VAV Terminal Unit Control Package
|
|
- Marshall Knight
- 7 years ago
- Views:
Transcription
1 VAV Terminal Unit Control Package Model CP-163-STK Analog Electronic, VAV Cooling, VAV Heating Controller/Actuator for Single Duct VAV applications. Includes: Duct Mounted change-over T-Stat, Wall Thermostat Notes: 1. This control Package is provided as loose components for field installation and wiring. 2. Controls require 24 V AC power provided by others. Wiring Diagram 2 Control Sequence.. 3 Component Data sheets and IOM s 4-10 Page 1 of 10
2 Tuttle & BaileyR CONTROL PACKAGE 3 AIR FLOW SENSOR AIR LO HI FLOW 1 CONTROLLER/ ACTUATOR RED BLUE H L 16 O 24 V I DC N U T - VAC - ~ 4 TRANSFORMER (optional) 24VAC SEE NOTE 2 V T3 R1 T1 + V A - THERMOSTAT T2 R2 T4 V2 JUMPERS 6 DUCT SENSOR 4 NC X Y C NO A 5 CHANGEOVER RELAY MODULE PNEUMATIC TUBING FACTORY WIRING FIELD WIRING ITEM 1 PART NO DESCRIPTION CONTROLLER/ACTUATOR NOTES: 1. SENSOR PART NUMBER VARIES WITH UNIT SIZE. SEE REPLACEMENT PARTS LIST IN PRICE MANUAL. 2. OPTIONAL - FOR VELOCITY THERMOSTAT. 3. TRANSFORMER PART NUMBER VARIES WITH VOLTAGE SEE REPLACEMENT PARTS LIST IN PRICE MANUAL. JOB NAME: LOCATION: ARCHITECT: ENGINEER: CONTRACTOR: SUBMITTED BY: Page 2 of NOTE #1 NOTE # THERMOSTAT CTE R FLO-CROSS SENSOR TRANSFORMER CHANGEOVER MODULE REE-1005 DUCT SENSOR STE-1002 REV LEVEL: A DATE: 9/01 DWG NO: SDV SINGLE DUCT VAV 2201 ANALOG ELECTRONIC CONTROLS Cooling / Heating Duct Sensing Auto Changeover /01
3 Tuttle & BaileyR CONTROL PACKAGE 2201 CONTROL DIAGRAM MAX FLOW CFM MIN COOL TR HTG SP SP TR CLG WARM SP = SET POINT TR = THROTTLING RANGE SEQUENCE OF OPERATION 1.) COOLING SPACE TEMPERATURE Air flow is at minimum or shut off when room temperature is below setpoint. On a rise in room temperature the air flow increases to maximum, within the throttling range. 2.) AUTO CHANGEOVER The changeover module initiates changeover by sensing supply duct air temperature, and programs the controller to automatically operate in the appropriate mode. The changeover occurs at fixed, non-adjustable factory settings, 77 F.±4 F. supply duct temperature for heating and 77 F.±4 F. for cooling. 3.) HEATING Air flow is at minimum or shut off when room temperature is above setpoint. On a drop in room temperature the air flow increases to maximum, within the throttling range. 4.) LOSS OF POWER With a loss of power to the controller, the damper will fail in place. Page 3 of P2-9/01
4 CSP 5001, 5002 VAV Flow Controller-Actuator Electronic Analog Description The KMC CSP 5001/5002 VAV Flow Controller- Actuators are pressure-independent combination controller-actuators designed primarily for use on variable air volume terminal units. Air flow is sensed by using a single or multi-point differential (velocity) pressure measuring station or pitot tube. Designed with an onboard flow-through sensor utilizing twin platinum resistance temperature detectors, these models are capable of controlling a velocity setpoint from 0 to 3,300 fpm with an accuracy of 3%. The CSP 5001/2 offers full range flow control of VAV terminal units when used with the CTE 5100 series room thermostats. Air velocity flow control limits may be set at the thermostat or internal to the CSP 5001/2. The actuator section provides adjustable stops, magnetic clutch and a gear disengagement button. A tri-color LED indicates green for opening, red for closing and white for satisfied damper positions. Available control options include proportional or two position wet or electric reheat, dual minimums, fan induction, dual duct, and automation interface. Features Onboard flow-thru sensors with twin platinum resistance temperature detectors Setpoint accuracy of 3% from 0 to 3,300 fpm Adjustable stops Magnetic clutch Gear disengagement button LED status indicator Accessories The following accessories are available: CME 1002 Single auxiliary switch CME 1004 Dual auxiliary switch CME 1006 Triple auxiliary switch HFO 0011 Adaptor for 3/8" shaft HMO 4518 Snap-in connector for 1/2" flexible metal conduit HMO 4520 Compression connector for plenum cable HMO 4526 Female connector for 1/2" conduit Models Two models are available: CSP 5001 CCW to close CSP 5002 CW to close Page 4 of 10 Specifications and design subject to change without notice.
