1 Syncro Modem Communications Module Installation and Commissioning Manual Man1068 Issue 04 June 2013
2 Index 1. General Description Fitting the Modem Module Fitting the modem module to the enclosure (diagram) Connecting the ribbon cable to the front panel board (diagram) Configuration Testing Using the dialup connection Using a mobile phone to dial the panel General description The Syncro fire alarm system modem communications module, allows the fire alarm control panel to be interrogated from a remote location via a dial up telephone connection. This allows the status of the control panel to be viewed and the configuration data, analogue values and event log to be uploaded to a PC. To enable modem configuration and connection, the user must be in possession of registered and dongle protected Loop Explorer software at version V3.0 or higher. The modem module fits inside the Syncro control panel in the space allocated for an I/O module and requires a 24V DC supply which can be taken from the adjacent AUX 24V connections. A telephone connection socket (type RJ11) is fitted at the top of the module to allow connection to a telephone point. The modem should only be connected to a direct telephone line and will not work through a PABX line. 2. Fitting the modem module Before fitting the modem module, the mains and battery power should be disconnected from the control panel. The modem module is supplied complete with a ribbon cable and ribbon cable clips. The ribbon cable must be connected to socket J5 on the Syncro front panel PCB and clipped into place as shown on the following drawings. Standoffs are already fitted to the control panel to accept the module, which simply pushes on to these. A 5 metre RJ11 to telephone socket lead is supplied for connection to a local telephone socket. This can be extended if the telephone socket is greater than 5 metres from the control panel using any proprietary telephone extension lead. The red and black wires from the 24V connection on the modem module connect to the AUX 24V terminals on the Syncro. The red wire should be connected to the terminal and the black wire connected to the terminal. If the AUX 24V supply is already in use, care must be taken to ensure that the total load on this supply does not exceed 500mA. It is essential that the telephone number of the line is now noted to enable testing. Product Manuals/Man1068 Syncro Modem_04 Page 2 of 8
3 2.1 Fitting the modem communications module to the enclosure NC C NO NC C NO NC C NO NC C NO NC C NO IN FIRE ALARM RELAY 1 RELAY 2 OUT IN OUT IN OUT OUT IN FAULT LOOP 1 LOOP 2 LOOP 3 LOOP 4 WARNING SOUNDER 1 SOUNDER 2 SOUNDER 3 SOUNDER 4 FIRE ROUTING FAULT ROUTING EXTINGUISHER OUTPUT TELEPHONE LINE FUSET3A 250V HRC G G G DO NOT PLUG OR UNPLUG RIBBON CABLES WHILST BOARD IS POWERED. STATIC SENSITIVE CIRCUITS.OBSERVE STATIC HANDLING PROCEDURES AT ALL TIMES WORKS ORDER NO. TESTED DATE SYSTEM FUSE FUSE F9 INT REMOTE CNT CONTROL AND AUX. SIL INPUTS COMMS ADDITIONAL I/O BOARDS AUX 24V NETWORK POWER SUPPLY (max. 30V DC) B B M E X4 D L F F FLT RES 0V PR1 PR2 PR3 C F J4 14W TO PSU R X 2 V MODEM MODULE MODEM COMMUNICATIONS MODULE 24V DC X3 X TO J5 ON FRONT PANEL V V BATT. LOAD 28V DC L1 L2 L4 L3 1. MAINS FAILED 2. BATT. DISCONN. 3. BATTERY LOW 4. EARTH FAULT 5. CHARGER FAIL 6. COMMON FAULT LED.1 MAINS FAIL LED.2 BATT DISC. LED.3 BATT LOW LED.4 EARTH FLT. LED.5 CHGR. FLT. MODEL S400 INPUT VOLTAGE FREQUENCY POWER RATING OUTPUT VOLTAGE V AC 50 60Hz 28V DC 112W WORKS ORDER NO. TESTED DATE L5 ALTERNATIVE PSU CONNECTIONS CABLE CLIP RIBBON CABLE TO FRONT PANEL PCB CABLE CLIP CONNECT RED AND BLACK WIRES CABLE CLIP PUSH MODULE ONTO EXISTING STANDOFFS Product Manuals/Man1068 Syncro Modem_04 Page 3 of 8
