Application Bulletin
|
|
- Elaine Manning
- 7 years ago
- Views:
Transcription
1 Bristol Compressors, Inc. Number: 124 Application Bulletin HIGH TEMPERATURE RETROFIT FROM R22 TO R407C Release EN Number C18811 Release Date 10/20/95 D /9/96 E /17/97 L /21/03 REVISIONS
2 Bristol Compressors, Inc. Application Bulletin No. 124 Release E/N: C18811 Date: 10/20/95 Revision E/N: L00910 Date: 2/21/03 Subject: High Temperature Retrofit from R22 to R407C These are general guidelines only and in no way should they replace, contradict or otherwise take precedence over any local, state or federal law or regulation pertaining to the recovery, reclamation, and recycling of refrigerants. With the phase-out of HCFC s, existing air conditioning/heat pump equipment will need to be replaced with new equipment or retrofitted with new components (including the compressor) that are approved for use with the new refrigerant and their lubricants. Using the procedures described below, existing R22 systems can be retrofitted for use with R407C, allowing them to continue in service for the remainder of their useful life. Bristol Compressors does not recommend the changeover of HCFC refrigerants to HFC s in systems that are operating and have no leaks. R407C is a zeotropic blend of refrigerants of the following composition: R32 23% R125 25% R134a 52% New High Temperature R407C Compressors are identified by the number 7 in the second digit of the model number (example: H75B28QABC). These compressors are factory oil charged with Polyol ester (POE) lubricant and employ an improved lubrication system which are required for the new refrigerant. For Bristol s approved lubricant type and required oil charge amounts for use with R407C, refer to the individual compressor model specification sheet. This information can be found on Bristol s website The use of any other lubricant may void the compressor warranty. Application Bulletin Page 2 of 13
3 SYSTEM DESIGN 1.0 Refrigerant Metering Devices The performance of each system is very dependent on the proper operation of each metering device. Devices such as solenoid valves, capillary tubes, fixed orifice valves, and expansion valves can perform differently if they are not correctly adjusted or properly sized. For example, the port size of a valve may not be correct for the new refrigerant density. Each valve and metering device manufacturer should be consulted, along with the system's manufacturer, to ensure all components will work properly in the presence of the new refrigerant and lubricant. 2.0 Filter Driers The proper selection of a system's filter drier is very important. Some filter driers may not be suitable for R407C refrigerant and polyol ester lubricant. Therefore, the original equipment manufacturer should be contacted for the proper filter drier selection. It is important to replace the filter drier any time the refrigerant or lubricant in a system is changed. Specifically, Bristol Compressors requires a new suction line filter drier be installed during any compressor replacement. Maintaining good system performance, reliability and cleanliness is closely linked to proper filter drier operation. 3.0 Controls The proper operation of many types of air conditioning/heat pump equipment requires that the control systems function correctly. The control system could be pressure controls, temperature controls, timing devices, or sophisticated electronic controls. Changing to R407C refrigerant and polyol ester lubricant in a system could adversely affect these control systems. Each equipment manufacturer should be consulted to ensure each control system will operate correctly with the R407C refrigerant/polyol ester lubricant combination. Changes most likely will have to be made for continued good equipment performance. These changes could involve adjusting temperature or pressure set points to new values or replacing the control system with a newly designed unit. 4.0 Explanation of R407C vs. R22 Condenser and Evaporator Temperature/Pressure Graphs Pressure versus temperature charts and graphs are included on pages 4 through 8 as a general information guideline. More detailed specific saturated property tables can be obtained from the chemical manufacturer and should be used when conducting system retrofits. The graphs are intended to represent the pressures that R407C delivers versus R22 at the equivalent saturated evaporator and condenser temperatures. 4.1 Explanation of refrigerant glide inherent to R407C R407C has refrigerant glide. Glide is due to the different boiling and condensing temperatures of the three components that make up R407C. This means there is not a one to one relationship between pressure and temperature as with R22. The saturated vapor and saturated liquid values are approximately 10 F apart for a given pressure, whereas with R22 they are one and the same The temperature glide of this refrigerant should not cause any problems as long as you keep in mind the following points about the relationship between pressures and temperatures of the evaporator and condenser. Application Bulletin Page 3 of 13
