1 Data Sheet Page 1/7 JUMO Wtrans RF-Series Receiver unit T01 for wireless temperature probes k For temperature measurements of -30 to +260 C k Interface RS485 with Modbus protocol k Wireless reception of measured values k Low wiring cost thanks to modern RF-technology k For a maximum of 16 probes per receiver In connection with suitable Wtrans probes, the Wtrans receiver is used for the mobile and stationary measurement of temperatures. The use of radio frequency (RF) technology (ISM band MHz or 915 MHz) reduces installation costs significantly. Cables are no longer necessary and the radio-based temperature sensor technology also works in rough industrial environments. The supplied lambda/4 antenna with an impedance of 50Ω can be screwed on directly or mounted externally. If the recommended antenna wall mounting is used, the maximum open air range is 300m. The measured values are converted within the receiver and made available directly at the terminals as analog and temperature-linear current or voltage signals (0(4) to 20mA, 0 to 10V). All outputs of the receiver are electrically isolated. A connection to superordinate systems, e. g. the plant visualization software JUMO SVS3000 or the Modbusmaster-capable paperless recorder JUMO LOGOSCREEN nt, is possible via the RS485 interface in the Modbus protocol. Operation and configuration are possible via the keyboard and a two-line LCD or, more comfortable, via a setup program. Thus it is possible to configure parameters such as filter constants, offset, alarms as well as peak-reading-pointer (minimum and maximum value storage) separately for each channel. For this purpose, there is an interface at the front to connect the receiver with a PC, using a TTL/RS232 or USB/TTL converter. The receiver is designed for mounting on DIN rail 35mm x 7.5mm to EN The screw terminals for the electric connection are arranged on different levels. Type /10... Block structure Suitable Wtrans probes Reception unit Keyboard Reception frequency 868,4 MHz or 915 MHz 4 keys for operation and configuration Wtrans receiver Outputs 4x 0(4) to 20mA or 0 to 10V Display 2-line LCD for the visualisation of measured values and configuration as well as 2 LED as status indicators k Max. 16 Wtrans probes per Wtrans receiver k For mobile or stationary temperature measurements k Open-air range approx. 300m k Radio frequency MHz or 915 MHz; within the frequency band 915 MHz, ten frequencies can be configured k Different thermowell lengths k Voltage supply via lithium-battery 3.6V, 2.1Ah k Oil and acid resistant housing k Protection class IP67 Voltage supply Interfaces AC 110 to 240 V +10/-15 % 48 to 63 Hz 1x RS485 1x Setup More information see data sheet

2 Data Sheet Page 2/7 Technical data Input Number of probes Reception frequency Open-air range Measurement range limits Configuration Unit A maximum number of 16 probes can be supported per receiver MHz (Europe), 915 MHz (America, Australia, Canada and New Zealand); within the frequency band, ten frequencies can be configured max. 300m if the antenna wall mounting with 3m antenna cable is used -30 to +260 C via the keys at the unit or via setup program C ( F); can be set at the unit or with setup program Analog outputs Number 4 Analog outputs Output signal: - Current - Voltage can be set via the keys at the unit or with the setup program proportional DC current 0 to 20mA or 4 to 20mA DC voltage 0 to 10V Transmission behaviour temperature-linear, freely scalable working resistance (at current output) 500 ohms Load (at voltage output) 10k ohms Setting time during temperature change The setting time depends on the sending interval set in the probe Setting time after switch-on or reset 5s Calibration conditions AC 230V/22 C (±3K) Accuracy ±0.1% 1 (accuracy includes calibration linearization, influence of working resistance, load and voltage supply) Ripple ±0.2% 1 Galvanic isolation Galvanic isolation voltage The outputs are isolated from each other as well as from the interfaces 50V Measuring circuit monitoring of the analog outputs Measuring range undercut: - Current output 4 to 20mA - Current output 0 to 20mA - Voltage output 0 to 10V Measuring range exceedance: - Current output 4 to 20mA - Current output 0 to 20mA - Voltage output 0 to 10V Sensor short circuit or sensor and cable break and alarms: - Current output 4 to 20mA - Current output 0 to 20mA - Voltage output 0 to 10V Output behaviour declining until 3.8mA, then jump to configured signalling declining until -0.1mA, then jump to configured signalling declining until -0.1V, then jump to configured signalling rising until 20.5mA, then jump to configured signalling rising until 20.5mA, then jump to configured signalling rising until 10.25V, then jump to configured signalling positive signalling: > 21mA negative signalling: < 3.6mA positive signalling: > 21mA negative signalling: < -0.1mA positive signalling: > 10.5V negative signalling: < -0.1V The output behaviour (pos. or neg. signalling) can be configured. 1 All accuracy details in % from the measuring range end value 20mA or 10V.

