Drives on submersible pumps? Yes you can

Size: px
Start display at page:

Download "Drives on submersible pumps? Yes you can"

Transcription

1 Drives on submersible pumps? Yes you can While variable-speed drives help save large amounts of energy in standard pump systems, they are less common in submersible pump applications, as it is more difficult to implement drives here. But with some advance planning, the difficulties can be overcome. It is well worth the effort, as many submersible pumps have long running hours of up to 8,000 hours per year. The potential energy savings and process improvements can be enormous. Variable-speed drives are common in standard pump applications these days and the installation rarely presents any problems. In submersible pump applications, however, the situation is a little different and users are often unsure about the measures necessary to achieve the longest lifetime of the system. There are many advantages of using drives in submersible pump applications. Variablespeed drives can offer great energy savings, often in the region of 30 to 50 percent, in applications where there is a need to vary the velocity, head or flow. This can be highly significant in applications with long running hours. Drives also offer improved process control. By matching pump output flow or pressure directly to the process requirements, small variations can be corrected more accurately than with other types of control. Drives can also help reduce stagnant water storage in pressurised systems. When using drives in submersible pump systems, there are however a few complications that users need to be aware of, but these can generally be overcome with some careful planning. For instance, motors in borehole pumps can have a motor cable as long as 100 metres and it is often necessary to fit output reactors or sine filters. These are quite effective at reducing the rate of voltage change (du/dt) and the peak motor voltage. Other potential problems include undesirable network distortion, which is possible if the drive uses a simple diode bridge. This can be avoided if low harmonic drives are used. High rates of voltage change can also lead to radio frequency interference, unless special care is taken at installation. The drive will generally require installation in a clean environment. Specialist advice should be sought on cable length, voltage spikes, motor insulation and other technical issues before installation. Reduced speed saves energy Using a variable-speed drive in systems running below maximum capacity saves energy, reduces maintenance and also avoids the problems associated with impeller trim. Impeller trim may seem equivalent to varying the speed and most pump manufacturers accept a 15 percent impeller trim, however excessive trims change the hydraulic condition within the pump. This can lead to reduction in efficiency and instability in operation. When using a drive and running the motor at low speed in systems with a high static head, users have to be careful not to move too close to the shut-off point, as this risks stopping the flow through the pump. This may typically happen to pumps that pump out of a tank which has a variable input. It may be tempting to implement the very simple control philosophy of maintaining a fixed level in the tank, but this will only work if the inflow meets the minimum flow requirements of the pump. If the inflow does not meet the minimum flow requirement, the pump could be severely damaged. The way around this problem is to determine the minimum acceptable running speed of the pump and to use this as the minimum speed setting for the drive. In some applications, reduced speed can also cause particles to come out of suspension and cause problems.

2 Smooth starting and stopping Drives are ideal for soft starting and stopping of pumps and because they are able to provide torque to and from zero speed, they can be used to control the fluid avoiding surges and run back. However, it is necessary to check the limits for both the pump and the motor. At speeds above the nominal speed, the torque available will drop as the drive cannot increase its output voltage beyond the input voltage. The motor then becomes progressively under-fluxed. This is known as field weakening and it does not necessarily restrict the ability to run at over-speed, but it needs to be considered. There will be a change in the noise from both the pump and the motor as the speed is changed. With higher speed, greater noise and potentially greater vibration will occur. If the pump is handling liquid containing abrasive particles, an increase in flow will result in increased abrasion and wear. With higher speed, it is necessary to ensure that the net positive suction head available at the pump is still sufficient to prevent cavitation. Control of fouling and solids Many submersible pumps are used for waste and a drive can be used to provide automatic de-ragging and solids deposition in the outgoing pipework. Avoiding critical speeds and vibration The risk of the pump or motor reaching a critical speed increases when using a variable speed drive. When running at fixed speed, the chance of the fixed speed coinciding with a critical speed is fairly small. But when the speed varies across a wide range, this likelihood increases dramatically. Lateral critical speeds occur when running speed excitation coincides with one of the rotor s lateral natural frequencies. This can be remedied by programming the drive to lock out certain speeds or speed ranges from the continuous operating speed range. It can also be achieved by detuning the excitation frequency, or by reducing excitation levels by improving balance and alignment. Submersible motors in installations without rigid fixing to a base plate or foundation (e.g. duck foot bend or pipe shaft) may have a higher vibration level. This is also the case for deep well motors, where the absence of a rigid fixing leads to a higher vibration level. Dimension according to motor plate data A variable-speed drive is a source of current and must always be selected on the basis of the motor name plate current. Where a catalogue gives kw ratings, these are always on the basis of typical values for conventional motors of four pole or six pole speed; these should be ignored for the purposes of submersible pumps. The kw rating of a motor is the power that is delivered at the motor shaft and not the power delivered to the motor terminals. The kw ratings allocated are based on conventional four or six pole TEFC motors, while submersible pumps often have motors with non-standard ratings. Drives need better motor insulation Using a variable-speed drive enables gentle starting of the pump system, potentially extending the life of the motor. However, it is important that the motor is suitable for variablespeed drive operation. Variable speed operation puts a higher voltage stress on the motor insulation system and it is recommended to have either reinforced insulation system or a filter between the motor and the drive. The rating of the motor insulation is of little help in this context. Motor insulation is generally only defined by the thermal capability, i.e. class B, Class F or Class H. These classes do not define the electrical capabilities of the insulation system. The manufacturer s advice has to be sought on whether the motor is suitable for variable speed drive operation.