4 a) When specifying the evaporating and condensing temperatures use the mean (or average of dew and bubble point) temperatures. b) When setting evaporator superheat, calculate it from the saturated vapor (or dew point) temperature. c) When setting subcooling, calculate it from the saturated liquid (or bubble point) temperature Specific examples: (Some interpolation between values may be required) Set conditions to run a 45 F evaporator, 130 F condenser with 20 F superheat and 15 liquid subcooling. a) Find the 45 F mean temperature from Table 1. The pressure corresponding to this mean temperature is your suction pressure = 94.4 psia. b) Calculate the return gas temperature using the dew point temperature at this pressure. Example: F + 20 F superheat = F return gas temperature. c) Find 130 F mean temperature from Table 1. The pressure corresponding to this mean temperature is your discharge pressure = psia. d) Calculate the liquid temperature using the bubble point temperature at this pressure. Example: 126 F - 15 F subcool = 111 F liquid temperature Determine the amount of superheat on a system that measures a suction pressure of 68 psig at the bulb, and the temperature at the bulb reads 52 F. a) Convert 68 psig to psia = (atmospheric pressure) = 82.7 psia. Look up the dew point temperature from Table 1 at 82.7 psia. This value is 43.3 F. Your superheat is 52 F F = 8.7 F. Application Bulletin Page 4 of 13
5 R407C PRESSURE/TEMPERATURE TABLE Saturated Liquid and Saturated Vapor Properties PRESSURE DEW POINT MEAN TEMP BUBBLE POINT PSIA PSIG F F F TABLE 1 Application Bulletin Page 5 of 13
6 R407C PRESSURE/TEMPERATURE TABLE (Page 2) PRESSURE DEW POINT MEAN TEMP BUBBLE POINT PSIA PSIG F F F TABLE 1 Application Bulletin Page 6 of 13
7 R407C PRESSURE/TEMPERATURE TABLE (Page 3) PRESSURE DEW POINT MEAN TEMP BUBBLE POINT PSIA PSIG F F F TABLE 1 Application Bulletin Page 7 of 13
8 Saturated Properties of R407C and R22 Pressure vs. Temperature Graph Condenser Pressure vs. Temperature Pressure (Psia) R22 R407C SAT VAPOR R407C SAT LIQUID Condenser Temperature ( F) FIGURE # 1 Application Bulletin Page 8 of 13
9 Saturated properties of R407C and R22 Pressure vs. Temperature Graph Evaporator Pressure vs. Temperature R22 R407C SAT VAPOR R407C SAT LIQUID 80 Pressure (Psia) Evaporator Temperature ( F) FIGURE # 2 Application Bulletin Page 9 of 13
10 5.0 Maximum Continuous Current (MCC) Data Extensive testing has been done at maximum continuous current (MCC) test conditions with R407C and R22 refrigerant on many different displacement compressors. The MCC values of the compressors did not change from the published R22 values when R407C refrigerant was utilized. 6.0 Retrofit Procedure Summarized below are the recommended procedures for retrofitting an R22 system to R407C: 6.1 Compatibility. Consult the original equipment manufacturer of the system components for their recommendation on the following: - Plastics compatibility - Elastomers compatibility - Lubricant (viscosity, manufacturer, additives) - Solid core driers: Check with drier manufacturer for recommendation 6.2 If compressor has failed: a. Determine reason for system/compressor failure and correct b. Recover refrigerant (see step 6.4) c. Remove compressor (see step 6.5) d. Measure lubricant remaining in compressor - should be greater than 95% of original charge to minimize removal efforts in step (e) e. Assure removal of residual levels of original lubricant (must be less than 5%) - Purge system heat transfer components using high pressure inert gas (e.g., nitrogen) - Disconnect and purge line sets, or any other component that could trap lubricant (e.g., oil separator, valves, etc.) - Large system/long line sets may require up to three (3) oil changes after replacing compressor f. Go to If compressor has not failed: a. Run at reference condition and record on data sheet (see Appendix 2) which will be used to confirm R407C charge requirement b. Run system at a high flow condition (highest suction pressure) for minutes for optimum lubricant pick-up/return to compressor e. Go back to step 6.2, item (b) through (f) 6.4 Remove R22 charge. Remove refrigerant and collect in a recovery cylinder using a recovery device capable of pulling in. Hg vacuum. If the correct R22 charge size for the system is not known, weigh the amount of refrigerant removed. The initial quantity of R407C charged in the system will be determined from this weight. 