1 SECTION STEAM BOILERS (FIRETUBE) PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract Documents. B. Boiler and accessories pre-purchased by Owner. Coordinate with owner selected boiler manufacture. 1.2 SUBMITTALS A. Submit product data for boiler-burners and accessories and all other auxiliaries. Submit 1/4 in. scale shop drawing for Boiler Room showing boilers, auxiliaries, piping, breeching and clearances. 1.3 COMPLIANCE WITH INDUSTRIAL CODE AND BOILER INPSPECTION A. Boiler and boiler installation shall comply with New York State Department of Labor, NYCRR, Code Rule 4. Obtain certificate of boiler inspection after boiler installation has been completed. Pay fees. 1.4 QUALIFICATIONS A. The following boiler-burner control features provided on all units; 1. Primary combustion controls shall operate on 120 volt, single phase, grounded circuit. 2. Control wiring in conduit separate from power wiring conduit. 3. Wiring to flame sensor in separate individual conduit. 4. Wiring in accordance with National Electrical Code. 5. Valves in accordance with "Valves" Section. 6. Provide terminals for control and power wiring to respective combustion air damper. B. Service Guarantees: 1. Arrange for boiler manufacturer to provide: a. Instructions for proper installation and operation of boilers, burners and controls supplied. b. Checking proper size of oil and gas piping. STEAM BOILERS (FIRETUBE)
2 c. Supplying motors, starters, and control wiring in compliance with requirements of "Motors" and "Electric Wiring" specifications sections and National Electric Code. d. Supplying required and certified-correct wiring diagrams, indicating wiring to remotely located equipment connected with boiler-burner operation. e. Providing factory trained technician for start-up service and instruction of authorized operators. f. Submitting name and address of factory authorized dealer or service agency, who: is located within 150 miles of job, equipped to render prompt and efficient 24-hour service, and stocks sufficient replacement parts. g. Examine Contract Documents of Boiler Room, breaching, fresh air inlets, fuel supply layout, and advise Owner's Representative if same are not satisfactory for proper operation of boilers firing at full load. 2. Complete installation to comply with (FM) Factory Mutual Insurance and applicable local municipal requirements. 1.5 SPECIAL COORDINATION a. Provide inspection, adjustment and 24-hour call-back service within guarantee period. b. Withstand a difference in supply and return temperature of at least 40 F without leaking, regardless of rate of change in temperature. A. Coordinate Work of other trades in Boiler Room. Furnish Division 26 "Electric" with dimensional drawings showing location of electrical connections, and equipment location of equipment mounted on walls, and of other equipment requiring electrical connections or removing/replacing to permit entry of boiler. PART 2 - PRODUCTS 2.1 PRE-PURCHASED STEAM BOILER A. Coordinate with owner for information on the pre-purchased boiler package. PART 3 - EXECUTION 3.1 BOILER-BURNERS A. Temporary Storage: If boilers or burners are exposed to weather, keep metal parts securely covered. Keep boiler openings plugged until piped. Remove susceptible electrical equipment and store in worm place. B. Install Per Manufacturer's Written Instructions: STEAM BOILERS (FIRETUBE)
3 1. Properly level on equipment pad. 2. Pipe blowoffs to the floor and drains to the floor drains. Pipe size shall not be less than tapping size on boiler, low water cutoffs and reliefs. 3. Protect boiler-burner unit from damage during construction. 4. Division 26 - Electrical to provide a manually operated break-glass type remote heating plant shutdown switch located just inside the Boiler Room door and marked for easy identification. C. Employ the services of a Water Treatment Supplier who shall: 1. Test water before filling boilers and prescribe proper water treatment to prevent corrosion or deterioration due to oxygen, acid or scaling. 2. Furnish for delivery to Owner, proper test kit for checking boiler water conditions. 3. Immediately after internal inspection and refilling of boiler, check water conditions at that time and prescribe proper water treatment again. 4. The Water Treatment Supplier shall be responsible for a proper boilout routine, meeting their own, as well as the boiler manufacturer's recommendations. 5. Provide water treatment services for the period of one (1) year as part of this contract. D. Internal Boiler Inspection: 1. Prior to request for acceptance, Contractor shall: a. Drain down each boiler. b. Remove manhole cover. c. Remove handhole plates. d. Thoroughly flush out. e. Notify Owner's Representative when this has been done. f. Must be done one boiler at a time. 2. After inspection and review with the Owner's Representative of condition of boilers: a. Replace handhole and manhole plates using new spare gaskets furnished with boilers. b. Refill boilers and immediately fire. STEAM BOILERS (FIRETUBE)