4 2.2 Connecting ribbon cable to front panel board C1 R42 DZ1 R51 R52 R53 OP1 C32 R47 VR2 R44 R49 C30 U22 R43 R13 R45 R48 F1 LED4 R11 R79 C31 R46 T1 D23 C33 C29 C28 D22 Q1 R56 Q2 R8 R64 R65 L2 R62 R63 L1 R60 R61 L3 R57 VR1 J9 WARNING! DO NOT PLUG OR UNPLUG RIBBON CABLES WHILST BOARD IS POWERED. STATIC SENSITIVE CIRCUITS.OBSERVE STATIC HANDLING PROCEDURES AT ALL TIMES LED2 R12 LED3 R19 LED10 R20 LED11 R21 LED12 J2 40 WAY RIBBON CABLE R5 JP1 R31 R32 R35 J8 R36 R30 R33 R41 R37 R39 C18 R38 C12 R40 C35 C23 WRITE SW13 C46 D12 U20 C11 ENABLE U24 C8 C9 U19 R76 R66 U21 D24 U6 U5 R55 R67 J4 U23 SD1 R59 R77 C34 R58 R54 U25 PRINTER Q3 OP2 OP3 OP4 J10 J7 U1 C14 C2 C10 BZ1 C44 C45 C55 R78 R14 LED5 R15 LED6 R16 LED7 R17 LED8 R18 LED9 R4 R1 R6 TR1 R7 J6 R34 C26 XT1 ZONE LED'S C56 C57 SW3 C50 S1 C21 U10 R29 C24 WATCHDOG C25 RESET C49 SW1 R10 LED1 SW14 D11 C13 D19 SW4 C27 R50 U4 U9 SW2 R72 R71 R70 R69 PART NO. S550 D6 U2 D5 D4 D13 D3 WORKS ORDER NO. SW7 SW8 SW9 SW10 TESTED R27 R28 DATE D1 R9 C22 C40 WATCHDOG D8 OPERATED SW15 RESET U13 U12 SW5 D18 SW12 SW16 C17 C37 C54 C38 C42 C36 C52 C39 C53 C47 C41 K6001 ISSUE C03 U15 C51 C43 R73 D9 R74 U11 U18 SERIAL NUMBER C48 C19 R68 SW17 D21 J11 D14 D2 SW11 U17 U8 J12 U16 SW6 D7 D25 C20 R75 R3 SW18 D20 PC J3 U14 J5 C58 C16 C7 C15 U3 SW19 D10 C5 R2 C3 U7 C59 R80 C6 R22 LED13 R23 LED14 R24 LED15 R25 LED16 R26 LED17 C4 J1 RIBBON CABLE TO MODEM MODULE PRINTER Product Manuals/Man1068 Syncro Modem_04 Page 4 of 8
5 3. Configuration The control panel needs to know that a modem is fitted. If the modem is fitted and correctly wired as shown on the installation drawings, then performing an autolearn will tell the panel that the modem is fitted. It is also possible to add the modem as an access level 3 menu command. This method may not be convenient however on a system that is already installed and configured because performing an autolearn will reset all parameters to their default settings. In this case, the Loop Explorer configuration programme should be used. For security reasons, Loop Explorer requires that the dongle supplied with the software is fitted. If the dongle is not fitted then the Loop Explorer software will function as normal Loop Explorer software (i.e. no modem and dial up configuration available. First, transfer the configuration file from the panel to the PC in the normal manner. Select the control panel to which the modem is connected and right click it to edit its settings. Check the box marked MODEM FITTED. Save the configuration file and then transfer the file from the PC back into the panel. The panel will now expect to see a modem fitted and will signal a fault condition if the modem is removed. 4. Testing Ensure that the PC is connected to a telephone line other than the line to which the control panel is connected. Open the site configuration file with Loop Explorer and the dongle fitted to the PC. Right click on the panel icon in the left windowpane and select edit settings. Check the Modem fitted box. Click OK and save the file. Modem fitted check box The telephone number of the control panel can now be entered by expanding the control panel and then double clicking the telephone icon. Click Telephone Product Manuals/Man1068 Syncro Modem_04 Page 5 of 8
6 After the number has been entered, click OK and then save the file. The control panel can now be called by clicking the Dial icon on the toolbar. Dial Icon Press the dial button to connect to the panel. Once the connection has established, a window will appear and will show any panels found (there may be more than one panel on a networked system). Select the virtual panel tab and then drop down list of panels next to the start button. Select the panel you wish to connect to and press start. The panel controls and display are now available as they would be if you were at the control panel. Using the menus, check that the number of devices fitted matches the configuration file. Product Manuals/Man1068 Syncro Modem_04 Page 6 of 8
7 Click on the event log tab, select the panel to connect to from the drop down list and then press fetch to get the event log from the panel. These tests should suffice to establish that the modem is connected and configured correctly. For a detailed description of the control panel operation, refer to the Syncro operation and maintenance manual. 5. Using the dial up connection The ability to dial into the control panel and to check its status has many benefits for both the maintainer of the system and for the end user. Detector contamination Detectors are automatically recalibrated every 24 hours and adjustments are made to compensate for the contamination, which inevitably builds up over time. Eventually, a point will be reached, where the detector can no longer compensate for the contamination and the detector will announce a maintenance fault. Before a maintenance fault is announced however, the Syncro control panel will identify any devices, which are over 80% of their calibration limits and put them into an easy to view list. This