Application Bulletin

Size: px
Start display at page:

Download "Application Bulletin"

Transcription

1 Bristol Compressors, Inc. Number: 124 Application Bulletin HIGH TEMPERATURE RETROFIT FROM R22 TO R407C Release EN Number C18811 Release Date 10/20/95 D /9/96 E /17/97 L /21/03 REVISIONS

2 Bristol Compressors, Inc. Application Bulletin No. 124 Release E/N: C18811 Date: 10/20/95 Revision E/N: L00910 Date: 2/21/03 Subject: High Temperature Retrofit from R22 to R407C These are general guidelines only and in no way should they replace, contradict or otherwise take precedence over any local, state or federal law or regulation pertaining to the recovery, reclamation, and recycling of refrigerants. With the phase-out of HCFC s, existing air conditioning/heat pump equipment will need to be replaced with new equipment or retrofitted with new components (including the compressor) that are approved for use with the new refrigerant and their lubricants. Using the procedures described below, existing R22 systems can be retrofitted for use with R407C, allowing them to continue in service for the remainder of their useful life. Bristol Compressors does not recommend the changeover of HCFC refrigerants to HFC s in systems that are operating and have no leaks. R407C is a zeotropic blend of refrigerants of the following composition: R32 23% R125 25% R134a 52% New High Temperature R407C Compressors are identified by the number 7 in the second digit of the model number (example: H75B28QABC). These compressors are factory oil charged with Polyol ester (POE) lubricant and employ an improved lubrication system which are required for the new refrigerant. For Bristol s approved lubricant type and required oil charge amounts for use with R407C, refer to the individual compressor model specification sheet. This information can be found on Bristol s website The use of any other lubricant may void the compressor warranty. Application Bulletin Page 2 of 13

3 SYSTEM DESIGN 1.0 Refrigerant Metering Devices The performance of each system is very dependent on the proper operation of each metering device. Devices such as solenoid valves, capillary tubes, fixed orifice valves, and expansion valves can perform differently if they are not correctly adjusted or properly sized. For example, the port size of a valve may not be correct for the new refrigerant density. Each valve and metering device manufacturer should be consulted, along with the system's manufacturer, to ensure all components will work properly in the presence of the new refrigerant and lubricant. 2.0 Filter Driers The proper selection of a system's filter drier is very important. Some filter driers may not be suitable for R407C refrigerant and polyol ester lubricant. Therefore, the original equipment manufacturer should be contacted for the proper filter drier selection. It is important to replace the filter drier any time the refrigerant or lubricant in a system is changed. Specifically, Bristol Compressors requires a new suction line filter drier be installed during any compressor replacement. Maintaining good system performance, reliability and cleanliness is closely linked to proper filter drier operation. 3.0 Controls The proper operation of many types of air conditioning/heat pump equipment requires that the control systems function correctly. The control system could be pressure controls, temperature controls, timing devices, or sophisticated electronic controls. Changing to R407C refrigerant and polyol ester lubricant in a system could adversely affect these control systems. Each equipment manufacturer should be consulted to ensure each control system will operate correctly with the R407C refrigerant/polyol ester lubricant combination. Changes most likely will have to be made for continued good equipment performance. These changes could involve adjusting temperature or pressure set points to new values or replacing the control system with a newly designed unit. 4.0 Explanation of R407C vs. R22 Condenser and Evaporator Temperature/Pressure Graphs Pressure versus temperature charts and graphs are included on pages 4 through 8 as a general information guideline. More detailed specific saturated property tables can be obtained from the chemical manufacturer and should be used when conducting system retrofits. The graphs are intended to represent the pressures that R407C delivers versus R22 at the equivalent saturated evaporator and condenser temperatures. 4.1 Explanation of refrigerant glide inherent to R407C R407C has refrigerant glide. Glide is due to the different boiling and condensing temperatures of the three components that make up R407C. This means there is not a one to one relationship between pressure and temperature as with R22. The saturated vapor and saturated liquid values are approximately 10 F apart for a given pressure, whereas with R22 they are one and the same The temperature glide of this refrigerant should not cause any problems as long as you keep in mind the following points about the relationship between pressures and temperatures of the evaporator and condenser. Application Bulletin Page 3 of 13