3 Automatic EMC shield Good practice installation technique involves ensuring the lowest possible impedance path on the shield connection to ground. In submersible motors, this principle is implemented automatically as the water around the housing provides a perfect EMC shield and equalizes the electric potential of all metal construction elements. The drive is installed as a piece of wall or floor mounted equipment, with a continuous cable running to the motor, allowing the Faraday Cage to be readily completed. Generally, the cable length is greater than in conventional installations due to the distance between pump and cabinet. To reduce the distance, the drive should be installed as close to the well head as possible. Unscreened cable should be used as down-hole cable, although this can pose a problem in relation to sensors. However, this can normally be overcome by using a an appropriate filter and having the sensor cables moved as far from the drop cable as possible, putting these cables into steel pilot tubes and using a good screen on the sensors. Where long cable runs are involved, it is necessary to consider the drive s filtering capabilities. Manufacturers recommend specific conducted emissions filters, based on tests with maximum lengths of cables. Longer cables will reduce the performance of the filter. Two basic forms of output filtering can be utilised; du/dt filters will reduce the rate of change of the voltage pulses and this will reduce the effects of long cables, although there will still be a finite limit. Sinus (or sinusoidal) filters are designed to produce a completely sinusoidal waveform, which has no distance limitation. Remote monitoring It is difficult to get access to submersible pump motors once they have been installed and inspection may not be possible. The motors are often equipped with sensors to enable remote condition monitoring, which must operate without disturbance from the drive. Monitoring of motor winding temperatures is particularly important, as ageing and lifetime are closely related to temperature. Operating at 10 C above the thermal class temperature will halve the winding lifetime. Sensors that are robust in relation to electro-magnetic interference are PTC temperature sensors; thermal contact temperature sensors (bi-metal); and float switches with mechanical contacts. In general, these sensors do not need separate screened sensor cables. Even combined power and control cables are possible for small drive systems. Critical sensors which need some attention include all conductivity electrodes and Pt 100 RTD thermometers. These sensors always need a separate control cable. Special monitoring relays with electronic filters may be necessary to suppress nuisance tripping. Combined power and sensor cables are not possible. Vibration sensors can be problematic to use in a variable-speed drive installation. These sensors need a separate screened control cable for themselves, as well as screened power cables. Special digital filters may be needed to eliminate high harmonics from the drive. Generator supply in critical applications Many borehole pumps are used in rural areas or in applications where reliability of the supply is of high importance, and are fed by generators either permanently or as a backup. Special care must be taken in this case. Maximum allowable voltage dip at starting and continuous run must be specified by the drive manufacturer. It is also necessary to keep an eye on the harmonic content, as generators might be an additional source of, or be susceptible to, harmonics. The presence of harmonics must also be considered when dimensioning feeder cables.

4 Generator frequency may not be of great importance since the input voltage waveform is rectified to obtain an approximately constant DC voltage source. These are the main factors to take into consideration installing a submersible pump system with variable speed drives, but it is wise to always consult the drive and motor manufacturers when planning an installation. Considering the long running hours that many submersible pump systems have, installing a variable-speed drive is normally an effort that is well worth making. Geoff Brown, Consultant Drives & Motors, ABB Limited Tel: ; Fax: energy@gb.abb.com; Web: Caption: Variable-speed drives are common in standard pump applications Caption: For automatic EMC shield good installation practice the drive is installed as close to the well head as possible

5 Caption: ABB drives installed in remote locations can be remotely accessed for monitoring early warning notification and easy reporting