6.5 Remove compressor. The compressor must be removed from system since it will not be compatible with HFC s/poe lubricant. 6.6 Replace filter drier. Replace filter drier with one approved for use with R407C refrigerant/polyol ester lubricant. 6.7 Install compressor. Using normal service practices, install compressor approved for R407C refrigerant/polyol ester lubricant. Application Bulletin Page 10 of 13
11 CAUTION: Do not leave compressor or system open to atmosphere for longer than 15 minutes maximum. Polyol ester lubricants are at least 100 times more hygroscopic (ability to absorb moisture) than mineral oils. It is almost impossible to remove the moisture absorbed by the lubricant even with heat and vacuum. 6.8 Leak check system. Use normal service practices. If a leak detector is used, consult the leak detector manufacturer for unit s sensitivity to R407C. 6.9 Evacuate. Use normal service practices to remove air and other non-condensables in the system, evacuate to at least 200 microns Charge system with R407C. To ensure that the proper refrigerant composition is charged in the system, it is important that liquid only be removed from the charging cylinder. Once removed from the cylinder, R407C can be charged to the system as vapor as long as all of the refrigerant removed from the cylinder is transferred to the system. Due to the liquid density difference of R407C versus R22, the refrigeration system will requires less weight of R407C than R22. The optimum charge will vary depending on the operating conditions, size of the evaporator and condenser, size of receiver (if present), and length of pipe or tubing runs in the system. For most systems, the optimum charge will be 85-90% by weight of the original R22 charge. It is recommended that the system be initially charged with about 85% by weight of the original R22 charge (refer to section 6.4). Add the initial charge to the liquid line of the system with the compressor not running. When the system and cylinder pressures are equal, start the compressor and meter the remainder of the refrigerant into the suction line of the system. Since some compressors may be damaged if liquid refrigerant enters the suction side of the compressor, it is important to charge the refrigerant slowly into the suction line to allow it to vaporize before it enters the compressor. A throttling valve can be used to ensure that the liquid is converted to vapor prior to entering the system Charge adjustment. Allow the system to run until conditions stabilize. Add additional R407C in small amounts until the system conditions reach the desired levels (refer to data recorded in step 6.3). Be sure to charge by evaporator/condenser temperatures since the pressures will be higher at the temperatures equal to R22. Total charge should not exceed original R22 charge levels Label components and system. After completion of retrofit, label the system and the converted components to identify the type of refrigerant and lubricant, so proper service will be performed in the future. Attached is a Retrofit Checklist (Appendix 1) for R407C to assist you in the retrofit process and a System Data Sheet (Appendix 2) to record the system operating conditions for your records. Application Bulletin Page 11 of 13
12 Appendix 1 Checklist for R407C Retrofit 1. Consult the original equipment manufacturer of the system components for their recommendation concerning compatibility and their retrofit procedures in order to sustain warranty 2. If compressor is operable, run high flow condition (highest suction pressure for minutes to maximize oil return to compressor). 3. Remove R22 charge from system (need in. Hg vacuum to remove charge). Use recovery cylinder --Do not vent to atmosphere-- 4. Replace filter drier with new filter drier approved for use with R407C. - Loose fill driers: Use XH7 or XH9 desiccant or equivalent. - Solid core driers: Check with drier manufacturer for recommendation. 5. Replace compressor with one approved for usage with R407C. - Measure and record oil remaining in old compressor - Residual lubricant should be less than 5% by weight of the total lubricant used in system 6. Leak check system. 7. Evacuate with vacuum pump using normal service practices (200 microns minimum). 8. Charge system with R407C. - Initially charge 85% by weight of original equipment manufacturer specified R22 charge. - Amount of refrigerant charged: 9. Start up equipment and adjust charge until desired operating conditions are achieved. - If low on charge, add in increments of 2-3% of original R22 charge. - Amount of refrigerant charged: 10. Total Refrigerant Charged (add 8 and 9) - Should not exceed original R22 charge level 11. Label components and system for type of refrigerant (R407C) and lubricant (polyol ester oil). 12. Conversion is complete!! Application Bulletin Page 12 of 13
