SECTION DUCTWORK INSULATION. A. Shop drawing and submittal data in accordance with Section and Division 1.

Size: px
Start display at page:

Download "SECTION DUCTWORK INSULATION. A. Shop drawing and submittal data in accordance with Section and Division 1."

Transcription

1 SECTION DUCTWORK INSULATION PART 1 GENERAL 1.01 DESCRIPTION: A. Section Includes: 1. Duct thermal insulation. 2. Duct acoustic liner SUBMITTALS A. Shop drawing and submittal data in accordance with Section and Division QUALITY ASSURANCE A. Supply all products new, free from defects and listed by Underwriters' Laboratories, Inc. or bearing its label. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Insulation - Fiber Glass: 1. Certain-Teed Corp. 2. Owens-Corning Fiberglass Corp. 3. Schuller. B. Prefabricated Fiberglass Ducts: 1. Casco Air Duct. 2. Schuller. C. Adhesives: 1. Foster Products Div., H.B. Fuller Co. 2. Insul-Coustic/Birma Corp. 3. Childers Products Co. 4. Goodyear Tire and Rubber Co. D. Mechanical Fasteners: 1. AGM Industries, Inc. 2. Miracle Adhesives Corp. 3. Grip-Nail November 13, 1998

2 2.02 GENERAL A. All insulation materials, including jackets, facings, adhesives, coatings, and accessories are to be fire hazard rated and listed by Underwriters' Laboratories, Inc., using Steiner Tunnel Test Method for Fire Hazard Classification of Building Materials, Standard UL 723 ASTM E-84, NFPA-255, ASA A Flamespread: maximum Fuel contributed and smoke developed: maximum Flameproofing treatments subject to deterioration from moisture of humidity, are not acceptable. 4. Erosion resistance per U.L B. Type as noted, for services listed. C. Adhesives and sealants: 1. UL listed or classified. 2. Type 1 per Adhesive and Sealant Council Standard ASC-A D. Mechanical Fasteners. 1. Either of following types acceptable. 2. Comply with SMACNA Mechanical Fasteners Standard, unless otherwise noted. 3. Adhesive type: a. Perforated galvanized steel base. b. 12 gauge spindle. c. AGM Industries TACTOO Insul-Hangers or equal. d. Adhesive similar to Goodyear Plio-Nail. 4. Pins secured mechanically to metal duct: Gripnail or equal. 5. Insulation washers: a. Galvanized steel. b. 1-1/2 in. diameter. c. AGM Industries SLW-l or equal. 6. Not acceptable: 2.03 DUCT INSULATION a. Welded pins. b. Self-adhering anchors. c. Pins penetrating sheet metal ductwork. A. Duct Wrap Without Vapor Barrier; Type DW: 1. Flexible fiberglass wrap. 2. Density: a. 3/4 lb./cu.ft.; K=0.28 maximum. b. 1.5 lb/cu.ft.; K= November 13, 1998

3 3. Installed R-value: 4.3 hr.-sq.ft.- o F/BTU. 4. Thickness per Duct Insulation Application Schedule. 5. Manville Microlite Unfaced Duct Wrap or equal. B. Duct Wrap With Vapor Barier; Type DW-V: 1. Flexible fiberglass wrap. 3/4 lb. per cu.ft. 2. Installed R-value: 4.2 hr.-sq.ft.- o F/BTU. 3. Compressed conductance: 0.28 BTU/sq.ft./in./deg F. 4. Thickness per Duct Insulation Application Schedule. 5. Factory applied jacket. a. Foil-scrim-kraft laminate. 1) Aluminum foil facing. 2) Glass scrim reinforcing. 3) Kraft paper backing. b. Maximum vapor permeance: 0.02 perms. c. One 2 in. flange. 6. Manville Type 75 Faced Duct-Wrap or equal. C. Duct Board Without Vapor Barrier; Type DB: 1. Rigid board, 3 lb. per cu.ft. 2. Installed conductance: 0.23 BTU/hr/sq.ft./in./deg F. 3. Thickness per Duct Insulation Application Schedule. 4. Manville 800 Series or equal. D. Duct Board With Vapor Barrier; Type DB-V: 1. Rigid board, 3 lb. per cu.ft. 2. Installed conductance: 0.23 BTU/hr/sq.ft./in./deg F. 3. Thickness per Duct Insulation Application Schedule. 4. Factory applied jacket: a. Foil-scrim-kraft laminate: 1) Aluminum foil facing. 2) Glass scrim reinforcing. 3) Kraft paper backing. b. Maximum vapor permeance: 0.02 perms. c. One 2-in. flange. 5. Certainteed Ultraduct EI 800 or equal DUCT LINING A. Rectangular Duct Lining, Type AL: November 13, 1998