3 Data Sheet Page 3/7 Electric data Voltage supply AC 110 to 240V +10/-15%, 48 to 63Hz Power consumption 9VA Electric connection Screw terminals up to 2.5mm 2 Electric safety EN , part 1 overvoltage class III, degree of pollution 2, for switching cabinet mounting to EN Electric isolation The voltage supply is electrically isolated from the outputs and the interfaces Test voltage 3700V Ambient factors Ambient temperature range -20 to +50 C (also in case of close-packed mounting) Storage temperature range -30 to +70 C Storage humidity relative humidity 85%, without condensation Temperature influence ±0.005% 1 /K; per K deviation from the reference temperature 22 C (±3K) Climatic conditions relative humidity 85%, without condensation to EN K3 Vibration resistance IEC , max. 1g at 10 to 55Hz EMC EN interference emission Class A - Immunity to interference Industrial requirement - radio frequency range ETSI EN , V Protection class IP20 to EN Housing Material Polyamide Flammability class UL 94 V-2 Dimensions with screwable antenna connection 22.5mm x 115.0mm x 117.8mm (WxHxD) Assembly DIN rail 35mm x 7.5mm to EN Mounting position vertical Weight approx. 200g Interfaces Setup interface - Baud rate - PC interface RS485 interface - Protocol - Baud rate - Unit address - minimum response time Galvanic isolation Galvanic isolation voltage 9600 with TTL/RS232 or USB/TTL converter Modbus 9600, 19200, to to 500ms The interfaces are electrically isolated from the analog outputs 50V LCD Top line Bottom line 4-digit, 7-segment display, 4.5mm high 5-digit, 16-segment display, 4.0mm high 1 All accuracy details in % from the measuring range end value 20mA or 10V.

4 Data Sheet Page 4/7 Operation and configuration At the receiver For the operation and configuration of the receiver, four front-sided keys suffice, having different functions depending on the respective menu chosen. The dialog is supported by a twoline LCD display. Two LEDs indicate different operating conditions. The operation as well as configuration of the parameters are organised on three different levels: - Normal display (display of values and signal quality) - Start-up level (linking channels with probe ID) - Parameter level (editing configuration parameters) The two levels can be protected from unauthorised access with the help of one code each. 1 7-segment LCD, 4.5mm, 4-digit 5 Bicolor-LED 2 16-segment LCD, 4.0mm, 5-digit 3 Setup interface 4 Function keys - green = fault-free operation - red, flashing = collection alarm (the collection alarm includes the radio timeout of the probes 1 to 16, the limit value monitoring min./max. of the channels C01 to C16, storage faults detected at switch-on and the low-battery signal of the probes 1 to 16) 6 Yellow LED, flashing shortly - Reception check for each data packet from the probe Setup program The configuration via the setup program is more comfortable than by using the keyboard. The configuration data can be stored on data carriers and printed out. All configurable parameters are described in the operating instructions. The setup program allows to overwrite modified parameters with the factory setting at any time. The connection between the receiver and the PC is established using a PC interface (USB/ TTL or TTL/RS232 converter).

5 Data Sheet Page 5/7 Allocation of probes to the receiver (linking) A receiver may be used to display and process data from a maximum of 16 probes. Each transmitter needs to be linked to the receiver. Linking is possible in three different ways: - at the unit, via a list of received, non-linked probe IDs or by direct entry of the probe ID, - using the setup program, and - via the RS485 interface through Modbus commands. The list of received, non-linked probe IDs is maintained automatically by the receiver. The probe IDs are detected, entered or deleted automatically in this list (max. 25 entries). The probe ID can be entered directly at the unit or by using the setup program. In addition, the probe ID can be configured at any time by a Modbus master (e. g. SPS) via the RS485 interface. Radio range The max. open-air range is 300m. To reach this maximum reception quality and to establish the ideal operating condition of the lambda/4 antenna, use the wall mounting, available as accessory, with the 3 meter antenna cable. Buildings, concrete floors, walls and other constructional conditions may reduce the range.