5 Details All dimensions are in inches (mm). Specifications Supply Voltage 24 VAC -15/ + 20%, 50/60 Hz Input Power 4 VA Output Supply 16 VDC (22 ma) Output Torque 50 in. lbs. min., 70 in. lb. max. (5.6 N m min., 7.9 N m max.) Velocity Range 0 to 3300 fpm (16.76 m/s), dependent on DP pickup, tubing size/length and connections Velocity Output 0 to 10 VDC (0 to 100% flow) VNOM adj. to box size Angular Rotation 0 to 95, both end stops adjustable. Stroke Time 18 per 60 Hz 15 per 50 Hz Reset Voltage 0 to 10 VDC Reset Limits Adjustable, 0 to 100% Mounting Direct to 1/2" (13 mm) diameter shaft or 3/8" (10 mm) diameter with adaptor Connections Wire clamp type, 14 to 22 AWG, Cu Material Flame retardant polymer, UL94-5V plenum rated, black housing with white cover Weight 2.4 lbs. (1 kg.) Temperature Limits Operating 32 to 120 F (0 to 49 C) Shipping -40 to 140 F (-40 to 60 C) KMC Controls, Inc Industrial Drive New Paris, IN Page 5 of KMC Controls Inc D
6 REE-1005 Relay Module Heat/Cool Changeover Description The KMC REE-1005 Relay Module is designed primarily for automatic heating /cooling changeover applications on single duct VAV terminal units in HVAC systems. Used in conjunction with the SSE-2000 series sensors the REE-1005 has the ability to change the action of the VAV terminal to either heating or cooling based on the temperature of the supply air to the VAV terminal. Features Automatic Heat/Cool changeover Simple installation Application KMC REE-1005 Relay Modules are intended for use with the following: Associated Controllers-Actuators: CEE-4000 Series CEP-4000 Series CSE-4000 Series CSP-4000 Series CSP-5001 Associated Thermostats: CEE-1103 CTE-1103 CTE-5103 Page 6 of 10 Specifications and design subject change without notice.
7 Details All dimensions are in inches (mm) Specifications Supply Voltage 9.1 to 18 VDC (2 ma) Contact Voltage Normally Closed (NC) = Supply voltage minus 1 VDC Common (C) = Supply voltage minus 1 VDC) Normally Open (NO) = Supply voltage minus 1 VDC Setpoint 77 F ±4 F (25 C ±2 C) Connections Plated screw terminals Wire Size AWG, stranded Material ABS, UL Flame Class 94HB Weight 2 oz. (57 grams) Temperature Limits Operating 40 to 120 F (4 to 49 C) KMC Controls, Inc Industrial Drive Shipping -40 to 140 F (-40 to 60 C) New Paris, IN Page 7 of KMC Controls Inc A
8 Heat/Cool Changeover Relay Module REE 1005 Required Tools digital voltmeter small phillips screwdriver small flatblade screwdriver Installation Guide Mounting The REE 1005 may be mounted directly to a control box surface or in a 2" x 4" electrical handy box. Add a blank cover to conceal the module. Wiring Wire as shown for single duct heating/cooling changeover using one box to supply hot or cold air to the space. Maintenance No routine maintenance is required, however protection from extremes of humidity and dirt is recommended. Careful installation will also ensure long term reliability and performance. Page 8 of 10 KMC Controls P.O. Box Industrial Drive New Paris, IN U.S.A. TEL: FAX: info@kmccontrols.com D
9 CTE 5100 Series Electronic Room Thermostat Description The KMC CTE 5100 Electronic Room Thermostat series is designed for use with the CSP 5001/5002 Flow Controller-Actuator and/or the REE 1000/ 4000 series auxiliary relays. Other high impedance (10K ohms or higher) controls such as MEP 1200/ 5000 series actuators, and VEP series valves requiring a 0 to 10 VDC control circuit, may be controlled via any of the CTE 5100 series thermostats. CTE 5100 s have both limited and unlimited outputs. The limited output is used to provide minimum and maximum limits to a CSP 5001/5002, or impose electronic limits to an MEP 1200/5000 series actuator or a VEP series valve. Models are