4 a) When specifying the evaporating and condensing temperatures use the mean (or average of dew and bubble point) temperatures. b) When setting evaporator superheat, calculate it from the saturated vapor (or dew point) temperature. c) When setting subcooling, calculate it from the saturated liquid (or bubble point) temperature Specific examples: (Some interpolation between values may be required) Set conditions to run a 45 F evaporator, 130 F condenser with 20 F superheat and 15 liquid subcooling. a) Find the 45 F mean temperature from Table 1. The pressure corresponding to this mean temperature is your suction pressure = 94.4 psia. b) Calculate the return gas temperature using the dew point temperature at this pressure. Example: F + 20 F superheat = F return gas temperature. c) Find 130 F mean temperature from Table 1. The pressure corresponding to this mean temperature is your discharge pressure = psia. d) Calculate the liquid temperature using the bubble point temperature at this pressure. Example: 126 F - 15 F subcool = 111 F liquid temperature Determine the amount of superheat on a system that measures a suction pressure of 68 psig at the bulb, and the temperature at the bulb reads 52 F. a) Convert 68 psig to psia = (atmospheric pressure) = 82.7 psia. Look up the dew point temperature from Table 1 at 82.7 psia. This value is 43.3 F. Your superheat is 52 F F = 8.7 F. Application Bulletin Page 4 of 13

5 R407C PRESSURE/TEMPERATURE TABLE Saturated Liquid and Saturated Vapor Properties PRESSURE DEW POINT MEAN TEMP BUBBLE POINT PSIA PSIG F F F TABLE 1 Application Bulletin Page 5 of 13

6 R407C PRESSURE/TEMPERATURE TABLE (Page 2) PRESSURE DEW POINT MEAN TEMP BUBBLE POINT PSIA PSIG F F F TABLE 1 Application Bulletin Page 6 of 13

7 R407C PRESSURE/TEMPERATURE TABLE (Page 3) PRESSURE DEW POINT MEAN TEMP BUBBLE POINT PSIA PSIG F F F TABLE 1 Application Bulletin Page 7 of 13

8 Saturated Properties of R407C and R22 Pressure vs. Temperature Graph Condenser Pressure vs. Temperature Pressure (Psia) R22 R407C SAT VAPOR R407C SAT LIQUID Condenser Temperature ( F) FIGURE # 1 Application Bulletin Page 8 of 13

9 Saturated properties of R407C and R22 Pressure vs. Temperature Graph Evaporator Pressure vs. Temperature R22 R407C SAT VAPOR R407C SAT LIQUID 80 Pressure (Psia) Evaporator Temperature ( F) FIGURE # 2 Application Bulletin Page 9 of 13

10 5.0 Maximum Continuous Current (MCC) Data Extensive testing has been done at maximum continuous current (MCC) test conditions with R407C and R22 refrigerant on many different displacement compressors. The MCC values of the compressors did not change from the published R22 values when R407C refrigerant was utilized. 6.0 Retrofit Procedure Summarized below are the recommended procedures for retrofitting an R22 system to R407C: 6.1 Compatibility. Consult the original equipment manufacturer of the system components for their recommendation on the following: - Plastics compatibility - Elastomers compatibility - Lubricant (viscosity, manufacturer, additives) - Solid core driers: Check with drier manufacturer for recommendation 6.2 If compressor has failed: a. Determine reason for system/compressor failure and correct b. Recover refrigerant (see step 6.4) c. Remove compressor (see step 6.5) d. Measure lubricant remaining in compressor - should be greater than 95% of original charge to minimize removal efforts in step (e) e. Assure removal of residual levels of original lubricant (must be less than 5%) - Purge system heat transfer components using high pressure inert gas (e.g., nitrogen) - Disconnect and purge line sets, or any other component that could trap lubricant (e.g., oil separator, valves, etc.) - Large system/long line sets may require up to three (3) oil changes after replacing compressor f. Go to If compressor has not failed: a. Run at reference condition and record on data sheet (see Appendix 2) which will be used to confirm R407C charge requirement b. Run system at a high flow condition (highest suction pressure) for minutes for optimum lubricant pick-up/return to compressor e. Go back to step 6.2, item (b) through (f) 6.4 Remove R22 charge. Remove refrigerant and collect in a recovery cylinder using a recovery device capable of pulling in. Hg vacuum. If the correct R22 charge size for the system is not known, weigh the amount of refrigerant removed. The initial quantity of R407C charged in the system will be determined from this weight. 6.5 Remove compressor. The compressor must be removed from system since it will not be compatible with HFC s/poe lubricant. 6.6 Replace filter drier. Replace filter drier with one approved for use with R407C refrigerant/polyol ester lubricant. 6.7 Install compressor. Using normal service practices, install compressor approved for R407C refrigerant/polyol ester lubricant. Application Bulletin Page 10 of 13