4 3. Thoroughly clean fire side of flue passages. 4. If excessive pitting of boilers has occurred, or boiler has deteriorated in other ways, Contractor responsible for making repairs. E. Services of Factory Mechanic (Provided under pre-purchase with Owner): 1. Arrange to have services of a trained field mechanic from the factory of the manufacturer of the boiler to start-up the installation. 2. Mechanic shall check out entire installation, including pumps and feed apparatus and controls, shall start the units into operation and shall make necessary tests and adjustments to have said equipment operate properly. 3. Manufacturer shall issue a letter stating that the installation has been checked and adjusted and is ready to turn over to the Owner following the completion of this Work. 4. Manufacturer is to forward three (3) copies of the start up report to Owner's Representative for distribution to Owner. 5. Factory mechanic shall be at the job for the initial start-up for not less than two consecutive calendar days and eight hours for each day. 6. Factory mechanic shall make two more trips to the job within the succeeding eight months from the date of the above mentioned letter for the purpose of further adjusting and checking and shall be immediately available in the event of operating failure of the units within a period of one year from the date of the letter. 7. Factory mechanic shall conduct demonstration and combustion tests each boiler for oil and gas firing and shall submit written report. Notify Owner's Representative. F. Tools and Spare Parts (provided under Pre-purchase with Owner): 1. Furnish and obtain receipt for a flue brush and scraper with light weight handles and all special tools recommended by Boiler Manufacturer. 2. Furnish one set of spare parts per boiler as follows: a. Complete set of gaskets. b. V-belts. c. Ignition cable assembly. d. Ignition electrode assembly. e. Nozzle. STEAM BOILERS (FIRETUBE)
5 END OF SECTION STEAM BOILERS (FIRETUBE)
Boiler and Burner Cleaning and Servicing Specifications
Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service
More informationLAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
More informationThe city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers
The city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers Table of Contents Introduction... 1 Intention... 2 Authority and responsibility letter... 3 Organizational
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationPLP - TERMS AND CONDITIONS
PLP - TERMS AND CONDITIONS 2014-2015 Philadelphia Gas Works Residential Parts & Labor Plan Contract This Residential Parts & Labor Plan Contract (this Plan ) is available to customers of the Philadelphia
More informationGuidelines for Preparing for a Temporary Steam Plant
Guidelines for Preparing for a Temporary Steam Plant Trailer-Mounted Boilers Skid Mounted Boilers Mobile Boiler Rooms Mobile Feedwater Vans Mobile Steam Plants Emergency Preparedness Plan Table of Contents
More informationPACKAGED FIRE TUBE BOILER
SAMPLE PREVENTIVE MAINTENANCE MANUAL PACKAGED FIRE TUBE BOILER 1 CONTENTS Introduction 1 Intention 2 Organisational setup 3 Boiler Fault reporting & Repair progression 4 Preventive Maintenance Schedules
More informationRESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00
RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls
More informationCARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
More informationBoiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
More informationRoutine and Emergency Boiler Operation
Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here
More informationEvaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
More informationCROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS
CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS WARNING Improper installation, adjustment, alteration, service, or maintenance of this product can cause
More informationFactory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
More informationC. Burner management system to follow requirements of Industrial Risk Insurers (IRI).
SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 36C01 Combination Gas Valves (24 Volt and 120 Volt Models) INSTALLATI INSTRUCTIS FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE
More informationINSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9
TABLE OF CONTENTS Description Page Number SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9 Indeck Keystone Energy, LLC. 5451 Merwin Lane, Suite 100 Erie,
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationFACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
More informationOTF Oil Fired Pool Heater
OTF Oil Fired Pool Heater Installation Operation Maintenance Manual Service Policy 722010 Congratulations on the purchase of your new pool heater. In order to maintain peak performance of your pool heater
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationBaxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler
User s Operating Instructions Baxi Combi Instant 8e & 15e Gas Fired Wall Mounted Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.
More informationecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user
For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents
More informationPropane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
More informationREDFYRE CENTRAL-HEATING COOKER (OIL & GAS FIRED)
REDFYRE CENTRAL-HEATING COOKER (OIL & GAS FIRED) MODELS 0, 80, 00, 20 PARTS LIST AUGUST 202 A REDFYRE CENTRAL HEATING COOKER ---- TOP - PLATE & LIDS 2 REDFYRE CENTRAL HEATING COOKER ---- TOP - PLATE &
More informationSECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
More informationBC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
More informationELECTRODE BOILERS VAPOR POWER INTERNATIONAL
ELECTRODE BOILERS WITH JET-FLO Technology VAPOR POWER INTERNATIONAL ELECTRODE boilers The Electrode Steam Boiler with Jet-Flo technology consists of an insulated pressure vessel and is fully enclosed in
More informationGAS SAFETY PRECAUTIONS
GAS SAFETY PRECAUTIONS Instructions on what to do when a user smells gas can be obtained from the local gas supplier. These instructions must be posted in a prominent location where the unit is to be operated.
More informationNFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
More informationRECON WATER HEATER INSTALLATION FORM
RECON WATER HEATER INSTALLATION FORM Please complete ONE (1) form for each SITE and return to AERCO for warranty validation within 30 days of start-up. After completion, e-mail this form to: STARTUP@AERCO.COM.
More informationCommercial Gas Water Heaters
POWERED BURNER MODELS LARGE-VOLUME POWERED BURNER FEATURES The large-volume powered burner line includes the largest, most powerful A. O. Smith tanktype gas water heaters. With tank capacities up to 600
More informationCHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS
CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.
More informationBaxi Combi 80e & 105e
Baxi Combi 8e & 15e Please keep these instructions safe. Should you move house, please hand them over to the next occupier. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Natural
More informationNorth Dakota State Fire and Tornado Fund Providing affordable property insurance coverage for the state and its political subdivisions since 1919.
North Dakota State Fire and Tornado Fund Providing affordable property insurance coverage for the state and its political subdivisions since 1919. Contents Check the condition of the hydronic system fluid.
More informationTrouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
More informationHow to Prevent Liquid Damage Property Losses
1. The leading cause of property losses is from liquid damage. A review of Zurich North America claims data highlights the problem. 2. Water damage originates from a number of sources: Domestic water lines
More informationImportant Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
More informationD Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00
SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air
More informationYour safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
More informationPart of Certas Energy. Taking care of your home heating needs TEAM ENERGY
TEAM ENERGY Part of Certas Energy Taking care of your home heating needs Our Service Promise Team Energy is committed to delivering the highest standards of customer service and care. Our promise to you
More informationSERVICE SERVICE COMPACT MANUAL. Mod. 3000 92X Mod. 3000 93X Mod. 3000 94X. Part 2
SERVICE COMPACT SERVICE 000 MANUAL Mod. 000 9X Mod. 000 9X Mod. 000 94X Part Forward This Service Handbook is intended to assist with servicing and fault-finding in Caravans and Motor Caravans equipped
More informationProtect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement.