6 Data Sheet Page 6/7 Dimensions Type /10... Connection diagram Connection for Voltage supply as per type plate Terminal assignment L1 N L1 N Outputs Type /10... Analog output 1 Analog output 2 Analog output 3 Analog output 4 Voltage 0 to 10V or Current 0(4) to 20mA Digital interface RS TxD+/RxD+ 10 GND 11 TxD-/RxD- Transmission/Reception data + Earth Transmission/Reception data -

7 Data Sheet Page 7/7 Order details: JUMO Wtrans RF-Series, receiver unit for wireless temperature probes (1) Basic type JUMO Wtrans RF-Series receiver unit for wireless temperature probes /10 DIN rail housing, protection class IP20, 4x outputs 0(4) to 20mA or 0 to 10V, galvanic isolation until 50V, Interface RS485 with Modbus protocol (2) Version x 8 Standard with factory settings x 9 customer-specific configuration (details in plain text) (3) Reception frequency x 10 ISM band 868.4MHz (Europe) x MHz (America, Australia, Canada and New Zealand) (4) Voltage supply x 23 AC 110 to 240V +10/-15%, 48 to 63Hz (5) Extra codes x 000 none (1) (2) (3) (4) (5) Order codes / Order example / / 000 Serial accessories Operating instructions Lambda/4 antenna, impedance 50 ohms, 868.4MHz or Lambda/4 antenna, impedance 50 ohms, 915MHz Accessories Sales item no. Setup program on CD-ROM, multilingual 90/ Lambda/4 antenna, impedance 50 ohms, 868.4MHz 90/ Lambda/4 antenna, impedance 50 ohms, 915MHz 90/ Wall mounting with counterweight for lambda/4 antenna 90/ Antenna cable, length 3m, impedance 50 ohms with pre-assembled screw connector 90/ Antenna cable, length 5m, impedance 50 ohms with pre-assembled screw connector 90/ Antenna cable, length 10m, impedance 50 ohms with pre-assembled screw connector 90/ PC interface with USB/TTL converter, adapter (socket) and adapter (pins) 70/ PC interface with TTL/RS232 converter and adapter (socket) 70/ Plant visualization software JUMO SVS3000 (data sheet ) - Paperless recorder JUMO LOGOSCREEN nt (data sheet ) - Stock versions (1) (2) (3) (4) (5) Sales item no / / / /

TX OPEN RS232/485 module

TX OPEN RS232/485 module s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the

More information

J TB/TW Temperature limiter, temperature monitor

J TB/TW Temperature limiter, temperature monitor JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net

More information

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate 1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421

VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421 VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421 TABLE OF CONTENTS 1. FEATURES... 1 2. SPECIFICATIONS... 1 2-1 General Specifications...1 2-2 Electrical Specifications... 2 3. FRONT PANEL DESCRIPTION... 4 3-1

More information

is then retained absolutely without interruption.

is then retained absolutely without interruption. Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection

More information

Multifunction devices

Multifunction devices devices devices devices, electronic Type Page LED multifunction displays pulse, frequency, time (DC) Codix 524 240 pulse, frequency, time (AC+DC) Codix 544 243 LCD multifunction preset counters 1 or 2

More information

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation

More information

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features Central 48 V DC Power Supplies for PoE-Components MICROSENS Description Active network equipment which is supporting the Power-over-Ethernet functions, typically requires a powerful 48 V DC power supply.