11 CAUTION: Do not leave compressor or system open to atmosphere for longer than 15 minutes maximum. Polyol ester lubricants are at least 100 times more hygroscopic (ability to absorb moisture) than mineral oils. It is almost impossible to remove the moisture absorbed by the lubricant even with heat and vacuum. 6.8 Leak check system. Use normal service practices. If a leak detector is used, consult the leak detector manufacturer for unit s sensitivity to R407C. 6.9 Evacuate. Use normal service practices to remove air and other non-condensables in the system, evacuate to at least 200 microns Charge system with R407C. To ensure that the proper refrigerant composition is charged in the system, it is important that liquid only be removed from the charging cylinder. Once removed from the cylinder, R407C can be charged to the system as vapor as long as all of the refrigerant removed from the cylinder is transferred to the system. Due to the liquid density difference of R407C versus R22, the refrigeration system will requires less weight of R407C than R22. The optimum charge will vary depending on the operating conditions, size of the evaporator and condenser, size of receiver (if present), and length of pipe or tubing runs in the system. For most systems, the optimum charge will be 85-90% by weight of the original R22 charge. It is recommended that the system be initially charged with about 85% by weight of the original R22 charge (refer to section 6.4). Add the initial charge to the liquid line of the system with the compressor not running. When the system and cylinder pressures are equal, start the compressor and meter the remainder of the refrigerant into the suction line of the system. Since some compressors may be damaged if liquid refrigerant enters the suction side of the compressor, it is important to charge the refrigerant slowly into the suction line to allow it to vaporize before it enters the compressor. A throttling valve can be used to ensure that the liquid is converted to vapor prior to entering the system Charge adjustment. Allow the system to run until conditions stabilize. Add additional R407C in small amounts until the system conditions reach the desired levels (refer to data recorded in step 6.3). Be sure to charge by evaporator/condenser temperatures since the pressures will be higher at the temperatures equal to R22. Total charge should not exceed original R22 charge levels Label components and system. After completion of retrofit, label the system and the converted components to identify the type of refrigerant and lubricant, so proper service will be performed in the future. Attached is a Retrofit Checklist (Appendix 1) for R407C to assist you in the retrofit process and a System Data Sheet (Appendix 2) to record the system operating conditions for your records. Application Bulletin Page 11 of 13

12 Appendix 1 Checklist for R407C Retrofit 1. Consult the original equipment manufacturer of the system components for their recommendation concerning compatibility and their retrofit procedures in order to sustain warranty 2. If compressor is operable, run high flow condition (highest suction pressure for minutes to maximize oil return to compressor). 3. Remove R22 charge from system (need in. Hg vacuum to remove charge). Use recovery cylinder --Do not vent to atmosphere-- 4. Replace filter drier with new filter drier approved for use with R407C. - Loose fill driers: Use XH7 or XH9 desiccant or equivalent. - Solid core driers: Check with drier manufacturer for recommendation. 5. Replace compressor with one approved for usage with R407C. - Measure and record oil remaining in old compressor - Residual lubricant should be less than 5% by weight of the total lubricant used in system 6. Leak check system. 7. Evacuate with vacuum pump using normal service practices (200 microns minimum). 8. Charge system with R407C. - Initially charge 85% by weight of original equipment manufacturer specified R22 charge. - Amount of refrigerant charged: 9. Start up equipment and adjust charge until desired operating conditions are achieved. - If low on charge, add in increments of 2-3% of original R22 charge. - Amount of refrigerant charged: 10. Total Refrigerant Charged (add 8 and 9) - Should not exceed original R22 charge level 11. Label components and system for type of refrigerant (R407C) and lubricant (polyol ester oil). 12. Conversion is complete!! Application Bulletin Page 12 of 13

