtrans RF-Series receiver unit for wireless temperature probes /10 DIN rail housing, protection class IP20, 4x outputs 0(4) to 20mA or 0 to 10V, galvanic isolation until 50V, Interface RS485 with Modbus protocol (2) Version x 8 Standard with factory settings x 9 customer-specific configuration (details in plain text) (3) Reception frequency x 10 ISM band 868.4MHz (Europe) x MHz (America, Australia, Canada and New Zealand) (4) Voltage supply x 23 AC 110 to 240V +10/-15%, 48 to 63Hz (5) Extra codes x 000 none (1) (2) (3) (4) (5) Order codes / Order example / / 000 Serial accessories Operating instructions Lambda/4 antenna, impedance 50 ohms, 868.4MHz or Lambda/4 antenna, impedance 50 ohms, 915MHz Accessories Sales item no. Setup program on CD-ROM, multilingual 90/ Lambda/4 antenna, impedance 50 ohms, 868.4MHz 90/ Lambda/4 antenna, impedance 50 ohms, 915MHz 90/ Wall mounting with counterweight for lambda/4 antenna 90/ Antenna cable, length 3m, impedance 50 ohms with pre-assembled screw connector 90/ Antenna cable, length 5m, impedance 50 ohms with pre-assembled screw connector 90/ Antenna cable, length 10m, impedance 50 ohms with pre-assembled screw connector 90/ PC interface with USB/TTL converter, adapter (socket) and adapter (pins) 70/ PC interface with TTL/RS232 converter and adapter (socket) 70/ Plant visualization software JUMO SVS3000 (data sheet ) - Paperless recorder JUMO LOGOSCREEN nt (data sheet ) - Stock versions (1) (2) (3) (4) (5) Sales item no / / / /
TX OPEN RS232/485 module
s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the
More informationJ TB/TW Temperature limiter, temperature monitor
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
More informationDifferential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
More informationAutomation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
More informationTelephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
More informationRISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
More informationQuick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
More informationVOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421
VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421 TABLE OF CONTENTS 1. FEATURES... 1 2. SPECIFICATIONS... 1 2-1 General Specifications...1 2-2 Electrical Specifications... 2 3. FRONT PANEL DESCRIPTION... 4 3-1
More informationis then retained absolutely without interruption.
Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection
More informationMultifunction devices
devices devices devices, electronic Type Page LED multifunction displays pulse, frequency, time (DC) Codix 524 240 pulse, frequency, time (AC+DC) Codix 544 243 LCD multifunction preset counters 1 or 2
More informationProcess modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
More informationMICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features
Central 48 V DC Power Supplies for PoE-Components MICROSENS Description Active network equipment which is supporting the Power-over-Ethernet functions, typically requires a powerful 48 V DC power supply.
More informationEZmoto V2. Product description Rev. 6 10/01/2014. EZmoto V2 Product description Rev.6 10/01/2014
EZmoto V2 Product description Rev. 6 10/01/2014 1 Contents 1. Overview... 3 2. Hardware Interface Description... 3 2.1 Main features of the EZmoto... 3 2.2 Hardware block diagram... 4 2.3 Internal Hardware
More informationTechnical data. General specifications. Indicators/operating means. Electrical specifications Operating voltage U B Power consumption P 0 Interface
Release date: 06-0- 09: Date of issue: 06-0- 009_eng.xml Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service
More informationFLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1
BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -
More informationRack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
More informationProgrammable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2
Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male
More informationHand-held thermometer Model CTH7000
Calibration technology Hand-held thermometer Model CTH7000 WIKA data sheet CT 55.50 Applications Precision thermometer for very accurate temperature measurements in a range of -200... +962 C Reference
More informationTechnical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5
Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis
More informationPCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
More informationconnecdim Gateway G1 Ethernet TCP/IP to DALI
Gateway G1 Ethernet TCP/IP to LI Independent lighting control for up to 256 LI gears on 4 LI lines Can be expanded by connecting multiple gateways on the same network Cloud based web interface for configuration
More informationElectronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm
Electronic pressure measurement Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm WIKA data sheet PE 81.67 Applications Machine tools Hydraulics
More informationQFP910. Water detector. Building Technologies. CE1N2732en. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
More information/ Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards.