More information

EZmoto V2. Product description Rev. 6 10/01/2014. EZmoto V2 Product description Rev.6 10/01/2014

EZmoto V2. Product description Rev. 6 10/01/2014. EZmoto V2 Product description Rev.6 10/01/2014 EZmoto V2 Product description Rev. 6 10/01/2014 1 Contents 1. Overview... 3 2. Hardware Interface Description... 3 2.1 Main features of the EZmoto... 3 2.2 Hardware block diagram... 4 2.3 Internal Hardware

More information

Technical data. General specifications. Indicators/operating means. Electrical specifications Operating voltage U B Power consumption P 0 Interface

Technical data. General specifications. Indicators/operating means. Electrical specifications Operating voltage U B Power consumption P 0 Interface Release date: 06-0- 09: Date of issue: 06-0- 009_eng.xml Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service

More information

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1 BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2 Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male

More information

Hand-held thermometer Model CTH7000

Hand-held thermometer Model CTH7000 Calibration technology Hand-held thermometer Model CTH7000 WIKA data sheet CT 55.50 Applications Precision thermometer for very accurate temperature measurements in a range of -200... +962 C Reference

More information

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5 Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

connecdim Gateway G1 Ethernet TCP/IP to DALI

connecdim Gateway G1 Ethernet TCP/IP to DALI Gateway G1 Ethernet TCP/IP to LI Independent lighting control for up to 256 LI gears on 4 LI lines Can be expanded by connecting multiple gateways on the same network Cloud based web interface for configuration

More information

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm Electronic pressure measurement Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm WIKA data sheet PE 81.67 Applications Machine tools Hydraulics

More information

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living 2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use

More information

/ Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards.

/ Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards. 56 / Accessories for inverters Accessories for inverters / Our accessories complement all PV systems, simplify installation and ensure that the system meets the required safety standards. FRONIUS STRING

More information

1. SAFETY INFORMATION

1. SAFETY INFORMATION RS-232 Sound Level Meter 72-860A INSTRUCTION MANUAL www.tenma.com 1. SAFETY INFORMATION Read the following safety information carefully before attempting to operate or service the meter. Use the meter

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

RTD Temperature Probe for the Food/Pharmaceutical Industry

RTD Temperature Probe for the Food/Pharmaceutical Industry sales@jumo.co.uk Data Sheet 902810 Page 1/9 RTD Temperature Probe for the Food/Pharmaceutical Industry For temperatures between -50 and +250 C Protection type up to IP69 according to DIN EN 60529 (IP69K

More information

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

MINI MCR-SL-R-UI(-SP)

MINI MCR-SL-R-UI(-SP) Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts

More information

Digital input modules

Digital input modules 8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a

More information

Measurement. SITRANS F US Inline. Transmitter FUS080/FUE080 4/219

Measurement. SITRANS F US Inline. Transmitter FUS080/FUE080 4/219 Siemens AG 2010 Flow Measurement Overview The transmitter is available in an IP67/NEMA X/6 enclosure and is designed for use in the flowmeters series: SONOKIT (1- or 2-track) FUS380 (2-track) FUE380 (2-track)

More information

SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:

SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET: SWITCH The Budderfly lighting switch is a Decora style, plug-and-play replacement for your existing building switches. Installing a Budderfly adapter transforms your building s existing wiring into the

More information

PC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS

PC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS PC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS FRANCE Head office USA 4 Rue du Bois Chêne le loup Parc d Activité de Brabois 54 500 VANDOEUVRE LES NANCY (33) 0383442413, Fax (33) 0383443797

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information

Unidirectional Transmitter/ Receiver Units Introduction

Unidirectional Transmitter/ Receiver Units Introduction Unidirectional Transmitter/ Receiver Units Introduction Wireless Input/Output (I/O) connects directly to analog, discrete and pulse transducer signals. The signals are transmitted by radio and either re-created

More information

SYSTEM DESCRIPTION Termination Boards

SYSTEM DESCRIPTION Termination Boards PROCESS AUTOMATION SYSTEM DESCRIPTION Termination Boards Non-IS Termination Boards for Yokogawa CENTUM C3 and ProSafe RS ISO9001 With regard to the supply of products, the current issue of the following

More information

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

Digital inductive conductivity transmitter

Digital inductive conductivity transmitter Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections

More information

Technical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.

Technical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output. Model Number Features Very small housing High climatic resistance 4 Bit multiturn Analog output Surge and reverse polarity protection Description This absolute rotary encoder with internal magnetic sampling

More information

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current. Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.

More information

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001 Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.

More information

ZC-24DO CANopen I/O Module: 24 Digital Outputs

ZC-24DO CANopen I/O Module: 24 Digital Outputs Z-PC Line EN ZC-24DO CANopen I/O Module: 24 Digital Outputs Installation Manual Contents: - General Specifications - Technical Specifications - Installation Rules - Electrical connections - DIP-switches

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

Physical Specifications (Custom design available.)