13 SYSTEM DATA SHEET Appendix 2 Type of System/Location: Equipment Mfg.: Model No.: Serial No.: Drier Mfg.: Model No.: Condenser Cooling Medium (Air/Water): Expansion Device (check one): Capillary Tube: Expansion Valve: If Expansion Valve: Manufacturer: Model No.: Control/Set Point: Location of Sensor: Other System Controls (e.g.: head press control); Describe: Compressor Mfg.: Model No.: Serial No.: Original Lubricant: Type/Mfg.: Charge Size: New Lubricant: Type/Mfg.: 1st Charge Size: 2nd Charge Size: Additional Charge Size: Drier type (check one): Loose Fill: Solid Core: (circle units used where applicable) Date/Time Refrigerant Charge Size Lb. Ambient Temperature ( F/ C) Relative Humidity Compressor: Suction Temperature ( F/ C) Suction Pressure psig DischargeTemperature ( F/ C) Discharge Pressure psig Indoor Temperature ( F/ C) Evaporator: Refrigerant Inlet Temperature ( F/ C) Refrigerant Outlet Temperature ( F/ C) Coil Air/H O In Temperature ( F/ C) 2 Coil Air/H O Out Temperature ( F/ C) 2 Refrigerant Superht. Ctl. Pt. ( F/ C) Condenser: Refrigerant Inlet Temperature ( F/ C) Refrigerant Outlet Temperature ( F/ C) Coil Air/H O In Temperature ( F/ C) 2 Coil Air/H O Out Temperature ( F/ C) 2 Exp. Device Inlet Temperature ( F/ C) Motor Amps Run/Cycle Time Comments: R22 Data R407 Data Application Bulletin Page 13 of 13

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as

More information

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale

More information

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants

More information

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm)

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm) RS-52 (R428A) COMPOSITION % HFC 125 77.5 HFC 143a 20.0 R600a 1.9 R290 0.6 HCFC replacement Temperature glide R22, 502 & interim blends Approximately 0.8 o C Drop-in or long term Both Lubricant MO/AB/POE

More information

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507 Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale changeover of HCFCs

More information

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C GUIDELINES FOR UTILIZATION OF R407C 2009 Tecumseh Products Company. All rights reserved. Page 1 of 6 After many years of testing and investigation, R407C is recognized as a suitable alternative refrigerant

More information

Refrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Refrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions Refrigerant Changeover Guidelines R-502 to R-402A/R-408A Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale CFC changeover of CFC HCFC

More information

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into

More information

RS-44 (R424A) : Q & A

RS-44 (R424A) : Q & A RS-44 (R424A) : Q & A 1 Q: What is RS-44? A: RS-44 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-44 contain? A: RS-44 is a blend of HFC134a, HFC125,

More information

UNDERSTANDING REFRIGERANT TABLES

UNDERSTANDING REFRIGERANT TABLES Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,

More information

REFRIGERANT REFERENCE GUIDE

REFRIGERANT REFERENCE GUIDE REFRIGERANT REFERENCE GUIDE WORLWIDE REFRIGERANT SUPPLIER 2004 FOURTH EDITION 2004 DISCLAIMER This publication is designed to provide accurate and authoritative information. It is not to be construed as

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

Subject: 2005 Air Conditioning Service Guidelines

Subject: 2005 Air Conditioning Service Guidelines Date: June 27, 2005 Bulletin Number: 05D-J-114 To: DDG Headquarters and Branches and Jobbers Category: Service From: Steve Sigg, Product Service and Training Line(s): 10 and 15 Subject: 2005 Air Conditioning

More information

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction ALCO s series of Thermo -Expansion Valves are designed for air conditioning, chillers, rooftops, close control, A/C transportation, heat pumps, industrial cooling process and refrigeration applications.

More information

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems Dr. Charles C. Allgood 1, C. Curtis Lawson 2 1 DuPont Fluorochemicals, Wilmington, DE, USA E-mail: Charles.C.Allgood-1@usa.dupont.com

More information

D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges

D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges ALCO s TX3 series of Thermo -Expansion Valves are designed for air conditioning, heat pumps and commercial refrigeration applications. The TX3 is ideal for those applications requiring hermetic / compact

More information

RS-24 (R426A): Q & A

RS-24 (R426A): Q & A RS-24 (R426A): Q & A 1 Q: What is RS-24? A: RS-24 is a non ozone depleting Drop-in replacement for R12 in all applications including mobile air conditioning. 2 Q: Yes, but what does RS-24 contain? A: RS-24

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION 1- INTRODUCTION The destruction of the ozone layer by the chlorofluorcarbons (CFC s), among which are CFC 11, CFC 12, and CFC 13 and its vital effect on the earth's ecosystem, were the principal reasons