4 1. Rigid fiberglass duct liner board. a. Installed conductance: 0.24 maximum BTU/hr./sq.ft./in./deg F. b. Minimum Noise Reduction Coefficient (NRC) of c. Schuller Permacote R-300 Duct Liner Board or equal. 2. Flexible fiberglass duct liner, ASTM C a. Installed conductance: 0.28 maximum BTU/hr/sq.ft./in./deg F. b. NRC of 0.60 minimum. 3. Thickness per Duct Installation Application Schedule. 4. NFPA-90A coating on side facing air stream shall have a water or acrylic base. 5. Minimum noise reduction coefficient: 0.60 per in. thickness. 6. Manville Permacote Linacoustic 1" high performance plenum liner or equal. B. Circular Duct Lining: Type AL: 1. Prefabricated fiberglass circular duct: a. l in. thick. b. Without outer jacket. c. Class 1 Air Duct per UL Standard Schuller Rigid Round or equal. C. Minimum sound-absorption coefficient (ASTM C423 Type A mounting) for sound-absorbing duct (AL) and plenum (PL) lining material: Octave Band Center Frequency, Hz " thickness lining pcf density 1.5" thickness lining pcf density 2" thickness lining pcf density November 13, 1998

5 PART 3 EXECUTION 3.01 DUCT INSULATION SCHEDULE A. Notes for Insulation Schedule. Note 1. Schedule Symbols: 1.5-DW-V. 1.5 = Installed thickness in inches. DW = Duct wrap: See PART 2 PRODUCTS V = Vapor barrier. Note 2. Within 25 ft., or 10 x dia. of fan inlet and outlet, whichever is greater. a. Supply fans or units. b. Return fan or units. c. All exhaust fans unless specifically excluded. Note 3. Note 4. Necks longer than 24 in. Where duct lining is specified, no other insulation needed if required maximum conductance results. a. If maximum conductance cannot be obtained by lining alone; apply additional wrap or lining to give total conductance equal to maximum allowable. Note 5. Provide facing for all duct wrap on ducts exposed in air plenums, if not otherwise called for. B. Duct Insulation Type and Thickness Schedule: ITEM SUPPLY RETURN OUTSIDE AIR EXHAUST AIR In Elevator Machine Room 1-AL 1-AL -- Out-of-Doors 1-AL 1-AL -- Concealed between roof and ceiling Concealed in ceilings and walls At fan inlet Note DW-V 1.5-DW-V 1.5-DW-V 1.5-DW-V DW-V -- 1-AL 1-AL At fan outlet Note 2 1-AL -- 1-AL Air transfer ducts -- 1-AL November 13, 1998

6 ITEM SUPPLY RETURN OUTSIDE AIR EXHAUST AIR Extended diffuser necks, concealed Note DW-V Flexible ducts, Unlined 1.5-DW-V INSTALLATION A. General: 1. Ensure that insulation is continuous through interior non-fire rated walls. 2. For insulated ducts passing through interior fire-rated walls: a. Pack around ducts with fire proof, self-supporting insulation material, properly sealed. b. Seal insulation on both sides of rated wall to fire proof packing. 3. Finish insulation neatly at hangers, supports and other protrusions. 4. Locate insulation joints or cover seams in least visible locations. 5. Where ducts run in groups too close to be individually insulated and finished: a. Completely fill all spaces between ducts with rigid or flexible insulating material. b. Insulate and finish exterior surfaces of group as specified for particular service. 6. Where ducts cannot be insulated after erection, insulate prior to installation. 7. Where specified thickness of insulation exceeds available thickness in single layer, provide insulation in 2 or more layers with joints staggered. 8. Preparation: a. Do not install covering before ductwork and equipment has been tested and approved. b. Ensure surface is clean and dry prior to installation. c. Ensure insulation is dry before and during application. 9. Mechanical fasteners: a. Adhered anchors. b. Clip off pin penetrations flush with insulation surface or facing. c. Seal pins and washers where pins penetrate vapor barriers: 1) With 4 in. square pieces of vapor barrier material to match facing. 2) Adhere with vaporseal adhesive. d. Spacing on rectangular ducts: 1) Typical of horizontal and vertical, unless otherwise specified. 2) Duct board: a) 3 in. in from edges November 13, 1998