Physical Specifications (Custom design available.) Helmholtz Coils A useful laboratory technique for getting a fairly uniform magnetic field, is to use a pair of circular coils on a common axis with equal currents flowing in the same sense. For a given

More information

LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual

LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual Ver. 1.0.0-0711 1 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital

More information

Operating Manual UMB Analogue/Digital Converter ANACON Order Number: 8160.UANA

Operating Manual UMB Analogue/Digital Converter ANACON Order Number: 8160.UANA Order Number: 8160.UANA Status: V6; 1425.03.2010 G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany 1 TABLE OF CONTENTS PLEASE READ BEFORE USE... 3 DESCRIPTION... 5 ANACON UMB ANALOGUE/DIGITAL CONVERTER...

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0 FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION

More information

PIEZOMETER AIRFLOW MEASURING RING

PIEZOMETER AIRFLOW MEASURING RING PIEZOMETER AIRFLOW MEASURING RING M.K. Plastics is pleased to introduce The Piezometer Airflow Measuring Ring, now available as an accessory for our steel Axijet fans. The system consists of a Piezometer

More information

Digital display DA 48

Digital display DA 48 Loop powered plug-in LCD display No auxiliary energy source needed Scale freely adjustable on site Can be turned to any position Suitable for any 0 ma transmitter with EN 175301-803A connector Digital

More information

Preset Counter signo 721

Preset Counter signo 721 Most simple handling Impressive, clearly readable display in 48x48 mm Input frequency up to 60 khz Easy installation due to pluggable terminals TECHNICAL DATA GENERAL Display Height of digits Supply voltage

More information

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

Contents. Document information

Contents. Document information User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions

More information

Energy Management Energy Meter Type EM23 DIN

Energy Management Energy Meter Type EM23 DIN Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy

More information

Product data sheet. JUMO MIDAS Pressure Transmitter. Sales No. Order code JUMO AS 40.1001 401001/000-459-405-502-20-601-61

Product data sheet. JUMO MIDAS Pressure Transmitter. Sales No. Order code JUMO AS 40.1001 401001/000-459-405-502-20-601-61 Produktdatenblatt - JUMO MIDAS Pressure Transmitter JUMO AS Street address: Solheimveien 50, 1470 Lørenskog, Norway Phone: +47 67 97 37 10 Delivery address: Solheimveien 50, 1470 Lørenskog, Norway Fax:

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

Digital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version

Digital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version Electronic pressure measurement Digital pressure gauge for industrial applications Model DG-10-S, Standard version Model DG-10-E, Enhanced version WIKA data sheet PE 81.66 Applications Machine building

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

Adjustment functions for both span and shift have been incorporated

Adjustment functions for both span and shift have been incorporated SENSORS FOR SERIES LED Type Wafer Alignment Sensor FX-0-F FT-F9 FD-F7 EX-F70/F60 M SH-7 FD-L4 M-DW The use of a safe LED light beam now allows for high precision detection with a resolution of 0!m (.8

More information

INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS

INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS VMC A4 INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS PRODUCT DATA SHEET FEATURES RF to 0-10 VDC out, analogue or PWM Maximal 3 digital inputs to RF RF communication with other equipment Wireless

More information

User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters

User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters SDM220MODBUS Single-Phase Two Module DIN rail Meters Measures kwh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc. Di-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting 36mm

More information

Application. Characteristics RTU560. Data Sheet Communication Unit 560CMD11. Communication Unit 560CMD11

Application. Characteristics RTU560. Data Sheet Communication Unit 560CMD11. Communication Unit 560CMD11 Communication Unit 560CMD11 The SLC works as master for the RTU560 serial peripheral bus (I/O-Interface/ Wired-OR-Bus ). The MPU is responsible for the other tasks. The MPU handles the absolute time and

More information

Current Monitoring Kit QUICK START GUIDE

Current Monitoring Kit QUICK START GUIDE Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...