enables maintenance visits to be scheduled to replace contaminated devices before a fault warning is generated. A list of the analogue values of all devices can be downloaded and saved to the PC for analysis offline if required. Fault diagnosis When the fire alarm system develops a fault, the information received by the engineer is often sketchy to say the least. The report is often made by the end user who (understandably), sometimes has difficulty in conveying the nature of the problem. The ability to dial into the control panel and view the display as if you were at the panel can provide valuable diagnostic information and prevent wasted site visits or ensure that an engineer attends equipped with the right parts. Product Manuals/Man1068 Syncro Modem_04 Page 7 of 8
8 Configuration problems Although the Loop Explorer configuration programme is simple to use, some more complex configuration problems may require assistance from a more experienced engineer or the equipment manufacturer. The dial up connection allows the configuration data to be extracted from the control panel for close analysis. This allows speedy resolution of problems, which may otherwise necessitate return visits to site. Configuration verification With the correct level 2 and level 3 passwords, it is possible for a system configuration to be changed via the front panel controls of the panel. The maintainer of the system can upload and compare the control panel configuration at will to ensure that the system is configured and operating as records show that it should be. This gives added confidence to the maintainer and end user that the fire alarm system is working as intended. 6. Using a mobile phone to dial the panel It is generally more convenient for testing purposes, to use a mobile telephone to dial into the control panel rather than a landline. When using a mobile telephone, the testing can be done right at the panel and the changes on the display can be witnessed. To use a mobile telephone for this purpose, the telephone service provider must be contacted and data/fax communication enabled for the phone in question. Service providers do not normally make any charge for this. Once data/fax services are enabled for the mobile telephone, a connection lead and some software will be required for the PC. The lead connects to the PCs serial port and to the utility socket on the mobile phone. There are many types of mobile phone connectors and it is essential to get the correct one. The software is a GSM terminal adapter, which acts as a software modem. Product Manuals/Man1068 Syncro Modem_04 Page 8 of 8
Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling
Electronics Ltd Presenting Power, Intelligence... with a sense of feeling By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford Plug in slots K772
More informationCM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way
More informationSyncro. Multi Loop Analogue Addressable Fire Control Panel. Product Manual. Man-1055 Issue 21 September 2010
Syncro Multi Loop Analogue Addressable Fire Control Panel Product Manual Man-1055 Issue 21 September 2010 Section Index Page 1. Introduction... 4 2. Safety... 4 3. Installation... 5 4. Cabling... 5 4.1
More informationSyncro. Multi Loop Analogue Addressable Fire Control Panel. Product Manual Man-1055 Issue 26 May 2016
Syncro Multi Loop Analogue Addressable Fire Control Panel Product Manual Man-1055 Issue 26 May 2016 Section Index Page 1. Introduction... 4 2. Safety... 4 3. Installation... 5 4. Cabling... 5 4.1 Loop
More informationTS510 & TS500. Installation & User Guide. Compatible Equipment
Installation & User Guide Compatible Equipment TS510 REM - Remote Keypad 9040 - Loudspeaker DC54/58 - Digital Communicator SD1+ - Speech Dialler 496525 Issue A 1 of 10 TS510 and TS500 Overview Introduction
More informationHow To Use A 1232 On A 1236 On A Computer Or A Cell Phone
12-36-1000 Autodialler and Relay Telephone Interface 1.0 INTRODUCTION 12-36-1000 I/O Telephone Interface with AutoDialer The 12-36-1000 is a autodialer and telephone interface that can be used autonomously
More informationSNMP Web Management. User s Manual For SNMP Web Card/Box
SNMP Web Management User s Manual For SNMP Web Card/Box Management Software for Off-Grid Inverter Version: 1.2 Table of Contents 1. Overview... 1 1.1 Introduction... 1 1.2 Features... 1 1.3 Overlook...
More informationIPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02
IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 TABLE OF CONTENTS DESCRIPTION 2 MOUNTING INSTRUCTIONS 2 HOW TO CABLE THE IPX 2/3 POWER SUPPLY INSTALLATION 3 OPERATION 3 CARE
More informationSpeedlink software will run on Windows NT, Windows 7, and Windows 8; it will run on both 32 byte and 64 byte versions of Windows.
Guide to the Speedlink software and drivers. Status Instruments has a range of process control equipment that can be configured using the Speedlink software. Some equipment will connect directly to a Windows
More informationGE Security. FHSD Monitor / Web Server user manual
GE Security FHSD Monitor / Web Server user manual version 1-0 / november 2004 http://www.geindustrial.com/ge-interlogix/emea 2004 GE Interlogix B.V.. All rights reserved. GE Interlogix B.V. grants the
More informationABUS WIRELESS ALARM SYSTEM
ABUS WIRELESS ALARM SYSTEM These installation instructions are published by Security-Center GmbH & Co. KG, Linker Kreuthweg 5, D-86444 Affing/Mühlhausen. All rights including translation reserved. Reproductions
More informationPRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL
Rev. D PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL 10 BORIGHT AVENUE, KENILWORTH NEW JERSEY 07033 TELEPHONE: 800-524-0273 FAX: 908-686-9317 TABLE OF CONTENTS Page
More informationSyncro AS. Analogue Addressable Fire Control Panel. Product Manual Man-1096 Issue 14 May 2016
Syncro AS Analogue Addressable Fire Control Panel Product Manual Man-1096 Issue 14 May 2016 Index Page 1. Introduction... 5 2. Safety... 6 3. Technical specification... 6 4. Installation... 7 5. Cabling...
More informationBARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
More informationAlarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6
Alarm over IP IRIS Touch Home Installation Manual Version 1.0 ENGLISH Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6 1. Introduction No more bulky batteries, just one sleek unit
More informationDSX Master Communications
DSX Access Systems, Inc. PC to Master Controller - Direct Connect Communications DSX Master Communications Communications between the Comm Server PC and the Master Controller can take several forms which
More informationPLC training panel (Twido version)
PLC training panel (Twido version) User manual Name School of Trades Produced by: GJR October 2012 Colour leaves: 9 BW leaves: 2 Cover colour: White Cover image: G.J.Rogerson Acknowledgments: Much of the
More informationTroubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
More informationBuilding Management System Gateway. Installation and Commissioning Manual Man-1181 Issue 07 June 2013
Building Management System Gateway Installation and Commissioning Manual Man-1181 Issue 07 June 2013 Index Page 1. Overview... 3 2. Power Requirements... 4 2.1 OpenConnect Gateway Power Requirements...
More informationUPS Network Interface. Quick InstallationGuide
UPS Network Interface Quick InstallationGuide Version 1.1 March 1999 COPYRIGHT Copyright 1999 RINGDALE UK Limited. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed,
More informationACP10 10 Zone Intruder Alarm System
ACP10 10 Zone Intruder Alarm System Installation Manual Contents 1. System Overview... 4 System Configuration... 4 Control Panel... 4 Remote Keypads... 5 LED Remote Keypad... 5 LCD Remote Keypad... 5 USB-Link...
More informationRHINO TRACKS STANDARD GPS VEHICLE TRACKER
RHINO TRACKS STANDARD GPS VEHICLE TRACKER Product Code: RHINO TRACKS STS ABOUT YOUR RHINO TRACKS STS This user guide covers the installation and operation of your RHINO TRACKS STS. The latest version of
More informationCB200W Water Leak Detection Panel Application Guide
Checked by: AJC Approved by: JBJ Contents CB200W Water Leak Detection Panel Application Guide 1. Cabinet Specifications... 2 2. Panel Hardware Specifications... 3 3. Panel Configuration... 4 4. Technical
More informationAeroqual Connect and Cloud
Aeroqual Connect and Cloud Page 1 Contents 1. Introduction to Aeroqual Connect and Cloud... 3 1.2. Aeroqual Connect... 3 1.3. Aeroqual Cloud... 3 2. How to Connect... 4 2.1. Aeroqual Connect... 4 2.1.1.