More information

Recommended Compressor Installation Practices

Recommended Compressor Installation Practices ASPEN COMPRESSOR, LLC Phone: 508.481.5058 Fax: 508.480.0328 Email:info@aspencompressor.com Website: www.aspencompressor.com Recommended Compressor Installation Practices 1. COMPRESSOR SELECTION AND USE

More information

Recharge Procedure for Telemark TVP-2000 and TVP-3500

Recharge Procedure for Telemark TVP-2000 and TVP-3500 Recharge Procedure for Telemark TVP-2000 and TVP-3500 Required items: 1.) Refrigeration service manifold. 2.) Charge recovery system. 3.) Dry nitrogen gas. If a high pressure cylinder is used, a pressure

More information

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Low GWP Replacements for R404A in Commercial Refrigeration Applications Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, Samuel.YanaMotta@honeywell.com Abstract

More information

COMPRESSOR REPLACEMENT PROCEDURE

COMPRESSOR REPLACEMENT PROCEDURE R-22 and R-410A COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003F Supersedes 2100-003E File: Volume I,

More information

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It. I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is

More information

THE REPLACEMENT OF R-22

THE REPLACEMENT OF R-22 ENGLISH TRANSLATION OF ARTICLE IN FRIO-CALOR AIRE ACONDICIONDAO BY GAS-SERVEI, S.A JUNE 2010 THE REPLACEMENT OF R-22 Courtesy of D. Lluis Giralt Lopez (Chemical Engineering Industrial) Gas Technical Department

More information

Flushing and Cleaning the A/C System

Flushing and Cleaning the A/C System Flushing and Cleaning the A/C System Once an AC system has been contaminated or has suffered a failure, the most important part of the AC service to restore the cooling performance to the system = FLUSHING

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 -

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 - Skills Canada National Competition Instructions and Competition Details / Post - Secondary May 27-30, 2015 - Saskatoon 1. Test Project Details This project is designed to test the range of skills used

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

Elements Elements describe the essential outcomes.

Elements Elements describe the essential outcomes. AURETU005 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. Retrofit and modify air conditioning and HVAC systems This unit describes the performance outcomes

More information

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

POLICY BULLETIN Tecumseh Compressor Company Compressor Group to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging

More information

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 21 Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems

More information

Rusty Walker, Corporate Trainer Hill PHOENIX

Rusty Walker, Corporate Trainer Hill PHOENIX Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1: PART 1: CO 2 Commercial refrigeration has been in the environmental spotlight for more than a decade, especially as leakage studies have revealed the true effects of hydrofluorocarbon (HFC) emissions.

More information

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016. Information compiled by Frank Prah, CMS

REFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016. Information compiled by Frank Prah, CMS Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 REFRIGERANT 410A Information compiled by Frank Prah, CMS INTRODUCTION Recently a new refrigerant, R-410A, has been formulated

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

Guide to good leak testing

Guide to good leak testing Page 0 Guide to good leak testing The Institute of Refrigeration, working with the Carbon Trust, brings you REAL Zero Refrigerant Emission and Loss Zero. The aim of this project is in the title zero refrigerant

More information

Automobile Air Conditioning Primer

Automobile Air Conditioning Primer Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the

More information

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning

More information

SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)

SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION) Form #SB4-304AS AirSourceR SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION) Second only to refrigerant hose leaks, compressors have the highest rate

More information

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS

CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS BULLETIN 240-10-3 June 2004 Supersedes June 1983 Many centrifugal systems get little maintenance. As a result they operate with the refrigerant highly contaminated

More information

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged

More information

Open Cycle Refrigeration System

Open Cycle Refrigeration System Chapter 9 Open Cycle Refrigeration System Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved An open cycle refrigeration system is that the system is without a traditional evaporator.