available for cooling, heating, cooling w/ reheat, cooling/heating changeover, day/night or night/day applications. Temperature averaging and/ or overrides are also available. All thermostats require a scale plate assembly and cover which may be ordered separately (See Accessories) or as part of a value package containing the most frequently ordered accessories. Thermostat and accessories styling allow the setpoint indicator and/or thermometer to be visible or concealed, setpoint adjustment locked or restricted, vertical or horizontal mounting and attractive color finishes in plastic or metal. Features Available for cooling, heating, cooling w/reheat, cooling/heating changeover, day/night or night/ day applications Single or dual setpoint models Limited and unlimited outputs Visible or hidden setpoint indicator Models The following models are available: CTE-5101 Single setpoint; direct acting CTE-5102 Single setpoint; reverse acting CTE-5103 Dual setpoint; direct & reverse acting CTE-5104 Dual setpoint; direct & reverse acting CTE-5105 Dual setpoint; both direct acting Page 9 of 10 Accessories Specifications and design subject to change without notice. Value packages which contain a cover, scale plate, and backplate may be ordered by adding the suffix 10 to your model selection. The following accessories are available: HFO-0027 Setpoint stops HMO-5023 Drywall mounting kit HMO " x 4" almond backplate w/ alum. trim HMO " x 4" white backplate w/ alum. trim HMO " x 4" almond backplate w/ matching trim HMO " x 4" white backplate w/ matching trim HPO Horizontal scale plate F HPO Horizontal scale plate C HPO Vertical scale plate F HPO Vertical scale plate C XEE VDC (14-20 VAC) Power supply ABS COVERS HPO-1501 Blank; almond color HPO-1502 Blank; white color HPO-1511 Window; almond color HPO-1512 Window; white color
10 Details All dimension are in inches (mm) METAL COVERS HPO-1503 HPO-1504 HPO-1505 HPO-1506 HPO-1513 HPO-1514 HPO-1515 HPO-1516 Specifications Supply Voltage Blank; brushed aluminum finish Blank; painted white Blank; brushed brass finish Blank; painted almond Window; brushed aluminum finish Window; painted white Window; brushed brass finish Window; painted almond 16 VDC (14 to 20 VDC) Output Range 0 to 10 VDC Temperature Range 55 to 85 F (13 to 29 C) Proportional Band CTE-5101/2/3/5 CTE F (1.1 C) w/limits output (T1/T2) 4 F (2.2 C) w/o limits output (T3/T4) 2 F (1.1 C) w/ & w/o limits output (T1/T2/T3) Thermostat Action CTE-5101 CTE-5102 CTE-5103 CTE-5104 CTE-5105 Connections Base Material Direct Acting (DA) T1/T3 Reverse Acting (RA) T2/T4 Direct Acting (DA) T1/T3 Reverse Acting (RA) T2/T4 Direct Acting (DA) T1/T3 Reverse Acting (RA) T2/T4 Direct Acting (DA) T1/T2/T3/ T4 Wire clamp type, AWG Black ABS UL Flame Class 94 HB Size 2-9/16" x 3-7/16" (65 mm x 87 mm) Weight 3.0 oz. (85 grams) Temperature Limits Operating 40 to 120 F (4 to 49 C) Shipping -40 to 140 F (-40 to 60 C) Page 10 of 10 KMC Controls, Inc Industrial Drive New Paris, IN KMC Controls Inc B
GENERAL PRODUCT OVERVIEW
CONTROLS Pneumatic Controls comprehensive range of factory supplied, installed and calibrated controls are available for pressure independent control applications with all terminal types. Pressure dependent
More informationPRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE
Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface
More informationPowers Controls TH 192 S Single Temperature Room Thermostat
Technical Instructions Document No. 155-065P25 TH 192-1 Powers Controls TH 192 S Single Temperature Room Thermostat 50 60 70 80 TH0355R1 70 80 POWERS Description The TH 192 S thermostats are proportional
More informationI nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.
FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and
More informationGeneral Information... 2
Pneumatic VAV Reset Volume Controllers CSC 2000 Series Applications Guide General Information... 2 CSC 2000 Series Overview...2 odels and Specifications...3 ounting...4 Connections...4 All Units...4 Beige
More informationPowers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat
Document No. 155-068P25 TH 193-4 Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 193 HC thermostats are proportional dual
More informationPowers Controls TH 192 HC Heating/Cooling Room Thermostat
Powers Controls TH 192 HC Heating/Cooling Room Thermostat Technical Instructions Document No. 155-066P25 TH 192-2 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 192 HC thermostats are proportional
More informationTAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM
TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution
More informationPNEUMATIC CONTROLS Selection and Description
PNEUMATIC CONTROLS Selection and Description Carnes pneumatic controlled throttling units are suitable for a standard 20 psi control system and may be supplied with pressure dependent or pressure independent
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More informationDUCT SMOKE DETECTOR D4120
Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity
More informationT 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ
TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size
More informationDPT-2015 Differential Pressure Transmitter for VAV Box Applications
FANs 216, 1628.3 Product/Technical Bulletin DPT-2015 Issue Date 1298 DPT-2015 Differential Pressure Transmitter for VAV Box Applications The DPT-2015 Differential Pressure Transmitter senses differential
More informationElectronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
More informationM9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators Product Bulletin Code No. LIT-1201742 Issued February 12, 2015 The M9102 and M9104 Series Actuators are directmount,
More informationRDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
More informationKRUEGER Single-Duct and Retro Fit Terminal Units
KRUEGER Single-Duct and Retro Fit Terminal Units PRE-INSTALLATION General The LMHS, RVE, and SVE single duct terminals are available with factory installed Pneumatic, Analog electronic, and DDC control
More informationSLIM LINE FUME HOOD MONITOR
SLIM LINE FUME HOOD MONITOR Phoenix Controls FHM420 Fume Hood Monitor is sized to fit any fume hood and includes icons for simple and universal operation. The FHM420 slim line monitor works in conjunction
More informationETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
More informationE-PDD Duct Smoke Detector Installation Sheet
E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating
More informationVentostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:
GE Measurement & Control Ventostat Wall Mount Telaire Wall Mount, Humidity and Temperature Transmitters Features: Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low
More informationTechnote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese.
Page 1 of 6 Application Proportional 0-10V or 3-position modulating or On/ Off control of Frese OPTIMA Compact valves in heating, ventilating and air conditioning systems. The actuator can be mounted on
More informationN20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL
N2xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL SPECIFICATIONS Supply voltage N224A / N3424A N223A / N3423A PRODUCT DATA 24 Vac 15%, 5/6 Hz 23 Vac 15%,
More informationHow To Drive A Compact Serie 1
Electric lifting cylinder Compact Series Table of Contents Glossary... 2 Compact serie SR 1... 4 Dimension SR 1... 5 Compact Serie SR 1SP... 6 Dimension SR 1SP... 7 Compact Serie SR 5... 8 Dimension SR
More informationInstalling the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital
More informationTable of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7
THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3
More information0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
More informationits ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.
Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please
More informationDS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches
DS 1.102 02/99 AIR ROOM TEMPERATURE SENSOR with fan speed control switches Specification No. 528-X-XXX* The Active Room Temperature sensor incorporating fan speed control switches is designed to give a
More informationCONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)
TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output
More informationWE-350 Series ¼ Turn Electric Actuator
WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationT-4000 Series Pneumatic Room Thermostats
T-4000 Series Pneumatic Room Thermostats Pneumatic Control Manual 717.1 Room Devices Section Product Bulletin T-4000 Issue Date 1285 Features Adjustable Sensitivities and Set Points Individual Set Points
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationIO-RM3 3-Stage Relay Module
Page 1 of 6 IO-RM3 3-Stage Relay Module Features: Benefits: Link selectable modes binary, heat/cool, staged or sequenced On/Off/Auto links for ease of commissioning DIN Rail mounting Fault finding LED
More informationSolid State Timers Type F