More informationPlena Voice Alarm System. Software Manual Configuration Software
Plena Voice Alarm System en Software Manual Configuration Software Plena Voice Alarm System Software Manual Table of Contents en 3 Table of Contents Table of Contents...3 1. Introduction...7 1.1 Purpose...7
More informationFIREDEX 2200. Conventional Fire Panels
68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class
More informationWorkshop 7 PC Software - Tracker
Workshop 7 PC Software - Tracker Goal: You will startup and perform advanced setup functions using Tracker PC software. You will also setup equations to control MP503 binary outputs. The Binary Output
More informationConventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
More informationRepeaters and Mimics Data Sheet
Repeaters and Mimics Data Sheet IDR series repeaters and mimics allow vital information from a Notifier fire system to be communicated to points around a building remote from the fire alarm control panel.
More informationProcessor. User Guide
Processor User Guide Land Instruments International Dronfield, S18 1DJ England Telephone: (01246) 417691 Facsimile: (01246) 410585 Email: infrared.sales@landinst.com Internet: www.landinst.com Land Instruments
More informationMemcom Emergency Telephone
Memcom Emergency Telephone Installation Guide Ref No. 450 900 (GB) Version 2 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based programming
More informationCrow Limited Warranty. Print Version 017
Crow Limited Warranty (Crow) warrants this product to be free from defects in materials and workmanship under normal use and service for a period of one year from the last day of the week and year whose
More informationCurrent Monitoring Kit QUICK START GUIDE
Current Monitoring Kit QUICK START GUIDE Pico Technology EL040 Current Monitoring Kit Quick Start Guide CONTENTS 1 Introduction... 1 2 Kit contents... 3 3 Installation... 3 3.1 Connecting the system together...
More informationFirmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS
More information500r+ Installation and User Guide
500r+ Installation and User Guide Compatible Equipment 502rUK-50 Watch/Pendant PA. 509rUK-50 Smoke Detector 515rUK-00 10 metre passive infra red movement detector. 525rUK-00 Remote Set/Unset (Full and
More informationData sheet GIOD.1 Input/output module with CAN bus. ERP no.: 5204183. www.guentner.de. Data sheet GIOD.1 V_3.0
Data sheet GIOD.1 Input/output module with CAN bus ERP no.: 5204183 www.guentner.de Page 2 / 10 Contents 1 GIOD.1... 3 1.1 Functional description...3 1.2 Connections... 5 1.3 Electrical properties of...
More informationCurrent Monitoring Kit
Current Monitoring Kit QUICK START GUIDE DO090-6 CONTENTS Issues: 1) 2.10.02 WP A4 format 2) 2.10.02 Added safety warning 3) 17.3.06 Word A5 format. S1: Removed relay modules. S2: Added MI010. S4.1: added
More informationIRIS Touch 600 Range Dialler Installation Manual. Version 1.3
IRIS Touch 600 Range Dialler Installation Manual Version 1.3 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised
More informationInteractive Fire Alarm System. User Guide. Loop viewer tool, LoopViewer. Protecting life, environment and property... P-ASAFE-LV/FE, Rev.
Interactive Fire Alarm System User Guide Loop viewer tool, LoopViewer Protecting life, environment and property... P-ASAFE-LV/FE, Rev. A, 033105 COPYRIGHT This publication, or parts thereof, may not be
More informationINTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.
INTRODUCTION The information provided herein covers the range of products known as the 'Sensor 901' series. The range of equipment is designed to meet the requirements of BS 5839 parts 1 & 4 1988. The
More informationProduct Information Fire alarm panel 8000 C
Product Information Fire alarm panel 8000 C Fire alarm panel 8000 C, basic configuration In common with all modern Esser panels, the 8000 C fire alarm panel is based on high-performance ringbus technology.
More informationDisabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions
Disabled Toilet Alarm Installation & Operating Contractor Pack Installation & Operating Instructions 1 Overview The Channel Safety Systems Disabled Toilet alarm contractor Packs are an efficient way of
More informationHM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
More informationTechnical Data Sheet
PC-NET-004 Mx / Lx Terminal and remote Dial-Up This software allows communication with Mx-4000 and Lx-9400 series of fire and lighting products using direct RS232 or modem connection. Technical Data Sheet
More informationSpectrum Technologies, Inc.
Weather Station Dial-Up Modem Operation Manual Catalog No. 3387 Spectrum Technologies, Inc. CONTENTS General Overview 3 Components 3 Specifications 3 Installation 4 Operation Setting up a Weather Station
More information56K PCI DATA/FAX Modem. User Manual
56K PCI DATA/FAX Modem User Manual Contents 1. Package Contents... 1 2. Minimum System Requirement... 2 3. Panel Descriptions... 3 4. Hardware Installation... 4 5. Installing The Modem Drivers... 5 A.
More informationTE100-P21/TEW-P21G Windows 7 Installation Instruction
Hardware Installation TE100-P21/TEW-P21G Windows 7 Installation Instruction 1. Go to http://www.trendnet.com/downloads/ to download the Windows 7 Utility. Save the file to your desktop. 2. Right click
More informationSelf Help Guide IMPORTANT! Configuring Your Router With Your Modem. Please read the following carefully; This Guide refers to the following Products:
IMPORTANT! This Guide refers to the following Products: Configuring Your Router With Your Modem Please read the following carefully; Synopsis: A standard (Wireless) Router does not come equipped with the
More informationLee County School Configuring Spec Ed Laptop Computers for Dialup, DSL/Cable Modem, and Wireless Access To the Internet
Lee County School Configuring Spec Ed Laptop Computers for Dialup, DSL/Cable Modem, and Wireless Access To the Internet Prepared by: Rich Morgan Technology Director Configuring your Spec Ed laptop for
More informationEMBEDDED ACCESS CONTROL Hardware Installation Guide
EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel
More informationInstalling Remote Desktop Connection
SETTING UP YOUR REMOTE DESKTOP This section will assist you in setting you Remote Desktop Connection. This will allow you to create an icon for easy access to your virtual desktop. DISCLAIMER: All images
More informationDUKANE Intelligent Assembly Solutions
PC Configuration Requirements: Configuration Requirements for ipc Operation The hardware and operating system of the PC must comply with a list of minimum requirements for proper operation with the ipc
More informationTroubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
More informationCurveMaker v2.1 DYNAFS programmable ignition software
CurveMaker v2.1 DYNAFS programmable ignition software Dynatek 164 S Valencia St. Glendora CA 91741 phone (626)963-1669 fax (626)963-7399 Contents 1) Installation...1 2) Overview...1 3) Programming a Curve...4
More information200 Range Dialer Installation Manual. Version 1.0
200 Range Dialer Installation Manual Version 1.0 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised by contract
More informationAndover Continuum Remote Communication Configuration Guide
Andover Continuum Remote Communication Configuration Guide 2010, Schneider Electric All Rights Reserved No part of this publication may be reproduced, read or stored in a retrieval system, or transmitted,
More informationDigital Photo Bank / Portable HDD Pan Ocean E350 User Manual
Digital Photo Bank / Portable HDD Pan Ocean E350 User Manual Installing a hard disk 1. Power off the unit. 2. Remove the bottom cover from the unit by removing four screws. 3. Insert the 2.5 HDD to the
More informationINTRODUCTION FEATURES OF THE ICM
INTRODUCTION The ICM, Internet Control Module, is a remote controller device accessible via the Internet that allows operational access to the IPS (and other base units available). Through the ICM you
More informationTemperature & Humidity SMS Alert Controller
Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal
More informationDaker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
More informationIO-DIM6 6-Channel, Digital to Analogue Converters
Page 1 of 6 IO-DIM6 6-Channel, Digital to Analogue Converters Features: Benefits: Input status indication Calibrated output DIN Rail mounting Expands controller input capacity Fault finding LED indication
More informationSECURITY SYSTEM MANAGEMENT SOFTWARE FOR WINDOWS. Quick Start Instructions
TM SECURITY SYSTEM MANAGEMENT SOFTWARE FOR WINDOWS Quick Start Instructions Introduction WinLoad for Windows was developed to simplify and speed up the task of programming Paradox control panels. Remote
More informationMAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS
MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.