Specifying a Variable Frequency Drive s

Specifying a Variable Frequency Drive s Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable

More information

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Variable Frequency Drives - a Comparison of VSI versus LCI Systems Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been

More information

The Company. QUALITY WHICH REDUCES PUMPING COSTS For over 45 years, PAPANTONATOS S.A. has focused on the customer s design,

The Company. QUALITY WHICH REDUCES PUMPING COSTS For over 45 years, PAPANTONATOS S.A. has focused on the customer s design, The Company QUALITY WHICH REDUCES PUMPING COSTS For over 45 years, PAPANTONATOS S.A. has focused on the customer s design, manufacturing and service needs in the field of submersible pumps. Our engineering

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

PI734D - Technical Data Sheet

PI734D - Technical Data Sheet PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

PI734B - Technical Data Sheet

PI734B - Technical Data Sheet PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international

More information

Solving VFD-sourced Bearing Current Problems in AC Motors.

Solving VFD-sourced Bearing Current Problems in AC Motors. Solving VFD-sourced Bearing Current Problems in AC Motors. The 2 main sources of motor shaft voltage are: 1. Asymmetric Motor construction The stator and rotor magnetic circuits within the motor itself

More information

Principles of Adjustable Frequency Drives

Principles of Adjustable Frequency Drives What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Drives and motors. A guide to using variable-speed drives and motors in car parks

Drives and motors. A guide to using variable-speed drives and motors in car parks Drives and motors A guide to using variable-speed drives and motors in car parks Helping car parks meet the energy and CO 2 reduction challenge In the UK, as population density increases and space becomes

More information

vacon ac drives for mining & minerals

vacon ac drives for mining & minerals vacon ac drives for mining & minerals 1 strong experience in mining & minerals Vacon AC drives are robust to handle your most demanding requirements from simple ventilation to the most complex load sharing

More information

N-PUMP SERIES FOR MAXIMUM RELIABILITY AND EFFICIENCY IN WASTEWATER HANDLING. Flygt

N-PUMP SERIES FOR MAXIMUM RELIABILITY AND EFFICIENCY IN WASTEWATER HANDLING. Flygt N-PUMP SERIES FOR MAXIMUM RELIABILITY AND EFFICIENCY IN WASTEWATER HANDLING Flygt The Concept N-Pump series. Bringing NEW levels of efficiency to wastewater handling applications Reduced pumping efficiency,

More information

understanding medium frequency induction melting furnace and its components

understanding medium frequency induction melting furnace and its components understanding medium frequency induction melting furnace and its components 9 Spruce Street, Jersey City, NJ 07306 USA sales@electroheatinduction.com INDUCTION MELTING FURNACE AND ITS COMPONENTS The purpose

More information

No compromise. Highest total efficiency wastewater pumping. grundfos se & sl ranges Submersible and dry-installed wastewater pumps

No compromise. Highest total efficiency wastewater pumping. grundfos se & sl ranges Submersible and dry-installed wastewater pumps grundfos se & sl ranges Submersible and dry-installed wastewater pumps 0.9-30 kw 2, 4, 6 pole 50Hz No compromise Highest total efficiency wastewater pumping ULTIMATE WASTEWATER PUMPING TECHNOLOGY The renewed

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to: OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND

More information

ABB drives. Technical guide No. 4 Guide to variable speed drives

ABB drives. Technical guide No. 4 Guide to variable speed drives ABB drives Technical guide No. 4 Guide to variable speed drives 2 Guide to variable speed drives Technical guide No. 4 Technical guide No. 4 Guide to variable speed drives Copyright 2011 ABB. All rights

More information

PART 1 - INTRODUCTION...

PART 1 - INTRODUCTION... Table of Contents PART 1 - INTRODUCTION... 3 1.1 General... 3 1.2 Sensor Features... 3 1.3 Sensor Specifications (CDE-45P)... 4 Figure 1-1 CDE-45P Sensor Dimensions (standard, convertible style)... 4 PART

More information

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw ,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted

More information

Flygt N-Pumps 3085, 3102 & 3127. For reliable and efficient wastewater handling

Flygt N-Pumps 3085, 3102 & 3127. For reliable and efficient wastewater handling Flygt N-Pumps 3085, 3102 & 3127 For reliable and efficient wastewater handling The Concept Flygt N-Pump series Reduced pumping efficiency, high energy and maintenance costs shouldn t be a fact of life