Protect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement. The benefits of a Home Service Agreement Provides peace of mind Regularly scheduled maintenance will keep
More informationFPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS
FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS To be used in conjunction with the Fire Protection Association Australia FPS4-2000: Agreement
More informationConsortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR BOILER SERVICING MAINTENANCE Maintenance Module 11 March 2012 issue This document has been compiled by the Engineering
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
More informationSECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
More informationALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationHigh efficiency, cast-iron gas boiler
SENTRY High efficiency, cast-iron gas boiler LOWER PROFILE MAKES PROBLEM INSTALLATIONS EASY SENTRY High efficiency, cast-iron gas boiler A smarter choice for informed The boiler you choose for your home
More informationOperating instructions
6300 9681 02/2006 GB For the user Operating instructions Logano GE315 Boiler for oil-/gas-fired pressure jet burners Please read thoroughly before use. Operating instructions Logano GE315 Dear Customer,
More informationELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
More informationReplacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS
Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The
More informationBorsodChem MCHZ, Czech Republic. 6,000 Nm 3 /h HTCR Topsøe Hydrogen Plant A Case Story: 18 Months from Engineering to Operation
6,000 Nm 3 /h HTCR Topsøe Hydrogen Plant 2 1. Introduction... 3 2. The BorsodChem MCHZ Company... 3 3. HTCR Process and Reformer Principle...4 4. Engineering of the BorsodChem MCHZ HTCR Plant... 6 5. Workshop
More informationSL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationCommercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationBradlee Boilers Ltd. Instruction Manual for starting up Bradlee Hire Boiler from Cold
Bradlee Boilers Ltd Instruction Manual for starting up Bradlee Hire Boiler from Cold To be read in conjunction with Bradlee Boiler guide to Commissioning Boilers Document Ref: HM001 1. Ensure that all
More informationSPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R8216470-01EN - Edition 01-26/10/2009
Instantaneous Gas Water Heaters Storage Gas Water Heaters SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model R8216470-01EN - Edition 01-26/10/2009 Boilers CUENOD Renewable 3121488 12 EAA1...... 3124527 25
More informationBoiler & Pressure Vessel Inspection discrepancies and failures
Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:
More informationFederal Wage System Job Grading Standard for Heating and Boiler Plant Equipment Mechanic, 5309. Table of Contents
Federal Wage System Job Grading Standard for Heating and Boiler Plant Equipment Mechanic, 5309 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 3 HELPER AND INTERMEDIATE
More informationSPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model. CELTIC RSc b CUENOD. R8202395-02EN - Edition 02-21/04/2005
CUENOD Instantaneous Gas Water Heaters Storage Gas Water Heaters SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model CELTIC RSc b R8202395-02EN - Edition 02-21/04/2005 Boilers Solar Panel 69214511 31 CELTIC
More informationINSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
More informationA. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.
DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly
More information! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
More informationBUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS
BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationAir Conditioner Water Heater Model ACWH18
Air Conditioner Water Heater Model ACWH18 Installation Guide IMPORTANT! READ THIS FIRST! Commissioning of this unit must be done by a licensed HVAC technician. Commissioning includes making the electrical
More informationMunchkin Heat Exchanger Maintenance
Munchkin Heat Exchanger Maintenance By: Mike Granahan *Refer to the appropriate boiler manual for your specific model number. Adjustment procedures will vary. Boiler shown below is an HTP Munchkin 80M
More informationOIL BURNERS LOW PRESSURE, DESIGNED FOR COMBUSTION OF LIGHT FUEL OIL, MEDIUM FUEL OIL-1P, WASTE OILS.
LOW PRESSURE OIL BURNERS CBW 50 CBW-150 OIL BURNERS LOW PRESSURE, DESIGNED FOR COMBUSTION OF LIGHT FUEL OIL, MEDIUM FUEL OIL-1P, WASTE OILS. CBW-50 CBW-150 40 100 kw 80 150 kw THIS TECHNICAL DOCUMENTATION
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More information36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
More informationNational Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
More informationBaxi Combi 130 HE. User s Operating Instructions. Gas Fired Wall Mounted Condensing Combination Boiler
User s Operating Instructions Baxi Combi 130 HE Gas Fired Wall Mounted Condensing Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.