More informationConfiguring the Siemens TC35 modems for use with the MI2292
Configuring the Siemens TC35 modems for use with the MI2292 The following instruction describe how to set up GSM communication between an MI2292 Power Quality Analyser Plus and a computer 1. Equipment
More informationAmcrest 960H DVR Quick Start Guide
Amcrest 960H DVR Quick Start Guide Welcome Thank you for purchasing our Amcrest 960H DVR! This quick start guide will help you become familiar with our DVR in a very short time. Before installation and
More informationEthernet. Customer Provided Equipment Configuring the Ethernet port.
Installing the RDSP-3000A-NIST Master Clock. Ethernet Connect the RJ-45 connector to a TCP/IP network. Equipment The following equipment comes with the clock system: RDSP-3000A-NIST Master Clock Module.
More informationJob Aid: Creating Additional Remote Access Logins
This job aid describes the steps required to add an additional remote access login to the Avaya S8300, S8500, and S8700 Series Media Servers. These logins may be used to establish a Point to Point Protocol
More informationACTIVE 5 ENGINEERING MANUAL
ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features
More informationDrayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
More informationVEGA Analogue Addressable Control Panels
Analogue Addressable Control Panels Representing the future of fire alarm control technology, Vega's modular concept enables the tailoring of system design for the smallest to the largest system. Designed
More informationSECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
More informationLD2 One & Two Zone Water Detection Alarm Installation and Operation Manual
CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual Contents 1) Operation 2)
More informationFTDI VCP DRIVER (free) (WIN/MAC/LINUX) http://www.ftdichip.com/drivers/vcp.htm
002 - CONNECTING THE PRINTER Now that you have an idea what 3D printing entails, we can continue and connect the printer to your computer. First make sure you have a computer with a decent amount of RAM
More informationFire Alarm Control Panel. Family. Operating Manual
Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...
More informationTransmitter Interface Program
Transmitter Interface Program Operational Manual Version 3.0.4 1 Overview The transmitter interface software allows you to adjust configuration settings of your Max solid state transmitters. The following
More informationAGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS
AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS AGRI-ALERT ALARM SYSTEMS Peace of Mind Agri-Alert is a complete alarm system for monitoring temperature, power, feed and watering systems, burglary,
More informationSMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision 090210 [Version 2.2]
SMS Alarm Messenger SMSPro_Setup Revision 090210 [Version 2.2] ~ 1 ~ Contents 1. How to setup SMS Alarm Messenger?... 3 2. Install the SMSPro_Setup software... 5 3. Connection Type... 6 4. Connection Port
More informationGSM Voice Auto Dialer & SMS Sender JC-999
GSM Voice Auto Dialer & SMS Sender JC-999 Main features: () Large LCD display,integrated integrated keypad, human-friendly programming; (2) Support 2 alarm receiving numbers; (3) Triggering means: N.C
More informationSFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description
SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped
More informationGST301. (Single Protection Zone) Operation Manual
GST301 Gas Extinguishing Control Panel (Single Protection Zone) Operation Manual 2 of 19 CONTENTS 1 OVERVIEW... 4 2 TECHNICAL DATA... 4 3 STRUCTURES... 5 3.1 FRONT SURFACE DESCRIPTION... 5 3.1.1 Indicators...
More informationDisturbance Recoder SPCR 8C27. Product Guide
Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power
More informationMODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
More informationPRT3 Printer Module: ASCII Protocol Programming Instructions
PRT3 Printer Module: ASCII Protocol Programming Instructions We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com and send
More informationRunning the R4 Software on a USB Port
Tech Note Running the R4 Software on a USB Port Like a lot of other engine management software programs that have been around for a while, the R4 program is designed to communicate through a 9-pin serial
More informationHyperAccess Access Control System
Control System We manufacture, an advanced PC based access control solution that will give you control over who has access to your building. With you can control access on hundreds of doors for up to 10,000
More informationAPPLICATION NOTE. The DMP Software Family DMP COMPUTER SOFTWARE PROGRAMS
APPLICATION NOTE Contents The DMP Software Family... 1 Stand-Alone Link Software... 1 Add-on Modules for Link Software... 1 System Link End-User Panel Management Software... 2 Simple Registration and Activation...