56 / Accessories for inverters Accessories for inverters / Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards. FRONIUS STRING
More information1. SAFETY INFORMATION
RS-232 Sound Level Meter 72-860A INSTRUCTION MANUAL www.tenma.com 1. SAFETY INFORMATION Read the following safety information carefully before attempting to operate or service the meter. Use the meter
More informationDrayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationModular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
More informationSafety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
More informationRTD Temperature Probe for the Food/Pharmaceutical Industry
sales@jumo.co.uk Data Sheet 902810 Page 1/9 RTD Temperature Probe for the Food/Pharmaceutical Industry For temperatures between -50 and +250 C Protection type up to IP69 according to DIN EN 60529 (IP69K
More informationABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationMINI MCR-SL-R-UI(-SP)
Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts
More informationDigital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
More informationMeasurement. SITRANS F US Inline. Transmitter FUS080/FUE080 4/219
Siemens AG 2010 Flow Measurement Overview The transmitter is available in an IP67/NEMA X/6 enclosure and is designed for use in the flowmeters series: SONOKIT (1- or 2-track) FUS380 (2-track) FUE380 (2-track)
More informationSWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:
SWITCH The Budderfly lighting switch is a Decora style, plug-and-play replacement for your existing building switches. Installing a Budderfly adapter transforms your building s existing wiring into the
More informationPC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS
PC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS FRANCE Head office USA 4 Rue du Bois Chêne le loup Parc d Activité de Brabois 54 500 VANDOEUVRE LES NANCY (33) 0383442413, Fax (33) 0383443797
More informationRDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
More informationUnidirectional Transmitter/ Receiver Units Introduction
Unidirectional Transmitter/ Receiver Units Introduction Wireless Input/Output (I/O) connects directly to analog, discrete and pulse transducer signals. The signals are transmitted by radio and either re-created
More informationSYSTEM DESCRIPTION Termination Boards
PROCESS AUTOMATION SYSTEM DESCRIPTION Termination Boards Non-IS Termination Boards for Yokogawa CENTUM C3 and ProSafe RS ISO9001 With regard to the supply of products, the current issue of the following
More informationWaveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
More informationDigital inductive conductivity transmitter
Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
More informationTechnical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.
Model Number Features Very small housing High climatic resistance 4 Bit multiturn Analog output Surge and reverse polarity protection Description This absolute rotary encoder with internal magnetic sampling
More informationH/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.
Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.
More informationAnalogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001
Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.
More informationZC-24DO CANopen I/O Module: 24 Digital Outputs
Z-PC Line EN ZC-24DO CANopen I/O Module: 24 Digital Outputs Installation Manual Contents: - General Specifications - Technical Specifications - Installation Rules - Electrical connections - DIP-switches
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More informationZlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION
Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature
More informationPhysical Specifications (Custom design available.)
Helmholtz Coils A useful laboratory technique for getting a fairly uniform magnetic field, is to use a pair of circular coils on a common axis with equal currents flowing in the same sense. For a given
More informationLevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual
LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual Ver. 1.0.0-0711 1 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital
More informationOperating Manual UMB Analogue/Digital Converter ANACON Order Number: 8160.UANA
Order Number: 8160.UANA Status: V6; 1425.03.2010 G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany 1 TABLE OF CONTENTS PLEASE READ BEFORE USE... 3 DESCRIPTION... 5 ANACON UMB ANALOGUE/DIGITAL CONVERTER...
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationR4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
More informationPIEZOMETER AIRFLOW MEASURING RING
PIEZOMETER AIRFLOW MEASURING RING M.K. Plastics is pleased to introduce The Piezometer Airflow Measuring Ring, now available as an accessory for our steel Axijet fans. The system consists of a Piezometer
More informationDigital display DA 48
Loop powered plug-in LCD display No auxiliary energy source needed Scale freely adjustable on site Can be turned to any position Suitable for any 0 ma transmitter with EN 175301-803A connector Digital
More informationPreset Counter signo 721
Most simple handling Impressive, clearly readable display in 48x48 mm Input frequency up to 60 khz Easy installation due to pluggable terminals TECHNICAL DATA GENERAL Display Height of digits Supply voltage
More informationProduct and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
More informationContents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
More informationType: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
More informationVroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR
Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions
More informationEnergy Management Energy Meter Type EM23 DIN
Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy
More informationProduct data sheet. JUMO MIDAS Pressure Transmitter. Sales No. Order code JUMO AS 40.1001 401001/000-459-405-502-20-601-61
Produktdatenblatt - JUMO MIDAS Pressure Transmitter JUMO AS Street address: Solheimveien 50, 1470 Lørenskog, Norway Phone: +47 67 97 37 10 Delivery address: Solheimveien 50, 1470 Lørenskog, Norway Fax:
More informationHMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
More informationTEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.
TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection
More informationDigital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version
Electronic pressure measurement Digital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version WIKA data sheet PE 81.66 Applications Machine building
More informationElectronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
More informationMILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
More informationAdjustment functions for both span and shift have been incorporated
SENSORS FOR SERIES LED Type Wafer Alignment Sensor FX-0-F FT-F9 FD-F7 EX-F70/F60 M SH-7 FD-L4 M-DW The use of a safe LED light beam now allows for high precision detection with a resolution of 0!m (.8
More informationINPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS
VMC A4 INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS PRODUCT DATA SHEET FEATURES RF to 0-10 VDC out, analogue or PWM Maximal 3 digital inputs to RF RF communication with other equipment Wireless
More informationUser Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters
SDM220MODBUS Single-Phase Two Module DIN rail Meters Measures kwh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc. Di-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting 36mm
More informationApplication. Characteristics RTU560. Data Sheet Communication Unit 560CMD11. Communication Unit 560CMD11
Communication Unit 560CMD11 The SLC works as master for the RTU560 serial peripheral bus (I/O-Interface/ Wired-OR-Bus ). The MPU is responsible for the other tasks. The MPU handles the absolute time and
More informationCurrent Monitoring Kit QUICK START GUIDE
Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...
More informationRemote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
More informationRosemount 333 HART Tri-Loop
Product Data Sheet Rosemount 333 Rosemount 333 HART Tri-Loop HART-TO-ANALOG SIGNAL CONVERTER Convert a digital HART signal into three additional analog signals Easy to configure and install Accessory product
More information4-Channel Thermometer / Datalogger
USER GUIDE 4-Channel Thermometer / Datalogger RTD and Thermocouple Inputs Model SDL200 Introduction Congratulations on your purchase of the Extech SDL200 Thermometer, an SD Logger Series meter. This meter
More informationCurrent Monitoring Kit
Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added
More informationInwall Room Temperature Unit
Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall
More informationTest equipment for temperature and its reduction
Data sheet 90.2721 Page 1/6 Test equipment for temperature and its reduction Pt100 precision RTD temperature probe Calibrated temperature measuring chain with precision display device Calibrations as service
More informationPower Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
More informationProduct Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB
Product Manual ABB i-bus KNX IP Interface IPS/S 2.1 Intelligent Installation Systems ABB This manual describes the function of the IP Interface IPS/S 2.1 with the application program IP Interface. Subject
More informationiva Cable & Antenna Analyzer
iva Cable & Antenna Analyzer VSWR, Return Loss Measurement & Distance to Fault The iva Series Cable & Antenna Analyzer is an exciting new product from Kaelus that enables users to accurately measure VSWR/return
More informationHCR3.2/.. Chipcard reader HOTEL SOLUTION
s 6 332 HOTEL SOLUTION Chipcard reader HCR3.2/.. Chipcard reader for hotel room access control Reads access code on chipcard Transfers access code to room controller Built-in optical display of messages
More informationPortal Software GSM-PRO Run LED displays module activity Com LED displays activity on the GSM network GSM-PRO
GSM-PRO GSM-PRO perfect for communication CONTA-CLIP s GSM-PRO module offers a remote control and maintenance solution which allows you to monitor and control decentralized facilities. The GSM-PRO module
More informationTLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR
TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.
More informationHSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.
NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24
More informationNC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
More informationElectronic Pressure Switch EDS 300
Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5
More informationProduct and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
More informationHARDWARE MANUAL. Ixx24-A 1/20. Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600 vc@valcontrols.com www.valcontrols.
HARDWARE MANUAL Ixx24-A 1/20 Table of contents 1 General... 3 1.1 Safety instructions... 3 1.2 Environment... 3 1.3 Mounting and dimension... 3 2 Communication... 4 2.1 Control loop AI0 and Transmitter
More informationUser's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction
User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger
More informationiva Cable & Antenna Analyzer
iva Cable & Antenna Analyzer VSWR, Return Loss Measurement & Distance to Fault The iva Series Cable & Antenna Analyzer is an exciting new product from Kaelus that enables users to accurately measure VSWR/return
More informationDRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
More informationRM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
More informationTechnote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese.
Page 1 of 6 Application Proportional 0-10V or 3-position modulating or On/ Off control of Frese OPTIMA Compact valves in heating, ventilating and air conditioning systems. The actuator can be mounted on
More informationHow To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
More informationRosemount 333 HART Tri-Loop
Product Data Sheet September 2014 00813-0100-4754, Rev GA Rosemount 333 HART Tri-Loop HART-to-Analog Signal Converter Convert a digital HART signal into three additional analog signals Easy to configure
More informationIMR 6000/10../20../30
IMR 6000/10../20../30 System frame Component of the MMS 6000 Machine Monitoring System Applications: Slots for adaptation of the signal processing periphery (monitors, logic cards and interface cards)
More informationCelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual
CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CGWTS-M001A Version 1, Release 1, December 2004 NOTICE
More informationSmarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION
Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION The Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier is a multi-functional compact device. It
More informationQFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
More information