Solid State Timers Type F Class 9050 CATALOG CONTENTS Description.....................................................Page Product Descriptions............................................. 3 Application
More information12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations
12S, 14S, 15S Series Time Delay Relays and Sequencers Time Delay Relays and Sequencers The Therm-O-Disc type 12S, 14S and 15S series time delay relays and sequencers are field-proven devices for controlling
More informationT-100-R Installation Guide
T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard
More informationWON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013
Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the
More informationHMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
More informationTS93 EMR T/PT/TDE. Surface applied door closer
TS EMR T/PT/TDE Surface applied door closer Installation instructions: Pull side track mount door closer with smoke detector (EMR T) Push side track mount door closer with smoke detector (EMR PT) Double
More informationRC 195 Multiple Input Receiver-Controller
Document No. 129-230 RC 195 Multiple Input Receiver-Controller Product Description The RC 195 Multiple Input Receiver-Controller is a pneumatic instrument that can be used as a one input (DA or RA), two
More informationACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
More information4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES
4-Wire Air Duct Smoke Detector Models DH-60 F-70.05 FEATURES Approvals/Listing UL 268A Listed File S1064 Factory Mutual Approved CSFM Listed #3240-1076:121 NYC MEA Listed #134-95-E City of Los Angeles
More informationDigi-Motor Installation Guide
Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support
More informationSolid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting
More informationVariable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
More informationElectronic Control Devices The European Product Catalogue 2007
FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically
More informationT6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control
T Series arge CD Digital Thermostat 0/0 VAC -pipe/-pipe fan coil control Data sheet Application T digital thermostats are designed for application of -speed fan and s in fan coil system. Including: -pipe
More informationDORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
More informationRoof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
More informationSystem 350 A350R Electronic Temperature Reset Control (with Relay)
FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350R Issue Date 0899 System 350 A350R Electronic Temperature Reset Control (with Relay) The A350R Electronic Temperature Reset Control is designed
More informationInstallation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types
Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:
More information225-230T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators
Actuators Technical data sheet 225-230T-05-S2 Rotary drive without spring return Description Actuator for adjusting air dampers of 90 angle of rotation to be used in HVAC installations. Torque Motor 5
More informationELECTRIC POSITION for electric heat, then confirm with Fan Test below.
Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please
More informationAdjustable room thermostat for heating only or cooling only systems
3 003 Room hermostat RAA30 Adjustable room thermostat for heating only or cooling only systems Room thermostat with manual O/OFF switch wo-position control witching voltage AC 24 250 V Use he RAA30 room
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationTECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Tankless Electric (RTE) Troubleshooting
Sequence of Operations 1 Power supply and field wiring block 2 Energy Cut Off (ECO) 3 Water flow plunger and cold inlet 4 Magnetic flow switch 5 Water temperature thermistor 6 Control panel and circuit
More informationAir damper actuators
4 634 OpenAir TM Air damper actuators GDB...1 GLB...1 Rotary version, / AC 230 V Electronic motor driven actuators for three-position and modulating control Nominal torque 5 Nm (GDB), 10 Nm (GLB) Mechanically
More informationSeries 71, 72, and 76 Modutrol IV Motors
Series 7, 7, and 76 Modutrol IV Motors PRODUCT DATA FEATURES APPLICATION The Series 7, 7 and 76 Modutrol IV Motors are spring return and nonspring return motors used to control dampers and valves. The
More informationRadiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
More informationContactless Encoder RI360P0-QR24M0-INCRX2-H1181
Compact, rugged housing Many mounting possibilities Status displayed via LED Immune to electromagnetic interference 1024 pulses per revolution (default) 360, 512, 1000, 1024, 2048, 2500, 3600, 4096, parametr.
More informationNEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More information225C-024T-05. Continuous control rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators
Actuators Technical data sheet 225C-024T-05 Continuous control rotary drive without spring return Description Actuator for adjusting air dampers of 90 angle of rotation to be used in HVAC installations.
More information40.3. Control Relays and Timers
.3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories
More informationFossil fuel heating equipment
Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating
More informationInstall Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.