More informationPreventing Overheated Boiler Incidents
Preventing Overheated Boiler Incidents PSE&G Appliance Service October 2012 Runaway Boiler Explosion Review Items Hazard Background Past Incidents PSE&G Emergency Response Future Process Improvements What
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
More informationUniversity of Iowa Main Power Plant 2008 Flood Preparations, Event, & Recovery
University of Iowa Main Power Plant 2008 Flood Preparations, Event, & Recovery Yellow Alert for Mayflower Residence hall Peak at 31.5 feet Power Plant floods from steam tunnel and shuts down 1993 Flood
More informationG26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
More informationThis will also provide you with the knowledge to insure long life for your Investment
CONDUIT PIPE DRYING This Presentation will guide you to why systems fail! This will also provide you with the knowledge to insure long life for your Investment Drainable and Dryable System Design Trough
More informationINSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER
INSTALLATION & MAINTENANCE MANUAL TURBOPOWER GAS, OIL & GAS/OIL WATER HEATER Installation and service must be performed by a qualified service installer, service agency or the gas supplier. Oil Gas/Oil
More informationCOMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
More informationG-704-0 SPECIFICATION: GAS METER AND REGULATOR INSTALLATION REQUIREMENTS. 3 and Gas Yellow Book. REVISIONS: (See ) 1/15/14 5 Years
LAST REVIEW DATE: REVIEW CYCLE: 1/15/14 5 Years SPECIFICATION: TITLE: VOLUME: G-704-0 3 and Gas Yellow Book REVISIONS: (See ) 1) This specification is being issued for the first time. G-704-0 Gas Operations
More informationStatement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary
Installation Service Statement of Work - 1 - Cooling Start-up Service Cooling Start-up Service Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details
More informationSECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
More informationREQUEST FOR QUOTATIONS
Metropolitan Washington Airports Authority Materials Management, MA-133 Terminal A, Room 278 Washington, DC 20001-4901 REQUEST FOR QUOTATIONS 1. FOR INFORMATION CONTACT NAME: Regina Leigh 2. REQUEST FOR
More informationA. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
More informationSafe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant
Safe management of industrial steam and hot water boilers A guide for owners, managers and supervisors of boilers, boiler houses and boiler plant Health and Safety Safe management of industrial steam and
More informationSecurity Systems Intrusion Alarm
Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted
More informationFIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
More informationCaution! Observe the safety instructions of this installation and maintenance manual before placing the boiler in operation. Danger!
Caution! Observe the safety instructions of this installation and maintenance manual before placing the boiler in operation. Danger! All installation, burner set-up and adjustment, and maintenance operations
More informationGUIDELINES FOR LOGBOOKS COMPLIANCE TO BOILER REGULATIONS N.J.A.C. 12:90
GUIDELINES FOR LOGBOOKS COMPLIANCE TO BOILER REGULATIONS N.J.A.C. 12:90 Department of Labor and Workforce Development Labor Standards & Safety Enforcement Division of Public Safety and Occupational Safety
More informationCalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
More informationSWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
More informationRheem Spare Parts Manual. Commercial gas model A631265 Exterior 265L
Commercial gas model A631265 Exterior 265L Commercial gas model A631265 Exterior 265L Item Part No. Description 1 221735 Foam cover 2 221914 Anode x 3 (black) 1153mm 2 221924 Anode x 3 (blue) 1153mm 3
More informationSeaward Products OWNER S MANUAL WATER HEATERS. Serial Number:
Seaward Products WATER HEATERS OWNER S MANUAL Serial Number: IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, basic safety precautions to reduce the risk of fire, electrical shock,
More informationConsortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR LAUNDRY EQUIPMENT MAINTENANCE Maintenance Module 32 March 2011 issue This document has been compiled by the Engineering
More informationGuide Specification SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY
SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. HVAC Commissioning description. 2. HVAC Commissioning responsibilities. 1.2 REFERENCES A. American Society
More informationAttachment J-C18.1. HVAC Work Instructions
. RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual
More information