More information

Remote Monitoring and REC 501 Control Unit Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the

More information

Rosemount 333 HART Tri-Loop

Rosemount 333 HART Tri-Loop Product Data Sheet Rosemount 333 Rosemount 333 HART Tri-Loop HART-TO-ANALOG SIGNAL CONVERTER Convert a digital HART signal into three additional analog signals Easy to configure and install Accessory product

More information

4-Channel Thermometer / Datalogger

4-Channel Thermometer / Datalogger USER GUIDE 4-Channel Thermometer / Datalogger RTD and Thermocouple Inputs Model SDL200 Introduction Congratulations on your purchase of the Extech SDL200 Thermometer, an SD Logger Series meter. This meter

More information

Current Monitoring Kit

Current Monitoring Kit Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added

More information

Inwall Room Temperature Unit

Inwall Room Temperature Unit Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall

More information

Test equipment for temperature and its reduction

Test equipment for temperature and its reduction Data sheet 90.2721 Page 1/6 Test equipment for temperature and its reduction Pt100 precision RTD temperature probe Calibrated temperature measuring chain with precision display device Calibrations as service

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

Product Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB

Product Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB Product Manual ABB i-bus KNX IP Interface IPS/S 2.1 Intelligent Installation Systems ABB This manual describes the function of the IP Interface IPS/S 2.1 with the application program IP Interface. Subject

More information

iva Cable & Antenna Analyzer

iva Cable & Antenna Analyzer iva Cable & Antenna Analyzer VSWR, Return Loss Measurement & Distance to Fault The iva Series Cable & Antenna Analyzer is an exciting new product from Kaelus that enables users to accurately measure VSWR/return

More information

HCR3.2/.. Chipcard reader HOTEL SOLUTION

HCR3.2/.. Chipcard reader HOTEL SOLUTION s 6 332 HOTEL SOLUTION Chipcard reader HCR3.2/.. Chipcard reader for hotel room access control Reads access code on chipcard Transfers access code to room controller Built-in optical display of messages

More information

Portal Software GSM-PRO Run LED displays module activity Com LED displays activity on the GSM network GSM-PRO

Portal Software GSM-PRO Run LED displays module activity Com LED displays activity on the GSM network GSM-PRO GSM-PRO GSM-PRO perfect for communication CONTA-CLIP s GSM-PRO module offers a remote control and maintenance solution which allows you to monitor and control decentralized facilities. The GSM-PRO module

More information

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.

More information

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000. NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

Electronic Pressure Switch EDS 300

Electronic Pressure Switch EDS 300 Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

HARDWARE MANUAL. Ixx24-A 1/20. Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600 vc@valcontrols.com www.valcontrols.

HARDWARE MANUAL. Ixx24-A 1/20. Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600 vc@valcontrols.com www.valcontrols. HARDWARE MANUAL Ixx24-A 1/20 Table of contents 1 General... 3 1.1 Safety instructions... 3 1.2 Environment... 3 1.3 Mounting and dimension... 3 2 Communication... 4 2.1 Control loop AI0 and Transmitter

More information

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger

More information

iva Cable & Antenna Analyzer

iva Cable & Antenna Analyzer iva Cable & Antenna Analyzer VSWR, Return Loss Measurement & Distance to Fault The iva Series Cable & Antenna Analyzer is an exciting new product from Kaelus that enables users to accurately measure VSWR/return

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese.

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese. Page 1 of 6 Application Proportional 0-10V or 3-position modulating or On/ Off control of Frese OPTIMA Compact valves in heating, ventilating and air conditioning systems. The actuator can be mounted on

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

Rosemount 333 HART Tri-Loop

Rosemount 333 HART Tri-Loop Product Data Sheet September 2014 00813-0100-4754, Rev GA Rosemount 333 HART Tri-Loop HART-to-Analog Signal Converter Convert a digital HART signal into three additional analog signals Easy to configure

More information

IMR 6000/10../20../30

IMR 6000/10../20../30 IMR 6000/10../20../30 System frame Component of the MMS 6000 Machine Monitoring System Applications: Slots for adaptation of the signal processing periphery (monitors, logic cards and interface cards)

More information

CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual

CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CelluLine CGW-TS GSM Cellular Gateway Installation and Programming Manual CGWTS-M001A Version 1, Release 1, December 2004 NOTICE

More information

Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION

Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION The Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier is a multi-functional compact device. It

More information

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living 2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use

More information