13 SYSTEM DATA SHEET Appendix 2 Type of System/Location: Equipment Mfg.: Model No.: Serial No.: Drier Mfg.: Model No.: Condenser Cooling Medium (Air/Water): Expansion Device (check one): Capillary Tube: Expansion Valve: If Expansion Valve: Manufacturer: Model No.: Control/Set Point: Location of Sensor: Other System Controls (e.g.: head press control); Describe: Compressor Mfg.: Model No.: Serial No.: Original Lubricant: Type/Mfg.: Charge Size: New Lubricant: Type/Mfg.: 1st Charge Size: 2nd Charge Size: Additional Charge Size: Drier type (check one): Loose Fill: Solid Core: (circle units used where applicable) Date/Time Refrigerant Charge Size Lb. Ambient Temperature ( F/ C) Relative Humidity Compressor: Suction Temperature ( F/ C) Suction Pressure psig DischargeTemperature ( F/ C) Discharge Pressure psig Indoor Temperature ( F/ C) Evaporator: Refrigerant Inlet Temperature ( F/ C) Refrigerant Outlet Temperature ( F/ C) Coil Air/H O In Temperature ( F/ C) 2 Coil Air/H O Out Temperature ( F/ C) 2 Refrigerant Superht. Ctl. Pt. ( F/ C) Condenser: Refrigerant Inlet Temperature ( F/ C) Refrigerant Outlet Temperature ( F/ C) Coil Air/H O In Temperature ( F/ C) 2 Coil Air/H O Out Temperature ( F/ C) 2 Exp. Device Inlet Temperature ( F/ C) Motor Amps Run/Cycle Time Comments: R22 Data R407 Data Application Bulletin Page 13 of 13
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as
More informationRefrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
More informationRefrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
More informationRS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm)
RS-52 (R428A) COMPOSITION % HFC 125 77.5 HFC 143a 20.0 R600a 1.9 R290 0.6 HCFC replacement Temperature glide R22, 502 & interim blends Approximately 0.8 o C Drop-in or long term Both Lubricant MO/AB/POE
More informationRefrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507 Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale changeover of HCFCs
More informationR407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C
GUIDELINES FOR UTILIZATION OF R407C 2009 Tecumseh Products Company. All rights reserved. Page 1 of 6 After many years of testing and investigation, R407C is recognized as a suitable alternative refrigerant
More informationRefrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-502 to R-402A/R-408A Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale CFC changeover of CFC HCFC
More informationTroubleshooting HVAC/R systems using refrigerant superheat and subcooling
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both
More informationRefrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
More informationINSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
More informationRS-44 (R424A) : Q & A
RS-44 (R424A) : Q & A 1 Q: What is RS-44? A: RS-44 is a non ozone depleting Drop-in replacement for R22 in most applications. 2 Q: Yes, but what does RS-44 contain? A: RS-44 is a blend of HFC134a, HFC125,
More informationUNDERSTANDING REFRIGERANT TABLES
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,
More informationREFRIGERANT REFERENCE GUIDE
REFRIGERANT REFERENCE GUIDE WORLWIDE REFRIGERANT SUPPLIER 2004 FOURTH EDITION 2004 DISCLAIMER This publication is designed to provide accurate and authoritative information. It is not to be construed as
More informationIt will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
More informationSubject: 2005 Air Conditioning Service Guidelines
Date: June 27, 2005 Bulletin Number: 05D-J-114 To: DDG Headquarters and Branches and Jobbers Category: Service From: Steve Sigg, Product Service and Training Line(s): 10 and 15 Subject: 2005 Air Conditioning
More informationD A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction
ALCO s series of Thermo -Expansion Valves are designed for air conditioning, chillers, rooftops, close control, A/C transportation, heat pumps, industrial cooling process and refrigeration applications.