More information

AC-Synchronous Generator

AC-Synchronous Generator Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to

More information

WIND TURBINE TECHNOLOGY

WIND TURBINE TECHNOLOGY Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems

More information

FREQUENCY CONTROLLED AC MOTOR DRIVE

FREQUENCY CONTROLLED AC MOTOR DRIVE FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly

More information

CRN32-2-2 A-F-G-E-HQQE 3x400D 50 HZ

CRN32-2-2 A-F-G-E-HQQE 3x400D 50 HZ GRUNDFOS DATA BOOKLET CRN32-2-2 A-F-G-E-HQQE 3x4D 5 HZ Grundfos Pump 96122352 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn32/96122352/crn-32-2-2-a-f-g-e-hqqe.html

More information

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw DLW 8 POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw Generator set consisting of engine and alternator mounted on a fabricated steel

More information

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an

More information

Series 6000 Torque measured metal bellow coupling

Series 6000 Torque measured metal bellow coupling Properties Free of float metal bellow coupling with integrated torque measurement Non-contact measurement system, high robustness High torsional stiffness Limited torque of inertia Performance Measurement

More information

Pump Maintenance - Repair

Pump Maintenance - Repair Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.

More information

PM734F - Technical Data Sheet Winding 28

PM734F - Technical Data Sheet Winding 28 - Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including

More information

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM NO-BREAK KS 7e Concentrated Energy e 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM Data Centre owners, operators and designers are required to meet ever increasing and

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

1 WATERFLUX - Comparisonon COO 2010-08-17. Rectangular Magmeter in water applications

1 WATERFLUX - Comparisonon COO 2010-08-17. Rectangular Magmeter in water applications 1 WATERFLUX - Comparisonon COO 2010-08-17 Rectangular Magmeter in water applications Jef Neven KROHNE WATERMETERS $3000 EMF Price C&I (mechanical) water meters Residential water meters $30 Water Metering

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 1 HYDRAULIC PUMPS The material needed for outcome 2 is very extensive so there

More information

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.

More information

Fundamentals of Inverter Fed Motors

Fundamentals of Inverter Fed Motors Fundamentals of Inverter Fed Motors Technical Manual 10/02 MN780 Contents Page The Growing Use Of Inverters.................................................................. 1 How Inverters Affect Motors....................................................................

More information

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

HCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards

More information

DC/DC power modules basics

DC/DC power modules basics DC/DC power modules basics Design Note 024 Ericsson Power Modules General Abstract This design note covers basic considerations for the use of on-board switch mode DC/DC power modules, also commonly known

More information

Single-Phase AC Synchronous Generator

Single-Phase AC Synchronous Generator ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description

More information

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS

More information

Drives and motors. A guide to using variable-speed drives and motors in data centres

Drives and motors. A guide to using variable-speed drives and motors in data centres Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

Troubleshooting accelerometer installations

Troubleshooting accelerometer installations Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.

More information

Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic energy).

Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic energy). HYDRAULIC MACHINES Used to convert between hydraulic and mechanical energies. Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic

More information

Mechanical shaft seal types and sealing systems

Mechanical shaft seal types and sealing systems Chapter 2 Mechanical shaft seal types and sealing systems 1. Mechanical shaft seal types 2. Sealing systems 3. Selecting a mechanical shaft seal Mechanical shaft seal types and sealing systems 1. Mechanical

More information

13 common causes of motor failure

13 common causes of motor failure 13 common causes of motor failure Application Note What to look for and how to improve asset uptime Motors are used everywhere in industrial environments and they are becoming increasingly complex and

More information

Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com

Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com 13 Aberdeen Way Elgin, SC 29045 Cell (803) 427-0791 VFD Fundamentals & Troubleshooting 19-Feb-2010 By: Timothy S. Irwin, P.E. Sr. Engineer tsi@mbesi.com Rotating Machinery Diagnostics & Instrumentation

More information

4" SUBMERSIBLE PUMPS

4 SUBMERSIBLE PUMPS 4" SUBMERSIBLE PUMPS 4" SUBMERSIBLE PUMPS 50/60 HZ Multi-stage centrifugal submersible pumps for clean water in 4" wells. The 4" VSP pump series is carefully designed and manufactured for maximum resistant

More information

Alternative Linear Motion Systems. Iron Core Linear Motors

Alternative Linear Motion Systems. Iron Core Linear Motors Alternative Linear Motion Systems ME EN 7960 Precision Machine Design Topic 5 ME EN 7960 Precision Machine Design Alternative Linear Motion Systems 5-1 Iron Core Linear Motors Provide actuation forces

More information

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before

More information

Mounting Instructions. Torque Transducer. A0329 3.2 en

Mounting Instructions. Torque Transducer. A0329 3.2 en Mounting Instructions Torque Transducer T5 T5 Contents 3 Page Safety instructions.............................................. 4 1 Measuring characteristics..................................... 7 2 Mounting.....................................................