7 b) Intermediate fasteners: ½ in. on counter maximum spacing all directions. c) Not less than one pin per surface. 3) Duct wrap: de Dimension Maximum Spacing 24 in. and under None required. 25 to 32 in. Horizontal - none. Vertical: 1 row centered, 12 in. on center. 33 to 48 in. 2 rows, 12 in. on center. 49 to 60 in. 3 rows, 12 in. on center. 61 in. and over 16 in. on center, all directions. 4) Duct wrap spacing applicable to flat surfaces of flat oval ducts. 10. Provide 24 gauge sheet metal Z section frames over edges of duct and plenum lining: a. At access openings and doors. b. Along edges exposed to air flow. B. Rectangular Duct Wrap: 1. With Vapor Barrier: C. Round Duct Wrap: a. Vapor barrier and sealing continuous without breaks, including around supports and bracing. b. 2 in. lap strip at one end. c. Peel insulation for 2 in. lap strip along longitudinal joints. d. Seal lap strips with vaporseal adhesive, Foster's or equal. e. Adhesive sealing not required in heating, return or exhaust air services. 1. General: a. Adhere flexible insulation to ductwork with adhesive applied in 6 in. wide strips on 16 in. centers. b. Provide 16 gauge annealed tie wire tied, spiral wound or half hitched at 16 in. centers. c. Butt insulation and seal joints and breaks with 2 in. lap of foil adhered over joint. 2. Apply duct wrap with vapor barrier as specified above for rectangular ducts. D. Duct Board: 1. Comply with published recommendations of manufacturer and with following: November 13, 1998

8 a. Secure with 4 in. strips of adhesive, 8 in. on center. b. Secure on top, sides and bottom of duct with mechanical fasteners, spacing as scheduled. E. Rectangular Duct Lining: 1. Comply with SMACNA Duct Liner Application Standard, published recommendations of manufacturer, and following: 2. Apply adhesive over 100% of surfaces to be lined. 3. Surface adjacent to air flow, including at joints, to be uniformly flat. 4. Seal butt joints and exposed edges of liner to prevent erosion. 5. Mechanical fasteners: Spacing per SMACNA Duct Liner Application Standard. 6. Internal acoustical lining may be substituted at contractor's option where (external) thermal insulation wrapping is specified. 7. Install internal acoustical lining as scheduled in 3.01 for all supply air and return air ductwork. F. Round duct lining: 1. Insert pre-fabricated circular fiberglass lining. a. Include tees and fittings. b. Segmental lining in elbows. 2. In ducts larger than maximum size of pre-fabricated lining install flexible lining as specified hereinbefore. a. Score lining at 4 in. maximum. END OF SECTION D:\Drawings\Office org1\spec\m\sss01m29.wpd November 13, 1998

SECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.

SECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010. SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall

More information

Fiberglas, Exterior Wall Thermal Insulation

Fiberglas, Exterior Wall Thermal Insulation PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

Fire Barrier Duct Wrap 15A

Fire Barrier Duct Wrap 15A 3 Fire Barrier Duct Wrap 15A Commerical Kitchen Grease Duct Fire Protection System Product Data and Installation Instructions Compliance 1998 Edition Complies with International Mechanical Code Complies

More information

B. Types of mechanical insulation specified in this section include the following:

B. Types of mechanical insulation specified in this section include the following: SECTION 23 0700 HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Extent of mechanical insulation required by this section is indicated on drawings and schedules, and by requirements of this section. B.