Install Guide CT100 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the
More informationE2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
More informationTelefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com. Installation and operating manual
Uni-Valve A /S VENTILER & INSTRUMENTER Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com UNI-EL Electric actuator Installation and operating manual Remote position
More informationDCS Input/Output Relay Card Series
Input/Output Relay Card Series I/O RELAY CARD (with loopback test function) 8N The 8N series I/O Relay Cards easily and quickly standardize and facilitate installation of the relay board. Loopback test
More informationSelection Chart T-4000 Series Accessories (Part 1 of 5) Code Number Figure Description Application (High or Low Volume)
Code No. LIT-1921710 Issued July 25, 2011 T-4000 Series Accessories Selection Chart T-4000 Series Accessories (Part 1 of 5) ( or Volume) F-100-20 F-300-30 F-300-34 F-300-31 F-300-35 F-500-45 F-300-30 Coupler,
More informationTalon and Talon SR User Manual
Talon and Talon SR User Manual Brushed DC motor controller Version 1.3 Cross the Road Electronics, LLC www.crosstheroadelectronics.com Cross The Road Electronics, LLC Page 1 4/2/2013 Device Overview Clear,
More informationMCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
More informationADDENDUM TO THE CONTRACT. for the. Bartlett Regional Hospital Server Room Cooling System Replacement. Contract No. E12-149
ADDENDUM TO THE CONTRACT for the ENGINEERING DEPARTMENT Bartlett Regional Hospital Server Room Cooling System Replacement Contract No. E12-149 ADDENDUM NO.: TWO CURRENT DEADLINE FOR BIDS: January 20, 2012
More informationTC-9102 Series Surface Mount Temperature Controllers
TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may
More informationPSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624
PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description
More informationT5000 T000 LCD Digital Fan Coil Thermostat
T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,
More information49 Series - Relay interface modules 8-10 - 16 A. Features
Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole
More informationJNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
More informationIMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.
QUIET-ONE Environmental Products 2000 Kickspace Heater Series Models: KS 2004, KS 2006 KS 2008, KS 2010 INSTALLATION OPERATING MAINTENANCE Please read these instructions thoroughly before beginning your
More informationSensors. Sensors. All Cylinders. Specifications. Features: Features Type REED HALL EFFECT NPN or PNP. Ø8mm - 125mm
Specifications Features Type REED HALL EFFECT NPN or PNP Applicable Series Configurations Construction Materials Body Mounting Bracket Cable Characteristics Operating Temperature Accuracy All Cylinders
More informationHow To Read A Pipe From A Sensor
Liquid Level Sensor Installation on pipes. Sensing by means electrostatic capacity and is not influenced by the color of the pipe or liquid. Available in 8 to mm dia. and to mm dia. models to enable sensing
More information48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
More informationFor UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.
s For UK only RX39.1 and the applications package SP-03 are sold in the United Kingdom only. 3 876 3876P01 RX Room controller Communicating controllers for fan-coil applications SP-03 RX39.1 The RX39.1
More informationOEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE
OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &
More informationOPERATING INSTRUCTIONS
PIPELINE INSPECTION COMPANY LTD. OPERATING INSTRUCTIONS Wet Sponge Holiday Detectors 670,673, and MSRB Wet Sponge Holiday Detectors Portable and In-Plant Detectors Table of Contents General Information.......................3
More informationContractors Guide Central Inverter System Installation
Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.
More information48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
More informationMoxa EtherDevice Switch
Moxa EtherDevice Switch EDS-205 Hardware Installation Guide Third Edition, June 2008 2008 Moxa Inc., all rights reserved. Reproduction without permission is prohibited. P/N: 1802002050000 Overview The
More informationRI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
More informationSERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
More informationHVAC Processes. Lecture 7
HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump
More informationSignaling Lights. LH Series Surface Mount Indicators. Part Numbers. Jumbo Dome (one color) Jumbo Dome (two color)
Innovative indicators in a slim & stylish design. uces installation space. LH Series Surface Mount Indicators Key features of the LH series include: Direct mounting on surfaces such as panels, aluminum
More informationClear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles
Clear Glass Sensor Optimum Sensor for Detecting Transparent Glass and Plastic Bottles E3S-CR67/62 Retroreflective Sensor smoothly detects 5-mm gaps. Detects transparent bottles that have a lens effect.
More informationSystem 350 A350E Electronic Cooling Control
FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0899 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw
More informationFlush-mounted room thermostats
s 3 076 RDF300, RDF300.02, RDF340 RDF400.01 RDF600 RDF600 Flush-mounted room thermostats for 2-pipe, 2-pipe with el. heater and 4-pipe fan coil units for use with compressors in DX type equipment RDF300
More informationINSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
More informationProgrammable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains
Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation
More informationInstallation Instructions
0.1.2....6.7..9 1 0.1.2....6.7..9 1 Installation Instructions Quick-Mount Visual Instructions for Mechanical Installation Quick-Mount Visual Instructions 1. Rotate the damper to its fail-safe position.
More informationModular Room Control (MRC) Series Digital Thermostat
Installation Instructions MRC Issue Date August 14, 2002 Modular Room Control (MRC) Series Digital Thermostat Application The MRC Digital Thermostat is an expandable multi-purpose, high-quality Direct
More information