More information

Refrigeration System Installation & Operation Manual

Refrigeration System Installation & Operation Manual Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3

More information

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

Test Code: 8297 / Version 1

Test Code: 8297 / Version 1 Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment

More information

Planning for the ban on R22 in building air conditioning

Planning for the ban on R22 in building air conditioning - ACHPI 32 Planning for the ban on R22 in building air conditioning Those responsible for cooling and heating commercial properties are under increased pressure to improve energy efficiency and negotiate

More information

Training Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. www.cliplight.com/hvacr/ Page 2 3 4 4 5 6 8 9

Training Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. www.cliplight.com/hvacr/ Page 2 3 4 4 5 6 8 9 SUPER SEAL PROFESSIONAL FORMULA Training Manual a. b. c. d. e. f. g. h. i. j. k. l. m. Inside Your Guide Frequently Asked Questions... How does Super Seal work?... Can you use Super Seal on 410a systems

More information

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units 2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not

More information

A/C refrigerant system, overview

A/C refrigerant system, overview Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -

More information

How To Clean Water From An Ammonia Refrigeration System

How To Clean Water From An Ammonia Refrigeration System Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can

More information

10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS

10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS Service Literature ACC SERIES UNITS ACC Corp. 0201 L1 Revised 08 2004 The ACC is a residential split-system condensing unit available in sizes ranging from 1 1/2 to 5 tons. Condensing coil size, circuiting

More information

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 A refrigerant retrofit project, involving the conversion of a large Data Room cooling system from R22 to R422D (DuPont

More information

Vacuum. How It Relates to Refrigeration And Air Conditioning Service

Vacuum. How It Relates to Refrigeration And Air Conditioning Service Vacuum How It Relates to Refrigeration And Air Conditioning Service Moisture In A Refrigeration System Visible Moisture Water Droplets Uncommon, but it can occur Invisible Moisture Water Vapor Found in

More information

Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment

Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment Brett Van Horn Market Manager HVAC Arkema Inc. 900 First Ave King of Prussia, PA 19406 Topics Covered Today R-22 Phase-out EPA Allowances

More information

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)

More information

DESIGN STANDARDS SECTION 23 60 00

DESIGN STANDARDS SECTION 23 60 00 PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.

More information

01-3 6820-11 6820-11 AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON 2010.01

01-3 6820-11 6820-11 AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON 2010.01 682011 013 GENERAL 1. SPECIFICATIONS 682011 014 682011 2. REPAIR INSTRUCTIONS 1) Precautions for Working with R134a R12 refrigerant and R134a refrigerant are not compatible. These refrigerants must never

More information

How does solar air conditioning work?

How does solar air conditioning work? How does solar air conditioning work? In a conventional air conditioning system; The working fluid arrives at the compressor as a cool, low-pressure gas. The compressor is powered by electricity to squeeze

More information

MACS Recommended Service Procedures

MACS Recommended Service Procedures MACS Recommended Service Procedures Initial Customer Contact It is important to obtain information from the customer identifying the problem and any previous servicing history prior to attempting repair

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Merit Series13ACD Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service

More information

SSB*H4. Service Literature. SSB*H4 Commercial Air Conditioner

SSB*H4. Service Literature. SSB*H4 Commercial Air Conditioner Service Literature Corp. 0628 L5 Revised 07 2010 SSB*H4 Commercial Air Conditioner SSB*H4 The SSB*H4 is a high efficiency commercial split system condensing unit, which features a two stage scroll compressor

More information

ON-VEHICLE INSPECTION

ON-VEHICLE INSPECTION Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI

More information

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7 Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator

More information

USC CFC Leak Repair and Recordkeeping Procedures

USC CFC Leak Repair and Recordkeeping Procedures USC CFC Leak Repair and Recordkeeping Procedures I. Introduction Chlorofluorocarbons (CFCs) released into the atmosphere can damage the ozone layer that protects the earth from the penetration of harmful

More information

COMPRESSOR REPLACEMENT PROCEDURE

COMPRESSOR REPLACEMENT PROCEDURE COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright

More information

HVAC-02, Air Conditioning Troubleshooting and Repair

HVAC-02, Air Conditioning Troubleshooting and Repair HVAC-02, Air Conditioning Troubleshooting and Introduction Since I'm constantly receiving questions on 944 air conditioning systems, I figured it's time to come up with come helpful troubleshooting tips.