More information

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

EcoTouch Insulation with PureFiber Technology

EcoTouch Insulation with PureFiber Technology PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

SECTION 07 21 16 - PRE-ENGINEERED BUILDING BLANKET INSULATION

SECTION 07 21 16 - PRE-ENGINEERED BUILDING BLANKET INSULATION PROJECT ARCHITECT RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION

DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

FINAL December 2012 SECTION 233100 DUCTWORK

FINAL December 2012 SECTION 233100 DUCTWORK SECTION 233100 DUCTWORK 1.0 Acoustical duct lining in any part of the duct system is prohibited. All ductwork requiring insula tion shall be externally insulated (Refer to the Sheet Metal Ductwork Insulation

More information

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016 Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.

More information

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation

More information

SUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES

SUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES SUGGESTED SPECIFICATION EXHAUST SYSTEM SILENCER, FLEX CONNECTOR, INSULATION BLANKETS, WALL / ROOF THIMBLES 4121 N.W. 37 th Street, Lincoln, NE 68524 Telephone (402) 470-2627 Fax (404) 470-2410 www.gtexhaust.com

More information

07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 15250 MECHANICAL INSULATION

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 15250 MECHANICAL INSULATION PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Minimum insulation thicknesses shall comply with ASHRAE Standard 90A. B. Provide saddles and shields under pipe hangers. C. If more than one type

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

Product Information Sheet

Product Information Sheet Distributed by Thermal Products Company, Inc. Product Information Sheet FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts) Introduction Unifrax s FyreWrap Elite 1.5 Duct Insulation

More information

SECTION 07400 STANDING SEAM METAL ROOF

SECTION 07400 STANDING SEAM METAL ROOF SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and

More information

Tremco Fire Protection Systems Group Technical Bulletin

Tremco Fire Protection Systems Group Technical Bulletin Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,

More information

SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK

SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,

More information

Roof Curbs, Extensions and Equipment Supports

Roof Curbs, Extensions and Equipment Supports Roof s, Extensions and Equipment Supports December 2012 Roof Page s, Header Extensions and Equipment Supports Table of Contents Model GPI Standard and Optional Construction Features... 3 Model Number Code....

More information

A D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, 2012. All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA

A D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, 2012. All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA Page 1 of 10, Addendum No. 3 Temporary Garage Structure City of Chelsea, MA November 5, 2012 CBI Job No.: 12055-A A D D E N D U M # 3 DATE: November 5, 2012 TO: FROM: PROJECT: All Bidders Jenne dos Santos,

More information

GreenGuard Housewrap Installation Guide

GreenGuard Housewrap Installation Guide 000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

FRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS

FRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS Perry Fiberglass Products, Inc. FRP AQUATIC DUCTWORK COMPONENTS LEADERS IN FIBERGLASS REINFORCED PLASTIC DUCT PRODUCTS PERRY FIBERGLASS Perry Fiberglass Products, Inc. is a leading manufacturer of high

More information

City of San Diego, CWP Guidelines

City of San Diego, CWP Guidelines PART 1 -- GENERAL SECTION 08520-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing aluminum windows with frames, bracing, glazing attachments, screens,

More information

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including general and supplementary conditions and other Division 1

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel

More information

Bafl-Sorb Sound Absorbing Ceiling Baffles

Bafl-Sorb Sound Absorbing Ceiling Baffles Bafl-Sorb Sound Absorbing Ceiling Baffles INC offers a complete line of Sound Absorbing Ceiling Baffles to compliment any environment. Our ceiling baffles are among the most cost-effective method of adding

More information

Specifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023

Specifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023 Specifications Preformed Metal Wall and Roof Panels Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023 Section 07410 Preformed Metal Wall and Roof Panels Structural

More information

INC Flexi-Sorb. Versatile Flexible Easy To Install Durable Good Noise Reduction Economical. Typical Applications

INC Flexi-Sorb. Versatile Flexible Easy To Install Durable Good Noise Reduction Economical. Typical Applications INC Flexi-Sorb Noise Control Curtain System Versatile Flexible Easy To Install Durable Good Noise Reduction Economical Our Flexi-Sorb noise control curtain product line consists of flexible, durable acoustical

More information

Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION

Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION The Condensation Process Condensation occurs when warmer moist air comes in contact with cold surfaces such as framing members, windows

More information

SECTION 07 61 13 STANDING SEAM METAL ROOFING

SECTION 07 61 13 STANDING SEAM METAL ROOFING SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced

More information

Underwriters Laboratories Testing Information

Underwriters Laboratories Testing Information Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum

More information

Design No. P736 September 26, 2003. Restrained Assembly Ratings 1, 1-1/2 or 2 Hr. (See Items 3, 7 and 8A)

Design No. P736 September 26, 2003. Restrained Assembly Ratings 1, 1-1/2 or 2 Hr. (See Items 3, 7 and 8A) Design No. P736 September 26, 2003 Restrained Ratings 1, 1-1/2 or 2 Hr (See Items 3, 7 and 8A) Ratings 1, 1-1/2 or 2 Hr (See Items 3, 7 and 8A) Beam Ratings 1, 1-1/2 or 2 Hr (See Items 7 and 8A) 1. Beam

More information

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems

Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Pipe and Equipment Insulations Zeston PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Zeston PVC Insulated Fitting Covers Installation Instructions for Hot,

More information

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment

More information

SECTION 23 07 00 HVAC AND PLUMBING INSULATION

SECTION 23 07 00 HVAC AND PLUMBING INSULATION SECTION 23 07 00 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. HVAC and plumbing piping insulation, jackets and accessories. 2. HVAC and plumbing equipment insulation, jackets and accessories. 3.

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

Avoiding Air Barrier Pitfalls

Avoiding Air Barrier Pitfalls Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

DARTMOUTH COLLEGE DESIGN November 15, 2007 &CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN November 15, 2007 &CONSTRUCTION GUIDELINES SECTION 15250 MECHANICAL INSULATION PART 1 DESIGN DIRECTIVES 1.1 QUALITY ASSURANCE A. Manufacturer's Qualifications: Firms regularly engaged in manufacture of mechanical insulation products, of types and

More information

Roxul Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK DD) Page 1 October 2013

Roxul Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK DD) Page 1 October 2013 Master Guide Specification (CAVITYROCK DD) Page 1 ROXUL GUIDE NOTE: This master specification section is based on ROXUL INC., CAVITYROCK DD. Standard application: Cavity wall. ROXUL GUIDE NOTE: This master

More information

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use

More information

SECTION 098400 ACOUSTICAL WALL TREATMENT. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION 098400 ACOUSTICAL WALL TREATMENT. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 098400 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

SECTION 233000 HVAC AIR DISTRIBUTION

SECTION 233000 HVAC AIR DISTRIBUTION 1320 / Talent Community Center 233000-1 HVAC AIR DISTRIBUTION SECTION 233000 HVAC AIR DISTRIBUTION PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Ductwork. 2. Ductwork accessories. 3. Fans. 4. Air

More information

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3. Pages identified with the NMBS Logo as shown above, have been produced by NMBS to assist specifiers and consumers in the application of New Millennium Building Systems Deck products. Pages identified with

More information

Gypsum Board Systems Manual

Gypsum Board Systems Manual CertainTeed Gypsum Board Systems Manual Fire Resistance and Sound Control Design Manual Division 09 GYPSUM BOARD SYSTEMS MANUAL TABLE OF CONTENTS Introduction General Fire Resistance...1 Sound Control...3

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed

More information

RACQUETBALL, HANDBALL OR SQUASH COURTS AND GYMNASIUM WALL SURFACES

RACQUETBALL, HANDBALL OR SQUASH COURTS AND GYMNASIUM WALL SURFACES 1807 Elmwood Avenue, Suite 275 Buffalo, New York 14207 (800) 543-5155 RACQUETBALL, HANDBALL OR SQUASH COURTS AND GYMNASIUM WALL SURFACES Fiberesin Wall System Provide materials and labor to complete courts

More information

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,

More information

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification Number: 3503-11.2.610 Rev. 2 Rubber Lined Steel Pipe and Fittings Mechanically Coupled Plain End Type System Issued Revised Approved

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

a a Fiber Glass Insulation Air Handling Systems Product Selector Guide

a a Fiber Glass Insulation Air Handling Systems Product Selector Guide a a a a Fiber Glass Insulation Air Handlg Systems Product Selector Guide Icon Key Thermal Acoustical Fire Resistant Moisture Control Recycled Content Formaldehyde-free Products for improved door air quality

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING. January 24, 2014 06610-1

ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING. January 24, 2014 06610-1 ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING January 24, 2014 06610-1 SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS MOLDED GRATING PART 1 - GENERAL 1.1 SCOPE OF WORK A. The CONTRACTOR

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

Holiday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated.