More informationPerformance of R-438A in R-22 Refrigeration and Air Conditioning Systems
Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems Dr. Charles C. Allgood 1, C. Curtis Lawson 2 1 DuPont Fluorochemicals, Wilmington, DE, USA E-mail: Charles.C.Allgood-1@usa.dupont.com
More informationD A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges
ALCO s TX3 series of Thermo -Expansion Valves are designed for air conditioning, heat pumps and commercial refrigeration applications. The TX3 is ideal for those applications requiring hermetic / compact
More informationRS-24 (R426A): Q & A
RS-24 (R426A): Q & A 1 Q: What is RS-24? A: RS-24 is a non ozone depleting Drop-in replacement for R12 in all applications including mobile air conditioning. 2 Q: Yes, but what does RS-24 contain? A: RS-24
More informationTECHNICAL INFORMATION
1- INTRODUCTION The destruction of the ozone layer by the chlorofluorcarbons (CFC s), among which are CFC 11, CFC 12, and CFC 13 and its vital effect on the earth's ecosystem, were the principal reasons
More informationRecommended Compressor Installation Practices
ASPEN COMPRESSOR, LLC Phone: 508.481.5058 Fax: 508.480.0328 Email:info@aspencompressor.com Website: www.aspencompressor.com Recommended Compressor Installation Practices 1. COMPRESSOR SELECTION AND USE
More informationRecharge Procedure for Telemark TVP-2000 and TVP-3500
Recharge Procedure for Telemark TVP-2000 and TVP-3500 Required items: 1.) Refrigeration service manifold. 2.) Charge recovery system. 3.) Dry nitrogen gas. If a high pressure cylinder is used, a pressure
More informationLow GWP Replacements for R404A in Commercial Refrigeration Applications
Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, Samuel.YanaMotta@honeywell.com Abstract
More informationCOMPRESSOR REPLACEMENT PROCEDURE
R-22 and R-410A COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003F Supersedes 2100-003E File: Volume I,
More informationAny Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.
I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is
More informationTHE REPLACEMENT OF R-22
ENGLISH TRANSLATION OF ARTICLE IN FRIO-CALOR AIRE ACONDICIONDAO BY GAS-SERVEI, S.A JUNE 2010 THE REPLACEMENT OF R-22 Courtesy of D. Lluis Giralt Lopez (Chemical Engineering Industrial) Gas Technical Department
More informationFlushing and Cleaning the A/C System
Flushing and Cleaning the A/C System Once an AC system has been contaminated or has suffered a failure, the most important part of the AC service to restore the cooling performance to the system = FLUSHING
More informationTroubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
More informationHow To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
More informationSkills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 -
Skills Canada National Competition Instructions and Competition Details / Post - Secondary May 27-30, 2015 - Saskatoon 1. Test Project Details This project is designed to test the range of skills used
More informationTable V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
More informationGeothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls
Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
More informationElements Elements describe the essential outcomes.
AURETU005 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. Retrofit and modify air conditioning and HVAC systems This unit describes the performance outcomes
More informationPOLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
More informationPerformance of R-438A in R-22 Refrigeration and Air Conditioning Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 21 Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems
More informationRusty Walker, Corporate Trainer Hill PHOENIX
Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat
More informationASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
More informationCommercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:
PART 1: CO 2 Commercial refrigeration has been in the environmental spotlight for more than a decade, especially as leakage studies have revealed the true effects of hydrofluorocarbon (HFC) emissions.
More informationREFRIGERANT 410A. Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016. Information compiled by Frank Prah, CMS
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 REFRIGERANT 410A Information compiled by Frank Prah, CMS INTRODUCTION Recently a new refrigerant, R-410A, has been formulated
More informationCharacteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
More informationWhy and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
More informationGuide to good leak testing
Page 0 Guide to good leak testing The Institute of Refrigeration, working with the Carbon Trust, brings you REAL Zero Refrigerant Emission and Loss Zero. The aim of this project is in the title zero refrigerant
More informationAutomobile Air Conditioning Primer
Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the
More informationTEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning
More informationSERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)
Form #SB4-304AS AirSourceR SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION) Second only to refrigerant hose leaks, compressors have the highest rate
More informationCONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS
CONTAMINANT REMOVAL FROM CENTRIFUGAL SYSTEMS BULLETIN 240-10-3 June 2004 Supersedes June 1983 Many centrifugal systems get little maintenance. As a result they operate with the refrigerant highly contaminated
More informationTEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged
More informationOpen Cycle Refrigeration System
Chapter 9 Open Cycle Refrigeration System Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved An open cycle refrigeration system is that the system is without a traditional evaporator.