More information

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Technology Fact Sheet CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Buildings for the 21st Century Buildings that are more energy-efficient, comfortable, and affordable that s the goal of DOE s Office

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 2012 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE The State of California has determined that this product may contain or produce a chemical

More information

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet Thermostatic expansion valves type REFRIGERATION AND AIR CONDITIONING Technical leaflet Thermostatic expansion valves, type Contents Page Introduction........................................................................................3

More information

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment

More information

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and

More information

High School Graduation years 2013, 2014, 2015. Unit/Standard Number

High School Graduation years 2013, 2014, 2015. Unit/Standard Number 1 Secondary Task List 100 INTRODUCTION TO HVAC 101 Identify HVAC systems. 102 Describe career opportunities in the HVAC profession. 103 Demonstrate awareness of the occupational requirements. 104 Explain

More information

Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400

Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400 Owners Manual Refrigerated Air Dryer HX75 thru HX2400 IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS INFORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILIAR WITH THE PROPER INSTALLATION

More information

Rotary Compressors RK, RG and HG

Rotary Compressors RK, RG and HG MANUAL INSTALLATION AND OPERATION Rotary Compressors RK, RG and HG 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 General Information 5 The working principle of the Rotary Compressor 5 Range 6 Performance 7 Voltage and

More information

EPA 608 Certification. Study Guide. 1 P a g e

EPA 608 Certification. Study Guide. 1 P a g e EPA 608 Certification Study Guide 1 P a g e Foreword All HVACR technicians must become certified for the equipment they work on, under the Environmental Protection Agency s (EPA), refrigerant recovery

More information

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you! CPX/HT Series REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM High-performance products. Designed for you! COMPRESSED AIR WATER CONTAMINATION Atmospheric air contains water in vapor form in different

More information

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation GTRDD SERIES HEATLESS DRYER INSTALLATION, OPERATION & MAINTENANCE MANUAL TABLE OF CONTENTS SECTION 1 General Information: Pg 2 Description of Operation SECTION 2 Safety Instructions: Pg 3 Installation

More information

Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet

Perkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet Perkins Statewide Articulation Agreement Documentation item: Secondary Task List Coversheet The Secondary School agrees to: A. Implement the approved PDE Program(s) of Study. B. Provide assessment of student

More information

How To Design A Refrigeration System

How To Design A Refrigeration System AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

TRAINING, EXAMINATION AND CERTIFICATION

TRAINING, EXAMINATION AND CERTIFICATION TECHNICAL STANDARDS & SAFETY AUTHORITY TRAINING, EXAMINATION AND CERTIFICATION REFRIGERATION OPERATOR CLASS B CERTIFICATION & EXAMINATION GUIDE REVISED EDITION 2 CERTIFICATIONS PERSUANT TO THE OPERATING

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING

INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES Split System Air Conditioner Save these instructions for future reference WARNING The equipment covered in this manual is to be installed by trained

More information

SEALED SYSTEM DIAGNOSIS

SEALED SYSTEM DIAGNOSIS CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS R-105 SEALED SYSTEM DIAGNOSIS Liquid level varies but ly last couple of passes of condenser is filled with liquid when running TRAINING MANUAL Part

More information

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications Commercial CO2 Refrigeration Systems Guide for Subcritical and Transcritical CO2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section 1.

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation Ohio Medical Corporation 1111 Lakeside Drive Gurnee, IL 60031 Phone: (800) 448-0770 Fax: (847) 855-6304 info@ohiomedical.com

More information

Central Air Conditioning Plants

Central Air Conditioning Plants Central Air Conditioning Plants In our department, these plants (Air cooled or water cooled) are commonly available above 10 TR up to 100 TR. These types of plants are more suitable for large installations

More information

Customized Assessment Blueprint

Customized Assessment Blueprint Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC

More information

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from

More information

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split Multi System 16 SEER, Inverter System 9,000 to 18,000 BTU/Hr Single Split 4MXW8-A 4TXM6-A March2013 42 Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate

More information

Model No. XP13 018 XP13 024 XP13 030 XP13 036 XP13 037 XP13 042 XP13 048 XP13 060 Data Nominal Tonnage 1.5 2 2.5 3 3+ 3.5 4 5 Connections (sweat)

Model No. XP13 018 XP13 024 XP13 030 XP13 036 XP13 037 XP13 042 XP13 048 XP13 060 Data Nominal Tonnage 1.5 2 2.5 3 3+ 3.5 4 5 Connections (sweat) Service Literature Corp. 0528 L10 Revised 05 2008 XP13 SERIES UNITS XP13 The XP13 is a high efficiency residential split system heat pump unit, which features a scroll compressor and R 410A refrigerant.

More information

PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS

PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS NOR-LAKE, INCORPORATED 727 Second Street P.O. Box 248 Hudson, Wisconsin 54016 800-955-5253 715-386-2323 866-961-5253 Parts 800-388-5253 Service 715-386-4291 FAX www.norlake.com Split-Pak Pre-Assembled

More information