Holiday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standing-seam metal roofing, custom fabricated. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: Show installation

More information

DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H

DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H Soil Drainage Mat with Built-In Protection Layer POLYGUARD DRAINAGE MATS are three-part prefabricated geocomposite drain consisting of a

More information

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings. SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

SECTION 02630 STORM DRAINAGE SYSTEM

SECTION 02630 STORM DRAINAGE SYSTEM SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE

More information

BOQ SPECIFICATIONS. The Blind system consist of a coated aluminium tube of 38 mm diameter with provision of fabric clamping.

BOQ SPECIFICATIONS. The Blind system consist of a coated aluminium tube of 38 mm diameter with provision of fabric clamping. BOQ SPECIFICATIONS VERTICAL BLINDS Vertical Blinds made of glass fibre fabrics in width 5 (or 4 ). Minimum overlapping of ¾ in fabric. Top aluminium anodized rail of 1.4 mm thickness. 2 inch wide channel

More information

Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 Fire Barrier Moldable Putty+ Pads 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 e-mail: info@fireretardantsinc.com Visit Our Web Site at www.fireretardantsinc.com Protecting

More information

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

SECTION 15410 GROUND WATER STORAGE TANKS

SECTION 15410 GROUND WATER STORAGE TANKS SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design

More information

DIVISION 7 - THERMAL AND MOISTURE PROTECTION

DIVISION 7 - THERMAL AND MOISTURE PROTECTION DIVISION 7 - THERMAL AND MOISTURE PROTECTION Note: This is a guide for Designers only. Contents shall not be used in lieu of specifications as part of the Designer s Contract Documents. SECTION 07 1000

More information

K2 STONE NATURAL VENEER

K2 STONE NATURAL VENEER INTRODUCTION WHAT IS K2 NATURAL THINSTONE VENEER? Natural K2 Stone veneer is real stone, cut 1 inch thick, making it light enough to be installed as a veneer. Sometimes referred to as thin veneer, thin

More information

SECTION 23 0700 HVAC INSULATION

SECTION 23 0700 HVAC INSULATION PART 1 GENERAL 1.01 QUALITY ASSURANCE SECTION 23 0700 HVAC INSULATION A. FIRE-TEST-RESPONSE CHARACTERISTICS: FLAME-SPREAD INDEX OF 25, AND SMOKE- DEVELOPED INDEX OF 50 FOR INSULATION INSTALLED INDOORS

More information

Preformed Metal Roofing and Siding

Preformed Metal Roofing and Siding Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision

More information

INSTRUCTIONS FOR COORDINATION SECTION 06651 SOLID SURFACE FABRICATIONS

INSTRUCTIONS FOR COORDINATION SECTION 06651 SOLID SURFACE FABRICATIONS INSTRUCTIONS FOR COORDINATION SECTION 06651 SOLID SURFACE FABRICATIONS 1. Paragraph 1.02 Provide solid surface countertops at sinks locations. Provide solid surface window sills at drywall framing walls.

More information

SECTION 072100 FIBERGLASS INSULATION

SECTION 072100 FIBERGLASS INSULATION This Specification Section is provided in CSI format for engineers and architects specifying fiberglass insulation manufactured by Knauf Insulation GmbH. in Shelbyville, Indiana. Delete insulation types

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

SECTION 07 42 13 METAL WALL PANELS

SECTION 07 42 13 METAL WALL PANELS Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: info@alpolic.com www.alpolic-northamerica.com This MANU-SPEC utilizes

More information

City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures

City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures City of Tucson and Pima County Arizona Building Code Appendix Chapter 72 Straw-Bale Structures SECTION 7201 - PURPOSE The purpose of this appendix chapter is to establish minimum prescriptive standards

More information

security products metric sizes Redefine your comfort zone. www.titus-hvac.com

security products metric sizes Redefine your comfort zone. www.titus-hvac.com metric sizes secure lethal objects monitoring areas suicide deterrent Redefine your comfort zone. www.titus-hvac.com humid areas prevents corrosion minimum security medium security maximum security Table

More information

H-Stud Area Separation Wall System

H-Stud Area Separation Wall System 12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic

More information

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional

More information

SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 230529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.