More informationRefrigeration System Installation & Operation Manual
Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3
More informationEnvironmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationTest Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
More informationPlanning for the ban on R22 in building air conditioning
- ACHPI 32 Planning for the ban on R22 in building air conditioning Those responsible for cooling and heating commercial properties are under increased pressure to improve energy efficiency and negotiate
More informationTraining Manual SUPER SEAL. Simplifying AC/R Repair. Inside Your Guide PROFESSIONAL FORMULA. www.cliplight.com/hvacr/ Page 2 3 4 4 5 6 8 9
SUPER SEAL PROFESSIONAL FORMULA Training Manual a. b. c. d. e. f. g. h. i. j. k. l. m. Inside Your Guide Frequently Asked Questions... How does Super Seal work?... Can you use Super Seal on 410a systems
More information2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not
More informationA/C refrigerant system, overview
Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -
More informationHow To Clean Water From An Ammonia Refrigeration System
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can
More information10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS
Service Literature ACC SERIES UNITS ACC Corp. 0201 L1 Revised 08 2004 The ACC is a residential split-system condensing unit available in sizes ranging from 1 1/2 to 5 tons. Condensing coil size, circuiting
More informationGround-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29
Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 A refrigerant retrofit project, involving the conversion of a large Data Room cooling system from R22 to R422D (DuPont
More informationVacuum. How It Relates to Refrigeration And Air Conditioning Service
Vacuum How It Relates to Refrigeration And Air Conditioning Service Moisture In A Refrigeration System Visible Moisture Water Droplets Uncommon, but it can occur Invisible Moisture Water Vapor Found in
More informationRepair, Retrofit, or Replace Choices for Servicing R-22 Equipment
Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment Brett Van Horn Market Manager HVAC Arkema Inc. 900 First Ave King of Prussia, PA 19406 Topics Covered Today R-22 Phase-out EPA Allowances
More informationHow much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.
Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)
More informationDESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
More information01-3 6820-11 6820-11 AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON 2010.01
682011 013 GENERAL 1. SPECIFICATIONS 682011 014 682011 2. REPAIR INSTRUCTIONS 1) Precautions for Working with R134a R12 refrigerant and R134a refrigerant are not compatible. These refrigerants must never
More informationHow does solar air conditioning work?
How does solar air conditioning work? In a conventional air conditioning system; The working fluid arrives at the compressor as a cool, low-pressure gas. The compressor is powered by electricity to squeeze
More informationMACS Recommended Service Procedures
MACS Recommended Service Procedures Initial Customer Contact It is important to obtain information from the customer identifying the problem and any previous servicing history prior to attempting repair
More informationINSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS Merit Series13ACD Units RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service
More informationSSB*H4. Service Literature. SSB*H4 Commercial Air Conditioner
Service Literature Corp. 0628 L5 Revised 07 2010 SSB*H4 Commercial Air Conditioner SSB*H4 The SSB*H4 is a high efficiency commercial split system condensing unit, which features a two stage scroll compressor
More informationON-VEHICLE INSPECTION
Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI
More informationEngineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
More informationUSC CFC Leak Repair and Recordkeeping Procedures
USC CFC Leak Repair and Recordkeeping Procedures I. Introduction Chlorofluorocarbons (CFCs) released into the atmosphere can damage the ozone layer that protects the earth from the penetration of harmful
More informationCOMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
More informationHVAC-02, Air Conditioning Troubleshooting and Repair
HVAC-02, Air Conditioning Troubleshooting and Introduction Since I'm constantly receiving questions on 944 air conditioning systems, I figured it's time to come up with come helpful troubleshooting tips.
More informationCENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION
Technology Fact Sheet CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Buildings for the 21st Century Buildings that are more energy-efficient, comfortable, and affordable that s the goal of DOE s Office
More informationINSTALLATION INSTRUCTIONS
2012 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE The State of California has determined that this product may contain or produce a chemical
More informationThermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet
Thermostatic expansion valves type REFRIGERATION AND AIR CONDITIONING Technical leaflet Thermostatic expansion valves, type Contents Page Introduction........................................................................................3
More informationA Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment
More informationElements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system
AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and
More informationHigh School Graduation years 2013, 2014, 2015. Unit/Standard Number
1 Secondary Task List 100 INTRODUCTION TO HVAC 101 Identify HVAC systems. 102 Describe career opportunities in the HVAC profession. 103 Demonstrate awareness of the occupational requirements. 104 Explain
More informationOwners Manual. Refrigerated Air Dryer. HX75 thru HX2400
Owners Manual Refrigerated Air Dryer HX75 thru HX2400 IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS INFORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILIAR WITH THE PROPER INSTALLATION
More informationRotary Compressors RK, RG and HG
MANUAL INSTALLATION AND OPERATION Rotary Compressors RK, RG and HG 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 General Information 5 The working principle of the Rotary Compressor 5 Range 6 Performance 7 Voltage and
More informationEPA 608 Certification. Study Guide. 1 P a g e
EPA 608 Certification Study Guide 1 P a g e Foreword All HVACR technicians must become certified for the equipment they work on, under the Environmental Protection Agency s (EPA), refrigerant recovery
More informationCPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!
CPX/HT Series REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM High-performance products. Designed for you! COMPRESSED AIR WATER CONTAMINATION Atmospheric air contains water in vapor form in different
More informationTABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation
GTRDD SERIES HEATLESS DRYER INSTALLATION, OPERATION & MAINTENANCE MANUAL TABLE OF CONTENTS SECTION 1 General Information: Pg 2 Description of Operation SECTION 2 Safety Instructions: Pg 3 Installation
More informationPerkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet
Perkins Statewide Articulation Agreement Documentation item: Secondary Task List Coversheet The Secondary School agrees to: A. Implement the approved PDE Program(s) of Study. B. Provide assessment of student
More informationHow To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
More informationNational Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
More informationTRAINING, EXAMINATION AND CERTIFICATION
TECHNICAL STANDARDS & SAFETY AUTHORITY TRAINING, EXAMINATION AND CERTIFICATION REFRIGERATION OPERATOR CLASS B CERTIFICATION & EXAMINATION GUIDE REVISED EDITION 2 CERTIFICATIONS PERSUANT TO THE OPERATING
More informationINSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES Split System Air Conditioner Save these instructions for future reference WARNING The equipment covered in this manual is to be installed by trained
More informationSEALED SYSTEM DIAGNOSIS
CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS R-105 SEALED SYSTEM DIAGNOSIS Liquid level varies but ly last couple of passes of condenser is filled with liquid when running TRAINING MANUAL Part
More informationCommercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications
Commercial CO2 Refrigeration Systems Guide for Subcritical and Transcritical CO2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section 1.
More informationTable Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
More informationACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation
ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation Ohio Medical Corporation 1111 Lakeside Drive Gurnee, IL 60031 Phone: (800) 448-0770 Fax: (847) 855-6304 info@ohiomedical.com
More informationCentral Air Conditioning Plants
Central Air Conditioning Plants In our department, these plants (Air cooled or water cooled) are commonly available above 10 TR up to 100 TR. These types of plants are more suitable for large installations
More informationCustomized Assessment Blueprint
Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC
More informationChapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from
More informationMulti System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split
Multi System 16 SEER, Inverter System 9,000 to 18,000 BTU/Hr Single Split 4MXW8-A 4TXM6-A March2013 42 Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate
More informationModel No. XP13 018 XP13 024 XP13 030 XP13 036 XP13 037 XP13 042 XP13 048 XP13 060 Data Nominal Tonnage 1.5 2 2.5 3 3+ 3.5 4 5 Connections (sweat)
Service Literature Corp. 0528 L10 Revised 05 2008 XP13 SERIES UNITS XP13 The XP13 is a high efficiency residential split system heat pump unit, which features a scroll compressor and R 410A refrigerant.
More informationPRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS
NOR-LAKE, INCORPORATED 727 Second Street P.O. Box 248 Hudson, Wisconsin 54016 800-955-5253 715-386-2323 866-961-5253 Parts 800-388-5253 Service 715-386-4291 FAX www.norlake.com Split-Pak Pre-Assembled
More information