More information

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Cable Solutions for Servo and Variable Frequency Drives (VFD) Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect

More information

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS PI144K - Winding 311 Technical Data Sheet PI144K SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section

More information

AC Electric Motors best practice

AC Electric Motors best practice If you want to learn more about best practice machinery maintenance, or world class mechanical equipment maintenance and installation practices, follow the link to our Online Store and see the Training

More information

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet PI044E - Winding 311 Technical Data Sheet PI044E SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards

More information

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com hott@ieee.org Page 2 THE BASIC

More information

*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS

*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS *ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS Jay Vaidya, President Electrodynamics Associates, Inc. 409 Eastbridge Drive, Oviedo, FL 32765 and Earl Gregory,

More information

Hydraulic Control Solutions

Hydraulic Control Solutions Hydraulic Control Solutions Vexve s Hydrox hydraulic control solutions are suitable for even the most challenging installation sites and conditions. Specifically designed for district heating and district

More information

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka S S B Udugampala, V Vijayarajah, N T L W Vithanawasam, W M S C Weerasinghe, Supervised by: Eng J Karunanayake, Dr. K T M U Hemapala

More information

Diode Applications. by Kenneth A. Kuhn Sept. 1, 2008. This note illustrates some common applications of diodes.

Diode Applications. by Kenneth A. Kuhn Sept. 1, 2008. This note illustrates some common applications of diodes. by Kenneth A. Kuhn Sept. 1, 2008 This note illustrates some common applications of diodes. Power supply applications A common application for diodes is converting AC to DC. Although half-wave rectification

More information

Yamaha Power Amplifier. White Paper

Yamaha Power Amplifier. White Paper Yamaha Power Amplifier White Paper August 2008 Table of Contents 1. About EEEngine...2 1.1. Introduction...2 1.2. Explanation of different amplifier topologies...2 2. Yamaha technology...5 2.1. Dual mono-amplifier

More information

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

Offshore Platform Powered With New Electrical Motor Drive System

Offshore Platform Powered With New Electrical Motor Drive System Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy

More information

GenTech Practice Questions

GenTech Practice Questions GenTech Practice Questions Basic Electronics Test: This test will assess your knowledge of and ability to apply the principles of Basic Electronics. This test is comprised of 90 questions in the following

More information

ATL Fuel Level Sender Probes

ATL Fuel Level Sender Probes T E C H N I C A L S P E C I F I C A T I O N The ATL EL-AD-151 (Resistance Output) and EL-AD-152 (Voltage Output) Fuel Level Senders are highly advanced sensors for continuously measuring the contents of

More information

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008 CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand

More information

Sigma Frequency Control

Sigma Frequency Control Sigma Frequency Control SFC Series 18 to 515 Capacities: from 22 to 3069 cfm Pressures: from 80 to 217 psig Variable Speed Technology from Kaeser Most compressed air systems have varying loads and it is

More information

D.C. Motors. Products and specifications subject to change without notice.

D.C. Motors. Products and specifications subject to change without notice. D.C. Motors Order/Technical Support - Tel: (8) 677-5 / FAX: (8) 677-865 / www.crouzet-usa.com / DC Motors Selection guide Gearbox Speed Torque max (Nm).5. Type of Gearbox 8 8 8. Power usable (w) Torque

More information

Instruction manual of pumps WQ, WQF, SN, Furiatka, Furia, KRAKEN, BIG, IP, IPE, SWQ, CTR

Instruction manual of pumps WQ, WQF, SN, Furiatka, Furia, KRAKEN, BIG, IP, IPE, SWQ, CTR CAUTION! Instruction manual of pumps WQ, WQF, SN, Furiatka, Furia, KRAKEN, BIG, IP, IPE, SWQ, CTR NOTE: read the manual prior to commencement of use. For safety reasons, the pump can only be operated by

More information

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor International Journal of Engineering Inventions e-issn: 78-7461, p-issn: 319-6491 Volume 3, Issue 5 (December 013) PP: 36-41 Modelling, Simulation and Performance Analysis of A Variable Frequency Drive

More information

UCI274C - Technical Data Sheet

UCI274C - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

HVAC Applications. VFD considerations for HVAC systems...