More information

Lightweight Partition Design for Residential and Commercial Buildings

Lightweight Partition Design for Residential and Commercial Buildings Lightweight Partition Design for Residential and Commercial Buildings Stanley D. Gatland II, CertainTeed Corporation, Valley Forge, Pennsylvania Guidelines are presented for the design and proper installation

More information

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

THE DOW CHEMICAL COMPANY Issued: August 1, 2008 200 LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN 48674 (989) 638-8655 www.dowbuildingmaterials.

THE DOW CHEMICAL COMPANY Issued: August 1, 2008 200 LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN 48674 (989) 638-8655 www.dowbuildingmaterials. ICC EVALUATION SERVICE, INC. EvaluateP InformP Protect Los Angeles Business/Regional OfficeP 5360 Workman Mill RoadP Whittier, CA 90601 (562) 699-0543 phonep (562) 695-4694 fax DIVISION: Section: 6 WOOD

More information

WASHROOM UPGRADE SIR CHARLES TUPPER BUILDING 2250 RIVERSIDE DRIVE, OTTAWA, ON SIR CHARLES TUPPER BUILDING A0.0 COVER SHEET / DRAWING LIST

WASHROOM UPGRADE SIR CHARLES TUPPER BUILDING 2250 RIVERSIDE DRIVE, OTTAWA, ON SIR CHARLES TUPPER BUILDING A0.0 COVER SHEET / DRAWING LIST 0 RIVERSIDE DRIVE, OTTAWA, ON A0.0 COVER SHEET / DRAWING LIST A0. LEGEND AND GENERAL NOTES A0. GENERAL NOTES A0. GENERAL NOTES A0. TYPICAL WASHROOM WALL/SINK SECTION A0. DETAIL - CONTROL JOINT A0. DETAIL

More information

Pre-Cut Sauna Specifications

Pre-Cut Sauna Specifications Pre-Cut Sauna Specifications When to specify a Pre-Cut Liner Sauna: Please review diagrams at the beginning of these specs. Pre-Cut saunas are best suited for projects that require the four walls and ceiling

More information

Phone: 1-800-852-8352 FAX: 937-866-4174 website: www.midwestfasteners.com GUIDE TO INSULATION FASTENING

Phone: 1-800-852-8352 FAX: 937-866-4174 website: www.midwestfasteners.com GUIDE TO INSULATION FASTENING Phone: 1-800-852-8352 FAX: 937-866-4174 website: GUIDE TO INSULATION FASTENING APPLICATION OF WELD PINS 1. WELD PINS IN PLACE. 2. INSTALL INSULATION ON PINS. 3. PRESS WASHERS ON PINS TO 4. EITHER CLIP

More information

PANELIZED HOME INSTALLATION GUIDELINE

PANELIZED HOME INSTALLATION GUIDELINE PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.

More information

BASIC FIRE DOOR REQUIREMENTS TECHNICAL DATA SHEET NO. 401

BASIC FIRE DOOR REQUIREMENTS TECHNICAL DATA SHEET NO. 401 BASIC FIRE DOOR REQUIREMENTS SHEET NO. 401 Fire door openings are classified by their locations in the building. The location determines the length of exposure protection required, based on the potential

More information

Technical Data Honeycomb Door Leaf 8-1-99

Technical Data Honeycomb Door Leaf 8-1-99 8--99 8-/8 8-7/8 B 8-/4 A A Dim. A Leaf Width B ELEVATION F DESIGN Vertical edge seams mechanically interlocked Square hinge and lock edges 4-/ x.4 full mortise hinge prep Gov. 60/6 cyl lock prep...prefix

More information

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such

More information

Guide Specification SECTION 23 07 00 - HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY

Guide Specification SECTION 23 07 00 - HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY SECTION 23 07 00 - HVAC INSULATION PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. HVAC piping insulation, jackets and accessories. 2. HVAC ductwork insulation, jackets, and accessories. 3. Equipment

More information

Product Guide Specification

Product Guide Specification Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail ri@reefindustries.com Product Guide

More information