More informationQuick installation guide for the Vista Quantum QNVR Network Video Recorder
QNVR range Quick Instalation guide Quick installation guide for the Vista Quantum QNVR Network Video Recorder Full manual found on the CD supplied with the NVR Contents SCOPE OF USE... 3 1. FRONT PANEL
More informationInstallation Manual Premier Elite ComIP
Installation Manual Premier Elite ComIP INS273-5 Overview Introduction The ComIP module allows the Premier & Premier Elite control panels to be connected to either a Local Area Network (LAN) or Wide Area
More informationPC Program User s Guide (01.01.05) 1. Connecting the PC. 2. Installation and Start-up. 3. Programming
Work Off-Line Set up a new database or modify a previously saved database (without being connected to the telephone system). This helps minimize on-site programming time. Work On-Line (connected directly
More informationBluetooth HC-06 with serial port module Easy guide
1 Bluetooth HC-06 with serial port module Easy guide This manual consists of 3 parts: PART 1. Overview of Bluetooth HC-06 module with serial port. PART 2. Installing Bluetooth HC-06 module with Bolt 18F2550
More informationHow to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers.
How to use the OMEGALOG software with the OM-SQ2010/SQ2020/SQ2040 Data Loggers. OMEGALOG Help Page 2 Connecting Your Data Logger Page 2 Logger Set-up Page 3 Download Data Page 8 Export Data Page 11 Downloading
More informationRack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
More informationSelf Help Guide. Please read the following carefully; Synopsis: Requirements: A Computer with a working RJ45 LAN Port All Belkin Modem Routers
IMPORTANT! This Guide refers to the following Products: Establishing A Connection From PC To Router Please read the following carefully; Synopsis: This Self-Help Guide is designed to assist you if you
More informationVOICE RECORDING SYSTEM ISDN PRI / BRI
Sense Box VOICE RECORDING SYSTEM ISDN PRI / BRI / Analog SUB-SYSTEM ISDN2, ISDN30 Sense Box USER MANUAL TABLE OF CONTENTS 1. STATUTORY INFORMATION... 3 1.1 SAFETY WARNING... 3 1.2 SAFETY EXTRA LOW VOLTAGE
More informationRouter Setup Manual. NETGEAR, Inc. 4500 Great America Parkway Santa Clara, CA 95054 USA 208-10060-01 2006-03-17
NETGEAR, Inc. 4500 Great America Parkway Santa Clara, CA 95054 USA 208-10060-01 2006-03-17 2006 by NETGEAR, Inc. All rights reserved. Trademarks NETGEAR is a trademark of Netgear, Inc. Microsoft, Windows,
More informationUser s Manual. Management Software for Inverter
WatchPower User s Manual Management Software for Inverter Table of Contents 1. WatchPower Overview... 2 1.1. Introduction... 2 1.2. Features... 2 2. WatchPower Install and Uninstall... 2 2.1. System Requirement...
More informationGETTING TO KNOW YOUR TELSTRA PRE-PAID 3G USB + WI-FI
FOR MORE INFORMATION CALL 125 8880 or FROM A NON-TELSTRA PHONE, CALL 13 2200 AND SAY PRE-PAID VISIT telstra.com/ppmbb VISIT A TELSTRA STORE OR PARTNER GETTING TO KNOW YOUR TELSTRA PRE-PAID 3G USB + WI-FI
More information1. Make sure that no client accounts are open. 2. Click on Setup, then click Modem. The Modem Setup window will appear.
SECURITY SYSTEM MANAGEMENT SOFTWARE FOR WINDOWS WINLOAD MODEM SETUP The modem setup is a very important step in the connection process. If the modem setup is not properly completed communication between
More informationInstallation Manual for D0700 ISDN Analogue Converter
Installation Manual for D0700 ISDN Analogue Converter Dycon Ltd Tel: +44 (0)1443 471 060 Fax: +44 (0)1443 479 374 Cwm Cynon Business Park Mountain Ash CF45 4ER - UK www.dyconsecurity.eu sales.en@dyconsecurity.eu
More informationRouteFinder SOHO. Quick Start Guide. SOHO Security Appliance. EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP
RouteFinder SOHO SOHO Security Appliance EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP Quick Start Guide RouteFinder RF825 Series Quick Start Guide RouteFinder SOHO Security Appliance
More information