HVAC Applications. VFD considerations for HVAC systems... HVAC Applications VFD considerations for HVAC systems... 1 COMMON TERMINOLOGY VFD (VARIABLE FREQUENCY DRIVES) AFC (ADJUSTABLE FREQ. CONTOLLER) ASD (ADJUSTABLE SPEED DRIVES) VSD (VARIABLE SPEED DRIVES)

More information

UCI274H - Technical Data Sheet

UCI274H - Technical Data Sheet - Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,

More information

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A Technical Data Manual Model Nos. and pricing: see Price List Vacuum tube collector based on the heat pipe principle For the utilisation of solar energy VITOSOL r 200-T SP2A Product may not be exactly as

More information

Motor Fundamentals. DC Motor

Motor Fundamentals. DC Motor Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical

More information

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE. SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION

More information

Introduction. Harmonics and IEEE 519 Page 1 of 19

Introduction. Harmonics and IEEE 519 Page 1 of 19 Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

IFC 070 Technical Datasheet

IFC 070 Technical Datasheet IFC 070 Technical Datasheet Electromagnetic signal converter Battery driven with low energy consumption Quick and easy to install and operate External data logger and GSM module for remote data transfer

More information

32/1/2013-14/PVSE(Part-II) Ministry of New and Renewable Energy SPV Off Grid Division

32/1/2013-14/PVSE(Part-II) Ministry of New and Renewable Energy SPV Off Grid Division Annexure-A 32/1/2013-14/PVSE(Part-II) Ministry of New and Renewable Energy SPV Off Grid Division Scheme: Installation of 10,000 nos. of solar photovoltaic water pumping systems for irrigation purpose implemented

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

Turbo generators Best quality for thermal power plants

Turbo generators Best quality for thermal power plants Turbo generators Best quality for thermal power plants www.andritz.com ANDRITZ HYDRO Turbo generators International technology Group ANDRITZ is a globally leading supplier of plants, equipment, and services

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

White Paper Mervin Savostianik P. Eng. Littelfuse, Inc.

White Paper Mervin Savostianik P. Eng. Littelfuse, Inc. Ground-Fault Protection with VFDs How to use a Sensitive Relay to Find Hard-to-Spot Ground Faults in VFDs on Resistance-Grounded Systems White Paper Mervin Savostianik P. Eng. Littelfuse, Inc. How to Use

More information

12. Inspection and Maintenance

12. Inspection and Maintenance 12. and Maintenance Mandatory Be sure to inspect the inverter regularly and periodically to prevent it from breaking down because of the environment of use, such as temperature, humidity, dust and vibration,

More information

Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.

Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product. COOLING FAN REQUIREMENTS CALCULATIONS Determining System Impedance Determining the actual airflow produced by a fan mounted in an enclosure is much more difficult than calculating the airflow required.

More information

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT

More information

BSM MOTOR DRIVEN CENTRIFUGAL PUMPS

BSM MOTOR DRIVEN CENTRIFUGAL PUMPS PRINCIPLE OF OPERATION A hydraulically and dynamically balanced impeller with raised vane sections discharges liquid as a result of the centrifugal force developed in rotation. The head developed is entirely

More information

Subminiature Load Cell Model 8417

Subminiature Load Cell Model 8417 w Technical Product Information Subminiature Load Cell 1. Introduction... 2 2. Preparing for use... 2 2.1 Unpacking... 2 2.2 Using the instrument for the first time... 2 2.3 Grounding and potential connection...

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

Installation and instruction manual for Laing DDC pumps

Installation and instruction manual for Laing DDC pumps Installation and instruction manual for Laing DDC pumps Application The Laing DDC series pumps are primarily used for the circulation of cooling liquid in liquid cooled computers. Construction - The Laing

More information

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw ,QGXVWULDO#*HQHUDWRU 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw Generator set consisting of engine and alternator mounted

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

Maxi Pressurisation Units (Maxi, Maxi Plus & HP)

Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Installation and Maintenance Instructions Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5

More information

HIGH REPEATABILITY, BROADBAND TO-5 RELAYS DPDT

HIGH REPEATABILITY, BROADBAND TO-5 RELAYS DPDT HIGH REPEATABILITY, BROADBAND TO-5 RELAYS DPDT SERIES RF00 RF00D RF00DD RF0 RF0D RF0DD RELAY TYPE Repeatable, RF relay Repeatable, RF relay with internal diode for coil transient suppression Repeatable,

More information